DB Mmu-Ap 4HP
DB Mmu-Ap 4HP
Contents
1. Specifications
2. Dimensions
3. Center of gravity
4. Piping diagram
5. Wiring diagram
6. Electrical characteristics
7. Sensible capacity table
8. Air flow distance chart
9. Sound data
10. Fresh air intake (Design guide)
11. Branching duct (Design guide)
12. Accessories
1
E13-371 MMU-AP_4HP-E
1. Specifications
Model name MMU- AP0094HP-E AP0124HP-E AP0154HP-E AP0184HP-E AP0244HP-E AP0274HP-E AP0304HP-E AP0364HP-E AP0484HP-E AP0564HP-E
Cooling / Heating capacity (*1) kW 2.8 / 3.2 3.6 / 4.0 4.5 / 5.0 5.6 / 6.3 7.1 / 8.0 8.0 / 9.0 9.0 / 10.0 11.2 / 12.5 14.0 / 16.0 16.0 / 18.0
Electical Running 50 Hz 0.23 0.23 0.27 0.29 0.38 0.38 0.43 0.73 0.88 0.88
characteristics current A
60 Hz 0.24 0.24 0.28 0.30 0.39 0.39 0.45 0.76 0.92 0.92
Starting current A 0.30 0.33 0.36 0.42 0.59 0.87 1.23 1.26
Main unit Heat-insulating material attached Zinc hot dipping steel plate
Depth mm 950
Main unit kg 20 25
Total weight
Ceiling panel kg 4.0
Motor output W 14 20 68 72
Note
(*1) Rated conditions Cooling : Indoor 27 degC Dry Bulb / 19 degC Wet Bulb, Outdoor 35 degC Dry Bulb.
Heating : Indoor 20 degC Dry Bulb, Outdoor 7 degC Dry Bulb / 6 degC Wet Bulb.
Based on equivalent piping length of 7.5 m and piping height difference of 0 m.
2
E13-371 MMU-AP_4HP-E
2. Dimensions
MMU-AP0094HP-E, AP0124HP-E
860 to 910 Ceiling open dimension 1000 or more
15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
661 or less
Standing
300 or less
850 or less
Standing
30
44
112
129
172
189
77
74 105
74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension
351
knockout square
80
105 77
hole Ø150
135 105
105
240
16.5
105
384
Ceiling panel
45
207.5
(sold separately)
105
Bottom face
Ø162 269 of ceiling
30
Z
64
57
(2 positions)
.5
OA for Ø100
74
15
5
18
7
Z view
Bottom face of ceiling Indoor unit
129
5
77
Unit : mm
3
E13-371 MMU-AP_4HP-E
MMU-AP0154HP-E, AP0184HP-E
860 to 910 Ceiling open dimension 1000 or more
15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
661 or less
Standing
300 or less
850 or less
Standing
Take-in port of wiring Bottom face of ceiling
30
44
112
129
172
189
77
74 105
74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension
351
knockout square
80
105 77
hole Ø150
135 105
105
240
16.5
105
384
Ceiling panel
45
207.5
(sold separately)
105
Bottom face
Ø162 269 of ceiling
30
Z
57
64
15
5
18
7
5
77
Indoor unit
Unit : mm
4
E13-371 MMU-AP_4HP-E
15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
661 or less
Standing
300 or less
850 or less
Standing
Take-in port of wiring Bottom face of ceiling
30
44
112
129
172
189
77
74 105
74
690 ± 20 Hanging bolt pitch
950 Panel external dimension
840 Unit external dimension
351
knockout square
80
105 77
hole Ø150
135 105
105
240
16.5
105
384
Ceiling panel
45
207.5
(sold separately)
105
Bottom face
Ø162 269 of ceiling
30
Z
57
64
15
5
18
7
5
77
Indoor unit
Unit : mm
5
E13-371 MMU-AP_4HP-E
15 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle
1000 or more
15 or more
The space that is necessary
for equipping and service
661 or less
Standing
300 or less
850 or less
Take-in port of wiring Bottom face of ceiling
Standing
30
44
112
129
172
189
77
105
137
287.5
416.5
408
351
hole Ø150
207.5 105 135 105
105
240
16.5
384
Ceiling panel
45
(sold separately)
64
(2 positions)
5
18
7
5
77
Indoor unit
Unit : mm
6
E13-371 MMU-AP_4HP-E
3. Center of gravity
Total weight
Model name X(mm) Y(mm) Z(mm) Main unit Ceiling panel
(kg) (kg)
MMU-AP0094HP-E
18
MMU-AP0124HP-E
MMU-AP0154HP-E
MMU-AP0184HP-E 455 154
MMU-AP0244HP-E 20
470 4.0
MMU-AP0274HP-E
MMU-AP0304HP-E
MMU-AP0364HP-E
MMU-AP0484HP-E 450 184 25
MMU-AP0564HP-E
7
E13-371 MMU-AP_4HP-E
4. Piping diagram
Liquid side Gas side
Pulse Motor
Valve (PMV)
Strainer
Sensor
Sensor (TCJ) Fan
(TC2)
Sensor
(TC1)
Sensor M Fan motor
(TA)
8
E13-371 MMU-AP_4HP-E
5. Wiring diagram
1 2 3 1 2 3 4 5 6 4 3 1 2 5
1 2 3 1 2 3 4 5 6 4 3 1 2 5
1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 3 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Flow
Selector unit 1 2 3 4 5 1 2 3 4 5 6 1 2 3 1 3 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Earth screw
CN81 CN82 CN334 CN333 CN510 1 1
(BLK) (BLU) (WHI) (WHI) (WHI) CN504 DM
(WHI) 2 2
Motor drive
Indoor unit circuit 1 1
Fuse, F01 Fuse, F02 CN34
Earth screw RED T6.3A, 250V~ T3.15A, 250V~ 2 FS
~ + (RED)
1 1 DC20V 3 3
CN67 Power supply DC15V
(BLK) circuit DC12V CN104 1 1
3 3 DC7V
~ – (YEL) 2 2
WHI TA
SW501 CN102 1 1
R(L) S(N) ON (RED) 2 2
Control P.C. board for Indoor unit TCJ
Power supply CN101 1 1
single phase (MCC-1570) 1 2 (BLK) 2 2
220V ~ 60Hz (High Wall setting) TC2
1 1
CN100 2
BLK (BRW)
P01 CN71 (CHK) 3 3 TC1
1
1 CN66
CN519 2
2 (WHI) CN72 (DISP)
(WHI) 3
1 1 CN40 4
CN508
2 2 (BLU) (RED)
1
CN41 CN309 CN20 CN60 CN32 CN61 CN50 CN70 CN73 CN80
(BLU) (YEL) (BLU) (WHI) (WHI) (YEL) (WHI) (WHI) (RED) (GRN) 2
1 2 3 1 3 1 2 3 4 5 1 2 3 4 5 6 1 2 1 2 3 4 5 6 1 2 3 4 5 1 2 1 2 1 2 3
1 3 1 3 (GRL) (OPTION) (FAN DRIVE) T10 (FILTER) (EXCT) (PNL)
BLU BLU BLK BLK
TR 1 2
U1 U2 A B 1 2
Color Indication
BLK CN01 (WHI)
3 3
CN02 RED : RED GRY : GRAY
WHI (BLU) WHI : WHITE PNK : PINK
1 1
CN03 (RED) YEL : YELLOW ORN : ORANGE
WHI BLK 1 2 BLU : BLUE GRN : GREEN
1 2 BLK : BLACK BRW : BROWN
1 2
U1 U2 A B X Y
1 2
Outdoor CN001
unit (WHI) Network adaptor
Symbol Parts name
(Option) FM Fan Motor
Wired Adapter
Remote for Wireless TA Indoor temp. sensor
controller Remote controller
TC1, TC2, TCJ Temp. sensor
LM1, 2, 3, 4 Louver Motor
DM Drain pump Motor
1. indicates the terminal block. FS Float Switch
Letter at inside indicates the terminal number. PMV Pulse Motor Valve
2. A dotted line and broken line indicate the wiring site. Power supply Transformer
TR
3. indicates the control P.C. board. (Fot Newtwork adapter)
9
E13-371 MMU-AP_4HP-E
6. Electrical characteristics
50 Hz
Nominal Voltage Voltage Range Fan Motor Power Supply
Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMU-AP0094HP-E 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0124HP-E 230-1-50 198 264 0.014 0.63 0.79 15
MMU-AP0154HP-E 230-1-50 198 264 0.014 0.80 1.00 15
MMU-AP0184HP-E 230-1-50 198 264 0.014 0.80 1.00 15
4-Way Air MMU-AP0244HP-E 230-1-50 198 264 0.020 0.87 1.09 15
50Hz Discharge
Cassette Type MMU-AP0274HP-E 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0304HP-E 230-1-50 198 264 0.020 0.87 1.09 15
MMU-AP0364HP-E 230-1-50 198 264 0.068 1.15 1.44 15
MMU-AP0484HP-E 230-1-50 198 264 0.072 1.15 1.44 15
MMU-AP0564HP-E 230-1-50 198 264 0.072 1.15 1.44 15
60 Hz
Nominal Voltage Voltage Range Fan Motor Power Supply
Type Model
(V-Ph-Hz) Min Max kW FLA MCA MOCP
MMU-AP0094HP-E 220-1-60 198 242 0.014 0.66 0.83 15
MMU-AP0124HP-E 220-1-60 198 242 0.014 0.66 0.83 15
MMU-AP0154HP-E 220-1-60 198 242 0.014 0.84 1.05 15
MMU-AP0184HP-E 220-1-60 198 242 0.014 0.84 1.05 15
4-Way Air MMU-AP0244HP-E 220-1-60 198 242 0.020 0.91 1.14 15
60Hz Discharge
Cassette Type MMU-AP0274HP-E 220-1-60 198 242 0.020 0.91 1.14 15
MMU-AP0304HP-E 220-1-60 198 242 0.020 0.91 1.14 15
MMU-AP0364HP-E 220-1-60 198 242 0.068 1.21 1.51 15
MMU-AP0484HP-E 220-1-60 198 242 0.072 1.21 1.51 15
MMU-AP0564HP-E 220-1-60 198 242 0.072 1.21 1.51 15
MCA: Minimum Circuit Amps FLA: Full Load Amps
MOCP: Maximum Overcurrent Protection (Amps)
10
E13-371 MMU-AP_4HP-E
11
E13-371 MMU-AP_4HP-E
12
E13-371 MMU-AP_4HP-E
13
E13-371 MMU-AP_4HP-E
0.7m/s 0.7m/s
0.5m/s 0.5m/s
2 2
Ceiling height (m)
1 1
0 1 2 3 4 5 0 1 2 3 4 5
Horizontal distance (m) Horizontal distance (m)
0.7m/s
0.7m/s
0.5m/s 0.5m/s
Ceiling height (m)
3
2
0.3m/s
0.3m/s
Ceiling height (m)
2
1
1
0 1 2 3 4 5
Horizontal distance (m)
0 1 2 3 4 5
Horizontal distance
0.3m/s
Ceiling height (m)
Ceiling height (m)
2
1
0 1 2 3 4 5
Horizontal distance (m)
0 1 2 3 4 5
Horizontal distance (m)
14
E13-371 MMU-AP_4HP-E
9. Sound data
Sound pressure spectrum
MMU-AP0094HP-E, AP0124HP-E
Sound pressure H-M-L
level(dB)(A) 30-29-27
90
H
M
60
NC-60
50
NC-50
1.5m 40
NC-40
30
Microphone NC-30
20
Audibility limits of NC-20
continous white level
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
MMU-AP0154HP-E MMU-AP0184HP-E
Sound pressure H-M-L Sound pressure H-M-L
level(dB)(A) 31-29-27 level(dB)(A) 32-29-27
90 90
H H
M M
Octave band sound pressure level (dB)
80 80
L L
70 NC-70 70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white level continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
L
70 NC-70 70 NC-70
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white level continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Octave band center frequency (Hz)
15
E13-371 MMU-AP_4HP-E
MMU-AP0364HP-E MMU-AP0484HP-E
Sound pressure H-M-L Sound pressure H-M-L
level(dB)(A) 43-38-32 level(dB)(A) 46-38-33
90 90
H H
M M
80
Octabe nabd sound pressure level (dB)
60 60
NC-60 NC-60
50 50
NC-50 NC-50
40 40
NC-40 NC-40
30 30
NC-30 NC-30
20 20
Audibility limits of NC-20 Audibility limits of NC-20
continous white level continous white level
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz) Ontave band center frequency (Hz)
MMU-AP0564HP-E
Sound pressure H-M-L
level(dB)(A) 46-40-33
90
H
M
Octave band sound pressure level (dB)
80
L
70 NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
Audibility limits of NC-20
continous white level
10
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
16
E13-371 MMU-AP_4HP-E
Usage
The fresh air and filter chamber is used as the filter chamber.
Fresh air intake by using the fresh air and filter chamber and fresh air intake box.
Caution
1. Be sure to provide air return.
2. The fresh air shall be treated by heat reclaim ventilator or the like.
3. Recommended treated air temperature is 12 C to 30 C.
4. Be sure to decide the fresh air volume so that mixed suction air with fresh air keep operating temperature.
Provide an air filter in fresh air way to prevent sucking dust.
5. Be sure to insulate the fresh air duct.
In order to accelate starting up in heating mode, implement pre-heating operation by cutting off fresh air intake.
195
P1 P
145
(Atmospheric)
95
45
Fresh Air
Static Pressure = P (atmospheric) - P1
-5 Chamber
0 50 100 150 200 250 300 350 400
Fresh Air Volume (m³/h)
17
E13-371 MMU-AP_4HP-E
40
8 015type
6 018type
30
4 024type,027type
5
20
030type
10 036type
1 2 3 048type
0
0 100 200 300 400 500 600 700 800 056type
Air volume (m³/h)
Cover method
Use air discharge direction kit
(TCB-BC1602UE)
to cover the air discharge port.
Dimension
45° 45°
114.6
105
2
Ø16
Ø145
Ø149
Ø176
114.6
105
4 - Ø6
Installation sample
18
E13-371 MMU-AP_4HP-E
12. Accessories
6 7
1,2,3
19
4-way Air Discharge Cassette Engineering Data Book
Model name:
MMU-AP_4HP-E
Apri, 2013 First Edition