Protective Relays
Protective Relays
Protective Relays
• The relays are in series on the third core and it can be seen from
the diagram that under healthy or external fault conditions the
two ends of the third core cable will be at the same potential and
therefore will be no operating current in the relays. However,
under the fault conditions between the CTs, the current at one
end either changes in direction or become larger than other end
and thus producing the voltage across the ends of the third core
and operating current in the relays.
3. Unit Protection Scheme applied to Generator
The relay consists of two restraining coil and one operating coil per
phase. The torque produced by the operating coil, which tends to
close the relay contacts is opposed by the restraining coil torque.
Under through-fault condition i.e. external faults outside the
protected zone, the relay setting is increased by the restraining coil
torque so that spill current will not cause relay operation. However
for in-zone faults, the torque produced by the restraining coil is
ineffective and the relay close its contacts by the torque produced
by the operating coil.
Numerical related to bias protection of
Transformers
1. A 3-phase 33000/6600 V transformer is connected in star/delta
and the protecting current transformer on low voltage side have a
ratio of 300/5. What will be the ratio of the current transformer
on the high voltage side?
2. A 3-phase, 200MVA, 11/0.4 KV transformer is connected in
delta /star. The protection transformer on the o.4 KV side has
the turn ratio of 500/5. What will be the CT ratio on HV side?
Voltage Balance Relay
• The relays are connected in series opposition with pilot wires one
at each end.
•The relative polarities of CT’s are such that no current flows in the
pilot wires under normal conditions and external fault.
•The voltage induced in secondary's of CT must be proportional to
primary current even under fault conditions. This can be achieved
by using air cored CT’s.
• For internal faults, the voltages of secondary of CT’s are different
and hence the current passes through relay coils and operates the
Relay.
• To avoid mal operation due to mismatch in characteristics of CT’s,
the relays are over current type and operate when the current
crosses the threshold value.
• In this system no restraining coil and balancing resistors are
required.
• Only disadvantage of this scheme is: As CT’s do not carry any
secondary current, acts as open circuited secondary and inserts a
high impedance to the circuit.
Comparison between Current Differential and
Voltage Differential Protection
• Current differential relays are convenient when both ends of
the protected element are close together. Ex: Generator,
Motor, Transformers, Bus-bars.
• For feeder protection of several Km long, secondary current of
greater or equal to 5A flows through the pilot wires of high
resistance. This burden is impractical for any economic design
of C.T.
Universal Relay Torque Equation
• Protection relay mostly consist of some arrangement of
electromagnets. These electromagnet have either current winding
or voltage winding and in some cases both the winding. Current
through the winding produces magnetic fluxes and the torque is
produced by interaction between the fluxes of the same winding
or between the fluxes of both the winding.
• By assigning plus or minus signs to certain of the constants
and letting others to zero and sometimes by adding other
similar terms the operating characteristics of all types of
protective relay can be obtained.
Distance Relay Protection
• Distance protection is the name given to the protection, whose
action depends upon the distance of the feeding point to the fault.
The time of operation of such protection is a function of ratio of
voltage and current i.e. impedance. This impedance between the
relay and fault depends upon the electrical distance between
them. Principle types of distance relays are impedance relays,
reactance relays & admittance or mho relays.
A) Impedance type distance relay
• An impedance relay is a voltage restrained over current relay. The
relay measures impedance up to the point of fault and gives
tripping command if this impedance is less than the relay setting Z.
Relay setting Z is known as replica impedance and is proportional
to the set impedance i.e. impedance up to the reach of relay. The
relay monitors continuously the line current I through CT and the
bus voltage through PT and operates when the V/I ratio falls below
the set value
The principle of operation is illustrated in figure. The voltage
element of relay is excited through a PT from the line under
protection and current element of relay is excited from a current
transformer (CT) in series with the line. The portion AB is the
protected zone. Under normal operating condition the impedance
of protected line is Z. The impedance, ratio of the bus voltage and
fault current (V/I), between the point where the relay is located and
point of fault will be less than Z in case of F1 so the relay operates.
But in case of F2, the V/I will be more than Z, so relay contacts don’t
operate.
• The impedance relay is a double actuating quantity relay and
essentially consists of two elements current operated and voltage
operated. The current element produces a positive or pick-up
torque while the voltage elements develops a negative or reset
torque.
• Taking effect of spring, the torque equation becomes: