H2 02 P2 GRS E.3 PRO 24003 Factory Acceptance Test Procedure (FAT) - Reply

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

PUBLIC RESTRICTED CONFIDENTIAL SECRET

H2-02 DATACENTER - PHASE 2


PROJECT

Project Name H2-02 DATACENTER PHASE 2


Vendor Name PT. BERKAT MANUNGGAL ENERGI
Purchase Order No #PO/DISM/24/01/0007
Equipment Tag No

Project Document No H2-02-P2-GRS-E3-PRO-24003

DOCUMENT TITLE FACTORY ACCEPTANCE TEST PROCEDURE (FAT)

DOCUMENT REVIEW STATUS

CODE A Approved - With No Comments. Document is accepted as Final. Supplier shall proceed with manufacture. Any changes to
the document shall require resubmission to Purchaser.

CODE B Approved with Comment Incorporated . Work may proceed subject to incorporation of comments. Supplier may
continue for puchase of material & manufacture pending full acceptance. A revised copy shall be returned for final acceptance.

CODE C Rejected. Revise and Resubmit. WORK MAY NOT PROCEED.

CODE D For Information Only. No further action required at time of submission.

Clarify generator 12 hrs burn in test with DISM BOQ.

Submission Record

0 1-Feb-24 APPROVAL DD RS HT

Rev.
Date Purposes for Submission Prepared Checked Approved
No

DISM - H2-02-P2
4
4
4
4
4
4
4
4
4

2000
4
4
4
4
4
TEST RECORD OF MITSUBISHI GENERATOR SET
Messrs

MODEL :
CUSTOMER : PROJECT No. :

BAROMETRIC FUEL OIL SPECIFIC


DIVISION TEST DATE WEATHER FUEL OIL LUB. OIL
PRESS. GRAVITY
FINE CLOUDY LIGHT OIL SAE 30
MFR'S TEST
RAINY SNOWY HEAVY OIL SAE 40

FINE CLOUDY LIGHT OIL SAE 30


WITNESS
RAINY SNOWY HEAVY OIL SAE 40

ENGINE SPECIFICATION GENERATOR SPECIFICATION


MAKER : MAKER :

MODEL & SERIAL No. : MODEL & SERIAL No. :

RATED OUTPUT : RATED OUTPUT :


kW rpm kVA kW
CLY.No. X BORE X STROKE VOLTAGE : CURRENT :
Cyl. X mm V A
TOTAL DISPLACEMENT : FREQUENCY : POWER FACTOR :
L Hz ø
INJECTION TIMING : PHASE : POLES :
BTDC
HEAT DIRECT
COOLING METHOD : RADIATOR RULE : MFG DATE :
EXCHANGER COOLING
IP23
STARTING METHOD : RADIATOR SPECIFICATION
ELECTRIC MODEL/PART NUMBER &
GOV. TYPE MECHANICAL HYDRAULIC ELECTRIC SERIAL NO:
STATUS
TURBO MODEL :
OK NOT OK
INJ. PUMP MODEL OR PART No. :

ENG, MFG. DATE GOVERNOR


TRIMMER SETTING
SETTING
CON-ROD RANK DR Rated Speed: -
GAIN
I Low idle:
D Rated Volt: 4-80

APPROVED BY

CHECKED BY

TESTED BY
ENGINE NUMBER
V Confirmation at WITNESS TES

PROTECTIVE DEVICE TEST @ Confirmation working by means of


making contact
ENGINE TRIP
No ITEM SETTING WORKING INDICATION
STOP SIGNAL
1 EMERGENCY STOP Press Button CLOSE OPEN
2 L/O LOW OIL PRESS BAR PRESSURE NORMAL 6 - 7 BAR 3,91 ALARM 1,5
3 C/W HIGH TEMP CELCIUS NORMAL 69 -92 96 ALARM 101
4 OVERSPEED RPM 1499 - 1501 1650 1750
ENGINE NUMBER
LOAD TEST STANDARD TEST
START 10:00 10:05 10:15 10:25 10:35
TIME
FINISH 10:05 10:15 10:25 10:35 10:55 REMARKS
Minutes 5 10 10 10 20
LOAD % 0 25 50 75 100
OUTPUT KW
VOLTAGE V
L1 A
LOAD CURRENT L2 A
L3 A
GENERATOR

POWER FACTOR
FREQUENCY Hz
o
INLET C
COOLING AIR TEMP o
OUTLET C
o
AMBIENT TEMP C

SPEED Rpm
Flow Meter
Consumption
FLOW METER
Liter/hours

o
COOLING WATER TEMP C
LUBE OIL PRESS Bar
ENGINE

o
INLET AIR TEMP C
o
EXHAUST GAS TEMP C
o
RADIATOR INLET C
DC VOLTAGE ALTERNATOR VDC