0% found this document useful (0 votes)
138 views10 pages

Copeland Scroll Parallel

This document provides guidelines for using Copeland scroll compressors in parallel configurations for refrigeration applications. Key points include: - Oil control is important to maintain adequate lubrication, with options like individual oil regulators or equalization lines between compressor sumps. - Tubing stress must be considered if compressors are mounted closely, to avoid issues from starting pulses or resonance. - A logical running sequence is recommended so compressors run equal times. - Model ranges and oil charge quantities are specified for different compressor models. Additional design points are also outlined.

Uploaded by

Behnam Ashouri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views10 pages

Copeland Scroll Parallel

This document provides guidelines for using Copeland scroll compressors in parallel configurations for refrigeration applications. Key points include: - Oil control is important to maintain adequate lubrication, with options like individual oil regulators or equalization lines between compressor sumps. - Tubing stress must be considered if compressors are mounted closely, to avoid issues from starting pulses or resonance. - A logical running sequence is recommended so compressors run equal times. - Model ranges and oil charge quantities are specified for different compressor models. Additional design points are also outlined.

Uploaded by

Behnam Ashouri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Refrigeration Scroll

for Parallel Applications

Application Guidelines
APPLICATION GUIDELINES: COPELAND SCROLL SCROLL COMPRESSORS IN
PARALLEL FOR REFRIGERATION APPLICATIONS

1 Introduction ................................................................................................................................................................2
2 Definitions ..................................................................................................................................................................2
3 Model Range .............................................................................................................................................................2
4 Parallel Application Considerations ...........................................................................................................................3
5 Oil Control using Regulators......................................................................................................................................3
5.1 Low Pressure Oil Reservoir .................................................................................................................................3
5.2 High Pressure Oil Reservoir ................................................................................................................................4
6 Oil Equalisation Lines without Active Oil Control.......................................................................................................4
6.1 Oil Equalisation Tube at Sight Glass Position .....................................................................................................4
6.2 Gas and Oil Equalization Tube at Sight Glass Position.......................................................................................5
6.3 Suction Line Configuration...................................................................................................................................5
6.4 Oil Equalization Line ............................................................................................................................................6
6.5 Oil and Gas Equalization plus Oil Regulator .......................................................................................................6
7 Oil Return to Running Compressors..........................................................................................................................6
8 Tubing and Mounting Considerations........................................................................................................................7
8.1 Starting Pulse.......................................................................................................................................................7
8.2 Resonance...........................................................................................................................................................7
8.3 Recommendations for Tubing and Mounting.......................................................................................................7
9 Additional Design Points............................................................................................................................................8
9.1 Check valves and Pump Down............................................................................................................................8
9.2 Heat Exchangers for Economised Scrolls (Vapour Injection)..............................................................................8

C6.2.5/0504-0904/E 1
1 Introduction
The concept of parallel operation for refrigeration scroll compressors brings several benefits:
Efficient Capacity Control:
If the load or ambient conditions change, compressors can be switched on and off to match capacity
requirements. This is more efficient than running larger semi-hermetic compressors at part load and also will
generally give a better power factor. Use of unequal compressors allows many capacity possibilities.
Redundancy:
If one compressor cannot run for any reason, the load can often be met by the remaining compressors.
Ease of Service:
If a compressor needs to be changed for any reason, the small, lightweight nature of the scroll makes this a
much less costly operation and causes much less disruption. This is particularly true for the 3 - 6 hp models.
Matching Several Evaporating Conditions:
If there are two or more temperatures to be controlled, individual compressor(s) can be matched to each
evaporator while working on a single condenser circuit, and this will give power savings compared with an
alternative system working at one (the lowest) suction pressure.
Parallel operation of compressors is not new, but scroll compressors have no positive displacement oil pump, and
therefore no oil pressure switch. The high performance Teflon® bearings provide protection for short periods in case
of oil losses, but sustained running at high-pressure differences without lubricant will fail the bearings. In order to
ensure adequate protection it is necessary to observe the following guidelines.

2 Definitions
Oil Equalisation Line:
Tubing connecting compressor sumps at or below oil level.
Regulator
A device to meter oil into a compressor sump, and control the oil level within limits.
Oil Charge Supplied:
Oil quantity supplied by Copeland when compressor is shipped.
Maximum Oil Quantity:
Maximum amount of oil recommended. Above this amount the oil level will be above the sight glass and could
be too high affecting power consumption.
Minimum Oil Quantity:
Minimum amount of oil recommended. Below this amount lubrication may be insufficient and so the life of the
compressor may be shortened.
Oil Recharge Quantity:
Amount of oil to refill compressor after drain the oil.

3 Model Range
Oil charge Oil charge
Model Name HP
supplied [l] quantity [l]
ZB15 2 1,0 1,0
ZB19 2,5 1,0 1,0
ZF09 ZS21 ZB21 3 1,24 1,12
ZF11 ZS26 ZB26 3,5 1,24 1,12
ZF13 ZS30 ZB30 4 1,95 1,83
ZF15 ZS38 ZB38 5 1,95 1,83
ZF18 ZS45 ZB45 6 1,77 1,66
ZF24 ZS56 ZB56 7,5 4,14 4,05
ZF33 ZS75 ZB75 10 4,14 4,05
ZF40 ZS92 ZB92 13 4,14 4,05
ZF48 ZS11M ZB11M 15 4,14 4,05
Tab 1: Model Range
Note: Air-conditioning type applications may use ZR models in parallel. Due to operating envelope limitations ZR
models are not normally suitable in Refrigeration applications.

C6.2.5/0504-0904/E 2
4 Parallel Application Considerations
If compressors are required to operate in parallel it is normally necessary to stop and start them independently for
capacity control purposes. There are three major considerations in this type of application:
Oil control:
An adequate oil level at all times is necessary to maintain lubrication of the bearings. Too much oil can result
in inefficient operation and excessive oil carry over to the system.
Tubing Stress:
If compressors are mounted close together, care must be taken to ensure that there is sufficient flexibility in
the tubing. If this is not done the starting pulse may result in excess stress at the mounting positions and
eventually give rise to a leak. Also tube resonance should be avoided.
Running sequence:
A certain logical sequence control is recommended so that each compressor runs for the same amount of
time.

5 Oil Control using Regulators


Individual oil control for each compressor is the safest method. Each compressor can be fitted with a regulator which
supplies oil only when required. Oil carried over to the system is replaced via the regulator when insufficient oil is
being returned from the system. A reservoir of oil is provided, and hence variations in oil quantity in the system can be
accommodated. There are many refrigeration scroll compressors operating today with regulators and this method is
recommended by Copeland provided that certain design points are observed. Because the scroll compressor has no
positive displacement oil pump and no oil pressure switch, it is recommended that the oil control system incorporates
protection as detailed below. It will be necessary to add oil to the system and the Copeland approved lubricants are:

HFC-refrigerants: Mobil EAL Arctic 22 CC


HCFC-refrigerants: Suniso 3GS

5.1 Low Pressure Oil Reservoir


This is the traditional method used also in many piston compressor systems. The oil reservoir is maintained at a
pressure slightly above the compressor sump pressure and this limits the amount of refrigerant dissolved in the oil in
the reservoir. The pressure drop is low when the oil enters the compressor and the amount of flash gas formed in the
sump is small.

Float switches or other devices can be used as regulators. It is recommended that the regulator has an electrical
output which can be wired into the control circuit and stop the compressor if the oil level falls below the minimum level
and remains below the minimum level for a period of time (maximum 2 minutes). This protects against failure of the oil
supply to the individual compressor. A level switch in the reservoir will only protect against insufficient oil in the
receiver, but not against loss of oil supply to an individual compressor or against a fault on an individual regulator.
Regulators currently on the market, which meet these requirements, include AC&R S9040 and the ALCO OMA
Traxoil. The Traxoil requires the oil reservoir to be pressurized to 3.5 bar above suction pressure for reliable
operation.

When using a regulator care must be taken to set the oil level in the upper half of the sight glass. If an adapter is
used to connect the regulator this may have a smaller internal diameter than the glass and this could give rise to a
false oil level reading.

When commissioning these systems it is important to allow sufficient time for equilibrium running conditions to be
attained. Because the oil carry over rate from the scroll compressors is low it may take some time for stable oil
quantities to build up in the coolers. Until this has happened the total oil requirement of the system cannot be
determined.

C6.2.5/0504-0904/E 3
S1
Model
Oil Level Control
Functions:
- Oil Fill Yes
- Alarm Yes
- Compressor Lockout Yes
Set point ½ Sight glass
Switch/Relay release time 120 sec
Reset mode/Time delay Auto/ 13 sec
Oil connection ¼“ flare
MOPD psi/bar 300/ 20,7
Max. working pressure psi/bar 400/ 27,6
0,4 A, 125 V
Contact ratings
0,2 A, 250 V
Solenoid Coil type/Watts MCK-1/10W
Fig 1: Alco OMA Traxoil Tab 2: Properties OMA Traxoil

5.2 High Pressure Oil Reservoir


The need for a separate oil receiver may be avoided if a combined separator/receiver is used, but in this case the oil
will be stored at discharge pressure. It will therefore cause much more disturbance and foaming when it enters the
compressor sump. For this reason it is desirable to limit the quantity of oil entering the sump when the valve opens.
The Alco OMA Traxoil (see Fig 1) is suitable for this type of application and has been proven to operate satisfactorily
with a high pressure oil supply.
6 Oil Equalisation Lines without Active Oil Control
Simple systems, which link the compressor sumps via tubes with no control are obviously attractive. They are quite
common on air-conditioning applications, but in refrigeration additional considerations apply. They can, of course, only
be considered for compressors working at a common suction condition.
If there are large variations in oil quantity in the system due to changing conditions or defrost this may result in too
much or too little oil in the compressors. Usually the only means of checking oil level is via the sight glass connection.
Once the oil level is above the sight glass it is not possible to determine if the maximum oil quantity is reached.
Likewise if no oil is visible in the sight glass, there is a danger of operation below the minimum quantity.
A tube connecting the oil level adjustment valves on the compressors is not adequate because when a compressor is
stopped, the pressure in the shell rises and oil will transfer to the running compressor(s). The adjustment valve is
located below sight glass level and therefore the stationary compressor will show no oil level. Even if all compressors
run together at all times, there will be small pressure differences which will cause the same effect.

Alternative methods using the sight glass connections for oil equalisation connections have been shown to work on
specific systems. Notes are given below on some possible methods, but because of wide variations in system design
and operating conditions, these methods cannot be given general approval by Copeland. The user has to verify
operation in each system type.

6.1 Oil Equalisation Tube at Sight Glass Position


Generously sized suction lines will minimise the flow along the oil connecting tube but will not eliminate it. Use of a
large diameter oil header tend to reduce oil transfer. Certain gas pressure equalisation designs have been shown to
be satisfactory but each one has to be tested and proven.

C6.2.5/0504-0904/E 4
6.2 Gas and Oil Equalization Tube at Sight Glass Position
Copeland has conducted tests to prove the satisfactory operation of up to
three compressors in parallel using a gas and oil equalising tube. The
configuration of suction line and equalization line should be as described
below (6.3 and 6.4).
This method can be used for:
Two or three ZF, ZS, ZB Refrigeration Scroll Compressors
No uneven configurations (all same model)
All voltages
Refrigerants R404A, R507, R22
Same operating envelope as single compressor with injection
where required
Adequate liquid flood back protection must be provided
Any sequence/combination of compressors is allowed
Fig 2: Scrolls in Parallel

Model Applicability

ZB15 KCE
ZB19 KCE
ZF09 K4E ZS21 K4E ZB21 KCE
ZF11 K4E ZS26 K4E ZB26 KCE
ZF13 KVE ZF13 K4E ZS30 K4E ZB30 KCE
ZF15 K4E ZS38 K4E ZB38 KCE
ZF18 KVE ZF18 K4E ZS45 K4E ZB45 KCE
ZF24 KVE ZF24 K4E ZS56 K4E ZB56 KCE
ZF33 KVE ZF33 K4E ZS75 K4E ZB75 KCE
ZF40 KVE ZF40 K4E ZS92 K4E ZB92 KCE
ZF48 KVE ZF48 K4E ZS11 M4E ZB11 MCE
Tab 3: Model Applicability

6.3 Suction Line Configuration


An adequately sized suction header providing equal distribution of returning refrigerant and oil to each individual
compressor must be used. The non-symmetrical design as shown below is acceptable and does not create oil level
problems between the compressors.

Fig 3: Oil Return Fig 4: Suction Line Configuration

C6.2.5/0504-0904/E 5
6.4 Oil Equalization Line
The oil equalization line between the two or three compressors must be at least 7/8” (22 mm) with a minimum inner
diameter of 19 mm. On no account must the internal diameter of any fitting in this line be less then 19 mm. Adaptors
to fit to the sight glass connection on. It is strongly recommended that these are used. Kits consisting of the adaptor
shown below, plus conversion to brazed connections are available (see spare parts lists for details). The equalization
tube must be level, and the compressors must be mounted level. Tests have shown that smaller tube diameters do
not provide proper oil balancing. An oil separator may be used and the oil return line from the separator should be
connected to the oil equalization line.
If no oil separator is installed the oil returns into the suction header and is picked up there from the individual
compressor suction lines.
Adaptor for Oil Sight Glass Connection
3/4“ - 14 NPTF
1 1/4“ –12 UNF

Notes:

Tightening Torque:
41-54 Nm

Use Loctite String:


7/8“ Everseal 483 White Pipe Sealant

Fig 4: Adaptor for oil sight glass connection

6.5 Oil and Gas Equalization plus Oil Regulator


If the Traxoil or other device is fitted to the equalization line (one device serving 2 or 3 compressors) the proper
functioning of the system has to be checked to ensure that no nuisance tripping occurs. The Traxoil sight glass,
remote from the sump, does not always accurately follow the sump oil level. The oil separator must be of the
combined separator/reservoir high pressure type, or alternatively a separate oil reservoir may be used if the separator
has its own float valve. The separator float valve outlet must not be connected directly to the Traxoil.

7 Oil Return to Running Compressors


Systems without active oil control are covered in section 6. For systems using oil regulation it is still recommended to
arrange for oil to be returned to the running compressors. If oil returns to the compressor at approximately the same
rate as it leaves, then the oil level will be maintained. It is always preferable to design the suction manifold in such a
way that oil returning with the suction gas can only enter the running compressor(s). This can be done in a number of
ways. Perhaps the most common is to use a suction header with vertical pick ups to each compressor which induce
sufficient velocity to lift the oil. Again, certain designs have been shown to be satisfactory but each one has to be
tested proven. With some system designs this is sufficient to ensure adequate oil level at all times, but there is no fail
safe pressure switch if one compressor loses oil.

Fig 5: Suction Lines to Compressors – Recommendation

C6.2.5/0504-0904/E 6
8 Tubing and Mounting Considerations

8.1 Starting Pulse


The standard mount for the scroll compressor is a soft rubber mount. This is designed to transmit the lowest possible
disturbance to the mounting frame. Because of the flexibility of this mount, it is essential that tubing to each
compressor is designed to accommodate the movement which will occur, particularly on start up.
The three phase motors used in the refrigeration scroll compressors exhibit a high starting torque characteristic. The
reaction of the stator is directly on the shell because there are no internal spring mounts. This reaction causes easily
observable movement of the shell when the standard mounts are used and this is normal. However, if the suction and
discharge tubing of the compressor is closely clamped to the frame or linked to another compressor, the tubing will
restrain the movement – the motor reaction force will be taken by the tubing and may cause excessive stress and
premature failure of tubing joints.
Care should be taken to avoid this situation in parallel arrangements of compressors where it is desired to minimise
the space between them (see also 8.3.).

8.2 Resonance
The discharge pulse can in some configurations give rise to resonance of tubing. It is desirable to avoid a natural
frequency of between 45 and 55 Hz for the section of tubing between the compressor and the first clamp. Often it is
not possible to determine this in advance, but in the unlikely event of a resonance problem arising, a change in tube
configuration will usually resolve it.

8.3 Recommendations for Tubing and Mounting


Always allow some flexibility in the tubing to the suction and discharge connections. If the standard mounts are used
there should be at least two bends and a vertical section before the tube joins a header. Test the finished assembly
by rocking the compressor on its mounts. Vibration eliminators may be used but are not essential if the tubing has
sufficient flexibility. Vibration eliminators should be fitted in the vertical plane.
An alternative harder mount as detailed in Fig. 7 is recommended. This will allow more loads to be transmitted via the
feet, and the very small additional vibration transmission is not usually a problem in refrigeration applications. It is still
desirable to incorporate a vertical section of tube between the compressor and the first rigid mount. This will give
flexibility and minimise the risk of resonance.

Fig 6: Tubing Recommendation Fig 7: Mounting Parts for Multiple Operation

C6.2.5/0504-0904/E 7
9 Additional Design Points
The topics described in the Application Guidelines are applicable. The following additional points are for parallel
installations.

9.1 Check valves and Pump Down


Pump down is not normally used or necessary for parallel Scroll installations. All Scroll compressors are fitted with an
internal check valve, and ZF/ZS models have a dynamic discharge valve also. Therefore external check valves are
not needed.

9.2 Heat Exchangers for Economised Scrolls (Vapour Injection)


A single heat exchanger may be used in multiple compressor installations. A plate heat exchanger with a single circuit
on the liquid side, and multiple circuits on the vapour side is a good solution (see Fig. 8 & 9 below). It is essential that
solenoid valves are fitted to ensure that refrigerant is not fed to the injection port of a stationary compressor.
If a single circuit heat exchanger is used, the solenoid valves must be fitted in the vapour lines as shown in the figures
below. A TEV can be used to regulate the injection. Depending on the configuration, the operational envelope may be
restricted due to higher vapour temperatures than with the capillary tube. Discharge temperature thermostats should
always be fitted.

Fig 8: Heat exchanger configuration example 1 Fig 9: Heat Exchanger configuration example 2

C6.2.5/0504-0904/E 8
Benelux Eastern Europe, Turkey & Iran
Deltakade 7 27, Rue des Trois Bourdons
NL-5928 PX Venlo B-4840 Welkenraedt
Tel. +31 (0) 77 324 0234 Tel. +32 (0) 87 305 061
Fax +31 (0) 77 324 0235 Fax +32 (0) 87 305 506

Deutschland/Österreich & Schweiz Poland


Senefelder Straße 3 11A, Konstruktorska
D-63477 Maintal P-02-673 Warszawa
Tel. +49 (0)6109 6059 0 Tel. +48 225 458 9205
Fax +49 (0)6109 6059 40 Fax +48 225 458 9255

France/Greece & Maghreb Russia & CIS


8, Allee Du Moulin Berger Malaya Trubetskaya, 8-11th Floor
F-69130 Ecully RUS-119881 Moscow
Tel. +33 (0)4 78668570 Tel. +7 095 232 94 72
Fax +33 (0)4 78668571 Fax +7 095 232 03 56

Italia Middle East & Africa


Via Ramazzotti, 26 PO Box 26382, R/A 8, FD-2
I-21047 Saronno (va) Jebel Ali, Dubai - UAE
Tel. +39 02 961781 Tel. +9714 883 2828
Fax +39 02 96178888 Fax +9714 883 2848

España & Portugal Asia/Pacific


Diputacion, 238 AT.8 10/F, Pioneer Building, 213 Wai Yip Street,
E-08007 Barcelona Kwun Tong, Kowloon - Hong Kong
Tel. +34 93 4123752 Tel. +852 28 66 31 08
Fax +34 93 4124215 Fax +852 25 20 62 27

UK & Ireland Latin America


Colthrop Way 7975 North West 154Th Street - Suite 300
GB- Thatcham, Berkshire - RG19 4 NQ Miami Lakes, FL, 33016 - USA
Tel. +44 (0)1635 87 6161 Tel. +1 305 818 8880
Fax +44 (0)1635 877111 Fax +1 305 818 8888
C6.2.5 / 0504-0904/E

Sweden/Denmark/Norway & Finland


Östbergavägen 4, P.O.Box 10
S-59021 Väderstad
Tel. +46 (0) 142 70520
Fax +46 (0) 142 70521

Copeland Marketing & Sales - 27, Rue des Trois Bourdons - B 4840 Welkenraedt, Belgium
Tel. +32 (0) 87 305411 - Fax +32 (0) 87 305506 - internet: www.ecopeland.com - email: [email protected]
The Emerson logo is a trademark and service mark of Emerson Electric Co. Copeland Corporation is a division of Emerson Electric Co. Copeland is a registered trademark and Copeland Scroll is
a trademark of Copeland Corporation. All other trademarks are the property of their respective owners. Information contained in this brochure is subject to change without notification.
© 2004 Copeland

You might also like