REFUstore 50K... 100K Datasheet EN V06 Screen
REFUstore 50K... 100K Datasheet EN V06 Screen
REFUstore 50K... 100K Datasheet EN V06 Screen
100K
The next generation of bidirectional
high power battery inverters
NEW
DC-PRECHARGE
OPTION
DC DATA
Max. voltage DC (V) 1,000
Nominal voltage DC (V) 750 620 600 620 600 Usdc + 50
DC voltage range at nominal power (V) 700 ... 900 585 … 900 555 … 900 585 ... 900 555 … 900 1.46 × Uac
DC start-up open circuit voltage, Usdc (V) 700 585 555 585 555 1.46 × Uac
Max. operational current DC (A) 153 153 153 153 87 153
DC connection PowerUnit - ConnectionBox 1 Plus, 1 Minus: Connector with Button Activated Coupling
AC DATA
Apparent power (kVA) 100.0 88.0 83.3 50.0 50.0 0.222 × Uac
Rated voltage AC 3-Phase, Uac (V) 480 400 380 400 380 180 … 480
Voltage range AC (V) 180 ... 528
AC grid connection / Grid types 3 Phases, PE / TT, TN-C, TN-S
Nominal power factor / Range 1 / 0.3i … 0.3c
Rated frequency / Frequency Range (Hz) 50, 60 / 45 … 65
Max. AC current, Imax (A) 128
Max. AC short circuit current (A rms) 64 (3 period average)
Inrush current (peak / duration) 25 A / 0.5 ms
Max. THD (%) <3
Max. efficiency (%) 98.4 98.4 98.3 98.4 98.4 96.8
Maximum admissible external AC fuse 160 A, gG, Un = 500 V
Maximum admissible external DC fuse 200 A, gR, Un = 1000 V
Peak current (Ip) / Initial short circuit
128 / 325
current (Ik“) acc. IEC 60690-0 (A)
AC connection PowerUnit - ConnectionBox Connector with Button Activated Coupling
AMBIENT CONDITIONS
Cooling Smart active cooling
Max. temp. for nominal power (°C) 45
Ambient temperature (°C) - 25 ... + 60
Rel. Air humidity (%) 0 … 100
Max. elevation (m above sea level) 3,000
Noise level (dBA) < 70
Environment classification (IEC 60721-3-4) 4K4H
Type of protection IP65
Installation type Indoor / outdoor, Vertical / flat / pole mounting
GENERAL DATA
Topology Transformerless
DC pole grounding not allowed
Status display / Keys 4 LED's (DC status, AC status, Fault, Bluetooth®) / 2 Keys (Connect, Clear)
Interfaces 2 × Ethernet Daisy-Chain / 2 × RS485, Bluetooth® BLE, 1 × Remote Off Signal
Communication Protocols Sunspec (Modbus TCP, Modbus RTU), USS (Ethernet, RS485)
Dimensions W × H × D (mm) 673 × 626 × 321
100
Weight (kg) 69
99
98
97
CERTIFICATES
EU Directive 96 2014/30/EU, 2014/35/EU
Efficiency (%)
IEC 62109-1, IEC 62109-2, IEC 62116, IEC 61727, IEC 62477-1,
Product
95IEC 61439, ETSI EN 300 328 V.2.1.1
EMC IEC 61000-6-2, IEC 61000-6-4
94
IEC 60068-2-1, -2-2, -2-30, -2-78, -2-14, -2-6, -2-27, -3-2, -2-75, IEC 60529,
Environment
IEC 60034-9
93
DIN VDE V 0126-1-1, VDE AR-N 4105:2011-08, BDEW Prototype Declaration,
620 VDC Discharge 620 VDC Charge
Grid Codes TOR D4, Önorm E 8001-4-712, UTE C15-712-1, EN 50438, VDE AR-N 4105:2018,
92
VDE AR-N 4110:2018, EN 50438 (BG, CY, HU, PL, RO, TR)
880 VDC Discharge 880 VDC Charge
All certificates are available at www.refu.com 91
90
0 20 40 60 80 100
Power (%/Pn)
99 90
98 80
97 70
96
Efficiency (%)
60
Power (kVA)
95 50
94 40
93 30
620 VDC Discharge 620 VDC Charge
92 20
880 VDC Discharge 880 VDC Charge 620 VDC 750 VDC 880 VDC
91 10
90 0
0 20 40 60 80 100 35 40 45 50 55 60
CBBS (1000V-BR)
Art. No. 940P300.0000
GENERAL DATA
DC Switch no
DC Connection (+ / - ) Ring terminal block (50 ... 240 mm²)
AC Connection L1, L2, L3: M10 / PE: M8 Ring terminal block (50 … 150 mm²)
Type of protection (IEC 60529) IP54
Dimensions ConnectionBox W × H × D (mm) 760 × 692 × 166
Weight (kg) 25
POWERUNIT
CONNECTIONBOX
SINGLE LINE DIAGRAMS
Monitoring Portal
Energy Management
System (EMS)
External precharge
Energy Meter
precharge circuit
DC Switch / MCB
circuit (optional)
(only 421Pxxx)
Integrated DC
AC grid relais
Master
DC Fuse
BMS
DC +
L1
Grid Connection
L2
DC - L3
3
PEN
AC SPD (opt.)
DC SPD (opt.)
AC grid connection
current detection
AC mains chokes
DC Connection
(only 421Pxxx)
AC grid relais
DC EMC filter
AC EMC filter
AC residual
Inverter
DC + L1
RCD L2
DC - L3
3 PEN
ISO
Control Panel
SR Control Card
This two-piece design also offers easiest serviceability – the PowerUnit can be quickly detached from the
ConnectionBox for trouble shooting and measurements – without disconnecting the power cables on the DC or
AC sides.
1 2
3
20200303_REFUstore_50K...100K_Datasheet_EN_V06
Ready.