Strobe Lamp
Strobe Lamp
Strobe Lamp
2
UL Current Draw Data
Table 3 lists the maximum UL Current Draw (mA RMS) allowed for Wall Horn Strobes.
8–17.5 16–33
Volts Volts
Switch Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
9* (See Note) Coded High 85 90 90
10* (See Note) 3.1 KHz Coded High 84 89 89
Note: Settings 9 and 10 are not available on 2-Wire horns and strobes.
Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains
constantly on.
Table 4: Horn Strobe Tones and Sound Output Data
3
L-Series Dimensions
1.91" 3.46"
48.5 mm 88 mm
1.25"
32 mm
3.57" 1.55"
3.46"
88 mm
1.25" (9.1 cm) (3.9 cm)
32 mm
5.38"
5.27" 5.27"
133.9 mm 133.9 mm (13.7 cm)
Figure 1 Compact Strobe, Horn Strobe Figure 2 Compact Horn Figure 3 Compact Wall Surface Mount
Backbox (SBBGRL, SBBGWL)
1.91"
(4.85 cm)
4.7" 1.25" 4.82" 1.85"
4.70"
1.25" (119 mm) (32 mm) (12.24 cm) (4.69 cm)
(11.94 cm)
(3.18 mm)
5.78"
5.67" 5.67" (14.68 cm)
(14.4 cm)
(144 mm)
Figure 4 Strobe, Horn Strobe Figure 5 Horn Figure 6 Wall Surface Mount Backbox
(SBBRL/SBBWL)
L-Series Ordering Information L-Series Ordering Information
Wall Strobes: HRL*: Horn, Red
SRL: Strobe, Red HWL*: Horn, White
SWL: Strobe, White HGRL*: Compact Horn, Red
SGRL: Compact Strobe, Red HGWL*: Compact Horn, White
SGWL: Compact Strobe, White Note: Horn-only models are listed for wall or ceiling use.
SRL-P: Strobe, Red, Plain Accessories:
SWL-P: Strobe, White, Plain TR-2: Universal Wall Trim Ring Red
SWL-CLR-ALERT: Strobe, White, ALERT TR-2W: Universal Wall Trim Ring White
Notes: SBBRL: Wall Surface Mount Back Box, Red
All -P models have a plain housing (no “FIRE” marking on SBBWL: Wall Surface Mount Back Box, White
cover).
SBBGRL: Compact Wall Surface Mount Backbox, Red
All -SP models have “FUEGO” marking on cover.
SBBGWL: Compact Wall Surface Mount Backbox, White
All -ALERT models have “ALERT” marking on cover.
4
L-Series, Indoor Strobes and Horn Strobes Technical Specifications
SYSTEMS STANDARDS For a complete listing of all
compliance approvals and
Temperature Ranges: The L-Series, Ceiling Strobes and Horn Strobes are certifications, please visit:
Standard Operating Temperature: 32°F to 120°F (0°C designed to comply with the following standard: http://www.gamewell-
to 49°C) UL Standard: UL 1971 and UL 464 fci.com/en-US/
Humidity Range: 10 to 93% non-condensing documentation/Pages/
AGENCY LISTINGS AND APPROVALS Listings.aspx
Voltages:
Strobe Flash Rate: 1 flash per second These listings and approvals apply to the modules E3 Series® and Gamewell-FCI®
Nominal Voltage: Regulated 12 VDC or regulated 24 specified in this document. In some cases, certain are registered trademarks of
modules or applications may not be listed by certain Honeywell International Inc.
DC/FWR1
approval agencies, or listing may be in process.
Operating Voltage Range2: 8 to 17.5 V (12 V nominal) Consult factory for latest listing status. UL® is a registered trademark
or 16 to 33 V (24 V nominal) of Underwriter’s Laboratories
UL: S5512, S4011 Inc.
Operating Voltage Range (MDL3): 8.5 to 17.5V(12 V CSFM: 7135-1653:0503
nominal) or 16.5 to 33 V(24V nominal) This document is not intended
7125-1653:0504
Wire Gage: to be used for installation
ISO 9001 Certification purposes. We try to keep our
Input Terminal Wire Gauge: 12 to 18 AWG
product information up-to-
Dimensions: date and accurate. We cannot
Wall-Mount Dimensions (including lens): cover all specific applications
5.6”L x 4.7”W x 1.91”D or anticipate all requirements.
(143 mm L x 119 mm W x 49 mm D) All specifications are subject to
change without notice.
Compact Wall-Mount Dimensions (including lens):
5.26” L x 3.46” W x 1.91” D
(133 mm L x 88 mm W x 49 mm D)
Horn Dimensions:
5.6” L x 4.7” W x 1.25” D
(143 mm L x 119 mm W x 32 mm D)
Compact Horn Dimensions:
5.25” L x 3.45” W x 1.25” D
(133 mm L x 88 mm W x 32 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-
regulated, time-varying power source that is
used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V
nominal only for 15 and 30 cd.
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161 9021-60929 | D | 02/19