TSC WSC Ysc 3 A 10 TR R410.cleaned
TSC WSC Ysc 3 A 10 TR R410.cleaned
TSC WSC Ysc 3 A 10 TR R410.cleaned
Packaged Gas/Electric
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . 11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model Number Description . . . . . . . . . . . . . . . . . . . . 13
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . 102
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . 119
RT-PRC023-EN 3
Features and Benefits
4 RT-PRC023-EN
Features and Benefits
RT-PRC023-EN 5
Features and Benefits
8 RT-PRC023-EN
Features and Benefits
valuable information helped to ReliaTel Makes Installing and Intelligent Fallback is a benefit to the
design a product that would get the Servicing Easy building occupant. If a component
serviceman off the job quicker and goes astray, the unit will continue to
ReliaTel eliminates the need for field
save the owner money. Precedent operate at predetermined
installed anti-shortcycle timer and
does this by offering outstanding temperature setpoint.
time delay relays. ReliaTel controls
standard features enhanced by a
provide these functions as an integral Intelligent Anticipation is a standard
variety of factory and field installed
part of the unit. The contractor no ReliaTel feature. It functions
options, multiple control options,
longer has to purchase these controls continuously as ReliaTel and zone
rigorously tested proven designs and
as options and pay to install them. sensor(s) work together in harmony
superior product and technical
to provide much tighter comfort
support.
control than conventional electro-
mechanical thermostats.
Flexibility
The same ReliaTel Board fits all
Precedent offers ultimate flexibility. Precedent Packaged Gas/Electrics,
Units are built to order in our Cooling with Electric Heat, and Heat
standard “shortest in the industry” Pump models. This provides
ship cycle time. standardization of parts for
The wiring of the low voltage
connections to the unit and the zone contractors. Less money is tied up in
ReliaTel™ Controls sensors is as easy as 1-1, 2-2, and 3-3. inventory with ReliaTel.
ReliaTel controls provide unit control This simplified system makes wiring
for heating, cooling and ventilating easier for the installer. Unit Cabinet
utilizing input from sensors that The compact cabinet with rounded
measure outdoor and indoor ReliaTel Makes Testing Easy
corners takes up less room and is
temperature. ReliaTel requires no special tools to less costly to ship. The beveled and
run the Precedent unit through its ribbed top is not only aesthetically
paces. Simply place a jumper pleasing, it is designed to prevent
between Test 1 and Test 2 terminals water from pooling.
on the Low Voltage Terminal Board
and the unit will walk through its VariTrac – Building Automation
operational steps automatically. System
The unit automatically returns When Trane’s changeover VAV
control to the zone sensor after System for light commercial
ReliaTel Control Logic Enhances stepping through the test mode a applications is coupled with
Quality and Reliability single time, even if the jumper is left Precedent, it provides the latest in
on the unit. technological advances for comfort
• —prevents the unit from short
cycling, considerably improving As long as the unit has power and management systems and can allow
compressor life. the “system on” LED is lit, ReliaTel is thermostat control in every zone
operational. The light indicates that served by VariTrac.
• —ensures that the compressor the controls are functioning properly.
will run for a specific amount of
time which allows oil to return ReliaTel features expanded
for better lubrication, enhancing diagnostic capabilities when utilized
the reliability of the compressor. with Trane Integrated Comfort™
Systems.
Precedent with ReliaTel reduces the
number of components required to Some zone sensor options have
operate the unit, thereby reducing central control panel lights which
possibilities for component failure. indicate the mode the unit is in and
possible diagnostic information (dirty
filters for example).
RT-PRC023-EN 9
Features and Benefits
10 RT-PRC023-EN
Application Considerations
RT-PRC023-EN 11
Selection Procedure
12 RT-PRC023-EN
Model Number Description
T S C 036 E 3 R B A ** C 0 0 0 A 1 0 0 0 2 A 1
1 2 3 456 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
RT-PRC023-EN 13
Model Number Description
14 RT-PRC023-EN
General Data
RT-PRC023-EN 15
General Data
(3-4 Tons Standard Efficiency)
16 RT-PRC023-EN
General Data
(5 Tons Standard Efficiency)
RT-PRC023-EN 17
General Data
(5 Tons Standard Efficiency)
18 RT-PRC023-EN
General Data
(6 – 10 Tons Standard Efficiency)
RT-PRC023-EN 19
General Data
(6 – 10 Tons Standard Efficiency)
20 RT-PRC023-EN
General Data
(3 – 4 Tons Standard Efficiency)
RT-PRC023-EN 21
General Data
(5 Tons Standard Efficiency)
22 RT-PRC023-EN
General Data
(3 – 4 Tons High Efficiency)
RT-PRC023-EN 23
General Data
(3 – 4 Tons High Efficiency)
24 RT-PRC023-EN
General Data
(5 Tons High Efficiency)
RT-PRC023-EN 25
General Data
(5 Tons High Efficiency)
26 RT-PRC023-EN
Performance Data
RT-PRC023-EN 27
Performance Data
(4 Tons Standard Efficiency)
28 RT-PRC023-EN
Performance Data
RT-PRC023-EN 29
Performance Data
(6 Tons Standard Efficiency)
30 RT-PRC023-EN
Performance Data
(7½ Tons Standard Efficiency)
RT-PRC023-EN 31
Performance Data
(8½ Tons Standard Efficiency)
32 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)
RT-PRC023-EN 33
Performance Data
(3 Tons Standard Efficiency)
Table 18. Gross Cooling Capacities 3 Tons Single Phase WSC036E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75.0 35.7 28.7 39.4 20.8 43.3 12.2 32.9 27.1 36.4 19.2 40.1 10.9 30.0 25.5 33.2 17.7 36.8 9.3 27.0 24.1 29.9 16.1 33.3 7.8
80.0 36.7 35.8 39.9 27.0 43.9 19.0 34.0 34.0 36.9 25.5 40.7 17.6 31.4 31.4 33.8 23.9 37.3 16.1 28.6 28.6 30.5 22.3 33.8 14.6
85.0 38.9 38.9 40.5 33.1 44.3 25.1 36.3 36.3 37.5 31.6 41.1 23.6 33.7 33.7 34.4 30.1 37.7 22.1 30.8 30.8 31.3 28.9 34.2 20.5
90.0 41.3 41.3 41.6 40.4 44.9 31.3 38.7 38.7 38.7 38.6 41.7 29.7 36.0 36.0 36.0 36.0 38.3 28.1 33.1 33.1 33.1 33.1 34.7 26.3
1200 75.0 36.5 30.6 40.2 21.9 44.1 12.5 33.7 29.0 37.0 20.2 40.8 11.0 30.8 27.7 33.8 18.5 37.4 9.5 27.7 26.3 30.5 16.9 33.8 8.0
80.0 37.8 37.8 40.8 28.7 44.6 19.9 35.3 35.3 37.6 27.1 41.4 18.5 32.6 32.6 34.5 25.4 37.9 17.0 29.7 29.7 31.1 23.7 34.3 15.3
85.0 40.4 40.4 41.5 35.5 45.1 26.5 37.7 37.7 38.4 34.2 41.9 25.0 35.0 35.0 35.3 33.0 38.4 23.4 32.0 32.0 32.1 31.7 34.8 22.1
90.0 42.9 42.9 42.9 42.9 45.8 33.1 40.2 40.2 40.1 40.1 42.4 31.5 37.3 37.3 37.3 37.3 39.0 29.9 34.3 34.3 34.3 34.3 35.4 28.5
1320 75.0 37.3 32.5 40.8 22.7 44.7 12.6 34.4 31.2 37.6 21.0 41.4 11.0 31.5 29.9 34.4 19.5 37.9 9.8 28.4 28.3 30.9 18.0 34.2 8.1
80.0 39.1 39.1 41.4 30.2 45.3 20.7 36.4 36.4 38.2 28.5 41.9 19.3 33.6 33.6 35.0 27.0 38.4 17.7 30.7 30.7 31.6 25.4 34.7 15.8
85.0 41.7 41.7 42.3 38.2 45.9 27.9 38.9 38.9 39.3 37.0 42.5 26.3 36.0 36.0 36.2 35.7 39.0 24.8 33.0 33.0 33.0 33.0 35.3 23.3
90.0 44.3 44.3 44.3 44.3 46.5 35.0 41.5 41.5 41.4 41.4 43.2 33.5 38.5 38.5 38.5 38.5 39.7 32.1 35.3 35.3 35.3 35.3 36.1 30.9
1440 75.0 38.0 34.7 41.3 23.6 45.2 12.8 35.1 33.4 38.1 22.0 41.9 11.4 32.1 31.8 34.8 20.6 38.3 9.8 29.0 29.0 31.3 18.9 34.6 8.1
80.0 40.1 40.1 42.0 31.7 45.9 21.6 37.4 37.4 38.9 30.2 42.4 20.0 34.5 34.5 35.5 28.7 38.8 18.1 31.4 31.4 32.1 27.3 35.1 16.5
85.0 42.8 42.8 43.2 41.0 46.5 29.1 40.0 40.0 40.0 39.6 43.1 27.8 37.0 37.0 37.0 37.0 39.5 26.2 33.9 33.9 33.8 33.8 35.7 24.5
90.0 45.5 45.5 45.5 45.5 47.2 37.1 42.6 42.6 42.6 42.6 43.8 35.7 39.5 39.5 39.5 39.5 40.3 34.6 36.3 36.3 36.2 36.2 36.7 33.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table 19. Gross Cooling Capacities 3 Tons Three Phase WSC036E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75.0 36.1 28.9 39.8 21.0 43.6 12.3 33.3 27.4 36.8 19.2 40.4 10.7 30.4 25.8 33.6 17.9 37.1 9.1 27.3 24.4 30.4 16.3 33.6 7.6
80.0 36.9 35.9 40.2 27.0 44.2 19.2 34.2 34.1 37.3 25.5 41.0 17.6 31.6 31.6 34.1 23.9 37.6 15.8 28.8 28.8 30.7 22.3 34.0 14.3
85.0 38.9 38.9 40.7 33.3 44.6 25.0 36.4 36.4 37.8 31.8 41.4 23.8 33.8 33.8 34.6 30.3 38.0 22.2 31.0 31.0 31.4 29.1 34.4 20.3
90.0 41.3 41.3 41.6 40.5 45.1 31.1 38.7 38.7 38.8 38.6 41.9 29.7 36.0 36.0 36.0 36.0 38.4 28.0 33.1 33.1 33.1 33.1 34.8 26.4
1200 75.0 36.9 30.9 40.6 21.8 44.4 12.4 34.1 29.4 37.5 20.3 41.2 10.8 31.1 28.0 34.3 18.8 37.7 9.3 28.0 26.6 30.9 17.1 34.1 7.8
80.0 38.0 37.9 41.1 28.7 45.0 19.7 35.4 35.4 38.0 27.3 41.7 18.3 32.7 32.7 34.7 25.6 38.2 16.8 29.9 29.9 31.4 24.0 34.6 15.0
85.0 40.4 40.4 41.7 35.7 45.5 26.8 37.8 37.8 38.7 34.5 42.1 24.9 35.0 35.0 35.5 33.2 38.6 23.4 32.1 32.1 32.2 31.8 35.0 21.7
90.0 42.9 42.9 42.9 42.9 46.0 33.3 40.3 40.3 40.2 40.2 42.6 31.7 37.3 37.3 37.3 37.3 39.1 30.1 34.3 34.3 34.3 34.3 35.5 28.5
1320 75.0 37.6 32.9 41.3 22.9 45.1 12.5 34.8 31.6 38.1 21.3 41.8 11.0 31.7 30.1 34.8 19.7 38.2 9.4 28.7 28.3 31.4 18.0 34.6 8.0
80.0 39.2 39.2 41.9 30.4 45.7 20.8 36.6 36.6 38.7 28.9 42.3 19.2 33.7 33.7 35.4 27.2 38.7 17.4 30.8 30.8 31.9 25.7 35.0 15.8
85.0 41.8 41.8 42.5 38.5 46.2 27.9 39.0 39.0 39.4 37.2 42.8 26.4 36.1 36.1 36.3 35.8 39.2 24.8 33.1 33.1 33.1 33.0 35.5 23.2
90.0 44.4 44.4 44.3 44.3 46.7 35.2 41.5 41.5 41.5 41.5 43.3 33.7 38.5 38.5 38.5 38.5 39.8 32.3 35.3 35.3 35.3 35.3 36.1 31.1
1440 75.0 38.4 35.1 41.9 23.9 45.7 12.7 35.4 33.7 38.6 22.3 42.3 11.2 32.4 31.9 35.2 20.6 38.7 9.3 29.3 29.2 31.8 19.0 34.9 7.9
80.0 40.3 40.3 42.5 32.1 46.3 21.6 37.6 37.6 39.2 30.4 42.8 20.0 34.6 34.6 35.8 29.0 39.1 18.3 31.6 31.6 32.4 27.6 35.4 16.5
85.0 42.9 42.9 43.3 41.2 46.9 29.3 40.1 40.1 40.3 39.7 43.3 27.8 37.1 37.1 37.1 37.0 39.7 26.4 33.9 33.9 33.9 33.9 35.9 24.6
90.0 45.6 45.6 45.5 45.5 47.5 37.3 42.6 42.6 42.6 42.6 44.0 35.9 39.5 39.5 39.5 39.5 40.4 34.9 36.2 36.2 36.2 36.2 36.6 33.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
34 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)
Table 20. Gross Cooling Capacities 4 Tons Single Phase WSC048E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 46.3 39.0 51.1 28.2 56.2 16.8 43.0 37.1 47.6 26.3 52.4 14.6 39.5 35.1 43.8 24.7 48.4 13.0 35.8 33.0 39.8 22.8 44.3 12.2
80.0 47.1 45.9 51.6 36.7 56.8 25.8 44.0 43.5 48.1 34.8 53.0 24.1 40.7 40.7 44.3 33.0 49.0 22.3 37.5 37.5 40.3 31.2 44.7 20.5
85.0 49.6 49.6 52.2 45.0 57.3 34.3 46.7 46.7 48.7 43.2 53.4 32.1 43.6 43.6 44.9 41.3 49.4 30.7 40.2 40.2 41.0 39.0 45.1 28.8
90.0 52.7 52.7 53.2 51.9 57.8 42.4 49.7 49.7 49.8 49.4 54.0 40.6 46.5 46.5 46.4 46.4 49.8 38.9 43.0 43.0 43.0 43.0 45.5 37.1
1600 75.0 47.3 41.6 52.1 29.5 57.3 17.3 43.9 39.6 48.5 27.9 53.3 14.9 40.4 37.4 44.6 26.1 49.2 12.1 36.6 34.8 40.5 24.1 44.9 13.4
80.0 48.5 48.2 52.7 39.0 57.9 26.9 45.3 45.3 49.0 37.2 53.9 25.2 42.2 42.2 45.2 35.3 49.8 23.4 38.8 38.8 41.1 33.5 45.4 21.7
85.0 51.5 51.5 53.3 48.2 58.3 36.2 48.4 48.4 49.8 46.2 54.4 34.4 45.2 45.2 46.0 43.8 50.3 32.7 41.7 41.7 42.1 41.0 45.8 30.9
90.0 54.7 54.7 54.8 54.6 58.9 45.4 51.5 51.5 51.5 51.5 54.9 43.6 48.2 48.2 48.2 48.2 50.7 41.8 44.6 44.6 44.6 44.6 46.3 40.1
1760 75.0 48.2 43.8 53.0 31.0 58.1 17.0 44.8 41.7 49.2 29.3 54.2 16.4 41.1 39.2 45.3 27.5 50.0 14.1 37.4 36.4 41.1 25.6 45.5 12.6
80.0 49.9 49.9 53.6 41.4 58.7 28.0 46.8 46.8 49.9 39.6 54.7 26.3 43.5 43.5 45.9 37.7 50.5 24.7 40.0 40.0 41.7 35.8 46.0 22.9
85.0 53.2 53.2 54.4 50.9 59.2 38.1 50.0 50.0 50.8 48.5 55.2 36.5 46.6 46.6 47.0 45.7 50.9 34.8 42.9 42.9 43.0 42.8 46.4 33.0
90.0 56.4 56.4 56.4 56.4 59.8 48.4 53.2 53.2 53.1 53.1 55.7 46.5 49.6 49.6 49.6 49.6 51.5 44.9 45.9 45.9 45.9 45.9 47.1 42.8
1920 75.0 49.0 45.9 53.7 32.6 58.9 18.0 45.6 43.4 49.9 30.8 54.8 16.3 41.9 40.7 45.8 28.9 50.5 14.6 38.1 37.8 41.6 27.1 46.0 12.8
80.0 51.2 51.2 54.4 43.6 59.5 29.1 48.0 48.0 50.5 41.9 55.4 27.4 44.6 44.6 46.5 39.9 51.0 25.9 41.0 41.0 42.3 37.8 46.5 23.9
85.0 54.6 54.6 55.4 53.1 60.0 40.2 51.3 51.3 51.7 50.4 55.9 38.6 47.8 47.8 47.9 47.6 51.5 36.9 44.1 44.1 44.0 44.0 47.0 35.0
90.0 58.0 58.0 58.0 58.0 60.6 51.3 54.6 54.6 54.5 54.5 56.6 49.5 51.0 51.0 50.9 50.9 52.2 47.4 47.1 47.1 47.1 47.1 47.8 44.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table 21. Gross Cooling Capacities 4 Tons Three Phase WSC048E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 47.2 39.3 52.1 28.6 57.4 17.1 43.8 37.4 48.6 26.7 53.6 15.3 40.3 35.5 44.8 24.9 49.6 13.9 36.6 33.5 40.8 23.0 45.4 12.1
80.0 48.1 46.7 52.7 37.0 57.9 25.7 44.8 44.2 49.1 35.2 54.2 24.1 41.5 41.5 45.3 33.4 50.1 22.3 38.3 38.3 41.3 31.4 45.9 20.6
85.0 50.6 50.6 53.3 45.5 58.5 34.0 47.6 47.6 49.7 43.6 54.7 32.5 44.4 44.4 45.9 41.8 50.7 30.7 41.1 41.1 42.0 39.6 46.4 29.0
90.0 53.7 53.7 54.3 52.7 59.0 42.4 50.6 50.6 50.9 50.2 55.2 41.0 47.4 47.4 47.4 47.4 51.2 39.3 44.0 44.0 44.0 44.0 46.9 37.4
1600 75.0 48.3 42.0 53.2 29.9 58.5 18.1 44.8 40.0 49.5 28.2 54.6 16.3 41.2 37.9 45.6 26.1 50.5 14.7 37.4 35.5 41.5 24.4 46.1 12.9
80.0 49.5 49.0 53.8 39.4 59.0 26.3 46.2 46.2 50.1 37.6 55.1 24.4 43.0 43.0 46.3 35.8 51.1 23.6 39.7 39.7 42.1 33.8 46.7 21.6
85.0 52.5 52.5 54.5 48.8 59.6 36.1 49.4 49.4 50.8 46.8 55.7 34.5 46.1 46.1 47.0 44.5 51.6 32.8 42.7 42.7 43.1 41.7 47.2 31.1
90.0 55.8 55.8 55.8 55.4 60.2 45.6 52.5 52.5 52.5 52.5 56.2 44.0 49.2 49.2 49.2 49.2 52.0 42.2 45.7 45.7 45.6 45.6 47.7 40.4
1760 75.0 49.3 44.5 54.1 31.1 59.4 19.0 45.7 42.3 50.3 29.6 55.4 16.5 42.0 39.9 46.3 27.5 51.2 14.5 38.3 37.1 42.2 25.9 46.8 13.0
80.0 50.8 50.8 54.7 41.8 60.0 28.4 47.7 47.7 51.0 39.9 55.9 26.5 44.4 44.4 47.0 38.0 51.8 24.5 40.9 40.9 42.8 36.1 47.3 22.8
85.0 54.2 54.2 55.5 51.7 60.5 38.3 51.0 51.0 51.9 49.3 56.5 36.7 47.6 47.6 48.0 46.5 52.4 35.0 44.0 44.0 44.1 43.7 47.9 33.0
90.0 57.6 57.6 57.5 57.5 61.2 48.7 54.2 54.2 54.2 54.2 57.1 46.9 50.8 50.8 50.8 50.8 52.9 45.3 47.1 47.1 47.1 47.1 48.6 43.5
1920 75.0 50.1 46.6 54.9 32.7 60.2 19.3 46.5 44.2 51.0 31.0 56.1 18.2 42.8 41.4 46.9 29.0 51.9 14.7 39.1 38.6 42.7 27.2 47.3 13.0
80.0 52.2 52.2 55.5 44.1 60.8 29.6 49.0 49.0 51.7 42.3 56.6 27.4 45.6 45.6 47.6 40.3 52.4 25.6 42.0 42.0 43.4 38.4 47.9 24.0
85.0 55.7 55.7 56.5 53.9 61.3 40.3 52.4 52.4 52.8 51.2 57.2 38.9 48.9 48.9 49.1 48.5 53.0 37.1 45.2 45.2 45.2 45.2 48.4 35.3
90.0 59.2 59.2 59.1 59.1 62.0 51.7 55.7 55.7 55.7 55.7 58.0 50.0 52.2 52.2 52.1 52.1 53.7 48.1 48.4 48.4 48.4 48.4 49.3 45.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC023-EN 35
Performance Data
(5 Tons Standard Efficiency)
Table 22. Gross Cooling Capacities 5 Tons Single Phase WSC060E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 55.3 46.9 60.3 32.1 65.7 17.3 51.5 44.9 56.2 30.5 61.3 15.7 47.4 42.9 51.8 27.8 56.7 13.8 43.2 40.5 47.2 26.2 51.7 12.1
80.0 57.1 56.3 61.3 43.1 67.0 29.4 53.4 53.2 57.2 41.1 62.4 26.7 49.6 49.6 52.8 39.3 57.7 24.8 45.8 45.8 48.2 37.2 52.7 22.8
85.0 60.4 60.4 62.6 54.5 67.9 39.5 56.8 56.8 58.4 52.5 63.4 37.3 53.0 53.0 54.1 50.3 58.6 35.4 49.0 49.0 49.6 47.6 53.6 33.8
90.0 64.1 64.1 64.5 63.6 69.0 50.1 60.4 60.4 60.5 60.3 64.4 48.3 56.6 56.6 56.5 56.5 59.6 46.4 52.4 52.4 52.4 52.4 54.5 44.5
2000 75.0 56.6 50.2 61.4 33.8 66.9 17.6 52.6 47.9 57.2 31.7 62.4 15.9 48.5 45.6 52.7 29.7 57.6 13.8 44.3 42.9 48.0 27.9 52.5 12.3
80.0 58.7 58.6 62.6 45.9 68.2 30.0 55.0 55.0 58.4 44.3 63.5 28.6 51.2 51.2 53.8 42.2 58.7 25.5 47.2 47.2 49.1 40.2 53.5 24.3
85.0 62.4 62.4 64.0 58.3 69.1 41.5 58.7 58.7 59.8 56.0 64.5 39.7 54.8 54.8 55.4 53.4 59.6 38.0 50.6 50.6 50.8 50.2 54.4 36.1
90.0 66.4 66.4 66.4 66.3 70.3 53.8 62.5 62.5 62.5 62.5 65.6 51.8 58.4 58.4 58.4 58.4 60.7 50.2 54.0 54.0 54.0 54.0 55.6 48.3
2200 75.0 57.7 53.0 62.4 35.5 67.9 17.9 53.7 50.7 58.0 33.5 63.3 15.1 49.5 47.9 53.5 31.3 58.4 14.2 45.2 44.7 48.6 29.2 53.2 12.6
80.0 60.2 60.2 63.6 48.9 69.2 31.2 56.5 56.5 59.3 47.0 64.5 29.4 52.6 52.6 54.7 45.0 59.4 27.1 48.4 48.4 49.9 43.1 54.1 25.3
85.0 64.3 64.3 65.3 61.6 70.1 44.5 60.4 60.4 61.0 59.0 65.5 42.1 56.4 56.4 56.6 55.9 60.5 40.5 51.9 51.9 52.0 51.9 55.2 38.7
90.0 68.3 68.3 68.3 68.3 71.4 57.2 64.3 64.3 64.3 64.3 66.7 55.7 60.1 60.1 60.0 60.0 61.8 53.9 55.5 55.5 55.5 55.5 56.5 51.7
2400 75.0 58.5 55.4 63.2 37.2 68.8 17.1 54.5 52.8 58.8 35.2 64.2 15.4 50.4 49.7 54.2 33.2 59.1 13.8 46.0 45.8 49.3 31.1 53.8 12.9
80.0 61.8 61.8 64.6 51.7 70.1 32.6 57.9 57.9 60.1 49.8 65.2 30.6 53.8 53.8 55.5 47.9 60.1 28.9 49.5 49.5 50.5 45.6 54.7 26.7
85.0 65.9 65.9 66.5 64.5 71.1 45.9 61.9 61.9 62.2 61.5 66.3 45.0 57.7 57.7 57.7 57.5 61.2 43.1 53.1 53.1 53.1 53.1 55.8 41.2
90.0 70.1 70.1 70.0 70.0 72.6 61.3 65.9 65.9 65.9 65.9 67.7 59.4 61.5 61.5 61.5 61.5 62.7 57.2 56.8 56.8 56.7 56.7 57.4 54.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table 23. Gross Cooling Capacities 5 Tons Three Phase WSC060E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 59.6 49.6 66.0 35.9 72.6 21.9 55.6 47.4 61.6 34.4 68.0 20.0 51.5 45.3 57.1 31.8 63.2 18.0 47.1 43.2 52.2 29.6 58.0 16.1
80.0 61.1 61.0 66.5 46.6 73.5 33.7 57.5 57.5 62.2 44.4 68.9 31.7 53.8 53.8 57.7 42.3 63.9 29.1 49.9 49.9 52.8 40.1 58.7 27.5
85.0 64.9 64.9 67.3 57.1 73.9 43.3 61.3 61.3 63.0 55.0 69.2 41.3 57.5 57.5 58.6 53.1 64.3 39.3 53.4 53.4 53.9 51.7 59.1 37.2
90.0 68.9 68.9 69.0 68.9 74.7 53.8 65.2 65.2 65.1 65.1 69.9 51.7 61.3 61.3 61.2 61.2 65.1 49.6 57.0 57.0 57.0 57.0 59.9 47.2
2000 75.0 61.0 52.9 67.1 37.7 74.0 22.1 56.9 50.8 62.7 35.8 69.2 20.2 52.7 49.0 58.0 33.5 64.2 18.5 48.3 47.2 53.2 31.5 58.9 16.3
80.0 63.2 63.2 67.8 49.4 74.9 35.2 59.6 59.6 63.4 47.2 70.0 32.6 55.7 55.7 58.8 45.1 64.9 31.1 51.6 51.6 53.8 42.8 59.6 28.9
85.0 67.4 67.4 68.9 61.3 75.3 45.9 63.6 63.6 64.5 59.6 70.5 43.7 59.6 59.6 60.0 58.3 65.5 41.7 55.3 55.3 55.4 55.3 60.2 39.5
90.0 71.5 71.5 71.4 71.4 76.1 57.2 67.7 67.7 67.5 67.5 71.3 55.1 63.5 63.5 63.4 63.4 66.3 52.8 59.1 59.1 59.1 59.1 61.0 50.8
2200 75.0 62.2 56.4 68.3 39.6 75.1 22.4 58.1 54.6 63.7 37.2 70.3 20.5 53.8 52.8 58.9 35.1 65.1 18.5 49.4 49.4 53.9 33.2 59.7 16.2
80.0 65.2 65.2 69.0 52.1 75.9 36.8 61.4 61.4 64.4 49.9 71.0 33.9 57.4 57.4 59.7 47.8 65.8 31.8 53.1 53.1 54.7 45.7 60.4 29.7
85.0 69.5 69.5 70.3 66.1 76.5 48.3 65.6 65.6 66.1 64.8 71.5 46.0 61.4 61.4 61.4 61.4 66.5 44.1 57.0 57.0 56.9 56.9 61.0 41.9
90.0 73.8 73.8 73.8 73.8 77.4 60.7 69.8 69.8 69.7 69.7 72.5 58.6 65.5 65.5 65.4 65.4 67.4 56.7 60.9 60.9 60.9 60.9 62.1 54.9
2400 75.0 63.4 60.2 69.0 40.9 76.0 22.7 59.2 58.3 64.5 38.8 71.1 20.7 54.9 54.8 59.6 36.7 65.9 18.7 50.5 50.5 54.5 34.3 60.3 16.3
80.0 66.9 66.9 70.1 54.9 76.8 37.2 63.0 63.0 65.4 52.8 71.8 35.9 58.9 58.9 60.6 50.8 66.6 33.6 54.4 54.4 55.6 48.9 61.0 30.8
85.0 71.3 71.3 71.8 70.9 77.6 50.5 67.3 67.3 67.4 67.3 72.5 48.6 63.0 63.0 63.0 63.0 67.3 46.3 58.5 58.5 58.4 58.4 61.8 44.3
90.0 75.9 75.9 75.8 75.8 78.6 64.3 71.7 71.7 71.6 71.6 73.6 62.5 67.2 67.2 67.2 67.2 68.5 60.9 62.5 62.5 62.5 62.5 63.1 59.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
36 RT-PRC023-EN
Performance Data
(3 Tons High Efficiency)
Table 24. Gross Cooling Capacities 3 Tons Single Phase High Efficiency T/YHC036E1
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 35.98 29.32 39.78 21.77 43.79 13.23 33.67 28.00 37.32 20.42 41.12 11.60 31.24 26.70 34.66 18.96 38.27 10.50 28.69 25.46 31.92 17.50 35.30 9.16
80 36.75 36.14 40.21 27.81 44.32 18.70 34.62 34.55 37.70 26.35 41.66 19.19 32.42 32.42 35.09 24.88 38.87 17.42 30.12 30.12 32.30 23.39 35.87 16.22
85 38.97 38.97 40.68 33.98 44.77 26.20 36.89 36.89 38.20 32.60 42.07 24.89 34.66 34.66 35.59 31.36 39.20 23.34 32.31 32.31 32.84 30.14 36.22 21.81
90 41.37 41.37 41.55 40.89 45.12 32.03 39.22 39.22 39.19 39.15 42.48 30.69 36.92 36.92 36.88 36.88 39.58 29.15 34.47 34.47 34.45 34.45 36.59 27.68
1200 75 36.80 31.29 40.58 22.70 44.56 13.08 34.51 30.19 38.04 21.35 41.82 12.07 31.94 28.81 35.33 19.89 38.93 10.74 29.36 27.53 32.47 18.40 35.89 8.96
80 37.98 37.98 41.02 29.37 45.25 19.91 35.87 35.87 38.49 27.95 42.46 19.36 33.61 33.61 35.81 26.49 39.52 18.36 31.22 31.22 32.95 25.14 36.47 16.48
85 40.43 40.43 41.60 36.52 45.62 27.66 38.29 38.29 39.06 35.26 42.84 26.24 35.97 35.97 36.43 34.19 39.90 24.63 33.50 33.50 33.70 32.88 36.84 23.18
90 42.94 42.94 42.92 42.92 46.01 34.09 40.67 40.67 40.69 40.69 43.25 32.66 38.29 38.29 38.28 38.28 40.34 31.25 35.78 35.78 35.75 35.75 37.28 29.77
1320 75 37.56 33.62 41.24 23.67 45.25 13.35 35.13 32.23 38.65 21.93 42.41 12.25 32.61 30.88 35.92 20.85 39.47 10.65 30.02 29.35 32.97 19.05 36.36 9.31
80 39.19 39.19 41.74 30.99 45.98 22.46 37.00 37.00 39.13 29.55 43.09 20.28 34.66 34.66 36.38 28.25 40.09 19.09 32.18 32.18 33.47 26.95 36.96 17.31
85 41.76 41.76 42.39 39.18 46.35 29.03 39.52 39.52 39.89 38.00 43.49 27.42 37.10 37.10 37.20 36.47 40.52 25.74 34.54 34.54 34.55 34.52 37.37 24.62
90 44.30 44.30 44.29 44.29 46.76 36.00 42.01 42.01 41.98 41.98 43.93 34.80 39.55 39.55 39.51 39.51 40.99 33.52 36.90 36.90 36.87 36.87 37.87 32.39
1440 75 38.21 35.56 41.79 24.49 45.87 13.71 35.79 34.23 39.17 23.63 42.95 12.14 33.22 32.55 36.38 21.75 39.93 10.77 30.66 30.61 33.40 20.29 36.76 9.40
80 40.26 40.26 42.38 32.66 46.51 22.10 38.00 38.00 39.72 31.36 43.60 20.97 35.58 35.58 36.92 30.15 40.56 19.85 33.03 33.03 33.96 28.89 37.38 18.26
85 42.94 42.94 43.26 41.79 46.93 30.25 40.60 40.60 40.67 40.12 44.03 28.88 38.09 38.09 38.12 38.10 41.01 27.36 35.46 35.46 35.43 35.43 37.85 25.96
90 45.57 45.57 45.52 45.52 47.42 38.18 43.15 43.15 43.15 43.15 44.56 37.07 40.63 40.63 40.60 40.60 41.57 36.03 37.89 37.89 37.86 37.86 38.47 34.85
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table 25. Gross Cooling Capacities 3 Tons Three Phase High Efficiency T/YHC036E,3,4
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 36.04 29.24 39.93 21.85 44.03 13.31 33.56 27.96 37.25 19.68 41.15 11.98 30.96 26.64 34.44 18.63 38.07 10.45 28.08 25.17 31.38 17.36 34.83 9.03
80 36.85 36.25 40.36 27.79 44.56 18.86 34.54 34.48 37.71 26.33 41.72 19.22 32.17 32.17 34.87 24.79 38.71 17.22 29.66 29.66 31.82 23.19 35.43 15.97
85 39.07 39.07 40.89 34.02 45.02 26.27 36.85 36.85 38.21 32.58 42.13 24.91 34.48 34.48 35.39 31.27 39.05 23.28 31.91 31.91 32.40 30.00 35.81 21.66
90 41.51 41.51 41.71 40.92 45.41 32.17 39.24 39.24 39.24 39.18 42.52 30.76 36.78 36.78 36.75 36.75 39.44 29.08 34.14 34.14 34.11 34.11 36.18 27.54
1200 75 36.89 31.39 40.75 22.78 44.80 13.19 34.36 30.13 38.02 21.34 41.86 12.08 31.63 28.72 35.11 19.72 38.73 10.53 28.80 27.28 31.99 18.16 35.42 8.84
80 38.07 38.07 41.22 29.43 45.44 21.73 35.82 35.82 38.49 27.94 42.51 19.35 33.39 33.39 35.57 26.40 39.36 18.31 30.78 30.78 32.47 24.98 36.01 16.40
85 40.58 40.58 41.79 36.51 45.90 27.82 38.27 38.27 39.04 35.24 42.91 26.26 35.80 35.80 36.22 34.00 39.75 24.57 33.12 33.12 33.29 32.64 36.43 23.02
90 43.14 43.14 43.10 43.10 46.32 34.18 40.75 40.75 40.71 40.71 43.32 32.62 38.18 38.18 38.15 38.15 40.20 31.10 35.44 35.44 35.41 35.41 36.88 29.78
1320 75 37.67 33.65 41.43 23.65 45.47 13.24 35.04 32.16 38.64 21.93 42.46 12.26 32.35 30.88 35.69 20.75 39.29 10.60 29.47 29.03 32.47 18.66 35.91 9.51
80 39.27 39.27 41.95 31.06 46.28 22.55 36.96 36.96 39.15 29.59 43.13 20.50 34.44 34.44 36.18 28.17 39.93 19.03 31.75 31.75 32.98 26.77 36.51 17.18
85 41.94 41.94 42.64 39.23 46.63 29.16 39.54 39.54 39.90 38.01 43.54 27.46 36.94 36.94 37.05 36.38 40.35 26.01 34.17 34.17 34.16 34.15 36.98 24.18
90 44.51 44.51 44.50 44.50 47.07 36.09 42.08 42.08 42.02 42.02 44.03 34.82 39.42 39.42 39.40 39.40 40.86 33.49 36.56 36.56 36.53 36.53 37.46 32.20
1440 75 38.28 35.59 42.01 24.58 46.08 13.79 35.73 34.21 39.17 23.62 43.00 12.15 32.96 32.43 36.15 21.66 39.73 10.77 30.16 30.15 32.90 20.10 36.30 9.28
80 40.43 40.43 42.60 32.73 46.77 21.55 37.97 37.97 39.77 31.36 43.69 20.99 35.39 35.39 36.72 30.03 40.41 19.49 32.60 32.60 33.49 28.79 36.94 17.90
85 43.13 43.13 43.49 41.88 47.26 30.64 40.62 40.62 40.78 40.21 44.14 28.86 37.94 37.94 37.95 37.94 40.89 27.31 35.10 35.10 35.07 35.07 37.48 25.84
90 45.81 45.81 45.77 45.77 47.72 38.26 43.26 43.26 43.23 43.23 44.68 37.16 40.53 40.53 40.49 40.49 41.48 35.99 37.55 37.55 37.52 37.52 38.10 34.84
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC023-EN 37
Performance Data
(4 Tons High Efficiency)
38 RT-PRC023-EN
Performance Data
(5 Tons High Efficiency)
RT-PRC023-EN 39
Performance Data
Table 30. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — No Electric Heat — TSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 TSC036E1 960 0.45 715 0.21 0.74 851 0.31 0.92 929 0.38 1.07 993 0.44 1.25 1053 0.52
Downflow 1020 0.39 695 0.20 0.66 826 0.30 0.84 905 0.37 0.99 969 0.43 1.17 1030 0.50
Airflow 1080 0.33 675 0.20 0.59 800 0.29 0.77 880 0.36 0.91 945 0.42 1.08 1007 0.49
1140 0.27 654 0.19 0.51 774 0.28 0.69 855 0.35 0.83 921 0.41 1.00 985 0.48
1200 0.21 634 0.18 0.43 749 0.27 0.61 831 0.34 0.75 898 0.40 0.91 962 0.47
1260 0.15 614 0.18 0.35 723 0.26 0.53 806 0.33 0.67 874 0.39 0.83 939 0.46
1320 0.09 593 0.17 0.28 697 0.25 0.45 782 0.32 0.59 850 0.38 0.74 916 0.45
1380 0.03 573 0.17 0.20 671 0.24 0.37 757 0.31 0.51 826 0.37 0.66 893 0.44
1440 — — — 0.12 646 0.23 0.29 732 0.30 0.43 802 0.36 0.57 871 0.43
TSC036E1 960 0.45 711 0.21 0.70 835 0.30 0.89 913 0.37 1.04 978 0.44 1.21 1037 0.51
Horizontal 1020 0.39 689 0.20 0.63 811 0.29 0.81 890 0.36 0.96 957 0.43 1.13 1016 0.50
Airflow 1080 0.32 667 0.19 0.56 787 0.28 0.73 868 0.35 0.88 935 0.42 1.04 996 0.49
1140 0.26 644 0.19 0.48 763 0.28 0.65 845 0.34 0.80 913 0.41 0.95 975 0.48
1200 0.20 622 0.18 0.41 739 0.27 0.57 823 0.33 0.72 892 0.40 0.87 955 0.47
1260 0.13 599 0.17 0.33 715 0.26 0.50 800 0.32 0.64 870 0.39 0.78 934 0.46
1320 0.07 577 0.17 0.26 691 0.25 0.42 777 0.32 0.56 848 0.38 0.69 913 0.45
1380 0.01 555 0.16 0.18 667 0.24 0.34 755 0.31 0.48 826 0.37 0.61 893 0.44
1440 — — — 0.11 642 0.23 0.26 732 0.30 0.40 805 0.36 0.52 872 0.43
4 TSC048E1 1280 0.60 865 0.36 0.84 977 0.47 1.02 1044 0.55 1.17 1090 0.63 — — —
Downflow 1360 0.48 833 0.35 0.72 944 0.45 0.90 1012 0.54 1.04 1062 0.61 — — —
Airflow 1440 0.37 802 0.34 0.60 912 0.44 0.77 980 0.52 0.92 1033 0.60 — — —
1520 0.25 770 0.32 0.48 879 0.42 0.65 948 0.50 0.80 1005 0.58 1.06 1100 0.69
1600 0.14 739 0.31 0.36 846 0.41 0.52 915 0.49 0.68 976 0.56 0.92 1069 0.67
1680 0.02 707 0.30 0.24 814 0.39 0.39 883 0.47 0.56 948 0.55 0.78 1038 0.65
1760 — — — 0.13 781 0.38 0.27 851 0.45 0.43 920 0.53 0.64 1006 0.63
1840 — — — 0.01 748 0.36 0.14 819 0.43 0.31 891 0.52 0.50 975 0.62
1920 — — — — — — 0.02 787 0.42 0.19 863 0.50 0.37 944 0.60
TSC048E1 1280 0.61 864 0.36 0.84 967 0.47 1.00 1038 0.55 1.16 1115 0.65 — — —
Horizontal 1360 0.51 831 0.35 0.73 935 0.45 0.88 1006 0.53 1.05 1084 0.63 — — —
Airflow 1440 0.40 798 0.33 0.62 904 0.44 0.77 974 0.52 0.94 1052 0.61 1.10 1114 0.70
1520 0.30 766 0.32 0.51 873 0.42 0.66 943 0.50 0.82 1020 0.59 0.99 1084 0.68
1600 0.19 733 0.31 0.40 842 0.41 0.55 911 0.48 0.71 989 0.57 0.87 1054 0.66
1680 0.09 701 0.29 0.29 810 0.39 0.44 879 0.47 0.60 957 0.55 0.75 1023 0.65
1760 — — — 0.18 779 0.38 0.32 848 0.45 0.48 925 0.54 0.64 993 0.63
1840 — — — 0.08 748 0.36 0.21 816 0.43 0.37 893 0.52 0.52 963 0.61
1920 — — — — — — 0.10 784 0.42 0.26 861 0.50 0.40 932 0.59
5 TSC060E1 1600 0.75 1006 0.60 0.91 1065 0.69 — — — — — — — — —
Downflow 1700 0.60 969 0.58 0.75 1024 0.66 0.96 1101 0.77 — — — — — —
Airflow 1800 0.45 933 0.56 0.58 982 0.63 0.78 1059 0.74 — — — — — —
1900 0.30 896 0.54 0.42 941 0.61 0.61 1017 0.71 0.82 1105 0.83 — — —
2000 0.14 860 0.52 0.25 899 0.58 0.43 975 0.68 0.64 1062 0.80 0.70 1083 0.85
2100 0.00 826 0.50 0.09 858 0.55 0.25 933 0.65 0.46 1019 0.77 0.54 1045 0.82
2200 — — — — — — 0.08 891 0.62 0.28 975 0.74 0.37 1007 0.79
2300 — — — — — — — — — 0.10 932 0.70 0.20 969 0.76
2400 — — — — — — — — — — — — 0.03 931 0.73
TSC060E1 1600 0.73 1003 0.60 0.90 1075 0.69 — — — — — — — — —
Horizontal 1700 0.60 968 0.58 0.74 1034 0.67 0.89 1104 0.77 — — — — — —
Airflow 1800 0.46 934 0.56 0.59 993 0.64 0.74 1064 0.74 — — — — — —
1900 0.33 899 0.54 0.44 952 0.62 0.59 1023 0.71 0.75 1095 0.83 — — —
2000 0.19 864 0.52 0.28 911 0.59 0.43 983 0.69 0.60 1053 0.79 0.69 1090 0.86
2100 0.05 829 0.50 0.13 870 0.56 0.28 942 0.66 0.44 1012 0.76 0.53 1051 0.83
2200 — — — 0.00 837 0.54 0.13 902 0.63 0.28 971 0.73 0.37 1012 0.80
2300 — — — — — — 0.00 868 0.61 0.12 930 0.70 0.21 972 0.77
2400 — — — — — — — — — 0.00 897 0.68 0.06 933 0.74
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16. For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
40 RT-PRC023-EN
Performance Data
(3-5 Tons Standard Efficiency)
Table 31. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — Low & Medium Gas Heat — YSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YSC036E1**L,M 960 0.43 718 0.19 0.64 825 0.27 0.88 923 0.35 1.12 1017 0.46 1.28 1074 0.52
Downflow 1020 0.37 696 0.18 0.57 800 0.26 0.80 900 0.35 1.04 997 0.45 1.20 1053 0.51
Airflow 1080 0.30 675 0.18 0.49 775 0.26 0.72 877 0.34 0.96 977 0.44 1.11 1033 0.50
1140 0.24 654 0.17 0.42 749 0.25 0.64 854 0.33 0.87 957 0.43 1.03 1013 0.49
1200 0.18 633 0.17 0.34 724 0.24 0.56 832 0.32 0.79 938 0.42 0.94 992 0.48
1260 0.11 612 0.16 0.26 698 0.23 0.48 809 0.31 0.71 918 0.41 0.86 972 0.47
1320 0.05 590 0.16 0.19 673 0.22 0.39 786 0.30 0.63 898 0.40 0.77 951 0.46
1380 — — — 0.11 647 0.21 0.31 763 0.29 0.55 878 0.39 0.68 931 0.45
1440 — — — 0.03 622 0.21 0.23 740 0.28 0.47 859 0.38 0.60 910 0.44
YSC036E1**L,M 960 0.42 715 0.19 0.67 842 0.28 0.90 937 0.36 1.15 1037 0.46 1.25 1062 0.51
Horizontal 1020 0.37 695 0.18 0.61 819 0.27 0.83 916 0.35 1.07 1014 0.45 1.18 1047 0.50
Airflow 1080 0.31 675 0.18 0.54 796 0.26 0.75 895 0.34 0.99 992 0.44 1.11 1032 0.50
1140 0.26 654 0.17 0.47 772 0.26 0.68 874 0.34 0.91 970 0.43 1.04 1017 0.49
1200 0.20 634 0.17 0.41 749 0.25 0.61 853 0.33 0.83 948 0.42 0.97 1002 0.48
1260 0.14 614 0.16 0.34 725 0.24 0.54 832 0.32 0.75 926 0.41 0.90 987 0.48
1320 0.09 594 0.16 0.27 702 0.23 0.47 811 0.31 0.67 903 0.40 0.83 972 0.47
1380 0.03 574 0.15 0.20 678 0.22 0.40 789 0.30 0.59 881 0.39 0.76 957 0.46
1440 — — — 0.14 654 0.22 0.33 768 0.29 0.51 859 0.38 0.69 942 0.45
4 YSC048E1**L,M 1280 0.71 933 0.42 0.89 1003 0.49 1.11 1094 0.59 — — — — — —
Downflow 1360 0.59 903 0.41 0.76 973 0.48 0.97 1061 0.57 1.14 1116 0.64 — — —
Airflow 1440 0.47 874 0.39 0.63 943 0.46 0.84 1027 0.56 1.00 1085 0.62 — — —
1520 0.34 845 0.38 0.50 913 0.45 0.70 993 0.54 0.86 1053 0.61 1.05 1122 0.70
1600 0.22 815 0.37 0.38 883 0.43 0.56 959 0.52 0.72 1021 0.59 0.90 1089 0.68
1680 0.10 786 0.36 0.25 852 0.42 0.42 926 0.50 0.58 990 0.57 0.76 1057 0.66
1760 — — — 0.12 822 0.41 0.28 892 0.48 0.45 958 0.55 0.61 1024 0.64
1840 — — — — — — 0.15 858 0.46 0.31 926 0.53 0.47 992 0.62
1920 — — — — — — 0.01 824 0.45 0.17 895 0.51 0.32 960 0.60
YSC048E1**L,M 1280 0.66 894 0.40 0.81 967 0.48 1.01 1051 0.57 1.14 1101 0.63 — — —
Horizontal 1360 0.54 863 0.39 0.70 935 0.46 0.88 1016 0.55 1.01 1069 0.61 — — —
Airflow 1440 0.43 831 0.38 0.58 904 0.45 0.76 982 0.53 0.89 1037 0.60 1.05 1101 0.69
1520 0.31 799 0.36 0.47 872 0.43 0.63 947 0.51 0.77 1006 0.58 0.93 1069 0.67
1600 0.20 768 0.35 0.35 840 0.41 0.51 912 0.49 0.64 974 0.56 0.80 1037 0.65
1680 0.08 736 0.33 0.24 809 0.40 0.38 877 0.47 0.52 942 0.54 0.67 1005 0.63
1760 — — — 0.12 777 0.38 0.26 842 0.46 0.40 911 0.52 0.55 973 0.61
1840 — — — 0.01 745 0.37 0.13 807 0.44 0.28 879 0.51 0.42 941 0.59
1920 — — — — — — 0.00 773 0.42 0.15 847 0.49 0.29 909 0.57
5 YSC060E1**L,M 1600 0.97 1110 0.71 — — — — — — — — — — — —
Downflow 1700 0.79 1068 0.68 0.91 1120 0.77 — — — — — — — — —
Airflow 1800 0.60 1026 0.66 0.73 1079 0.74 — — — — — — — — —
1900 0.42 984 0.63 0.54 1038 0.71 0.69 1093 0.78 — — — — — —
2000 0.24 942 0.60 0.36 997 0.68 0.50 1050 0.74 0.60 1079 0.82 — — —
2100 0.06 900 0.57 0.18 956 0.65 0.31 1006 0.71 0.42 1040 0.79 0.52 1078 0.86
2200 — — — 0.00 916 0.63 0.12 963 0.68 0.24 1001 0.76 0.32 1036 0.83
2300 — — — — — — 0.00 936 0.66 0.05 962 0.73 0.13 994 0.79
2400 — — — — — — — — — — — — 0.00 965 0.77
YSC060E1**L,M 1600 0.83 1054 0.67 — — — — — — — — — — — —
Horizontal 1700 0.67 1013 0.65 0.83 1084 0.74 — — — — — — — — —
Airflow 1800 0.51 971 0.62 0.65 1039 0.71 0.75 1075 0.76 — — — — — —
1900 0.36 930 0.59 0.48 995 0.68 0.57 1031 0.73 0.72 1086 0.82 — — —
2000 0.20 888 0.57 0.30 951 0.65 0.39 987 0.70 0.54 1045 0.79 0.67 1092 0.87
2100 0.04 847 0.54 0.12 907 0.62 0.21 942 0.67 0.36 1004 0.76 0.48 1051 0.84
2200 — — — 0.00 877 0.60 0.02 898 0.64 0.17 963 0.73 0.29 1010 0.81
2300 — — — — — — — — — 0.00 924 0.70 0.10 968 0.77
2400 — — — — — — — — — — — — 0.00 946 0.76
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
RT-PRC023-EN 41
Performance Data
(3-5 Tons Standard Efficiency)
Table 32. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — High Heat — YSC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YSC036E1**H 960 0.43 718 0.19 0.64 825 0.26 0.88 923 0.34 1.12 1017 0.44 1.28 1074 0.51
Downflow 1020 0.37 696 0.19 0.57 800 0.26 0.80 900 0.34 1.04 997 0.43 1.20 1053 0.50
Airflow 1080 0.30 675 0.18 0.49 775 0.25 0.72 877 0.33 0.96 977 0.42 1.11 1033 0.49
1140 0.24 654 0.18 0.42 749 0.24 0.64 854 0.32 0.87 957 0.42 1.03 1013 0.48
1200 0.18 633 0.17 0.34 724 0.23 0.56 832 0.31 0.79 938 0.41 0.94 992 0.47
1260 0.11 612 0.16 0.26 698 0.22 0.48 809 0.30 0.71 918 0.40 0.86 972 0.46
1320 0.05 590 0.16 0.19 673 0.21 0.39 786 0.29 0.63 898 0.39 0.77 951 0.45
1380 — — — 0.11 647 0.21 0.31 763 0.28 0.55 878 0.38 0.68 931 0.44
1440 — — — 0.03 622 0.20 0.23 740 0.28 0.47 859 0.37 0.60 910 0.43
YSC036E1**H 960 0.44 732 0.20 0.65 836 0.27 0.87 935 0.35 1.12 1033 0.45 1.25 1078 0.51
Horizontal 1020 0.37 708 0.19 0.58 811 0.26 0.80 911 0.34 1.03 1010 0.44 1.17 1059 0.50
Airflow 1080 0.31 684 0.18 0.51 787 0.25 0.72 886 0.33 0.95 987 0.43 1.09 1040 0.49
1140 0.24 660 0.18 0.43 762 0.24 0.64 862 0.32 0.87 964 0.42 1.01 1021 0.48
1200 0.18 636 0.17 0.36 737 0.24 0.56 838 0.31 0.79 941 0.41 0.93 1002 0.47
1260 0.11 612 0.16 0.29 712 0.23 0.48 814 0.30 0.70 918 0.40 0.85 983 0.47
1320 0.05 588 0.16 0.21 688 0.22 0.40 789 0.29 0.62 895 0.39 0.77 964 0.46
1380 — — — 0.14 663 0.21 0.32 765 0.28 0.54 872 0.38 0.69 945 0.45
1440 — — — 0.07 638 0.20 0.24 741 0.28 0.45 849 0.37 0.61 926 0.44
4 YSC048E1**H 1280 0.73 951 0.44 0.93 1025 0.52 1.10 1084 0.60 — — — — — —
Downflow 1360 0.61 917 0.42 0.80 991 0.50 0.96 1051 0.58 1.14 1116 0.67 — — —
Airflow 1440 0.48 883 0.41 0.66 957 0.49 0.82 1019 0.56 1.00 1085 0.65 — — —
1520 0.35 849 0.39 0.53 923 0.47 0.69 986 0.55 0.86 1053 0.63 — — —
1600 0.23 816 0.38 0.39 888 0.45 0.55 954 0.53 0.72 1021 0.61 0.91 1093 0.71
1680 0.10 782 0.36 0.26 854 0.43 0.42 922 0.51 0.58 990 0.59 0.76 1060 0.68
1760 — — — 0.12 820 0.42 0.28 889 0.49 0.45 958 0.57 0.62 1028 0.66
1840 — — — — — — 0.14 857 0.47 0.31 926 0.55 0.47 995 0.64
1920 — — — — — — 0.01 824 0.46 0.17 895 0.53 0.32 962 0.62
YSC048E1**H 1280 0.69 933 0.43 0.86 1005 0.51 1.04 1075 0.59 1.18 1124 0.67 — — —
Horizontal 1360 0.57 899 0.42 0.74 971 0.49 0.91 1041 0.57 1.05 1091 0.65 — — —
Airflow 1440 0.45 865 0.40 0.61 938 0.48 0.78 1006 0.56 0.92 1059 0.63 — — —
1520 0.33 831 0.38 0.49 904 0.46 0.65 972 0.54 0.79 1026 0.61 0.95 1091 0.70
1600 0.21 797 0.37 0.36 870 0.44 0.52 938 0.52 0.65 993 0.59 0.82 1060 0.68
1680 0.08 764 0.35 0.24 837 0.42 0.38 904 0.50 0.52 961 0.57 0.69 1030 0.66
1760 — — — 0.11 803 0.41 0.25 870 0.48 0.39 928 0.55 0.55 999 0.65
1840 — — — — — — 0.12 835 0.46 0.26 896 0.54 0.42 968 0.63
1920 — — — — — — — — — 0.12 863 0.52 0.29 937 0.61
5 YSC060E1**H 1600 0.97 1110 0.73 — — — — — — — — — — — —
Downflow 1700 0.79 1068 0.70 0.91 1120 0.78 — — — — — — — — —
Airflow 1800 0.60 1026 0.67 0.73 1079 0.75 — — — — — — — — —
1900 0.42 984 0.65 0.54 1038 0.72 0.69 1093 0.81 — — — — — —
2000 0.24 942 0.62 0.36 997 0.69 0.50 1050 0.78 0.60 1079 0.84 — — —
2100 0.06 900 0.59 0.18 956 0.66 0.31 1006 0.74 0.42 1040 0.81 0.52 1078 0.86
2200 — — — 0.00 916 0.64 0.12 963 0.71 0.24 1001 0.78 0.32 1036 0.83
2300 — — — — — — 0.00 936 0.69 0.05 962 0.75 0.13 994 0.79
2400 — — — — — — — — — — — — 0.00 965 0.77
YSC060E1**H 1600 0.95 1110 0.73 — — — — — — — — — — — —
Horizontal 1700 0.76 1064 0.70 0.87 1110 0.77 — — — — — — — — —
Airflow 1800 0.58 1019 0.67 0.69 1067 0.74 — — — — — — — — —
1900 0.40 973 0.64 0.51 1024 0.71 0.64 1075 0.79 — — — — — —
2000 0.21 927 0.61 0.32 982 0.68 0.45 1033 0.76 0.55 1069 0.83 0.64 1103 0.88
2100 0.03 882 0.58 0.14 939 0.65 0.26 991 0.73 0.37 1029 0.80 0.45 1060 0.85
2200 — — — 0.00 907 0.63 0.08 949 0.70 0.18 989 0.77 0.26 1017 0.81
2300 — — — — — — — — — 0.00 949 0.74 0.07 975 0.78
2400 — — — — — — — — — — — — — — —
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
42 RT-PRC023-EN
Performance Data
(3-5 Tons Standard Efficiency)
Table 33. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — WSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 WSC036E1 960 0.43 707 0.21 0.70 843 0.38 0.88 919 0.38 1.02 979 0.36 1.15 1027 0.50
Downflow 1020 0.37 687 0.20 0.62 818 0.37 0.80 896 0.37 0.94 956 0.35 1.07 1006 0.49
Airflow 1080 0.31 668 0.19 0.55 792 0.36 0.73 872 0.36 0.87 933 0.34 0.99 985 0.48
1140 0.25 648 0.19 0.47 766 0.35 0.65 849 0.35 0.79 911 0.33 0.91 964 0.47
1200 0.19 628 0.18 0.39 740 0.34 0.57 826 0.34 0.71 888 0.32 0.83 943 0.46
1260 0.13 609 0.18 0.31 715 0.32 0.50 803 0.33 0.63 866 0.32 0.75 922 0.45
1320 0.07 589 0.17 0.24 689 0.31 0.42 780 0.32 0.56 843 0.31 0.68 901 0.44
1380 0.01 569 0.17 0.16 663 0.30 0.34 757 0.31 0.48 820 0.30 0.60 880 0.43
1440 — — — 0.08 637 0.29 0.26 734 0.30 0.40 798 0.29 0.52 859 0.42
WSC036E1 960 0.40 707 0.21 0.69 856 0.31 0.88 941 0.39 1.03 987 0.45 1.16 1034 0.50
Horizontal 1020 0.35 688 0.20 0.62 831 0.30 0.80 916 0.38 0.95 967 0.44 1.08 1011 0.49
Airflow 1080 0.30 669 0.19 0.55 806 0.29 0.73 891 0.37 0.87 947 0.43 1.00 989 0.48
1140 0.24 650 0.19 0.48 781 0.28 0.65 866 0.36 0.79 927 0.42 0.92 966 0.47
1200 0.19 631 0.18 0.41 756 0.28 0.58 841 0.35 0.71 906 0.41 0.84 943 0.46
1260 0.14 612 0.18 0.34 731 0.27 0.50 816 0.34 0.63 886 0.40 0.76 920 0.45
1320 0.09 593 0.17 0.26 706 0.26 0.43 791 0.33 0.55 866 0.39 0.68 898 0.44
1380 0.04 574 0.17 0.19 681 0.25 0.35 766 0.32 0.47 846 0.38 0.60 875 0.43
1440 — — — 0.12 655 0.24 0.28 741 0.30 0.40 826 0.37 0.52 852 0.42
4 WSC048E1 1280 0.60 865 0.36 0.84 977 0.47 1.02 1044 0.55 1.17 1090 0.63 — — —
Downflow 1360 0.48 833 0.35 0.72 944 0.45 0.90 1012 0.54 1.04 1062 0.61 — — —
Airflow 1440 0.37 802 0.34 0.60 912 0.44 0.77 980 0.52 0.92 1033 0.60 — — —
1520 0.25 770 0.32 0.48 879 0.42 0.65 948 0.50 0.80 1005 0.58 1.06 1100 0.69
1600 0.14 739 0.31 0.36 846 0.41 0.52 915 0.49 0.68 976 0.56 0.92 1069 0.67
1680 0.02 707 0.30 0.24 814 0.39 0.39 883 0.47 0.56 948 0.55 0.78 1038 0.65
1760 — — — 0.13 781 0.38 0.27 851 0.45 0.43 920 0.53 0.64 1006 0.63
1840 — — — 0.01 748 0.36 0.14 819 0.43 0.31 891 0.52 0.50 975 0.62
1920 — — — — — — 0.02 787 0.42 0.19 863 0.50 0.37 944 0.60
WSC048E1 1280 0.61 864 0.36 0.84 967 0.47 1.00 1038 0.55 1.16 1115 0.65 — — —
Horizontal 1360 0.51 831 0.35 0.73 935 0.45 0.88 1006 0.53 1.05 1084 0.63 — — —
Airflow 1440 0.40 798 0.33 0.62 904 0.44 0.77 974 0.52 0.94 1052 0.61 1.10 1114 0.70
1520 0.30 766 0.32 0.51 873 0.42 0.66 943 0.50 0.82 1020 0.59 0.99 1084 0.68
1600 0.19 733 0.31 0.40 842 0.41 0.55 911 0.48 0.71 989 0.57 0.87 1054 0.66
1680 0.09 701 0.29 0.29 810 0.39 0.44 879 0.47 0.60 957 0.55 0.75 1023 0.65
1760 — — — 0.18 779 0.38 0.32 848 0.45 0.48 925 0.54 0.64 993 0.63
1840 — — — 0.08 748 0.36 0.21 816 0.43 0.37 893 0.52 0.52 963 0.61
1920 — — — — — — 0.10 784 0.42 0.26 861 0.50 0.40 932 0.59
5 WSC060E1 1600 0.83 888 0.49 0.95 948 0.56 1.19 1048 0.67 — — — — — —
Downflow 1700 0.69 847 0.46 0.82 908 0.53 1.04 1004 0.64 1.33 1110 0.78 — — —
Airflow 1800 0.56 806 0.44 0.69 867 0.51 0.90 959 0.62 1.18 1063 0.75 — — —
1900 0.43 764 0.42 0.56 826 0.48 0.76 915 0.59 1.02 1016 0.71 — — —
2000 0.30 723 0.40 0.43 785 0.46 0.62 870 0.56 0.87 969 0.68 1.18 1089 0.88
2100 0.16 681 0.37 0.30 744 0.44 0.47 826 0.53 0.71 922 0.65 1.03 1044 0.84
2200 0.03 640 0.35 0.17 703 0.41 0.33 781 0.50 0.56 876 0.61 0.87 999 0.81
2300 — — — 0.04 663 0.39 0.19 737 0.47 0.41 829 0.58 0.72 954 0.77
2400 — — — — — — 0.05 693 0.44 0.25 782 0.55 0.56 909 0.73
WSC060E1 1600 0.76 884 0.48 0.82 932 0.55 0.98 1022 0.66 1.13 1104 0.77 — — —
Horizontal 1700 0.63 842 0.46 0.69 893 0.52 0.85 981 0.63 1.00 1061 0.74 — — —
Airflow 1800 0.50 801 0.44 0.57 854 0.50 0.72 941 0.60 0.87 1018 0.71 — — —
1900 0.36 759 0.42 0.45 815 0.48 0.60 900 0.58 0.74 975 0.68 — — —
2000 0.23 718 0.39 0.32 776 0.46 0.47 859 0.55 0.61 932 0.65 0.87 1069 0.86
2100 0.10 676 0.37 0.20 737 0.43 0.34 818 0.53 0.49 890 0.62 0.74 1025 0.83
2200 — — — 0.07 699 0.41 0.22 778 0.50 0.36 847 0.59 0.61 980 0.79
2300 — — — — — — 0.09 737 0.47 0.23 804 0.56 0.48 936 0.75
2400 — — — — — — — — — 0.10 761 0.53 0.35 892 0.72
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
RT-PRC023-EN 43
Performance Data
(3-5 Tons High Efficiency)
Table 34. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — No Electric Heat — THC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 THC036E1,3,4 960 0.45 715 0.21 0.74 851 0.31 0.92 929 0.38 1.07 993 0.44 1.25 1053 0.52
Downflow 1020 0.39 695 0.20 0.66 826 0.30 0.84 905 0.37 0.99 969 0.43 1.17 1030 0.50
Airflow 1080 0.33 675 0.20 0.59 800 0.29 0.77 880 0.36 0.91 945 0.42 1.08 1007 0.49
1140 0.27 654 0.19 0.51 774 0.28 0.69 855 0.35 0.83 921 0.41 1.00 985 0.48
1200 0.21 634 0.18 0.43 749 0.27 0.61 831 0.34 0.75 898 0.40 0.91 962 0.47
1260 0.15 614 0.18 0.35 723 0.26 0.53 806 0.33 0.67 874 0.39 0.83 939 0.46
1320 0.09 593 0.17 0.28 697 0.25 0.45 782 0.32 0.59 850 0.38 0.74 916 0.45
1380 0.03 573 0.17 0.20 671 0.24 0.37 757 0.31 0.51 826 0.37 0.66 893 0.44
1440 — — — 0.12 646 0.23 0.29 732 0.30 0.43 802 0.36 0.57 871 0.43
THC036E1,3,4 960 0.45 711 0.21 0.70 835 0.30 0.89 913 0.37 1.04 978 0.44 1.21 1037 0.51
Horizontal 1020 0.39 689 0.20 0.63 811 0.29 0.81 890 0.36 0.96 957 0.43 1.13 1016 0.50
Airflow 1080 0.32 667 0.19 0.56 787 0.28 0.73 868 0.35 0.88 935 0.42 1.04 996 0.49
1140 0.26 644 0.19 0.48 763 0.28 0.65 845 0.34 0.80 913 0.41 0.95 975 0.48
1200 0.20 622 0.18 0.41 739 0.27 0.57 823 0.33 0.72 892 0.40 0.87 955 0.47
1260 0.13 599 0.17 0.33 715 0.26 0.50 800 0.32 0.64 870 0.39 0.78 934 0.46
1320 0.07 577 0.17 0.26 691 0.25 0.42 777 0.32 0.56 848 0.38 0.69 913 0.45
1380 0.01 555 0.16 0.18 667 0.24 0.34 755 0.31 0.48 826 0.37 0.61 893 0.44
1440 — — — 0.11 642 0.23 0.26 732 0.30 0.40 805 0.36 0.52 872 0.43
4 THC048E1,3,4 1280 0.65 805 0.31 0.86 902 0.40 1.04 966 0.48 1.27 1042 0.58 — — —
Downflow 1360 0.55 769 0.30 0.76 866 0.38 0.94 934 0.46 1.17 1010 0.56 1.43 1113 0.68
Airflow 1440 0.46 733 0.28 0.66 830 0.37 0.84 902 0.44 1.06 977 0.54 1.31 1078 0.66
1520 0.36 696 0.27 0.56 794 0.35 0.74 869 0.43 0.95 944 0.52 1.20 1043 0.64
1600 0.27 660 0.25 0.46 758 0.33 0.63 837 0.41 0.85 912 0.50 1.08 1009 0.62
1680 0.17 624 0.24 0.36 722 0.32 0.53 805 0.40 0.74 879 0.49 0.97 974 0.60
1760 — — — 0.26 686 0.30 0.43 772 0.38 0.63 847 0.47 0.85 939 0.58
1840 — — — 0.16 650 0.29 0.33 740 0.36 0.53 814 0.45 0.74 905 0.55
1920 — — — 0.06 614 0.27 0.23 707 0.35 0.42 782 0.43 0.62 870 0.53
THC048E1,3,4 1280 0.56 795 0.31 0.77 880 0.39 0.95 967 0.48 1.16 1040 0.57 — — —
Horizontal 1360 0.48 760 0.29 0.67 847 0.37 0.86 935 0.46 1.06 1010 0.56 1.26 1105 0.68
Airflow 1440 0.39 725 0.28 0.58 814 0.36 0.76 903 0.44 0.96 980 0.54 1.16 1075 0.66
1520 0.30 690 0.27 0.48 780 0.34 0.66 871 0.43 0.86 951 0.53 1.06 1045 0.64
1600 0.22 655 0.25 0.39 747 0.33 0.57 838 0.41 0.76 921 0.51 0.96 1016 0.62
1680 0.13 619 0.24 0.30 714 0.31 0.47 806 0.40 0.66 891 0.49 0.86 986 0.60
1760 — — — 0.20 681 0.30 0.37 774 0.38 0.56 861 0.48 0.76 956 0.59
1840 — — — 0.11 647 0.29 0.28 742 0.37 0.46 831 0.46 0.66 926 0.57
1920 — — — 0.01 614 0.27 0.18 710 0.35 0.36 802 0.44 0.56 896 0.55
5 THC060E1,3,4 1600 0.82 918 0.50 1.04 1002 0.60 1.26 1087 0.72 — — — — — —
Downflow 1700 0.67 873 0.47 0.89 957 0.58 1.11 1043 0.69 — — — — — —
Airflow 1800 0.53 828 0.45 0.74 913 0.55 0.96 1000 0.66 1.16 1083 0.78 — — —
1900 0.39 782 0.42 0.59 869 0.52 0.82 957 0.63 1.02 1041 0.75 1.17 1099 0.85
2000 0.25 737 0.40 0.45 824 0.50 0.67 914 0.60 0.87 999 0.72 1.02 1056 0.82
2100 0.11 692 0.37 0.30 780 0.47 0.52 870 0.58 0.72 957 0.69 0.87 1014 0.78
2200 — — — 0.15 735 0.44 0.37 827 0.55 0.57 914 0.66 0.71 971 0.75
2300 — — — 0.00 691 0.42 0.22 784 0.52 0.42 872 0.63 0.56 929 0.72
2400 — — — — — — 0.07 741 0.49 0.27 830 0.60 0.41 886 0.68
THC060E1,3,4 1600 0.71 918 0.50 0.91 1001 0.60 1.09 1070 0.71 — — — — — —
Horizontal 1700 0.59 875 0.47 0.78 959 0.58 0.96 1029 0.68 1.11 1102 0.79 — — —
Airflow 1800 0.46 832 0.45 0.65 916 0.55 0.82 987 0.65 0.97 1063 0.77 — — —
1900 0.33 788 0.43 0.51 874 0.53 0.68 945 0.62 0.84 1023 0.74 1.01 1093 0.85
2000 0.21 745 0.40 0.38 831 0.50 0.54 903 0.60 0.71 984 0.71 0.87 1052 0.81
2100 0.08 701 0.38 0.25 788 0.47 0.41 861 0.57 0.57 944 0.68 0.73 1010 0.78
2200 — — — 0.12 746 0.45 0.27 819 0.54 0.44 904 0.65 0.59 968 0.75
2300 — — — — — — 0.13 778 0.51 0.31 865 0.62 0.45 926 0.72
2400 — — — — — — — — — 0.17 825 0.59 0.31 884 0.68
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
44 RT-PRC023-EN
Performance Data
(3-5 Tons High Efficiency)
Table 35. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — Low & Medium Gas Heat — YHC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YHC036E1,3,4**L,M 960 0.43 718 0.19 0.64 825 0.27 0.88 923 0.35 1.12 1017 0.46 1.28 1074 0.52
Downflow 1020 0.37 696 0.18 0.57 800 0.26 0.80 900 0.35 1.04 997 0.45 1.20 1053 0.51
Airflow 1080 0.30 675 0.18 0.49 775 0.26 0.72 877 0.34 0.96 977 0.44 1.11 1033 0.50
1140 0.24 654 0.17 0.42 749 0.25 0.64 854 0.33 0.87 957 0.43 1.03 1013 0.49
1200 0.18 633 0.17 0.34 724 0.24 0.56 832 0.32 0.79 938 0.42 0.94 992 0.48
1260 0.11 612 0.16 0.26 698 0.23 0.48 809 0.31 0.71 918 0.41 0.86 972 0.47
1320 0.05 590 0.16 0.19 673 0.22 0.39 786 0.30 0.63 898 0.40 0.77 951 0.46
1380 — — — 0.11 647 0.21 0.31 763 0.29 0.55 878 0.39 0.68 931 0.45
1440 — — — 0.03 622 0.21 0.23 740 0.28 0.47 859 0.38 0.60 910 0.44
YHC036E1,3,4**L,M 960 0.42 715 0.19 0.67 842 0.28 0.90 937 0.36 1.15 1037 0.46 1.25 1062 0.51
Horizontal 1020 0.37 695 0.18 0.61 819 0.27 0.83 916 0.35 1.07 1014 0.45 1.18 1047 0.50
Airflow 1080 0.31 675 0.18 0.54 796 0.26 0.75 895 0.34 0.99 992 0.44 1.11 1032 0.50
1140 0.26 654 0.17 0.47 772 0.26 0.68 874 0.34 0.91 970 0.43 1.04 1017 0.49
1200 0.20 634 0.17 0.41 749 0.25 0.61 853 0.33 0.83 948 0.42 0.97 1002 0.48
1260 0.14 614 0.16 0.34 725 0.24 0.54 832 0.32 0.75 926 0.41 0.90 987 0.48
1320 0.09 594 0.16 0.27 702 0.23 0.47 811 0.31 0.67 903 0.40 0.83 972 0.47
1380 0.03 574 0.15 0.20 678 0.22 0.40 789 0.30 0.59 881 0.39 0.76 957 0.46
1440 — — — 0.14 654 0.22 0.33 768 0.29 0.51 859 0.38 0.69 942 0.45
4 YHC048E1,3,4**L,M 1280 0.69 820 0.33 0.88 903 0.41 1.07 969 0.49 1.07 969 0.49 1.27 1039 0.58
Downflow 1360 0.59 785 0.32 0.78 869 0.40 0.96 936 0.48 0.96 936 0.48 1.16 1007 0.56
Airflow 1440 0.49 750 0.30 0.68 835 0.38 0.86 903 0.46 0.86 903 0.46 1.05 976 0.55
1520 0.40 714 0.29 0.58 801 0.37 0.75 870 0.44 0.75 870 0.44 0.94 944 0.53
1600 0.30 679 0.27 0.48 767 0.35 0.65 837 0.42 0.65 837 0.42 0.84 912 0.51
1680 0.20 643 0.26 0.38 733 0.34 0.54 804 0.41 0.54 804 0.41 0.73 881 0.49
1760 0.10 608 0.25 0.28 699 0.32 0.44 771 0.39 0.44 771 0.39 0.62 849 0.48
1840 0.01 572 0.23 0.18 666 0.31 0.33 738 0.37 0.33 738 0.37 0.51 817 0.46
1920 — — — 0.08 632 0.29 0.23 705 0.36 0.23 705 0.36 0.41 786 0.44
YHC048E1,3,4**L,M 1280 0.61 813 0.33 0.81 896 0.41 1.00 977 0.50 1.00 977 0.50 1.17 1044 0.58
Horizontal 1360 0.51 777 0.31 0.70 862 0.40 0.89 944 0.48 0.89 944 0.48 1.06 1011 0.57
Airflow 1440 0.42 742 0.30 0.60 828 0.38 0.79 911 0.46 0.79 911 0.46 0.95 979 0.55
1520 0.32 707 0.28 0.50 794 0.36 0.68 878 0.45 0.68 878 0.45 0.84 946 0.53
1600 0.22 671 0.27 0.40 760 0.35 0.57 845 0.43 0.57 845 0.43 0.73 913 0.51
1680 0.13 636 0.26 0.29 725 0.33 0.46 812 0.41 0.46 812 0.41 0.62 881 0.49
1760 0.03 600 0.24 0.19 691 0.32 0.36 779 0.40 0.36 779 0.40 0.51 848 0.47
1840 — — — 0.09 657 0.30 0.25 746 0.38 0.25 746 0.38 0.40 815 0.46
1920 — — — — — — 0.14 713 0.36 0.14 713 0.36 0.29 783 0.44
5 YHC060E1,3,4**L,M 1600 0.90 962 0.55 1.07 1027 0.64 1.28 1099 0.75 — — — — — —
Downflow 1700 0.76 919 0.53 0.93 985 0.61 1.14 1060 0.72 — — — — — —
Airflow 1800 0.62 875 0.50 0.78 943 0.59 0.99 1022 0.70 1.15 1092 0.81 — — —
1900 0.48 832 0.48 0.64 900 0.56 0.84 984 0.67 1.00 1051 0.78 1.18 1116 0.89
2000 0.34 788 0.45 0.49 858 0.53 0.70 945 0.65 0.86 1010 0.75 1.03 1076 0.86
2100 0.20 745 0.43 0.35 815 0.51 0.55 907 0.62 0.71 969 0.72 0.88 1037 0.83
2200 0.06 701 0.40 0.20 773 0.48 0.41 868 0.59 0.56 928 0.69 0.73 997 0.80
2300 — — — 0.06 730 0.46 0.26 830 0.57 0.41 887 0.66 0.58 958 0.77
2400 — — — — — — 0.12 792 0.54 0.26 846 0.63 0.43 918 0.73
YHC060E1,3,4**L,M 1600 0.75 944 0.54 0.91 1010 0.63 1.10 1094 0.75 — — — — — —
Horizontal 1700 0.61 899 0.52 0.77 969 0.60 0.96 1052 0.72 1.12 1114 0.82 — — —
Airflow 1800 0.48 855 0.49 0.63 927 0.58 0.82 1011 0.69 0.97 1074 0.79 — — —
1900 0.34 811 0.47 0.49 885 0.55 0.67 969 0.66 0.83 1035 0.76 1.01 1111 0.89
2000 0.20 766 0.44 0.35 843 0.53 0.53 928 0.63 0.68 995 0.74 0.87 1070 0.85
2100 0.07 722 0.42 0.21 801 0.50 0.39 887 0.61 0.54 956 0.71 0.72 1028 0.82
2200 — — — 0.07 759 0.47 0.25 845 0.58 0.39 916 0.68 0.57 987 0.79
2300 — — — — — — 0.10 804 0.55 0.25 877 0.65 0.42 945 0.76
2400 — — — — — — — — — 0.10 837 0.62 0.27 904 0.72
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
RT-PRC023-EN 45
Performance Data
(3-5 Tons High Efficiency)
Table 36. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — High Heat — YHC036,048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YHC036E1,3,4**H 960 0.43 718 0.19 0.64 825 0.26 0.88 923 0.34 1.12 1017 0.44 1.28 1074 0.51
Downflow 1020 0.37 696 0.19 0.57 800 0.26 0.80 900 0.34 1.04 997 0.43 1.20 1053 0.50
Airflow 1080 0.30 675 0.18 0.49 775 0.25 0.72 877 0.33 0.96 977 0.42 1.11 1033 0.49
1140 0.24 654 0.18 0.42 749 0.24 0.64 854 0.32 0.87 957 0.42 1.03 1013 0.48
1200 0.18 633 0.17 0.34 724 0.23 0.56 832 0.31 0.79 938 0.41 0.94 992 0.47
1260 0.11 612 0.16 0.26 698 0.22 0.48 809 0.30 0.71 918 0.40 0.86 972 0.46
1320 0.05 590 0.16 0.19 673 0.21 0.39 786 0.29 0.63 898 0.39 0.77 951 0.45
1380 — — — 0.11 647 0.21 0.31 763 0.28 0.55 878 0.38 0.68 931 0.44
1440 — — — 0.03 622 0.20 0.23 740 0.28 0.47 859 0.37 0.60 910 0.43
YHC036E1,3,4**H 960 0.44 732 0.20 0.65 836 0.27 0.87 935 0.35 1.12 1033 0.45 1.25 1078 0.51
Horizontal 1020 0.37 708 0.19 0.58 811 0.26 0.80 911 0.34 1.03 1010 0.44 1.17 1059 0.50
Airflow 1080 0.31 684 0.18 0.51 787 0.25 0.72 886 0.33 0.95 987 0.43 1.09 1040 0.49
1140 0.24 660 0.18 0.43 762 0.24 0.64 862 0.32 0.87 964 0.42 1.01 1021 0.48
1200 0.18 636 0.17 0.36 737 0.24 0.56 838 0.31 0.79 941 0.41 0.93 1002 0.47
1260 0.11 612 0.16 0.29 712 0.23 0.48 814 0.30 0.70 918 0.40 0.85 983 0.47
1320 0.05 588 0.16 0.21 688 0.22 0.40 789 0.29 0.62 895 0.39 0.77 964 0.46
1380 — — — 0.14 663 0.21 0.32 765 0.28 0.54 872 0.38 0.69 945 0.45
1440 — — — 0.07 638 0.20 0.24 741 0.28 0.45 849 0.37 0.61 926 0.44
4 YHC048E1,3,4**H 1280 0.69 833 0.35 0.90 924 0.43 1.07 989 0.51 1.07 989 0.51 1.27 1066 0.61
Downflow 1360 0.60 796 0.33 0.80 889 0.42 0.97 956 0.50 0.97 956 0.50 1.17 1033 0.59
Airflow 1440 0.50 759 0.32 0.71 855 0.40 0.87 922 0.48 0.87 922 0.48 1.06 1000 0.57
1520 0.40 722 0.30 0.61 820 0.39 0.77 889 0.46 0.77 889 0.46 0.96 966 0.56
1600 0.31 684 0.29 0.51 785 0.37 0.67 855 0.44 0.67 855 0.44 0.85 933 0.54
1680 0.21 647 0.27 0.41 751 0.35 0.57 822 0.43 0.57 822 0.43 0.75 900 0.52
1760 0.12 610 0.26 0.31 716 0.34 0.47 788 0.41 0.47 788 0.41 0.64 867 0.50
1840 — — — 0.22 681 0.32 0.37 755 0.39 0.37 755 0.39 0.54 834 0.48
1920 — — — 0.12 647 0.30 0.27 721 0.37 0.27 721 0.37 0.43 801 0.46
YHC048E1,3,4**H 1280 0.60 822 0.34 0.81 912 0.43 0.97 986 0.51 0.97 986 0.51 1.18 1063 0.61
Horizontal 1360 0.51 787 0.33 0.70 876 0.41 0.87 952 0.49 0.87 952 0.49 1.07 1031 0.59
Airflow 1440 0.41 752 0.31 0.60 840 0.40 0.76 918 0.48 0.76 918 0.48 0.96 998 0.57
1520 0.31 718 0.30 0.49 805 0.38 0.66 885 0.46 0.66 885 0.46 0.84 966 0.56
1600 0.22 683 0.29 0.38 769 0.36 0.55 851 0.44 0.55 851 0.44 0.73 933 0.54
1680 0.12 648 0.27 0.28 733 0.34 0.45 818 0.42 0.45 818 0.42 0.62 901 0.52
1760 0.03 613 0.26 0.17 697 0.33 0.34 784 0.41 0.34 784 0.41 0.51 868 0.50
1840 — — — 0.07 661 0.31 0.23 750 0.39 0.23 750 0.39 0.40 836 0.48
1920 — — — — — — 0.13 717 0.37 0.13 717 0.37 0.29 803 0.46
5 YHC060E1,3,4**H 1600 0.90 955 0.57 1.06 1022 0.66 1.25 1095 0.77 — — — — — —
Downflow 1700 0.76 910 0.54 0.92 977 0.63 1.11 1052 0.74 1.28 1113 0.85 — — —
Airflow 1800 0.62 865 0.52 0.77 932 0.60 0.96 1009 0.71 1.13 1072 0.82 — — —
1900 0.47 819 0.49 0.63 888 0.57 0.82 966 0.68 0.98 1031 0.79 1.18 1105 0.91
2000 0.33 774 0.46 0.49 843 0.54 0.67 922 0.65 0.83 990 0.75 1.02 1062 0.87
2100 0.19 729 0.44 0.34 798 0.52 0.52 879 0.62 0.68 949 0.72 0.87 1019 0.84
2200 0.04 683 0.41 0.20 754 0.49 0.38 836 0.59 0.54 908 0.69 0.71 976 0.80
2300 — — — 0.05 709 0.46 0.23 793 0.56 0.39 867 0.66 0.55 933 0.77
2400 — — — — — — 0.09 750 0.53 0.24 826 0.63 0.40 890 0.73
YHC060E1,3,4**H 1600 0.77 948 0.57 0.95 1016 0.66 1.10 1093 0.77 — — — — — —
Horizontal 1700 0.63 903 0.54 0.80 973 0.63 0.96 1052 0.74 — — — — — —
Airflow 1800 0.48 859 0.51 0.66 930 0.60 0.81 1012 0.71 1.00 1084 0.83 — — —
1900 0.34 814 0.49 0.51 888 0.57 0.67 971 0.68 0.85 1042 0.79 1.01 1106 0.91
2000 0.20 770 0.46 0.36 845 0.55 0.52 931 0.65 0.70 1000 0.76 0.86 1063 0.87
2100 0.06 725 0.43 0.22 803 0.52 0.38 890 0.62 0.55 959 0.73 0.70 1021 0.84
2200 — — — 0.07 760 0.49 0.23 850 0.60 0.39 917 0.70 0.54 979 0.80
2300 — — — — — — 0.09 809 0.57 0.24 875 0.67 0.39 937 0.77
2400 — — — — — — — — 0.00 0.09 833 0.63 0.23 894 0.73
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.
46 RT-PRC023-EN
.
Performance Data
Table 37. Belt Drive Evaporator Fan Performance — 3 Tons — TSC036E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 608 0.17 676 0.22 734 0.27 785 0.32 833 0.37 878 0.42 922 0.47 963 0.53
1080 — — 557 0.15 629 0.20 697 0.25 757 0.30 809 0.36 857 0.42 901 0.47 944 0.53 983 0.59
1200 — — 588 0.18 653 0.23 718 0.29 777 0.35 832 0.41 881 0.47 925 0.53 967 0.59 1006 0.66
1320 553 0.17 621 0.22 681 0.27 741 0.33 799 0.39 854 0.46 903 0.53 948 0.59 990 0.66 1030 0.73
1440 591 0.21 655 0.27 712 0.32 766 0.38 821 0.44 873 0.51 923 0.58 970 0.66 1014 0.73 1053 0.80
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure drop due to
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1002 0.59 1039 0.65 1073 0.70 1107 0.76 1138 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1022 0.65 1059 0.71 1095 0.78 1129 0.84 1162 0.91 Using the full horsepower range of our fan motors as shown in our
1200 1044 0.72 1081 0.79 1115 0.85 1149 0.92 1183 0.99 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1068 0.80 1104 0.87 1138 0.94 1172 1.01 1205 1.08
1440 1091 0.88 1127 0.95 1161 1.03 1195 1.10 1227 1.18
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 38. Belt Drive Evaporator Fan Performance — 3 Tons — TSC036E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 619 0.16 680 0.20 738 0.25 791 0.30 840 0.35 885 0.39 927 0.44 968 0.49
1080 — — 570 0.14 647 0.19 708 0.24 762 0.29 814 0.34 863 0.39 908 0.45 950 0.50 991 0.55
1200 — — 595 0.17 674 0.23 736 0.28 789 0.33 839 0.39 885 0.44 931 0.50 973 0.56 1013 0.62
1320 551 0.16 622 0.20 698 0.26 764 0.33 817 0.38 866 0.44 911 0.50 954 0.56 997 0.62 1036 0.68
1440 588 0.20 653 0.24 722 0.30 789 0.37 846 0.44 894 0.50 938 0.56 980 0.63 1020 0.69 1060 0.76
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1005 0.54 1040 0.59 1074 0.64 1107 0.69 1139 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1029 0.61 1066 0.67 1100 0.72 1134 0.77 1165 0.83 Using the full horsepower range of our fan motors as shown in our
1200 1052 0.68 1088 0.74 1124 0.80 1157 0.86 1190 0.92 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1074 0.75 1112 0.82 1147 0.88 1181 0.95 1213 1.02
1440 1098 0.83 1134 0.90 1169 0.97 1203 1.04 1237 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 47
Performance Data
(3 Tons Standard Efficiency)
Table 39. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 600 0.15 664 0.19 722 0.23 774 0.27 824 0.31 870 0.36 913 0.41 952 0.45
1080 — — 560 0.14 625 0.17 687 0.22 743 0.26 795 0.31 844 0.36 890 0.40 933 0.45 973 0.51
1200 — — 593 0.17 655 0.21 712 0.25 767 0.30 817 0.35 865 0.40 910 0.45 952 0.51 993 0.56
1320 — — 626 0.20 685 0.25 740 0.29 791 0.34 841 0.40 887 0.45 931 0.51 974 0.56 1014 0.62
1440 592 0.20 660 0.25 718 0.29 769 0.34 818 0.39 866 0.45 911 0.51 955 0.57 996 0.63 1034 0.69
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.50 1025 0.55 1058 0.59 1091 0.64 1120 0.69 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1012 0.56 1047 0.61 1083 0.66 1116 0.72 1148 0.77 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.62 1069 0.67 1104 0.73 1138 0.79 1171 0.85 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1051 0.68 1088 0.74 1124 0.80 1159 0.86 1191 0.93
1440 1072 0.75 1108 0.81 1145 0.88 1179 0.94 1212 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 40. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 605 0.15 670 0.19 726 0.24 776 0.28 824 0.32 871 0.37 915 0.42 955 0.47
1080 — — 556 0.14 628 0.18 693 0.23 750 0.27 801 0.32 847 0.37 891 0.42 932 0.47 975 0.52
1200 — — 584 0.17 653 0.21 717 0.26 773 0.31 825 0.37 872 0.42 915 0.47 955 0.52 994 0.58
1320 — — 614 0.20 679 0.25 740 0.30 796 0.36 848 0.41 896 0.47 940 0.53 980 0.59 1018 0.65
1440 582 0.19 646 0.24 708 0.29 767 0.35 820 0.40 871 0.47 920 0.53 963 0.59 1005 0.66 1043 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 994 0.52 1031 0.58 1066 0.63 1101 0.69 1131 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously
1080 1013 0.58 1051 0.63 1087 0.69 1122 0.75 1155 0.81 at all cataloged conditions. Using the full horsepower range of our fan
1200 1032 0.63 1069 0.69 1105 0.75 1140 0.82 1175 0.88 motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our product’s warranty will not be
1320 1056 0.70 1090 0.76 1125 0.82 1159 0.89 1193 0.96 affected.
1440 1079 0.78 1114 0.84 1148 0.91 1181 0.97 1211 1.04
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
48 RT-PRC023-EN
Performance Data
(3 Tons Standard Efficiency)
Table 41. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 603 0.15 664 0.19 722 0.24 775 0.28 824 0.33 869 0.37 912 0.42 953 0.47
1080 — — 568 0.14 632 0.18 690 0.23 744 0.27 796 0.32 844 0.37 889 0.42 933 0.47 973 0.53
1200 — — 602 0.18 663 0.22 718 0.27 770 0.31 819 0.36 865 0.42 911 0.47 953 0.53 993 0.58
1320 572 0.17 638 0.22 695 0.26 748 0.31 798 0.36 845 0.41 889 0.47 932 0.53 974 0.58 1015 0.65
1440 611 0.21 674 0.27 729 0.31 779 0.36 827 0.42 872 0.47 915 0.53 957 0.59 997 0.65 1036 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.52 1026 0.58 1060 0.63 1092 0.68 1123 0.73 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1011 0.58 1047 0.63 1083 0.69 1115 0.75 1148 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1033 0.64 1069 0.70 1105 0.76 1138 0.82 1170 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1053 0.71 1089 0.77 1124 0.83 1159 0.90 1191 0.96
1440 1074 0.78 1109 0.84 1145 0.91 1178 0.98 1212 1.05
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 42. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 615 0.16 678 0.20 737 0.24 789 0.29 838 0.33 883 0.38 923 0.42 962 0.47
1080 — — 576 0.14 643 0.19 704 0.23 760 0.28 812 0.32 861 0.38 906 0.43 949 0.48 988 0.53
1200 — — 608 0.18 673 0.22 732 0.27 785 0.32 836 0.37 883 0.42 928 0.48 971 0.53 1012 0.59
1320 571 0.17 642 0.22 705 0.26 761 0.31 813 0.37 862 0.42 908 0.48 952 0.53 995 0.59 1034 0.66
1440 609 0.21 677 0.26 737 0.31 791 0.37 841 0.42 889 0.48 934 0.54 977 0.60 1017 0.66 1057 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 999 0.52 1034 0.57 1068 0.62 1100 0.67 1132 0.72 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1024 0.58 1061 0.64 1094 0.69 1126 0.74 1156 0.79 Using the full horsepower range of our fan motors as shown in our
1200 1050 0.65 1086 0.71 1120 0.77 1153 0.83 1183 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1072 0.72 1109 0.78 1145 0.85 1177 0.91 1209 0.98
1440 1095 0.79 1132 0.86 1167 0.93 1201 1.00 1234 1.07
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 49
Performance Data
(3 Tons Standard Efficiency)
Table 43. Belt Drive Evaporator Fan Performance — 3 Tons — WSC036E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — 570 0.14 635 0.19 697 0.23 756 0.28 809 0.34 858 0.39 900 0.44 939 0.49 976 0.54
1080 — — 606 0.18 669 0.23 726 0.27 780 0.33 834 0.38 883 0.44 929 0.50 970 0.56 1008 0.62
1200 572 0.18 644 0.23 705 0.28 758 0.33 809 0.38 858 0.44 907 0.50 953 0.57 997 0.63 1037 0.70
1320 613 0.22 682 0.28 741 0.33 793 0.39 842 0.44 889 0.50 933 0.56 977 0.63 1020 0.70 1062 0.78
1440 655 0.27 722 0.34 779 0.40 830 0.46 877 0.52 921 0.58 963 0.64 1004 0.71 1045 0.78 1086 0.86
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1011 0.59 1046 0.64 1081 0.69 1113 0.74 1146 0.80 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1042 0.67 1077 0.73 1109 0.79 1141 0.84 1173 0.90 Using the full horsepower range of our fan motors as shown in our
1200 1074 0.76 1108 0.83 1141 0.89 1172 0.95 1202 1.02 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1100 0.85 1137 0.92 1172 1.00 1203 1.06 1233 1.13
1440 1124 0.94 1161 1.01 1196 1.09 1231 1.18 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 44. Belt Drive Evaporator Fan Performance — 3 Tons — WSC036E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — 555 0.13 635 0.17 703 0.22 761 0.27 812 0.32 858 0.37 900 0.42 939 0.46 977 0.51
1080 — — 585 0.16 659 0.21 727 0.26 787 0.31 841 0.37 888 0.42 930 0.47 969 0.53 1007 0.58
1200 549 0.15 618 0.19 685 0.24 751 0.30 811 0.36 866 0.42 915 0.48 960 0.54 1001 0.60 1037 0.66
1320 590 0.19 654 0.24 716 0.29 777 0.35 836 0.41 890 0.47 940 0.54 986 0.60 1028 0.67 1068 0.74
1440 633 0.24 692 0.29 749 0.34 805 0.40 860 0.46 914 0.53 964 0.60 1010 0.67 1054 0.75 1094 0.82
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1014 0.57 1049 0.62 1082 0.67 1115 0.73 1149 0.78 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1044 0.64 1077 0.70 1110 0.75 1144 0.81 1175 0.87 Using the full horsepower range of our fan motors as shown in our
1200 1073 0.72 1108 0.78 1140 0.84 1172 0.90 1203 0.97 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1104 0.80 1139 0.87 1171 0.94 1203 1.01 1233 1.07
1440 1133 0.89 1169 0.97 1202 1.04 1234 1.11 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
50 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)
Table 45. Belt Drive Evaporator Fan Performance — 4 Tons — TSC048E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 613 0.20 672 0.24 725 0.29 778 0.34 830 0.39 879 0.45 923 0.51 965 0.56 1005 0.63
1440 592 0.20 657 0.25 716 0.30 765 0.35 812 0.40 859 0.46 906 0.52 952 0.58 995 0.65 1034 0.71
1600 644 0.26 703 0.32 760 0.37 809 0.43 853 0.49 895 0.54 936 0.60 980 0.67 1023 0.74 1062 0.81
1760 696 0.34 751 0.39 804 0.46 853 0.52 897 0.58 936 0.64 975 0.71 1012 0.77 1052 0.84 1091 0.91
1920 750 0.43 801 0.49 850 0.55 897 0.62 941 0.70 980 0.76 1017 0.83 1052 0.89 1087 0.96 1122 1.04
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1043 0.69 1080 0.75 1117 0.81 1152 0.88 1185 0.94 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1071 0.78 1107 0.84 1142 0.91 1176 0.98 1208 1.05 Using the full horsepower range of our fan motors as shown in our
1600 1101 0.88 1137 0.95 1171 1.03 1205 1.10 1237 1.17 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1129 0.99 1165 1.07 1200 1.14 1234 1.23 1266 1.31
1920 1157 1.11 1193 1.19 1227 1.27 1262 1.36 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 46. Belt Drive Evaporator Fan Performance — 4 Tons — TSC048E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 627 0.20 696 0.26 757 0.31 810 0.37 859 0.42 902 0.48 943 0.54 981 0.60 1019 0.66
1440 601 0.20 670 0.26 736 0.32 794 0.38 848 0.44 896 0.50 941 0.57 982 0.63 1020 0.70 1056 0.76
1600 653 0.27 715 0.32 776 0.39 834 0.45 886 0.52 935 0.59 979 0.66 1020 0.73 1059 0.80 1095 0.87
1760 706 0.34 763 0.40 820 0.47 874 0.54 925 0.61 972 0.69 1017 0.77 1058 0.84 1096 0.92 1134 1.00
1920 759 0.43 813 0.50 865 0.57 916 0.64 965 0.72 1011 0.80 1054 0.88 1096 0.97 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1054 0.71 1089 0.77 1122 0.83 1156 0.90 1187 0.97 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1090 0.82 1125 0.89 1157 0.96 1189 1.02 1220 1.09 Using the full horsepower range of our fan motors as shown in our
1600 1130 0.95 1162 1.02 1195 1.09 1225 1.16 1255 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1168 1.08 1201 1.15 1233 1.24 1263 1.31 1292 1.39
1920 1206 1.22 1239 1.30 1272 1.39 1302 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 51
Performance Data
(4 Tons Standard Efficiency)
Table 47. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 635 0.22 693 0.26 746 0.31 796 0.36 846 0.42 893 0.49 938 0.55 981 0.61 1020 0.67
1440 621 0.23 684 0.28 740 0.33 790 0.39 837 0.44 881 0.50 926 0.56 969 0.63 1011 0.70 1052 0.78
1600 675 0.30 734 0.35 787 0.41 836 0.47 880 0.53 923 0.59 963 0.66 1002 0.72 1042 0.80 1082 0.88
1760 731 0.38 786 0.44 836 0.51 883 0.58 927 0.64 967 0.71 1005 0.77 1043 0.84 1079 0.91 1114 0.99
1920 788 0.48 839 0.55 886 0.62 931 0.69 973 0.76 1012 0.84 1049 0.91 1085 0.98 1119 1.05 1153 1.13
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1057 0.73 1094 0.79 1128 0.85 1161 0.92 1192 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1089 0.85 1125 0.91 1160 0.98 1192 1.05 1224 1.11 Using the full horsepower range of our fan motors as shown in our
1600 1120 0.96 1156 1.04 1191 1.12 1223 1.19 1255 1.27 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1150 1.07 1186 1.16 1222 1.25 1255 1.34 1288 1.43
1920 1186 1.21 1219 1.29 1253 1.38 1285 1.48 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 48. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 632 0.21 696 0.26 756 0.31 812 0.37 862 0.42 908 0.48 952 0.54 993 0.60 1033 0.66
1440 618 0.22 679 0.26 738 0.32 794 0.38 847 0.44 897 0.50 944 0.56 987 0.63 1027 0.70 1066 0.76
1600 673 0.29 729 0.34 783 0.39 835 0.45 885 0.52 933 0.59 980 0.66 1023 0.73 1063 0.80 1101 0.87
1760 729 0.37 781 0.42 831 0.48 879 0.55 926 0.62 972 0.69 1015 0.76 1058 0.84 1098 0.92 1136 0.99
1920 785 0.47 834 0.53 880 0.59 926 0.66 970 0.73 1012 0.80 1055 0.88 1095 0.96 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1073 0.73 1109 0.79 1144 0.85 1179 0.92 1212 0.99 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1103 0.83 1139 0.90 1174 0.97 1210 1.04 1242 1.11 Using the full horsepower range of our fan motors as shown in our
1600 1138 0.95 1173 1.02 1206 1.09 1240 1.17 1273 1.25 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1173 1.07 1208 1.15 1241 1.23 1273 1.31 1304 1.40
1920 1208 1.21 1244 1.30 1278 1.39 1309 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
52 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)
Table 49. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 583 0.17 647 0.21 705 0.26 758 0.31 809 0.36 859 0.41 907 0.47 951 0.53 993 0.59 1033 0.65
1440 639 0.23 699 0.28 753 0.33 803 0.38 851 0.43 895 0.49 940 0.55 983 0.61 1025 0.68 1064 0.74
1600 696 0.30 752 0.36 803 0.41 850 0.47 895 0.53 937 0.58 979 0.65 1019 0.71 1058 0.78 1097 0.85
1760 754 0.39 807 0.45 855 0.51 900 0.57 942 0.63 982 0.70 1021 0.76 1059 0.83 1096 0.90 1132 0.97
1920 813 0.49 862 0.56 908 0.63 951 0.69 991 0.76 1029 0.82 1067 0.89 1102 0.96 1138 1.04 1172 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1071 0.71 1105 0.77 1139 0.83 1173 0.89 1202 0.94 Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
1440 1103 0.81 1139 0.88 1174 0.94 1207 1.01 1238 1.08 reliably and continuously at all cataloged conditions. Using the
1600 1135 0.92 1171 0.99 1207 1.07 1239 1.14 1271 1.21 full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
1760 1167 1.04 1203 1.12 1238 1.20 1271 1.28 1303 1.36 failure. Our product’s warranty will not be affected.
1920 1204 1.19 1238 1.27 1271 1.35 1303 1.43 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 50. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 583 0.18 653 0.23 715 0.28 772 0.33 825 0.39 874 0.45 919 0.51 962 0.57 1002 0.64 1041 0.70
1440 637 0.24 703 0.29 762 0.35 815 0.41 866 0.47 913 0.53 958 0.60 1000 0.67 1040 0.74 1077 0.81
1600 693 0.31 755 0.37 810 0.44 861 0.50 909 0.56 955 0.63 998 0.70 1039 0.78 1078 0.85 1115 0.92
1760 749 0.40 808 0.47 861 0.54 909 0.61 954 0.68 997 0.75 1039 0.82 1079 0.90 1117 0.98 1154 1.06
1920 807 0.50 861 0.58 912 0.66 959 0.73 1002 0.81 1043 0.88 1083 0.96 1121 1.04 1158 1.12 1194 1.21
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1079 0.76 1114 0.83 1149 0.89 1181 0.95 1213 1.02 Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
1440 1114 0.88 1148 0.95 1182 1.02 1216 1.09 1248 1.16 reliably and continuously at all cataloged conditions. Using the
1600 1151 1.00 1186 1.08 1218 1.16 1251 1.24 1281 1.31 full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
1760 1189 1.14 1224 1.22 1256 1.31 1287 1.39 1319 1.48 failure. Our product’s warranty will not be affected.
1920 1229 1.29 1263 1.38 1295 1.47 — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 53
Performance Data
(4 Tons Standard Efficiency)
Table 51. Belt Drive Evaporator Fan Performance — 4 Tons — WSC048E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 613 0.20 672 0.24 725 0.29 778 0.34 830 0.39 879 0.45 923 0.51 965 0.56 1005 0.63
1440 592 0.20 657 0.25 716 0.30 765 0.35 812 0.40 859 0.46 906 0.52 952 0.58 995 0.65 1034 0.71
1600 644 0.26 703 0.32 760 0.37 809 0.43 853 0.49 895 0.54 936 0.60 980 0.67 1023 0.74 1062 0.81
1760 696 0.34 751 0.39 804 0.46 853 0.52 897 0.58 936 0.64 975 0.71 1012 0.77 1052 0.84 1091 0.91
1920 750 0.43 801 0.49 850 0.55 897 0.62 941 0.70 980 0.76 1017 0.83 1052 0.89 1087 0.96 1122 1.04
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1043 0.69 1080 0.75 1117 0.81 1152 0.88 1185 0.94 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1071 0.78 1107 0.84 1142 0.91 1176 0.98 1208 1.05 Using the full horsepower range of our fan motors as shown in our
1600 1101 0.88 1137 0.95 1171 1.03 1205 1.10 1237 1.17 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1129 0.99 1165 1.07 1200 1.14 1234 1.23 1266 1.31
1920 1157 1.11 1193 1.19 1227 1.27 1262 1.36 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 52. Belt Drive Evaporator Fan Performance — 4 Tons — WSC048E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 627 0.20 696 0.26 757 0.31 810 0.37 859 0.42 902 0.48 943 0.54 981 0.60 1019 0.66
1440 601 0.20 670 0.26 736 0.32 794 0.38 848 0.44 896 0.50 941 0.57 982 0.63 1020 0.70 1056 0.76
1600 653 0.27 715 0.32 776 0.39 834 0.45 886 0.52 935 0.59 979 0.66 1020 0.73 1059 0.80 1095 0.87
1760 706 0.34 763 0.40 820 0.47 874 0.54 925 0.61 972 0.69 1017 0.77 1058 0.84 1096 0.92 1134 1.00
1920 759 0.43 813 0.50 865 0.57 916 0.64 965 0.72 1011 0.80 1054 0.88 1096 0.97 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1054 0.71 1089 0.77 1122 0.83 1156 0.90 1187 0.97 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1090 0.82 1125 0.89 1157 0.96 1189 1.02 1220 1.09 Using the full horsepower range of our fan motors as shown in our
1600 1130 0.95 1162 1.02 1195 1.09 1225 1.16 1255 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1168 1.08 1201 1.15 1233 1.24 1263 1.31 1292 1.39
1920 1206 1.22 1239 1.30 1272 1.39 1302 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
54 RT-PRC023-EN
Performance Data
(5 Tons Standard Efficiency)
Table 53. Belt Drive Evaporator Fan Performance — 5 Tons — TSC060E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 697 0.31 751 0.37 800 0.42 846 0.48 888 0.53 929 0.59 967 0.64 1005 0.71 1041 0.77
1800 704 0.35 758 0.41 808 0.47 854 0.53 898 0.59 938 0.66 977 0.72 1015 0.78 1050 0.85 1085 0.91
2000 771 0.46 820 0.53 866 0.60 910 0.67 951 0.73 991 0.80 1028 0.87 1064 0.94 1098 1.01 1131 1.08
2200 838 0.60 883 0.68 926 0.75 968 0.83 1007 0.90 1044 0.97 1081 1.05 1115 1.12 1148 1.20 1180 1.28
2400 906 0.77 948 0.85 989 0.93 1027 1.01 1065 1.09 1101 1.17 1135 1.25 1168 1.34 1200 1.42 1232 1.50
Continued For Standard Evaporator Fan Speed (RPM), reference Table 123.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 128 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1075 0.83 1110 0.90 1142 0.96 1176 1.03 1208 1.10 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1118 0.98 1151 1.05 1182 1.12 1212 1.19 1243 1.26 Using the full horsepower range of our fan motors as shown in our
2000 1163 1.15 1194 1.22 1225 1.30 1255 1.37 1283 1.45 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1211 1.35 1241 1.43 — — — — — —
2400 — — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 54. Belt Drive Evaporator Fan Performance — 5 Tons — TSC060E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 707 0.31 763 0.37 815 0.42 862 0.48 905 0.54 946 0.60 984 0.65 1020 0.71 1056 0.78
1800 715 0.36 768 0.41 819 0.47 868 0.54 914 0.60 957 0.67 996 0.73 1034 0.79 1068 0.86 1103 0.92
2000 783 0.47 831 0.54 878 0.60 924 0.67 967 0.74 1009 0.81 1049 0.89 1085 0.96 1119 1.03 1152 1.10
2200 852 0.61 896 0.68 939 0.75 982 0.83 1023 0.90 1063 0.98 1100 1.06 1137 1.14 1172 1.22 1203 1.30
2400 921 0.78 963 0.86 1002 0.94 1041 1.01 1080 1.09 1118 1.18 1153 1.26 1189 1.35 1222 1.43 — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1091 0.84 1124 0.90 1156 0.97 1189 1.04 1220 1.11 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1135 0.99 1168 1.06 1199 1.13 1230 1.20 1260 1.27 Using the full horsepower range of our fan motors as shown in our
2000 1184 1.17 1215 1.24 1245 1.32 1273 1.39 1302 1.47 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1235 1.38 1264 1.45 — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 55
Performance Data
(5 Tons Standard Efficiency)
Table 55. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 699 0.31 755 0.36 805 0.42 849 0.47 891 0.53 932 0.58 971 0.64 1008 0.70 1046 0.76 1081 0.82
1800 773 0.42 823 0.48 871 0.54 914 0.60 953 0.67 991 0.73 1027 0.79 1063 0.86 1097 0.92 1131 0.98
2000 847 0.56 894 0.63 938 0.70 979 0.77 1018 0.83 1053 0.90 1087 0.97 1120 1.04 1153 1.11 1185 1.18
2200 923 0.73 966 0.81 1007 0.88 1046 0.96 1083 1.03 1118 1.10 1151 1.18 1182 1.26 1212 1.34 1242 1.41
2400 999 0.93 1039 1.01 1077 1.10 1114 1.18 1150 1.26 1183 1.34 1215 1.42 1245 1.50 — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1115 0.88 1149 0.95 1182 1.01 1213 1.08 1246 1.15 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1163 1.05 1196 1.12 1228 1.19 1257 1.26 1288 1.33 Using the full horsepower range of our fan motors as shown in our
2000 1215 1.25 1246 1.32 1276 1.40 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1271 1.49 — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
Table 56. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 667 0.27 724 0.33 778 0.38 829 0.43 877 0.49 923 0.55 966 0.61 1006 0.68 1046 0.74 1082 0.80
1800 737 0.38 788 0.43 837 0.49 885 0.55 930 0.61 973 0.68 1014 0.74 1054 0.81 1092 0.88 1127 0.95
2000 807 0.50 854 0.57 900 0.63 943 0.69 986 0.76 1026 0.83 1066 0.90 1103 0.97 1140 1.05 1174 1.12
2200 879 0.65 922 0.72 963 0.79 1004 0.86 1044 0.94 1083 1.01 1119 1.08 1155 1.16 1191 1.24 1225 1.32
2400 951 0.83 991 0.91 1029 0.99 1067 1.06 1104 1.14 1141 1.22 1176 1.30 1210 1.38 1243 1.46 — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1117 0.87 1152 0.94 1185 1.00 1218 1.07 1247 1.14 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1162 1.02 1196 1.10 1228 1.17 1259 1.24 1290 1.32 Using the full horsepower range of our fan motors as shown in our
2000 1209 1.20 1242 1.28 1274 1.36 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1257 1.40 1290 1.49 — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
56 RT-PRC023-EN
Performance Data
(5 Tons Standard Efficiency)
Table 57. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 709 0.32 766 0.37 818 0.43 862 0.48 902 0.54 944 0.60 985 0.66 1025 0.72 1063 0.79 1100 0.86
1800 784 0.44 835 0.50 885 0.56 928 0.62 967 0.68 1003 0.75 1040 0.81 1077 0.88 1113 0.95 1149 1.02
2000 859 0.58 907 0.65 952 0.72 995 0.79 1034 0.86 1069 0.93 1101 0.99 1134 1.07 1168 1.14 1201 1.22
2200 936 0.76 980 0.84 1022 0.92 1062 0.99 1101 1.07 1136 1.14 1167 1.21 1198 1.29 1228 1.37 1257 1.44
2400 1013 0.97 1054 1.05 1093 1.14 1131 1.22 1168 1.31 1202 1.39 1234 1.47 — — — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1134 0.92 1168 0.99 1200 1.06 1232 1.12 1262 1.19 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1184 1.10 1217 1.17 1247 1.24 1279 1.32 — — Using the full horsepower range of our fan motors as shown in our
2000 1233 1.29 1265 1.37 1297 1.46 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 — — — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
Table 58. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 706 0.30 762 0.36 813 0.41 862 0.47 908 0.53 951 0.59 993 0.65 1031 0.71 1068 0.78 1104 0.84
1800 780 0.42 832 0.48 879 0.54 924 0.60 968 0.67 1009 0.73 1049 0.80 1086 0.87 1121 0.94 1156 1.01
2000 855 0.56 903 0.63 947 0.69 989 0.76 1028 0.83 1068 0.90 1106 0.97 1143 1.05 1177 1.12 1210 1.20
2200 930 0.72 976 0.80 1017 0.88 1056 0.95 1093 1.03 1130 1.10 1166 1.18 1200 1.26 1235 1.34 1268 1.42
2400 1006 0.92 1049 1.01 1088 1.09 1126 1.17 1160 1.25 1194 1.33 1228 1.42 1261 1.50 — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1140 0.91 1173 0.98 1207 1.05 1240 1.12 1270 1.19 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1189 1.08 1221 1.15 1253 1.22 1284 1.30 — — Using the full horsepower range of our fan motors as shown in our
2000 1243 1.28 1274 1.35 — — — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 — — — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 57
Performance Data
(5 Tons Standard Efficiency)
Table 59. Belt Drive Evaporator Fan Performance — 5 Tons — WSC060E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — — — 606 0.26 660 0.31 710 0.36 757 0.41 802 0.46 846 0.52 889 0.58 930 0.65
1800 — — 582 0.27 640 0.32 692 0.38 740 0.43 785 0.49 827 0.55 868 0.60 908 0.67 947 0.73
2000 564 0.28 622 0.34 675 0.40 725 0.46 772 0.52 815 0.58 856 0.64 895 0.71 933 0.77 969 0.84
2200 608 0.36 663 0.42 712 0.49 760 0.55 805 0.62 847 0.69 886 0.76 924 0.82 961 0.89 995 0.96
2400 653 0.45 705 0.52 752 0.59 796 0.66 839 0.74 880 0.81 919 0.88 955 0.96 990 1.03 1024 1.11
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 968 0.71 1005 0.78 1040 0.84 1076 0.91 1108 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 986 0.80 1022 0.87 1058 0.94 1092 1.02 1124 1.09 Using the full horsepower range of our fan motors as shown in our
2000 1005 0.91 1041 0.98 1075 1.05 1110 1.13 1142 1.21 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1030 1.03 1063 1.11 1095 1.18 1127 1.26 1160 1.34
2400 1057 1.18 1089 1.26 1120 1.34 1151 1.42 1180 1.49
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 60. Belt Drive Evaporator Fan Performance — 5 Tons — WSC060E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 573 0.23 642 0.29 705 0.35 764 0.42 821 0.49 873 0.56 919 0.64 963 0.71 1004 0.79
1800 — — 611 0.29 674 0.36 733 0.43 790 0.49 843 0.57 894 0.65 943 0.73 988 0.81 1030 0.90
2000 593 0.31 651 0.37 710 0.44 766 0.52 819 0.59 869 0.66 917 0.74 965 0.83 1010 0.92 1053 1.01
2200 641 0.40 694 0.46 747 0.54 799 0.62 850 0.70 898 0.78 945 0.86 988 0.95 1032 1.04 1075 1.14
2400 690 0.50 738 0.57 787 0.65 836 0.74 884 0.82 929 0.91 974 1.00 1016 1.09 1057 1.18 1096 1.27
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1042 0.86 1076 0.93 1109 1.01 1141 1.08 1171 1.16 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1069 0.98 1106 1.06 1140 1.15 1173 1.23 1205 1.31 Using the full horsepower range of our fan motors as shown in our
2000 1094 1.10 1131 1.20 1168 1.29 1203 1.38 1235 1.48 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1116 1.24 1154 1.34 1191 1.44 — — — —
2400 1136 1.38 1175 1.48 — — — — — —
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
58 RT-PRC023-EN
Performance Data
(6 Tons Standard Efficiency)
Table 61. Belt Drive Evaporator Fan Performance 6 Tons TSC072E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — — — 588 0.35 643 0.43 693 0.50 738 0.57 782 0.65 823 0.73 862 0.81 900 0.89
2160 — — 564 0.37 618 0.44 672 0.52 721 0.60 765 0.68 806 0.76 847 0.85 885 0.93 922 1.02
2400 — — 602 0.47 652 0.54 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2640 589 0.50 642 0.59 690 0.67 734 0.76 779 0.85 822 0.95 864 1.05 901 1.15 936 1.24 971 1.34
2880 634 0.63 682 0.74 728 0.82 770 0.91 810 1.01 851 1.11 892 1.22 930 1.33 965 1.44 999 1.54
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 937 0.98 971 1.06 1004 1.14 1037 1.22 1068 1.30 1097 1.38 1127 1.47 1154 1.55 1182 1.64 1210 1.74
2160 957 1.12 991 1.21 1024 1.30 1057 1.40 1087 1.49 1117 1.58 1146 1.67 1174 1.76 1201 1.85 1227 1.95
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68 1137 1.78 1166 1.89 1194 1.99 1220 2.08 1248 2.19
2640 1004 1.44 1036 1.55 1067 1.65 1098 1.77 1129 1.88 1158 1.99 1185 2.10 1214 2.22 — — — —
2880 1030 1.64 1061 1.75 1092 1.86 1123 1.98 1151 2.09 1181 2.22 — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or
options are included in pressure drop data. Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial
equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horse
power range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not
be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
Table 62. Belt Drive Evaporator Fan Performance 6 Tons TSC072E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 580 0.33 641 0.41 692 0.47 738 0.54 783 0.63 827 0.71 870 0.79 912 0.88 951 0.96
2160 578 0.37 623 0.43 679 0.51 731 0.59 775 0.67 817 0.74 857 0.83 896 0.93 935 1.02 974 1.12
2400 633 0.49 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2640 688 0.64 725 0.71 762 0.79 808 0.87 853 0.98 894 1.09 931 1.17 966 1.26 1000 1.36 1032 1.47(ii)
2880 743 0.81 778 0.90 811 0.98 848 1.06 891 1.16 932 1.28 970 1.40 1004 1.49 1037 1.59 1068 1.69
1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor)
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 990 1.05 1026 1.14 1062 1.24 1096 1.33 1130 1.43 1160 1.52 1190 1.61 1218 1.71 1247 1.80 1273 1.90
2160 1010 1.21 1047 1.31 1082 1.40 1116 1.50 1150 1.61 1182 1.71 1211 1.81 1242 1.92 1271 2.03 1298 2.14
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81 1201 1.92 1232 2.03 1261 2.14 1291 2.26 — —
2640 1065 1.59 1097 1.71 1129 1.82 1161 1.93 1192 2.05 1223 2.16 1252 2.27 — — — — — —
2880 1099 1.80 1130 1.93 1159 2.05 1188 2.18 1217 2.30 — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or
options are included in pressure drop data. Refer to Table 114 to determine additional static pressure drop due to other options accessories. 1-HP Fan Motor
Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 2-HP Oversized Motor & Field Supplied Drive
(iii) Field Supplied Fan Sheave AK56 and Belt AX30.
RT-PRC023-EN 59
Performance Data
(6 Tons Standard Efficiency)
Table 63. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — — — 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91
2160 — — 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04
2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20
2640 606 0.53 657 0.62 703 0.70 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37
2880 651 0.67 699 0.77 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 1010 1.58
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 941 0.99 977 1.07 1009 1.15 1041 1.23 1073 1.32 1103 1.40 1132 1.49 1159 1.57 1187 1.66 1213 1.75
2160 964 1.13 997 1.23 1031 1.32 1061 1.41 1093 1.50 1123 1.60 1151 1.69 1179 1.78 1207 1.87 1234 1.97
2400 988 1.29 1020 1.39 1054 1.50 1085 1.60 1114 1.70 1143 1.80 1171 1.90 1200 2.01 1227 2.11 1254 2.21
2640 1014 1.47 1046 1.58 1077 1.69 1107 1.80 1138 1.91 1166 2.02 1193 2.13 1222 2.25 — — — —
2880 1042 1.68 1073 1.79 1103 1.90 1132 2.02 1162 2.14 1190 2.26 — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
Table 64. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95
2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11
2400 612 0.48 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2640 663 0.63 709 0.71 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 1018 1.49(ii)
2880 715 0.80 758 0.88 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 963 1.04 997 1.12 1028 1.20 1061 1.28 1090 1.36 1119 1.45 1149 1.54 1177 1.63 1203 1.71 1229 1.80
2160 990 1.21 1023 1.30 1055 1.39 1086 1.48 1115 1.57 1144 1.66 1173 1.76 1200 1.85 1227 1.95 1253 2.04
2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 — —
2640 1050 1.59 1081 1.70 1111 1.81 1141 1.93 1170 2.04 1198 2.15 1226 2.27 — — — — — —
2880 1084 1.83 1114 1.94 1143 2.06 1172 2.18 1199 2.30 — — — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor).
60 RT-PRC023-EN
Performance Data
(6 Tons Standard Efficiency)
Table 65. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 591 0.34 649 0.42 699 0.48 745 0.56 789 0.64 834 0.72 877 0.81 918 0.89 957 0.97
2160 587 0.38 633 0.44 690 0.52 740 0.61 784 0.68 825 0.76 865 0.85 904 0.95 943 1.04 981 1.13
2400 643 0.51 682 0.58 732 0.65 781 0.75 825 0.84 864 0.92 902 1.01 938 1.11 974 1.21 1010 1.32(ii)
2640 700 0.66 736 0.74 775 0.81 822 0.90 866 1.01 906 1.11 942 1.20 976 1.29 1009 1.40 1042 1.51
2880 756 0.84 790 0.93 823 1.01 864 1.09 907 1.20 947 1.32 983 1.43 1017 1.53 1048 1.62 1080 1.73
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 996 1.06 1033 1.16 1067 1.25 1102 1.35 1134 1.44 1165 1.53 1195 1.63 1223 1.72 1251 1.82 1277 1.91
2160 1018 1.23 1054 1.32 1090 1.42 1123 1.52 1156 1.63 1188 1.73 1218 1.84 1247 1.94 1276 2.05 1304 2.16
2400 1044 1.42 1079 1.52 1112 1.62 1145 1.73 1177 1.83 1208 1.94 1240 2.06 1268 2.17 1298 2.29 — —
2640 1075 1.62 1107 1.74 1139 1.85 1170 1.96 1201 2.08 1232 2.19 — — — — — — — —
2880 1111 1.85 1140 1.97 1169 2.09 1200 2.22 — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied High Static Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 114
to determine additional static pressure drop due to other options/accessories. 1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor
Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive (or 2-HP Oversized Motor).
(iii) Field Supplied Fan Sheave AK56 and Belt AX30 required.
Table 66. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 565 0.31 627 0.39 680 0.46 727 0.52 772 0.61 816 0.69 859 0.77 902 0.86 942 0.94 981 1.03
2160 621 0.43 677 0.50 729 0.59 774 0.66 816 0.74 856 0.83 895 0.93 934 1.02 973 1.11 1009 1.21(ii)
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2640 741 0.75 782 0.82 828 0.92 872 1.03 911 1.13 947 1.21 981 1.31 1014 1.41 1048 1.53 1079 1.64
2880 802 0.95 837 1.04 880 1.13 921 1.24 960 1.36 995 1.47 1028 1.56 1060 1.66 1091 1.77 1122 1.89
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78 1268 1.88 1293 1.97
2160 1045 1.30 1081 1.40 1114 1.50 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03 1298 2.13 1324 2.24
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 — — — —
2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21 — — — — — — — — — —
2880 1151 2.02 1180 2.14 1209 2.27 — — — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied High Static Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories. 1-HP Fan Motor Heat (MBH) = 2.829 x Fan
BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor).
(iii) Field Supplied Fan Sheave AK56 and Belt AX30 required.
RT-PRC023-EN 61
Performance Data
(7½ Tons Standard Efficiency)
Table 67. Belt Drive Evaporator Fan Performance 7½ Tons TSC092E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit(i)
2400 — — 487 0.32 536 0.40 583 0.50 627 0.61 669 0.72 708 0.83 743 0.95 776 1.08 808 1.21
2700 — — 522 0.41 569 0.50 611 0.60 653 0.71 693 0.83 731 0.95 768 1.07 801 1.20 832 1.33
3000 — — 559 0.51 604 0.61 643 0.71 682 0.83 719 0.95 755 1.08 791 1.21 824 1.35 856 1.48
3300 — — 599 0.63 639 0.74 678 0.86 713 0.97 748 1.09 783 1.23 815 1.37 848 1.52 880 1.66
3600 601 0.68 640 0.79 675 0.89 713 1.02 748 1.14 780 1.26 811 1.40 844 1.55 874 1.70 904 1.86
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2400 839 1.34 868 1.48 898 1.61 926 1.75 953 1.89 980 2.04 1006 2.18 1032 2.34 1056 2.49 1080 2.64
2700 862 1.48 891 1.62 918 1.77 946 1.92 971 2.07 998 2.23 1023 2.38 1049 2.54 1074 2.70 1097 2.86
3000 886 1.63 915 1.78 942 1.93 968 2.09 994 2.25 1019 2.42 1044 2.59 1067 2.75 1092 2.93 1115 3.09
3300 910 1.81 939 1.96 967 2.12 993 2.28 1019 2.45 1043 2.62 1066 2.79 1091 2.98 1113 3.15 1136 3.34
3600 933 2.01 962 2.17 990 2.33 1016 2.49 1042 2.66 1067 2.84 1091 3.02 1114 3.21 1137 3.39 1158 3.58
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.
Table 68. Belt Drive Evaporator Fan Performance 7½ Tons TSC092E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit(i)
2400 502 0.36 552 0.43 603 0.52 653 0.63 707 0.75 754 0.88 792 0.99 825 1.09 857 1.19 886 1.30
2700 554 0.49 595 0.56 644 0.66 686 0.77 732 0.89 780 1.03 824 1.17 863 1.30 895 1.42 925 1.54
3000 605 0.65 644 0.73 684 0.82 726 0.94 765 1.06 806 1.20 849 1.35 891 1.51 929 1.66 962 1.80
3300 658 0.84 694 0.93 728 1.02 767 1.15 805 1.28 840 1.40 876 1.55 916 1.71 955 1.89 991 2.06
3600 711 1.07 746 1.18 776 1.27 809 1.38 846 1.52 880 1.66 912 1.80 943 1.95 980 2.13 1016 2.30
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 913 1.40 941 1.51 966 1.61 991 1.71 1017 1.82 1040 1.92 1064 2.04 1087 2.14 1110 2.26 1132 2.37
2700 954 1.66 981 1.77 1006 1.89 1030 2.00 1054 2.12 1077 2.24 1100 2.36 1121 2.47 1144 2.60 1164 2.71
3000 992 1.94 1019 2.07 1045 2.20 1069 2.32 1094 2.46 1116 2.58 1138 2.71 1160 2.84 1181 2.97 1202 3.10
3300 1025 2.22 1055 2.38 1082 2.53 1108 2.67 1132 2.82 1156 2.96 1178 3.11 1200 3.25 1221 3.39 — —
3600 1052 2.50 1085 2.69 1117 2.88 1144 3.05 1170 3.21 1193 3.37 — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x
Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.
62 RT-PRC023-EN
Performance Data
(7½ Tons Standard Efficiency)
Table 69. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — — — — — 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30
2700 — — — — 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45
3000 — — 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64
3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85
3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75
2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00
3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27
3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 — —
3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table 70. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — — — — — 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32
2700 — — — — 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49
3000 — — 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69
3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91
3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78
2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05
3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33
3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 — — — —
3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
RT-PRC023-EN 63
Performance Data
(7½ Tons Standard Efficiency)
Table 71. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39
2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68
3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99
3300 719 1.00 758 1.11 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 1048 2.34
3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49
2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86
3000 1031 2.12 1056 2.25 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30
3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36 — — — — — —
3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table 72. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42
2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72
3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05
3300 740 1.06 780 1.19 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 1063 2.42
3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 1043 2.45 1077 2.64 1108 2.83
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52
2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90
3000 1043 2.18 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35
3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43 — — — — — —
3600 137 3.00 1163 3.17 1188 3.33 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
64 RT-PRC023-EN
Performance Data
(8½ Tons Standard Efficiency)
Table 73. Belt Drive Evaporator Fan Performance 8½ Tons TSC102E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive Accessory Kit(i)
2720 — — 539 0.44 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
3060 — — 583 0.58 626 0.68 665 0.78 703 0.90 740 1.04 775 1.17 810 1.30 843 1.44 875 1.58
3400 — — 628 0.72 669 0.84 706 0.96 741 1.08 775 1.21 809 1.36 841 1.51 873 1.65 904 1.81
3740 641 0.81 677 0.92 713 1.04 749 1.17 781 1.30 813 1.43 845 1.58 875 1.73 905 1.89 935 2.06
4080 693 1.03 726 1.15 758 1.27 792 1.41 824 1.56 854 1.69 883 1.83 912 1.99 940 2.16 968 2.33
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3060 905 1.73 933 1.89 960 2.05 986 2.20 1010 2.37 1035 2.54 1059 2.71 1083 2.89 1107 3.06 1131 3.24
3400 933 1.96 962 2.11 990 2.27 1016 2.44 1041 2.62 1065 2.79 1089 2.97 1112 3.15 1134 3.34 — —
3740 964 2.22 992 2.39 1018 2.55 1045 2.72 1071 2.90 1095 3.08 1118 3.26 1141 3.45 — — — —
4080 995 2.51 1023 2.69 1048 2.86 1075 3.05 1100 3.23 1124 3.41 — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan
BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR009A Required.
Table 74. Belt Drive Evaporator Fan Performance 8½ Tons TSC102E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive Accessory Kit(i)
2720 570 0.52 612 0.60 660 0.71 703 0.81 751 0.95 798 1.09 841 1.23 877 1.36 909 1.48 939 1.60
3060 631 0.72 667 0.80 709 0.91 750 1.03 788 1.15 830 1.29 873 1.45 914 1.62 951 1.77 983 1.92
3400 692 0.96 726 1.05 760 1.15 800 1.29 836 1.42 870 1.56 907 1.71 945 1.88 984 2.06 1020 2.24
3740 754 1.26 786 1.36 815 1.46 850 1.59 886 1.74 918 1.88 949 2.03 980 2.19 1015 2.37 1052 2.57
4080 817 1.61 848 1.72 874 1.83 903 1.95 935 2.10 968 2.26 998 2.42 1026 2.58 1054 2.75 1085 2.94
2-HP Standard Motor & Drive 3-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 967 1.72 994 1.84 1018 1.96 1042 2.07 1066 2.19 1089 2.31 1112 2.43 1134 2.55 1155 2.67 1176 2.79
3080 1012 2.06 1039 2.19 1065 2.32 1090 2.46 1113 2.59 1136 2.73 1158 2.86 1179 2.99 1199 3.12 1220 3.26
3400 1052 2.41 1083 2.58 1109 2.73 1135 2.88 1159 3.04 1183 3.19 1204 3.33 — — — — — —
3740 1086 2.77 1119 2.96 1149 3.15 1178 3.34 — — — — — — — — — — — —
4080 1117 3.14 1151 3.36 — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan
BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.
RT-PRC023-EN 65
Performance Data
(8½ Tons Standard Efficiency)
Table 75. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*L Low Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — — — 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52
3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 814 1.32 846 1.45 878 1.60 907 1.75
3400 643 0.77 683 0.89 718 1.00 753 1.13 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02
3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 982 2.33
4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09
3060 936 1.90 962 2.06 989 2.22 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43
3400 973 2.17 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 — — — —
3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 — — — — — — — —
4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table 76. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*M Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — — — 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53
3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 815 1.32 848 1.46 880 1.60 909 1.75
3400 645 0.77 685 0.89 721 1.01 755 1.13 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02
3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 984 2.34
4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10
3060 936 1.91 964 2.07 989 2.23 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44
3400 974 2.18 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 — — — —
3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 — — — — — — — —
4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
66 RT-PRC023-EN
Performance Data
(8½ Tons Standard Efficiency)
Table 77. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56
3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80
3400 660 0.82 698 0.94 733 1.05 767 1.18 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08
3740 718 1.06 754 1.19 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 996 2.41
4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13
3060 945 1.95 971 2.11 997 2.28 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 — —
3400 985 2.24 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 — — — — — —
3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 — — — — — — — — — —
4080 1063 2.96 1089 3.15 1114 3.34 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table 78. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*L Low Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74
3060 688 0.85 732 0.97 770 1.09 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13
3400 756 1.14 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 1049 2.40 1079 2.56
3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 1025 2.42 1061 2.62 1095 2.82 1127 3.02
4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94
3060 1053 2.26 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45
3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 — — — — — — — —
3740 1158 3.21 1185 3.39 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
RT-PRC023-EN 67
Performance Data
(8½ Tons Standard Efficiency)
Table 79. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*M Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75
3060 691 0.86 734 0.98 772 1.10 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14
3400 759 1.15 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 1052 2.41 1082 2.57
3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 1029 2.44 1064 2.64 1098 2.84 1130 3.03
4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95
3060 1054 2.27 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 — —
3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 — — — — — — — — — —
3740 1160 3.23 1187 3.41 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
Table 80. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i) 2-HP Standard Motor & Drive
2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79
3060 709 0.91 750 1.03 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19
3400 778 1.21 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.30 1067 2.49 1095 2.65
3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15
4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 — — — —
3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98
3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 — —
3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 — — — — — — — — — —
3740 1177 3.34 — — — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.
68 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)
Table 81. Belt Drive Evaporator Fan Performance 10 Tons TSC102E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Low Static Drive Accessory Kit(i)
3200 576 0.57 618 0.67 659 0.79 697 0.90 734 1.03 770 1.17 804 1.31 839 1.45 871 1.60 901 1.74
3600 638 0.78 675 0.89 714 1.02 749 1.14 782 1.27 815 1.41 847 1.57 879 1.73 909 1.89 939 2.04
4000 701 1.04 734 1.16 768 1.30 803 1.44 834 1.58 863 1.72 894 1.87 923 2.04 952 2.21 979 2.39
4400 764 1.36 795 1.49 825 1.63 857 1.79 888 1.95 916 2.10 943 2.25 970 2.41 997 2.59 1024 2.78
4800 828 1.74 857 1.88 884 2.02 913 2.18 942 2.36 970 2.53 996 2.70 1021 2.86 1045 3.03 1070 3.22
3-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Oversized Motor & Drive
3200 931 1.89 959 2.06 986 2.22 1012 2.39 1037 2.56 1061 2.74 1084 2.91 1108 3.09 1131 3.28 1153 3.46
3600 969 2.21 997 2.37 1024 2.54 1050 2.72 1074 2.89 1098 3.08 1122 3.27 1145 3.46 1166 3.65 1188 3.85
4000 1007 2.57 1034 2.74 1062 2.93 1087 3.11 1112 3.29 1136 3.47 1159 3.66 1182 3.86 1204 4.07 1226 4.28
4400 1050 2.97 1075 3.17 1101 3.36 1126 3.55 1150 3.75 1173 3.94 1198 4.15 1219 4.34 1241 4.54 1264 4.77
4800 1095 3.42 1119 3.62 1143 3.83 1166 4.05 1189 4.26 1212 4.47 1235 4.68 1258 4.90 1280 5.12 1300 5.32
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR010A required.
Table 82. Belt Drive Evaporator Fan Performance 10 Tons TSC102E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Low Static Drive Accessory Kit(i)
3200 671 0.85 706 0.93 748 1.06 787 1.19 824 1.32 864 1.47 906 1.64 946 1.81 983 1.97 1015 2.13
3600 746 1.18 777 1.27 811 1.39 849 1.54 883 1.68 916 1.82 950 1.98 987 2.16 1024 2.35 1060 2.55
4000 822 1.59 850 1.70 879 1.81 912 1.95 946 2.12 977 2.28 1006 2.43 1035 2.60 1067 2.79 1101 2.99
4400 898 2.09 925 2.21 950 2.32 977 2.46 1008 2.63 1039 2.81 1067 2.98 1094 3.16 1121 3.33 1147 3.52
4800 974 2.69 1000 2.83 1023 2.95 1046 3.07 1072 3.23 1101 3.42 1130 3.62 1156 3.81 1181 4.00 1206 4.19
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1044 2.28 1072 2.42 1097 2.57 1122 2.71 1145 2.84 1168 2.99 1189 3.12 1210 3.27 1231 3.41 1250 3.54
3600 1093 2.74 1124 2.92 1151 3.09 1176 3.25 1201 3.42 1224 3.58 1246 3.74 1268 3.90 1289 4.06 1308 4.20
4000 1135 3.21 1167 3.42 1198 3.63 1227 3.84 1254 4.05 1278 4.23 1301 4.41 1323 4.60 1344 4.77 1365 4.95
4400 1177 3.73 1207 3.96 1239 4.19 1268 4.42 1297 4.67 1324 4.90 1351 5.12 1376 5.35 1398 5.56 1420 5.75
4800 1229 4.39 1254 4.59 1282 4.83 1310 5.07 1338 5.32 1365 5.58 — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR010A required.
RT-PRC023-EN 69
Performance Data
(10 Tons Standard Efficiency)
Table 83. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i)
3200 — — — — — — 743 1.06 779 1.20 814 1.35 847 1.49 879 1.63 910 1.78 938 1.93
3600 — — 735 1.10 768 1.22 802 1.36 834 1.50 866 1.66 897 1.82 927 1.98 957 2.14 985 2.30
4000 767 1.29 802 1.44 833 1.58 863 1.71 892 1.87 922 2.04 951 2.21 979 2.39 1006 2.56 1034 2.74
4400 837 1.69 869 1.85 899 2.00 926 2.15 953 2.31 980 2.48 1007 2.66 1033 2.85 1059 3.04 1085 3.24
4800 908 2.16 937 2.33 965 2.50 991 2.67 1017 2.83 1041 3.00 1066 3.19 1090 3.38 1115 3.59 1139 3.80
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 966 2.10 992 2.26 1018 2.43 1042 2.60 1066 2.78 1091 2.96 1114 3.15 1136 3.33 1159 3.51 1182 3.70
3600 1013 2.47 1039 2.64 1065 2.82 1089 3.00 1113 3.19 1135 3.38 1157 3.56 1179 3.76 1201 3.97 1221 4.16
4000 1060 2.92 1086 3.10 1111 3.28 1135 3.47 1159 3.66 1182 3.86 1203 4.05 1224 4.26 1246 4.47 1266 4.68
4400 1110 3.43 1134 3.62 1159 3.82 1183 4.02 1205 4.22 1229 4.43 1251 4.64 1272 4.84 1292 5.05 1313 5.27
4800 1162 4.01 1185 4.22 1209 4.44 1231 4.64 1253 4.86 1276 5.07 1298 5.30 1319 5.51 1338 5.73 — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Table 84. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i)
3200 — — — — 739 1.05 774 1.19 809 1.33 843 1.47 874 1.61 905 1.76 935 1.92 963 2.08
3600 738 1.11 772 1.23 805 1.37 838 1.52 869 1.68 900 1.84 930 2.00 960 2.16 988 2.32 1016 2.49
4000 813 1.49 844 1.63 873 1.77 903 1.93 932 2.10 961 2.27 989 2.45 1017 2.63 1043 2.80 1070 2.98
4400 889 1.95 917 2.10 944 2.25 971 2.42 998 2.59 1024 2.78 1050 2.97 1076 3.17 1101 3.37 1126 3.56
4800 964 2.50 991 2.66 1016 2.83 1040 3.00 1065 3.18 1090 3.38 1114 3.58 1138 3.79 1161 4.00 1184 4.22
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 989 2.24 1015 2.41 1039 2.58 1064 2.76 1087 2.93 1111 3.12 1133 3.30 1156 3.48 1179 3.68 1200 3.85
3600 1042 2.66 1067 2.84 1091 3.02 1115 3.21 1138 3.40 1160 3.59 1181 3.78 1203 3.98 1224 4.19 1244 4.39
4000 1095 3.17 1120 3.35 1145 3.54 1167 3.73 1190 3.93 1212 4.14 1233 4.35 1253 4.55 1273 4.76 1293 4.97
4400 1150 3.75 1174 3.95 1197 4.15 1221 4.36 1243 4.56 1265 4.77 1285 4.97 1306 5.20 1326 5.42 1345 5.65
4800 1208 4.42 1231 4.64 1253 4.86 1275 5.07 1297 5.29 1317 5.50 1338 5.72 — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
70 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)
Table 85. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i) 3-HP Standard Motor & Drive
3200 — — 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38
3600 819 1.42 857 1.57 890 1.71 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96
4000 902 1.91 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 1189 3.57
4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 1155 3.58 1186 3.80 1217 4.03 1246 4.25
4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1090 2.53 1115 2.67 1139 2.81 1161 2.95 1183 3.09 1205 3.23 1225 3.37 1246 3.51 1265 3.65 1284 3.78
3600 1157 3.13 1181 3.29 1205 3.45 1228 3.61 1250 3.77 1272 3.93 1293 4.09 1312 4.24 1331 4.40 1351 4.56
4000 1218 3.78 1246 3.99 1271 4.18 1294 4.36 1317 4.55 1338 4.72 1360 4.91 1379 5.07 1398 5.25 1418 5.43
4400 1276 4.49 1304 4.73 1333 4.97 1359 5.20 1383 5.42 1405 5.62 — — — — — — — —
4800 1336 5.30 1363 5.56 — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.
Table 86. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i) 3-HP Standard Motor & Drive
3200 785 1.18 821 1.31 861 1.46 903 1.62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55
3600 874 1.64 907 1.78 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21
4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 1185 3.55 1215 3.76 1242 3.96
4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79
4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1120 2.70 1143 2.84 1166 2.98 1188 3.12 1208 3.25 1229 3.39 1249 3.53 1269 3.67 1289 3.82 1308 3.96
3600 1194 3.37 1217 3.53 1240 3.69 1262 3.85 1282 4.01 1303 4.17 1322 4.32 1341 4.48 1361 4.64 1378 4.79
4000 1269 4.16 1292 4.34 1314 4.52 1335 4.70 1356 4.88 1377 5.06 1397 5.24 1415 5.41 — — — —
4400 1339 5.02 1365 5.25 1388 5.47 1410 5.67 — — — — — — — — — — — —
4800 — — — — — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required
RT-PRC023-EN 71
Performance Data
(3 Tons High Efficiency)
Table 87. Belt Drive Evaporator Fan Performance — 3 Tons — THC036E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 608 0.17 676 0.22 734 0.27 785 0.32 833 0.37 878 0.42 922 0.47 963 0.53
1080 — — 557 0.15 629 0.20 697 0.25 757 0.30 809 0.36 857 0.42 901 0.47 944 0.53 983 0.59
1200 — — 588 0.18 653 0.23 718 0.29 777 0.35 832 0.41 881 0.47 925 0.53 967 0.59 1006 0.66
1320 553 0.17 621 0.22 681 0.27 741 0.33 799 0.39 854 0.46 903 0.53 948 0.59 990 0.66 1030 0.73
1440 591 0.21 655 0.27 712 0.32 766 0.38 821 0.44 873 0.51 923 0.58 970 0.66 1014 0.73 1053 0.80
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1002 0.59 1039 0.65 1073 0.70 1107 0.76 1138 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1022 0.65 1059 0.71 1095 0.78 1129 0.84 1162 0.91 Using the full horsepower range of our fan motors as shown in our
1200 1044 0.72 1081 0.79 1115 0.85 1149 0.92 1183 0.99 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1068 0.80 1104 0.87 1138 0.94 1172 1.01 1205 1.08
1440 1091 0.88 1127 0.95 1161 1.03 1195 1.10 1227 1.18
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 88. Belt Drive Evaporator Fan Performance — 3 Tons — THC036E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 619 0.16 680 0.20 738 0.25 791 0.30 840 0.35 885 0.39 927 0.44 968 0.49
1080 — — 570 0.14 647 0.19 708 0.24 762 0.29 814 0.34 863 0.39 908 0.45 950 0.50 991 0.55
1200 — — 595 0.17 674 0.23 736 0.28 789 0.33 839 0.39 885 0.44 931 0.50 973 0.56 1013 0.62
1320 551 0.16 622 0.20 698 0.26 764 0.33 817 0.38 866 0.44 911 0.50 954 0.56 997 0.62 1036 0.68
1440 588 0.20 653 0.24 722 0.30 789 0.37 846 0.44 894 0.50 938 0.56 980 0.63 1020 0.69 1060 0.76
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1005 0.54 1040 0.59 1074 0.64 1107 0.69 1139 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1029 0.61 1066 0.67 1100 0.72 1134 0.77 1165 0.83 Using the full horsepower range of our fan motors as shown in our
1200 1052 0.68 1088 0.74 1124 0.80 1157 0.86 1190 0.92 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1074 0.75 1112 0.82 1147 0.88 1181 0.95 1213 1.02
1440 1098 0.83 1134 0.90 1169 0.97 1203 1.04 1237 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
72 RT-PRC023-EN
Performance Data
(3 Tons High Efficiency)
Table 89. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 600 0.15 664 0.19 722 0.23 774 0.27 824 0.31 870 0.36 913 0.41 952 0.45
1080 — — 560 0.14 625 0.17 687 0.22 743 0.26 795 0.31 844 0.36 890 0.40 933 0.45 973 0.51
1200 — — 593 0.17 655 0.21 712 0.25 767 0.30 817 0.35 865 0.40 910 0.45 952 0.51 993 0.56
1320 — — 626 0.20 685 0.25 740 0.29 791 0.34 841 0.40 887 0.45 931 0.51 974 0.56 1014 0.62
1440 592 0.20 660 0.25 718 0.29 769 0.34 818 0.39 866 0.45 911 0.51 955 0.57 996 0.63 1034 0.69
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.50 1025 0.55 1058 0.59 1091 0.64 1120 0.69 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1012 0.56 1047 0.61 1083 0.66 1116 0.72 1148 0.77 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.62 1069 0.67 1104 0.73 1138 0.79 1171 0.85 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1051 0.68 1088 0.74 1124 0.80 1159 0.86 1191 0.93
1440 1072 0.75 1108 0.81 1145 0.88 1179 0.94 1212 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 90. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 605 0.15 670 0.19 726 0.24 776 0.28 824 0.32 871 0.37 915 0.42 955 0.47
1080 — — 556 0.14 628 0.18 693 0.23 750 0.27 801 0.32 847 0.37 891 0.42 932 0.47 975 0.52
1200 — — 584 0.17 653 0.21 717 0.26 773 0.31 825 0.37 872 0.42 915 0.47 955 0.52 994 0.58
1320 — — 614 0.20 679 0.25 740 0.30 796 0.36 848 0.41 896 0.47 940 0.53 980 0.59 1018 0.65
1440 582 0.19 646 0.24 708 0.29 767 0.35 820 0.40 871 0.47 920 0.53 963 0.59 1005 0.66 1043 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 994 0.52 1031 0.58 1066 0.63 1101 0.69 1131 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1013 0.58 1051 0.63 1087 0.69 1122 0.75 1155 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.63 1069 0.69 1105 0.75 1140 0.82 1175 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1056 0.70 1090 0.76 1125 0.82 1159 0.89 1193 0.96
1440 1079 0.78 1114 0.84 1148 0.91 1181 0.97 1211 1.04
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 73
Performance Data
(3 Tons High Efficiency)
Table 91. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 603 0.15 664 0.19 722 0.24 775 0.28 824 0.33 869 0.37 912 0.42 953 0.47
1080 — — 568 0.14 632 0.18 690 0.23 744 0.27 796 0.32 844 0.37 889 0.42 933 0.47 973 0.53
1200 — — 602 0.18 663 0.22 718 0.27 770 0.31 819 0.36 865 0.42 911 0.47 953 0.53 993 0.58
1320 572 0.17 638 0.22 695 0.26 748 0.31 798 0.36 845 0.41 889 0.47 932 0.53 974 0.58 1015 0.65
1440 611 0.21 674 0.27 729 0.31 779 0.36 827 0.42 872 0.47 915 0.53 957 0.59 997 0.65 1036 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.52 1026 0.58 1060 0.63 1092 0.68 1123 0.73 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1011 0.58 1047 0.63 1083 0.69 1115 0.75 1148 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1033 0.64 1069 0.70 1105 0.76 1138 0.82 1170 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1053 0.71 1089 0.77 1124 0.83 1159 0.90 1191 0.96
1440 1074 0.78 1109 0.84 1145 0.91 1178 0.98 1212 1.05
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 92. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 615 0.16 678 0.20 737 0.24 789 0.29 838 0.33 883 0.38 923 0.42 962 0.47
1080 — — 576 0.14 643 0.19 704 0.23 760 0.28 812 0.32 861 0.38 906 0.43 949 0.48 988 0.53
1200 — — 608 0.18 673 0.22 732 0.27 785 0.32 836 0.37 883 0.42 928 0.48 971 0.53 1012 0.59
1320 571 0.17 642 0.22 705 0.26 761 0.31 813 0.37 862 0.42 908 0.48 952 0.53 995 0.59 1034 0.66
1440 609 0.21 677 0.26 737 0.31 791 0.37 841 0.42 889 0.48 934 0.54 977 0.60 1017 0.66 1057 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 999 0.52 1034 0.57 1068 0.62 1100 0.67 1132 0.72 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1024 0.58 1061 0.64 1094 0.69 1126 0.74 1156 0.79 Using the full horsepower range of our fan motors as shown in our
1200 1050 0.65 1086 0.71 1120 0.77 1153 0.83 1183 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1072 0.72 1109 0.78 1145 0.85 1177 0.91 1209 0.98
1440 1095 0.79 1132 0.86 1167 0.93 1201 1.00 1234 1.07
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
74 RT-PRC023-EN
Performance Data
(4 Tons High Efficiency)
Table 93. Belt Drive Evaporator Fan Performance — 4 Tons — THC048E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — — — 574 0.17 635 0.21 692 0.26 745 0.30 795 0.35 842 0.40 886 0.45 930 0.51
1440 — — 533 0.17 598 0.21 657 0.26 711 0.30 762 0.35 811 0.40 857 0.45 900 0.51 943 0.57
1600 — — 563 0.21 625 0.26 681 0.31 734 0.36 782 0.41 828 0.46 874 0.51 917 0.57 957 0.63
1760 526 0.20 594 0.26 652 0.31 706 0.36 757 0.42 804 0.47 849 0.53 891 0.58 933 0.64 974 0.70
1920 561 0.25 624 0.31 682 0.37 734 0.43 783 0.49 829 0.55 871 0.60 913 0.66 953 0.72 992 0.79
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 971 0.56 1010 0.62 1049 0.68 1083 0.74 1118 0.80 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 981 0.62 1020 0.68 1058 0.74 1096 0.81 1131 0.87 Using the full horsepower range of our fan motors as shown in our
1600 997 0.69 1034 0.75 1070 0.82 1106 0.88 1140 0.95 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1012 0.77 1049 0.83 1086 0.90 1119 0.96 1153 1.03
1920 1029 0.85 1064 0.92 1100 0.99 1135 1.06 1168 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 94. Belt Drive Evaporator Fan Performance — 4 Tons — THC048E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 537 0.16 619 0.21 692 0.27 754 0.33 807 0.39 855 0.46 899 0.52 937 0.58 973 0.64
1440 — — 564 0.19 639 0.25 710 0.31 774 0.38 830 0.45 881 0.52 926 0.59 968 0.66 1007 0.73
1600 — — 593 0.24 663 0.30 729 0.36 793 0.44 851 0.51 903 0.59 950 0.67 993 0.74 1034 0.82
1760 555 0.23 623 0.29 690 0.35 751 0.42 812 0.50 869 0.58 922 0.66 972 0.74 1017 0.83 1059 0.91
1920 593 0.28 656 0.35 719 0.42 777 0.49 833 0.57 889 0.65 942 0.74 991 0.83 1038 0.92 1080 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1008 0.70 1041 0.76 1074 0.82 1106 0.89 1138 0.95 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1042 0.80 1074 0.86 1105 0.93 1135 1.00 1166 1.07 Using the full horsepower range of our fan motors as shown in our
1600 1072 0.90 1107 0.97 1139 1.05 1170 1.12 1198 1.20 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1097 1.00 1133 1.08 1169 1.17 1201 1.25 1233 1.34
1920 1121 1.10 1158 1.19 1194 1.29 1228 1.38 1260 1.47
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 75
Performance Data
(4 Tons High Efficiency)
Table 95. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — — — 583 0.18 644 0.23 700 0.27 752 0.32 799 0.37 845 0.42 891 0.47 933 0.53
1440 — — 542 0.18 608 0.22 667 0.27 721 0.32 772 0.37 818 0.42 863 0.48 906 0.53 946 0.59
1600 — — 572 0.22 636 0.27 692 0.32 744 0.37 793 0.43 839 0.49 883 0.55 924 0.60 964 0.66
1760 538 0.21 603 0.27 664 0.32 719 0.38 768 0.44 817 0.50 861 0.56 904 0.62 945 0.68 983 0.75
1920 574 0.27 636 0.32 692 0.38 746 0.45 795 0.51 841 0.57 885 0.63 927 0.70 966 0.77 1004 0.84
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 975 0.58 1014 0.64 1052 0.70 1087 0.76 1121 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 986 0.65 1025 0.71 1063 0.77 1098 0.83 1134 0.90 Using the full horsepower range of our fan motors as shown in our
1600 1002 0.72 1038 0.78 1075 0.85 1112 0.92 1145 0.98 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1020 0.81 1057 0.88 1091 0.94 1126 1.01 1158 1.08
1920 1041 0.91 1076 0.98 1110 1.05 1144 1.12 1176 1.19
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 96. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 552 0.16 619 0.21 680 0.26 735 0.31 785 0.36 833 0.42 878 0.47 921 0.53 962 0.59
1440 — — 589 0.21 649 0.26 708 0.31 762 0.36 811 0.42 857 0.48 901 0.54 943 0.60 982 0.66
1600 560 0.21 627 0.26 684 0.31 738 0.37 789 0.43 838 0.49 883 0.55 926 0.61 967 0.68 1006 0.75
1760 602 0.27 666 0.33 721 0.38 770 0.44 819 0.50 866 0.57 911 0.63 953 0.70 993 0.77 1031 0.84
1920 644 0.33 705 0.40 759 0.46 806 0.52 851 0.59 895 0.66 939 0.73 980 0.80 1019 0.87 1057 0.95
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1000 0.65 1038 0.72 1076 0.78 1113 0.85 1149 0.91 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1021 0.73 1058 0.80 1093 0.86 1128 0.94 1162 1.01 Using the full horsepower range of our fan motors as shown in our
1600 1043 0.82 1079 0.89 1114 0.96 1148 1.03 1182 1.11 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1068 0.91 1103 0.99 1137 1.06 1172 1.14 1203 1.22
1920 1094 1.02 1128 1.10 1161 1.18 1195 1.26 1227 1.34
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
76 RT-PRC023-EN
Performance Data
(4 Tons High Efficiency)
Table 97. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 524 0.15 595 0.19 653 0.23 708 0.28 760 0.33 809 0.38 856 0.43 901 0.48 945 0.54
1440 — — 553 0.18 621 0.23 680 0.28 732 0.33 781 0.38 828 0.43 873 0.49 917 0.55 959 0.61
1600 — — 584 0.22 647 0.28 706 0.34 759 0.39 805 0.44 849 0.50 892 0.55 935 0.61 975 0.68
1760 554 0.22 617 0.28 676 0.33 733 0.39 786 0.46 832 0.52 876 0.58 916 0.63 955 0.69 994 0.76
1920 593 0.28 652 0.34 707 0.39 760 0.46 811 0.53 859 0.60 903 0.66 942 0.73 980 0.79 1016 0.85
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 987 0.60 1027 0.66 1064 0.71 1100 0.77 1135 0.83 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 998 0.67 1037 0.73 1076 0.79 1114 0.86 1149 0.92 Using the full horsepower range of our fan motors as shown in our
1600 1014 0.74 1053 0.81 1089 0.87 1124 0.94 1160 1.01 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1033 0.82 1069 0.89 1105 0.96 1139 1.03 1173 1.11
1920 1052 0.92 1088 0.99 1122 1.06 1156 1.14 1190 1.21
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 98. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 558 0.16 621 0.20 678 0.25 732 0.29 783 0.34 831 0.39 879 0.45 922 0.50 965 0.56
1440 — — 592 0.20 656 0.25 710 0.30 759 0.35 808 0.40 853 0.45 898 0.51 941 0.57 982 0.63
1600 561 0.20 627 0.25 691 0.31 744 0.36 792 0.41 836 0.47 880 0.52 922 0.58 963 0.64 1003 0.71
1760 603 0.26 664 0.31 724 0.37 778 0.43 825 0.49 868 0.54 909 0.60 949 0.67 988 0.73 1027 0.80
1920 647 0.32 704 0.38 759 0.44 813 0.52 859 0.58 902 0.63 942 0.70 980 0.76 1017 0.83 1053 0.90
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1004 0.62 1042 0.68 1079 0.75 1114 0.81 1148 0.87 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1023 0.69 1060 0.76 1097 0.82 1132 0.89 1166 0.96 Using the full horsepower range of our fan motors as shown in our
1600 1043 0.77 1079 0.84 1116 0.91 1149 0.98 1184 1.05 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1064 0.86 1100 0.93 1135 1.00 1169 1.07 1203 1.15
1920 1088 0.97 1123 1.04 1158 1.11 1191 1.19 1223 1.26
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 77
Performance Data
(5 Tons High Efficiency)
Table 99. Belt Drive Evaporator Fan Performance — 5 Tons — THC060E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 563 0.21 622 0.25 678 0.31 730 0.36 778 0.41 823 0.46 867 0.52 908 0.57 948 0.63
1800 — — 604 0.27 659 0.32 710 0.37 760 0.43 808 0.49 851 0.55 892 0.61 932 0.67 970 0.73
2000 588 0.29 645 0.35 698 0.40 746 0.46 791 0.52 837 0.58 880 0.65 921 0.71 959 0.78 995 0.84
2200 636 0.37 689 0.43 739 0.50 784 0.56 827 0.62 868 0.68 909 0.75 951 0.83 988 0.90 1024 0.97
2400 683 0.47 734 0.54 780 0.61 824 0.68 865 0.74 904 0.81 942 0.88 980 0.95 1017 1.03 1054 1.11
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 987 0.70 1024 0.76 1061 0.83 1095 0.89 1128 0.96 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1008 0.79 1043 0.86 1078 0.92 1113 1.00 1145 1.06 Using the full horsepower range of our fan motors as shown in our
2000 1031 0.90 1066 0.97 1100 1.05 1134 1.12 1167 1.19 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1059 1.04 1092 1.11 1124 1.18 1157 1.26 1187 1.33
2400 1088 1.19 1120 1.27 1152 1.34 1183 1.42 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 100. Belt Drive Evaporator Fan Performance — 5 Tons — THC060E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 619 0.24 681 0.29 745 0.35 810 0.42 868 0.48 916 0.55 959 0.62 998 0.68 1034 0.75
1800 597 0.25 664 0.31 723 0.37 777 0.42 834 0.49 893 0.57 947 0.64 996 0.72 1037 0.80 1075 0.87
2000 648 0.33 711 0.39 767 0.46 818 0.52 867 0.58 918 0.66 971 0.74 1021 0.83 1068 0.91 1110 1.00
2200 700 0.42 759 0.50 812 0.57 861 0.63 907 0.70 951 0.77 997 0.85 1045 0.94 1093 1.04 1137 1.13
2400 752 0.54 808 0.61 859 0.69 906 0.77 949 0.84 991 0.92 1032 0.99 1072 1.08 1117 1.17 1161 1.27
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1068 0.81 1101 0.88 1132 0.94 1161 1.00 1190 1.07 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1111 0.95 1143 1.02 1175 1.09 1205 1.16 1233 1.23 Using the full horsepower range of our fan motors as shown in our
2000 1147 1.08 1182 1.17 1215 1.25 1246 1.33 1276 1.41 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1179 1.23 1219 1.33 1252 1.42 — — — —
2400 1205 1.38 — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
78 RT-PRC023-EN
Performance Data
(5 Tons High Efficiency)
Table 101. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 577 0.22 639 0.27 694 0.32 743 0.37 790 0.42 835 0.47 879 0.53 920 0.59 961 0.65
1800 557 0.23 618 0.28 676 0.34 729 0.40 778 0.45 822 0.50 864 0.56 905 0.62 945 0.68 984 0.74
2000 604 0.30 662 0.36 715 0.42 766 0.48 813 0.55 857 0.61 897 0.67 935 0.73 974 0.79 1010 0.86
2200 653 0.39 707 0.45 756 0.51 803 0.58 849 0.65 892 0.72 933 0.79 969 0.85 1005 0.92 1040 0.99
2400 702 0.49 753 0.56 799 0.63 843 0.70 887 0.77 928 0.85 968 0.93 1006 1.00 1041 1.07 1074 1.14
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 999 0.71 1037 0.77 1072 0.83 1107 0.90 1141 0.96 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1021 0.81 1058 0.88 1093 0.94 1126 1.01 1161 1.08 Using the full horsepower range of our fan motors as shown in our
2000 1046 0.93 1081 1.00 1115 1.07 1149 1.14 1181 1.22 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1075 1.06 1108 1.13 1140 1.21 1173 1.29 1204 1.36
2400 1106 1.21 1138 1.29 1168 1.37 1200 1.45 — —
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 102. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 565 0.21 630 0.26 689 0.31 740 0.36 791 0.41 839 0.47 884 0.52 927 0.58 968 0.65 1007 0.71
1800 620 0.28 678 0.33 735 0.39 784 0.45 830 0.51 875 0.57 918 0.63 960 0.69 1000 0.76 1038 0.82
2000 677 0.37 729 0.43 781 0.49 831 0.56 874 0.62 915 0.69 956 0.75 996 0.82 1034 0.89 1072 0.96
2200 733 0.48 782 0.54 830 0.61 876 0.68 921 0.75 959 0.82 997 0.90 1035 0.97 1071 1.04 1106 1.12
2400 791 0.61 837 0.68 880 0.75 923 0.82 966 0.90 1006 0.98 1042 1.06 1076 1.14 1110 1.22 1144 1.30
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1045 0.78 1082 0.85 1117 0.91 1151 0.98 1183 1.05 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1074 0.89 1110 0.96 1145 1.04 1178 1.11 1211 1.19 Using the full horsepower range of our fan motors as shown in our
2000 1108 1.03 1142 1.10 1176 1.18 1207 1.26 1239 1.34 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1141 1.19 1175 1.27 1208 1.35 1240 1.43 — —
2400 1178 1.38 1210 1.46 — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
RT-PRC023-EN 79
Performance Data
(5 Tons High Efficiency)
Table 103. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 - - 590 0.22 651 0.27 706 0.32 755 0.37 802 0.42 848 0.47 891 0.53 933 0.59 974 0.65
1800 571 0.23 632 0.29 690 0.34 742 0.40 791 0.45 836 0.51 878 0.56 919 0.62 959 0.68 999 0.75
2000 620 0.31 676 0.36 731 0.42 782 0.49 828 0.55 871 0.61 913 0.67 952 0.73 988 0.79 1026 0.86
2200 671 0.39 723 0.46 773 0.52 822 0.59 866 0.66 908 0.72 948 0.79 987 0.86 1023 0.93 1058 1.00
2400 722 0.50 771 0.57 818 0.64 863 0.71 907 0.78 947 0.86 985 0.93 1023 1.00 1059 1.08 1093 1.15
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1013 0.72 1051 0.78 1087 0.85 1122 0.91 1157 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1036 0.82 1072 0.88 1108 0.95 1143 1.02 1176 1.09 Using the full horsepower range of our fan motors as shown in our
2000 1062 0.93 1097 1.00 1132 1.08 1164 1.15 1199 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1091 1.07 1124 1.14 1157 1.21 1190 1.29 1222 1.37
2400 1125 1.23 1157 1.30 1188 1.38 1219 1.46 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
Table 104. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 569 0.21 636 0.26 697 0.32 752 0.37 800 0.41 842 0.46 881 0.52 922 0.58 963 0.64 1002 0.70
1800 620 0.28 686 0.34 741 0.40 795 0.46 843 0.52 887 0.57 925 0.62 961 0.68 997 0.75 1033 0.81
2000 672 0.36 739 0.44 788 0.50 838 0.57 886 0.64 930 0.71 970 0.76 1006 0.82 1040 0.88 1072 0.95
2200 724 0.46 789 0.55 839 0.62 884 0.69 929 0.77 973 0.85 1013 0.92 1050 0.99 1084 1.05 1117 1.11
2400 778 0.58 840 0.68 892 0.76 933 0.84 974 0.91 1015 1.00 1055 1.09 1094 1.17 1129 1.25 1161 1.31
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1041 0.76 1078 0.83 1113 0.90 1147 0.96 1180 1.03 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1069 0.88 1104 0.95 1139 1.02 1173 1.09 1206 1.17 Using the full horsepower range of our fan motors as shown in our
2000 1103 1.02 1137 1.09 1170 1.17 1201 1.24 1233 1.32 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1147 1.18 1177 1.25 1205 1.33 1234 1.41 — —
2400 1192 1.38 1221 1.45 — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
80 RT-PRC023-EN
Performance Data
Table 106. Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
3 T/YSC036E3 AK71x3/4" N/A 556 606 657 707 757 808
4 T/YSC048E3 AK69x3/4" N/A N/A 624 675 727 779 832
5 T/YSC060E3 AK61x3/4" N/A N/A 708 765 823 880 938
7½ TSC092E AK99x1" N/A 462 498 533 569 604 640
AK79x1" N/A 582 627 672 716 761 806
8½ TSC102E AK99x1" N/A 462 498 533 569 604 640
AK79x1" N/A 582 627 672 716 761 806
10 TSC120E AK94x1" N/A 563 600 638 675 713 750
AK74x1" N/A 719 767 815 862 910 958
3 WSC036E3 AK71x3/4" N/A 549 600 650 701 751 802
4 WSC048E3 AK69x3/4" N/A 567 619 671 723 775 828
5 WSC060E3 AK69x3/4" N/A 566 617 668 719 770 821
Factory set at 3 turns open.
Table 107. Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Open Open Open Open Open Open Closed
3 T/YSC036E3 AK41x3/4" N/A 967 1040 1113 1187 N/A
4 T/YSC048E3 AK41x3/4" N/A 957 1033 1110 1187 1263
5 T/YSC060E3 N/A N/A N/A N/A N/A N/A N/A
6 T/YSC072E3,E4,EW N/A 831 895 959 1022 1086 1150
3 WSC036E3 AK41 x 3/4" N/A 966 1041 1115 1190 N/A
4 WSC048E3 AK41 x 3/4" N/A 958 1034 1110 1186 1261
5 WSC060E3 AK41 x 3/4" N/A 970 1034 1097 1161 1224
Factory set at 3 turns open.
RT-PRC023-EN 81
Performance Data
Table 111. Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
3 T/YHC036E AK71x3/4" N/A 556 606 657 707 757 808
4 T/YHC048E AK74x3/4" N/A 528 576 625 673 722 770
5 T/YHC060E AK69x3/4" N/A 565 617 669 721 773 825
Factory set at 3 turns open.
82 RT-PRC023-EN
Performance Data
Table 112. Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Open Open Open Open Open Open Closed
3 T/YHC036E AK41x3/4" N/A 967 1040 1113 1187 N/A
4 T/YHC048E AK41x3/4" N/A 966 1048 1132 1215 N/A
5 T/YHC060E AK41x3/4" N/A 961 1041 1122 1203 N/A
Factory set at 3 turns open.
Table 114. Static Pressure Drop Through Accessories (Inches Water Column) —3-10 Tons
Economizer with OA/RA Dampers(i) Electric Heater Accessory (kW)(ii),(iii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36 54
Tons Number Filters(iv) Filter OA RA OA RA
Downflow Horizontal
3 T/YSC036E1 960 0.01 0.03 0.04 0.01 0.04 0.01 0.01 0.01 0.01 —
1200 0.02 0.04 0.06 0.01 0.06 0.01 0.02 0.02 0.02 —
1440 0.03 0.05 0.08 0.02 0.08 0.01 0.02 0.03 0.03 —
T/YSC036E3 960 0.01 0.03 0.04 0.01 0.04 0.01 0.01 0.01 0.01 —
1200 0.02 0.04 0.06 0.01 0.06 0.01 0.02 0.02 0.02 —
1440 0.03 0.05 0.08 0.02 0.08 0.01 0.02 0.03 0.03 —
4 T/YSC048E1 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
T/YSC048E3 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
5 T/YSC060E1 1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
2000 0.06 0.10 0.18 0.07 0.18 0.02 0.06 0.07 0.08 —
2400 0.08 0.13 0.25 0.11 0.25 0.03 0.08 0.10 0.12 —
T/YSC060E3 1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
2000 0.06 0.10 0.18 0.07 0.18 0.02 0.06 0.07 0.08 —
2400 0.08 0.13 0.25 0.11 0.25 0.03 0.08 0.10 0.12 —
6 T/YSC072E 1920 0.04 0.07 0.10 0.01 0.06 0.02 0.02 0.011 0.021 —
2400 0.06 0.09 0.11 0.02 0.08 0.02 0.02 0.020 0.034 —
2880 0.09 0.12 0.13 0.04 0.10 0.04 0.04 0.033 0.052 —
7½ T/YSC092E 2400 0.04 0.06 0.11 0.02 0.08 0.02 0.02 0.016 0.021 —
3000 0.06 0.09 0.14 0.05 0.12 0.05 0.05 0.025 0.032 —
3600 0.09 0.13 0.21 0.07 0.25 0.08 0.08 0.036 0.046 —
8½ T/YSC102E 2720 0.05 0.08 0.12 0.03 0.09 0.04 0.04 0.020 0.026 —
3400 0.08 0.11 0.19 0.06 0.18 0.06 0.06 0.032 0.041 —
4080 0.12 0.16 0.30 0.07 0.31 0.09 0.09 0.047 0.059 —
10 T/YSC120E 3200 0.07 0.10 0.17 0.05 0.14 0.05 0.05 0.028 0.036 0.042
4000 0.11 0.15 0.26 0.07 0.30 0.08 0.08 0.045 0.056 0.070
4800 0.16 0.20 0.34 0.09 0.35 0.10 0.10 0.065 0.081 0.106
RT-PRC023-EN 83
Performance Data
Table 114. Static Pressure Drop Through Accessories (Inches Water Column) —3-10 Tons (continued)
Economizer with OA/RA Dampers(v) Electric Heater Accessory
(kW)(vi),(vii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36 54
Tons Number Filters(viii) Filter OA RA OA RA
Downflow Horizontal
3 WSC036E1 960 0.02 0.03 0.05 0.01 0.05 0.01 0.01 0.02 0.02 —
1200 0.03 0.05 0.07 0.02 0.07 0.01 0.02 0.03 0.03 —
1440 0.03 0.06 0.10 0.03 0.10 0.01 0.03 0.04 0.04 —
WSC036E3 960 0.02 0.03 0.05 0.01 0.05 0.01 0.01 0.02 0.02 —
1200 0.03 0.05 0.07 0.02 0.07 0.01 0.02 0.03 0.03 —
1440 0.03 0.06 0.10 0.03 0.10 0.01 0.03 0.04 0.04 —
4 WSC048E1 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
WSC048E3 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
5 WSC060E1 1600 0.03 0.06 0.09 0.01 0.05 0.01 0.01 0.01 0.02 —
2000 0.05 0.08 0.11 0.01 0.07 0.02 0.02 0.01 0.03 —
2400 0.07 0.10 0.12 0.03 0.09 0.03 0.03 0.02 0.04 —
WSC060E3 1600 0.03 0.06 0.09 0.01 0.05 0.01 0.01 0.01 0.02 —
2000 0.05 0.08 0.11 0.01 0.07 0.02 0.02 0.01 0.03 —
2400 0.07 0.10 0.12 0.03 0.09 0.03 0.03 0.02 0.04 —
(i) OA = Outside Air and RA = Return Air.
(ii) Nominal kW ratings at 240, 480, 600 volts.
(iii) Electric heaters restricted on applications below 320 CFM/Ton.
(iv) Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing
optional 2” pleated filters.
(v) OA = Outside Air and RA = Return Air.
(vi) Nominal kW ratings at 240, 480, 600 volts.
(vii) Electric heaters restricted on applications below 320 CFM/Ton.
(viii) Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing
optional 2” pleated filters.
Table 115. Static Pressure Drop Through Accessories (Inches Water Column) —3-5 Tons
Economizer with OA/RA Dampers(i) Electric Heater Accessory (kW)(ii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36
Tons Number Filters(iii) Filter OA RA OA RA
Downflow Horizontal
3 T/YHC036E1 960 0.013 0.027 0.041 0.007 0.041 0.006 0.010 0.012 0.014
1200 0.020 0.037 0.059 0.013 0.059 0.008 0.015 0.019 0.022
1440 0.027 0.048 0.080 0.021 0.080 0.010 0.022 0.027 0.032
T/YHC036E3,4 960 0.013 0.027 0.041 0.007 0.041 0.006 0.010 0.012 0.014
1200 0.020 0.037 0.059 0.013 0.059 0.008 0.015 0.019 0.022
1440 0.027 0.048 0.080 0.021 0.080 0.010 0.022 0.027 0.032
4 T/YHC048E1 1280 0.015 0.042 0.081 0.000 0.038 0.009 0.009 0.001 0.006
1600 0.031 0.059 0.092 0.006 0.052 0.015 0.015 0.008 0.016
1920 0.046 0.076 0.102 0.014 0.066 0.020 0.020 0.014 0.025
T/YHC048E3,4 1280 0.015 0.042 0.081 0.000 0.038 0.009 0.009 0.001 0.006
1600 0.031 0.059 0.092 0.006 0.052 0.015 0.015 0.008 0.016
1920 0.046 0.076 0.102 0.014 0.066 0.020 0.020 0.014 0.025
5 T/YHC060E1 1600 0.031 0.059 0.091 0.007 0.052 0.015 0.015 0.008 0.016
2000 0.049 0.079 0.105 0.014 0.069 0.021 0.021 0.015 0.026
2400 0.070 0.101 0.118 0.026 0.086 0.029 0.029 0.024 0.040
T/YHC060E3,4 1600 0.031 0.059 0.091 0.007 0.052 0.015 0.015 0.008 0.016
2000 0.049 0.079 0.105 0.014 0.069 0.021 0.021 0.015 0.026
2400 0.070 0.101 0.118 0.026 0.086 0.029 0.029 0.024 0.040
(i)OA = Outside Air and RA = Return Air.
(ii)
Nominal kW ratings at 240, 480, 600 volts. Heaters only available on T_C units.
(iii)
Tested with standard filters (1” filters). Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
Unit applications below 320 CFM/Ton are not applicable with Gas Heat or Electric Heaters.
84 RT-PRC023-EN
Performance Data
RT-PRC023-EN 85
Performance Data
86 RT-PRC023-EN
Performance Data
Table 121. 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
6 Tons 7½ Tons 8½ Tons 10 Tons
2000 CFM 3000 CFM 3400 CFM(i) 4000 CFM
kW Stages TSC072A3, A4, AW TSC092E3,4,W TSC102E3,4,W TSC120E3,4,W
9.00 1 14.2 9.5 8.4 —
11.30 1 — — — —
16.90 2 — — — —
18.00 1 28.5 19.0 16.7 14.2
22.60 2 — — — —
27.00 2 42.7 28.5 25.1 21.3
33.80 2 — — — —
36.00 2 56.9 37.9 33.5 28.5
54.00 2 — — — 42.7
For minimum design airflow, see airflow performance table for each unit. To calculate temp
rise at different airflow, use the following formula:
Temp. rise across Electric Heater = kWx3414/1.08xCFM.
(i) Minimum allowable airflow with a 17.4 or 17.6 kW heater is 1440 cfm.
RT-PRC023-EN 87
Performance Data
Table 122. 3 Tons Single Phase Heating Capacities (Net) WSC036E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 12.3 11.4 11.0 10.5 2.54 2.82 2.96 3.11
-3 14.3 13.5 13.0 12.5 2.58 2.85 3.00 3.17
2 16.5 15.7 15.2 14.8 2.61 2.89 3.05 3.21
7 17.6 16.6 16.0 15.4 2.62 2.90 3.05 3.21
12 20.0 18.9 18.2 17.7 2.67 2.96 3.10 3.26
17 22.4 21.2 20.6 20.0 2.71 2.99 3.14 3.30
22 25.0 23.7 23.1 22.5 2.75 3.03 3.19 3.36
27 27.7 26.4 25.6 25.0 2.80 3.10 3.26 3.43
32 30.3 28.8 28.2 27.4 2.84 3.13 3.30 3.47
37 33.1 31.6 30.8 30.1 2.89 3.20 3.37 3.54
42 35.8 34.2 33.4 32.6 2.94 3.24 3.42 3.60
47 38.8 37.0 36.2 35.4 3.00 3.31 3.49 3.67
52 41.5 39.7 38.8 37.9 3.05 3.37 3.54 3.73
57 44.6 42.6 41.7 40.7 3.12 3.44 3.62 3.81
62 47.4 45.3 44.3 43.3 3.17 3.51 3.69 3.88
67 50.5 48.3 47.4 46.2 3.23 3.59 3.78 3.96
72 53.4 51.0 49.9 48.7 3.30 3.65 3.84 4.04
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
Table 123. 3 Tons Three Phase Heating Capacities (Net) WSC036E3,E4,EW at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 11.7 11.0 10.5 10.2 2.41 2.68 2.81 2.97
-3 13.8 13.0 12.6 12.1 2.45 2.72 2.87 3.02
2 15.9 15.0 14.7 14.3 2.48 2.75 2.92 3.07
7 16.9 15.8 15.3 14.7 2.48 2.76 2.91 3.05
12 19.5 18.3 17.8 17.1 2.53 2.81 2.94 3.12
17 21.8 20.7 20.1 19.5 2.57 2.85 3.02 3.17
22 24.4 23.1 22.6 21.9 2.62 2.90 3.06 3.22
27 27.2 26.0 25.3 24.7 2.66 2.96 3.11 3.29
32 29.9 28.5 27.8 27.1 2.71 3.01 3.18 3.35
37 32.9 31.4 30.7 30.0 2.77 3.08 3.25 3.42
42 35.5 34.0 33.2 32.5 2.82 3.14 3.31 3.49
47 38.7 37.0 36.2 35.5 2.90 3.21 3.38 3.58
52 41.4 39.7 38.8 38.1 2.95 3.27 3.45 3.65
57 44.7 42.9 41.9 41.1 3.02 3.35 3.53 3.73
62 47.5 45.6 44.6 43.8 3.09 3.42 3.61 3.82
67 50.7 48.7 47.8 46.8 3.16 3.51 3.70 3.91
72 53.5 51.5 50.5 49.5 3.22 3.59 3.79 3.99
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
88 RT-PRC023-EN
Performance Data
(4 Tons)
Table 124. 4 Tons Single Phase Heating Capacities (Net) WSC048E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 15.2 14.0 13.4 12.8 3.23 3.60 3.81 4.02
-3 17.6 16.5 15.8 15.2 3.24 3.61 3.81 4.03
2 20.3 19.0 18.5 17.8 3.28 3.62 3.83 4.07
7 20.8 19.2 18.3 17.6 3.24 3.59 3.77 3.97
12 23.9 22.2 21.4 20.6 3.27 3.61 3.80 4.01
17 26.6 25.0 24.2 23.4 3.28 3.63 3.82 4.03
22 29.8 28.2 27.3 26.4 3.33 3.68 3.88 4.08
27 33.2 31.5 30.6 29.8 3.37 3.72 3.91 4.13
32 36.2 34.5 33.5 32.6 3.41 3.77 3.95 4.17
37 39.8 37.9 36.9 36.0 3.46 3.81 4.01 4.22
42 42.9 40.9 39.9 38.9 3.50 3.86 4.06 4.27
47 46.6 44.4 43.3 42.3 3.56 3.91 4.11 4.34
52 49.9 47.6 46.4 45.5 3.61 3.97 4.17 4.39
57 53.8 51.2 50.2 49.1 3.67 4.02 4.24 4.46
62 57.3 54.6 53.4 52.2 3.72 4.09 4.30 4.52
67 61.4 58.5 57.1 55.8 3.79 4.16 4.37 4.59
72 64.9 61.9 60.4 59.0 3.85 4.22 4.44 4.67
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
Table 125. 4 Tons Three Phase Heating Capacities (Net) WSC048E3,E4,EW at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 13.9 12.3 11.4 10.4 3.02 3.33 3.51 3.69
-3 16.7 15.0 14.1 13.2 3.06 3.38 3.55 3.74
2 19.5 17.8 17.1 16.1 3.11 3.44 3.61 3.81
7 20.7 19.0 17.9 16.9 3.11 3.44 3.61 3.80
12 23.8 22.0 21.1 20.0 3.16 3.49 3.67 3.85
17 26.6 24.9 23.9 22.9 3.20 3.53 3.71 3.90
22 29.9 28.1 27.1 26.1 3.24 3.59 3.77 3.96
27 33.3 31.4 30.4 29.3 3.29 3.65 3.82 4.02
32 36.2 34.3 33.3 32.3 3.33 3.69 3.88 4.07
37 39.8 37.8 36.8 35.8 3.39 3.74 3.94 4.15
42 42.9 40.8 39.8 38.7 3.44 3.79 3.99 4.20
47 46.6 44.4 43.3 42.1 3.50 3.86 4.05 4.26
52 50.0 47.6 46.5 45.3 3.55 3.92 4.12 4.33
57 53.9 51.3 50.3 49.0 3.62 3.98 4.19 4.41
62 57.5 54.7 53.4 52.2 3.69 4.05 4.25 4.48
67 61.5 58.7 57.4 56.0 3.75 4.13 4.34 4.56
72 65.0 62.3 60.8 59.3 3.82 4.21 4.42 4.64
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
RT-PRC023-EN 89
Performance Data
(5 Tons)
Table 126. 5 Tons Single Phase Heating Capacities (Net) WSC060E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 18.6 17.1 16.4 15.7 3.73 4.16 4.37 4.60
-3 22.2 20.9 20.1 19.4 3.82 4.26 4.49 4.71
2 26.0 24.6 23.8 23.0 3.88 4.31 4.55 4.79
7 28.4 26.7 25.7 24.9 3.92 4.36 4.58 4.80
12 32.3 30.2 29.5 28.6 3.97 4.45 4.66 4.91
17 36.2 34.5 33.6 32.7 4.03 4.46 4.69 4.97
22 40.1 38.3 37.4 36.4 4.08 4.52 4.75 5.01
27 44.1 42.2 41.3 40.4 4.15 4.61 4.84 5.08
32 48.2 46.2 45.2 44.2 4.21 4.66 4.90 5.15
37 52.4 50.3 49.2 48.2 4.27 4.72 4.97 5.24
42 56.5 54.3 53.2 52.1 4.33 4.79 5.04 5.31
47 60.7 58.5 57.4 56.2 4.41 4.86 5.12 5.39
52 64.9 62.7 61.4 60.1 4.48 4.94 5.20 5.47
57 69.7 67.0 65.6 64.3 4.55 5.03 5.28 5.57
62 74.1 71.2 69.8 68.4 4.62 5.11 5.38 5.66
67 79.0 75.6 74.1 72.6 4.72 5.19 5.47 5.76
72 83.3 79.9 78.2 76.6 4.80 5.29 5.58 5.88
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
Table 127. 5 Tons Three Phase Heating Capacities (Net) WSC060E3,E4,EW at 1600 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 20.4 19.4 18.8 18.3 3.68 4.13 4.37 4.64
-3 23.7 22.6 22.0 21.5 3.76 4.21 4.45 4.73
2 27.1 26.0 25.4 24.8 3.84 4.30 4.53 4.81
7 28.6 27.2 26.4 25.7 3.85 4.29 4.54 4.80
12 32.4 30.8 30.1 29.3 3.92 4.37 4.63 4.89
17 36.0 34.4 33.6 32.8 3.98 4.44 4.69 4.96
22 39.9 38.2 37.4 36.6 4.06 4.52 4.77 5.05
27 44.0 42.3 41.3 40.4 4.13 4.61 4.85 5.13
32 47.9 46.1 45.1 44.2 4.20 4.68 4.94 5.21
37 52.2 50.2 49.3 48.3 4.28 4.76 5.03 5.31
42 56.3 54.2 53.2 52.2 4.36 4.84 5.12 5.41
47 60.8 58.5 57.4 56.4 4.45 4.94 5.21 5.50
52 65.0 62.6 61.5 60.3 4.54 5.03 5.30 5.60
57 69.7 67.1 65.9 64.7 4.64 5.13 5.40 5.70
62 74.0 71.3 70.0 68.8 4.74 5.24 5.51 5.81
67 78.8 75.9 74.6 73.2 4.85 5.36 5.63 5.93
72 83.1 80.2 78.7 77.2 4.95 5.48 5.75 6.04
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.
90 RT-PRC023-EN
Controls
setpoint lever.
AUTO
Sensor
This sensor will allow the customer
to reduce the total number of remote
sensors to obtain space temperature Humidity Sensor
Manual/ averaging. This sensor should be Field installed,
Automatic Changeover utilized with ReliaTel controls. wall-mounted or
Auto, Heat, Cool duct-mounted
or Off System Digital Display Zone Sensor humidity sensor
Switch. Fan The Digital LCD is used to control
Auto or Off (Liquid Crystal activation of the
Switch. Two Display) zone hot gas reheat
temperature sensor has the dehumidification
setpoint levers. look and option. The
Optional Status functionality of humidity sensor
Indication LED standard zone can be set for
lights, System sensors. This humidity levels
On, Heat, Cool, sensor includes a between 40% and 60% relative
or Service. digital display of humidity by adjusting the ReliaTel
set point Options Module.
Remote Sensor adjustment and
space CO2 Sensing
Sensor(s) available for all zone temperature in F (Fahrenheit) or C
sensors to provide remote sensing The CO2
(Celsius). Includes FAN and SYSTEM sensor shall
capabilities. buttons (supports the service have the
functions of the standard sensor). E- ability to
squared memory stores last monitor space
programmed set points. Requires 24 occupancy
VAC (Volts AC). This sensor should levels within
be utilized with ReliaTel™ controls. the building
by measuring
the parts per
million of CO2
(Carbon
Dioxide) in the air. As the CO2 levels
increase, the outside air damper
modulates to meet the CO2 space
ventilation requirements. The CO2
accessory shall be available as field
installed.
RT-PRC023-EN 91
Controls
Auto
Heat
Touchscreen Programmable
Thermostat (2H/2C)
RA Remote Sensor
Two Heat/Two Cool programmable
thermostat with touch screen digital Return Air Remote Sensor which can
display. Menu-driven programming. be mounted in the return air duct to
Effortless set-up. Program each day report return air temperature.
separately with no need to copy
multiple days. All programming can Room Remote Sensor
be done on one screen. Easy to read
and use. Large, clear backlit digital Space Remote Sensor which can be
display. mounted on the wall to report/control
from a remote location in the space.
FAN
ON
HEAT
AUTO
CIRC
92 RT-PRC023-EN
Electrical Data
RT-PRC023-EN 93
Electrical Data
(Standard Efficiency)
Table 129. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency
Standard Indoor Motor Oversized Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size or Max Fuse Size or
Tons Number Number Rating(i) Stages MCA Max Circuit Breaker MCA Max Circuit Breaker
208/230 Volts Single Phase
3 TSC036E1 BAYHTRE105A 3.8/5.0 1 30.1/33.5 40.0/40.0 — —
BAYHTRE110A 7.5/10.0 2 52.6/59.6 60.0/60.0 — —
BAYHTRE114A 10.4/13.8 2 69.8/79.4 70.0/80.0 — —
4 TSC048E1 BAYHTRE105A 3.8/5.0 1 35.2/35.5 50.0/50.0 — —
BAYHTRE110A 7.5/10.0 2 54.6/61.6 60.0/70.0 — —
BAYHTRE114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRE118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
5 TSC060E1 BAYHTRE105A 3.8/5.0 1 43.8/43.8 70.0/70.0 — —
BAYHTRE110A 7.5/10.0 2 54.6/61.6 70.0/70.0 — —
BAYHTRE114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRE118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
208/230 Volts Three Phase
3 TSC036E3 BAYHTRE306A 4.5/6.0 1 21.9/24.3 30.0/30.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 40.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
4 TSC048E3 BAYHTRE306A 4.5/6.0 1 25.2/25.2 35.0/35.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 40.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
5 TSC060E3 BAYHTRE306A 4.5/6.0 1 29.5/29.5 45.0/45.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 45.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
BAYHTRE323A 17.3/23.0 2 66.3/75.4 70.0/80.0 — —
6 TSC072E3 BAYHTRS309A 6.8/9.0 1 36.5/36.5 50/50 37.8/37.8 60/60
BAYHTRS318A 13.5/18.0 1 53.1/60.4 60/70 54.8/62.0 60/70
BAYHTRS327A 20.3/27.0 2 76.6/87.5 80/90 78.3/89.1 80/90
BAYHTRS336A 27.0/36.0 2 100.1/114.5 110/125 101.8/116.1 110/125
7½(ii) TSC092E3 BAYHTRT309A 6.8/9.0 1 43.3/43.3 50/50 46.4/46.4 60/60
BAYHTRT318A 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
BAYHTRT327A 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
BAYHTRT336A 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
8.5 TSC102E3 BAYHTRT309A 6.8/9.0 1 46.3/46.3 60/60 49.4/49.4 60/60
BAYHTRT318A 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
BAYHTRT327A 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
BAYHTRT336A 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
10 TSC120E3 BAYHTRT318A 13.5/18.0 1 58.6/65.9 60/70 63.6/70.9 80/80
BAYHTRT327A 20.3/27.0 2 82.1/93.0 90/100 87.1/98.0 90/100
BAYHTRT336A 27.0/36.0 2 105.6/120.0 110/125 110.6/125.0 125/125
BAYHTRT354A 40.6/54.0 2 152.5/141.7 175/150 157.5/146.7 175/150
480 Volts Three Phase
3 TSC036E4 BAYHTRE406A 6.0 1 12.1 15.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
4 TSC048E4 BAYHTRE406A 6.0 1 12.5 15.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
5 TSC060E4 BAYHTRE406A 6.0 1 15.5 25.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
BAYHTRE423A 23.0 2 37.8 40.0 — —
6 TSC072E4 BAYHTRS409A 9.0 1 18.2 25 18.8 25
BAYHTRS418A 18.0 1 30.3 35 31.0 35
BAYHTRS427A 27.0 2 43.8 45 44.5 45
BAYHTRS436A 36.0 2 57.3 60 58.0 60
94 RT-PRC023-EN
Electrical Data
(Standard Efficiency)
Table 129. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (continued)
Standard Indoor Motor Oversized Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size or Max Fuse Size or
Tons Number Number Rating(i) Stages MCA Max Circuit Breaker MCA Max Circuit Breaker
7½(ii) TSC092E4 BAYHTRT409A 9.0 1 21.5 25 23.0 30
BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
8½ TSC102E4 BAYHTRT409A 9.0 1 21.9 25 23.4 30
BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
10 TSC120E4 BAYHTRT418A 18.0 1 32.9 35 35.4 40
BAYHTRT427A 27.0 2 46.4 50 48.9 50
BAYHTRT436A 36.0 2 59.9 60 62.4 70
BAYHTRT454A 54.0 2 70.8 80 73.3 80
575 Volts Three Phase
3 TSC036EW BAYHTREW06A 6.0 1 9.4 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
4 TSC048EW BAYHTREW06A 6.0 1 9.4 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
5 TSC060EW BAYHTREW06A 6.0 1 10.1 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
BAYHTREW23A 23.0 2 29.8 30.0 — —
6 TSC072EW BAYHTRSW09A 9.0 1 13.0 20 14.0 20
BAYHTRSW18A 18.0 1 23.8 25 24.8 25
BAYHTRSW27A 27.0 2 34.6 35 35.6 40
BAYHTRSW36A 36.0 2 45.4 50 46.4 50
7½(ii) TSC092EW BAYHTRTW18A 18.0 1 24.8 25 26.3 30
BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
8½ TSC102EW BAYHTRTW18A 18.0 1 24.8 25 26.3 30
BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
10 TSC120EW BAYHTRTW18A 18.0 1 26.3 30 28.4 30
BAYHTRTW27A 27.0 2 37.1 40 39.3 40
BAYHTRTW36A 36.0 2 47.9 50 50.0 50
BAYHTRTW54A 54.0 2 56.6 60 58.8 60
(i) No optional motors available for 3-5 tons. The standard motor for 1-Phase models is a Multispeed, Direct Drive Motor. The Standard Motor for the 3-
Phase models is a Belt Drive Motor.
(ii) Dual refrigeration system.
RT-PRC023-EN 95
Electrical Data
(Standard Efficiency)
Table 130. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency
Standard
Indoor Motor(i)
Unit Model Heater Model Heater kW Control Max Fuse Size or Max
Tons Number Number Rating Stages MCA Circuit Breaker
208/230 Volts Single Phase
3 WSC036E1 BAYHTRE105A 3.8/5.0 1 53.9/57.2 60.0/70.0
BAYHTRE110A 7.5/10.0 2 76.4/83.4 80.0/90.0
BAYHTRE114A 10.4/13.8 2 93.5/103.1 100.0/110.0
4 WSC048E1 BAYHTRE105A 3.8/5.0 1 61.6/64.9 80.0/80.0
BAYHTRE110A 7.5/10.0 2 84.1/91.1 90.0/100.0
BAYHTRE114A 10.4/13.8 2 101.2/110.8 110.0/125.0
BAYHTRE118A 13.2/17.6 2 118.4/130.6 125.0/150.0
5 WSC060E1 BAYHTRX105A 3.8/5.0 1 67.2/70.6 90.0/90.0
BAYHTRX110A 7.5/10.0 2 89.7/96.7 100.0/110.0
BAYHTRX114A 10.4/13.8 2 106.8/116.4 110.0/125.0
BAYHTRX118A 13.2/17.6 2 124.1/136.2 125.0/150.0
208/230 Volts Three Phase
3 WSC036E3 BAYHTRE306A 4.5/6.0 1 39.5/41.8 45.0/50.0
BAYHTRE312A 9.0/12.0 2 55.1/60.0 60.0/60.0
BAYHTRE318A 13.1/17.4 2 69.2/76.2 70.0/80.0
4 WSC048E3 BAYHTRE306A 4.5/6.0 1 43.2/45.5 50.0/50.0
BAYHTRE312A 9.0/12.0 2 58.8/63.7 60.0/70.0
BAYHTRE318A 13.1/17.4 2 72.9/79.9 80.0/80.0
5 WSC060E3 BAYHTRX306A 4.5/6.0 1 45.8/48.2 60.0/60.0
BAYHTRX312A 9.0/12.0 2 61.4/66.3 70.0/70.0
BAYHTRX318A 13.1/17.4 2 75.6/82.6 80.0/90.0
BAYHTRX323A 17.3/23.0 2 90.2/99.3 100.0/100.0
480 Volts Three Phase
3 WSC036E4 BAYHTRE406A 6.0 1 20.4 25.0
BAYHTRE412A 12.0 2 29.4 30.0
BAYHTRE418A 17.4 2 37.5 40.0
4 WSC048E4 BAYHTRE406A 6.0 1 21.3 25.0
BAYHTRE412A 12.0 2 30.3 35.0
BAYHTRE418A 17.4 2 38.4 40.0
5 WSC060E4 BAYHTRX406A 6.0 1 23.7 30.0
BAYHTRX412A 12.0 2 32.7 35.0
BAYHTRX418A 17.4 2 40.8 45.0
BAYHTRX423A 23.0 2 49.3 50.0
575 Volts Three Phase
3 WSC036EW BAYHTREW06A 6.0 1 16.1 20.0
BAYHTREW12A 12.0 2 23.2 25.0
BAYHTREW18A 17.4 2 29.7 30.0
4 WSC048EW BAYHTREW06A 6.0 1 16.7 20.0
BAYHTREW12A 12.0 2 23.8 25.0
BAYHTREW18A 17.4 2 30.3 35.0
5 WSC060EW BAYHTRXW06A 6.0 1 18.2 20.0
BAYHTRXW12A 12.0 2 25.4 30.0
BAYHTRXW18A 17.4 2 31.9 35.0
BAYHTRXW23A 23.0 2 38.6 40.0
(i) No optional motors available for 3-5 Tons. The standard motor for the 1 Phase Models is a Multispeed Direct Drive Motor. The
standard motor for the 3 Phase Models is a Belt Drive Motor.
96 RT-PRC023-EN
Electrical Data
(Standard Efficiency)
Table 131. Electrical Characteristics — Compressor Motor and Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motors Condenser Fan Motors
Unit Model Amps(i) Amps(i)
Tons Number No. Volts Phase HP(ii) RPM RLA LRA No. Volts Phase HP FLA LRA
3 T/YSC036E1 1 208-230 1 2.8 3500 15.4 83.0 1 208-230 1 0.33 2.0 6.6
T/YSC036E3 1 208-230 3 2.8 3500 11.5 77.0 1 208-230 1 0.33 2.0 6.6
T/YSC036E4 1 460 3 2.7 3500 5.1 35.0 1 460 1 0.33 1.2 2.5
T/YSC036EW 1 575 3 2.8 3500 4.3 31.0 1 575 1 0.33 0.9 1.3
4 T/YSC048E1 1 208-230 1 3.6 3500 20.5 109.0 1 208-230 1 0.33 2.0 6.6
T/YSC048E3 1 208-230 3 3.6 3500 14.6 91.0 1 208-230 1 0.33 2.0 6.6
T/YSC048E4 1 460 3 3.6 3500 7.1 46.0 1 460 1 0.33 1.2 2.5
T/YSC048EW 1 575 3 3.5 3500 5.1 34.0 1 575 1 0.33 0.9 1.3
5 T/YSC060E1 1 208-230 1 4.4 3500 26.9 145.0 1 208-230 1 0.40 2.5 6.6
T/YSC060E3 1 208-230 3 4.3 3500 17.6 123.0 1 208-230 1 0.40 2.5 6.6
T/YSC060E4 1 460 3 4.3 3500 9.6 62.0 1 460 1 0.40 1.0 2.8
T/YSC060EW 1 575 3 4.3 3500 6.1 40.0 1 575 1 0.40 0.8 2.0
6 T/YSC072E3 1 208-230 3 5.6 3500 22.4 149.0 1 208-230 1 .70 3.5 10.9
T/YSC072E4 1 460 3 5.6 3500 10.6 75.0 1 460 1 .70 2.4 6.6
T/YSC072EW 1 575 3 5.6 3500 7.7 54.0 1 575 1 .70 1.4 3.60
7½ T/YSC092E3 2 208-230 3 3.7/3.1 3500/3500 16/13.5 91.0/88.0 1 208-230 1 .70 3.5 10.9
T/YSC092E4 2 460 3 3.7/3.1 3500/3500 7.1/7.1 46.0/46.0 1 460 1 .70 2.4 6.6
T/YSC092EW 2 575 3 3.7/3.1 3500/3500 5.6/5.0 34.0/34.0 1 575 1 .70 1.4 3.60
8½ T/YSC102E3 2 208-230 3 3.7/3.7 3500/3500 16/16 91.0/96.0 1 208-230 1 .75 4.0 9.4
T/YSC102E4 2 460 3 3.7/3.7 3500/3500 7.1/7.1 46.0/46.0 1 460 1 .75 2.8 6.8
T/YSC102EW 2 575 3 3.7/3.7 3500/3500 5.6/5.6 37.0/37.0 1 575 1 .75 2.4 6.2
10 T/YSC120E3 2 208-230 3 4.8/3.7 3500/3500 20.5/16.9 155.0/91.0 1 208-230 1 .75 4.0 9.4
T/YSC120E4 2 460 3 4.8/3.7 3500/3500 9.6/7.1 75.0/46.0 1 460 1 .75 2.8 6.8
T/YSC120EW 2 575 3 4.8/3.7 3500/3500 7.6/5.6 54.0/37.0 1 575 1 .75 2.4 6.2
3 WSC036E1 1 208-230 1 3.2 3500 18.6 105.0 1 208-230 1 0.25 2.0 4.4
WSC036E3 1 208-230 3 3.2 3500 13.5 88.0 1 208-230 1 0.25 2.0 4.4
WSC036E4 1 460 3 3.2 3500 6.4 39.0 1 460 1 0.25 0.9 2.2
WSC036EW 1 575 3 3.2 3500 5.1 34.0 1 575 1 0.25 0.7 1.4
4 WSC048E1 1 208-230 1 3.8 3500 23.1 134.0 1 208-230 1 0.40 2.5 6.6
WSC048E3 1 208-230 3 3.8 3500 16.0 91.0 1 208-230 1 0.40 2.5 6.6
WSC048E4 1 460 3 3.8 3500 7.1 46.0 1 460 1 0.40 1.0 2.8
WSC048EW 1 575 3 3.8 3500 5.6 37.0 1 575 1 0.40 0.8 2.0
5 WSC060E1 1 208-230 1 4.8 3500 27.6 158.0 1 208-230 1 0.40 2.5 6.6
WSC060E3 1 208-230 3 4.7 3500 18.1 137.0 1 208-230 1 0.40 2.5 6.6
WSC060E4 1 460 3 4.7 3500 9.0 62.0 1 460 1 0.40 1.0 2.8
WSC060EW 1 575 3 4.7 3500 6.8 50.0 1 575 1 0.40 0.8 2.0
(i) Amp draw for each motor; multiply value by number of motors to determine total amps.
(ii) HP for each compressor.
RT-PRC023-EN 97
Electrical Data
(Standard Efficiency)
Table 132. Electrical Characteristics — Standard Evaporator Fan Motor — 60 Cycle — Direct or Belt Drive— Standard Efficiency
Unit Model Direct or Belt Amps
Tons Number Drive No. Volts Phase HP FLA LRA
3 T/YSC036E1 Direct Drive 1 208-230 1 0.75 6.0 —
T/YSC036E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC036E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC036EW Belt Drive 1 575 3 1.00 1.7 13.2
4 T/YSC048E1 Direct Drive 1 208-230 1 1.00 7.6 —
T/YSC048E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC048E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC048EW Belt Drive 1 575 3 1.00 1.7 13.2
5 T/YSC060E1 Direct Drive 1 208-230 1 1.00 7.6 —
T/YSC060E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC060E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC060EW Belt Drive 1 575 3 1.00 1.7 13.2
6 T/YSC072E3 Belt Drive 1 208-230 3 1.00 5.00 32.20
T/YSC072E4 Belt Drive 1 460 3 1.00 2.50 16.10
T/YSC072EW Belt Drive 1 575 3 1.00 1.70 13.20
7½ T/YSC092E3 Belt Drive 1 208-230 3 2.00 6.30 48.00
T/YSC092E4 Belt Drive 1 460 3 2.00 3.10 24.00
T/YSC092EW Belt Drive 1 575 3 2.00 2.50 18.20
8½ T/YSC102E3 Belt Drive 1 208-230 3 2.00 6.30 48.00
T/YSC102E4 Belt Drive 1 460 3 2.00 3.10 24.00
T/YSC102EW Belt Drive 1 575 3 2.00 2.50 18.20
10 T/YSC120E3 Belt Drive 1 208-230 3 3.00 9.40 83.00
T/YSC120E4 Belt Drive 1 460 3 3.00 4.60 42.00
T/YSC120EW Belt Drive 1 575 3 3.00 3.70 31.00
3 WSC036E1 Direct Drive 1 208-230 1 0.75 6.0 —
WSC036E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC036E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC036EW Belt Drive 1 575 3 1.00 1.7 13.2
4 WSC048E1 Direct Drive 1 208-230 1 1.00 7.6 —
WSC048E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC048E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC048EW Belt Drive 1 575 3 1.00 1.7 13.2
5 WSC060E1 Direct Drive 1 208-230 1 1.00 7.6 —
WSC060E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC060E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC060EW Belt Drive 1 575 3 1.00 1.7 13.2
Table 133. Electrical Characteristics — Oversized Evaporator Fan Motor — 60 Cycle — Belt Drive — Standard Efficiency
Unit Model Amps
Tons Number No. Volts Phase HP FLA LRA
6 T/YSC072E3 1 208-230 3 2.00 6.30 48.00
T/YSC072E4 1 460 3 2.00 3.10 24.00
T/YSC072EW 1 575 3 2.00 2.50 18.20
7½ T/YSC092E3 1 208-230 3 3.00 9.40 83.00
T/YSC092E4 1 460 3 3.00 4.60 42.00
T/YSC092EW 1 575 3 3.00 3.70 31.00
8½ T/YSC102E3 1 208-230 3 3.00 9.40 83.00
T/YSC102E4 1 460 3 3.00 4.60 42.00
T/YSC102EW 1 575 3 3.00 3.70 31.00
10 T/YSC120E3 1 208-230 3 5.00 13.40 112.00
T/YSC120E4 1 460 3 5.00 6.60 56.00
T/YSC120EW 1 575 3 5.00 5.40 44.00
98 RT-PRC023-EN
Electrical Data
(Standard Efficiency)
RT-PRC023-EN 99
Electrical Data
(High Efficiency)
Table 137. Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency
Standard Optional Belt Drive
Indoor Motor Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size Max Fuse Size
Tons Number Number Rating(i) Stages MCA or Max Circuit MCA or Max Circuit
Breaker Breaker
208/230 Volts Single Phase
3 THC036E1 BAYHTRE105A 3.8/5.0 1 30.1/33.5 40.0/40.0 — —
BAYHTRE110A 7.5/10.0 2 52.6/59.6 60.0/60.0 — —
BAYHTRE114A 10.4/13.8 2 69.8/79.4 70.0/80.0 — —
4 THC048E1 BAYHTRX105A 3.8/5.0 1 35.7/35.7 50.0/50.0 — —
BAYHTRX110A 7.5/10.0 2 54.6/61.6 60.0/70.0 — —
BAYHTRX114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRX118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
5 THC060E1 BAYHTRX105A 3.8/5.0 1 43.8/43.8 70.0/70.0 — —
BAYHTRX110A 7.5/10.0 2 54.6/61.6 70.0/70.0 — —
BAYHTRX114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRX118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
208/230 Volts Three Phase
3 THC036E3 BAYHTRE306A 4.5/6.0 1 23.1/25.5 30.0/30.0 21.9/24.3 30.0/30.0
BAYHTRE312A 9.0/12.0 2 38.8/43.6 40.0/45.0 37.5/42.4 40.0/45.0
BAYHTRE318A 13.1/17.4 2 52.9/59.9 60.0/60.0 51.6/58.6 60.0/60.0
4 THC048E3 BAYHTRX306A 4.5/6.0 1 28.3/28.3 40.0/40.0 25.7/25.7 40.0/40.0
BAYHTRX312A 9.0/12.0 2 40.8/45.6 45.0/50.0 37.5/42.4 40.0/45.0
BAYHTRX318A 13.1/17.4 2 54.9/61.9 60.0/70.0 51.6/58.6 60.0/60.0
5 THC060E3 BAYHTRX306A 4.5/6.0 1 32.1/32.1 45.0/45.0 29.5/29.5 45.0/45.0
BAYHTRX312A 9.0/12.0 2 40.8/45.6 45.0/50.0 37.5/42.4 45.0/45.0
BAYHTRX318A 13.1/17.4 2 54.9/61.9 60.0/70.0 51.6/58.6 60.0/60.0
BAYHTRX323A 17.3/23.0 2 69.5/78.6 70.0/80.0 66.3/75.4 70.0/80.0
460 Volts Three Phase
3 THC036E4 BAYHTRE406A 6.0 1 12.8 15.0 12.1 15.0
BAYHTRE412A 12.0 2 21.8 25.0 21.1 25.0
BAYHTRE418A 17.4 2 29.9 30.0 29.3 30.0
4 THC048E4 BAYHTRX406A 6.0 1 13.8 20.0 12.3 15.0
BAYHTRX412A 12.0 2 22.8 25.0 21.1 25.0
BAYHTRX418A 17.4 2 30.9 35.0 29.3 30.0
5 THC060E4 BAYHTRX406A 6.0 1 16.8 25.0 15.5 25.0
BAYHTRX412A 12.0 2 22.8 25.0 21.1 25.0
BAYHTRX418A 17.4 2 30.9 35.0 29.3 30.0
BAYHTRX423A 23.0 2 39.4 40.0 37.8 40.0
(i) Heater kW ratings are at 208/240v for 208/230v units, 480v for 460v units.
100 RT-PRC023-EN
Electrical Data
(High Efficiency)
Table 138. Electrical Characteristics — Compressor Motor and Condenser Fan Motor — 60 Cycle — High Efficiency
Unit Model Compressor Motors Condenser Fan Motors
Tons Number No. Volts Phase HP RPM RLA LRA No. Volts Phase HP FLA LRA
3 T/YHC036E1 1 208-230 1 2.8 3500 15.4 83.0 1 208-230 1 0.20 1.5 2.4
T/YHC036E3 1 208-230 3 2.8 3500 11.5 77.0 1 208-230 1 0.20 1.5 2.4
T/YHC036E4 1 460 3 2.7 3500 5.1 35.0 1 460 1 0.20 0.6 1.3
4 T/YHC048E1 1 208-230 1 3.6 3500 20.5 109.0 1 208-230 1 0.40 2.5 6.6
T/YHC048E3 1 208-230 3 3.6 3500 14.6 91.0 1 208-230 1 0.40 2.5 6.6
T/YHC048E4 1 460 3 3.6 3500 7.1 46.0 1 460 1 0.40 1.0 2.8
5 T/YHC060E1 1 208-230 1 4.4 3500 26.9 145.0 1 208-230 1 0.40 2.5 6.6
T/YHC060E3 1 208-230 3 4.3 3500 17.6 123.0 1 208-230 1 0.40 2.5 6.6
T/YHC060E4 1 460 3 4.3 3500 9.6 62.0 1 460 1 0.40 1.0 2.8
Table 139. Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Direct Drive — High Efficiency
Unit Model
Tons Number Volts Hz. Phase No. FLA LRA BHP
3 T/YHC036E1 208-230 60 1 1 6.0 — 0.75
T/YHC036E3 208-230 60 1 1 6.0 — 0.75
T/YHC036E4 460 60 1 1 6.0 — 0.75
4 T/YHC048E1 208-230 60 1 1 7.6 — 1.00
T/YHC048E3 208-230 60 1 1 7.6 — 1.00
T/YHC048E4 460 60 1 1 7.6 — 1.00
5 T/YHC060E1 208-230 60 1 1 7.6 — 1.00
T/YHC060E3 208-230 60 1 1 7.6 — 1.00
T/YHC060E4 460 60 1 1 7.6 — 1.00
Table 140. Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Optional Belt Drive — High Efficiency
Unit Model
Tons Number Volts Hz. Phase No. FLA LRA BHP
3 T/YHC036E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC036E4 460 60 3 1 2.5 16.1 1.00
4 T/YHC048E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC048E4 460 60 3 1 2.5 16.1 1.00
5 T/YHC060E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC060E4 460 60 3 1 2.5 16.1 1.00
RT-PRC023-EN 101
Jobsite Connections
DISCONNECT
SWITCH
(BY OTHERS)
ZONE SENSOR OR A
THERMOSTAT
ROOFTOP
UNIT
102 RT-PRC023-EN
Dimensional Data
Figure 1. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/Electric;
3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
* All dimensions are in inches/millimeters.
**1/2 NPT Gas Connection = (Y_C Models only); 2" Electrical Connection: Single Point Power When Heat Installed (T_C Models only.)
SUPPLY
16”
457 MM
24” RETURN
610 MM
Figure 2. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Downflow Airflow Supply/Return - Through the Base Utilities
* All dimensions are in inches/millimeters.
RT-PRC023-EN 103
Dimensional Data
(3-5 Tons)
Figure 3. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Horizontal Airflow Supply/Return
* All dimensions are in inches/millimeters.
Figure 4. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Unit Clearance and Roof Opening
* All dimensions are in inches/millimeters.
104 RT-PRC023-EN
Dimensional Data
(3-5 Tons)
44 MM
44 MM
7
1038 MM
1053 MM
Figure 5. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and
Gas Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Roof Curb
* All dimensions are in inches/millimeters.
7
(433 MM)
Figure 6. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and
Gas/Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Downflow Duct Connections - Field Fabricated
* All dimensions are in inches/millimeters.
RT-PRC023-EN 105
Dimensional Data
(3-5 Tons)
106 RT-PRC023-EN
Dimensional Data
(3-5 Tons)
17 7/8" 16"
(454 MM) (406 MM)
Applicable to 22 1/4"
Y_C models only (565 MM)
RT-PRC023-EN 107
Dimensional Data
(4-6 Tons)
108 RT-PRC023-EN
Dimensional Data
(4-6 Tons)
Return
Supply
Figure 13. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Horizontal Airflow Supply and Return
* All dimensions are in inches/millimeters.
Figure 14. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Unit Clearance and Roof Opening
* All dimensions are in inches/millimeters.
RT-PRC023-EN 109
Dimensional Data
(4-6 Tons)
(356 MM)
(2130 MM)
Figure 15. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Roof Curb
* All dimensions are in inches/millimeters.
857
857
PLY
SUP
Figure 16. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and
Gas/Electric - 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Downflow Duct Connections Field Fabricated
* All dimensions are in inches/millimeters.
110 RT-PRC023-EN
Dimensional Data
(4-6 Tons)
Figure 17. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Barometric Relief Damper Hood
* All dimensions are in inches/millimeters.
17”
(432 MM)
21 3/8”
(543 MM)
34 5/8”
(879 MM)
Figure 18. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and
Gas/Electric 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Swing Diameter for Hinged Door(s) Option
* All dimensions are in inches/millimeters.
RT-PRC023-EN 111
Dimensional Data
(7½-10 Tons)
Figure 19. Cooling and Gas/Electric Models - 7½, 8½ and 10 Tons Standard Efficiency
* All dimensions are in inches/millimeters.
**1/2 NPT & 3/4" Gas Connection = (Y_C Models only); 2" Electrical Connection: Single Point Power When Heat Installed
(T_C Models only.)
112 RT-PRC023-EN
Dimensional Data
(7½-10 Tons)
Return
Supply
RT-PRC023-EN 113
Dimensional Data
(7½-10 Tons)
(356 MM)
(2130 MM)
857
857
PLY
SUP
114 RT-PRC023-EN
Dimensional Data
(7½-10 Tons)
RT-PRC023-EN 115
Dimensional Data
(7½-10 Tons)
17"
432 MM
21 3/8"
543 MM
Applicable to
Y_C models only
34 5/8"
879 MM
116 RT-PRC023-EN
Weights
Table 144. Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.)
Unit Maximum Model Corner Weights(ii) Center of Gravity (in.)
Weights(i)
Tons Model No. Shipping Net A B C D Length Width
3 TSC036E1,3,4,W 555 480 157 122 95 107 31 19
YSC036E1,3,4,W 607 532 165 137 95 134 31 19
WSC036E1,3,4,W 589 514 177 107 113 117 29 20
4 TSC048E1,3,4,W 586 511 167 129 101 114 31 19
YSC048E1,3,4,W 638 563 175 145 101 142 31 19
WSC048E1,3,4,W 600 525 181 109 115 119 29 20
5 TSC060E1,3,4,W 636 561 183 142 111 125 31 19
YSC060E1,3,4,W 688 613 190 158 110 155 31 19
WSC060E1,3,4,W 825 682 228 177 114 163 38 24
6 TSC072E 898 755 295 136 209 115 40 23
YSC072E 936 793 304 146 219 124 41 23
7½ TSC092E 1009 866 358 147 252 109 41 22
YSC092E 1059 916 370 160 265 121 41 22
8½ TSC102E 1048 905 359 161 265 120 42 23
YSC102E 1096 953 371 173 277 132 42 23
10 TSC120E 1139 996 388 185 281 142 41 23
YSC120E 1201 1058 403 201 297 157 42 23
(i) Weights are approximate.
(ii) Corner weights are given for information only.
Table 145. Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.)
Unit Maximum Model Corner Weights(ii) Center of Gravity (in.)
Weights(i)
Tons Model No. Shipping Net A B C D Length Width
3 THC036E1,3,4 566 472 109 85 186 92 40 26
YHC036E1,3,4 637 544 127 103 204 110 39 26
4 THC048E1,3,4 798 653 155 127 248 123 40 25
YHC048E1,3,4 869 725 173 145 266 141 40 25
5 THC060E1,3,4 823 676 204 74 327 71 41 26
YHC060E1,3,4 894 748 222 92 345 89 41 26
(i) Weights are approximate.
(ii) Corner weights are given for information only.
RT-PRC023-EN 117
Weights
118 RT-PRC023-EN
Mechanical Specifications
General forklift and crane lifting, with forklift have single point power entry as
capabilities on three sides of the standard.
The units shall be convertible unit.
airflow. The operating range shall be
Evaporator and Condenser Coils
between 115°F and 0°F in cooling as
Compressors
standard from the factory for units Internally finned, 5/16” copper tubes
with microprocessor controls. All units shall have direct-drive, mechanically bonded to a configured
Operating range for units with hermetic, scroll type compressors aluminum plate fin shall be
electromechanical controls shall be with centrifugal type oil pumps. standard. Coils shall be leak tested at
between 115°F and 40°F. Cooling Motor shall be suction gas-cooled the factory to ensure the pressure
performance shall be rated in and shall have a voltage utilization integrity. The evaporator coil and
accordance with ARI testing range of plus or minus 10 percent of condenser coil shall be leak tested to
procedures. All units shall be factory unit nameplate voltage. Internal 575 psig and pressure tested to 450
assembled, internally wired, fully overloads shall be provided with the psig. The condenser coil shall have a
charged with R-410A, and 100 scroll compressors. patent pending 1+1+1 hybrid coil
percent run tested to check cooling designed with slight gaps for ease of
All standard and high efficiency units
operation, fan and blower rotation, cleaning. A removable, reversible,
shall have direct-drive, hermetic,
and control sequence before leaving double-sloped condensate drain pan
scroll type compressors with
the factory. Wiring internal to the with provision for through the base
centrifugal type oil pumps. Motor
unit shall be colored and numbered condensate drain is standard.
shall be suction gas-cooled and shall
for simplified identification. Units
have a voltage utilization range of
shall be UL listed and labeled,
plus or minus 10 percent of unit Filters
classified in accordance to UL 1995/
nameplate voltage. Internal One inch, throwaway filters shall be
CAN/CSA No. 236-M90 for Central
overloads shall be provided with the standard on all 3-4 ton standard
Cooling Air Conditioners. Canadian
scroll compressors. Crankcase efficiency heat pumps and 3 ton high
units shall be CSA Certified.
heaters shall be included on 6-10 ton efficiency units. Two inch throwaway
standard efficiency units. filters shall be standard on all 4-5 ton
Casing
high-efficiency units and 5 ton
Unit casing shall be constructed of Controls standard efficiency heat pumps.
zinc coated, heavy gauge, galvanized
Unit shall be completely factory- Two inch filters shall be factory
steel. Exterior surfaces shall be
wired with necessary controls and supplied on all 6-10 ton units.
cleaned, phosphatized, and finished
contactor pressure lugs or terminal Optional 2-inch pleated filters shall
with a weather-resistant baked
block for power wiring. Unit shall also be available.
enamel finish. Unit’s surface shall be
provide an external location for
tested 1000 hours in a salt spray test
mounting a fused disconnect device. Gas Heating Section
in compliance with ASTM B117.
Cabinet construction shall allow for A choice of microprocessor or The heating section shall have a
all maintenance on one side of the electromechanical controls shall be progressive tubular heat exchanger
unit. Service panels shall have lifting available. design using stainless steel burners
handles and be removed and and corrosion resistant steel
Microprocessor controls provide for
reinstalled by removing two throughout. An induced draft
all 24 volt control functions. The
fasteners while providing a water combustion blower shall be used to
resident control algorithms shall
and air tight seal. All exposed pull the combustion products
make all heating, cooling, and/or
vertical panels and top covers in the through the firing tubes. The heater
ventilating decisions in response to
indoor air section shall be insulated shall use a direct spark ignition (DSI)
electronic signals from sensors
with a cleanable foil-faced, fire- system. On initial call for heat, the
measuring indoor and outdoor
retardant permanent, odorless glass combustion blower shall purge the
temperatures. The control algorithm
fiber material. The base of the unit heat exchanger for 20 seconds
maintains accurate temperature
shall be insulated with 1/8 inch, 1 before ignition After three
control, minimizes drift from set
pound density foil-faced, closed-cell unsuccessful ignition attempts, the
point, and provides better building
material. All insulation edges shall entire heating system shall be locked
comfort. A centralized
be either captured or sealed. The out until manually reset at the
microprocessor shall provide anti-
unit’s base pan shall have no thermostat/zone sensor. Units shall
short cycle timing and time delay
penetrations within the perimeter of be suitable for use with natural gas
between compressors to provide a
the curb other than the raised 11/8 or propane (field-installed kit) and
higher level of machine protection.
inch high downflow supply/return also comply with the California
openings to provide an added water 24-volt electromechanical control requirement for low NOx emissions
integrity precaution, if the circuit shall include control (Gas/Electric Only).
condensate drain backs up. The base transformer and contactor pressure
of the unit shall have provisions for lugs for power wiring. Units shall
RT-PRC023-EN 119
Mechanical Specifications
120 RT-PRC023-EN
Mechanical Specifications
liquid-tight conduit and an external will be registered with either a zone meet all NEC and CEC requirements
field-installed disconnect switch. sensor with status indication lights or when properly installed. Power
an Integrated Comfort™ System. assemblies shall provide single-point
Through the Base Electrical with This option is available for connection. Electric heat modules
Circuit Breaker microprocessor controlled units. shall be UL listed or CSA certified.
This option is a thermal magnetic, Differential Pressure Switches Frostat
molded case, HACR Circuit Breaker
with provisions for through the base These sensors allow individual fan This option is to be utilized as a
electrical connections. The circuit failure and dirty filter indication for safety device. The Frostat opens
breaker will be installed in a water microprocessor controlled units. The when temperatures on the
tight enclosure in the unit with fan failure switch will disable all unit evaporator coil fall below 10°F. The
access through a swinging door. functions and “flash” the Service temperature will need to rise to 50°F
Wiring will be provided from the LED on the zone sensor. The dirty before closing. This option should be
switch to the unit high voltage filter switch will light the Service LED utilized in low airflow or high outside
terminal block. The circuit breaker on the zone sensor and will allow air applications (Cooling Only).
will provide overcurrent protection, continued unit operation.
be sized per NEC and UL guidelines, LonTalk® Communication
and be agency recognized by UL/ Discharge Air Sensing Interface
CSA.
This option provides true discharge This option shall be provided to allow
air sensing in heating models. This the unit to communicate as a
Through the Base Electrical with sensor is a status indicator readable Tracer™LCI-R device or directly with
Disconnect Switch through Tracer™ or Tracker™. This generic LonTalk Network Building
This 3-pole, molded case, disconnect option is available for Automation System Controls.
switch with provisions for through microprocessor controlled units.
the base electrical connections are Reference or Comparative
available. The disconnect switch will Economizer Enthalpy
be installed in the unit in a water tight This accessory shall be available with
enclosure with access through a Reference Enthalpy is used to
or without barometric relief. The measure and communicate outdoor
swinging door. Wiring will be assembly includes fully modulating
provided from the switch to the unit humidity. The unit receives and uses
0-100 percent motor and dampers, this information to provide improved
high voltage terminal block. The minimum position setting, preset
switch will be UL/CSA agency comfort cooling while using the
linkage, wiring harness with plug, economizer. Comparative Enthalpy
recognized. Note: The disconnect spring return actuator and fixed dry
switch will be sized per NEC and UL measures and communicates
bulb control. The barometric relief humidity for both outdoor and return
guidelines but will not be used in shall provide a pressure operated
place of unit overcurrent protection. air conditions, and return air
damper that shall be gravity closing temperature. The unit receives and
and shall prohibit entrance of outside uses this information to maximize
Through the Base Gas Piping air during the equipment “off” cycle. use of economizer cooling, and to
The unit shall include a standard Optional solid state or differential provide maximum occupant comfort
through the base gas provision. This enthalpy control shall be available for control. Reference or Comparative
option shall have all piping necessary either factory or field installation. The Enthalpy option shall be available
including, black steel, manual gas economizer arrives in the shipping when a factory or field installed
shut-off valve, elbows, and union. position and shall be moved to the Downflow Economizer is ordered.
The manual shut-off valve shall operating position by the installing This option is available on all
include a 1/8” NPT pressure tap. This contractor. downflow models.
assembly will require minor field
labor to install (Gas/Electric Only). Electric Heaters Tool-less Hail Guards
Electric heat modules shall be Tool-less, hail protection quality coil
Two-Inch Pleated Filters available for installation within basic guards are available for condenser
Two inch pleated media filters shall unit. Electric heater elements shall be coil protection.
be available on all models. constructed of heavy-duty nickel
chromium elements internally delta Trane Communication Interface
connected for 240 volt, wye
Factory or Field Installed connected for 480 and 600 volt. This option shall be provided to
Options Staging shall be achieved through interface ReliaTel™ controlled units
ReliaTel™. Each heater package shall with the Trane Integrated Comfort™
have automatically reset high limit systems.
Clogged Filter/Fan Failure Switch
control operating through heating
A dedicated differential pressure element contactors. All heaters shall
switch is available to achieve active be individually fused from the
fan failure indication and/or clogged factory, where required, and shall
filter indication. These indications
RT-PRC023-EN 121
Mechanical Specifications
122 RT-PRC023-EN
Literature Order Number RT-PRC023-EN