10 Mva 33 KV / 6.6 KV Data Sheet: Description Unit Requirement

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

10 MVA 33 KV / 6.

6 KV DATA SHEET

SCHEDULE B

Description Unit Requirement


Required Quantity No. 2
No. of Phases No. 3
Max. Continuous rating (ONAN) MVA 10
Normal ratio of transformation KV 33/6.6

Description Unit Requirement


Vector Group Reference IEC600 76 Dyn1
ON- Loan Tap
Type of transformation ratio control
Changer
Range of Tran5formation ratio variation
% +5% to -15%
HV/LV ( 33/6.6KV)
Size of transformation ratio steps % 1.25
Normal operating voltage range:-

• High voltage system (33KV) % 0 to 10

• Low voltage system ( 6.6KV) % 0 to 10

Which Winding to be tapped H. V


Supply voltage for control circuit V (dc) 110

Phase connection:

• 33 KV winding Delta

• 6.6 KV winding Star

Terminal Arrangements:

* 33 KV winding Cable Box

* 6.6 KV winding Cable Box

* 6.6 KV neutral Open for Earhing


10 MVA 33 KV / 6.6 KV DATA SHEET

Description Unit Requirement

Current Transformer details (State ratio, class and phase). Quantity/

• HV current transformer for HV winding temperature. (class 3FS5,


• 1 CT For phase (B)
10VA).Ratio shall be determined by the manufacturer
206/2 AMP

• LV current transformer for LV winding temperature, and • 1 CT For phase


AVR. (class 3FS5,10VA) Ratio shall be determined by the (b)
manufacturer 875/2 AMP

Whether hot or cold rolled steel core Coiled Rolled


Thickness of laminations (shall be 0.23mm) 0.23 mm
Maximum flux density at normal volts frequency and < 1.6 T
ratio TESLA
R.M.S Exciting current at normal voltage
amps
on taps (HV Ido) < 0.45 Amp
R.M.S Fundamental excelling current amps TBA
R.M.S 3rd. harmonic current amps TBA
R.M.S Sth, harmonic current amps TBA
R.M.S 7th harmonic current amps TBA

Description Unit Requirement


Maximum current density in windings at
C.M.R on normal tap:-
» 33 KV windings Amps/mm2 LESS THEN 2.0
» 6.6 KV winding Amps/mm2 LESS THEN 2.0

- No load losses at normal ratio


KW 6.1KW
33/6.6 KV
- Load lossed at C.M.R 75°C and normal
KW 41.5 KW
ratio ( excluding cooling plant ) 33/ 6.6 KV
- Tap position on which maximum losses
occur at C.M.R KW 17 TAP , 42 KW
- Load lossed at C.M.R on tap position with
KW 42 KW APPROX
maximum losses
Total losses at C.M.R 75°C when operating
KW 48 KWAPPROX
on tap position giving maximum losses
Regulation at 75°C and C.M.R:-
% of
» At Unity P.F. Normal 0.72%
» At 0.8.P.F. Lagging volts 5.14%
10 MVA 33 KV / 6.6 KV DATA SHEET

Description Unit Requirement

- Impedance voltage at 75”C and C.M.R. % Appr. 9.0%


normal ratio between 33KV and 6.6KV windings.

- Impedance voltage at 75”C and C.M.R at highest


transformation ratio between 33KV and 6.6KV %Appr. 9.2%
windings.

- Impedance voltage at 75°C and C.M.R at lowest


transformation ratio between 33KV and 6.6KV 8.5%
windings.

Temperature rise of windings at C.M.R


C° 55
above specified design ambient, not to exceed
Temperature rise of top oil at C.M.R above
C° 50
specified design ambient, not to exceed
Temperature rise of core at C.M.R and
C° 50
rated voltage
Type of Windings:-

• 33KV CONT DISC


• 6.6 KV CONT DISC

Description Unit Requirement


Insulating material on windings:
• 33KV CLASS A
• 6.6KV CLASS A
Type of insulating paper CLASS A
Insulation of tapping connections CLASS A
insulation resistance between at 20°C :
HV-LV&E >2 Gohm
GΩ
LV-HV&E >1 Gohm
HV&LV—E >2 Gohm
Insulation of core bolts Not Applicable
Insulation of laminations Carlite Insulation
Type of coil supports
Axial class A
Radial class A

Type of material used for gaskets and


joints cooling surfaces:- SRBC
• Total cooling area. mm2 207.1 x 10 6
• Total external area of cooling plates. ( 14 Plate ) mm2 183.456 x 10 6
Number of radiators per transformer ( 1800 mm ) 7
cooling surface of each radiators pair mm2 1.872 x 10 6
10 MVA 33 KV / 6.6 KV DATA SHEET

Description Unit Requirement

Maximum oil pressure in system and position KN/m2 TBA Later

Temperature grad land transformer oil at


°C TBA Later
CMR.( between cooler inlet and cooler outlet)
Time for winding hot spot temperature to
reach 1S0C” on loss of coolers following operation lins TBALater
at C.M.R.
Quantity of oil in transformer (tank and
Liters 8000
conservator)
Speed of air blowers rpm Not Applicable
Full load rating of each air blower motor KW Not Applicable
Voltage for air blower motor Kv Not applicable
Starting current of each blower motor amp Not Applicable
Efficiency of blower motor at full load
% Not Applicable
rating

Power factor of blower motor at full load Not Applicable

Maximum pressure of oil at the Inlet to


KN/m2 Mot AppliCable
cooler under Service conditions
Velocity of oil through cooler mm/sec Not Applicable
Friction head across oil side of cooler of oil mm of oil TBA Later

Description Unit Requirement


Cooler surface of each cooler Sq.mm 26.208 X 1 0 6
Length between cooler tube plates mm 50
External diameter cooler tubes mm 80
Number of air blowers per transformer. TBA
Total power consumption of cooling plant at CMR KW TBA
Quantity of oil in tap changer liters TBA
Quantity of oil in coolers liters 510
Total oil required (including coolers) liters 7000
Total volume of conservator tank liters TBA
Volume of oil in conservator between high
liters TBA
and low level marks.
Thickness of transformer tank:
• Sides not less than mm 8
• Bottom not less than mm 12
• Top not less than mm 12
Thickness of conservation tank approx mm 4
Thickness of radiator plates and / or
mm 1.2 mm
cooling tubes
Weight of core and winding assembly Kg 17600
Weight of tap change gear Kg TBA
10 MVA 33 KV / 6.6 KV DATA SHEET

Description Unit Requirement


Weight of OLTC and compartment Kg TBA
Weight of conservator tank Kg TBA
Total weight of largest section arranged for transport Kg 25000
Total weight of transformer ready for
operation but excluding weight of coolers if these are 26000
Kg
not supported on transformer tank (including oil)
Total weight of separately supported
Kg 28000
including oil, pipework etc.
Overall dimensions of transformer
complete with tap change gear in millimeters: -
» Width mm 3550
« Length mm 4550
» Height mm 3850
Overall dimensions of coolers in millimeters:
» Width mm 520
» Length mm 950
» Height mm 1800

Description Unit Requirement


Overall dimensions of largest action
arranged for transport in millimeters:
• Width mm 3550
• Length mm 4550
• Height mm 3850
marshalling kiosk to be mounted on
Yes
transformer
Is tap changer mounted for transport? Yes
Is locks and cabinets as specified? Yes
Impulse withstand voltage
Of windings, bushing etc. (1.2/50/micro
second.Wave)
Min requirements:-
• 33KV system - 170KV 170 KVp
• 6.6 system =60KV 60 KVp

The offered Transformer is similar to the type and


special tested transformer in one of the STL group Yes/No
laboratory
10MVA
Bushing Details inside the cable box Unit
33KV 6.6 KV
KAIZEN/ KAIZEN/
Maker
EQUIV EQUIV
10 MVA 33 KV / 6.6 KV DATA SHEET

Description Unit Requirement


Current rating Amps 630 2000
Insulator material PORCELAIN PORCELAIN
Insulator type
Pitch circle diameter and drilling flange Mm TBA TBA
Length of bushing insulation (Overall) Mm TBA TBA
Weight of bushing insulator Kg TBA TBA
Range of arcing horn gap setting Mm TBA TBA
Material of fittings TBA TBA
Material and construction of arcing horns TBA TBA
Dry withstand power frequency voltage without
KV TBA TBA
arcing horns
Routine power frequency test voltage (1 70
KV
minute) 20
Voltage at which corona is not visible KV TBA TBA
Impulse withstand voltage 1.2/50
microsecond full wave:
• (positive) 170 20
KV
• (negative) 170 20

Type test voltage momentary KV TBA TBA


Wet withstand voltage, without arcing
KV TBA TBA
horns

Description Unit Requirement


Total creepage distance of shedding. mm TBA TBA
Protected creepage distance of shedding mm TBA TBA
Maximum diameter of bushing passing mm
through CT’s chamber TBA TBA
Penetration of bushing into tank measured mm
from bottom of fixing flange TBA TBA
33&6.6 KV cable box suitable for dry type
termination:

• No. of Termination per phase TBA TBA

• Type of cable to be terminated TBA TBA

• Size of Cable TBA TBA