The first control engineering lab was the simulation of a proportional liquid level system with the aid of matlab. According to this lab the 2nd lab was to perform a control of a real liquid level system. Different controller types could be applied to it and via a digital storage oscilloscope the behaviour of the system was to obtain.
Vin
Vh
Controller
Pump
Tank
The schematic above shows the block diagram of the used liquid level control system. The controller drives the pump which fills the tank with water. The backward signal transfers the water level back to the input. The controller could be changed in its characteristics between proportional. integral. derivative. some of them and all together to change the properties of the control-process.
Page 3 of 11
Water level /cm Sensor voltage / V 10 0.4 20 0.85 40 1.65 60 2.42 80 3.22 100 4 120 4.77 140 5.55 150 6 160 6.35 180 7.19 200 8.03 220 8.81 240 9.59
Sensor Characteristics
10 9 8 Sensor Voltage/V 7 6 5 4 3 2 1 0 10 20 40 60 80 100 120 140 160 180 200 220 240 Water Level/mm
The liquid level sensors works linear A higher liquid level provides a proportional higher output voltage.
Page 4 of 11
5. Different controllers
a) Proportional controller
Pump Voltage u(t)
Proportional Controlle gain k=10
Vin
Vh Pump Tank
With the proportional control only the difference of the actual liquid-level and the input voltage (error signal) is amplified and directly fed to the pump. Therefore the proportional control doesnt reach the desired setting point of 150mm, because the end value depends very much on the value of k. The following plot from the oscilloscope shows this.
Figure 1 Transient response plot of the proportional controller with gain k=10
Page 5 of 11
Vin
Vh Pump Tank
The combination of the integral and the proportional controller brings an improvement to the system by reducing the final error e. Now the output reaches the desired input (6V==150mm). The integral part brings a short oscillation with over and- under-shots to the system before it settles.
Page 6 of 11
Vin
Vh Pump Tank
The overall performance of the system increases, when the integral part is reduced and the proportional factor is left constant. This reduces the oscillating and results only in one overshot, after which the outputs settles to its desired value.
Figure 3 Transient response with ki=1 and kp=10 =13s, ts=45s, e=0per cent
Page 7 of 11
Vin
Vh Pump Tank
Adding a derivative controller to the proportional one brings no big difference. The output never reaches the desired input value and the derivative controller brings no improvement to the time constant or the settling time.
Figure 4 Proportional and derivative controller with kp=10 and kd=10 =17s, ts=40s, e=7per cent (6V/0.4V)
Page 8 of 11
Vin
PID gains kp + ki + kd
Vh Pump Tank
From the other parts it should be expected, that a combination of all three controllers brings the best result, but the transient response shows, that the settling time t increases and the systems tends to oscillate.
Figure 5 Transient respone with kp=10, ki=10 and kp=10 =12s, ts=55s, e=0
Page 9 of 11
6. Comparision
Part a) b) c) d) e) P 10 10 10 10 10 I 0 10 1 0 10 D 0 0 0 10 10 10 16 13 17 12 ts 25 48 45 40 45 E 7 2 0 7 0
From the above table it can be said, that part c) and e) produce the best result. From the transient response part c) has the best overall performance:-No oscillation - Output value = desired - Reasonable settling-time The following graph shows part c) with the occurring error signal.
At the beginning the pump voltage increases to its maximum. Then, when the output reaches its desired value the pump-voltage drops, the output overshoots and due to the negative error signal the output decreases until it has settled down to the end-value of 150mm or 6V. So the PI controller is the best solution for this system.
Page 10 of 11
7. Conclusion
In difference to the first lab, where only a simulation with a simple proportional controller was to do, in this Lab the difference between a range of controllers could be seen. Also it could be obtained, that not a mixing of all three used controller types results in the best solution. Hence its very important to choose the right type and structure of arrangement the when a control system is to be designed.