MCCPLBTGOPER 042 - SOP For COAL MILL LOP
MCCPLBTGOPER 042 - SOP For COAL MILL LOP
MCCPLBTGOPER 042 - SOP For COAL MILL LOP
SECTION- O&M
Revision # R-0
Implementation Date
1. Purpose
Purpose of the SOP is to use it as instructions for the safe startup and
normal operation of COAL MILL Fan lube oil pump.
2. Equipment specifications
EQUIPMENT DETAIL:
2.1 MODEL -OWTSO9
2.2 Pump discharge flow - 175 L / min
2.3 Oil pump type screw
2.4 Oil temperature - Running value 30°C~45°C
2.5 Oil type -ISO VG 46
Implementation Date
3. Scope
The scope of this document is limited to 2X100% oil pump with all its related
auxiliary equipment.
4. Prerequisites
4.1 Mechanical healthiness of the Lube oil pumpshould be healthy i.e. no
mechanical defect in the equipment.
4.2 Stand by lube oil pump should be available.
4.3 Lube Oil tank level should be normal (~80%) and oil quality should be
qualified (NAS- 7).
4.4 All protections and trip interlock should be healthy and in service.
4.5 All transmitter signals should be healthy and in service.
4.6 All local pressure gauges are healthy condition.
5. Responsibilities
5.1 Shift In charge - Coordination between field and
DCS
5.2 BoilerControl room engineer -For operating and monitoring the
Equipment from CCR
5.3 Boiler field engineers - For inspection and reporting
6. Procedure
5.1 Preparation for startup
5.1.1 Be sure that all related equipment PTW has been cancelled.
5.1.2 Ensure that operator is available near the equipment for giving the start
clearance from field by using proper communication device i.e. walkie-talkie.
5.1.3 Ensure that Lube oil tank level is slightly higher than normal oil level (>80%)
and oil quality is qualified (NAS-7).
5.1.4 Ensure that Lube oil pump power supply is in healthy condition.
5.1.5 Ensure tank oil temp > 30 Degree C IF it is <30 Degree C start heater to
achieve temp.
5.1.6 Ensure that oil cooler I/L& O/L isolation valves (of both stream - oil and
Implementation Date
Implementation Date
5.3.10 Stop the previous running pump.. Put the second Lube oil pump into
STANDBY MODE.
6.4.1 Ensure that unit condition fulfills the shutdown requirements of running Lube
oil pump.
6.4.2 Drives bearing temp cooled and its value <40degc
6.4.3 Release standby Lube oil pump from STANDBY MODE to NORMAL MODE.
6.4.4 Stop running Lube oil pump
6.4.5 Isolate the pump if required.
Implementation Date
6.7.1 Communicate the field operator regarding changeover of Lube oil filter.
6.7.2 Ensure that Lube oil pump pressure is normal.
6.7.3 Ensure that cooler changeover lever is extreme end position.
6.7.4 Rotate the lever slowly by observing pressure, When Small jerk observed
stop rotation and hold the same position till pressure constant,
Above practice is continuing till both valves rest at ends.
6.7.5 Same Observe lube oil supply pressure normal and in field DP indicator is in
green position.
6.7.6 Declare lube oil filter change over done
7. References