5SYA 2110-01 - SEMIS For 6 Pulse Controlled Rectifier - User Manual
5SYA 2110-01 - SEMIS For 6 Pulse Controlled Rectifier - User Manual
5SYA 2110-01 - SEMIS For 6 Pulse Controlled Rectifier - User Manual
Figure 1. Page layout of six pulse controlled rectifier in ABB semiconductors website.
The circled elements shown in grey colour in the circuit schematic above can be clicked to enter the user defined values.
2.1.1 Supply
The user can select the desired AC line to line voltage. If the voltage across the thyristor exceeds its maximum surge peak forward and
reverse blocking voltage limit, the user will get overvoltage alarm message. To calculate the required maximum surge peak forward and
reverse blocking voltage for a given line to line voltage, the following formula is used.
Where VLL is line to line voltage and k is the expected safety factor. The choice of k=2 is given as arbitrary default value, however this value
can be changed by the user. It depends on the expected network conditions.
The user can select the desired thyristor product names for simulation. Up to 4 elements can be selected simulatenously and simulated.
If one or more elements produce results that are exceeding the safe operating area (SOA) the simulation will stop. In this case the user
should run the simulation again changing parameters and/or product selection suitably, so that the results are within SOA.
The value entered is attributed to each individual switch shown in the electrical configuration schematic of the thyristor
module data sheet.
3 Output results
As soon as the user has defined all necessary parameters the simulation can be started by pressing the relevant button. The output
results are displayed in two different ways. They are graphical output and numerical output (listed in tables). When the simulation
finishes, the semiconductor as well as both AC and DC side waveforms will appear as shown in Figure 10:
5 Clicking on button allows to zoom in by scrolling on the desired waveform and clicking on button resets
initial view.
2 Converter AC parameters
Conduction losses: Losses during on state (Static) based on ABB data sheet values.
All types of semiconductor losses are calculated according to PLEXIM software principle through reference of look up table.
Converter losses: Aggregated amount of losses on all consisting semiconductor elements of the converter (e.g. 6 x loss
across each thyristor for 6 pulse circuit)
Average junction temperature: Mean value of generated waveform for junction temperature for each semiconductor.
Losses (%): Defined as the (%) ratio of calculated combined converter losses to the input power depending on converter
operation.
AC frequency: Frequency of the fundamental harmonic of the AC waveforms for voltage and current in AC side of converter
(defined by user through the controller block).
Phase voltage (RMS): AC phase value according to 1st order harmonic of AC frequency.
Phase current (RMS): AC phase value according to 1st order harmonic of AC frequency.
Reactive power: Effective power on converter AC side calculated as: Q = 3 * Vph * Iph * sin(θ) where Vph, Iph, θ stand for phase
voltage (RMS), phase current (RMS) and power factor angle respectively.
Real power: Effective power on converter AC side calculated as: P = 3 * Vph * Iph * PF, where Vph, Iph, PF stand for phase voltage
(RMS), phase current (RMS) and power factor respectively.
DC side results:
DC voltage: The value of DC voltage is calculated accounting the user inputs for alpha angle and commutation inductance Ls
using the following equations.
Average thyristor current: Current flowing through each thyristor device of the converter . Equals to one third of the average
DC current defined by the user.
5SYA 2110-01 December 2016 SEMIS – Simulation Tool for 6 pulse Controlled Rectifier
ABB Switzerland Ltd. Note
Semiconductors We reserve all rights in this document and in the
Fabrikstrasse 3 subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
5600 Lenzburg, Switzerland
utilization of its contents – in whole or in parts – is
Phone: +41 58 586 1419 forbidden without prior written consent of ABB AG.
Fax: +41 58 586 1306 Copyright© 2014 ABB
E-Mail: [email protected] All rights reserved
www.abb.com/semiconductors