AD003, DA003, DA004, MAD01 Analog IO Units Operation Manual
AD003, DA003, DA004, MAD01 Analog IO Units Operation Manual
AD003, DA003, DA004, MAD01 Analog IO Units Operation Manual
! DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
! WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
! Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1997
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis-
sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa-
tion contained in this publication.
v
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
SECTION 1
System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Features and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-3 Setting the Unit Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-4 Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SECTION 2
C200H-AD003 Analog Input Unit . . . . . . . . . . . . . . . . . . 9
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-5 Using the Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2-6 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2-7 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SECTION 3
C200H-DA003 and C200H-DA004 Analog Output Units 37
3-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-5 Using the Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3-6 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3-7 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
SECTION 4
C200H-MAD01 Analog I/O Unit . . . . . . . . . . . . . . . . . . . 65
4-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4-5 Analog Input Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
4-6 Analog Output Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4-7 Ratio Conversion Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
4-8 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
4-9 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Appendices
A Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
B Changes From Earlier Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
C Sample Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
D Data Memory Coding Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
vii
About this Manual:
This manual describes the installation and operation of the C200H-AD003 Analog Input Unit, the
C200H-DA003/DA004 Analog Output Unit, and the C200H-MAD01 Analog I/O Unit and includes the sec-
tions described below.
The C200H-AD003 Analog Input Unit converts analog sensor output to digital format and transmits it to
C200H, C200HS and C200HX/HG/HE PCs.
The C200H-DA003 and C200H-DA004 Analog Output Units convert C200H, C200HS, and C200HX/HG/
HE digital data to analog format for output.
The C200H-MAD01 Analog I/O Unit provides both input and output functions.
Please read this manual carefully and be sure you understand the information provided before attempting
to install and operate the C200H-AD003, C200H-DA003, C200H-DA004, or C200H-MAD01.
Section 1 describes the features and system configuration of the C200H-AD003 Analog Input Unit, the
C200H-DA003 and C200H-DA004 Analog Output Units, and the C200H-MAD01 Analog I/O Unit, and
explains the operations that they have in common.
Section 2 provides the information required to install and operate a C200H-AD003 Analog Input Unit.
Section 3 provides the information required to install and operate a C200H-DA003 or C200H-DA004
Analog Output Unit.
Section 4 provides the information required to install and operate a C200H-MAD01 Analog I/O Unit.
The Appendices provide dimensions, model change differences, sample programs, and data memory
coding sheets.
! WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each
section in its entirety and be sure you understand the information provided in the section
and related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and Analog I/O Units.
The information contained in this section is important for the safe and reliable application of the Analog I/O Unit. You
must read this section and understand the information contained before attempting to set up or operate a PC system
and Analog I/O Unit.
xi
Operating Environment Precautions 4
1 Intended Audience
This manual is intended for the following personnel, who must also have knowl-
edge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems
• Personnel in charge of designing FA systems
• Personnel in charge of managing FA systems and facilities
2 General Precautions
The user must operate the product according to the performance specifications
described in the operation manuals.
Before using the product under conditions which are not described in the manual
or applying the product to nuclear control systems, railroad systems, aviation
systems, vehicles, combustion systems, medical equipment, amusement
machines, safety equipment, and other systems, machines, and equipment that
may have a serious influence on lives and property if used improperly, consult
your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide the
systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating OMRON Ana-
log I/O Units. Be sure to read this manual before attempting to use the software
and keep this manual close at hand for reference during operation.
! WARNING It is extremely important that a PC and all PC Units be used for the specified
purpose and under the specified conditions, especially in applications that can
directly or indirectly affect human life. You must consult with your OMRON
representative before applying a PC System to the above-mentioned
applications.
3 Safety Precautions
! WARNING Do not attempt to take any Unit apart while power is being supplied. Doing so
may result in electric shock.
! WARNING Do not touch any of the terminals or terminal blocks while power is being
supplied. Doing so may result in electric shock.
! Caution Tighten the screws on the terminal block of the AC Power Supply Unit to the
torque specified in the operation manual. The loose screws may result in burning
or malfunction.
! Caution Execute online edit only after confirming that no adverse effects will be caused
by extending the cycle time. Otherwise, the input signals may not be readable.
xii
Application Precautions 5
! Caution Take appropriate and sufficient countermeasures when installing systems in the
following locations:
! Caution The operating environment of the PC System can have a large effect on the lon-
gevity and reliability of the system. Improper operating environments can lead to
malfunction, failure, and other unforeseeable problems with the PC System. Be
sure that the operating environment is within the specified conditions at installa-
tion and remains within the specified conditions during the life of the system.
5 Application Precautions
Observe the following precautions when using the PC.
! WARNING Always heed these precautions. Failure to abide by the following precautions
could lead to serious or possibly fatal injury.
• Always connect to a ground of 100 Ω or less when installing the Units. Not con-
necting to a ground of 100 Ω or less may result in electric shock.
• Always turn off the power supply to the PC before attempting any of the follow-
ing. Not turning off the power supply may result in malfunction or electric
shock.
• Mounting or dismounting I/O Units, CPU Units, Memory Cassettes, or any
other Units.
• Assembling the Units.
• Setting DIP switch or rotary switches.
• Connecting or wiring the cables.
• Connecting or disconnecting the connectors.
! Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these pre-
cautions.
xiii
Application Precautions 5
• Take appropriate measures to ensure that the specified power with the rated
voltage and frequency is supplied. Be particularly careful in places where the
power supply is unstable. An incorrect power supply may result in malfunction.
• Install external breakers and take other safety measures against short-circuit-
ing in external wiring. Insufficient safety measures against short-circuiting may
result in burning.
• Do not apply voltages to the Input Units in excess of the rated input voltage.
Excess voltages may result in burning.
• Do not apply voltages or connect loads to the Output Units in excess of the
maximum switching capacity. Excess voltage or loads may result in burning.
• Disconnect the functional ground terminal when performing withstand voltage
tests. Not disconnecting the functional ground terminal may result in burning.
• Be sure that all the mounting screws, terminal screws, and cable connector
screws are tightened to the torque specified in the relevant manuals. Incorrect
tightening torque may result in malfunction.
• Do not attempt to disassemble, repair, or modify any Units.
• Be sure to confirm that the DIP switch and the data memory (DM) are properly
set.
• Leave the label attached to the Unit when wiring. Removing the label may re-
sult in malfunction.
• Remove the labels after the completion of wiring to ensure proper heat dissipa-
tion. Leaving the label attached may result in malfunction.
• Mount the Unit only after checking the terminal block completely.
• Be sure that the terminal blocks, Memory Units, expansion cables, and other
items with locking devices are properly locked into place. Improper locking
may result in malfunction.
• Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to
terminals. Connection of bare stranded wires may result in burning.
• Double-check all the wiring before turning on the power supply. Incorrect wir-
ing may result in burning.
• Confirm that no adverse effect will occur in the system before attempting any of
the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC.
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Resume operation only after transferring to the new CPU Unit the contents of
the DM Area, HR Area, and other data required for resuming operation. Not
doing so may result in an unexpected operation.
• Do not pull on the cables or bend the cables beyond their natural limit. Doing
either of these may break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so may
break the cables.
• Before touching the Unit, be sure to first touch a grounded metallic object in
order to discharge any static built-up. Not doing so may result in malfunction or
damage.
• When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
xiv
SECTION 1
System Design
This section describes the features and system configuration of the C200H-AD003 Analog Input Unit, the C200H-DA003 and
C200H-DA004 Analog Output Units, and the C200H-MAD01 Analog I/O Unit, and explains the operations that they have in
common.
1
Features and Functions Section 1-1
Units for C200H, C200HS, These special-purpose Units enable highly accurate analog input and output at
and C200HX/HG/HE PCs a resolution of 4,000, for C200H, C200HS, and C200HX/HG/HE PC systems.
The C200H-AD003 Analog Input Unit converts analog sensor output to digital
format and transmits it to C200H, C200HS and C200HX/HG/HE PCs. The
C200H-DA003 and C200H-DA004 Analog Output Units convert C200H,
C200HS, and C200HX/HG/HE digital data to analog format for output. The
C200H-MAD01 Analog I/O Unit provides both input and output functions.
Item C200H-AD003 C200H-DA003 C200H-DA004 C200H-MAD01
Analog input Maximum input points 8 --- --- 2
Input signal range –10 to 10 V --- --- –10 to 10 V
(See note.) 0 to 10 V 0 to 10 V
1 to 5 V 1 to 5 V
4 to 20 mA 4 to 20 mA
Analog output Minimum input points --- 8 8 2
Output signal range --- –10 to 10 V 4 to 20 mA –10 to 10 V
(See note.) 0 to 10 V 0 to 10 V
1 to 5 V 1 to 5 V
4 to 20 mA
Note The input and output signal ranges can be set individually for each input.
High-speed Conversion The Analog Input and Output Units provide high-speed data conversion at 1 ms
per I/O point. The sampling period can be further shortened by setting unused
inputs and outputs so their use is prohibited.
Input Disconnection The input disconnection detection function can be used for analog inputs within
Detection Function an input signal range of 1 to 5 V (4 to 20 mA). When this function is set for use,
any input under 0.3 V will be regarded as a disconnection. For details, refer to
2-5-5 Input Disconnection Detection Function and 4-5-5 Input Disconnection
Detection Function.
2
Features and Functions Section 1-1
Peak Value Function The peak value function holds the maximum digital conversion value for every
input (including mean value processing). This function can be used with analog
input. The following diagram shows how digital conversion values are affected
when the peak value function is used. For details, refer to 2-5-4 Peak Value
Function.
t (Time)
Output Hold Function The output hold function can be used to hold the analog output value at any pre-
set value when there is an error at the PC’s CPU Unit. When conversion is
stopped, CLR, HOLD, or MAX can be selected for output. For details, refer to
3-5-2 Output Hold Function.
Mean Value Function The mean value function can be used to remove erroneous values that occur
due to factors such as noise that is included in analog inputs. The operating
mean is taken without affecting the data refresh cycle. For details, refer to 2-5-3
Mean Value Processing and 4-5-3 Mean Value Processing.
Offset and Gain The A/D and D/A converter offset deviation and gain deviation can be adjusted
Adjustment Function for each input and output. The offset and gain adjustments are made with the
Unit set for the adjustment mode, and the adjustment values are stored in the
Unit’s built-in EEPROM. For details, refer to 2-6 Offset Gain Adjustment, 3-6 Off-
set Gain Adjustment, and 4-8 Offset Gain Adjustment.
10 V
Gain Gain
adjustment Analog adjustment
output
Adjustable range Adjustable range
10 V
Offset adjustment Analog input Offset adjustment
Ratio Conversion The C200H-MAD01 Analog I/O Unit can output in analog format the results of
Function analog inputs calculated for ratio and bias. For details, refer to 4-7 Ratio Conver-
sion Function.
3
Basic Configuration Section 1-2
Sensor
Regulator
Temperature (Temperature control)
Pressure Preamp
Speed Servo-
Flow rate controller
(Position control)
Variable speed
Voltage controller
Current Transducer (Speed control)
Power
Power factor Chart recorder
Sensor
Number of Units Analog I/O Units are classified as C200H, C200HS, and C200HX/HG/HE Spe-
cial I/O Units. The maximum totals of Special I/O Units (including PC Link Units)
that can be mounted to a single CPU Unit are shown in the following table.
Item C200H, C200HS, C200HE C200HX/HG-CPU5j-E/6j-E
C200HX/HG-CPU3j-E/4j-E
Number of Units 10 max. 16 max.
The Units that belong to the various Special I/O Unit groups are shown in the
following table. Their usage is limited according to the maximum current pro-
vided for the Rack and the amount of current consumed by each Unit. For de-
tails, refer to the C200H, C200HS, or C200HX/HG/HE Installation Guide.
Slave Racks Certain limitations apply to the number of Special I/O Units that can be mounted
on Slave Racks. The following table shows the maximum number of Group A, B,
C, and D Special I/O Units that can be mounted on a single Slave Rack when
only Units of that group are used.
Item A B C D
Type of Unit High-speed Counters High-density I/O Units Temperature Sensor Position Control Units
Position Control Units Temperature Control Units (NC211)
(NC111/112) Units Voice Units
ASCII Units PID Control Units
Analog I/O Units Cam Positioner Units
ID Sensor Units
Fuzzy Logic Units
Mountable number 4 Units 8 Units 6 Units 2 Units
4
Basic Configuration Section 1-2
If Units from any of the four groups are to be combined, then both of the following
two equations must be satisfied.
3A + B + 2C + 6D x 12
A+B+C+Dx8
When considering the limitations on the numbers of different types of Special I/O
Units that can be used, refer also to Number of Units previously described.
System Configuration Special I/O Units are allocated IR area addresses according to the unit number
Considerations switch settings on their front panels, and not according to the slots in which they
are mounted.
With the C200H, do not mount an Analog I/O Unit in the two slots adjacent to the
CPU Unit. Doing so would prevent peripheral devices such as the Programming
Console from being connected.
Special I/O Units cannot be used on a C200H Remote I/O Slave Rack if the
Slave Rack is connected to different PC (i.e., C500, C1000H, or C2000H).
Mounting Analog I/O Units Use the following procedure to mount an Analog I/O Unit to the Backplane.
1, 2, 3... 1. Lock the top of the Analog I/O Unit into the slot on the Backplane and rotate
the Unit downwards as shown in the following diagram.
Hook
Backplane
Lock lever
2. While making sure to align the Unit properly with the connectors, press
down on the lock lever at the bottom of the slot, press the Unit firmly into po-
sition, and then release the lock lever.
(To remove a Unit, hold down the lock lever with an implement such as a
screwdriver.)
Lock lever
5
Basic Configuration Section 1-2
Leave enough space below each Rack, as shown in the following diagram for
mounting and removing the Units.
20 mm min.
Backplane
20 mm min.
Flat-blade screwdriver
Precautions Be sure to turn off the power supply to the PC before installing or disconnecting
Units or connecting lines.
To reduce the risk of malfunctioning due to electrical noise, wire input and output
lines in separate ducts from high-voltage and power lines.
When wiring a Unit, place a cover over the top of the Unit to prevent wire clip-
pings and so on from getting inside. When the wiring has been completed, the
cover must be removed to prevent heat radiation.
6
Setting the Unit Number Section 1-3
7
Operating Procedure Section 1-4
8
SECTION 2
C200H-AD003 Analog Input Unit
This section provides the information required to install and operate a C200H-AD003 Analog Input Unit.
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-1-2 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-1-3 Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2-2-1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-2-2 Unit Number Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2-2-3 Operation Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3-1 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2-3-2 Internal Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2-3-3 Line Breakage while Using Voltage Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2-3-4 Input Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2-3-5 Input Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-4-1 IR Area Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2-4-2 DM Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2-5 Using the Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2-5-1 Setting Inputs and Signal Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2-5-2 Reading Conversion Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2-5-3 Mean Value Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2-5-4 Peak Value Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2-5-5 Input Disconnection Detection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2-6 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2-6-1 Adjustment Mode Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2-6-2 Offset and Gain Adjustment Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2-7 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2-7-1 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2-7-2 Errors Detected by Analog Input Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2-7-3 Errors Detected by CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2-7-4 Restarting Special I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2-7-5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9
Specifications Section 2-1
2-1 Specifications
2-1-1 General Specifications
All general specifications of the C200H-AD003 Analog Input Unit conform to
those of the C200H, C200HS, and C200HX/HG/HE Series.
10
Specifications Section 2-1
1068
0FA0
Resolution: 4,000
0000
FF38
Range: 0 to 10 V
Conversion value (16-bit binary data)
1068
0FA0
Resolution: 4,000
0000
FF38
0V +10 V
–0.5 V +10.5 V
Analog input signal
11
Nomenclature and Functions Section 2-2
Range: –10 to 10 V
0898
07D0
Resolution: 4,000
0000
F830
F768
–10 V 0V +10 V
–11 V +11 V
Analog input signal
Front Back
Model label
Backplane connector
12
Nomenclature and Functions Section 2-2
2-2-1 Indicators
The RUN and ERROR indicators show the operating status of the Unit. The fol-
lowing table shows the meanings of the indicators.
LED Indicator Operating status
RUN (green) Lit Operating in normal mode.
Flashes Operating in adjustment mode.
Not lit Abnormal (Unit operation stopped)
ERROR (red) Lit Error occurred. The error codes are stored in bits
08 to 15 of word n+9.
Not lit Other than the above.
13
Wiring Section 2-3
! Caution Do not set the pins to any combination other than those shown in the above
table. Be sure to set pins 2, 3, and 4 to OFF.
! Caution Be sure to turn off the power to the PC before changing the operation mode
switch settings.
2-3 Wiring
2-3-1 Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the
following diagram.
Note 1. The analog input numbers that can be used are set in the Data Memory
(DM).
14
Wiring Section 2-3
2. The input signal ranges for individual inputs are set in the Data Memory
(DM). They can be set in units of analog input numbers.
3. The COM terminal is connected to the 0-V analog circuit in the Unit. Con-
necting shielded input lines can improve noise resistance.
Current
input (+)
250 Ω
10 kΩ 10 kΩ
Voltage
input (+) Input circuit
and
1 MΩ
10 kΩ 10 kΩ conversion
Voltage
circuit
input (–)
COM
(analog
0 V) 1 MΩ
Con-
nected
device
1
Con-
nected
device
2
24 VDC
Note If the power supply is shared by two channels as shown above, while the con-
nected device 2 outputs 5 V, approximately 1.6 V (one-third of the output volt-
age) is generated in input 1.
If a line breakage occurs while using the voltage input, either separate the power
supply from the connected device or use an isolator for each input to avoid the
following problem.
15
Wiring Section 2-3
A0 Input 1
Input 2 B0 (Voltage input)
(Voltage input) A1
B1
A2
B2
A3
Input 4 B3
A4 Input 3
(Voltage input) B4 (Current input)
A5
B5
A6
B6
A7
Input 6 Input 5
B7
(Current input) A8 (Voltage input)
B8
A9
B9
A10
B10
Input 8 A11 Input 7
(Voltage input) B11 (Voltage input)
A12
B12
A13
B13
Note 1. When using current inputs, the voltage input terminals (V+) and current in-
put terminals (I+) must be individually short-circuited as shown in the above
diagram.
2. For inputs that are not used, either set to “0: Do not use” in the input number
settings (refer to 2-5-1 Setting Inputs and Signal Ranges) or short-circuit the
voltage input terminals (V+) and (V–).
3. Crimp-type terminals must be used for terminal connections, and the
screws must be tightened securely. Use M3 screws and tighten them to a
torque of 0.5 N S m.
Fork Type
Round Type
6.0 mm max.
Connecting shielded cable to the Unit’s COM terminals (A3, A10, B6, B13)
can improve noise resistance.
16
IR and DM Areas Section 2-4
17
IR and DM Areas Section 2-4
Allocation for Normal For normal mode, set the operation mode switch on the rear panel of the Unit as
Mode shown in the following diagram.
The disconnection detection function can be used when the input signal range is
set for 1 to 5 V (4 to 20 mA).
Input signal range Voltage/current
1 to 5 V 0.3 V max.
4 to 20 mA 1.2 mA max.
18
IR and DM Areas Section 2-4
Allocation for For adjustment mode, set the operation mode switch on the rear panel of the
Adjustment Mode Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the RUN indicator on the front panel of the Unit will flash.
Item Contents
Input to be adjusted Sets input to be adjusted. Leftmost digit: Fixed at 2.
Rightmost digit: 1 to 9
Offset (Offset Bit) When ON, adjusts offset deviation.
Gain (Gain Bit) When ON, adjusts gain deviation.
Set (Set Bit) Sets adjusted value and writes to EEPROM.
Clr (Clear Bit) Clears adjusted value. (Returns to default status)
Conversion value for The conversion value for adjustment is stored as 16
adjustment bits of binary data.
Disconnection detection 0: No disconnection
1: Disconnection
Error code Two digits, hexadecimal (00 for no error)
The disconnection detection function can be used when the input signal range is
set for 1 to 5 V (4 to 20 mA).
19
IR and DM Areas Section 2-4
DM words
Unit #0 DM 1000 to 1099 DM (m) Use designation
Unit #1 DM 1100 to 1199
Data is automatically DM (m+1) Input signal range
Unit #2 DM 1200 to 1299 setting
transferred to each unit
Unit #3 DM 1300 to 1399 number when the power Sets number of
is turned on, or when the DM (m+2 samples for mean
Unit #4 DM 1400 to 1499 to m+9)
Special I/O Unit’s Re- value processing
Unit #5 DM 1500 to 1599 start Bit is turned ON.
Note For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
20
Using the Functions Section 2-5
DM (m)
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
0: Do not use
1: Use
The analog input sampling interval can be shortened by setting any unused input
numbers to 0.
Sampling interval = (1 ms) x (Number of inputs used)
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Input Signal Range Any of four types of input signal range can be selected for each of the eight inputs
(input numbers 1 to 8). In order to specify the input signal range for each input,
set from a Peripheral Device the DM bits shown in the following diagram.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m+1)
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
00: -10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: Same as 10 above.
21
Using the Functions Section 2-5
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 2-7-4 Restarting Special I/O
Units.
Example 1 In this example, the conversion data from only one input is read. (The unit num-
ber is #0.)
Input condition
MOV(21) Conversion data in IR word
101 (input number 1) is read
101
to DM 0001.
DM0001
Example 2 In this example, the conversion data from multiple inputs is read. (The unit num-
ber is #0.)
Input condition
XFER(70) Conversion data in IR words
101 to 104 (input numbers 1
#0004
to 4) is read to DM 0001
101 through DM 0004.
DM0001
For details regarding conversion value scaling, refer to page 116, Sample Pro-
gram 5: Scaling Function.
22
Using the Functions Section 2-5
Buffer 2
Buffer 3
(Mean value Conversion value
processing)
Buffer 4 (Values stored in IR
words n+1 to n+8)
Buffer n
(Discarded)
When “n” number of history buffers are being used, the first conversion data will
be stored for all “n” number of history buffers immediately data conversion has
begun or after a disconnection is restored.
When mean value processing is used together with the peak value function, the
mean value will be held.
To specify whether or not mean value processing is to be used, and to specify the
number of history buffers for mean data processing, use a Peripheral Device to
make the settings in DM m+2 through DM m+9 as shown in the following table.
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 2-7-4 Restarting Special I/O
Units.
23
Using the Functions Section 2-5
The history buffer operational means are calculated as shown below. (In this ex-
ample there are four buffers.)
1, 2, 3... 1. With the first cycle, the data is stored with Data 1 being in all the history buff-
ers.
Data 1
Data 1
(Mean value Conversion value
processing)
Data 1
Data 1
Data 1
(Mean value Conversion value
processing)
Data 1
Data 1
Data 2
(Mean value Conversion value
processing)
Data 1
Data 1
Data 3
(Mean value Conversion value
processing)
Data 2
Data 1
Data 4
(Mean value Conversion value
processing)
Data 3
Data 2
24
Using the Functions Section 2-5
t (Time)
The peak value function can be set individually for each input number by turning
on the respective bits (00 to 07) in IR word n.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
The peak hold function will be in effect
for the above input numbers while
their respective bits are ON. The
conversion values will be reset when
the bits are turned OFF.
Input condition
The maximum
10000
conversion
data value is
held for input
number 1.
When mean value processing is used together with the peak value function, the
mean value will be held.
As long as the peak value function is in effect, the peak value will be held even in
the event of a disconnection.
25
Using the Functions Section 2-5
The input disconnection detection signals for each input number are stored in
bits 00 to 07 of IR word n+9. Specify these bits as execution conditions in order to
use disconnection detection in the user’s program.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+9
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
The respective bit turns ON when a
disconnection is detected for a given
input. When the disconnection is
restored, the bit turns OFF.
10900
MOV(21) The conver-
101
sion value in
IR word 101
DM0001 (input number
1) is read to
DM 00001.
26
Offset and Gain Adjustment Section 2-6
Power up the PC
The RUN indicator will flash while
When adjusting another input number in adjustment mode.
Offset adjustment (Refer to page 28) Gain adjustment (Refer to page 30)
! Caution Be sure to turn off the power to the PC before changing the operation mode
switch.
If the I/O table is registered in the PC, an I/O setting error may occur, not allowing
any adjustment. In such a case, either cancel the I/O table or create the I/O table
again.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
27
Offset and Gain Adjustment Section 2-6
Note Input adjustments can be performed more accurately in conjunction with mean
value processing.
Word n
CH B A A
c100
SHIFT
*
1 0 0 MONTR 0000
PRES VAL?
CHG c100 0000 ????
A A C B
c100
0 0 2 1 WRITE 0021
Bits Used for Adjusting The IR word n+1 bits shown in the following diagram are used for adjusting offset
Offset and Gain and gain.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
Offset bit
Set bit
Gain bit
Clear bit
Offset Adjustment The procedure for adjusting the analog input offset is explained below. As shown
in the following diagram, the offset is adjusted by sampling inputs so that the
conversion value becomes 0.
0FA0
0 10 V
28
Offset and Gain Adjustment Section 2-6
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 00 (the Offset Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100
^OFF
PLAY
10100
SET
ON
The analog input’s digital conversion values while the Offset Bit is ON will be
monitored in IR word n+8.
2. Check whether the input devices are connected.
A0 Voltage input
A1 +
A2 –
A3
Input 1
A0
Current input
A1 +
A2 –
A3
Input 1
3. Input the voltage or current so that the conversion value becomes 0000. The
following table shows the the offset adjustment voltages and currents to be
input according to the input signal range.
Input signal range Input voltage/current Input range
0 to 10 V 0V –0.5 to 0.5 V
–10 to 10 V 0V –1.0 to 1.0 V
1 to 5 V 1V 0.8 to 1.2 V
4 to 20 mA 4 mA 3.2 to 4.8 mA
4. With the voltage or current having been input so that the conversion value
for the Analog Input Unit is 0000, turn bit 04 (the Set Bit) of IR word n+1 ON
and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
10104 10100
^OFF ^ ON
PLAY
10104 10100
SET
ON ^ ON
REC
10104 10100
RESET
OFF ^ ON
29
Offset and Gain Adjustment Section 2-6
While the Offset Bit is ON, the offset value will be saved to the Unit’s EE-
PROM when the Set Bit turns ON.
5. To finish the offset adjustment, turn OFF bit 00 (the Offset Bit) of IR word
n+1.
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100 10104
^ ON ^OFF
REC
10100 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Gain Adjustment The procedure for adjusting the analog input gain is explained below. As shown
in the following diagram, the gain is adjusted by sampling inputs so that the con-
version value is maximized.
0FA0
0 10 V
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 01 (the Gain Bit) of IR word n+1. (Hold the ON status.)
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101
^OFF
PLAY
10101
SET
ON
The analog input’s digital conversion values while the Gain Bit is ON will be
monitored in IR word n+8.
30
Offset and Gain Adjustment Section 2-6
A0 Voltage input
A1 +
A2 –
A3
Input 1
A0 Current input
A1 +
A2 –
A3
Input 1
3. Input the voltage or current so that the conversion value is maximized (0FA0
or 07D0). The following table shows the the gain adjustment voltages and
currents to be input according to the input signal range.
4. With the voltage or current having been input so that the conversion value
for the Analog Input Unit is maximized (0FA0 or 07D0), turn bit 04 (the Set
Bit) of IR word n+1 ON and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
10104 10101
^OFF ^ ON
PLAY
10104 10101
SET
ON ^ ON
REC
10104 10101
RESET
OFF ^ ON
While the Gain Bit is ON, the gain value will be saved to the Unit’s EEPROM
when the Set Bit turns ON.
5. To finish the gain adjustment, turn OFF bit 01 (the Gain Bit) of IR word n+1.
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101 10104
^ ON ^OFF
REC
10101 10104
RESET
OFF ^OFF
31
Offset and Gain Adjustment Section 2-6
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Clearing Offset and Gain Follow the procedure outlined below to return the offset and gain adjusted val-
Adjusted Values ues to their default settings.
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 05 (the Clear Bit) of IR word n+1. (Hold the ON status.) Regard-
less of the input value, 0000 will be monitored in IR word n+8.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105
^OFF
PLAY
10105
SET
ON
10104 10105
^OFF ^ ON
PLAY
10104 10105
SET
ON ^ ON
REC
10104 10105
RESET
OFF ^ ON
While the Clear Bit is ON, the default offset and gain values will be saved to
the Unit’s EEPROM when the Set Bit turns ON.
3. To finish the clearing of adjusted values, turn OFF bit 05 (the Clear Bit) of IR
word n+1.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105 10104
^ ON ^OFF
PLAY
10105 10104
SET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
32
Error Processing Section 2-7
Word n+9
33
Error Processing Section 2-7
Note Disconnection detection (82) operates for input numbers used with a range of 1
to 5 V (4 to 20 mA).
Errors indicated with 8j codes are automatically reset when proper counter-
measures are taken. The errors indicated with Fj codes are cleared when the
power is turned on after making the correct settings and when the Special I/O
Unit Restart Bit is turned OFF, ON, and OFF again.
Note SR bits 28210 to 28215 cannot be used with C200HE and C200HX/HG-
CPU3j-E/4j-E PCs.
34
Error Processing Section 2-7
Note SR bits 28210 to 28215 cannot be used with C200HE and C200HX/HG-
CPU3j-E/4j-E PCs.
If the error is not cleared even after turning the Special I/O Unit Restart Bit ON
and then OFF again, then replace the Unit.
2-7-5 Troubleshooting
The following tables explain the probable causes of troubles that may occur, and
the countermeasures for dealing with them.
35
Error Processing Section 2-7
36
SECTION 3
C200H-DA003 and C200H-DA004 Analog Output Units
This section provides the information required to install and operate a C200H-DA003 or C200H-DA004 Analog Output Unit.
3-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3-1-2 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3-1-3 Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-2-1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-2-2 Unit Number Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-2-3 Operation Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-3-1 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-3-2 Internal Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3-3-3 Output Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3-3-4 Output Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-4-1 IR Area Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-4-2 DM Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-5 Using the Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3-5-1 Setting Outputs and Signal Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3-5-2 Output Hold Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-5-3 Writing Set Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-5-4 Starting and Stopping Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3-5-5 Output Setting Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3-6 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3-6-1 Adjustment Mode Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3-6-2 Offset and Gain Adjustment Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
3-7 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3-7-1 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3-7-2 Errors Detected by Analog Output Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3-7-3 Errors Detected by CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3-7-4 Restarting Special I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3-7-5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
37
Specifications Section 3-1
3-1 Specifications
3-1-1 General Specifications
All general specifications of the C200H-DA003/DA004 Analog Output Units
conform to those of the C200H, C200HS, and C200HX/HG/HE Series.
38
Specifications Section 3-1
5.2 V (20.8mA)
5 V (20mA)
1 V (4mA)
0.8 V (3.2mA)
0000 OFA0
FF38 1068
Resolution: 4,000
Range: 0 to 10 V
Analog output signal
+10.5 V
+10 V
0V
–0.5 V
0000 OFA0
FF38 Resolution: 4,000 1068
39
Nomenclature and Functions Section 3-2
Range: –10 to 10 V
+11 V
+10V
0V
–10 V
–11 V
Front Back
Model label
Backplane connector
40
Nomenclature and Functions Section 3-2
Check to be sure that the black terminal block mounting screw is securely tight-
ened to a torque of 0.5 N S m.
3-2-1 Indicators
The RUN and ERROR indicators show the operating status of the Unit. The fol-
lowing table shows the meanings of the indicators.
LED Indicator Operating status
RUN (green) Lit Operating in normal mode.
Flashes Operating in adjustment mode.
Not lit Abnormal (Unit operation stopped)
ERROR (red) Lit Error occurred. The error codes are stored in bits
08 to 15 of word n+9.
Not lit Other than the above.
41
Wiring Section 3-3
2. If two or more Special I/O Units are assigned the same unit number, an I/O
UNIT OVER error will be generated and the PC will not operate.
! Caution Do not set the pins to any combination other than those shown in the above
table. Be sure to set pins 2, 3, and 4 to OFF.
! Caution Be sure to turn off the power to the PC before changing the operation mode
switch settings.
3-3 Wiring
3-3-1 Terminal Arrangement
The signal names corresponding to the connecting terminals are as shown in the
following diagram.
42
Wiring Section 3-3
A0 NC
NC B0
A1 Current output 1 (–)
Current output 2 (–) B1
A2 Current output 1 (+)
Current output 2 (+) B2
A3 NC
NC B3
A4 Current output 3 (–)
Current output 4 (–) B4
A5 Current output 3 (+)
Current output 4 (+) B5
A6 NC
NC B6
A7 Current output 5 (–)
Current output 6 (–) B7
A8 Current output 5 (+)
Current output 6 (+) B8
A9 NC
NC B9
A10 Current output 7 (–)
Current output 8 (–) B10
A11 Current output 7 (+)
Current output 8 (+) B11
A12 NC
NC B12
A13 NC
NC B13
Note 1. The analog output numbers that can be used are set in the Data Memory
(DM).
2. The output signal ranges for individual outputs are set in the Data Memory
(DM). Setting is possible for every Analog Output Unit output number.
Output AMP
switch and Voltage
conversion output (+)
circuit
Voltage
output (–)
Output
switch and
conversion AMP
circuit
Current
output (+)
Current
output (–)
43
Wiring Section 3-3
A0 Output 1
B0
Output 2 A1
B1
A2
B2
A3
B3 Output 3
Output 4 A4
B4
A5
B5
A6
B6 Output 5
Output 6 A7
B7
A8
B8
A9
B9 Output 7
Output 8 A10
B10
A11
B11
A12
B12
A13
B13
A0 Output 1
Output 2 B0
A1
B1
A2
B2
A3
Output 3
B3
Output 4 A4
B4
A5
B5
A6
B6
Output 5
Output 6 A7
B7
A8
B8
A9
B9
Output 7
Output 8 A10
B10
A11
B11
A12
B12
A13
B13
44
Wiring Section 3-3
Note Crimp-type terminals must be used for terminal connections, and the screws
must be tightened securely. Use M3 screws and tighten them to a torque of
0.5 N S m.
Fork Type
Round Type
6.0 mm max.
To minimize output wiring noise, ground the output signal line to the output de-
vice.
45
IR and DM Areas Section 3-4
46
IR and DM Areas Section 3-4
Allocation for Normal For normal mode, set the operation mode switch on the rear panel of the Unit as
Mode shown in the following diagram.
47
IR and DM Areas Section 3-4
Allocation for For adjustment mode, set the operation mode switch on the rear panel of the
Adjustment Mode Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the RUN indicator on the front panel of the Unit will flash.
48
IR and DM Areas Section 3-4
DM words
Unit #0 DM 1000 to 1099 DM (m) Use designation
Unit #1 DM 1100 to 1199
Data is automatically DM (m+1) Output signal
Unit #2 DM 1200 to 1299 range setting
transferred to each unit
Unit #3 DM 1300 to 1399 number when the power
is turned on, or when the DM (m+2 Output hold
Unit #4 DM 1400 to 1499 to m+9) function setting
Special I/O Unit Restart
Unit #5 DM 1500 to 1599 Bit is turned ON.
49
Using the Functions Section 3-5
DM (m)
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
0: Do not use
1: Use
The analog output conversion cycle can be shortened by setting any unused
output numbers to 0.
Conversion cycle = (1 ms) x (Number of outputs used)
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Output Signal Range With the C200H-DA003 (voltage output model), any of three types of output sig-
nal range can be selected for each of the eight outputs (output numbers 1 to 8).
In order to specify the output signal range for each output, set from a Peripheral
Device the DM bits shown in the following diagram.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m+1)
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
00: -10 to 10 V
01: 0 to 10 V
10: 1 to 5 V
11: Same as 10 above.
50
Using the Functions Section 3-5
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
This setting is not valid for the C200H-DA004 (current output model). The output
signal range for the C200-DA004 is 4 to 20 mA, regardless of the settings.
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 3-7-4 Restarting Special I/O
Units.
In order to specify the the output hold function, set from a Peripheral Device the
DM words shown in the following table.
DM word Function Set value
DM (m+2) Output 1: Output status when stopped xx00: CLR
0 output
DM (m+3) Output 2: Output status when stopped
xx01: HOLD
DM (m+4) Output 3: Output status when stopped
Hold output value
DM (m+5) Output 4: Output status when stopped prior to stop
DM (m+6) Output 5: Output status when stopped xx02: MAX
DM (m+7) Output 6: Output status when stopped Output maximum
value of range
DM (m+8) Output 7: Output status when stopped
Set any value in the
DM (m+9) Output 8: Output status when stopped leftmost bytes (xx).
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 3-7-4 Restarting Special I/O
Units.
51
Using the Functions Section 3-5
Input condition
MOV (21) The set value stored in DM 0001
DM0001 is written to IR word 101 (output
101 number 1).
Example 2 In this example, multiple set values are written. (The unit number is #0.)
Input condition
XFER(70)
The set values stored in DM 0001
#0004 to DM 0004 are written to IR words
DM0001 101 to 104 (outputs 1 to 4).
101
For details regarding set value scaling, refer to page 116, Sample Program 5:
Scaling Function.
Note Turn ON the Conversion Enable Bit for converting set values into analog output.
Word n
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
52
Using the Functions Section 3-5
The analog output when conversion is stopped will differ depending on the out-
put signal range setting. (Refer to 3-5-1 Setting Outputs and Signal Ranges.)
Conversion will not begin under the following conditions even if the Conversion
Enable Bit is turned ON.
1, 2, 3... 1. In adjustment mode, when something other than the output number is out-
put during adjustment. (Refer to 3-6-1 Adjustment Mode Operational Flow.)
2. When there is an output setting error. (Refer to 3-5-5 Output Setting Errors.)
3. When a fatal error occurs at the PC. (Refer to the C200HX/HG/HE Program-
ming Manual.)
In this example, conversion is begun for analog output number 1. (The unit num-
ber is #0.)
Input condition
10000 Conversion
begins for
output
number 1.
Word n+9
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
When a setting error is detected for a
particular output, the corresponding
bit turns ON. When the error is
cleared, the bit turns OFF.
53
Offset and Gain Adjustment Section 3-6
Power up the PC
The RUN indicator will flash while
When adjusting another output number in adjustment mode.
Offset adjustment (Refer to page 55) Gain adjustment (Refer to page 58)
! Caution Be sure to turn off the power to the PC before changing the operation mode
switch settings.
If the I/O table is registered in the PC, an I/O setting error may occur, not allowing
any adjustment. In such a case, either cancel the I/O table or create the I/O table
again.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
54
Offset and Gain Adjustment Section 3-6
(Leftmost) (Rightmost)
Word n
CH B A A
c100
SHIFT
*
1 0 0 MONTR 0000
PRES VAL?
CHG c100 0000 ????
A A B B
c100
0 0 1 1 WRITE 0011
Bits Used for Adjusting The IR word n+1 bits shown in the following diagram are used for adjusting offset
Offset and Gain and gain.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
Offset bit
Set bit
Clear bit
Up bit
Down bit
Gain bit
Offset Adjustment The procedure for adjusting the analog output offset is explained below. As
shown in the following diagram, the set value is adjusted so that the analog out-
put reaches the standard value (0V/1V/4mA).
10 V
0
0FA0
55
Offset and Gain Adjustment Section 3-6
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 00 (the Offset Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100
^OFF
PLAY
10100
SET
ON
Voltage output
A0
A1
Output 1
A2
A3
Current output
A0
A1 Output 1
A2
A3
3. Monitor IR word n+8 and check the set value while the Offset Bit is ON.
00000
CLR
CH B A
SHIFT 1 0 8 MONTR
*
c108
0000
4. Change the set value so that the output voltage and output current are as
shown in the following table. The data can be set within the indicated
ranges.
56
Offset and Gain Adjustment Section 3-6
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down Bit
(bit 02 of word n+1).
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
CONT B A B A C
SHIFT 1 0 1 0 2 MONTR
#
10102 c108
^OFF 0000
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
PLAY
10102 c108
SET
ON FFFF
REC
10102 c108
RESET
OFF FFFF
5. Check the 0V/1V/4mA output, and then turn bit 04 (the Set Bit) of IR word
n+1 OFF, ON, and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
PLAY
10104 10102 c108
SET
ON ^ OFF FFFF
REC
10104 10102 c108
RESET
OFF ^ OFF FFFF
While the Offset Bit is ON, the offset value will be saved to the Unit’s EE-
PROM when the Set Bit turns ON.
57
Offset and Gain Adjustment Section 3-6
6. To finish the offset adjustment, turn OFF bit 00 (the Offset Bit) of IR word
n+1.
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100 10104
^ ON ^OFF
REC
10100 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Gain Adjustment The procedure for adjusting the analog output gain is explained below. As shown
in the following diagram, the set value is adjusted so that the analog output is
maximized (to 10V/5V/20mA).
10 V
0
0FA0
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 01 (the Gain Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101
^OFF
PLAY
10101
SET
ON
58
Offset and Gain Adjustment Section 3-6
Voltage output
A0
A1
Output 1
A2
A3
Current output
A0
A1
Output 1
A2
A3
3. Monitor IR word n+8 and check the set value while the Gain Bit is ON.
00000
CLR
CH B A
SHIFT 1 0 8 MONTR
*
c108
0FA0
4. Change the set value so that the output voltage and output current are as
shown in the following table. The data can be set within the indicated
ranges.
Output signal range Output voltage/current Output range
0 to 10 V 10 V 0ED8 to 1068
–10 to 10 V 10 V 0708 to 0898
1 to 5 V 5V 0ED8 to 1068
4 to 20 mA 20 mA 0ED8 to 1068
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down Bit
(bit 02 of word n+1).
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
59
Offset and Gain Adjustment Section 3-6
CONT B A B A C
SHIFT 1 0 1 0 2 MONTR
#
10102 c108
^OFF 0FA0
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
PLAY
10102 c108
SET
ON 0F9F
REC
10102 c108
RESET
OFF 0F9F
5. Check the 10V/5V/20mA output, and then turn bit 04 (the Set Bit) of IR word
n+1 OFF, ON, and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
PLAY
10104 10102 c108
SET
ON ^ OFF 0F9F
REC
10104 10102 c108
RESET
OFF ^ OFF 0F9F
While the Gain Bit is ON, the gain value will be saved to the Unit’s EEPROM
when the Set Bit turns ON.
6. To finish the gain adjustment, turn OFF bit 01 (the Gain Bit) of IR word n+1.
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101 10104
^OFF ^OFF
REC
10101 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
60
Offset and Gain Adjustment Section 3-6
Clearing Offset and Gain Follow the procedure outlined below to return the offset and gain adjusted val-
Adjusted Values ues to their default settings.
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 05 (the Clear Bit) of IR word n+1. (Hold the ON status.) Regard-
less of the set value, 0000 will be monitored in IR word n+8.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105
^OFF
PLAY
10105
SET
ON
10104 10105
^OFF ^ ON
PLAY
10104 10105
SET
ON ^ ON
REC
10104 10105
RESET
OFF ^ ON
While the Clear Bit is ON, the default offset and gain values will be saved to
the Unit’s EEPROM when the Set Bit turns ON.
3. To finish the clearing of adjusted values, turn OFF bit 05 (the Clear Bit) of IR
word n+1.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105 10104
^ ON ^OFF
REC
10105 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
61
Error Processing Section 3-7
Word n+9
62
Error Processing Section 3-7
63
Error Processing Section 3-7
If the error is not cleared even after turning the Special I/O Unit Restart Bit ON
and then OFF again, then replace the Unit.
3-7-5 Troubleshooting
The following tables explain the probable causes of troubles that may occur, and
the countermeasures for dealing with them.
Analog Output Does Not Probable Cause Countermeasure Page
Change
The output is not set for being Set the output for being used. 50
used.
The output hold function is in Turn ON the Output Conversion 52
operation. Enable Bit.
The conversion value is set outside Set the data within the range. 39
of the permissible range.
64
SECTION 4
C200H-MAD01 Analog I/O Unit
This section provides the information required to install and operate a C200H-MAD01 Analog I/O Unit.
4-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4-1-2 Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4-1-3 Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4-1-4 Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4-2 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-2-1 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-2-2 Unit Number Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4-2-3 Operation Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4-3-1 Terminal Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4-3-2 Internal Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4-3-3 Line Breakage while Using Voltage Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4-3-4 I/O Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4-3-5 I/O Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4-4 IR and DM Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4-4-1 IR Area Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4-4-2 DM Allocation and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4-5 Analog Input Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
4-5-1 Setting Inputs and Signal Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
4-5-2 Reading Conversion Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4-5-3 Mean Value Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4-5-4 Peak Value Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
4-5-5 Input Disconnection Detection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
4-6 Analog Output Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4-6-1 Setting Outputs and Signal Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
4-6-2 Output Hold Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
4-6-3 Writing Set Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
4-6-4 Starting and Stopping Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
4-6-5 Output Setting Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
4-7 Ratio Conversion Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
4-8 Offset and Gain Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
4-8-1 Adjustment Mode Operational Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
4-8-2 Input Offset and Gain Adjustment Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4-8-3 Output Offset and Gain Adjustment Procedures . . . . . . . . . . . . . . . . . . . . . . . . . 98
4-9 Error Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
4-9-1 Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
4-9-2 Errors Detected by Analog I/O Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
4-9-3 Errors Detected by CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
4-9-4 Restarting Special I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
4-9-5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
65
Specifications Section 4-1
4-1 Specifications
Item C200H-MAD01
Voltage input Current input
Input Number of analog inputs 2
Input signal range (note 0 to 10 V 4 to 20 mA
1) –10 to 10 V
1 to 5 V
Max. input signal (note 2) ±15 V ±30 mA
Input impedance 1 MΩ min. 250 Ω (rated value)
Resolution 1/4000 (full scale)
Converted output data 16-bit binary data
Accuracy 23°±2°C ±0.2% of full scale ±0.4% of full scale
(note 3)
0° to ±0.4% of full scale ±0.6% of full scale
55°C
Output Number of analog outputs 2
Output signal range (note 0 to 10 V 4 to 20 mA
1) –10 to 10 V
1 to 5 V
Output impedance 0.5 Ω max. ---
Resolution 1/4000 (full scale)
Set data 16-bit binary data
Accuracy 23°±2°C ±0.3% of full scale ±0.5% of full scale
(note 3)
0° to ±0.5% of full scale ±0.8% of full scale
55°C
Com- Conversion time (note 4) 1.0 ms/point max.
mon Isolation Between I/O terminals and PC: photocoupler
(No isolation between individual input and
output signals.)
External connectors 28-point terminal block (M3 screws)
Power consumption 100 mA max. at 5 VDC
200 mA max. at 26 VDC
Dimensions 34.5 x 130 x 128 (W x H x D) mm (refer to
Appendix A Dimensions)
Weight 450 g max.
Note 1. The I/O signal range can be set individually for each input.
2. Operate within the ranges listed above. Operation in ranges beyond the
maximum input signals will damage the Unit.
3. The accuracy is given for full scale. For example, an accuracy of ±0.2%
means a maximum error of ±8 (BCD).
The default setting is adjusted with the voltage input for the analog input and
with the current output for the analog output. When using the current input
and voltage output, perform the offset and gain adjustment as required.
66
Specifications Section 4-1
4. A/D conversion time is the time it takes for an analog signal to be stored in
memory as converted data after it has been input. It takes at least one cycle
before the converted data is read by the CPU Unit. D/A conversion time is
the time required for converting and outputting the PC data. It takes at least
one cycle for the data stored in the PC to be read by the Analog Output Unit.
By executing an I/O refresh, the conversion time may be extended by an
additional 0.3 ms approximately.
Range: 1 to 5 V (4 to 20 mA)
1068
0FA0
Resolution: 4,000
0000
FF38
Range: 0 to 10 V
1068
0FA0
Resolution: 4,000
0000
FF38
0V +10 V
–0.5 V +10.5 V
Analog input signal
67
Specifications Section 4-1
Range: –10 to 10 V
Conversion value (16-bit binary data)
0898
07D0
Resolution: 4,000
0000
F830
F768
–10 V 0V +10 V
–11 V +11 V
Analog input signal
5.2 V (20.8mA)
5 V (20mA)
1 V (4mA)
0.8 V (3.2mA)
0000 OFA0
FF38 Resolution: 4,000 1068
68
Specifications Section 4-1
Range: 0 to 10 V
Analog output signal
+10.5 V
+10 V
0V
–0.5 V
0000 OFA0
FF38 Resolution: 4,000
1068
Range: –10 to 10 V
Analog output signal
+11 V
+10 V
0V
–10 V
–11 V
69
Nomenclature and Functions Section 4-2
Model label
Backplane connector
4-2-1 Indicators
The RUN and ERROR indicators show the operating status of the Unit. The fol-
lowing table shows the meanings of the indicators.
LED Indicator Operating status
RUN (green) Lit Operating in normal mode.
Flashes Operating in adjustment mode.
Not lit Abnormal (Unit operation stopped)
ERROR (red) Lit Error occurred. The error codes are stored in bits
08 to 15 of word n+9.
Not lit Other than the above.
70
Nomenclature and Functions Section 4-2
! Caution Do not set the pins to any combination other than those shown in the above
table.
Be sure to set pins 2, 3, and 4 to OFF.
! Caution Be sure to turn off the power to the PC before mounting or removing any Units.
71
Wiring Section 4-3
4-3 Wiring
Note 1. The analog I/O numbers that can be used are set in the Data Memory (DM).
2. The I/O signal ranges for individual inputs and outputs are set in the Data
Memory (DM). They can be set in units of analog I/O numbers.
3. The COM terminal (A9, B9) is connected to the 0-V analog circuit in the Unit.
Connecting shielded input lines can improve noise resistance.
Input Circuitry
Current
input (+)
250 Ω
15 kΩ 15 kΩ
Voltage
input (+) Input circuit
and
1 MΩ
15 kΩ 15 kΩ conversion
Voltage
circuit
input (–)
COM
(analog
0 V) 1 MΩ
72
Wiring Section 4-3
Output
AMP
switch and Voltage
conversion output (+)
circuit
Voltage
output (–)
Output
switch and
conversion
AMP
circuit
Current
output (+)
Current
output (–)
Con-
nected
device
1
Con-
nected
device
2
24 VDC
Note If the power supply is shared by two channels as shown above, while the con-
nected device 2 outputs 5 V, approximately 1.6 V (one-third of the output volt-
age) is generated in input 1.
73
Wiring Section 4-3
If a line breakage occurs while using the voltage input, either separate the power
supply from the connected device or use an isolator for each input to avoid the
following problem.
In case of the current input, this kind of problem will not occur even if the power
supply is shared by the connected devices.
Output 2 A0
Output 1
(Voltage output) (Current output)
B0
A1
B1
A2
B2
A3
B3
A4
B4
A5
B5 Input 1
Input 2 A6
(Current input)
(Voltage input) B6
+
A7
+ B7
A8 –
– B8
A9
B9
A10
B10
A11
B11
A12
B12
A13
B13
Note 1. When using current inputs, the voltage input terminals (V+) and current in-
put terminals (I+) must be individually short-circuited as shown in the above
diagram.
3. For inputs that are not used, either set to “0: Do not use” in the input number
settings (refer to 4-5-1 Setting Inputs and Signal Ranges) or short-circuit the
voltage input terminals (V+) and (V–).
74
Wiring Section 4-3
Fork Type
Round Type
6.0 mm max.
Connecting shielded cable to the Unit’s COM terminals (A9, B9) can improve
noise resistance.
To minimize output wiring noise, ground the output signal line to the output de-
vice.
75
IR and DM Areas Section 4-4
76
IR and DM Areas Section 4-4
Allocation for Normal For normal mode, set the operation mode switch on the rear panel of the Unit as
Mode shown in the following diagram.
The disconnection detection function can be used when the input signal range is
set for 1 to 5 V (4 to 20 mA).
77
IR and DM Areas Section 4-4
Allocation for For adjustment mode, set the operation mode switch on the rear panel of the
Adjustment Mode Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the RUN indicator on the front panel of the Unit will flash.
The disconnection detection function can be used when the input signal range is
set for 1 to 5 V (4 to 20 mA).
Input signal range Voltage/current
1 to 5 V 0.3 V max.
4 to 20 mA 1.2 mA max.
78
IR and DM Areas Section 4-4
Word
I/O conversion
Unit #0 DM 1000 to 1099 DM (m) permission loop
mode setting
Unit #1 DM 1100 to 1199
Unit #2 DM 1200 to 1299 DM (m+1) Input signal range
Data is automatically
Unit #3 DM 1300 to 1399 transferred to each unit
DM (m+2 Output hold
number when the power
Unit #4 DM 1400 to 1499 to m+3) function setting
is turned on, or when the
Special I/O Unit’s Re-
Unit #5 DM 1500 to 1599 Sets number of
start Bit is turned ON. DM (m+6
Unit #6 DM 1600 to 1699 to m+9) samples for mean
value processing
Unit #7 DM 1700 to 1799
DM (m+10 Ratio set value,
Unit #8 DM 1800 to 1899 to m+13) bias value setting
Unit #9 DM 1900 to 1999
Unit #A DM 2000 to 2099
Unit #B DM 2100 to 2199
Unit #C DM 2200 to 2299
m = 1000 + 100 x unit number
Unit #D DM 2300 to 2399 (Units #A to #F = Unit numbers 10 to 15)
79
IR and DM Areas Section 4-4
DM Allocation Contents The following table shows the allocation of DM words and bits for both normal
and adjustment mode.
DM word Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
DM (m) Not used. Ratio conversion use Not used. Use desig- Not used. Use desig-
designation nation nation
Loop 2 Loop 1 Input Input Out- Out-
2 1 put 2 put 1
DM (m+1) Not used. Input signal range set- Not used. Output signal range set-
ting (See note 2.) ting (See note 2.)
Input 2 Input 1 Output 2 Output 1
DM (m+2) Not used. Output 1: Output status when conversion stopped
DM (m+3) Not used. Output 2: Output status when conversion stopped
DM (m+4) Not used.
DM (m+5) Not used.
DM (m+6) Input 1: Mean value processing setting
DM (m+7) Input 2: Mean value processing setting
DM (m+8) Not used.
DM (m+9) Not used.
DM (m+10) Loop 1 (input 1 to output 1), A constant
DM (m+11) Loop 1 (input 1 to output 1), B constant
DM (m+12) Loop 2 (input 2 to output 2), A constant
DM (m+13) Loop 2 (input 2 to output 2), B constant
Note 1. For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F =
Unit numbers 10 to 15).
2. The I/O signal range of “1 to 5 V” or “4 to 20 mA” is switched according to the
input or output terminal connections.
80
Analog Input Functions Section 4-5
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m)
Input 2
Input 1
0: Do not use
1: Use
The analog input sampling interval can be shortened by setting any unused input
numbers to 0.
Sampling interval = (1 ms) x (Number of inputs used) +(1ms) x (Number of
outputs used (see note a)) (+ (0.5ms) x (Number of loops used (see note b)))
Note a) Refer to 4-6 Analog Output Functions for output settings.
b) Only when using the ratio conversion function.
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Input Signal Range Any of four types of input signal range can be selected for each of the eight inputs
(input numbers 1 and 2). In order to specify the input signal range for each input,
set from a Peripheral Device the DM bits shown in the following diagram.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m+1)
Input 2
Input 1
Note 1. For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F =
Unit numbers 10 to 15).
2. The I/O signal range of “1 to 5 V” or “4 to 20 mA” is switched according to the
input terminal connections.
3. After making the DM settings from a Peripheral Device, it will be necessary
to either power up the PC again or turn ON the Special I/O Unit Restart Bit in
order to transfer the contents of the DM settings to the Special I/O Unit. For
details regarding the Special I/O Unit Restart Bit, refer to 4-9-4 Restarting
Special I/O Units.
81
Analog Input Functions Section 4-5
Input condition
MOV(21) Conversion data in IR word
105 (input number 1) is read
105
to DM 0001.
DM0001
Example 2 In this example, the conversion data from multiple inputs is read. (The unit num-
ber is #0.)
Input condition
XFER(70) Conversion data in IR words
105 and 106 (input numbers 1
#0002
and 2) is read to DM 0001
105 and DM 0002.
DM0001
For details regarding conversion value scaling, refer to page 116, Sample Pro-
gram 5: Scaling Function.
Buffer 2
Buffer 3
(Mean value Conversion value
processing)
Buffer 4 (Values stored in IR
words n+5 and n+6)
Buffer n
(Discarded)
When “n” number of history buffers are being used, the first conversion data will
be stored for all “n” number of history buffers immediately data conversion has
begun or after a disconnection is restored.
82
Analog Input Functions Section 4-5
When mean value processing is used together with the peak value function, the
mean value will be held.
To specify whether or not mean value processing is to be used, and to specify the
number of history buffers for mean data processing, use a Peripheral Device to
make the settings in DM m+6 and DM m+7 as shown in the following table.
DM word Function Set value
DM (m+6) Input 1 mean value processing 0000: No mean value processing
0001: Mean value processing with 2 buffers
0002: Mean value processing with 4 buffers
DM (m+7) Input 2 mean value processing 0003: Mean value processing with 8 buffers
0004: Mean value processing with 16 buffers
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 4-9-4 Restarting Special I/O
Units.
The history buffer operational means are calculated as shown below. (In this ex-
ample there are four buffers.)
1, 2, 3... 1. With the first cycle, the data is stored with Data 1 being in all the history buff-
ers.
Data 1
Data 1
(Mean value Conversion value
processing)
Data 1
Data 1
Data 2
Data 1
(Mean value Conversion value
processing)
Data 1
Data 1
Data 3
Data 2
(Mean value Conversion value
processing)
Data 1
Data 1
83
Analog Input Functions Section 4-5
4. With the fourth cycle, the Data 4 data is stored in the first history buffer.
Data 4
Data 3
(Mean value Conversion value
processing)
Data 2
Data 1
Data 4
(Mean value Conversion value
processing)
Data 3
Data 2
t (Time)
The peak value function can be set individually for each input number by turning
on the respective bits (04 and 05) in IR word n.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n
Input 2
Input 1
84
Analog Input Functions Section 4-5
In the following example, the peak value function is in effect for input number 1,
and the unit number is 0.
Input condition
The maximum
10004
conversion
data value is
held for input
number 1.
When mean value processing is used together with the peak value function, the
mean value will be held.
As long as the peak value function is in effect, the peak value will be held even in
the event of a disconnection.
The input disconnection detection signals for each input number are stored in
bits 04 and 05 of IR word n+9. Specify these bits as execution conditions in order
to use disconnection detection in the user’s program.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+9
Input 2
Input 1
10904
MOV (21) The conver-
sion value in
105
IR word 105
DM0001 (input number
1) is read to
DM 00001.
85
Analog Output Functions Section 4-6
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m)
Output 2
Output 1
0: Do not use
1: Use
The analog output conversion cycle can be shortened by setting any unused
output numbers to 0.
Conversion cycle = (1 ms) x (Number of outputs used) + (1ms) x (Number of
outputs used (see note))
Note Refer to 4-5 Analog Input Functions for input settings.
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Output Signal Range Any of four types of output signal range can be selected for each of the two out-
puts (output numbers 1 and 2). In order to specify the output signal range for
each output, use a Peripheral Device to set the DM bits shown in the following
diagram.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
DM (m + 1) Output 2
Output 1
Note 1. For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F =
Unit numbers 10 to 15).
2. The I/O signal range of “1 to 5 V” or “4 to 20 mA” is switched according to the
input terminal connections.
3. After making the DM settings from a Peripheral Device, it will be necessary
to either power up the PC again or turn ON the Special I/O Unit Restart Bit in
order to transfer the contents of the DM settings to the Special I/O Unit. For
details regarding the Special I/O Unit Restart Bit, refer to 4-9-4 Restarting
Special I/O Units.
86
Analog Output Functions Section 4-6
87
Analog Output Functions Section 4-6
Input condition
MOV (21) The set value stored in DM 0001
DM0001 is written to IR word 101 (output
101 number 1).
Example 2 In this example, multiple set values are written. (The unit number is #0.)
Input condition
XFER(70)
The set values stored in DM 0001
#0002 and DM 0002 are written to IR words
DM0001 101 and 102 (outputs 1 and 2).
101
Note Turn ON the Conversion Enable Bit for converting set values into analog output.
Word n
Output 2
Output 1
Analog conversion is executed while
these bits are ON. When the bits are
turned OFF, the conversion is stopped
and the output data is held. (Refer to
4-6-2 Output Hold Function.)
Input condition
10000 Conversion
begins for
output
number 1.
88
Ratio Conversion Function Section 4-7
Word n+9
Output 2
Output 1
When a setting error is detected
for a particular output, the corre-
sponding bit turns ON. When the
error is cleared, the bit turns OFF.
10900 Conversion
10000 begins for
output
number 1.
A
B
Analog input
89
Ratio Conversion Function Section 4-7
∆Y
∆X
Analog input
DM (m)
Loop 2 Loop 1
The response time of ratio conversion (input to output conversion) is 2.5 ms.
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Specifying Ratio Set The ratio set value (A) and the bias (B) are set in the four DM words from DM
Value and Bias m+10 to DM m+13.
DM word Function Set value
DM (m+10) Loop 1 (input 1 → output 1), BCD 0 to 9999 (0.00 to 99.99;
A constant unit: 0.01)
DM (m+11) Loop 1 (input 1 → output 1), 16-bit binary data
B constant
DM (m+12) Loop 2 (input 2 → output 2), BCD 0 to 9999 (0.00 to 99.99;
A constant unit: 0.01)
DM (m+13) Loop 2 (input 2 → output 2), 16-bit binary data
B constant
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 4-9-4 Restarting Special I/O
Units.
90
Offset and Gain Adjustment Section 4-8
Power up the PC
The RUN indicator will flash while
When adjusting another I/O number in adjustment mode.
Offset adjustment (Refer to pages 93, 98) Gain adjustment (Refer to pages 95, 101)
91
Offset and Gain Adjustment Section 4-8
! Caution Be sure to turn off the power to the PC before mounting or removing any Units.
If the I/O table is registered in the PC, an I/O setting error may occur, not allowing
any adjustment. In such a case, either cancel the I/O table or create the I/O table
again.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Note Input adjustments can be performed more accurately in conjunction with mean
value processing.
(Leftmost) (Rightmost)
Word n
00000
CLR
CH B A A
c100
SHIFT
*
1 0 0 MONTR 0000
CHG
PRES VAL?
c100 0000 ????
A A C B
c100
0 0 2 1 WRITE 0021
Bits Used for Adjusting The IR word n+1 bits shown in the following diagram are used for adjusting offset
Offset and Gain and gain.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
Offset bit
Set bit
Gain bit
Clear bit
92
Offset and Gain Adjustment Section 4-8
Offset Adjustment The procedure for adjusting the analog input offset is explained below. As shown
in the following diagram, the offset is adjusted by sampling inputs so that the
conversion value becomes 0.
0FA0
0 10 V
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 00 (the Offset Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100
^OFF
PLAY
10100
SET
ON
The analog input’s digital conversion values while the Offset Bit is ON will be
monitored in IR word n+8.
2. Check whether the input devices are connected.
A6 Voltage input
A7 +
A8 –
A9
Input 1
A6
Current input
A7 +
A8 –
A9
Input 1
93
Offset and Gain Adjustment Section 4-8
3. Input the voltage or current so that the conversion value becomes 0000. The
following table shows the the offset adjustment voltages and currents to be
input according to the input signal range.
4. With the voltage or current having been input so that the conversion value
for the Analog Input Unit is 0000, turn bit 04 (the Set Bit) of IR word n+1 ON
and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
10104 10100
^OFF ^ ON
PLAY
10104 10100
SET
ON ^ ON
REC
10104 10100
RESET
ON ^ ON
While the Offset Bit is ON, the offset value will be saved to the Unit’s EE-
PROM when the Set Bit turns ON.
5. To finish the offset adjustment, turn OFF bit 00 (the Offset Bit) of IR word
n+1.
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100 10104
^ ON ^OFF
REC
10100 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
94
Offset and Gain Adjustment Section 4-8
Gain Adjustment The procedure for adjusting the analog input gain is explained below. As shown
in the following diagram, the gain is adjusted by sampling inputs so that the con-
version value is maximized.
0FA0
0 10 V
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 01 (the Gain Bit) of IR word n+1. (Hold the ON status.)
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101
^OFF
PLAY
10101
SET
ON
The analog input’s digital conversion values while the Gain Bit is ON will be
monitored in IR word n+8.
2. Check whether the input devices are connected.
A6 Voltage input
A7 +
A8 –
A9
Input 1
A6 Current input
A7 +
A8 –
A9
Input 1
3. Input the voltage or current so that the conversion value is maximized (0FA0
or 07D0). The following table shows the the gain adjustment voltages and
currents to be input according to the input signal range.
Input signal range Input voltage/current Input range
0 to 10 V 10 V 9.5 to 10.5 V
–10 to 10 V 10 V 9.0 to 11.0 V
1 to 5 V 5V 4.8 to 5.2 V
4 to 20 mA 20 mA 19.2 to 20.8 mA
95
Offset and Gain Adjustment Section 4-8
4. With the voltage or current having been input so that the conversion value
for the Analog I/O Unit is maximized (0FA0 or 07D0), turn bit 04 (the Set Bit)
of IR word n+1 ON and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
10104 10100
^OFF ^ ON
PLAY
10104 10100
SET
ON ^ ON
REC
10104 10100
RESET
OFF ^ ON
While the Gain Bit is ON, the gain value will be saved to the Unit’s EEPROM
when the Set Bit turns ON.
5. To finish the gain adjustment, turn OFF bit 01 (the Gain Bit) of IR word n+1.
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101 10104
^ ON ^OFF
REC
10101 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Clearing Offset and Gain Follow the procedure outlined below to return the offset and gain adjusted val-
Adjusted Values ues to their default settings.
The following example uses input number 1 adjustment for illustration. (The unit
number is 0.)
1, 2, 3... 1. Turn ON bit 05 (the Clear Bit) of IR word n+1. (Hold the ON status.) Regard-
less of the input value, 0000 will be monitored in IR word n+8.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105
^OFF
PLAY
10105
SET
ON
96
Offset and Gain Adjustment Section 4-8
10104 10105
^OFF ^ ON
PLAY
10104 10105
SET
ON ^ ON
REC
10104 10105
RESET
OFF ^ ON
While the Clear Bit is ON, the default offset and gain values will be saved to
the Unit’s EEPROM when the Set Bit turns ON.
3. To finish the clearing of adjusted values, turn OFF bit 05 (the Clear Bit) of IR
word n+1.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105 10104
^ ON ^OFF
REC
10105 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Word n
CH B A A
c100
SHIFT
*
1 0 0 MONTR 0000
97
Offset and Gain Adjustment Section 4-8
PRES VAL?
CHG c100 0000 ????
A A B B
c100
0 0 1 1 WRITE 0011
Bits Used for Adjusting The IR word n+1 bits shown in the following diagram are used for adjusting offset
Offset and Gain and gain.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
Offset bit
Set bit
Clear bit
Up bit
Down bit
Gain bit
Offset Adjustment The procedure for adjusting the analog output offset is explained below. As
shown in the following diagram, the set value is adjusted so that the analog out-
put reaches the standard value (0V/1V/4mA).
10 V
0
0FA0
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 00 (the Offset Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100
^OFF
PLAY
10100
SET
ON
98
Offset and Gain Adjustment Section 4-8
Voltage output
A0
A1
Output 1
A2
A3
Current output
A0
A1 Output 1
A2
A3
3. Monitor IR word n+8 and check the set value while the Offset Bit is ON.
00000
CLR
CH B A
SHIFT 1 0 8 MONTR
*
c108
0000
4. Change the set value so that the output voltage and output current are as
shown in the following table. The data can be set within the indicated
ranges.
Output signal range Output voltage/current Output range
0 to 10 V 0V FF38 to 00C8
–10 to 10 V 0V
1 to 5 V 1V
4 to 20 mA 4 mA
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down Bit
(bit 02 of word n+1).
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
99
Offset and Gain Adjustment Section 4-8
CONT B A B A C
SHIFT 1 0 1 0 2 MONTR
#
10102 c108
^OFF 0000
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
PLAY
10102 c108
SET
ON FFFF
REC
10102 c108
RESET
OFF FFFF
5. Check the 0V/1V/4mA output, and then turn bit 04 (the Set Bit) of IR word
n+1 ON and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
PLAY
10104 10102 c108
SET
ON ^ OFF FFFF
REC
10104 10102 c108
RESET
OFF ^ OFF FFFF
While the Offset Bit is ON, the offset value will be saved to the Unit’s EE-
PROM when the Set Bit turns ON.
6. To finish the offset adjustment, turn OFF bit 00 (the Offset Bit) of IR word
n+1.
CONT B A B A A
SHIFT 1 0 1 0 0 MONTR
#
10100 10104
^ ON ^OFF
PLAY
10100 10104
SET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
100
Offset and Gain Adjustment Section 4-8
Gain Adjustment The procedure for adjusting the analog output gain is explained below. As shown
in the following diagram, the set value is adjusted so that the analog output is
maximized (to 10V/5V/20mA).
10 V
0
0FA0
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 01 (the Gain Bit) of IR word n+1. (Hold the ON status.)
00000
CLR
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101
^OFF
PLAY
10101
SET
ON
Voltage output
A0
A1
Output 1
A2
A3
Current output
A0
A1
Output 1
A2
A3
101
Offset and Gain Adjustment Section 4-8
3. Monitor IR word n+8 and check the set value while the Gain Bit is ON.
00000
CLR
CH B A
SHIFT 1 0 8 MONTR
*
c108
0FA0
4. Change the set value so that the output voltage and output current are as
shown in the following table. The data can be set within the indicated
ranges.
Output signal range Output voltage/current Output range
0 to 10 V 10 V 0ED8 to 1068
–10 to 10 V 10 V 0708 to 0898
1 to 5 V 5V 0ED8 to 1068
4 to 20 mA 20 mA 0ED8 to 1068
Change the set value, using the Up Bit (bit 03 of word n+1) and the Down Bit
(bit 02 of word n+1).
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+1
CONT B A B A C
SHIFT 1 0 1 0 2 MONTR
#
10102 c108
^OFF 0FA0
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
PLAY
10102 c108
SET
ON 0F9F
REC
10102 c108
RESET
OFF 0F9F
102
Offset and Gain Adjustment Section 4-8
5. Check the 10V/5V/20mA output, and then turn bit 04 (the Set Bit) of IR word
n+1 ON and then OFF again.
CONT B A B A E
SHIFT 1 0 1 0 4 MONTR
#
PLAY
10104 10102 c108
SET
ON ^ OFF 0F9F
REC
10104 10102 c108
RESET
OFF ^ OFF 0F9F
While the Gain Bit is ON, the gain value will be saved to the Unit’s EEPROM
when the Set Bit turns ON.
6. To finish the gain adjustment, turn OFF bit 01 (the Gain Bit) of IR word n+1.
CONT B A B A B
SHIFT 1 0 1 0 1 MONTR
#
10101 10104
^ ON ^OFF
REC
10101 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Clearing Offset and Gain Follow the procedure outlined below to return the offset and gain adjusted val-
Adjusted Values ues to their default settings.
The following example uses output number 1 adjustment for illustration. (The
unit number is 0.)
1, 2, 3... 1. Turn ON bit 05 (the Clear Bit) of IR word n+1. (Hold the ON status.) Regard-
less of the set value, 0000 will be monitored in IR word n+8.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105
^OFF
PLAY
10105
SET
ON
103
Error Processing Section 4-9
10104 10105
^OFF ^ ON
PLAY
10104 10105
SET
ON ^ ON
REC
10104 10105
RESET
OFF ^ ON
While the Clear Bit is ON, the default offset and gain values will be saved to
the Unit’s EEPROM when the Set Bit turns ON.
3. To finish the clearing of adjusted values, turn OFF bit 05 (the Clear Bit) of IR
word n+1.
CONT B A B A F
SHIFT 1 0 1 0 5 MONTR
#
10105 10104
^ ON ^OFF
REC
10105 10104
RESET
OFF ^OFF
! Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
104
Error Processing Section 4-9
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word n+9
Note Disconnection detection (82) operates for input numbers used with a range of 1
V to 5 V (4 mA to 20 mA).
Errors indicated with 8j codes are automatically reset when proper counter-
measures are taken. The errors indicated with Fj codes are cleared when the
power is turned on after making the correct settings and when the Special I/O
Unit Restart Bit is turned OFF, ON, and OFF again.
105
Error Processing Section 4-9
Note SR bits 28210 to 28215 cannot be used with C200HE and C200HX/HG-
CPU3j-E/4j-E PCs.
106
Error Processing Section 4-9
There are two ways to restart Special I/O Unit operation after having changed
DM contents or having corrected the cause of an error. The first way is to power
up the PC again, and the second way is to turn the Special I/O Unit Restart Bit
ON and then OFF again.
Bits Functions
C200HX/HG/HE
C200H/HS
28100 AR 0100 Unit #0 Restart Bit Turning the Restart Bit
28101 AR 0101 Unit #1 Restart Bit for any Unit ON and
then OFF again
28102 AR 0102 Unit #2 Restart Bit restarts that Unit.
28103 AR 0103 Unit #3 Restart Bit
28104 AR 0104 Unit #4 Restart Bit
28105 AR 0105 Unit #5 Restart Bit
28106 AR 0106 Unit #6 Restart Bit
28107 AR 0107 Unit #7 Restart Bit
28108 AR 0108 Unit #8 Restart Bit
28109 AR 0109 Unit #9 Restart Bit
28110 (See note.) --- Unit #A Restart Bit
28111 (See note.) --- Unit #B Restart Bit
28112 (See note.) --- Unit #C Restart Bit
28113 (See note.) --- Unit #D Restart Bit
28114 (See note.) --- Unit #E Restart Bit
28115 (See note.) --- Unit #F Restart Bit
Note SR bits 28210 to 28215 cannot be used with C200HE and C200HX/HG-
CPU3j-E/4j-E PCs.
If the error is not cleared even after turning the Special I/O Unit Restart Bit ON
and then OFF again, then replace the Unit.
4-9-5 Troubleshooting
The following tables explain the probable causes of troubles that may occur, and
the countermeasures for dealing with them.
107
Error Processing Section 4-9
108
Appendix A
Dimensions
External Dimensions
Unit: mm
C200H-AD003
C200H-DA003
C200H-DA004
C200H-MAD01
100.7
130
34.5 126.2
109
Appendix B
Changes From Earlier Models
Scaling Function
The C200H-AD003 does not have this function, but an equivalent can be created using a ladder program. (Refer to
page 116, Sample Program 5: Scaling Function.)
Input Range
The voltage and current can be converted for up to ±5% of the full input range.
111
Changes From Earlier Models Appendix B
Error Codes
Error codes have been provided for the C200H-AD003. DM area setting errors and errors during operation are
stored in the IR area when the ERR indicator lights. (Refer to 2-7-2 Errors Detected by Analog Input Unit.)
Output Range
The voltage and current can be converted for up to ±5% of the full output range.
Error Codes
Error codes have been provided for the C200H-DA003/004. DM area setting errors and errors during operation
are stored in the IR area when the ERR indicator lights. (Refer to 3-7-2 Errors Detected by Analog Output Unit.)
112
Appendix C
Sample Programs
Sample Program 1:
Obtaining Analog Input Unit Conversion Values
This is a program for obtaining the Analog Input Unit’s conversion values. Individual input values are obtained by
MOV(21) when their Disconnection Detection Flags turn OFF. (With the C200H-AD003, there are no causes for
errors in normal mode other than disconnections, so a disconnection can be determined merely by seeing that bit
15 of word 109 is ON.)
Unit Settings
Item Setting contents Actual settings
Unit C200H-AD003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Inputs 1 to 8 used --- DM 1000 = 00FF
Input signal range All input numbers, 1 to 5 V DM 1001 = AAAA
Program Example
10900
MOV(21)
101 Conversion value
DM0000
10901
MOV(21)
102 Conversion value
DM0001
10907
MOV(21)
108 Conversion value
DM0007
113
Sample Programs Appendix C
Program Example
Execution condition
MOV(21)
DM0000 Set value
101
Upper limit
Lower limit
ON
Alarm Flag
OFF
Unit Settings
When using the upper- or lower-limit alarm for input conversion values:
Item Setting contents Actual settings
Unit C200H-AD003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Input 1 used --- DM 1000 = 0001
Input signal range Input number 1, 0 to 10 V DM 1001 = 0001
When using the upper- or lower-limit alarm for output set values:
Item Setting contents Actual settings
Unit C200H-DA003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Output 1 used --- DM 1000 = 0001
Output signal range Output number 1, 0 to 10 V DM 1001 = 0001
114
Sample Programs Appendix C
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
Operation condition
ZCP(88)
101 Conversion value
DM0000 Lower limit (16-bit binary)
DM0001 Upper limit (16-bit binary)
25506(=) 25503((ERR)
Alarm Flag
Upper limit
Lower limit
ON
Alarm Flag
OFF
Unit Settings
Item Setting contents Actual settings
Unit C200H-AD003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Input 1 used --- DM 1000 = 0001
Input signal range Input number 1, 0 to 10 V DM 1001 = 0001
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
Execution condition
ZCP(88)
101 Conversion value
DM0000 Lower limit (16-bit binary)
DM0001 Upper limit (16-bit binary)
02001 25506(=) 25503((ERR)
Alarm Flag
115
Sample Programs Appendix C
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
• Data Flow (Unit Number 0): Word 101 → Word 200 (scaling result)
Execution condition
ADB(50)
Conversion value +
101 Negative number
(1)
DM0000
DM0001
SCL(––)
Conversion is executed
DM0001
using augmented value. (2)
DM0002 Result is output to word
200 200.
1, 2, 3...
1. Negative numbers cannot be used as conversion values with the SCL in-
struction, so the negative portion (0 V–5%, 1 V–5%, 4 mA–5%) is aug-
mented.
2. The lower limit (FF38) to upper limit (1068) range is scaled to a range of 0 to
4400 BCD, and output to word 200.
DM Area Setting Value for All Input Signal Ranges
Input Signal Range: 0 to 10 V / 1 to 5 V / 4 to 20 mA
The following shows a case where conversion data (full-scale) for the input signal range of 0 to 10 V is scaled to a
range of 0 to to 4400 BCD.
• Data Flow (0 to 10 V range)
Word 101 value Program (1) Program (2) Final
0200
00C8(BIN) 0200(BCD)
0.0 V 0000(BIN) 0000(BIN) 0000(BCD) –0.5 V (FF38) 10.5 V (1068)
–0.5 V FF38(BIN)
116
Sample Programs Appendix C
• DM Area Setting
1130(BIN) 4400(BCD)
1068(BIN) 4200(BCD) 4400
–10 V F830(BIN)
–11 V F768(BIN)
Note The following shows a case where conversion data (full-scale) for the input range of 0 to 10 V is scaled to a
range of 100 to to 500 BCD.
• Data Flow (0 to 10 V range)
120
00C8(BIN) 120(BCD)
0.0 V 0000(BIN) 0000(BIN) 100(BCD) –0.5 V (FF38) 10.5 V (1068)
–0.5 V FF38(BIN)
117
Sample Programs Appendix C
• DM Area Setting
00002000 00004200
–10 V (F830)
10 V (07D0)
–0.5 V (FF38)
F0002000 F0002000 10.5 V (1068)
Unit Settings
Item Setting contents Actual settings
Unit C200H-AD003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Input 1 used --- DM 1000 = 0001
Input signal range Input number 1, 0 to 10 V DM 1001 = 0001
118
Sample Programs Appendix C
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
• Data Flow (Unit Number 0):
Word 101 (AD Conversion Value) → Words 201 and 202 (Conversion Results)
Execution condition
MOV(21)
101 16-bit binary data
DM0000
MOV(21)
#0000
Clears leftmost word to 0000
DM0001
ANDW(34)
#8000
DM0000
(1)
DM0002
25503((ERR) 25506(=)
NEG
DM0000
Reverses leftmost bit if it is not 0.
DM0000
MOV(21)
#F000 Reverses leftmost word to
F000 if it is not 0.
DM0001
BCD(24)
DM0000 (2)
Converts to BCD.
DM0000
XFER(70)
#0002
Outputs BCD data with sign to (3)
DM0000 words 200 and 201.
200
1, 2, 3... 1. If the leftmost bit is a 1 (negative number) in 16-bit binary data, the data is
reversed.
2. 16-bit binary data is converted to BCD.
3. BCD data with sign is output to words 200 and 201.
119
Sample Programs Appendix C
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
• Data Flow (Unit Number 0): Word 101 (AD Conversion Value) → Word 200 (Calculation Result)
Execution condition
ADB(50)
Conversion value +
101 (1)
Negative number
DM0000
DM0001
SCL(––)
DM0001 Scaling is executed using
augmented value. Result is (2)
DM0002
output to word DM 0006.
DM0006
MUL(32)
DM0006 Result of step #2 (above)
is multiplied by 4400. (3)
#4400
DM0006
ROOT(72)
Square root is calculated, and
DM0006 result is output to word 200. (4)
200
1, 2, 3... 1. The negative number portion is added to the conversion value (word 101).
2. The binary data is scaled to a range of 0 to 4400.
3. The scaling results are multiplied by 4400.
4. The square root is calculated, and the result is output to word 200.
DM Area Settings
Input signal range: 0 to 10 V / 1 to 5 V / 4 to 20 mA
If the result of the binary-to-BCD conversion is negative, an error will be generated by the ROOT(72) instruction.
With a signal range of –10 to 10 V, scaling is executed by augmenting the negative portion (–10 V–5%). In this
program example, the value of DM 0000 is converted to 0898. Refer to page 116.
120
Sample Programs Appendix C
Program Example
The following program can be executed only with the C200HS, C200HX/HG/HE CPU Units.
• Data Flow (Unit Number 0): Word 101 (AD Conversion Value) → DM 0001 (Mean Value Result)
Execution condition
AVG
#101 Conversion value
#0064 Number of samplings
DM0001 Mean value
The number of samplings will be no more than 64 when the AVG instruction is used.
5 V (03E8)
Set value
0 V (0000)
Actual output value
Unit Settings
Item Setting contents Actual settings
Unit C200H-DA003 ---
Unit number #0 Unit number switch: 0
Operation mode Normal mode Back-panel DIP switch: All OFF
Output 1 used --- DM 1000 = 0001
Output signal range All output numbers, –10 to 10 V DM 1001 = 0000
Output hold function HOLD DM 1002 = 0001
Program Example
Execution condition
MOV(21)
DM0000 Set value
101
ZCP(88)
101
DM Area Settings
121
Appendix D
Data Memory Coding Sheet
C200H-AD003
Setting contents
DM word
15 8 7 0
DM jj00
DM jj01
DM jj02
DM jj03
DM jj04
DM jj05
DM jj06
DM jj07
DM jj08
DM jj09
122
Data Memory Coding Sheet Appendix D
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
m+3 Input 2: Mean value processing setting
0: Do not use.
m+4 Input 3: Mean value processing setting 1: Use.
m+5 Input 4: Mean value processing setting Input Signal Range Setting
07 06 05 04 03 02 01 00
m+6 Input 5: Mean value processing setting
Input 4
Input 3
Input 2
Input 1
m+8 Input 7: Mean value processing setting
15 14 13 12 11 10 09 08
m+9 Input 8: Mean value processing setting
Input 8
Input 7
Input 6
Input 5
00: -10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: Same as 10 above
123
Data Memory Coding Sheet Appendix D
C200H-DA003/DA004
Setting contents
DM word
15 8 7 0
DM jj00
DM jj01
DM jj02
DM jj03
DM jj04
DM jj05
DM jj06
DM jj07
DM jj08
DM jj09
124
Data Memory Coding Sheet Appendix D
Output 1: Output
m+2 status when con-
version stopped
Output 8
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
Output 1
Output 2: Output
m+3 status when con-
version stopped
Output 3: Output
m+4 status when con- 0: Do not use.
version stopped 1: Use.
Output 4: Output
m+5 status when con-
version stopped Signal Range Setting (Not Valid for C200H-DA004)
Output 5: Output
m+6 status when con- 07 06 05 04 03 02 01 00
version stopped
Output 6: Output
m+7 status when con-
version stopped
Output 7: Output
Output 4
Output 3
Output 2
Output 1
m+8 status when con-
version stopped
Output 8: Output
m+9 status when con-
version stopped
15 14 13 12 11 10 09 08
Output 8
Output 7
Output 6
Output 5
00: -10 to 10 V
01: 0 to 10 V
10: 1 to 5 V / 4 to 20 mA
11: Same as 10 above
163 162
125
Data Memory Coding Sheet Appendix D
C200H-MAD01
Setting contents
DM word
15 8 7 0
DM jj00
DM jj01
DM jj02
DM jj03
DM jj04
DM jj05
DM jj06
DM jj07
DM jj08
DM jj09
DM jj10
DM jj11
DM jj12
DM jj13
126
Data Memory Coding Sheet Appendix D
Use Designation
07 06 05 04 03 02 01 00
Input 2
Input 1
Output 2
Output 1
15 8 7 0 0: Do not use.
1: Use
Loop use Input use Output use
m designation designation designation
Loop 2
Loop 1
Output 2: Output status 00: Do not use.
m+3 when conversion stopped
01: Positive gradient conversion
10: Negative gradient conversion
m+4 11: Do not use.
m+5
Signal Range Setting
m+6 Input 1: Mean value processing setting 07 06 05 04 03 02 01 00
Output 2
Output 1
m+8
m+9
15 14 13 12 11 10 09 08
Input 2
Input 1
00: -10 to 10 V
01: 0 to 10 V
m+12 Loop 2 (input 2 → output 2), A constant 10: 1 to 5 V / 4 to 20 mA
11: Same as 10 above
163 162
127
Index
D
B differences, from earlier models, 113
dimensions, external, 111
B constant, 91
DM area, unit number setting, 7
C200H-MAD01, DM set value, 80
C200H-AD003, 13
bias, 91 C200H-DA003, 41
C200H-DA004, 41
binary to BCD, conversion program, 120
C200H-MAD01, 71
DM area allocation
C200H-AD003, 20
C set and stored values, 21
C200H-DA003, 49
circuits set and stored values, 50
C200H-AD003, 15 C200H-DA004, 49
C200H-DA003, 43 set and stored values, 50
C200H-DA004, 43 C200H-MAD01, 79
current output, C200H-MAD01, 73 set and stored values, 80
input, C200H-MAD01, 72 DM coding sheets
voltage output, C200H-MAD01, 73 C200H-AD003, 124
Clear Bit C200H-DA003, 126
C200H-AD003, IR set value, 19 C200H-DA004, 126
C200H-DA003, IR set value, 48 C200H-MAD01, 128
C200H-DA004, IR set value, 48 Down Bit
C200H-MAD01, IR set value, 78 C200H-DA003, IR set value, 48
conversion programs C200H-DA004, IR set value, 48
binary to BCD, 120 C200H-MAD01, IR set value, 78
mean value processing, 122
scaling, 118
square root, 121 E
upper- and lower-limit alarm, 116 error codes
conversion values C200H-AD003, 33
C200H-AD003 IR adjustment mode stored value, 19
IR adjustment mode stored value, 19 IR normal mode stored value, 18
IR normal mode stored value, 18 C200H-DA003, 62
reading, 22 IR adjustment mode stored value, 48
C200H-DA003, 52 IR normal mode stored value, 47
IR adjustment mode stored value, 48 C200H-DA004, 62
IR normal mode set value, 47 IR adjustment mode stored value, 48
C200H-DA004, 52 IR normal mode stored value, 47
IR adjustment mode stored value, 48 C200H-MAD01, 106
IR normal mode set value, 47 IR adjustment mode stored value, 78
C200H-MAD01, 88 IR normal mode stored value, 77
IR adjustment mode stored value, 78 errors
IR normal mode set value for output, 77 C200H-DA003, setting, 47, 53
IR normal mode stored value for input, 77 C200H-DA004, setting, 47, 53
reading, 82 C200H-MAD01, setting, 77, 89
129
Index
130
Index
131
Index
132
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
133