Firebeam Xtra User Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

user guide

issue 0025-10
Reflective optical beam smoke detector user guide

1 Distance and position guidelines


These guidelines are recommendations only and it is important that you refer to your
appropriate governing standards at all times.
When positioning your firebeam there are important factors that you should consider, mainly
what distance you are covering and the optimal position in the building.

What distance?
The standard firebeam is suitable for distances of 7m to 70m to the reflector. If you require 70m to 140m you
will need to use the mid range reflector extension kit. For ranges of 140m to 160m you will require the
long range reflector extension kit.

NOTE. for distances under 20m use the short range mask supplied on the single reflector.

7 to 70 metres - the standard firebeam


The standard firebeam comes boxed with the head unit, low level controller, one reflector, short range mask,
3mm allen key and quick start installation guide, this should be used for distances over 7m and up to 70m.

Standard firebeam covers 7m and up to 70m

70 to 140 metres - the standard firebeam + mid range 70 to 140m kit


For distances of 70 to 140 metres you will need to use the standard firebeam and
a mid range extension kit (the mid range kit comes with a backing plate and 3
extra reflectors, you will need to add the reflector from the standard kit to the mid
range kit with the screws provided).

140 to 160 metres - the standard firebeam + long range 140 to 160m kit
For distances of 140 to 160 metres you will need to use the standard
firebeam and a long range extension kit (the long range kit comes with a
backing plate and 8 extra reflectors, you will need to add the reflector from
the standard kit to the long range kit with the screws provided).

2
What position?
A roof is considered flat unless the height of the apex is greater then 0.6m. If the roof is flat thefirebeam system
can be placed anywhere under the roof between 0.3m and 0.6m below the roof, up to a maximum height of
40m from the floor. thefirebeam has a detection area of 7.5m either side of the beam. If the roof is considered to
have an apex, place thefirebeam system 0.3m to 0.6m down from the top of the apex, up to a maximum height
of 40m from the floor. The maximum protected area either side of the beam can be extended by 1% for every
degree of roof pitch, see the example below: (please check with your local regulations)

0.3m - 0.6m

40m max
2.7m min
Field of view should be a 50cm radius from
the centre of the beam
Warning: So that the beam works effectively,
ensure the beam is not obstructed in a 1m
diameter clear line of sight along its entire axis
Flat roof

0.3 -0.6m

15m detection area

Extra coverage due to apex angle

0.3 -0.6m
100

15 + (15 x 10%) = 15m + 1.5m = 16.5m


8.25m 8.25m
16.5m detection area

Wall Wall

Min 0.5m

You should always position the beam at least 0.5m away from any protrusion

Note. Careful design consideration should be made when positioning beams and reflectors in environments
that can be susceptible to condensation i.e. warehouses near to water that have areas open to the outside
environment or that are exposed to quick extreme changes in temperature. To assist with this problem that can
affect all beam detectors we produce an anti-fog kit comprising of a specially coated reflector and lens cover.
Individual reflectors are also available. The standard firebeam and range kits can be supplied as anti-fog sets as
a special order.

3
2 Installing, commissioning and testing
step 1 mounting the head
Screw the head backing plate to the wall - always try to use as sturdy a location as possible, such as brick
or major structural steels (avoid mounting to outer metal cladding etc). Avoid mounting the head where direct
sunlight can shine directly into the ‘eyes’ of the beam (care should be taken when mounting in glass atriums).
Ambient sunlight will not affect the beam.

Also available - unistrut adapter plate


Use this accessory for easy mounting to unistrut fabrication. Holes are pre-
drilled to the correct pitch of the head and conveniently positioned for use
with unistrut.
2 knock-outs are provided Wire into system as required
on both sides. Take care when (see generic wiring diagram on
using drills not to damage the circuit the following page). Ensure that
board. Only punch out with head all wiring is below the level of
open and disconected from power the front edge of the box.

Wire to low level controller using Screw in through holes provided


bottom colour coded terminals. outside of the rubber seal.
Connect the head to
the base plate by first
plugging in the connector.
Do not force in, white
wires should be
uppermost. Should you
forget to connect this
the controller screen
will read ERROR. IMPORTANT ensure the Screw the head screws
To avoid damaging the detector head never dangle the connector is this way up. down with the 3mm allen
front cover assembly from the ribbon cable. key provided.
Your wiring should be
step 2 mounting the controller flush and not flattened by
tightening down screws.
Important mount the controller at eye level and ensure easy access.
Screw in through holes provided outside of the
rubber seal.
Wire to head using colour coded terminals.
If this connection is not made ERROR will appear
on the controller, this connection can be checked
by reading the resistance across the black and
grey terminals, they will read 110 ohm if OK or
220 ohm if not connected properly.

4
Generic wiring configurations
thefirebeam is a conventional device, below are suggested wiring configurations for single and multi heads on a
zone. thefirebeam can easily be made addressable with the use of a manufacturers interface and in some cases
can also be powered from the loop. Most wiring diagrams can be found on our website in more detail and in PDF
format, go to www.thefirebeam.com

Brown + supply (normal 12 - 30Vdc) Supply voltage 12Vdc to 30Vdc normal


Blue - supply (return) Quiescent current 3.5mA
Black zone + Alarm current 3.5mA
Grey zone - Aligning current normal 3.5mA fast 17mA
Green earth (screen) Fault/Alarm relay contact rating 2A @ 30Vdc

FIRE and EOL components as


supplied by the panel manufacturer

Single head on zone

To fire panel

no c nc no c nc

fault fire

FIRE EOL
manufactured by
Lemtronics Sdn. Bhd.
Phase 2, Bayan Lepas
technical support Free Industrial Zone
+44 (0)1582 608000 11900 Penang, Malaysia
Fire LED Auxiliary no relay
contact 2A > 30Vdc used
for External LED switching
fire
external
controller interface reset

To controller

5
Schottky barrier diode 1A 60V EOL
MBR160TR (RS 469-0714 or MBR160RGL (farnel 9556761

To fire panel

no c nc no c nc no c nc no c nc

fault fire fault fire

FIRE manufactured by
Lemtronics Sdn. Bhd.
FIRE manufactured by
Lemtronics Sdn. Bhd.
Phase 2, Bayan Lepas Phase 2, Bayan Lepas
technical support Free Industrial Zone
technical support Free Industrial Zone
+44 (0)1582 608000 11900 Penang, Malaysia +44 (0)1582 608000 11900 Penang, Malaysia

fire fire
external external
controller interface reset controller interface reset

6
To controller Beams 1,2,3... To controller ...end of line beam

diagrams
Other wiring

manufacturers protocols
Multiple beams on a zone

www.firebeamsupport.com
See our support website for further
diagrams including interfacing with
step 3 commissioning
Commissioning thefirebeam is a simple procedure outlined in the following step by step explanation.
Ensure the installation guidelines have been followed correctly and that the firebeam has a clear line of
sight through to the reflector and there are no obstacles in its path.

stage one, language and commissioning speed


1. Important. Do NOT put the reflector up. However, if you are recommissioning thefirebeam COVER it with a
non-reflective black cloth or similar. You cannot commission the beam if the reflector can been
seen
the Firebeam Air Quality 0%
2. Power up the unit and you will see Xtra the screen will default Status Fault
to Fault or Fire this is
Air Quality 0%
normal Status Fire
3. Access the menu by pressing enter enter

english
4. The first screen you see is if you need to change this use the right and left hand keys to
scroll through languages, when you have found your language press enter to access the commissioning menu.
If you have changed the language the system will continue in your chosen language.

5. Press enter and you will now see the commissioning speed screen. In most cases it is recommended to use
fast mode (in normal mode the system uses 3.5mA, in fast mode it uses 17mA) - if you are commissioning
more than one beam at a time and the system cannot support the extra draw it may be necessary to use
normal mode to prevent excessive current draw. Fast mode allows x4 times faster motor response and it may
be quicker to commission each beam in turn. Once commissioning is complete thefirebeam will automatically
revert to normal low power mode - (3.5mA).
left normal fast* right enter

6. Use the left and right keys to toggle between fast and normal, the
enter key to continue.
* indicates which mode is selected. Press the
stage two, pre-alignment
pre-alignment
7. The next screen is this is the most important part of setting up your beam.
Pre-alignment sets up the amount of power you need for the distance you are covering and can indicate if you
are receiving unwanted reflections from anything else in the beam path.
8. Press enter to begin pre-alignment. Remember no reflector. You will see the screen below. Take a moment to
understand what the figures on the screen mean.
output power receiver sensitivity received signal strength
10.0% 5% 0% P ‘P’ indicates pre-alignment
‘X’ - horizontal lens position in degrees X+0.000 Y+0.000

‘Y’ -vertical lens position in degrees

7
Pre Alignment continued
Receiver sensitivity (RX Sense) will start by raising to 100% and then the output power (IR power) will rise to
100%. More power will be output than is necessary to cover the distance and these levels will then be reduced
once the auto align process takes place. The air quality figure at this point should normally stay at 0%.
Pre-Align Complete will now be indicated

9. Press enter to accept Pre-Alignment and confirm these settings by pressing the right key and enter into Manual
Alignment.

Pre-Align - Complete right


Manual Alignment enter
Manual AQ 0%
Press (right) X+0.000 Y+0.000
thefirebeam is looking for the far wall of the building and in some shorter distance applications will stop raising
the IR Power when its sufficient for the distance. In these cases you can press Enter to accept the
Pre-Alignment then right key and enter into Manual Alignment.

10.0% 100% 0% P enter


Press (right) right
Manual Alignment enter
Manual AQ 0%
X+0.000 Y+0.000 to confirm X+0.000 Y+0.000

CAUTION: If you have not allowed the 50cm radius and thefirebeam encounters an obstruction this will also
stop raising the IR Power and halt the Pre Alignment as the beam will assume it has found the far wall. You will
need to identify and move the obstruction or reconsider the positioning of thefirebeam. You can identify that the
beam is obstructed by the right hand figure (Air Quality) has risen and may fluctuate between 5%-10%.
Obstructions near the head will disturb the pre-alignment process and care should be taken to ensure no solid
objects are close to the beam path.

Obstacle Roofline

Reflections from nearby objects will Sufficient power for distance Target wall
limit the output power and prevent
ability of the beam to cover the
required distance

Ensure 1m of clear space along the path of the beam


and 500mm from the edges of the reflector.
if the wall you are placing the reflector/s on is shiny or
glass then the reflectors should be placed on a 1meter
piece of non-reflective material like MDF to ensure
correct operation.
To find more information on Pre-Alignment look at our FAQ’s which can be found on
wwwfirebeamsupport.com

8
stage three, manual alignment
Once Pre Alignment is complete you will enter Manual Alignment.

10. NOW place or uncover the reflector


When you install or uncover the reflector the Right hand Figure (AQ) will jump up as high as 135%, this clearly
shows that thefirebeam can see the reflector and you can press Enter to move to Auto Alignment..
Manual
X+0.000
AQ 125%
Y+0.000 3
As long as there is a received signal of at least 80 to 100% ideally over 100% you can move onto the
next stage: Auto Alignment No.11.

If thefirebeam AQ does not rise significantly you will need to use the Left Right Up Down keys to move
the Eyes of thefirebeam onto the reflector and once you have targeted thefirebeam onto the reflector
the AQ will rise significantly.
Manual
X+0.000
AQ 13%
Y+0.000 7
In the example below we can see that the reflector is below the eye line of thefirebeam head, so in this
case you would need to lower the angle of the beam (-Y) until you receive an AQ of over 100%.

Beam head Reflector is lower than the beam head... use -Y to bring the beam onto the reflector
Reflector

y+
thefirebeam can be moved on both X and Y axis to a maximum 5 degrees using the
left (x-), right (x+), up (y+) and down (y-) keys. Looking at the reflector this will move
the beam across the reflector. Holding the keys down will quickly scroll through to your x- x+
desired position, on release of the button the screen will revert to the actual beam
position and can be seen stepping toward the requested position. y-
To confirm the beam is seeing the reflector covering the reflector at any time should
drop the AQ and prove the beam is on the reflector.
In the example above moving the y axis down
(y-) results in a greater AQ
Manual
X+0.000
AQ 6%
Y+0.000
down
Manual
X+0.000
AQ 110%
Y-1.260 3
Try and achieve as high an AQ as possible, it must be at least 80 to 100% ideally above 100%. Once you have
achived this you can move onto Auto Alignment No.11.

To find more information on Manual Alignment look at our FAQ’s which can be found on
wwwfirebeamsupport.com

9
stage four, auto-alignment
11. Having received an AQ reading of over 100% in manual mode press enter to exit manual and enter again to go
into auto alignment mode.
Auto Alignment enter
100% 100% 103% A
X+0.000 Y+0.000

Auto Alignment is an automatic process that will firstly reduce the RX Sense and IR Power to accommodate the
best settings for thefirebeams environment.
thefirebeam will automatically align to the centre of the Reflector, you will notice the X and Y axis moving as
thefirebeam moves up, down, left and right to find the centre point.

When finished thefirebeam will state Align Complete and pressing Enter to confirm will show
Air Quality 100% Status Normal. Air Quality 100%
Status - NORMAL

CAUTION: This process should take up to 10 Minutes, if thefirebeam does not complete after this time then
look at the X and Y axis to check it has not deviated off the reflector onto an obstruction. The X and Y figures
should be below 1.50 on each axis and would normally be below 0.90.
If this is not the case you may need to start the Manual Alignment process again to return both thefirebeam
axis to 0.00 and identify and remove the obstruction.

To find more information on Pre-Alignment look at our FAQ’s which can be found on
wwwfirebeamsupport.com

step 4 testing
1. The FireBeam should now be tested for Fire and Fault.

The FireBeam must be tested at the reflector end and not at the Fire Beam head. This is to confirm it
is looking at the reflector and completes the commissioning process.

FAULT - Cover the reflector within 1 second with a non reflective card to simulate a fault such as
a fork truck breaking the path of thefirebeam. After 10 Seconds thefirebeam
beam should register FAULT
and the Amber light will flash.

2. FIRE - Cover the reflector slowly up to 70% with a non reflective card to simulate a fire such
as smoke entering the path of thefirebeam. After 10 Seconds thefirebeam should register
FIRE and the Red light will flash.

To find more information on Testing look at our FAQ’s which can be found on
wwwfirebeamsupport.com

Once you have successfully completed both tests your firebeam is commissioned.
You can now fine tune your beam to suit the environment if needed. Look through the following menus to see
adjustments that can be made.

10
3 Screen and menu systems
Home screen
Air Quality 100%
Status – NORMAL This is the screen you would normally see when the beam is commissioned.

Other screens you may see are:


Air Quality 29%
FIRE Status – FIRE The air quality level has fallen below the fire threshold setting.

If alarm is set to latching and you need to reset from fire press enter enter to see this screen:
Alarm Reset
and press enter enter again to reset and return to the normal screen.
This can also be reset by dropping the power to the beam for 5 seconds. If set to auto reset it
will reset to normal automatically. See the menu sytem on page 13 to change between auto and
latching if required
Air Quality 0% The beam path has been fully blocked within 1 second (used when fault testing
FAULT Status – FAULT in commissioning).
Air Quality XX No communication with the controller. This could be that the flying lead is not
ERROR Status – ERROR connected, or that the head is not connected to the controller, this can be
checked by reading the resistance across the black and grey terminals,
if connected it should read 110ohms if not connected at one end this will
read 220ohms.
Air Quality 89% This screen will appear when the beam is performing a self alignment,
ALIGN Status – ALIGN normally because of building movement.
DIRT Status – Dirt Comp This is due to the compensation for dirt build up reaching its maximum -
COMP FAULT or FIRE LED may be flashing.

How to use the menu system


Press enter enter to go into the menu system, then press down down to go through the main menu options:

English
enter enter here to change languages.

Commission
enter enter here to commission thefirebeam.

Mode Change
enter enter here to make all changes and adjustments to thefirebeam.

Beam Maintenance
enter enter here as part of your routine maintenance.

Diagnostics
enter enter here to access power and temperature headings.

11
Individual menu items
1. Language The language is factory set to English if this is okay press enter enter to continue to
commissioning or arrow up to return to the home screen. To change the language use
the right and left keys to change to your preferred language and press enter to confirm
your choice – you will then continue in the language of your choice. Languages currently
available are: English, Dutch, Italian, French, Spanish, Czechoslovakian and German.

2. Commissioning Press enter enter


to go into commissioning.

enter

Normal Fast* Pressing right or left changes between normal and fast. It is recommended in most
cases to use fast mode (in normal mode the system uses 3.5mA, in fast mode it uses
17mA) - if you are commissioning more than one beam at a time and the system
cannot support the extra draw it may be necessary to use normal mode to prevent
excessive current draw. Fast mode allows x4 times faster motor response and it
enter
may be quicker to commission each beam in turn. Once commissioning is complete
thefirebeam will automatically revert to normal low power mode - (3.5mA).

Pre-Alignment Press enter enter to start pre-alignment. In pre-alignment you should ALWAYS COVER
THE REFLECTOR. Starting at 10% power and 5% receiver sensitivity, the receiver
sensitivity will automatically increase to a maximum of 100% then the output power will
enter increase. These settings will automatically stop when a received signal strength reaches
6% - this received signal is the returned strength of the output signal without a reflector
X Y (if no return signal is received the beam will reach full power and the screen will say
Pre-Align - complete). If you don’t receive high enough output power and receiver
sensitivity readings this will usually be because you are receiving a reflection from an
object nearby - use the left, right, up and down keys to avoid the obstruction. When
enter happy with your readings press enter and confirm by pressing the right button, this will
take you to manual alignment - if you wish to abort Pre-Align press the left button.

Manual Alignment Press enter enter to go into manual alignment - NOW THE REFLECTOR CAN BE
PLACED OR THE COVER CAN BE REMOVED. You should see a large jump in signal
enter
strength. If no jump is seen use the X and Y keys to locate the reflector (the better the
signal strength the better the beam is aligned) try to achieve a figure of around 100%
X Y or over for optimum auto alignment times. Press enter to okay this and go to auto
alignment.
enter

Auto Alignment Press enter enter to start auto-alignment. The beam will calibrate its power and search for
the edges of the reflector – adjusting its power as it aligns itself onto the reflector. Once
it has found all four edges twice it will then centre itself on the middle of the reflector and
the screen will say align complete. Press enter to return to the home screen. If you see
align aborted this means something has crossed the beam path of the received signal and
the signal has dropped out. Press back / left to return to auto alignment.

12
3. Mode Change Here we can make changes to how the beam behaves. Press enter enter
to go into
mode change and the sub menus.
enter

Threshold Threshold. Use the right and left keys to increase or decrease the beams sensitivity.
It is factory set at 35% (meaning the received signal has to drop by 35% to trigger
the fire relay. This sensitivity can be adjusted between 25% (sensitive) and 50% (less
sensitive) (press enter to return to mode change or down to go to time to fire).

Time to fire Time to fire. Here we can adjust how long the beam has to be in fire before the fire
relay is triggered. This is factory set at 10s, you may want to increase this if there is
something that may momentarily obscure the beam path (birds / forklift truck) this can
be adjusted between 2 and 30 seconds by using the right and left keys (press enter to
return to mode change or down to go to time to fault).

Time to fault Time to fault. Here we can adjust the time to fault between 2 and 60 seconds (factory
set at 10 seconds). For a beam to go into fault the beam path must be totally blocked
within ONE second. By using the right and left keys (press enter to return to mode
change or down to go to auto reset).

Auto reset Auto reset. The beam is factory set to auto reset when the received signal raises above
the fire threshold hysteresis. This can be set to latching if your system requires this.
Change by using the right and left keys (press enter to return to mode change or down
to go to align on / off).

Align On/Off Align on / off. You may want to turn the auto alignment function off, for example, in an
environment that often gets filled with welding smoke, the auto align function kicks
in when the received signal drops below 90%, the point that the beam automatically
checks for building movement. The beam will try to align through the smoke which
could be a problem if it is unable to see the edges of the reflector. Use the right and
left keys to turn off and on. When turning this function off extra care should be taken
to ensure that the beam head is on a sturdy fixing ie., brick wall or major structural
steel. Auto alignment will still function in commissioning (press enter to return to mode
change or down to go to align time).

Align Time Align time. This is factory set to 4hrs, you can adjust this, by using the right and left
keys, between 0 to 12 hours depending on your environment (press enter to return to
mode change or down to go to green flashing light).

13
Green Flashing Light Green flashing light on / off. By using the right and left keys you can turn the green
On / Off flashing LED, located on the head and controller, on or off. This is a useful way of
identifying the beam head you are working with (press enter to return to mode change
or down to go to phase).

Phase Phase. When using multiple beams that face each other the beam output signals could
phase together and can cause unreliable readings, by setting each beam to phase
differently alleviates this problem. Use the right and left keys to give each beam a
different phase pattern (length between output beam sample times) you can choose
between 0 (default setting) and 6 (press enter to return to mode change or down to go
to hysteresis).

Hysteresis Hysteresis. Changing the hysteresis will change the delay in returning from a fire
state back to a normal state, for example, the beam is factory set at 15% so if the
beam falls into fire at 65% (35% threshold) it has to recover 15% to 80% before it
returns to normal. This action prevents small fluctuations in returned signal causing
the beam to fall in and out of a fire state. This can be adjusted between 1% and 40%
by using the right and left keys (press enter to return to mode change or down to go to
compensation fire / fault).

4. Beam Maintenance Press enter enter


to go into beam maintenance.

enter

Dirt Comp Dirt Comp. This screen shows how much the beam has compensated for dust build-
up on the beam head and reflectors, ALWAYS take a note of this value as part of your
routine maintenance to see any build-up pattern, if you see figures above +50% you
should clean both the lens face and the reflectors (once cleaned you should instigate
an auto alignment to re-calibrate the beam settings).
It is possible that you may see a negative number here, this can happen when
thefirebeam has been commissioned in a ‘dirty’ atmosphere such as builders dust
which, once cleared, the beam then compensates for. To reset, perform an auto
alignment to re-calibrate the beam (press enter to return to beam maintenance or
down to go to event counts).

14
Alarm & Fault Event counts. Here we can see how many times the beam has gone into fire or fault since
Event Counts the beam was commissioned or since the event log was last cleared including testing.

Press enter enter to clear events.

left/
Press left / back back to return to beam maintenance or down to go to self test.

Self Test Self test.

Press enter enter to perform a fire test, this works by running a test algorithm to lower
the output power, the receiver sees this as obscuration. When the received signal
drops below the threshold point the beam will trip the fire relay – this relay will not trip
until the time to fire has passed which could be anything between 2 and 30 seconds.
left/
Press left / back back to end test, the fire test should show on the panel. Press left /
back to return to beam maintenance or down to go to on / off.

On / Off On / off. If something needs to be maintained in the beam path use the right and left
keys to turn the system on and off.
This will show as a fault on the panel.

Press enter enter to return to beam maintenance.

5. Diagnostics Press enter enter to go into diagnostics.

enter

IR Power IR power. This screen shows the amount of output power that is being transmitted.
It can be increased or decreased by using the right and left keys (press enter to return
to diagnostics or down to go to RX sensitivity).

RX Sensitivity RX sensitivity. This screen shows the receiver sensitivity and can be changed by
using the right and left keys (press enter to return to diagnostics or down to go to
temperature).

Temperature xxc Temperature & Gain. Here we can see displayed the temperature at thefirebeam head
TC +x G1 xxx and the amount of temperature compensation and Gain figure (no adjustments can be
made here).

Press enter enter


to return to diagnostics.

FAQ’s. a comprehensive list of FAQ’s can be found on www.firebeamsupport.com


15
technical specifications
12 to 30 Vdc normal Controller Status – FIRE
3.5mA (constant current) Controller Red Flashing LED
in all operational states Head Red Flashing LED
17mA (constant current) Alarm Relay Change Over (CO) Contact
in fast commissioning
Rating 2A @ 30 Vdc

-10°C to +55°C
Beam test function by controller
10 to 95% RH Non-condensing
IP65 when suitably
Alarm latching/auto-reset selectable
mounted and terminated (default auto-reset)
Alarm reset in latching mode by controller
reset function, removing power for >5
seconds or momentarily apply >5 VDC to
180mmH x 155mmW x137mmD reset connections in Beam Head.
Weight 1.1Kg

185mmH x 120mmW x 62mmD <4%


Weight 0.55g

293mmH x293mmW x 5mmD Obscuration drops to below the fault


Weight 0.8Kg sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
394mmH x 394mmW x 5mmD Commissioning modes, Pre-Alignment
Weight 1.8Kg and Auto Alignment

270mmH x 250mmW x 5mmD Time to Fault Condition adjustable,


Weight 0.6g 2 to 60 seconds in 1 second increments
(mounts the Beam Head onto unistrut)
(default 10 seconds)

870nm
Controller Status – FAULT
±5°
Controller Yellow Flashing LED 1 Second
(static not auto-aligning) Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact
Rating 2A @ 30 VDC

Obscuration level is above the


Standard Product 7 to 70 metres. Use short Alarm sensitivity level
range mask for distances between 7 & 20 Controller Status – NORMAL
metres
Controller Green Flashing LED

Head Green Flashing LED

25%(1.25dB) to 50%(3dB) in 1%(0.05dB)


increments (default 35% (1.87dB)) Auto-align during normal operation if
obscuration drops below 90% for the
duration of the align time set
sensitivity level.
Time to Alarm Condition adjustable Beam Contamination Compensation 4 hour
2 to 30 seconds in 1 second increments monitoring. Compensation data available at
(default 10 seconds) the controller

16

You might also like