Electrical Standards and Practices PART 1 PEC
Electrical Standards and Practices PART 1 PEC
Electrical Standards and Practices PART 1 PEC
Note: PEC consists of rules which are intended to make use of electricity safe for
person and property.
OBJECTIVES:
a) Safe Use of Electricity - To establish basic materials quality and electrical work
standards for the safe use of electricity for light, heat, power, communications,
signaling and for other purposes.
b) Adequacy – Strict compliance with the provisions of this Code will ensure safety
in electrical installation and construction, but not necessarily efficient, convenient, or
adequate for good service or future expansion of electrical use.
THE USE OF PEC IS MANDATED BY R.A. 7920 ( FORMERLY R.A. 184 ), ALSO KNOWN
AS THE NEW ELECTRICAL ENGINEERING LAW. LIKEWISE, REFERRAL CODES ARE
ALSO USED WHICH ARE MANDATED BY THEIR CORRESPONDING LAWS.
1. P.D. 1096 – National Building Code
2. P.D. 1185 – Fire Code of the Philippines
3. Structural Code R.A. 7920 – is an act providing for a more responsive and
comprehensive regulation for the practice, licensing and registration of electrical
engineers and electricians.
GOVERNMENT AUTHORITIES WHO IMPLEMENT PEC:
1. Office of the Building Official
2. Office of the City Electrician (City Electrical Supervising Engineer )
3. Office of the Municipal Electrician (Municipal Electrical Supervising Engineer)
4. Regional Office of the DOLE
EXCEPTIONS
A permit is not required for;
1. the installation of electrical portable equipment rated not more than 1,200
VA.
2. reconnection of disconnected service due to non-payment of electric bill or
change of occupants for a period of one year.
INSULATION
Service-lateral conductor shall withstand exposure to atmospheric and other
conditions of use without detrimental leakage of current.
EXCEPTION:
A grounded conductor shall be permitted to be uninsulated as follows:
a) Bare copper used in a raceway.
b) Bare copper for direct burial where bare copper is judged to be suitable for
the soil conditions.
c) Bare copper for direct burial without regard to soil conditions where part of
cable assembly identified for underground use.
d) Aluminum or copper-clad aluminum without insulation or covering where
part of a cable assembly identified for underground use in a raceway or for
direct burial.
Note: Where two to six service disconnecting means in separate enclosures supply
separate loads from one service drop or lateral, one set of service entrance
conductors shall be permitted to supply each or several such service equipment
enclosures.
EXCEPTION:
– For installations to supply only limited loads of a single branch circuit such
as small polyphase power, controlled water heaters and the like, they shall
not be smaller than 3.5 mm2 copper or 5.0 mm2aluminum or copper-clad
aluminum.
SERVICE ENTRANCE
– Service is defined as the portion of the supply which extends from the street
main duct or transformer to the service switch or switchboard of the building
supply.
-It is the conductor and equipment for delivering energy from the electricity
supply system to the wiring system of the premises served.
TYPES:
1. Overhead Service Entrance
The most common type of service entrance employed by the power companies
supplying electricity which is either a 2, 3 or 4-wire connection. Generally, the
overhead service cable between the building property line and the supply point is
supplied by electric company to a limit of 30 meters.
EXCEPTIONS:
1. Buildings with more than one occupancy.
2. Where two to six service disconnecting means in a separate enclosures
are grouped at one location and supply separate loads from one service drop
or lateral.
SIZE AND RATING:
– Service entrance conductors shall be of sufficient size to carry the computed loads.
Ungrounded conductors shall not be smaller than:
1. 100 A —- For one family dwelling with six or more 2-wire branch circuits.
2. 60 A —- For one family dwelling with an initial computed load of 10 kVA
above.
3. 40 A —- For other loads.
EXCEPTIONS:
1. For loads consisting of not more than 2 – wire branch circuits, 5.5 mm2copper or
8.0 mm2 aluminum or copper-clad aluminum.
2. By special permission, for loads limited by demand or by the source of supply, 5.5
mm2 copper or 8.0 mm2 aluminum or copper-clad aluminum.
3. For limited loads of single branch circuit, 3.5 mm2 copper or 5.5 mm2aluminum or
copper-clad aluminum.
PROTECTION:
Service entrance conductors subjected to physical damage shall be protected in any
of the following ways or methods:
1. By RMC
2. By IMC
3. By RNMC suitable for the location
4. By EMT
5. Type MC cable or other approved means
NOTE:
The service disconnecting means shall simultaneously disconnect all
ungrounded conductors and shall be capable of being closed on a fault
equal to or greater than the maximum available short-circuit current.
EXAMPLE :
1. Works here under shall comply with the latest edition of the P.E.C, the
national building code, municipal or city ordinances, office of the municipal or
city electrician, & Meralco.
2. Type of services shall be 230 volts, 1 phase, 2 wire system, 60 hertz and
there shall be only one service drop to the building.
3. Method of wiring shall be EMT both exposed and embedded work with
proper fitting and supports. In cases where concealed conduits wiring is
impracticable to use, metal moulding may be applied.
4. All materials and equipment shall be new and approved type for both
location and purpose intended.
5. All lighting and convenience outlet circuit homeruns shall be wired with no
less than 2 sq. mm and 3.5 sq. mm respectively, unless otherwise indicated
on the plan.
6. Lighting and power panel board shall be circuit breaker type surface or
flushed mounted or as indicated on the plan; door shall be provided with
locked and milled key, a line circuit directory card and holder shall be
provided in innerface or door.
7. Whenever required and necessary, full boxes and junction boxes of proper
sizes shall be installed at convenient and inconspicuous locations although
such boxes are not shown on the plans nor mentioned in the specification.
8. All outdoor installation shall be weather proof type.
9. All electrical work shall be done under the direct and immediate supervision
of a duly
licensed Electrical Engineer.
C. LOCATION PLAN
Location or site plan with proposed structures and owner’s land drawn to appropriate
metric scale shall show:
1. Bordering areas showing public or well known streets.
2. Location of service drop, service equipment and nearest pole of the utility
company furnishing electrical energy.
3. Clearance of the path or run of service drops and service structure wires to
adjacent existing or proposed structures.
D. RISER DIAGRAM
The riser diagram consists of the schematic diagram of service entrance, feeders and
branch circuits. This indicates:
1. The number of branch circuits, the size of conductors, size of conduit and
protection for each branch circuit.
2. The sizes of feeders, its conduit and feeder’s protection.
3. The type of service, size of service entrance conductor, conduits and main
protective device.
E. TITLE BLOCK:
Title block or nameplate of plans and drawings shall be a standard strip of 40 mm
high at the bottom of each sheet.
a. MOTOR LOADS:
1. Motor as numbered or identified in power layout.
2. Type of motor
3. HP/kW/kVA rating
4. Voltage rating
5. Full load current rating
6. Frequency rating
7. Number of phases
c. OTHER LOADS
1. Designation number on plan
2. Description loads
3. Classification of service duty
4. Rating in kilovolt ampere (KVA) or kilowatt (KW)
5. Phase loading indicating full load line current
6. Voltage rating
H. DESIGN COMPUTATION
Or design analysis where necessary shall be included on the drawings or may be
submitted on separate sheets of uniform size paper, shall allow :
1. Illumination design computations and tabulated lighting levels in lux critical
areas in institutional, Industrial recreational & commercial building.
2. Feed lines and protective devices of motors, electrical equipment and
appliances indicating types and ratings.
3. Sizes of branch circuit wires, Feeders and busbars including protective
devices.
4. Size and type of service entrance wires, race ways and equipment.
5. Setting / ratingsof over current devices.
GROUNDING PROTECTION
A ground is an electrical connection which may either be intentional or
accidental between an electric circuit or equipment and the earth, or to some
conducting body that serves in place of the earth. The purpose of grounding a
circuit is to fix permanently a zero voltage point in the system. The grounded
line of a circuit should not be broken nor fused to maintain a solid and
uninterrupted connection to the ground.
THE PANELBOARD
A panelboard is a single panel or group of panel units designed for assembly
in the form of a single panel. This includes buses, automatic overcurrent
protective devices, and with or without switches for the control of light, heat or
power circuit. It is designed to be placed in a cabinet or cutout box placed in or
against a wall or partition and accessible only from the front.
MAIN- is the feeder interior wiring extending from service switch, generator bus, or
converter bus to the main distribution.
BRANCH CIRCUIT- is defined as the circuit conductors between the final overcurrent device
protecting the circuit and the outlets. This means that the branch circuit is only the wiring
between the circuit overcurrent protection device such as fuses or circuit breaker and the
outlets. However, it is a common knowledge and practice that the branch circuit comprises
the entire circuit including the outlet receptacles and other wiring devices.
A fuse is also an overcurrent protective device with a circuit opening fusible element
which opens when there is an overcurrent in the circuit. It is considered as the
simplest and the most common circuit protective device used into the house wiring
connection.
Exception:
Circuit breakers or fuses, factory assembled in parallel, and approved as a unit.
Position of Knife Switches
a) Single-throw Knife Switches. Single-throw knife switches shall be so
placed that gravity will not tend to close them. Single-throw knife switches,
approved for use in the inverted position, shall be provided with a locking
device that will ensure that the blades remain in the open position when so
set.
b) Double-throw Knife Switches. Double-throw knife switches shall be
permitted to be mounted so that the throw will be either vertical or horizontal.
Where the throw is vertical, a locking device shall be provided to hold the
blades in the open position when so set.
Stranded wire – consists of a group of wires twisted to form metallic string. The total
circular-mil area of a stranded wire is found by multiplying the circular mil area of
each strand by the total number of strand.
CIRCULAR MIL. This is the unit of cross section in the American wire gauge. The term “mil”
means one-thousandth of an inch (0.001 in.). It is the area of a circular wire having a
diameter of one mil. To find the number of circular mils in a circle of a given diameter, we
have to square the number of mils in the diameter.
SQUARE MIL. It is the area of a square having its side equal to 1 mil.
Square mil = ( sides )2 = ( 1 mil )2 = ( 0.001 in.)2 = 1 x 10-6 in.2
Square mil = 0.7854 x circular mils
4. Nonmetallic Sheathed CableTypes NM and NMC are factory assembled two or more
insulated conductors having a moisture-resistant outer sheath, flame-retardant and non-
metallic material. These types are used specifically for one or two dwelling not exceeding 3
storey buildings.
5. Shielded Nonmetallic Sheathed Cable. This type of cable, the type SNM, is a factory
assembly of two or more insulated conductors in an extruded core or moisture-resistant and
flame-retardant material, covered with an overlapping spiral metal tape. This type is used in
hazardous locations and in cable trays or in raceways.
7. Underground Feeder and Brach Circuit Cables. This type of cable, the type UF cable is
a moisture-resistant cable used for underground, including direct burial in the ground, as
feeder or branch circuit.
8. Power and Control Tray Cable. Type TC cable is a factory assembly of two or more
insulated conductors with or without associated bare or covered grounding under a metallic
sheath. This is used for installation in cable trays, raceways or where supported by a
messenger wire.
9. Flat Cable Assemblies. This is an assembly of parallel conductors formed integrally with
an insulating material web designed specifically for field installation in metal surface
raceway. Cables of this type are the types FC.
10. Flat Conductor Cable. This type of cable, type FCC consists of three or more flat
conductors placed edge to edge, separated and enclosed within an insulating assembly.
This used for general purpose, appliance branch circuits and for individual branch circuits
specifically on hard, smooth, continuous floor surfaces, etc.
RACEWAYS
Raceways are channels designed for holding wires, cables or bus-bars, which are either
made of metal or insulating materials. The common types of raceways in household wiring
are the a) conduits, b) connectors, and c) others.
a) Conduits
Conduits, pipes or tubings are the most common electrical raceway.
According to the type of materials used, conduit maybe classified as either metallic
such as steel pipes or nonmetallic such as PVC, and the like. According to its make,
conduits maybe classified as: rigid metal, flexible metal, rigid nonmetal and flexible
nonmetal.
b) Connectors
A connector is a metal sleeve usually made of copper that is slipped over and
secured to the butted ends of conductors in making joint. A connector is also called a
splicing sleeve.
c) Other Raceways
Aside from the conduits and connectors there are still numerous types and kinds of
raceways, among these are the a) conduit couplings, elbows and other fittings; b)
conduit supports, such as clamps, hangers,etc; c) cable trays, cablebus; d) metal
raceways;e) nonmetal raceways.
TYPES OF WIRES
C. TYPE XHHW
In appearance, it resembles Types T, TW, THW but because of somewhat thinner
layer of insulation, the over-all diameter is smaller. The insulation is “cross-linked
synthetic polymer,” which has an extraordinary properties as to insulating value, heat
resistance, and moisture resistance. It may be used in dry or wet locations. While at
present, it is an expensive wire, it would be no surprise if in due course of time, this
one single type will replace all the many types and subtypes of Type T or R now
recognized by the Code.
D. RUBBER-COVERED WIRE
It consists of copper conductor, tinned to make it easier to remove the insulation, and
for easy
soldering. Over the copper is a layer of rubber, the thickness of which depends on
the size of the wire.
Then follows an outer fabric braid which is saturated with moisture-and-fire-resistant
compounds; if it is
set on fire with a blowtorch, the flame dies out when the torch is removed.
E. OTHER TYPES
Other types such as the basic Type R, which is suitable for only in dry locations, is no
longer being made.
The most ordinary kind is Type RHW, which may be used for dry or wet locations.
Types RH and RHH have insulation which withstands more heat and therefore have
a higher ampacity in the larger size. They may be used only in dry locations.
KINDS OF LOCATIONS
DAMP LOCATION
Partially protected locations under canopies, marquees, roofed open porches, and
like locations, and interior locations subjected to moderate degree of moisture, such
as some basements, some barns, and some cold-storage warehouses.
DRY LOCATION
A location not normally subject to dampness or wetness. A location classified as dry may be
temporarily subject to dampness or wetness, as in the case of a building under construction.
WET LOCATION
Installations underground or in concrete slabs or masonry in direct contact with the earth,
and location subject to saturation with water or other liquids, such as vehicle washing areas,
and locations exposed to weather and unprotected.
1. Class I Locations. Class I locations are those in which flammable gases or vapors are or
may be present in the air in quantities sufficient to produce explosive or ignitible mixtures.
2. Class II Locations. Class II locations are those that are hazardous because of the
presence of combustible dust.
b) Class II, Division 2. A Class II, Division 2 location is a location where combustible
dust is not normally in the air in quantities sufficient to produce explosive or ignitible
mixtures, and dust accumulations are normally insufficient to interfere with the normal
operation of electrical equipment or other apparatus, but combustible dust may be in
suspension in the air as a result of infrequent malfunctioning of handling or
processing equipment and where combustible dust accumulations on, in, or in the
vicinity of the electrical equipment may be sufficient to interfere with the safe
dissipation of heat from electrical equipment or may be ignitible by abnormal
operation or failure of electrical equipment.
3. Class III Locations. Class III locations are those that are hazardous because of the
presence of easily combustible fibers or flyings, but in which such fibers or flyings are not
likely to be in suspension in the air in quantities sufficient to produce ignitible mixtures.
a) Class III, Division 1. A Class III, Divisions 1 location is a location in which easily
ignitible fibers or materials producing combustible flyings are handled, manufactured,
or used.
b) Class III, Division 2. A Class III, Division 2 location is a location in which easily
ignitible fibers are stored or handled.
Researched by: