K85001-0533 - Input-Output Modules

The document discusses Kidde Input/Output Modules that can be configured with different "personality codes" to perform various control functions. The modules provide 10 personality codes that allow configurations such as alarm inputs with normally open or normally closed relay outputs, delayed alarm inputs, and active non-latching or latching inputs. The modules mount in electrical boxes or on motherboards and are addressed electronically by the control panel to reduce installation time.

Uploaded by

Joash Oropilla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views6 pages

K85001-0533 - Input-Output Modules

The document discusses Kidde Input/Output Modules that can be configured with different "personality codes" to perform various control functions. The modules provide 10 personality codes that allow configurations such as alarm inputs with normally open or normally closed relay outputs, delayed alarm inputs, and active non-latching or latching inputs. The modules mount in electrical boxes or on motherboards and are addressed electronically by the control panel to reduce installation time.

Uploaded by

Joash Oropilla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

KIDDE® Catalog u Intelligent Input-Output

Compatible with VS & VM control systems

Technology that saves lives

Input/Output
Modules
GSA-IO, GSA-MIO

S3424

7300-1483:
0154

Overview Standard Features


GSA-IO and MIO Input/Output Modules are intelligent analog • 10 modules in one
addressable devices that form part of Kidde’s Signature line Multiple applications including normally-open or normally-
of products. The actual operation of the GSA-IO and MIO is closed alarm relay and latching or non-latching alarm inputs.
determined by the “personality code” selected by the installer, The installer selects one of up to 10 personality codes to be
which is downloaded to the module from the Signature loop downloaded from the loop controller.
controller during system configuration.
• Adjustable time delays
Depending on their assigned personality, Input/Output Modules User sets the expected response time (5 - 120 seconds) for
provide the following modes of operation: maximum flexibility.
• Output with monitor input (two personalities) • Plug in (UIO) or standard 1-gang mount
• Input/programmable output (eight personalities) UIO versions allow quick installation where multiple modules
Each IO module requires one module address. are required. The 1-gang mount version is ideal for remote
locations that require a single module.
• Automatic device mapping
Signature modules transmit information to the loop controller
regarding their circuit locations with respect to other Signature
devices on the wire loop.
• Electronic addressing
Programmable addresses are downloaded from the loop
controller, a PC, or the SIGA-PRO Signature Program/Service
Tool. There are no switches or dials to set.
• Intelligent device with microprocessor
All decisions are made at the module to allow lower
communication speed with substantially improved control panel
response time and less sensitivity to line noise and loop wiring
properties; twisted or shielded wire is not required.

Page 1 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1
Application Personality codes 33: Alarm input and N.O. relay output
Personality code 33 configures the module as a normally-open,
The GSA-IO mounts to a standard North American one-gang dry-contact relay and an alarm latching input for Class B contact
electrical box, making it ideal for locations where only one module initiating devices. When the input contact of the initiating de-
is required. Separate I/O and data loop connections are made to vice changes state, the I/O module sends an alarm signal to the
each module. Signature loop controller and the alarm condition is latched at the
The GSA-MIO is part of the UIO family of plug-in Signature Series module.
modules. It functions identically to the GSA-IO, but takes advan- Personality code 34: Alarm input and N.C. relay output
tage of the modular flexibility and easy installation that character- Personality code 34 operates the same as personality code 33,
ize all UIO modules. Two- and six-module UIO motherboards except that the output is configured as a normally closed, dry-
are available. These can accommodate individual risers for each contact relay.
on-board module, or risers that are shared by any combination
of its UIO modules. All wiring connections are made to terminal Personality code 35: Delayed alarm input and N.O. relay
blocks on the motherboard. UIO assemblies may be mounted in output
Kidde enclosures. Personality code 35 configures the module as a normally-open,
dry-contact relay and an alarm latching input for Class B contact
initiating devices. This personality requires that a change in the
state of the initiating device be maintained for approximately 16
Electronic Addressing seconds before the I/O module sends an alarm signal to the Sig-
The loop controller electronically addresses each module saving nature loop controller. The alarm condition is latched at the mod-
valuable time during system commissioning. Setting complicated ule. Use only with non-retarded, N.O. waterflow alarm switches.
switches or dials is not required. Each module has its own unique
Personality code 36: Delayed alarm input and N.C. relay
serial number stored in its “on-board memory”. The loop control-
output
ler identifies each device on the loop and assigns a “soft” address
Personality code 36 operates the same as personality code 35,
to each serial number. If desired, the modules can be addressed
except that the output is configured as a normally closed, dry-
using the SIGA-PRO Signature Program/Service Tool.
contact relay. Use only with non-retarded, N.C. waterflow alarm
switches.
Personality code 37: Active input (non-latching) and N.O.
Personality Codes relay output
A signature module requires a Signature loop controller to down- Personality code 37 configures the module as a normally-open,
load the personality code that determines how it will operate. The dry-contact relay and an active input for Class B contact initiating
Input/Output Module provides personality codes 31 through 40. devices. When the input contact of the initiating device changes
For personalities 33 through 40, the outputs must be programmed state, the I/O module sends an active signal to the Signature loop
to be activated by the panel. controller. The active signal does not latch, and restores when the
Personality code 31 (default): N.O. relay output with monitor input device returns to its normal state. Typically used for monitor-
input ing N.O. fans, dampers, doors, etc.
Personality code 31 configures the module as a normally-open Personality codes 38: Active input (non-latching) and N.C.
output relay contact that requires a maintained dry contact input relay output
activation. The activation must take place within a time period Personality code 38 operates the same as personality code 37,
defined by the user (15 seconds default; 5 - 120 seconds selecta- except that the output is configured as a normally closed, dry-
ble) after the output circuit activation. If the fire alarm control panel contact relay. Typically used for monitoring N.C. fans, dampers,
does not receive a monitor input within the specified time, it will doors, etc.
generate a trouble condition.
Personality code 39: Active input (latching) and N.O. relay
Personality code 32: N.C. relay output with monitor input output
Personality code 32 operates the same as personality code 31, Personality code 39 configures the module as a normally-open,
except that the output is configured as a normally closed, dry- dry-contact relay and an active latching input for Class B contact
contact relay. initiating devices. When the input contact of the initiating device
changes state, the I/O module sends an active signal to the
Signature loop controller and the active condition is latched at the
module.
Personality code 40: Active input (latching) and N.C. relay
output
Personality code 40 operates the same as personality code 39,
except that the output is configured as a normally closed, dry-
contact relay.

Page 2 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1
Installation Warnings & Cautions
The GSA-IO: modules mount to North American 2½ inch (64 mm) This module will not operate without electrical power. As fires
deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square frequently cause power interruption, we suggest you discuss
boxes with 1-gang covers. They also can be snapped directly to further safeguards with your fire protection specialist.
the GSA-MP mounting plates. The terminals are suited for #12 to
#18 AWG (2.5 mm2 to 0.75 mm2) wire size. Kidde recommends that these modules be installed according to
latest recognized edition of national and local fire alarm codes.
UIO Motherboard

Testing & Maintenance


The module’s automatic self-diagnosis identifies when it is
Plug-in (UIO) defective and causes a trouble message. The user-friendly
Module maintenance program shows the current state of each module
and other pertinent messages. Single modules may be turned off
(de-activated) temporarily, from the control panel.
Scheduled maintenance (Regular or Selected) for proper system
operation should be planned to meet the requirements of the
Cabinet or electrical enclosure Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ULC 536 standards.
GSA-MIO: mount the UIOxR motherboard inside a suitable Kidde
enclosure with screws and washers provided. Plug the module
into any available position on the motherboard and secure the
module to the motherboard with the captive screws. Wiring Compatibility
connections are made to the terminals on the motherboard (see These modules are part of Kidde’s Signature Series intelligent
wiring diagram). UIOxR motherboard terminals are suited for #12 processing and control platform. They are compatible with VM,
to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. and VS Series control panels.

Compatible electrical box

Wall plate, white


(1-gang)

M
ALAR
FIRE DULE
MO

Page 3 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1
Typical Wiring (GSA-IO)
Modules will accept #18 AWG to #12 AWG (0.75mm2 to 2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2)
are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.

Input/Output Module (personality codes 31 - 40)


8
Wiring Notes:
N.O. or N.C. 1
5 Maximum 25 Ohm resistance per wire.
N.O. or N.C. UL/ULC
Listed 2 #12 AWG (2.5 mm²) max; #18 AWG (0.75²) mm min.
47 kW 3
EOL 10 Vdc @ 350 mA, max.
4 See the loop controller installation sheet for wiring
specifications.
Input/Output Module
7 2 (personality codes
6 31
3 2- 40)
1
Input/Output Module 5 System programming determines whether contact
8 TB2 will be normally-open (N/O) or normally-closed (N/C).
N.O. or N.C. 8 7 65 6 Supervised and power-limited.
5 N.O. or N.C. UL/ULC 7 Power-limited unless connected to a nonpower-
Red LED (Active/Alarm) Green LED (Normal/Trouble) Listed
limited source. If the source is nonpower-limited,
47 kW eliminate the power-limited mark and:
EOL • Maintain a 1/4-inch (6.4 mm) space from power-
4 3 21
limited wiring.
7 2 TB1 6 3 2 1 or
• Use FPL, FPLR, FPLP, or an equivalent cable in
Input/Output Module accordance with the National Electric Code.
6 4 2 TB2
8 The Nomex isolation barrior separates power-limited
From loop controller Data in (+) 8 7 65 Data out (-)
To next device and nonpower-limited wiring. Watch out for the sharp
or previous device Data in (-) Data out (+) corners during installation and maintenance.
Red LED (Active/Alarm) Green LED (Normal/Trouble)

4 3 21
TB1

6 4 2
Input/Output
From loop controller Module
Data in (+) (personality codes 31out-(-)40)
Data
To next device
Typical Wiring
or previous device Data(GSA-MIO)
in (-) Data out (+)
5
Modules will accept #12 AWG (2.5mm2), #18 AWG (0.75mm2), #16 (1.0mm2), and #14 AWG (1.50mm2) wire sizes. Note: Sizes #16 AWG
(1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring
requirement specifications. 1 2 4
TB1 through TB6
Green LED (Normal/Trouble) Input/Output Module
Red LED (Active/Alarm) 1 23 4
Input/Output Module (personality codes 31 UIO2R
- 40)or UIO6R motherboard
4 3
Data In
5
4
Data 3 Wiring Notes:
Circuit 2
1 1 Maximum 25 Ohm resistance per wire. Maximum
1 TB72 4
TB1 through TB6 circuit capacitance of 0.1 mF.
Data Out
Green LED (Normal/Trouble) Input/Output Module 2
4
10 Vdc @ 350 mA, max.
Red LED (Active/Alarm) 1 23 4 No connections required
3 UIO2R
for MIO.or UIO6R
Other motherboard
modules
2 3 See the Signature loop controller installation sheet for
May require connections.
4 3 1 wiring specifications.
TB15
Data In Remove motherboard jumpers. 4 Supervised and power-limited

4 1 23 4 5 UL/ULC listed 47 kW EOL


Data
TB8 through TB13 3
Circuit 2 6 System programming determines whether contact
1
will be normally-open (N/O) or normally-closed (N/C).
TB7 7 6 Dry contact relay
Data Out 7 Power-limited unless connected to a nonpower-
4 No connections required limited source. If the source is nonpower-limited,
3
2
for MIO. Other modules eliminate the power-limited mark and:
May require connections.
1 • Maintain a 1/4-inch (6.4 mm) space from power-
TB15 limited wiring.
Remove motherboard jumpers. or
• Use FPL, FPLR, FPLP, or an equivalent cable in
1 23 4 accordance with the National Electric Code.
TB8 through TB13
8 See the UIO2R or UIO6R installation sheet for
additional instructions about the separation of power-
7 6 Dry contact relay limited and nonpower-limited wiring.

Page 4 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1
Signature Series Overview
The Signature Series intelligent analog-addressable system from Kidde Fast Stable Communication – Built-in intelligence means less information
is an entire family of multi-sensor detectors and mounting bases, needs to be sent between the device and the Signature Data Controller
multiple-function input and output modules, network and non-network (SDC). Other than regular supervisory polling response, Signature devices
control panels, and user-friendly maintenance and service tools. Analog only need to communicate with the SDC when they have something new
information from equipment connected to Signature devices is gathered to report. This provides very fast control panel response and allows a lower
and converted into digital signals. An onboard microprocessor in each baud rate (speed) to be used for communication on the circuit. The lower
Signature device measures and analyzes the signal and decides whether baud rate offers several advantages including:
or not to input an alarm. The microprocessor in each Signature device
provides four additional benefits – Self-diagnostics and History Log, • Less sensitivity to circuit wire characteristics.
Automatic Device Mapping, and Fast, Stable Communication. • Less sensitivity to noise glitches on the cable.
Self-diagnostics and History Log – Each Signature Series device • Less emitted noise from the data wiring.
constantly runs self-checks to provide important maintenance information.
The results of the self-check are automatically updated and permanently • Twisted or shielded wiring is not required.
stored in its non-volatile memory. This information is accessible for review
Diagnostic LEDs – Twin LEDs on most Signature devices provide visual
any time at the control panel, PC, or using the SIGA-PRO Signature
indication of normal and alarm-active conditions. A flashing green LED
Program/Service Tool.
shows normal system polling. A flashing red LED means the module is
Automatic Device Mapping –The Signature Data Controller (SDC) learns in alarm-active state. Both LEDs on steady indicates alarm-active state –
where each device’s serial number address is installed relative to other standalone mode.
devices on the circuit. The SDC keeps a “map” of all Signature Series
Testing & Maintenance – Automatic self-diagnosis identifies when a
devices connected to it. The Signature Series Data Entry Program also
Signature device is defective and causes a trouble message. The user-
uses the mapping feature. With interactive menus and graphic support, the
friendly maintenance program shows the current state of each device and
wired circuits between each device can be examined. Layout or “as-built”
other pertinent information. Single devices may be turned off temporarily, from
drawing information showing branch wiring (T-taps), device types and their
the control panel. Scheduled maintenance (Regular or Selected) for proper
address are stored on disk for printing hard copy. This takes the mystery
system operation should be planned to meet the requirements of the Authority
out of the installation. The preparation of “as-built” drawings is fast and
Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC
efficient.
536 standards.
Most Signature modules use a “personality code” selected by the installer
Quality and Reliability – Kidde Signature devices are manufactured in
to determine their actual function. Personality codes are downloaded
North America to strict international ISO 9001 standards. All electronics
from the SDC during system configuration and are indicated during
utilize surface mount technology (SMT) for smaller size and greater immunity
device mapping.
to RF noise. A conformal coating is used for humidity and corrosion
resistance.

Specifications
Model GSA-IO GSA-MIO
Description Standard Mount Input/Output Module Plug-in (UIO) Input/Output Module
North American 2½ inch (64 mm) deep one-gang boxes
Mounting and 1½ inch (38 mm) deep 4 inch square boxes with one- Plugs into UIO2R or UIO6R Motherboards only.
gang covers and GSA-MP mounting plates
Current
Standby 250 µA
Activated 430 µA
Relay type Form A or B
Contact ratings (pilot duty) 24 Vdc: 2 A. 120 Vac: 0.5 A (Not rated for capacitive loads.)
Initiating Device Circuit
EOL (end-of-line) resistor UL/ULC listed 47k Ohm
Max. circuit resistance 50 Ohm (25 Ohms per wire)
Max. circuit capacitance 0.1 µF
Wiring Terminations Suitable for #12 to #18 AWG (2.5 mm² to 0.75mm²)
Personality Codes Ten Selectable Codes Available
Address Requirements Uses One Module Address
Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Construction High Impact Engineering Polymer
Environment
Operating Temperature 32° F to 120° F (0° C to 49° C)
Storage Temperature -4° F to 140° F (-20° C to 60° C)
Humidity 0 to 93% RH
LED Operation On-board Green LED - Flashes when polled; On-board Red LED - Flashes when in alarm/active
Compatibility Use GSA-IO and GSA-MIO with: Signature Loop Controller Plug GSA-MIO into: UIO6R or UIO2R Motherboards
Agency Listings UL, ULC, MEA, CSFM

Page 5 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1
Ordering Information
Catalog Ship Wt.
Description
Number lbs (kg)
0.34
GSA-IO Input/Output Module (Standard Mount) - UL/ULC Listed
(0.15)
0.22
GSA-MIO Input/Output Module (Plug-in) - UL/ULC Listed
Technology that saves lives (0.10)

Contact us Related Equipment


Phone: 888.244.9979 (Option 4) 27193-11 Surface Mount Box - Red, 1-gang 2 (1.2)
Email: [email protected] 27193-16 Surface Mount Box - White, 1-gang 2 (1.2)
Website: kidde-esfire.com Universal Input-Output Module Board w/Riser Inputs 0.32
GSA-UIO2R
Kidde is a Carrier brand.
- Two Module Positions (0.15)
8985 Town Center Pkwy, Universal Input-Output Module Board w/Riser Inputs 0.62
GSA-UIO6R
Bradenton, FL 34202 - Six Module Positions (0.28)
UL listed cabinet for mounting releasing modules, red with white
MFC-A 7.0 (3.1)
© 2020 Carrier “FIRE”.
All rights reserved.
Transponder Mounting Bracket (allows for mounting
GSA-MB4 0.4 (0.15)
two 1-gang modules in a 2-gang box)
GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
1.02
GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint
(0.46)

04-04-20

Page 6 of 6 D ATA S H E E T K85001-0533


Not to be used for installation purposes. Issue 1.1