The document provides calculations to determine the cooling tower capacity in tons (TR) for a system with a water flow rate of 225 cubic meters per hour, an inlet water temperature of 37°C, an outlet water temperature of 32°C, and ambient wet-bulb temperature of 29°C. Using the given values for water density, specific heat of water, and flow rate difference in temperature, the cooling tower capacity is calculated to be 369.0476 TR with a 20% excess capacity of 442.8571 TR.
The document provides calculations to determine the cooling tower capacity in tons (TR) for a system with a water flow rate of 225 cubic meters per hour, an inlet water temperature of 37°C, an outlet water temperature of 32°C, and ambient wet-bulb temperature of 29°C. Using the given values for water density, specific heat of water, and flow rate difference in temperature, the cooling tower capacity is calculated to be 369.0476 TR with a 20% excess capacity of 442.8571 TR.
The document provides calculations to determine the cooling tower capacity in tons (TR) for a system with a water flow rate of 225 cubic meters per hour, an inlet water temperature of 37°C, an outlet water temperature of 32°C, and ambient wet-bulb temperature of 29°C. Using the given values for water density, specific heat of water, and flow rate difference in temperature, the cooling tower capacity is calculated to be 369.0476 TR with a 20% excess capacity of 442.8571 TR.
The document provides calculations to determine the cooling tower capacity in tons (TR) for a system with a water flow rate of 225 cubic meters per hour, an inlet water temperature of 37°C, an outlet water temperature of 32°C, and ambient wet-bulb temperature of 29°C. Using the given values for water density, specific heat of water, and flow rate difference in temperature, the cooling tower capacity is calculated to be 369.0476 TR with a 20% excess capacity of 442.8571 TR.
Download as XLSX, PDF, TXT or read online from Scribd
Download as xlsx, pdf, or txt
You are on page 1of 1
Density 992
Water flow rate through CT 225 m3/hr
SP. Heat of water 1 k.Cal/kg °C Inlet water temperature 37 Outlet water temperature 32 Ambient WBT 29 Cooling tower capacity (TR) = (flow rate x density x sp.heat x diff. temp)/3024