Packaged Rooftops

Precedent™ 3-10 Tons — 60 Hz


R-410A

Packaged Cooling, Heat Pumps (T*C), (WSC)

Packaged Gas/Electric (Y*C)

May 2007 RT-PRC023-EN


Introduction

Packaged Rooftop Air Conditioners


Through the years, Trane has designed and developed the most complete line
of Packaged Rooftop products available in the market today. Trane was the
first to introduce the Micro—microelectronic unit controls—and has continued
to improve and revolutionize this design concept.
Electromechanical controls are available for simpler applications, and for the
more sophisticated, ReliaTel™ microprocessor controls.
The ReliaTel control platform offers the same great features and functionality
as the original Micro, with additional benefits for greater application flexibility.
With its sleek, compact cabinet, rounded corners and beveled top Precedent
continues to provide the highest standards in quality and reliability, comfort,
ease of service, and the performance of Trane light commercial products.
Trane customers demand products that provide exceptional reliability, meet
stringent performance requirements, and are competitively priced. Trane
delivers with Precedent.
Precedent features cutting edge technologies: reliable compressors, Trane
engineered ReliaTel controls, computer-aided run testing, and Integrated
Comfort™ Systems. So, whether you’re the contractor, the engineer, or the
owner you can be certain Precedent Products are built to meet your needs.
It’s Hard To Stop A Trane.®

Packaged Cooling and Heat Pumps

Packaged Gas/Electric

© 2007 American Standard All rights reserved RT-PRC023-EN


Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . 11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Model Number Description . . . . . . . . . . . . . . . . . . . . 13
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . 102
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . 119

RT-PRC023-EN 3
Features and Benefits

Standard Features • Progressive Tubular Aluminized • Economizer


Steel Heat Exchanger
• 1" throwaway filters provided on • Electric Heaters
Standard Efficiency 3-5 ton • Provisions for Through-the-Base
• Frostat
Cooling, Gas/Electric, 3-4 ton Gas and Condensate Drain
Heat Pumps and 3 ton High Connections • LonTalk® Communications
Efficiency Cooling, Gas/Electric Interface (LCI)
• Quick Access Panels
units • Reference or Comparative
• Quick Adjust Fan Motor
• 2” throwaway filters provided Enthalpy
Mounting Plate
on 6-10 Ton Cooling, Gas/Electric • Tool-less Hail Guards
and 5 ton Heat Pump units • Single Point Power
• Trane Communications Interface
• 5-year Limited Compressor • Single Side Service
(TCI)
Warranty • Standardized Components
Field Installed Options
• 5-year Limited Heat Exchanger • Thermal Expansion Valve
Warranty • CO2 Sensing
• Trane built Scroll Compressors
• 1-year Limited Parts Warranty • Digital Display Zone Sensor
• Anti-Short Cycle Timer Options* • Dual Thermistor Remote Zone
(Standard with ReliaTel™) Sensor
Factory Installed Options • High Altitude Kit
• Colored and Numbered Wiring
• Belt Drive Motors5 (Three- • High Static Drive
• Convertible Airflow
phase)
• Crankcase Heaters1 • Humidity Sensor
• Black Epoxy Pre-Coated Coils
• Easy Access Low Voltage • LP Conversion Kit
• CompleteCoat™ Condenser Coil
Terminal Board (LTB) • Manual Outside Air Damper
• Hinged Access Doors
• Electromechanical2 or ReliaTel • Motorized Outside Air Dampers
Microprocessor Controls • Novar Return Air Sensor
• Powered Exhaust
• Foil-Faced and Edge Captured • Novar Unit Controls
Insulation • Quick Adapt Curbs
• Phase Monitor
• High Pressure Control • Quick Start Kit
• Powered or Unpowered
• IAQ Dual Sloped and Removable Convenience Outlet • Remote Potentiometer
Drain Pans • Roof Curb
• Stainless Steel Heat Exchanger
• Liquid Line Refrigerant Drier with 10-year warranty • Thermostat
• Low Ambient Cooling to 0°F on • Supply and/or Return Air Smoke • Ventilation Override Accessory
Microprocessor Models Detector
• Zone Sensor
• Low Ambient Cooling to 40°F on • Through the Base Electrical
Electromechanical Models Access *Refer to Model Number Description
• Low Pressure Control • Through the Base Electrical with for option availability.
Circuit Breaker
• Multispeed Direct Drive Motors
• Through the Base Electrical with Other Benefits
• Operating Charge of R-410A3
Disconnect Switch • Cabinet design ensures water
• Patented Hybrid Condenser Coil integrity
• 2” Pleated Filters
for easy cleaning
• Ease of Service, Installation and
• Phase Reversal Protection4 Factory or Field Installed Options
Maintenance
• Barometric Relief
• Mixed model build enables
• Clogged Filter/Fan Failure Switch “fastest in the industry” ship
cycle times
• Crankcase Heaters
1 Crankcase heaters are optional on: • Outstanding Airflow Distribution
(Y,T)SC(036,048,060)E,
• Discharge Air Sensing Kit
WSC036E,WSC048E1,WSC060E1 • ReliaTel Controls
2 Not available for Heat Pumps
3 Standard for 3-10 Ton, R-410A units
4 Only available on 3-5 Ton Direct Drive 5 Standard for 6-10 Ton

4 RT-PRC023-EN
Features and Benefits

• Unmatched Product Support is Condenser Coil Cooling


one of our finest assets. Trane
Sales Representatives are a Precedent boasts a patent-pending Standard or High Efficiency Cooling
Support Group that can assist 1+1+1 condenser coil, permanently available.
you with: gapped for easy cleaning.
Crankcase Heaters
– Product
These band heaters provide
– Application improved compressor reliability by
– Service warming the oil to prevent migration
– Training during off-cycles or low ambient
conditions.
– Special Applications
– Specifications Dual Sloped Drain Pans
– Computer Programs and Every Precedent
much more unit has a non-
Controls – ReliaTel or corrosive,
Electromechanical removable,
Standard Features double-sloped
ReliaTel microprocessor controls
provide unit control for heating, drain pan that’s
Anti-Short Cycle Timer (Standard easy to clean and
cooling and ventilating utilizing input
with ReliaTel) from sensors that measure indoor reversible to
Provides a 3 minute minimum “ON” and outdoor temperature and other allow installation
time and 3 minute “OFF” time for zone sensors. ReliaTel also provides of drain trap on
compressors to enhance compressor outputs for building automation either side of the
reliability by assuring proper oil systems and expanded diagnostics. unit.
return. For a complete list of ReliaTel
offerings, refer to the “Other Easy Access Low Voltage
Direct Drive Motors Benefits” section within the Features Terminal Board
and Benefits section of this catalog.
For additional static requirements, Precedent’s Low
single-phase 13 SEER and 15 SEER For the simpler job that does not Voltage Terminal
R-410A units offer multi-speed, direct require a building automation Board is external
drive motors. system, or expanded diagnostics to the electrical
capabilities, Precedent offers control cabinet. It
Colored And Numbered Wiring electromechanical controls. This 24- is extremely easy
volt control includes the control to locate and
Save time and money tracing wires transformer and contactor pressure attach the
and diagnosing the unit. lugs for power wiring. thermostat wire
and test
Compressors Convertible Units operation of all
Precedent unit functions.
The units ship in a downflow This is another cost and time saving
contains the best configuration. They can be easily
compressor installation feature.
converted to horizontal by simply
technology moving two panels.
available to Foil Faced Insulation
achieve the Units come complete with horizontal All panels in the
highest possible duct flanges so the contractor evaporator
performance. Our doesn’t have to field fabricate them.
section of the
compressor line These duct flanges are a time and unit have
includes Trane cost saver. cleanable foil-
built scrolls. faced insulation.
All edges are
either captured or
sealed to ensure
no insulation
fibers get into the
airstream.

RT-PRC023-EN 5
Features and Benefits

Heat Exchanger Quick-Access Panels Black Epoxy Pre-Coated Coils


The compact cabinet features a Remove two screws for access to the The pre-coated coils are an
progressive tubular heat exchanger standardized internal components economical option for protection in
in low, medium and high heat and wiring. mildly corrosive environments.
capacities.
The heat exchanger is fabricated Quick-Adjust Idler Arm CompleteCoat™ Condenser Coil
using stainless steel burners and With the Quick-Adjust Idler Arm, the These coils provide excellent
corrosion-resistant aluminized steel belt and sheaves can be quickly corrosion resistance as well as
tubes as standard on all models. It adjusted without moving the uniformity of coverage and coating
has an induced draft blower to pull mounted fan motor. The result is a thickness.
the gas mixture through the burner major savings in time and money.
tubes. The heater has a direct spark Disconnect Switch (Required
ignition system which doubles as a Single Point Power with Through-the-Base Electrical)
safety device to prove the flame.
A single electrical connection powers Factory installed 3-pole, molded
Gas/Electric Precedent models the unit. case, disconnect switch with
exceed all California seasonal provisions for through the base
efficiency requirements. They also Single Side Service electrical connections are available.
perform better than required to meet
the California NOx emission Single side service is standard on all Codes require a method of assured
requirements. units. unit shutdown for servicing. Field-
installed disconnects sometimes
High Pressure Control Standardized Components interfere with service access. Factory
installation of unit disconnects
All units include High Pressure Components are placed in the same reduces costs, assures proper
Control as standard. location on all Precedent units. mounting and provides the
Familiarize yourself with one opportunity to upgrade to unit circuit
Low Ambient Cooling Precedent and you are familiar with breaker protection.
every Precedent.
All Precedent microprocessor units
have cooling capabilities down to 0°F Due to standardized components Circuit Breaker (Required with
as standard. Electromechanical throughout the Precedent line, Through- the-Base Electrical)
models have cooling capabilities to contractors/owners can stock fewer
parts. This option is a factory installed
40°F as built, or to 0°F by adding the thermal magnetic, molded case,
optional low ambient control HACR Circuit Breaker with provisions
(frostat). Thermal Expansion Valve
for through the base electrical
This feature is standard on all units. connections.
Low Voltage Connections
The wiring of the low voltage Through the Base Condensate
connections to the unit and the zone Every unit includes provisions for
sensors is as simple as 1-1, 2-2, and through the base condensate drain
3-3. This simplified system makes it connections. This allows the drain to
easy for the installer to wire. be connected through the roof curb
instead of a roof penetration.

Variety of Options* Hinged Access Doors


These doors permit
Factory Installed Options easy access to the
*Refer to Model Number Description filter, fan/heat, and
for option availability. compressor/control
sections. They
Belt Drive Motors (Three-phase) reduce the potential
roof damage from
Phase Reversal Protection
For additional screws or sharp
Precedent units with 3-phase power static access door
and direct drive supply fan motors (3- requirements, corners.
5 ton) are equipped with phase Precedent 3-5
reversal protection. This feature ton units offer Novar Unit Controls
shall provide 100% protection for an optional belt
compressor against problems caused drive motor to Novar 3051 and 2024 are available
by phase reversal. meet a wide for Precedent Gas and Electric Heat
range of models.
airflow needs.
6 RT-PRC023-EN
Features and Benefits

Phase Monitor Through-the-Base Electrical Crankcase Heaters


Phase monitor shall provide 100% Utility Access These band or insertion heaters
protection for motors and An electrical service provide improved compressor
compressors against problems entrance shall be reliability by warming the oil to
caused by phase loss, phase provided allowing prevent migration during off-cycles
imbalance, and phase reversal. electrical access for or low ambient conditions.
Phase monitor is equipped with an both control and
LED that provides an ON or FAULT main power Discharge Air Sensing Kit
indicator. connections inside
Provides true discharge air sensing in
the curb and
heating models. The kit is functional
Powered or Unpowered through the base of
only with the ReliaTel Options
Convenience Outlet the unit. Option will
Module.
allow for field
This option is a GFCI, 120v/15amp, 2 installation of liquid-tight conduit
plug, convenience outlet, either and an external field installed Electric Heaters
powered or unpowered. This option disconnect switch. Electric heat modules are available
can only be ordered when Through
Factory within the basic unit. If ordering the
the Base Electrical with either the
provided Through the Base Electrical option
Disconnect Switch or Circuit Breaker
through the with an Electrical Heater, the heater
option is ordered.
base must be factory installed.
openings
simplify Fresh Air Options – Dampers and
wiring and Economizer
piping. 0 - 25% manual or 0 - 50% motorized
Because these utility openings outside air hoods are available.
frequently minimize the number of
roof penetrations, the integrity of Economizers are equipped with
roofing materials is enhanced. either dry bulb or reference or
comparative enthalpy sensing. These
Two-Inch Pleated Filters economizers provide free cooling as
Stainless Steel Heat Exchanger the outdoor temperature and/or
The optional stainless steel heat 2” pleated media filters are offered humidity decreases. Correctly
exchanger is constructed of 304 as an option on all Precedent units installed, they offer a valuable energy
stainless steel. It is resistant to for jobs with enhanced Indoor Air savings. Factory-installed
corrosion and oxidation and easy to Quality (IAQ) requirements. economizers save time and ensure
clean. proper installation.
The high strength to weight ratio
Factory or Field Installed The economizers come with three
allows for high ventilation rates with Options* control options — dry bulb is
gas units. It is an excellent option to standard, enthalpy and differential
compliment the dehumidification *Refer to Model Number Description enthalpy are optional.
option as a high outside air for option availability.
ventilation unit. Frostat
Barometric Relief
With this option, a 10-year stainless This capillary bulb embedded in the
steel heat exchanger warranty is Designed to be used on downflow face of the evaporator coil monitors
standard. units, barometric relief is an coil temperature to prevent
unpowered means of relieving evaporator icing and protect the
Supply and/or Return Air Smoke excess building pressure. compressor. Recommended for
Detector applications with low leaving air
Clogged Filter/Fan Failure Switch temperatures, low airflow and or
With this option high latent load applications.
installed, if smoke is A dedicated differential pressure
detected, all unit switch is available to achieve active
fan failure indication and/or clogged LonTalk® Communications
operation will be shut
down. Reset will be filter indication. Interface
manual at the unit. These sensors allow a zone sensor The LonTalk communications
Return Air Smoke service light or Integrated Comfort interface allows the unit to
Detectors require System to indicate a dirty filter or a communicate as a Tracer™LCI-V
minimum allowable fan that’s not working. The field device or directly with generic
airflow when used with installation charges for these LonTalkNetwork Building Automation
certain models. valuable feedback devices often System Controls.
eliminate them from consideration.
Factory installation can make such
features a good investment.
RT-PRC023-EN 7
Features and Benefits

Reference or Comparative Dual Thermistor Remote Zone Remote Potentiometer


Enthalpy Sensor When properly installed in the
Measures and communicates This sensor will reduce the total economizer control circuitry, this
humidity while maximizing comfort number of remote sensors to obtain accessory provides a remote variable
control. space temperature averaging. This resistance to enable the operator to
sensor should be utilized with adjust the minimum damper
Tool-less Hail Guards ReliaTel controls. position.
Tool-less, hail protection quality coil Ventilation Override Accessory
High Altitude Kit
guards shall be either factory or field-
installed for condenser coil Previously a Canadian Agency With the Ventilation Override
protection. This option protects the requirement for units applied about Accessory installed, the unit can be
condenser coil from vandalism and/ 2000 feet, it is not required by the set to transition to up to 3 different
or hail damage. U.S. Domestic contractors should pre-programmed sequences for
consult with local authority on best Smoke Purge, Pressurization, and
practice. Devates gas orifices by 10%. Exhaust. The transition occurs when
a binary input on the RTOM is closed
High Static Drive (shorted). This would typically be a
hard wired relay output from a
Available on many models, this high smoke detector or fire control panel.
static drive accessory extends the The ventilation override kit is
capability of the standard motor. available as a field installed
Avoid expensive motors and accessory.
operating costs by installing this
optimized sheave accessory. Zone Sensors/Thermostats
Trane Communication Interface
(TCI) Humidity Sensor/Humidistat Available in programmable,
automatic and manual styles.
Available factory or field installed. Used in conjunction with our
This module when applied with the Dehumidification (Hot Gas Reheat)
ReliaTel™ easily interfaces with units to provide outstanding Other Benefits
Trane’s Integrated Comfort™ System. humidity control and comfort.
Humidity sensors can be wall or duct Airflow Distribution
Field Installed Options* mounted and set for levels between
Airflow is outstanding. The Precedent
40% and 60%.
*Refer to Model Number Description can replace an older machine with
for option availability. old ductwork and, in many cases,
LP Conversion Kit improve the comfort through better
CO2 Sensing Provided for field conversion of gas/ air distribution.
electric units from Natural gas to
The CO2 sensor has the ability to Propane. Cabinet Integrity
monitor space occupancy levels
within the building by measuring the For added water integrity, Precedent
Quick Adapt Curbs has a raised 1 1/8" lip around the
parts per million of CO2 (Carbon
Dioxide) in the air. As the CO2 levels Enables easy conversion of existing supply and return of the downflow
increase, the outside air damper Voyager 3-10 ton units to Precedent units to prevent water from blowing
modulates to meet the CO2 space units on replacement jobs. into the ductwork.
ventilation requirements. The CO2
sensor kit is available as a field Quick Start Kits
installed accessory.
Single phase equipment to enable
startup and prevent building lighting
Digital Display Zone Sensor
dimming during low voltage.
The Digital LCD (Liquid Crystal
Display) zone sensor has the look and Roof Curbs
functionality of standard zone
sensors. This sensor should be Available for downflow units. Only
utilized with ReliaTel™ controls. two roof curbs for the entire
Precedent line simplifies curb Easy to Install, Service and
selection. Maintain
Because today’s owners are very
cost-conscious when it comes to
service and maintenance, the Trane
Precedent was designed with direct
input from service contractors. This

8 RT-PRC023-EN
Features and Benefits

valuable information helped to ReliaTel Makes Installing and Intelligent Fallback is a benefit to the
design a product that would get the Servicing Easy building occupant. If a component
serviceman off the job quicker and goes astray, the unit will continue to
ReliaTel eliminates the need for field
save the owner money. Precedent operate at predetermined
installed anti-shortcycle timer and
does this by offering outstanding temperature setpoint.
time delay relays. ReliaTel controls
standard features enhanced by a
provide these functions as an integral Intelligent Anticipation is a standard
variety of factory and field installed
part of the unit. The contractor no ReliaTel feature. It functions
options, multiple control options,
longer has to purchase these controls continuously as ReliaTel and zone
rigorously tested proven designs and
as options and pay to install them. sensor(s) work together in harmony
superior product and technical
to provide much tighter comfort
support.
control than conventional electro-
mechanical thermostats.
Flexibility
The same ReliaTel Board fits all
Precedent offers ultimate flexibility. Precedent Packaged Gas/Electrics,
Units are built to order in our Cooling with Electric Heat, and Heat
standard “shortest in the industry” Pump models. This provides
ship cycle time. standardization of parts for
The wiring of the low voltage
connections to the unit and the zone contractors. Less money is tied up in
ReliaTel™ Controls sensors is as easy as 1-1, 2-2, and 3-3. inventory with ReliaTel.
ReliaTel controls provide unit control This simplified system makes wiring
for heating, cooling and ventilating easier for the installer. Unit Cabinet
utilizing input from sensors that The compact cabinet with rounded
measure outdoor and indoor ReliaTel Makes Testing Easy
corners takes up less room and is
temperature. ReliaTel requires no special tools to less costly to ship. The beveled and
run the Precedent unit through its ribbed top is not only aesthetically
paces. Simply place a jumper pleasing, it is designed to prevent
between Test 1 and Test 2 terminals water from pooling.
on the Low Voltage Terminal Board
and the unit will walk through its VariTrac – Building Automation
operational steps automatically. System
The unit automatically returns When Trane’s changeover VAV
control to the zone sensor after System for light commercial
ReliaTel Control Logic Enhances stepping through the test mode a applications is coupled with
Quality and Reliability single time, even if the jumper is left Precedent, it provides the latest in
on the unit. technological advances for comfort
• —prevents the unit from short
cycling, considerably improving As long as the unit has power and management systems and can allow
compressor life. the “system on” LED is lit, ReliaTel is thermostat control in every zone
operational. The light indicates that served by VariTrac.
• —ensures that the compressor the controls are functioning properly.
will run for a specific amount of
time which allows oil to return ReliaTel features expanded
for better lubrication, enhancing diagnostic capabilities when utilized
the reliability of the compressor. with Trane Integrated Comfort™
Systems.
Precedent with ReliaTel reduces the
number of components required to Some zone sensor options have
operate the unit, thereby reducing central control panel lights which
possibilities for component failure. indicate the mode the unit is in and
possible diagnostic information (dirty
filters for example).

Other ReliaTel Benefits


The ReliaTel built-in anti-shortcycle
timer, time delay relay and minimum
“on” time control functions are Rigorous Testing
factory tested to assure proper All of Precedent’s designs were
operation. rigorously rain tested at the factory
ReliaTel softens electrical “spikes” by to ensure water integrity.
staging on fans, compressors and Actual shipping tests were
heaters. performed to determine packaging
requirements. Units were test

RT-PRC023-EN 9
Features and Benefits

shipped around the country to


determine the best packaging.
Factory shake and drop tests were
used as part of the package design
process to help assure that the unit
arrives at the job site in top
condition.
Rigging tests include lifting a unit
into the air and letting it drop one
foot, assuring that the lifting lugs and
rails hold up under stress.
We perform a 100% coil leak test at
the factory. The evaporator and
condenser coils are leak tested at 575
psig and pressure tested to 450 psig.
All parts are inspected at the point of
final assembly. Sub-standard parts
are identified and rejected
immediately.
Every unit receives a 100% unit run
test before leaving the production
line to make sure it lives up to
rigorous Trane requirements.

10 RT-PRC023-EN
Application Considerations

Application of this product should be Heating Operation


within the cataloged airflow and
cooling considerations. The heat exchanger is manufactured
with aluminized steel. To prevent
condensation within the heat
Barometric Relief
exchanger, do not exceed 50%
This product line offers an optional outside air or a minimum mixed air
barometric relief damper for use in temperature of 40°F.
conjunction with economizer option.
This accessory consists of gravity Low Ambient Cooling
dampers which open with increased
pressure. As the building air The Precedent™ line features, with
pressure increases, the pressure in ReliaTel™ microprocessor controls,
the unit return air section also low ambient cooling down to 0°F.
increases, opening the dampers and With electromechanical controls,
relieving the conditioned space. Precedent features low ambient
cooling to 40°F. The following
Note: The effectiveness of features or options need to be
barometric relief damper included/considered when low
during economizing ambient applications are required:
operation is system related. continuous fan operation, crankcase
Note: Pressure drop of the return heaters, thermal expansion valves,
air system should be frostat.
considered to control Contact your local Trane
building pressurization. Representative for more assistance
with low ambient cooling
Black Epoxy Coil applications.
The coils are manufactured with a
thermoset, vinyl coating that is Optional Stainless Steel Heat
bonded to the aluminum fin stock Exchanger
prior to the fin stamping process. The optional stainless steel heat
These coils are an economical option exchanger is manufactured with 304
for protection in mildly corrosive stainless steel. To prevent corrosion
environments. and prolong heat exchanger
Note: Not to be used where reliability, the minimum mixed air
seacoast applications exist. temperature allowed across the heat
exchanger is 20°F.
CompleteCoat™ Condenser Coil The stainless steel heat exchanger
option is an excellent option that
The coils provide protection from compliments the dehumidification
corrosive environments and is ideal package. Whenever high outside air
for seacoast applications. or outside applications exist, these
options should be utilized.
Condensate Trap
The evaporator is a draw-thru Unit Pitch
configuration. A trap must be field
These units have reversible sloped
provided prior to start-up on the
condensate drain pans. Units must
cooling cycle.
be installed level. Any unit slope
must be toward the side of unit
Clearance Requirements where condensate drain is
The recommended clearances connected.
identified with unit dimensions
should be maintained to assure
adequate service maximum capacity
and peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the local
Trane sales personnel.

RT-PRC023-EN 11
Selection Procedure

Cooling Capacity Step 4. Heating Capacity


Note: Cooling Capacity Procedure In order to select the correct unit Note: Heating capacity procedure
is the same for electric heat which meets the building’s DIFFERS for electric heat
(T*C) and gas heat (Y*C). requirements, the fan motor heat (T*C) and gas heat (Y*C)
must be deducted from the gross units.)
Step 1. cooling capacity. The amount of heat
that the fan motor generates is Step 1.
Calculate the building’s total and dependent on the effort by the motor
sensible cooling loads at design - cfm and static pressure. To Calculate the building heating load
conditions. Use the Trane calculation determine the total unit static using the Trane calculation form or
methods or any other standard pressure: other standard accepted method.
accepted method.
External Static Duct System 0.36 wg Step 2.
Factors used in unit selection: Standard Filter 2 in. from 0.049 wg
Table 115 Size the system heating capacity to
Packaged Cooling with Optional Economizer from Table 115 0.105 wg match the calculated building
Electric Heat (100% Outside Air) *worst
case
heating load. The following are
Total Cooling Load: 59 MBh building heating requirements:
Electric Heater Size 6 kW 0.021 wg
Sensible Cooling Load: 40 MBh from Table 115 Total heating load of 15 MBh
Airflow: 2000 cfm (reference "Heating Capacity" section on
this page for determination of heater size)
2000 cfm
Electrical Characteristics: 460/60/3
Total Static Pressure 0.535 wg
Summer Design Conditions: T*C units with optional electric heat:
Entering Evaporator Coil: 80 DB, 67 460 volt/3 phase Power Supply
WB Outdoor Ambient: 95 Note: The Evaporator Fan The electric heat accessory
External Static Pressure: 0.36 in. wg Performance Table 34 has capacities are listed in Table 118.
Downflow Configuration deducted the pressure drop From the table, a 6 kW heater will
Efficiency: 13 SEER for a 1 in. filter already in the deliver 20.48 MBH at 480 volts. In
Economizer unit (see note below order to determine capacity at 460
Table 34). Therefore, the volts, the heater voltage correction
Step 2. actual total static pressure is factor from Table 119 must be used.
As a starting point, a rough 0.535 -0.049 (from Table 115) Therefore, 20.48 MBH x 0.918
determination must be made of the = 0.486 wg. (voltage correction factor) = 18.8
size of the unit. The final selection With 2000 cfm and 0.5 wg. MBh.
will be made after examining the Table 34 shows 0.575 bhp for this Y*C units with gas heat: Fuel- natural
performance at the given conditions. unit. Note below the table gives a gas.
Divide the total cooling load by formula to calculate Fan Motor Heat,
nominal BTUH per ton (12 MBh per 2.87 x bhp + 0.75 = MBh. 60 MBh, 80 MBh and 130 MBh input
ton); then round up to the nearest 2.87 x 0.575 + 0.15 = 1.8 MBh. models shown in Table 116. The
unit size. output capacities of these furnaces
Now subtract the fan motor heat are 48 MBh, 64 MBh and 104 MBh
59 MBh / 12 MBh = approx. 5 tons from the gross cooling capacity of respectively. The low heat model
the unit: with 48 MBh best matches the
Step 3. Net Total Cooling Capacity building requirements.
Table 13 shows that a TSC060E4 has = 62.3 MBh - 1.8 = 60.5 MBh.
a gross cooling capacity of 62.3 MBh Net Sensible Cooling Capacity Air Delivery Selection
and 48.1 MBh sensible capacity at = 48.1 MBh - 1.8 = 46.3 MBh.
2000 cfm and 95 DB outdoor Note: Air Delivery procedure is the
ambient with 80 DB, 67 WB air Subtracting Sensible from Total same for electric heat and
entering the evaporator. Capacity to find Latent Capacity gas heat units.)
Net Latent Capacity External static pressure drop
To Find Capacity at Intermediate
= 60.5 - 46.3 = 14.2 MBh through the air distribution system
Conditions Not in the Table.
has been calculated to be 0.5 inches
When the design conditions are Step 5. of water. Enter Table 53 for a
between two numbers that are in the TSC063E4 at 2000 cfm and 0.5 static
capacity table, interpolation is Compare your resulting capacities to pressure. The standard direct drive
required to approximate the the building load. If the performance motor will give the desired airflow at
capacity. will not meet the required load of the a rated bhp of 0.73 and 951 rpm.
building’s total or sensible cooling
Note: Extrapolation outside of the load, try a selection at the next
table conditions is not higher size unit.
recommended.

12 RT-PRC023-EN
Model Number Description

T S C 036 E 3 R B A ** C 0 0 0 A 1 0 0 0 2 A 1
1 2 3 456 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25

DIGIT 1 — UNIT TYPE


Y Medium, Stainless Steel Heat 2 Black Epoxy Pre-Coated
T DX Cooling Exchanger Condenser Coil
Y DX Cooling, Gas Heat Z High, Stainless Steel Heat 3 Black Epoxy Pre-Coated
W Packaged Heat Pump2,4 Exchanger Condenser Coil with Hail Guard
4 CompleteCoat™ Condenser Coil
DIGIT 2 — EFFICIENCY DIGIT 11 — MINOR DESIGN 5 CompleteCoat™ Condenser Coil
S Standard Efficiency SEQUENCE with Hail Guard
(13 SEER R-410A) A First Sequence
H High Efficiency DIGIT 18 - THROUGH THE BASE
(15 SEER R-410A) DIGIT 12,13 — SERVICE SEQUENCE PROVISIONS

** Factory Assigned Note: (Applicable to Digit 1, T or Y


DIGIT 3 — AIRFLOW models)
C Convertible DIGIT 14 — FRESH AIR SELECTION 0 No Through the Base Provisions
0 No Fresh Air A Through the Base Electric9
DIGIT 4,5,6 — NOMINAL GROSS A Manual Outside Air Damper
COOLING CAPACITY (MBh) Note: (Applicable to Digit 1, Y
0-50%5 models only)
036 3 Tons B Motorized Outside Air Damper
048 4 Tons 0-50% B Through the Base Gas Piping
060 5 Tons C Economizer, Dry Bulb 0-100% C Through the Base Electric and
072 6 Ton without Barometric Relief8 Gas Piping17
090 7½ Ton, Single Compressor D Economizer, Dry Bulb 0-100%
with Barometric Relief8 DIGIT 19 - DISCONNECT/CIRCUIT
092 7½ Ton, Dual Compressor
E Economizer, Reference Enthalpy BREAKER/PHASE MONITOR
102 8½ Ton
0-100% without Barometric (THREE- PHASE ONLY)
120 10 Ton
Relief4,8 0 No Disconnect/No Circuit Breaker
DIGIT 7 — MAJOR DESIGN F Economizer, Reference Enthalpy No Phase Monitor21
SEQUENCE 0-100% with Barometric Relief4,8 1 Unit Mounted Non-Fused
G Economizer, Comparative Disconnect9
E R-410A Refrigerant
Enthalpy 0-100% without 2 Unit Mounted Circuit Breaker9
DIGIT 8 — VOLTAGE SELECTION Barometric Relief4,8 3 Phase Monitor21,22
H Economizer, Comparative 4 Phase Monitor & Non-Fused
1 208/230/60/1 Enthalpy 0-100% with Barometric Disconnect Switch9,21,22
3 208-230/60/3 Relief4,8 5 Phase Monitor & Circuit
4 460/60/3 Breaker9,21,22
W 575/60/3 DIGIT 15 - SUPPLY FAN/DRIVE
TYPE/MOTOR DIGIT 20 - CONVENIENCE OUTLET
DIGIT 9 — UNIT CONTROLS
0 Standard Drive7 0 No Convenience Outlet
E Electromechanical1 2) Optional Belt Drive Motor20 A Unpowered Convenience Outlet
R ReliaTel™ Microprocessor B Powered Convenience Outlet
DIGIT 16 - HINGED SERVICE (three-phase only)10
DIGIT 10 — HEATING CAPACITY ACCESS/FILTERS
0=No Electric Heat E=12 kW (3 phase) 0 Standard Panels/Standard Filters DIGIT 21 - COMMUNICATIONS
A=5 kW (1 phase)2 F=14 kW (1 phase)2 A Hinged Access Panels/Standard OPTIONS 4
B=6 kW (3 phase) G=18 kW (1&3 phase)
D=10 kW (1 phase)2 J=23 kW (3 phase) Filters 0 No Communications Interface
B Standard Panels/2” Pleated 1 Trane Communications Interface
Note: Applicable to Digit 1, Y Filters 2 LonTalk® Communications
models only. C Hinged Access Panels/2” Pleated Interface
L Low Filters 3 Novar 2024 Controls1
M Medium 4 Novar 3051 Controls1
DIGIT 17 - CONDENSER COIL
H High PROTECTION
X Low, Stainless Steel Heat DIGIT 22 - REFRIGERATION SYSTEM
Exchanger 0 Standard Coil OPTION
1 Standard Coil with Hail Guard 0 Standard Refrigeration System11

RT-PRC023-EN 13
Model Number Description

DIGIT 23 - REFRIGERATION configured units must be


CONTROLS ordered as field installed
accessory.
Note: Applicable to Digit 7 = E
9. Through the base electric
0 No Refrigeration Control6
required when ordering
1 Frostat12
disconnect/circuit breaker
2 Crankcase Heater3
options.
3 Frostat12 and Crankcase Heater3
10. Requires use of Disconnect or
DIGIT 24 - SMOKE DETECTOR18 Circuit Breaker.
0 No Smoke Detector 11. Standard metering devices are
A Return Air Smoke Detector13,14 TXVs.
B Supply Air Smoke Detector
C Supply and Return Air Smoke 12. Frostat cannot be field installed
Detectors13,14 in electro-mechanical units.
13. The return air smoke detector
DIGIT 25 - MONITORING may not fit up or work properly
CONTROLS4 on the Precedent units when
0 No Monitoring Control15 used in conjunction with 3rd
1 Clogged Filter Switch15 party accessories such as bolt on
2 Fan Failure Switch15 heat wheels, economizers and
3 Discharge Air Sensing Tube15 power exhaust. Do not order the
4 Clogged Filter Switch and Fan return air smoke detectors when
Fail Switch15 using this type of accessory.
5 Clogged Filter Switch and 14. Return Air Smoke Detector
Discharge Air Sensing Tube15 cannot be ordered with Novar
6 Fan Fail Switch and Discharge Air Controls.
Sensing Tube15
7 Clogged Filter and Fan Fail 15. These options are standard
Switches and Discharge Air when ordering Novar Controls.
Sensing Tube15 16. This option is used when
8 Novar Return Air Sensor16 ordering Novar Controls.

Model Number Notes 17. Includes gas piping and shutoff


(field assembly required).
1. Not available for 3-5 tons,
R-410A Heat Pumps. 18. Not available with high
temperature duct sensor
2. Available on 3-5 Standard accessory.
Efficiency.
19. Requires hinged access panels.
3. Standard on all 15 SEER and 4-5
Ton E3,4,W Heat Pumps and all 20. Belt Drive optional on three-
6-10 Ton units. phase 15 SEER, R-410A units.

4. Not available with 21. Phase Reversal protection is


electromechanical controls. standard on 3-5 ton units with
Direct Drive and 3 phase power.
5. Manual outside air damper will
ship factory supplied within the 22. Available on Belt Drive (3-10)
unit, but must be field installed. tons

6. High pressure control is standard


on all units.
7. Multispeed direct drive standard
on single-phase and 15 SEER
products. Belt drive standard on
three-phase 13 SEER and 6-10
Ton products.
8. Economizer with Barometric
Relief is for downflow configured
units only. Order Economizer
without Barometric Relief for
horizontal configuration.
Barometric Relief for horizontal

14 RT-PRC023-EN
General Data

Table 1. General Data — 3-4 Tons — Standard Efficiency


3 Tons 4 Tons
T/YSC036E1 T/YSC036E3,4,W T/YSC048E1 T/YSC048E3,4,W
Cooling Performance(1)
Gross Cooling Capacity 35,620 37,150 49,210 49,450
SEER(2) 13.0 13.0 13.0 13.0
Nominal CFM / ARI Rated CFM 1,200/1,200 1,200/1,200 1,600/1,600 1,600/1,600
ARI Net Cooling Capacity 35,000 35,800 48,000 48,000
System Power (kW) 3.04 3.20 4.32 4.39
Compressor
Number/Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(3) 81 81 82 82
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 10.96 9.59 10.96 10.96
Rows/FPI 2/17 2/17 2/17 2/17
Indoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 7.71 7.71 7.71 7.71
Rows/FPI 3/16 3/16 4/16 4/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 1/22 1/22 1/22 1/22
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 3,466 3,375 3,411 3,403
Motor HP 0.33 0.33 0.33 0.33
Motor RPM 1,075 1,075 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Belt/Variable Direct/5 Belt/Variable
Number Motors 1 1 1 1
Motor HP 0.75 1.0 1.0 1.0
Motor Frame Size 48 56 48 56
Filters(4)
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (2) 20x30x1 (2) 20x30x1 (2) 20x30x1 (2) 20x30x1
Refrigerant Charge(5)
Pounds of R-410A 6.3 6.3 7.4 7.4

RT-PRC023-EN 15
General Data
(3-4 Tons Standard Efficiency)

Table 1. (continued) General Data — 3-4 Tons — Standard Efficiency


3 Tons 4 Tons
Heating Performance(6)
(Gas/Electric Only)
Heating Input
Low Heat Input (Btu) 60,000 60,000 60,000 60,000
Mid Heat Input (Btu) 80,000 80,000 80,000 80,000
High Heat Input (Btu) 120,000 120,000 120,000 120,000
Heating Output
Low Heat Input (Btu) 48,000 48,000 49,000 48,000
Mid Heat Input (Btu) 65,000 64,000 65,000 64,000
High Heat Input (Btu) 96,000 96,000 96,000 96,000
AFUE%(7)
Low Heat Input (Btu) 78 80 79 80
Mid Heat Input (Btu) 78 80 79 80
High Heat Input (Btu) 78 80 79 80
Steady State Efficiency%
Low Heat Input (Btu) 80 80 81 80
Mid Heat Input (Btu) 81 80 81 80
High Heat Input (Btu) 80 80 80 80
No. Burners
Low Heat Input (Btu) 2 2 2 2
Mid Heat Input (Btu) 2 2 2 2
High Heat Input (Btu) 3 3 3 3
No. Stages
Low Heat Input (Btu) 1 1 1 1
Mid Heat Input (Btu) 1 1 1 1
High Heat Input (Btu) 1 1 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/10.5 4.5/10.5 4.5/10.5 4.5/10.5
LP (minimum/maximum) 10.0/13.0 10.0/13.0 10.0/13.0 10.0/13.0
Gas Connection Pipe Size (in)
Low Heat 1/2 1/2 1/2 1/2
Mid Heat 1/2 1/2 1/2 1/2
High Heat 1/2 1/2 1/2 1/2
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with
the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 109.
(4) Optional 2” pleated filters also available.
(5) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(6) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards In-
stitute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each
1000 feet above sea level. Applicable to Gas/Electric units only.
(7) AFUE is rated in accordance with DOE test procedures.

16 RT-PRC023-EN
General Data
(5 Tons Standard Efficiency)

Table 2. General Data — 5 Tons — Standard Efficiency


5 Tons
T/YSC060E1 T/YSC060E3,4,W
Cooling Performance(1)
Gross Cooling Capacity 59,900 62,270
SEER(2) 13.0 13.0
Nominal CFM / ARI Rated CFM 2,000/2,000 2,000/2,000
ARI Net Cooling Capacity 58,000 60,000
System Power (kW) 5.25 5.46
Compressor
Number/Type 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(3) 82 82
Outdoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 10.96 10.96
Rows/FPI 3/17 3/17
Indoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 7.71 7.71
Rows/FPI 4/16 4/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller
Number Used/Diameter (in.) 1/22 1/22
Drive Type/No. Speeds Direct/1 Direct/1
CFM 3,271 3,245
Number Motors/HP 0.40 0.40
Motor RPM 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Belt/Variable
Motor HP 1.0 1.0
Motor Frame Size 48 56
Filters(4)
Type Furnished Throwaway Throwaway
Number Size Recommended (2) 20x30x1 (2)20x30x1
Refrigerant Charge (5)
Pounds of R-410A 9.5 9.4

RT-PRC023-EN 17
General Data
(5 Tons Standard Efficiency)

Table 2. (continued) General Data — 5 Tons — Standard Efficiency


5 Tons
Heating Performance(6)
(Gas/Electric Only)
Heating Input
Low Heat Input (Btu) 60,000 60,000
Mid Heat Input (Btu) 80,000 80,000
High Heat Input (Btu) 130,000 130,000
Heating Output
Low Heat Input (Btu) 48,000 48,000
Mid Heat Input (Btu) 65,000 64,000
High Heat Input (Btu) 104,000 104,000
AFUE%(7)
Low Heat Input (Btu) 78 80
Mid Heat Input (Btu) 79 80
High Heat Input (Btu) 78 80
Steady State Efficiency%
Low Heat Input (Btu) 80 80
Mid Heat Input (Btu) 81 80
High Heat Input (Btu) 80 80
No. Burners
Low Heat Input (Btu) 2 2
Mid Heat Input (Btu) 2 2
High Heat Input (Btu) 3 3
No. Stages
Low Heat Input (Btu) 1 1
Mid Heat Input (Btu) 1 1
High Heat Input (Btu) 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/10.5 4.5/10.5
LP (minimum/maximum) 10.0/13.0 10.0/13.0
Gas Connection Pipe Size (in)
Low Heat 1/2 1/2
Mid Heat 1/2 1/2
High Heat 1/2 1/2
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suit-
able for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equip-
ment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to
Table 109.
(4) Optional 2” pleated filters also available.
(5) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(6) Heating performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For eleva-
tions above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to
Gas/Electric units only.
(7) AFUE is rated in accordance with DOE test procedures.

18 RT-PRC023-EN
General Data
(6 – 10 Tons Standard Efficiency)

Table 3. General Data — 6-10 Tons — Standard Efficiency


6 Tons 7½ Tons 8½ Tons 10 Tons
T/YSC072E3,4,W T/YSC092E3,4,W T/YSC102E3,4,W T/YSC120E3,4,W
Cooling Performance(1)
Gross Cooling Capacity 75,000 94,000 102,000 118,000
EER(2) 11.2 11.2 11.2 10.6
Nominal CFM / ARI Rated CFM 2,400/2,100 3,000/2,625 3,400/2,975 4,000/3,500
ARI Net Cooling Capacity 71,200 89,300 96,600 110,300
Integrated Part Load Value(3) — 12.5 12.5 12.0
System Power (kW) 6.36 7.97 8.62 10.4
Compressor
Number/Type 1/Scroll 2/Scroll 2/Scroll 2/Scroll
Sound
Outdoor Sound Rating (dB)(4) 89 87 86 86
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 17 19.83 19.83 27.21
Rows/FPI 3/17 3/17 3/17 3/17
Indoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 9.89 12.36 12.36 12.36
Rows/FPI 3/16 3/16 3/16 3/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 1/26 1/26 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 6,037 6,610 6,610 7,057
Motor HP 0.7 0.75 0.75 0.75
Motor RPM 1,100 1,100 1,100 1,100
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/12x12 1/15x15 1/15x15 1/15x15
Drive Type/Number Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable
Motor HP (Standard/Oversized) 1.0/2.0 2.0/3.0 2.0/3.0 3.0/5.0
Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56 56/56
Filters(5)
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (4) 16x25x2 (4) 20x25x2 (4) 20x25x2 (4) 20x25x2
Refrigerant Charge (6)
Pounds of R-410A 10.5 7.12/6.62 8.37/7.56 11.81/7.25

RT-PRC023-EN 19
General Data
(6 – 10 Tons Standard Efficiency)

Table 3. (continued) General Data — 6-10 Tons — Standard Efficiency


6 Tons 7½ Tons 8½ Tons 10 Tons
Heating Performance(7)
(Gas/Electric Only)
Heating Input
Low Heat Input (Btu) 80,000 120,000 120,000 150,000/105,000
Mid Heat Input (Btu) 120,000 150,000/105,000 150,000/105,000 200,000/140,000
High Heat Input (Btu) 150,000/105,000 200,000/140,000 200,000/140,000 250,000/175,000
Heating Output
Low Heat Input (Btu) 64,800 97,200 97,200 121,500/85,000
Mid Heat Input (Btu) 97,200 121,500/85,000 121,500/85,000 162,000/113,000
High Heat Input (Btu) 121,500/85,000 160,000/112,000 160,000/112,000 202,500/141,800
AFUE%(8)
Low Heat Input (Btu) 81 81 81 81
Mid Heat Input (Btu) 81 81 81 81
High Heat Input (Btu) 81 81 81 81
Steady State Efficiency%
Low Heat Input (Btu) 81 81 81 81
Mid Heat Input (Btu) 81 81 81 81
High Heat Input (Btu) 81 80 80 81
No. Burners
Low Heat Input (Btu) 2 3 3 3
Mid Heat Input (Btu) 3 3 3 4
High Heat Input (Btu) 3 4 4 5
No. Stages
Low Heat Input (Btu) 1 1 1 2
Mid Heat Input (Btu) 1 2 2 2
High Heat Input (Btu) 2 2 2 2
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/14.0 4.5/14.0 4.5/14.0 4.5/14.0
LP (minimum/maximum) 10.0/14.0 10.0/14.0 10.0/14.0 10.0/14.0
Gas Connection Pipe Size (in)
Low Heat 1/2 1/2 1/2 3/4
Mid Heat 1/2 3/4 3/4 3/4
High Heat 3/4 3/4 3/4 3/4
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with
the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER is rated at ARI conditions and in accordance with DOE test procedures.
(3) Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated 80°F ambient, 80°F entering dry bulb and 67°F entering
wet bulb at ARI rated cfm.
(4) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 109.
(5) Optional 2” pleated filters also available.
(6) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(7) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards In-
stitute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each
1000 feet above sea level. Applicable to Gas/Electric units only.
(8) AFUE is rated in accordance with DOE test procedures.

20 RT-PRC023-EN
General Data
(3 – 4 Tons Standard Efficiency)

Table 4. General Data — 3-4 Tons — Standard Efficiency


3 Tons 4 Tons
WSC036E1 WSC036E3,4,W WSC048E1 WSC048E3,4,W
Cooling Performance(1)
Gross Cooling Capacity 37,650 38,030 49,040 50,130
SEER(2) 13.0 13.0 13.0 13.0
Nominal CFM / ARI Rated CFM 1,200/1,200 1,200/1,200 1,600/1,600 1,600/1,600
ARI Net Cooling Capacity 37,000 37,000 48,000 48,800
System Power (kW) 3.49 3.45 4.40 4.40
Heating Performance(3)
High Temp. Btuh Rating 37,000 37,000 44,400 44,400
System Power kW/COP 3.31/3.30 3.21/3.40 3.91/3.30 3.86/3.40
Low Temp. Btuh Rating 21,200 20,700 25,000 24,900
System Power (kW)/COP 2.99/2.10 2.85/2.10 3.63/2.00 3.53/2.10
HSPF (Btu/Watts-hr) 8.00 8.00 7.80 7.80
Compressor
Number/Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(4) 81 80 82 82
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 9.59 10.96 10.96 10.96
Rows/FPI 2/17 3/17 3/17 3/17
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve
Indoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 6.68 6.68 7.71 7.71
Rows/FPI 3/16 3/16 4/16 4/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 1/22 1/22 1/22 1/22
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 3,323 2,823 3,276 3,279
Number Motors/HP 0.25 0.25 0.40 0.40
Motor RPM 1,075 1,075 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Belt/Variable Direct/5 Belt/Variable
Motor HP 0.75 1.0 1.0 1.0
Motor Frame Size (Standard/Oversized) 48 56 48 56
Filters(5)
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (2) 20x30x1 (2) 20x30x1 (2) 20x30x1 (2) 20x30x1
Refrigerant Charge (6)
Pounds of R-410A 5.6 7.3 8.8 9.4
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with
the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Heating performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with
the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(4) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 109.
(5) Optional 2” pleated filters also available.
(6) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC023-EN 21
General Data
(5 Tons Standard Efficiency)

Table 5. General Data — 5 Tons —Standard Efficiency


5 Tons
WSC060E1 WSC060E3,4,W
Cooling Performance(1)
Gross Cooling Capacity 58,360 63,440
SEER(2) 13.0 13.0
Nominal CFM / ARI Rated CFM 2,000/2,000 2,000/2,000
ARI Net Cooling Capacity 57,000 62,000
System Power (kW) 5.06 5.13
Heating Performance(3)
High Temp. Btuh Rating 58,500 58,500
System Power kW/COP 4.86/3.50 4.94/3.50
Low Temp. Btuh Rating 34,500 34,400
System Power kW/COP 4.46/2.30 4.44/2.30
HSPF (Btu/Watts-hr) 8.00 8.00
Compressor
Number/Type 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(4) 87 87
Outdoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 17.00 17.00
Rows/FPI 3/17 3/17
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve
Indoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 9.27 9.27
Rows/FPI 3/16 3/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller
Number Used/Diameter (in.) 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1
CFM 5,145 5,138
Motor HP 0.40 0.40
Motor RPM 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Belt/Variable
Motor HP 1.00 1.00
Motor Frame Size 48 56
Filters(5)
Type Furnished Throwaway Throwaway
Number Size Recommended (4) 16x25x2 (4) 16x25x2
Refrigerant Charge(6)
Pounds of R-410A 10.0 10.6
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suit-
able for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equip-
ment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Heating performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suit-
able for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equip-
ment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(4) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to
Table 109.
(5) Optional 2” pleated filters also available.
(6) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

22 RT-PRC023-EN
General Data
(3 – 4 Tons High Efficiency)

Table 6. General Data — 3-4 Tons — High Efficiency


3 Tons 4 Tons
T/YHC036E1 T/YHC036E3,4 T/YHC048E1 T/YHC048E3,4
Cooling Performance(1)
Gross Cooling Capacity 38,490 38,490 48,930 49,930
SEER(2) 15.2 15.0 15.0 15.0
Nominal CFM / ARI Rated CFM 1,200/1,200 1,200/1,200 1,600/1,600 1,600/1,600
ARI Net Cooling Capacity 38,000 38,000 48,000 49,000
System Power (kW) 2.93 2.99 3.83 3.67
Compressor
Number/Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(3) 81 81 87 87
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) OD 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 10.96 10.96 17.00 17.00
Rows/FPI 3/17 3/17 3/17 3/17
Indoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size (in.) 0.3125 0.3125 0.3125 0.3125
Face Area (sq. ft.) 7.71 7.71 9.27 9.27
Rows/FPI 3/16 3/16 3/16 3/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 1/22 1/22 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 3,064 3,064 3,986 3,982
Motor HP 0.2 0.2 0.4 0.4
Motor RPM 1,075 1,075 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Direct/5 Direct/5 Direct/5
Number Motors 1 1 1 1
Motor HP (Standard/Oversized) 0.75 1.0 1.0 1.0
Motor Frame Size (Standard/Oversized) 48 48 48 48
Indoor Fan
Type (Optional) — FC Centrifugal — FC Centrifugal
Number Used/Diameter (in.) — 1/11x11 — 1/11x11
Drive Type/Number Speeds — Belt/Variable — Belt/Variable
Number Motors — 1 — 1
Motor HP (Standard/Oversized) — 1.0 — 1.0
Motor Frame Size (Standard/Oversized) — 56 — 56
Filters(4)
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (2) 20x30x1 (2) 20x30x1 (4) 16x25x2 (4) 16x25x2
Refrigerant Charge (5)
Pounds of R-410A 7.9 7.9 11.0 11.0

RT-PRC023-EN 23
General Data
(3 – 4 Tons High Efficiency)

Table 6. (continued) General Data — 3-4 Tons — High Efficiency


3 Tons 4 Tons
Heating Performance(6)
(Gas/Electric Only)
Heating Input
Low Heat Input (Btu) 60,000 60,000 60,000 60,000
Mid Heat Input (Btu) 80,000 80,000 80,000 80,000
High Heat Input (Btu) 120,000 120,000 120,000 120,000
Heating Output
Low Heat Input (Btu) 48,000 48,000 49,000 48,000
Mid Heat Input (Btu) 65,000 64,000 64,000 64,000
High Heat Input (Btu) 96,000 96,000 96,000 96,000
AFUE%(7)
Low Heat Input (Btu) 78 78 80 80
Mid Heat Input (Btu) 78 78 79 79
High Heat Input (Btu) 78 78 79 79
Steady State Efficiency%
Low Heat Input (Btu) 80 80 81 81
Mid Heat Input (Btu) 81 80 80 80
High Heat Input (Btu) 80 80 80 81
No. Burners
Low Heat Input (Btu) 2 2 2 2
Mid Heat Input (Btu) 2 2 2 2
High Heat Input (Btu) 3 3 3 3
No. Stages
Low Heat Input (Btu) 1 1 1 1
Mid Heat Input (Btu) 1 1 1 1
High Heat Input (Btu) 1 1 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/10.5 4.5/10.5 4.5/10.5 4.5/10.5
LP (minimum/maximum) 10.0/13.0 10.0/13.0 10.0/13.0 10.0/13.0
Gas Connection Pipe Size (in)
Low Heat 1/2 1/2 1/2 1/2
Mid Heat 1/2 1/2 1/2 1/2
High Heat 1/2 1/2 1/2 1/2
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with
the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 109.
(4) Optional 2” pleated filters also available.
(5) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(6) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards In-
stitute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each
1000 feet above sea level. Applicable to Gas/Electric units only.
(7) AFUE is rated in accordance with DOE test procedures.

24 RT-PRC023-EN
General Data
(5 Tons High Efficiency)

Table 7. General Data — 5 Tons — High Efficiency


5 Tons
T/YH060E1 T/YHC060E3,4
Cooling Performance(1)
Gross Cooling Capacity 62,490 63,490
SEER(2) 15.0 15.0
Nominal CFM / ARI Rated CFM 2,000/2,000 2,000/2,000
ARI Net Cooling Capacity 61,000 62,000
System Power (kW) 4.75 4.83
Compressor
Number/Type 1/Scroll 1/Scroll
Sound
Outdoor Sound Rating (dB)(3) 87 87
Outdoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 17.00 17.00
Rows/FPI 3/17 3/17
Indoor Coil
Type Lanced Lanced
Tube Size (in.) 0.3125 0.3125
Face Area (sq. ft.) 9.89 9.89
Rows/FPI 4/16 4/16
Refrigerant Control Thermal Expansion Valve Thermal Expansion Valve
Drain Connection Number/Size (in.) 1¾ NPT 1¾ NPT
Outdoor Fan
Type Propeller Propeller
Number Used/Diameter (in.) 1/26 1/26
Drive Type/No. Speeds Direct/1 Direct/1
CFM 3,953 3,953
Number Motors/HP 0.40 0.40
Motor RPM 1,075 1,075
Indoor Fan
Type (Standard) FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1/11x11 1/11x11
Drive Type/Number Speeds Direct/5 Direct/5
Motor HP 1.0 1.0
Motor Frame Size 48 48
Indoor Fan
Type (Optional) — FC Centrifugal
Number Used/Diameter (in.) — 1/11x11
Drive Type/Number Speeds — Belt/Variable
Motor HP — 1.0
Motor Frame Size — 56
Filters(4)
Type Furnished Throwaway Throwaway
Number Size Recommended (4) 16x25x2 (4) 16x25x2
Refrigerant Charge(5)
Pounds of R-410A 12.5 12.5

RT-PRC023-EN 25
General Data
(5 Tons High Efficiency)

Table 7. (continued) General Data — 5 Tons — High Efficiency


5 Tons
Heating Performance(6)
(Gas/Electric Only)
Heating Input
Low Heat Input (Btu) 60,000 60,000
Mid Heat Input (Btu) 80,000 80,000
High Heat Input (Btu) 130,000 130,000
Heating Output
Low Heat Input (Btu) 49,000 48,000
Mid Heat Input (Btu) 64,000 64,000
High Heat Input (Btu) 104,000 104,000
AFUE%(7)
Low Heat Input (Btu) 80 80
Mid Heat Input (Btu) 79 79
High Heat Input (Btu) 80 80
Steady State Efficiency%
Low Heat Input (Btu) 81 81
Mid Heat Input (Btu) 80 80
High Heat Input (Btu) 80 80
No. Burners
Low Heat Input (Btu) 2 2
Mid Heat Input (Btu) 2 2
High Heat Input (Btu) 3 3
No. Stages
Low Heat Input (Btu) 1 1
Mid Heat Input (Btu) 1 1
High Heat Input (Btu) 1 1
Gas Supply Line Pressure
Natural (minimum/maximum) 4.5/10.5 4.5/10.5
LP (minimum/maximum) 10.0/13.0 10.0/13.0
Gas Connection Pipe Size (in)
Low Heat 1/2 1/2
Mid Heat 1/2 1/2
High Heat 1/2 1/2
(1) Cooling performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suit-
able for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equip-
ment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).
(2) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
(3) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to
Table 109.
(4) Optional 2” pleated filters also available.
(5) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
(6) Heating performance limit settings and rating data were established and approved under laboratory test conditions
using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For eleva-
tions above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to
Gas/Electric units only.
(7) AFUE is rated in accordance with DOE test procedures.

26 RT-PRC023-EN
Performance Data

Table 8. Gross Cooling Capacities 3 Tons Single Phase T/YSC036E1


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 33.6 28.2 37.2 20.6 41.0 12.4 31.0 26.6 34.4 19.3 38.0 10.9 28.2 25.2 31.4 17.4 34.9 9.2 25.3 23.7 28.3 15.8 31.6 8.3
80 34.6 34.5 37.7 26.6 41.7 19.7 32.2 32.2 34.9 25.2 38.8 17.6 29.8 29.8 31.9 23.5 35.6 16.2 27.1 27.1 28.8 21.8 32.3 14.6
85 36.8 36.8 38.2 32.8 42.1 25.2 34.4 34.4 35.4 31.3 39.1 23.5 32.0 32.0 32.5 30.0 36.0 22.0 29.4 29.4 29.6 28.6 32.7 20.4
90 39.1 39.1 39.2 39.1 42.4 30.9 36.8 36.8 36.7 36.7 39.5 29.4 34.3 34.3 34.2 34.2 36.4 27.9 31.6 31.6 31.6 31.6 33.1 26.3
1200 75 34.4 30.2 38.0 21.7 41.8 12.5 31.7 28.7 35.1 20.2 38.7 11.6 28.9 27.3 32.0 18.4 35.5 9.5 26.0 25.5 28.8 16.7 32.1 8.5
80 35.8 35.8 38.5 28.2 42.6 20.0 33.4 33.4 35.6 26.9 39.5 18.6 30.9 30.9 32.6 25.1 36.2 16.9 28.2 28.2 29.4 23.5 32.8 15.6
85 38.2 38.2 39.0 35.3 42.8 26.4 35.8 35.8 36.2 34.0 39.8 24.9 33.2 33.2 33.4 32.5 36.6 23.5 30.5 30.5 30.5 30.4 33.2 21.8
90 40.6 40.6 40.6 40.6 43.2 33.1 38.2 38.2 38.1 38.1 40.2 31.5 35.6 35.6 35.5 35.5 37.1 29.9 32.8 32.8 32.8 32.8 33.8 28.5
1320 75 35.0 32.3 38.6 22.6 42.4 12.7 32.4 30.7 35.6 20.9 39.3 11.1 29.6 29.0 32.5 19.4 36.0 10.3 26.7 26.7 29.3 17.8 32.6 8.7
80 37.0 37.0 39.1 30.3 43.2 20.9 34.5 34.5 36.2 28.5 40.0 19.3 31.8 31.8 33.2 26.8 36.7 17.7 29.1 29.1 29.9 25.4 33.2 16.4
85 39.4 39.4 39.8 37.9 43.5 27.9 36.9 36.9 37.1 36.3 40.4 26.4 34.3 34.3 34.3 34.2 37.1 24.7 31.4 31.4 31.4 31.4 33.8 23.1
90 41.9 41.9 41.9 41.9 43.9 35.0 39.4 39.4 39.4 39.4 40.8 33.6 36.7 36.7 36.6 36.6 37.6 32.2 33.8 33.8 33.8 33.8 34.3 31.1
1440 75 35.7 34.2 39.1 23.7 43.0 13.6 33.0 32.4 36.1 22.2 39.8 11.4 30.2 30.2 33.0 20.4 36.5 10.6 27.4 27.4 29.7 18.6 32.9 8.9
80 38.0 38.0 39.7 31.6 43.7 21.7 35.4 35.4 36.7 30.1 40.5 20.4 32.7 32.7 33.7 28.8 37.1 18.4 29.9 29.9 30.4 27.3 33.6 16.7
85 40.5 40.5 40.6 40.0 44.0 29.3 37.9 37.9 37.9 37.9 40.9 27.8 35.2 35.2 35.2 35.2 37.6 26.2 32.3 32.3 32.3 32.3 34.2 24.7
90 43.1 43.1 43.1 43.1 44.5 37.2 40.5 40.5 40.4 40.4 41.5 36.1 37.7 37.7 37.7 37.7 38.3 34.8 34.7 34.7 34.7 34.7 35.0 33.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 9. Gross Cooling Capacities 3 Tons Three Phase T/YSC036E,3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 34.9 29.1 38.7 21.5 42.6 12.9 32.4 27.7 36.0 19.8 39.8 11.8 29.8 26.2 33.3 18.4 36.9 9.9 27.0 24.8 30.3 16.9 33.7 8.6
80 35.6 35.6 39.0 27.6 43.2 19.3 33.5 33.5 36.4 26.1 40.3 18.2 31.2 31.2 33.6 24.7 37.4 16.7 28.7 28.7 30.7 23.2 34.2 15.4
85 37.9 37.9 39.4 33.5 43.5 25.8 35.7 35.7 36.8 32.2 40.7 24.5 33.5 33.5 34.1 30.9 37.8 23.3 30.9 30.9 31.2 29.8 34.6 21.6
90 40.1 40.1 40.1 40.1 43.7 31.8 38.0 38.0 37.9 37.9 41.0 30.5 35.7 35.7 35.6 35.6 38.1 29.1 33.1 33.1 33.1 33.1 34.9 27.5
1200 75 35.6 31.1 39.4 22.3 43.4 13.3 33.2 29.7 36.7 21.0 40.5 11.2 30.5 28.3 33.9 19.3 37.5 10.1 27.7 27.0 30.8 18.0 34.3 8.7
80 36.9 36.9 39.8 29.2 43.9 19.6 34.7 34.7 37.2 27.8 41.1 18.7 32.4 32.4 34.4 26.3 38.1 17.9 29.8 29.8 31.3 24.8 34.8 15.9
85 39.3 39.3 40.2 36.1 44.3 27.3 37.1 37.1 37.6 34.8 41.5 26.0 34.7 34.7 35.0 33.8 38.5 24.6 32.1 32.1 32.1 32.1 35.2 23.0
90 41.7 41.7 41.6 41.6 44.5 33.9 39.4 39.4 39.4 39.4 41.7 32.6 37.0 37.0 37.0 37.0 38.8 31.2 34.4 34.4 34.3 34.3 35.6 29.8
1320 75 36.3 33.1 40.1 23.3 44.0 13.2 33.8 31.7 37.3 22.0 41.1 11.4 31.2 30.4 34.4 20.1 38.0 10.0 28.4 28.4 31.3 18.7 34.7 8.6
80 38.1 38.1 40.5 30.9 44.6 21.0 35.8 35.8 37.8 29.4 41.7 20.1 33.4 33.4 34.9 28.1 38.6 17.9 30.7 30.7 31.8 26.5 35.3 17.4
85 40.6 40.6 41.0 38.8 45.0 28.7 38.3 38.3 38.5 37.6 42.0 27.0 35.8 35.8 35.9 35.8 39.0 25.9 33.1 33.1 33.1 33.1 35.7 24.4
90 43.0 43.0 43.0 43.0 45.2 36.0 40.7 40.7 40.6 40.6 42.4 34.8 38.2 38.2 38.1 38.1 39.4 33.3 35.5 35.5 35.5 35.5 36.1 32.0
1440 75 37.0 35.1 40.6 24.3 44.6 13.4 34.5 33.8 37.8 22.8 41.6 12.0 31.8 31.8 34.9 21.5 38.5 10.7 29.1 29.1 31.7 19.8 35.1 9.2
80 39.1 39.1 41.1 32.6 45.2 22.3 36.8 36.8 38.3 31.1 42.2 21.2 34.3 34.3 35.4 29.8 39.1 19.6 31.6 31.6 32.3 28.4 35.7 18.3
85 41.7 41.7 41.8 41.3 45.5 30.2 39.3 39.3 39.3 39.3 42.5 28.7 36.8 36.8 36.8 36.8 39.5 27.1 34.0 34.0 34.0 34.0 36.2 25.9
90 44.2 44.2 44.2 44.2 45.8 38.1 41.8 41.8 41.7 41.7 43.0 36.7 39.2 39.2 39.2 39.2 39.9 35.6 36.4 36.4 36.4 36.4 36.7 34.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 27
Performance Data
(4 Tons Standard Efficiency)

Table 10. Gross Cooling Capacities 4 Tons Single Phase T/YSC048E1


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 46.2 38.6 51.6 28.3 57.2 17.8 42.8 36.7 48.0 26.4 53.4 15.6 39.1 34.6 44.1 24.4 49.3 15.6 35.3 32.6 40.0 22.3 44.9 11.9
80.0 46.9 46.9 51.9 36.5 57.6 26.2 44.0 44.0 48.3 34.6 53.9 24.3 40.8 40.8 44.4 32.6 49.7 22.0 37.4 37.4 40.3 30.6 45.5 20.3
85.0 49.9 49.9 52.2 44.8 57.9 34.2 47.0 47.0 48.6 42.9 54.1 32.3 43.8 43.8 44.9 41.1 50.1 30.4 40.4 40.4 40.9 39.1 45.8 28.5
90.0 53.0 53.0 52.9 52.9 58.2 42.3 50.0 50.0 49.9 49.9 54.4 40.5 46.8 46.8 46.7 46.7 50.3 38.7 43.3 43.3 43.3 43.3 46.2 36.7
1600 75.0 47.2 41.3 52.6 29.7 58.3 18.0 43.8 39.3 48.9 27.8 54.3 18.1 40.0 37.4 44.9 25.8 50.2 14.1 36.1 35.2 40.7 23.7 45.6 12.5
80.0 48.7 48.7 52.9 38.8 58.8 27.2 45.7 45.7 49.2 36.9 54.8 25.4 42.4 42.4 45.3 35.0 50.6 23.5 38.9 38.9 41.2 33.0 46.3 21.4
85.0 51.9 51.9 53.3 48.2 59.0 36.2 48.8 48.8 49.7 46.4 55.1 34.4 45.5 45.5 45.9 44.4 51.0 32.5 41.9 41.9 42.0 42.0 46.6 30.6
90.0 55.0 55.0 55.0 55.0 59.2 45.3 51.9 51.9 51.9 51.9 55.4 43.5 48.6 48.6 48.6 48.6 51.4 41.8 45.0 45.0 45.0 45.0 47.0 39.8
1760 75.0 48.2 44.0 53.5 31.1 59.1 18.2 44.6 42.0 49.7 29.2 55.1 16.2 40.8 40.0 45.6 27.1 50.8 14.8 37.0 37.0 41.3 25.2 46.3 12.6
80.0 50.3 50.3 53.8 41.2 59.6 28.3 47.1 47.1 50.1 39.3 55.6 26.5 43.8 43.8 46.0 37.3 51.4 24.6 40.2 40.2 41.8 35.3 46.8 22.6
85.0 53.6 53.6 54.2 51.5 59.9 38.3 50.4 50.4 50.7 49.7 56.0 36.4 47.0 47.0 46.9 46.9 51.7 34.6 43.4 43.4 43.3 43.3 47.2 32.6
90.0 56.8 56.8 56.8 56.8 60.1 48.3 53.7 53.7 53.6 53.6 56.3 46.5 50.2 50.2 50.2 50.2 52.1 44.7 46.5 46.5 46.4 46.4 47.7 42.8
1920 75.0 48.9 46.6 54.2 32.5 59.9 20.1 45.3 44.7 50.3 30.6 55.7 17.1 41.7 41.7 46.2 28.7 51.4 14.4 38.1 38.1 41.8 26.5 46.8 12.4
80.0 51.7 51.7 54.5 43.5 60.4 29.4 48.5 48.5 50.8 41.7 56.3 27.7 45.0 45.0 46.7 39.7 52.0 25.8 41.3 41.3 42.4 37.7 47.4 23.7
85.0 55.0 55.0 55.3 54.9 60.6 40.3 51.8 51.8 51.8 51.8 56.6 38.5 48.3 48.3 48.3 48.3 52.4 36.6 44.6 44.6 44.6 44.6 47.9 34.7
90.0 58.4 58.4 58.3 58.3 60.9 51.3 55.2 55.2 55.1 55.1 57.0 49.6 51.7 51.7 51.6 51.6 52.9 47.8 47.8 47.8 47.8 47.8 48.3 45.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 11. Gross Cooling Capacities 4 Tons Three Phase T/YSC048E,3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 46.2 38.9 51.7 28.6 57.3 17.6 42.8 37.0 48.0 26.6 53.5 16.0 39.2 35.0 44.1 24.5 49.3 14.0 35.3 32.9 39.9 22.7 44.8 11.5
80.0 47.2 47.2 52.0 36.8 57.9 25.5 44.2 44.2 48.4 34.9 54.0 24.4 41.1 41.1 44.6 33.1 49.9 22.8 37.7 37.7 40.5 31.1 45.5 20.6
85.0 50.4 50.4 52.5 45.3 58.3 34.5 47.4 47.4 48.9 43.4 54.4 32.7 44.2 44.2 45.2 41.5 50.3 31.0 40.8 40.8 41.0 39.5 46.0 28.8
90.0 53.5 53.5 53.5 53.5 58.7 42.8 50.5 50.5 50.4 50.4 54.8 40.9 47.3 47.3 47.2 47.2 50.8 39.2 43.8 43.8 43.7 43.7 46.4 37.2
1600 75.0 47.3 41.6 52.7 29.9 58.3 17.6 43.8 39.7 48.9 27.9 54.4 16.2 40.1 37.6 44.9 25.9 50.1 14.1 36.2 35.7 40.7 23.7 45.5 11.5
80.0 49.1 49.1 53.1 39.2 59.0 27.8 46.0 46.0 49.4 37.3 55.0 25.6 42.7 42.7 45.5 35.5 50.8 23.8 39.2 39.2 41.3 33.4 46.3 21.7
85.0 52.3 52.3 53.7 48.6 59.4 36.5 49.3 49.3 50.0 46.6 55.4 35.0 46.0 46.0 46.2 44.9 51.2 32.9 42.4 42.4 42.3 42.3 46.8 30.9
90.0 55.6 55.6 55.6 55.6 59.8 45.8 52.5 52.5 52.4 52.4 55.9 44.1 49.2 49.2 49.1 49.1 51.8 42.3 45.5 45.5 45.5 45.5 47.4 40.5
1760 75.0 48.3 44.3 53.5 31.3 59.3 18.4 44.7 42.3 49.7 29.3 55.2 16.2 41.0 40.5 45.6 27.7 50.8 14.5 37.2 37.2 41.3 25.7 46.2 12.5
80.0 50.7 50.7 54.1 41.6 59.9 28.9 47.6 47.6 50.3 39.7 55.9 27.0 44.1 44.1 46.3 37.8 51.5 24.7 40.5 40.5 42.0 35.8 46.9 23.0
85.0 54.1 54.1 54.7 51.9 60.3 38.6 50.9 50.9 51.1 50.2 56.3 36.8 47.5 47.5 47.4 47.4 52.0 34.8 43.8 43.8 43.8 43.8 47.5 32.9
90.0 57.5 57.5 57.5 57.5 60.8 48.9 54.3 54.3 54.3 54.3 56.9 47.2 50.8 50.8 50.7 50.7 52.6 45.2 47.0 47.0 46.9 46.9 48.1 43.4
1920 75.0 49.1 46.9 54.3 32.9 59.9 18.3 45.5 45.0 50.4 30.8 55.8 16.6 42.0 42.0 46.2 29.0 51.3 15.3 38.3 38.3 41.8 26.9 46.8 13.0
80.0 52.1 52.1 54.8 44.1 60.7 30.0 48.9 48.9 51.1 42.1 56.5 27.3 45.4 45.4 46.9 40.1 52.1 26.2 41.7 41.7 42.6 38.1 47.5 24.1
85.0 55.6 55.6 55.7 55.3 61.1 40.8 52.3 52.3 52.3 52.3 57.0 38.9 48.8 48.8 48.8 48.8 52.7 37.1 45.0 45.0 44.9 44.9 48.0 35.0
90.0 59.2 59.2 59.2 59.2 61.6 52.0 55.8 55.8 55.8 55.8 57.6 50.1 52.3 52.3 52.2 52.2 53.4 48.1 48.4 48.4 48.4 48.4 48.8 46.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

28 RT-PRC023-EN
Performance Data

(5 Tons Standard Efficiency)

Table 12. Gross Cooling Capacities 5 Tons Single Phase T/YSC060E1


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 56.4 48.2 62.4 34.4 69.0 21.3 52.6 46.3 58.4 32.8 64.7 18.5 48.5 44.2 54.1 30.8 60.1 17.6 44.2 42.1 49.4 28.4 55.1 15.2
80.0 57.5 57.5 62.8 45.1 69.4 31.1 54.3 54.3 58.9 43.2 65.2 29.5 50.7 50.7 54.5 41.2 60.5 27.6 46.9 46.9 49.8 39.1 55.5 25.5
85.0 61.1 61.1 63.3 55.7 69.8 41.7 57.8 57.8 59.3 53.8 65.5 39.9 54.2 54.2 55.1 51.9 60.9 38.0 50.2 50.2 50.5 49.9 55.8 35.9
90.0 64.7 64.7 64.6 64.6 70.1 52.1 61.3 61.3 61.2 61.2 65.9 50.3 57.6 57.6 57.6 57.6 61.3 48.4 53.5 53.5 53.5 53.5 56.2 46.5
2000 75.0 57.5 51.4 63.6 36.1 70.1 21.4 53.7 49.5 59.5 34.1 65.8 19.9 49.6 47.6 55.0 32.2 61.1 17.4 45.2 45.0 50.2 30.2 55.9 15.2
80.0 59.5 59.5 64.0 47.9 70.6 32.6 56.1 56.1 59.9 46.0 66.3 30.7 52.5 52.5 55.5 44.1 61.6 28.8 48.5 48.5 50.7 42.0 56.3 26.9
85.0 63.2 63.2 64.6 59.7 71.0 44.1 59.8 59.8 60.5 58.0 66.6 42.5 56.1 56.1 56.4 56.0 61.9 40.4 51.9 51.9 51.9 51.9 56.7 38.5
90.0 67.0 67.0 66.9 66.9 71.4 55.8 63.5 63.5 63.5 63.5 67.0 53.9 59.7 59.7 59.6 59.6 62.3 52.1 55.4 55.4 55.4 55.4 57.2 50.2
2200 75.0 58.6 54.7 64.6 37.8 71.2 22.1 54.7 52.8 60.3 35.9 66.7 18.5 50.6 50.3 55.8 34.0 61.9 17.6 46.3 46.3 50.9 31.9 56.6 15.6
80.0 61.3 61.3 65.0 50.7 71.6 33.9 57.8 57.8 60.8 48.9 67.2 32.1 54.0 54.0 56.3 47.0 62.3 30.2 49.8 49.8 51.4 44.9 57.0 28.2
85.0 65.1 65.1 65.8 63.9 72.0 46.6 61.6 61.6 61.8 61.6 67.5 44.8 57.8 57.8 57.7 57.7 62.7 42.9 53.4 53.4 53.4 53.4 57.4 41.0
90.0 69.0 69.0 68.9 68.9 72.4 59.3 65.4 65.4 65.4 65.4 68.0 57.7 61.4 61.4 61.4 61.4 63.2 55.8 57.0 57.0 57.0 57.0 58.0 54.0
2400 75.0 59.5 57.9 65.4 39.5 72.1 20.4 55.6 55.4 61.1 37.6 67.4 19.7 51.6 51.6 56.5 35.6 62.5 17.6 47.5 47.5 51.5 33.6 57.2 15.7
80.0 62.8 62.8 65.9 53.6 72.5 34.9 59.2 59.2 61.6 51.8 68.0 33.5 55.3 55.3 57.0 49.8 63.1 31.5 51.0 51.0 52.1 47.9 57.6 29.6
85.0 66.8 66.8 66.9 66.8 72.9 49.2 63.2 63.2 63.2 63.2 68.3 47.3 59.2 59.2 59.1 59.1 63.4 45.4 54.7 54.7 54.7 54.7 58.0 43.6
90.0 70.9 70.9 70.7 70.7 73.3 63.1 67.0 67.0 67.0 67.0 68.8 61.4 63.0 63.0 62.9 62.9 64.0 59.7 58.4 58.4 58.4 58.4 58.8 57.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 13. Gross Cooling Capacities 5 Tons Three Phase T/YSC060E3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 58.8 50.1 65.0 36.7 71.7 22.6 54.7 47.9 60.6 35.4 67.1 20.8 50.3 45.5 56.1 32.4 62.3 19.5 45.8 43.3 51.2 30.4 57.1 18.0
80.0 59.9 59.9 65.4 47.0 72.1 33.4 56.3 56.3 61.1 44.9 67.5 31.4 52.6 52.6 56.6 42.9 62.7 29.6 48.6 48.6 51.7 40.7 57.4 27.8
85.0 63.5 63.5 65.9 57.7 72.5 43.9 59.9 59.9 61.6 55.6 67.9 41.6 56.1 56.1 57.0 53.3 63.0 39.8 52.0 52.0 52.2 51.2 57.8 37.7
90.0 67.1 67.1 67.1 67.1 72.9 54.1 63.5 63.5 63.5 63.5 68.2 52.3 59.6 59.6 59.5 59.5 63.4 50.3 55.4 55.4 55.3 55.3 58.2 48.2
2000 75.0 60.0 53.4 66.2 38.7 72.9 24.5 55.8 51.1 61.8 35.8 68.2 22.4 51.5 49.0 57.1 34.3 63.3 20.3 46.9 46.7 52.1 32.2 58.0 16.9
80.0 62.0 62.0 66.7 50.2 73.4 35.3 58.4 58.4 62.3 48.1 68.6 33.6 54.5 54.5 57.6 46.0 63.6 30.5 50.3 50.3 52.6 43.7 58.3 29.6
85.0 65.8 65.8 67.2 61.8 73.8 46.5 62.1 62.1 62.8 59.8 69.1 44.7 58.1 58.1 58.1 57.5 64.1 42.6 53.8 53.8 53.8 53.8 58.7 40.5
90.0 69.6 69.6 69.6 69.6 74.1 58.0 65.8 65.8 65.8 65.8 69.3 56.1 61.7 61.7 61.7 61.7 64.5 54.2 57.3 57.3 57.3 57.3 59.1 52.0
2200 75.0 61.0 56.8 67.3 41.3 74.0 24.2 56.8 54.4 62.7 38.2 69.2 22.2 52.4 52.1 58.0 36.2 64.1 21.3 48.2 48.2 52.9 34.0 58.7 17.6
80.0 63.9 63.9 67.7 53.1 74.5 38.1 60.1 60.1 63.2 51.0 69.6 35.1 56.1 56.1 58.5 49.0 64.6 32.2 51.8 51.8 53.4 46.7 59.0 30.4
85.0 68.0 67.4 68.4 66.0 74.8 49.8 64.0 64.0 64.0 63.7 70.0 47.3 59.9 59.9 59.7 59.7 64.9 45.4 55.4 55.4 55.4 55.4 59.4 43.1
90.0 71.7 71.7 71.8 71.8 75.2 62.0 67.8 67.8 67.8 67.8 70.4 60.1 63.6 63.6 63.5 63.5 65.2 57.8 59.0 59.0 59.0 59.0 59.9 55.7
2400 75.0 62.0 60.1 68.1 42.2 74.9 24.2 57.8 57.6 63.5 40.0 70.0 22.2 53.7 53.7 58.7 38.0 64.9 20.6 49.3 49.3 53.5 35.7 59.3 17.7
80.0 65.6 65.6 68.6 56.1 75.2 39.4 61.7 61.7 64.0 54.1 70.5 36.4 57.6 57.6 59.2 51.9 65.3 34.4 53.1 53.1 54.0 49.5 59.7 32.2
85.0 69.6 69.6 69.6 69.5 75.7 51.8 65.7 65.7 65.6 65.6 70.9 50.1 61.4 61.4 61.4 61.4 65.7 47.9 56.8 56.8 56.8 56.8 60.1 45.8
90.0 73.6 73.6 73.5 73.5 76.2 65.7 69.6 69.6 69.5 69.5 71.2 63.6 65.2 65.2 65.2 65.2 66.1 61.5 60.5 60.5 60.5 60.5 60.7 59.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 29
Performance Data
(6 Tons Standard Efficiency)

Table 14. Gross Cooling Capacities 6 Tons Three Phase T/YSC072E3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1920 75 68.5 52.9 75.2 37.7 82.4 22.5 64.4 50.7 70.8 35.5 77.6 20.2 60.0 48.2 66.1 33.2 72.6 17.9 55.4 45.9 61.1 31.2 67.1 15.6
80 69.8 64.6 76.2 49.2 83.4 33.8 65.8 62.6 71.8 46.9 78.8 31.4 61.5 59.9 67.1 44.3 73.7 29.2 56.8 56.6 62.1 42.2 68.3 26.9
85 72.2 72.2 77.2 60.4 84.4 44.5 68.5 68.5 72.8 58.1 79.7 42.5 64.7 64.7 68.1 55.9 74.7 40.4 60.5 60.5 63.1 53.6 69.3 38.3
90 76.4 76.4 78.5 72.0 85.4 56.0 72.7 72.7 74.2 70.1 80.6 53.8 68.8 68.8 69.5 67.6 75.6 51.6 64.5 64.5 64.6 64.4 70.2 49.3
2160 75 70.3 56.6 77.0 39.5 84.2 22.3 66.1 54.3 72.4 37.4 79.2 20.1 61.7 52.1 67.6 35.1 74.0 18.0 56.8 49.6 62.4 32.3 68.3 15.4
80 71.9 69.7 78.1 51.9 85.3 35.1 67.7 66.9 73.5 49.8 80.4 32.4 63.3 63.3 68.7 47.7 75.3 30.5 59.0 59.0 63.5 45.4 69.7 28.3
85 75.3 75.3 79.2 65.1 90.8 55.7 71.5 71.5 74.7 62.9 85.5 54.0 67.4 67.4 69.9 60.6 80.0 51.8 63.0 63.0 64.8 58.4 74.0 48.9
90 79.8 79.8 80.9 78.2 87.4 59.9 75.8 75.8 76.4 75.5 82.5 57.7 71.7 71.7 71.8 71.7 77.3 55.9 67.2 67.2 67.1 67.1 71.8 53.5
2400 75 72.0 60.4 78.5 41.3 85.6 22.5 67.6 58.1 73.8 39.2 80.6 20.4 63.0 55.7 68.9 36.0 75.2 18.2 58.1 53.4 63.6 34.4 69.2 14.9
80 73.8 73.5 79.6 55.2 87.0 36.1 69.6 69.6 75.0 53.2 81.9 33.6 65.4 65.4 70.1 51.0 76.6 32.2 61.0 61.0 64.7 48.6 70.9 29.4
85 78.0 78.0 81.0 69.7 88.1 50.4 74.0 74.0 76.4 67.6 83.1 48.6 69.8 69.8 71.5 65.4 77.8 45.9 65.3 65.3 66.4 63.3 72.0 43.8
90 82.6 82.6 82.9 82.6 89.2 64.1 78.6 78.6 78.6 78.6 84.2 62.0 74.3 74.3 74.2 74.2 78.8 59.7 69.5 69.5 69.5 69.5 73.1 57.7
2640 75 73.4 64.0 79.8 42.1 86.9 22.5 68.9 61.7 75.0 40.0 81.6 19.9 64.3 59.4 70.0 37.6 76.1 18.0 59.3 56.9 64.6 35.8 70.0 15.1
80 75.6 75.6 81.1 58.6 88.3 37.8 71.6 71.6 76.3 56.4 83.3 35.9 67.3 67.3 71.2 54.2 77.7 32.9 62.7 62.7 65.8 51.9 71.8 30.8
85 80.4 80.4 82.7 74.5 89.6 52.9 76.3 76.3 77.9 72.3 84.4 50.4 71.9 71.9 73.0 70.1 79.0 48.9 67.1 67.1 67.6 66.8 73.1 46.3
90 85.2 85.2 85.2 85.2 90.7 68.2 81.0 81.0 80.9 80.9 85.6 66.1 76.5 76.5 76.4 76.4 80.1 64.0 71.6 71.6 71.5 71.5 74.3 61.9
2880 75 74.6 67.7 81.0 44.7 88.0 22.9 70.1 65.4 76.1 42.1 82.5 20.0 65.4 62.8 70.9 40.0 76.8 18.0 60.3 59.5 65.4 37.5 70.6 14.1
80 77.6 77.6 82.3 61.9 89.5 39.3 73.4 73.4 77.4 59.7 84.2 37.7 69.0 69.0 72.3 57.5 78.7 34.2 64.3 64.3 66.8 55.2 72.8 32.7
85 82.5 82.5 84.1 79.1 90.8 55.7 78.2 78.2 79.3 76.7 85.5 54.0 73.7 73.7 74.2 73.3 80.0 51.8 68.8 68.8 68.9 68.8 74.0 48.9
90 87.5 87.5 87.4 87.4 92.1 72.4 83.1 83.1 83.1 83.1 86.8 70.3 78.4 78.4 78.4 78.4 81.3 68.3 73.3 73.3 73.3 73.3 75.4 66.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

30 RT-PRC023-EN
Performance Data
(7½ Tons Standard Efficiency)

Table 15. Gross Cooling Capacities 7½ Tons Three Phase T/YSC092E3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
2400 75 86.8 68.4 95.5 50.1 104.8 31.2 81.3 65.4 89.5 47.1 98.4 28.5 75.5 62.3 83.3 44.2 91.7 25.8 69.4 59.1 76.8 41.2 84.7 23.0
80 88.1 83.1 96.2 64.0 105.6 45.3 82.6 80.0 90.2 60.9 99.2 42.7 77.1 76.1 84.0 57.9 92.5 39.7 71.5 71.4 77.4 54.8 85.4 36.8
85 91.5 91.5 96.9 77.7 106.1 58.8 86.6 86.6 91.0 74.8 99.7 56.1 81.5 81.5 84.8 71.8 93.0 53.1 76.0 76.0 78.2 68.9 85.9 50.2
90 96.4 96.4 98.0 92.3 106.7 72.5 91.4 91.4 92.3 89.3 100.3 69.6 86.2 86.2 86.4 85.4 93.5 66.7 80.5 80.5 80.4 80.4 86.4 63.7
2700 75 89.0 73.2 97.6 52.6 107.0 31.5 83.4 70.2 91.5 49.6 100.4 28.9 77.4 67.1 85.1 46.4 93.5 26.2 71.2 64.3 78.4 43.4 86.3 23.2
80 90.6 88.9 98.4 68.0 107.8 47.4 85.3 84.9 92.3 65.0 101.2 44.3 79.8 79.8 85.8 62.0 94.2 41.8 74.2 74.2 79.0 58.9 87.0 38.5
85 95.3 95.3 99.3 83.6 113.3 73.0 90.2 90.2 93.2 80.8 106.2 70.2 84.8 84.8 86.8 78.1 98.7 67.3 79.0 79.0 80.2 75.3 90.9 64.4
90 100.5 100.5 100.9 99.1 109.0 77.6 95.2 95.2 95.4 95.1 102.4 74.7 89.6 89.6 89.6 89.6 95.4 71.9 83.6 83.6 83.6 83.6 88.0 68.8
3000 75 90.9 78.0 99.5 54.7 108.9 31.7 85.1 75.1 93.2 52.1 102.1 29.0 79.1 72.2 86.6 48.8 95.1 26.5 72.8 69.1 79.7 45.9 87.6 23.4
80 93.3 93.2 100.2 72.0 109.6 49.0 88.0 88.0 94.0 69.1 102.9 46.5 82.5 82.5 87.4 66.1 95.8 43.4 76.7 76.7 80.5 63.1 88.3 41.0
85 98.6 98.6 101.3 89.8 110.3 67.0 93.2 93.2 95.1 87.1 103.4 62.8 87.6 87.6 88.7 84.2 96.3 60.1 81.5 81.5 81.9 80.3 88.8 57.2
90 104.0 104.0 104.0 103.9 110.9 82.8 98.5 98.5 98.4 98.4 104.1 80.0 92.6 92.6 92.6 92.6 97.0 77.1 86.4 86.4 86.3 86.3 89.4 74.3
3300 75 92.6 82.8 101.0 57.7 110.4 32.2 86.8 80.1 94.6 54.3 103.5 29.5 80.6 77.0 87.8 51.3 96.3 26.9 74.1 72.8 80.7 48.2 88.6 23.5
80 95.8 95.8 101.9 76.2 111.3 51.0 90.5 90.5 95.4 73.1 104.3 48.1 84.8 84.8 88.7 70.3 97.0 44.8 78.7 78.7 81.6 67.3 89.4 42.3
85 101.4 101.4 103.2 96.1 111.9 69.5 95.9 95.9 97.0 93.1 104.9 66.6 90.0 90.0 90.4 89.0 97.6 63.7 83.7 83.7 83.8 83.8 89.9 60.7
90 107.0 107.0 106.9 106.9 112.6 88.2 101.3 101.3 101.2 101.2 105.6 85.4 95.2 95.2 95.1 95.1 98.4 82.6 88.7 88.7 88.6 88.6 90.7 80.2
3600 75 94.2 87.9 102.3 59.7 111.8 32.6 88.2 84.6 95.8 56.8 104.8 30.1 81.9 80.5 88.9 53.8 97.3 27.4 75.5 75.4 81.7 50.6 89.5 23.6
80 98.2 98.2 103.3 80.4 112.7 53.0 92.7 92.7 96.7 77.5 105.5 50.0 86.8 86.8 89.9 74.6 98.1 47.1 80.6 80.6 82.7 71.8 90.3 44.6
85 104.0 104.0 104.9 101.6 113.3 73.0 98.2 98.2 98.6 97.4 106.2 70.2 92.2 92.2 92.2 92.1 98.7 67.3 85.7 85.7 85.6 85.6 90.9 64.4
90 109.7 109.7 109.6 109.6 114.1 93.6 103.8 103.8 103.7 103.7 107.0 91.0 97.5 97.5 97.4 97.4 99.7 88.6 90.7 90.7 90.7 90.7 92.0 86.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer
to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 31
Performance Data
(8½ Tons Standard Efficiency)

Table 16. Gross Cooling Capacities 8½ Tons Three Phase T/YSC102E3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
2720 75 93.9 74.9 103.6 55.0 113.9 34.3 88.1 71.6 97.4 52.1 107.2 33.2 82.1 68.2 91.0 49.0 100.4 28.2 75.8 64.8 84.2 45.4 93.0 25.4
80 94.8 90.5 104.2 70.3 114.7 50.3 89.2 87.2 98.0 67.2 108.1 47.3 83.6 83.0 91.6 63.9 101.1 43.8 77.8 77.8 84.9 60.5 93.9 40.9
85 99.1 99.1 104.8 85.6 115.2 65.1 94.0 94.0 98.7 82.4 108.6 62.1 88.6 88.6 92.3 79.1 101.8 59.0 82.9 82.9 85.5 75.6 94.4 55.7
90 104.5 104.5 105.7 100.9 115.7 80.2 99.3 99.3 99.8 97.7 109.1 77.1 93.8 93.8 93.9 93.4 102.2 74.0 88.0 88.0 87.9 87.9 94.9 70.9
3060 75 96.2 80.3 105.9 58.0 116.2 35.2 90.3 77.1 99.6 54.8 109.3 32.1 84.1 73.6 92.9 51.8 102.2 28.5 77.6 70.2 85.9 48.2 94.7 24.9
80 97.7 97.1 106.6 75.0 117.1 52.6 92.5 92.5 100.2 71.9 110.3 49.5 86.8 86.8 93.6 68.6 103.0 46.5 81.1 81.1 86.7 65.3 95.6 43.0
85 103.4 103.4 107.3 92.2 122.8 81.7 97.8 97.8 101.0 89.0 115.6 79.3 92.5 92.5 94.4 85.7 108.0 75.6 86.4 86.4 87.6 82.6 100.1 72.6
90 109.1 109.1 109.1 108.6 118.1 86.3 103.5 103.5 103.4 103.4 111.4 83.2 97.8 97.8 97.7 97.7 104.3 80.1 91.7 91.7 91.4 91.4 96.8 76.9
3400 75 98.2 85.5 107.8 61.0 118.0 35.5 92.1 82.3 101.4 57.8 110.9 30.3 85.8 79.0 94.5 55.6 103.7 29.0 78.7 75.3 87.4 50.8 95.9 24.2
80 101.1 101.1 108.6 79.9 119.1 55.9 95.6 95.6 102.1 76.7 112.1 52.4 89.9 89.9 95.3 73.3 104.7 48.6 83.8 83.8 88.2 70.1 97.1 45.4
85 107.1 107.1 109.4 98.7 119.6 73.3 101.4 101.4 103.1 95.7 112.7 70.9 95.5 95.5 96.4 92.6 105.4 67.5 89.4 89.4 89.6 88.4 97.7 64.1
90 112.9 112.9 112.8 112.8 120.2 92.2 107.3 107.3 107.2 107.2 113.3 89.3 101.2 101.2 101.2 101.2 106.0 86.1 94.7 94.7 94.8 94.8 98.4 82.8
3740 75 99.9 90.9 109.5 64.0 119.6 35.5 93.8 87.7 102.8 60.6 112.3 31.2 87.4 84.3 95.8 57.2 104.8 27.7 80.9 79.9 88.5 53.8 96.9 24.9
80 104.0 104.0 110.3 84.6 120.5 57.0 98.3 98.3 103.6 81.3 113.5 54.3 92.5 92.5 96.7 77.9 106.2 50.5 86.3 86.3 89.5 74.7 98.3 47.3
85 110.1 110.1 111.4 105.7 121.3 77.8 104.3 104.3 104.9 102.2 114.2 74.6 98.3 98.3 98.5 97.9 106.8 71.7 92.0 92.0 91.9 91.9 99.0 68.3
90 116.3 116.3 116.3 116.3 122.0 98.4 110.4 110.4 110.3 110.3 114.9 95.2 103.9 103.9 104.1 104.1 107.5 92.1 97.6 97.6 97.5 97.5 99.8 88.9
4080 75 101.4 96.3 110.8 65.2 120.8 34.1 95.3 92.8 104.0 63.2 113.3 33.1 88.9 88.3 96.9 60.2 105.8 30.2 82.5 82.5 89.6 56.3 97.6 26.0
80 106.5 106.5 111.8 89.3 122.1 59.4 100.7 100.7 105.0 86.0 114.8 56.3 94.7 94.7 98.0 82.6 107.2 53.2 88.4 88.4 90.7 79.5 99.3 49.6
85 112.9 112.9 113.3 111.7 122.8 81.7 107.0 107.0 107.2 107.1 115.6 79.3 100.8 100.8 100.7 100.7 108.0 75.6 94.2 94.2 94.0 94.0 100.1 72.6
90 119.3 119.3 119.4 119.4 123.6 104.3 113.2 113.2 113.1 113.1 116.3 101.2 106.8 106.8 106.7 106.7 108.9 98.3 100.0 100.0 99.9 99.9 101.2 95.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

32 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)

Table 17. Gross Cooling Capacities 10 Tons Three Phase T/YSC120E3,4,W


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
3200 75 109.5 90.4 120.7 66.7 132.6 42.6 102.9 87.0 113.5 63.3 124.9 39.5 95.8 83.3 105.9 59.9 116.7 36.2 88.3 79.6 97.8 55.8 108.0 32.7
80 111.2 107.1 121.0 84.7 133.0 60.9 105.1 102.3 113.9 81.7 125.2 57.6 98.5 97.1 106.3 77.8 117.0 54.0 91.6 91.5 98.2 74.2 108.2 50.5
85 115.9 115.9 121.5 103.0 133.2 78.9 110.1 110.1 114.3 99.6 125.5 75.5 103.8 103.8 106.8 96.2 117.3 72.0 97.1 97.1 98.8 92.6 108.5 68.4
90 122.1 122.1 123.3 118.8 133.4 96.4 116.0 116.0 116.8 113.9 125.7 93.3 109.5 109.5 109.8 108.5 117.5 89.9 102.6 102.6 102.4 102.4 108.7 86.3
3600 75 111.9 96.8 123.1 70.8 135.1 43.3 105.1 93.4 115.7 66.7 127.0 39.9 97.9 89.7 107.9 63.3 118.7 36.8 90.3 85.5 99.5 59.4 109.7 33.1
80 114.8 112.7 123.5 90.4 135.3 63.2 108.4 107.6 116.1 86.9 127.4 59.8 101.7 101.7 108.3 83.5 118.9 56.8 94.8 94.8 99.9 79.8 110.0 53.3
85 120.5 120.5 124.1 111.0 140.9 98.6 114.3 114.3 116.8 107.7 132.4 95.2 107.7 107.7 109.3 103.4 123.4 91.9 100.6 100.6 101.5 97.7 113.9 88.1
90 126.9 126.9 127.3 125.2 135.9 103.8 120.4 120.4 120.6 120.1 127.9 100.4 113.7 113.7 113.5 113.5 119.5 97.1 106.3 106.3 106.2 106.2 110.5 93.6
4000 75 114.1 103.3 125.1 73.7 137.0 43.8 107.1 99.8 117.5 70.1 128.9 40.8 100.0 95.0 109.5 66.4 120.3 37.3 92.6 89.3 101.0 62.7 111.0 33.8
80 118.0 117.8 125.5 96.1 137.4 65.9 111.6 111.6 118.0 92.7 129.2 63.0 104.9 104.9 110.0 89.2 120.6 59.5 97.7 97.7 101.5 85.4 111.4 56.1
85 124.4 124.4 126.3 118.8 137.8 88.8 118.0 118.0 119.4 113.7 129.6 85.4 111.1 111.1 111.9 108.2 120.9 82.1 103.7 103.7 104.0 102.3 111.7 78.4
90 131.0 131.0 130.8 130.8 138.0 111.0 124.3 124.3 124.2 124.2 129.8 107.6 117.2 117.2 117.2 117.2 121.2 104.4 109.5 109.5 109.4 109.4 112.0 101.1
4400 75 116.1 109.4 126.8 76.9 138.7 44.6 109.2 104.2 119.0 73.9 130.4 41.2 102.0 98.7 110.8 69.7 121.5 37.5 94.5 93.0 102.2 66.1 112.2 33.8
80 121.0 121.0 127.3 101.7 139.1 68.9 114.6 114.6 119.6 98.3 130.8 65.6 107.6 107.6 111.4 94.7 121.9 62.2 100.2 100.2 102.8 91.2 112.6 58.8
85 127.8 127.8 129.1 123.7 139.4 94.6 121.1 121.1 121.9 118.5 131.1 90.2 113.9 113.9 114.3 112.7 122.2 86.9 106.3 106.3 106.3 106.2 112.9 83.2
90 134.5 134.5 134.4 134.4 139.5 118.2 127.7 127.7 127.5 127.5 131.4 115.0 120.3 120.3 120.2 120.2 122.7 111.8 112.4 112.4 112.2 112.2 113.6 107.2
4800 75 118.0 113.1 128.2 80.3 140.2 45.2 111.5 108.0 120.3 77.0 131.7 42.2 103.9 102.3 112.0 73.1 122.6 38.6 96.3 96.0 103.2 69.4 113.1 34.7
80 123.9 123.9 128.8 107.4 140.5 71.7 117.1 117.1 121.0 104.0 132.0 68.4 110.0 110.0 112.7 100.5 123.1 65.0 102.4 102.4 104.0 96.9 113.6 61.5
85 130.8 130.8 131.6 128.4 140.9 98.6 123.9 123.9 124.2 122.8 132.4 95.2 116.5 116.5 116.5 116.5 123.4 91.9 108.6 108.6 108.5 108.5 113.9 88.1
90 137.6 137.6 137.5 137.5 141.2 128.3 130.6 130.6 130.4 130.4 133.1 122.5 123.1 123.1 122.8 122.8 124.4 117.4 114.7 114.7 114.6 114.6 115.5 111.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 33
Performance Data
(3 Tons Standard Efficiency)

Table 18. Gross Cooling Capacities 3 Tons Single Phase WSC036E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75.0 35.7 28.7 39.4 20.8 43.3 12.2 32.9 27.1 36.4 19.2 40.1 10.9 30.0 25.5 33.2 17.7 36.8 9.3 27.0 24.1 29.9 16.1 33.3 7.8
80.0 36.7 35.8 39.9 27.0 43.9 19.0 34.0 34.0 36.9 25.5 40.7 17.6 31.4 31.4 33.8 23.9 37.3 16.1 28.6 28.6 30.5 22.3 33.8 14.6
85.0 38.9 38.9 40.5 33.1 44.3 25.1 36.3 36.3 37.5 31.6 41.1 23.6 33.7 33.7 34.4 30.1 37.7 22.1 30.8 30.8 31.3 28.9 34.2 20.5
90.0 41.3 41.3 41.6 40.4 44.9 31.3 38.7 38.7 38.7 38.6 41.7 29.7 36.0 36.0 36.0 36.0 38.3 28.1 33.1 33.1 33.1 33.1 34.7 26.3
1200 75.0 36.5 30.6 40.2 21.9 44.1 12.5 33.7 29.0 37.0 20.2 40.8 11.0 30.8 27.7 33.8 18.5 37.4 9.5 27.7 26.3 30.5 16.9 33.8 8.0
80.0 37.8 37.8 40.8 28.7 44.6 19.9 35.3 35.3 37.6 27.1 41.4 18.5 32.6 32.6 34.5 25.4 37.9 17.0 29.7 29.7 31.1 23.7 34.3 15.3
85.0 40.4 40.4 41.5 35.5 45.1 26.5 37.7 37.7 38.4 34.2 41.9 25.0 35.0 35.0 35.3 33.0 38.4 23.4 32.0 32.0 32.1 31.7 34.8 22.1
90.0 42.9 42.9 42.9 42.9 45.8 33.1 40.2 40.2 40.1 40.1 42.4 31.5 37.3 37.3 37.3 37.3 39.0 29.9 34.3 34.3 34.3 34.3 35.4 28.5
1320 75.0 37.3 32.5 40.8 22.7 44.7 12.6 34.4 31.2 37.6 21.0 41.4 11.0 31.5 29.9 34.4 19.5 37.9 9.8 28.4 28.3 30.9 18.0 34.2 8.1
80.0 39.1 39.1 41.4 30.2 45.3 20.7 36.4 36.4 38.2 28.5 41.9 19.3 33.6 33.6 35.0 27.0 38.4 17.7 30.7 30.7 31.6 25.4 34.7 15.8
85.0 41.7 41.7 42.3 38.2 45.9 27.9 38.9 38.9 39.3 37.0 42.5 26.3 36.0 36.0 36.2 35.7 39.0 24.8 33.0 33.0 33.0 33.0 35.3 23.3
90.0 44.3 44.3 44.3 44.3 46.5 35.0 41.5 41.5 41.4 41.4 43.2 33.5 38.5 38.5 38.5 38.5 39.7 32.1 35.3 35.3 35.3 35.3 36.1 30.9
1440 75.0 38.0 34.7 41.3 23.6 45.2 12.8 35.1 33.4 38.1 22.0 41.9 11.4 32.1 31.8 34.8 20.6 38.3 9.8 29.0 29.0 31.3 18.9 34.6 8.1
80.0 40.1 40.1 42.0 31.7 45.9 21.6 37.4 37.4 38.9 30.2 42.4 20.0 34.5 34.5 35.5 28.7 38.8 18.1 31.4 31.4 32.1 27.3 35.1 16.5
85.0 42.8 42.8 43.2 41.0 46.5 29.1 40.0 40.0 40.0 39.6 43.1 27.8 37.0 37.0 37.0 37.0 39.5 26.2 33.9 33.9 33.8 33.8 35.7 24.5
90.0 45.5 45.5 45.5 45.5 47.2 37.1 42.6 42.6 42.6 42.6 43.8 35.7 39.5 39.5 39.5 39.5 40.3 34.6 36.3 36.3 36.2 36.2 36.7 33.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 19. Gross Cooling Capacities 3 Tons Three Phase WSC036E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75.0 36.1 28.9 39.8 21.0 43.6 12.3 33.3 27.4 36.8 19.2 40.4 10.7 30.4 25.8 33.6 17.9 37.1 9.1 27.3 24.4 30.4 16.3 33.6 7.6
80.0 36.9 35.9 40.2 27.0 44.2 19.2 34.2 34.1 37.3 25.5 41.0 17.6 31.6 31.6 34.1 23.9 37.6 15.8 28.8 28.8 30.7 22.3 34.0 14.3
85.0 38.9 38.9 40.7 33.3 44.6 25.0 36.4 36.4 37.8 31.8 41.4 23.8 33.8 33.8 34.6 30.3 38.0 22.2 31.0 31.0 31.4 29.1 34.4 20.3
90.0 41.3 41.3 41.6 40.5 45.1 31.1 38.7 38.7 38.8 38.6 41.9 29.7 36.0 36.0 36.0 36.0 38.4 28.0 33.1 33.1 33.1 33.1 34.8 26.4
1200 75.0 36.9 30.9 40.6 21.8 44.4 12.4 34.1 29.4 37.5 20.3 41.2 10.8 31.1 28.0 34.3 18.8 37.7 9.3 28.0 26.6 30.9 17.1 34.1 7.8
80.0 38.0 37.9 41.1 28.7 45.0 19.7 35.4 35.4 38.0 27.3 41.7 18.3 32.7 32.7 34.7 25.6 38.2 16.8 29.9 29.9 31.4 24.0 34.6 15.0
85.0 40.4 40.4 41.7 35.7 45.5 26.8 37.8 37.8 38.7 34.5 42.1 24.9 35.0 35.0 35.5 33.2 38.6 23.4 32.1 32.1 32.2 31.8 35.0 21.7
90.0 42.9 42.9 42.9 42.9 46.0 33.3 40.3 40.3 40.2 40.2 42.6 31.7 37.3 37.3 37.3 37.3 39.1 30.1 34.3 34.3 34.3 34.3 35.5 28.5
1320 75.0 37.6 32.9 41.3 22.9 45.1 12.5 34.8 31.6 38.1 21.3 41.8 11.0 31.7 30.1 34.8 19.7 38.2 9.4 28.7 28.3 31.4 18.0 34.6 8.0
80.0 39.2 39.2 41.9 30.4 45.7 20.8 36.6 36.6 38.7 28.9 42.3 19.2 33.7 33.7 35.4 27.2 38.7 17.4 30.8 30.8 31.9 25.7 35.0 15.8
85.0 41.8 41.8 42.5 38.5 46.2 27.9 39.0 39.0 39.4 37.2 42.8 26.4 36.1 36.1 36.3 35.8 39.2 24.8 33.1 33.1 33.1 33.0 35.5 23.2
90.0 44.4 44.4 44.3 44.3 46.7 35.2 41.5 41.5 41.5 41.5 43.3 33.7 38.5 38.5 38.5 38.5 39.8 32.3 35.3 35.3 35.3 35.3 36.1 31.1
1440 75.0 38.4 35.1 41.9 23.9 45.7 12.7 35.4 33.7 38.6 22.3 42.3 11.2 32.4 31.9 35.2 20.6 38.7 9.3 29.3 29.2 31.8 19.0 34.9 7.9
80.0 40.3 40.3 42.5 32.1 46.3 21.6 37.6 37.6 39.2 30.4 42.8 20.0 34.6 34.6 35.8 29.0 39.1 18.3 31.6 31.6 32.4 27.6 35.4 16.5
85.0 42.9 42.9 43.3 41.2 46.9 29.3 40.1 40.1 40.3 39.7 43.3 27.8 37.1 37.1 37.1 37.0 39.7 26.4 33.9 33.9 33.9 33.9 35.9 24.6
90.0 45.6 45.6 45.5 45.5 47.5 37.3 42.6 42.6 42.6 42.6 44.0 35.9 39.5 39.5 39.5 39.5 40.4 34.9 36.2 36.2 36.2 36.2 36.6 33.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

34 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)

Table 20. Gross Cooling Capacities 4 Tons Single Phase WSC048E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 46.3 39.0 51.1 28.2 56.2 16.8 43.0 37.1 47.6 26.3 52.4 14.6 39.5 35.1 43.8 24.7 48.4 13.0 35.8 33.0 39.8 22.8 44.3 12.2
80.0 47.1 45.9 51.6 36.7 56.8 25.8 44.0 43.5 48.1 34.8 53.0 24.1 40.7 40.7 44.3 33.0 49.0 22.3 37.5 37.5 40.3 31.2 44.7 20.5
85.0 49.6 49.6 52.2 45.0 57.3 34.3 46.7 46.7 48.7 43.2 53.4 32.1 43.6 43.6 44.9 41.3 49.4 30.7 40.2 40.2 41.0 39.0 45.1 28.8
90.0 52.7 52.7 53.2 51.9 57.8 42.4 49.7 49.7 49.8 49.4 54.0 40.6 46.5 46.5 46.4 46.4 49.8 38.9 43.0 43.0 43.0 43.0 45.5 37.1
1600 75.0 47.3 41.6 52.1 29.5 57.3 17.3 43.9 39.6 48.5 27.9 53.3 14.9 40.4 37.4 44.6 26.1 49.2 12.1 36.6 34.8 40.5 24.1 44.9 13.4
80.0 48.5 48.2 52.7 39.0 57.9 26.9 45.3 45.3 49.0 37.2 53.9 25.2 42.2 42.2 45.2 35.3 49.8 23.4 38.8 38.8 41.1 33.5 45.4 21.7
85.0 51.5 51.5 53.3 48.2 58.3 36.2 48.4 48.4 49.8 46.2 54.4 34.4 45.2 45.2 46.0 43.8 50.3 32.7 41.7 41.7 42.1 41.0 45.8 30.9
90.0 54.7 54.7 54.8 54.6 58.9 45.4 51.5 51.5 51.5 51.5 54.9 43.6 48.2 48.2 48.2 48.2 50.7 41.8 44.6 44.6 44.6 44.6 46.3 40.1
1760 75.0 48.2 43.8 53.0 31.0 58.1 17.0 44.8 41.7 49.2 29.3 54.2 16.4 41.1 39.2 45.3 27.5 50.0 14.1 37.4 36.4 41.1 25.6 45.5 12.6
80.0 49.9 49.9 53.6 41.4 58.7 28.0 46.8 46.8 49.9 39.6 54.7 26.3 43.5 43.5 45.9 37.7 50.5 24.7 40.0 40.0 41.7 35.8 46.0 22.9
85.0 53.2 53.2 54.4 50.9 59.2 38.1 50.0 50.0 50.8 48.5 55.2 36.5 46.6 46.6 47.0 45.7 50.9 34.8 42.9 42.9 43.0 42.8 46.4 33.0
90.0 56.4 56.4 56.4 56.4 59.8 48.4 53.2 53.2 53.1 53.1 55.7 46.5 49.6 49.6 49.6 49.6 51.5 44.9 45.9 45.9 45.9 45.9 47.1 42.8
1920 75.0 49.0 45.9 53.7 32.6 58.9 18.0 45.6 43.4 49.9 30.8 54.8 16.3 41.9 40.7 45.8 28.9 50.5 14.6 38.1 37.8 41.6 27.1 46.0 12.8
80.0 51.2 51.2 54.4 43.6 59.5 29.1 48.0 48.0 50.5 41.9 55.4 27.4 44.6 44.6 46.5 39.9 51.0 25.9 41.0 41.0 42.3 37.8 46.5 23.9
85.0 54.6 54.6 55.4 53.1 60.0 40.2 51.3 51.3 51.7 50.4 55.9 38.6 47.8 47.8 47.9 47.6 51.5 36.9 44.1 44.1 44.0 44.0 47.0 35.0
90.0 58.0 58.0 58.0 58.0 60.6 51.3 54.6 54.6 54.5 54.5 56.6 49.5 51.0 51.0 50.9 50.9 52.2 47.4 47.1 47.1 47.1 47.1 47.8 44.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 21. Gross Cooling Capacities 4 Tons Three Phase WSC048E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75.0 47.2 39.3 52.1 28.6 57.4 17.1 43.8 37.4 48.6 26.7 53.6 15.3 40.3 35.5 44.8 24.9 49.6 13.9 36.6 33.5 40.8 23.0 45.4 12.1
80.0 48.1 46.7 52.7 37.0 57.9 25.7 44.8 44.2 49.1 35.2 54.2 24.1 41.5 41.5 45.3 33.4 50.1 22.3 38.3 38.3 41.3 31.4 45.9 20.6
85.0 50.6 50.6 53.3 45.5 58.5 34.0 47.6 47.6 49.7 43.6 54.7 32.5 44.4 44.4 45.9 41.8 50.7 30.7 41.1 41.1 42.0 39.6 46.4 29.0
90.0 53.7 53.7 54.3 52.7 59.0 42.4 50.6 50.6 50.9 50.2 55.2 41.0 47.4 47.4 47.4 47.4 51.2 39.3 44.0 44.0 44.0 44.0 46.9 37.4
1600 75.0 48.3 42.0 53.2 29.9 58.5 18.1 44.8 40.0 49.5 28.2 54.6 16.3 41.2 37.9 45.6 26.1 50.5 14.7 37.4 35.5 41.5 24.4 46.1 12.9
80.0 49.5 49.0 53.8 39.4 59.0 26.3 46.2 46.2 50.1 37.6 55.1 24.4 43.0 43.0 46.3 35.8 51.1 23.6 39.7 39.7 42.1 33.8 46.7 21.6
85.0 52.5 52.5 54.5 48.8 59.6 36.1 49.4 49.4 50.8 46.8 55.7 34.5 46.1 46.1 47.0 44.5 51.6 32.8 42.7 42.7 43.1 41.7 47.2 31.1
90.0 55.8 55.8 55.8 55.4 60.2 45.6 52.5 52.5 52.5 52.5 56.2 44.0 49.2 49.2 49.2 49.2 52.0 42.2 45.7 45.7 45.6 45.6 47.7 40.4
1760 75.0 49.3 44.5 54.1 31.1 59.4 19.0 45.7 42.3 50.3 29.6 55.4 16.5 42.0 39.9 46.3 27.5 51.2 14.5 38.3 37.1 42.2 25.9 46.8 13.0
80.0 50.8 50.8 54.7 41.8 60.0 28.4 47.7 47.7 51.0 39.9 55.9 26.5 44.4 44.4 47.0 38.0 51.8 24.5 40.9 40.9 42.8 36.1 47.3 22.8
85.0 54.2 54.2 55.5 51.7 60.5 38.3 51.0 51.0 51.9 49.3 56.5 36.7 47.6 47.6 48.0 46.5 52.4 35.0 44.0 44.0 44.1 43.7 47.9 33.0
90.0 57.6 57.6 57.5 57.5 61.2 48.7 54.2 54.2 54.2 54.2 57.1 46.9 50.8 50.8 50.8 50.8 52.9 45.3 47.1 47.1 47.1 47.1 48.6 43.5
1920 75.0 50.1 46.6 54.9 32.7 60.2 19.3 46.5 44.2 51.0 31.0 56.1 18.2 42.8 41.4 46.9 29.0 51.9 14.7 39.1 38.6 42.7 27.2 47.3 13.0
80.0 52.2 52.2 55.5 44.1 60.8 29.6 49.0 49.0 51.7 42.3 56.6 27.4 45.6 45.6 47.6 40.3 52.4 25.6 42.0 42.0 43.4 38.4 47.9 24.0
85.0 55.7 55.7 56.5 53.9 61.3 40.3 52.4 52.4 52.8 51.2 57.2 38.9 48.9 48.9 49.1 48.5 53.0 37.1 45.2 45.2 45.2 45.2 48.4 35.3
90.0 59.2 59.2 59.1 59.1 62.0 51.7 55.7 55.7 55.7 55.7 58.0 50.0 52.2 52.2 52.1 52.1 53.7 48.1 48.4 48.4 48.4 48.4 49.3 45.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 35
Performance Data
(5 Tons Standard Efficiency)

Table 22. Gross Cooling Capacities 5 Tons Single Phase WSC060E1 — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 55.3 46.9 60.3 32.1 65.7 17.3 51.5 44.9 56.2 30.5 61.3 15.7 47.4 42.9 51.8 27.8 56.7 13.8 43.2 40.5 47.2 26.2 51.7 12.1
80.0 57.1 56.3 61.3 43.1 67.0 29.4 53.4 53.2 57.2 41.1 62.4 26.7 49.6 49.6 52.8 39.3 57.7 24.8 45.8 45.8 48.2 37.2 52.7 22.8
85.0 60.4 60.4 62.6 54.5 67.9 39.5 56.8 56.8 58.4 52.5 63.4 37.3 53.0 53.0 54.1 50.3 58.6 35.4 49.0 49.0 49.6 47.6 53.6 33.8
90.0 64.1 64.1 64.5 63.6 69.0 50.1 60.4 60.4 60.5 60.3 64.4 48.3 56.6 56.6 56.5 56.5 59.6 46.4 52.4 52.4 52.4 52.4 54.5 44.5
2000 75.0 56.6 50.2 61.4 33.8 66.9 17.6 52.6 47.9 57.2 31.7 62.4 15.9 48.5 45.6 52.7 29.7 57.6 13.8 44.3 42.9 48.0 27.9 52.5 12.3
80.0 58.7 58.6 62.6 45.9 68.2 30.0 55.0 55.0 58.4 44.3 63.5 28.6 51.2 51.2 53.8 42.2 58.7 25.5 47.2 47.2 49.1 40.2 53.5 24.3
85.0 62.4 62.4 64.0 58.3 69.1 41.5 58.7 58.7 59.8 56.0 64.5 39.7 54.8 54.8 55.4 53.4 59.6 38.0 50.6 50.6 50.8 50.2 54.4 36.1
90.0 66.4 66.4 66.4 66.3 70.3 53.8 62.5 62.5 62.5 62.5 65.6 51.8 58.4 58.4 58.4 58.4 60.7 50.2 54.0 54.0 54.0 54.0 55.6 48.3
2200 75.0 57.7 53.0 62.4 35.5 67.9 17.9 53.7 50.7 58.0 33.5 63.3 15.1 49.5 47.9 53.5 31.3 58.4 14.2 45.2 44.7 48.6 29.2 53.2 12.6
80.0 60.2 60.2 63.6 48.9 69.2 31.2 56.5 56.5 59.3 47.0 64.5 29.4 52.6 52.6 54.7 45.0 59.4 27.1 48.4 48.4 49.9 43.1 54.1 25.3
85.0 64.3 64.3 65.3 61.6 70.1 44.5 60.4 60.4 61.0 59.0 65.5 42.1 56.4 56.4 56.6 55.9 60.5 40.5 51.9 51.9 52.0 51.9 55.2 38.7
90.0 68.3 68.3 68.3 68.3 71.4 57.2 64.3 64.3 64.3 64.3 66.7 55.7 60.1 60.1 60.0 60.0 61.8 53.9 55.5 55.5 55.5 55.5 56.5 51.7
2400 75.0 58.5 55.4 63.2 37.2 68.8 17.1 54.5 52.8 58.8 35.2 64.2 15.4 50.4 49.7 54.2 33.2 59.1 13.8 46.0 45.8 49.3 31.1 53.8 12.9
80.0 61.8 61.8 64.6 51.7 70.1 32.6 57.9 57.9 60.1 49.8 65.2 30.6 53.8 53.8 55.5 47.9 60.1 28.9 49.5 49.5 50.5 45.6 54.7 26.7
85.0 65.9 65.9 66.5 64.5 71.1 45.9 61.9 61.9 62.2 61.5 66.3 45.0 57.7 57.7 57.7 57.5 61.2 43.1 53.1 53.1 53.1 53.1 55.8 41.2
90.0 70.1 70.1 70.0 70.0 72.6 61.3 65.9 65.9 65.9 65.9 67.7 59.4 61.5 61.5 61.5 61.5 62.7 57.2 56.8 56.8 56.7 56.7 57.4 54.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 23. Gross Cooling Capacities 5 Tons Three Phase WSC060E3,4,W — Heat Pump
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75.0 59.6 49.6 66.0 35.9 72.6 21.9 55.6 47.4 61.6 34.4 68.0 20.0 51.5 45.3 57.1 31.8 63.2 18.0 47.1 43.2 52.2 29.6 58.0 16.1
80.0 61.1 61.0 66.5 46.6 73.5 33.7 57.5 57.5 62.2 44.4 68.9 31.7 53.8 53.8 57.7 42.3 63.9 29.1 49.9 49.9 52.8 40.1 58.7 27.5
85.0 64.9 64.9 67.3 57.1 73.9 43.3 61.3 61.3 63.0 55.0 69.2 41.3 57.5 57.5 58.6 53.1 64.3 39.3 53.4 53.4 53.9 51.7 59.1 37.2
90.0 68.9 68.9 69.0 68.9 74.7 53.8 65.2 65.2 65.1 65.1 69.9 51.7 61.3 61.3 61.2 61.2 65.1 49.6 57.0 57.0 57.0 57.0 59.9 47.2
2000 75.0 61.0 52.9 67.1 37.7 74.0 22.1 56.9 50.8 62.7 35.8 69.2 20.2 52.7 49.0 58.0 33.5 64.2 18.5 48.3 47.2 53.2 31.5 58.9 16.3
80.0 63.2 63.2 67.8 49.4 74.9 35.2 59.6 59.6 63.4 47.2 70.0 32.6 55.7 55.7 58.8 45.1 64.9 31.1 51.6 51.6 53.8 42.8 59.6 28.9
85.0 67.4 67.4 68.9 61.3 75.3 45.9 63.6 63.6 64.5 59.6 70.5 43.7 59.6 59.6 60.0 58.3 65.5 41.7 55.3 55.3 55.4 55.3 60.2 39.5
90.0 71.5 71.5 71.4 71.4 76.1 57.2 67.7 67.7 67.5 67.5 71.3 55.1 63.5 63.5 63.4 63.4 66.3 52.8 59.1 59.1 59.1 59.1 61.0 50.8
2200 75.0 62.2 56.4 68.3 39.6 75.1 22.4 58.1 54.6 63.7 37.2 70.3 20.5 53.8 52.8 58.9 35.1 65.1 18.5 49.4 49.4 53.9 33.2 59.7 16.2
80.0 65.2 65.2 69.0 52.1 75.9 36.8 61.4 61.4 64.4 49.9 71.0 33.9 57.4 57.4 59.7 47.8 65.8 31.8 53.1 53.1 54.7 45.7 60.4 29.7
85.0 69.5 69.5 70.3 66.1 76.5 48.3 65.6 65.6 66.1 64.8 71.5 46.0 61.4 61.4 61.4 61.4 66.5 44.1 57.0 57.0 56.9 56.9 61.0 41.9
90.0 73.8 73.8 73.8 73.8 77.4 60.7 69.8 69.8 69.7 69.7 72.5 58.6 65.5 65.5 65.4 65.4 67.4 56.7 60.9 60.9 60.9 60.9 62.1 54.9
2400 75.0 63.4 60.2 69.0 40.9 76.0 22.7 59.2 58.3 64.5 38.8 71.1 20.7 54.9 54.8 59.6 36.7 65.9 18.7 50.5 50.5 54.5 34.3 60.3 16.3
80.0 66.9 66.9 70.1 54.9 76.8 37.2 63.0 63.0 65.4 52.8 71.8 35.9 58.9 58.9 60.6 50.8 66.6 33.6 54.4 54.4 55.6 48.9 61.0 30.8
85.0 71.3 71.3 71.8 70.9 77.6 50.5 67.3 67.3 67.4 67.3 72.5 48.6 63.0 63.0 63.0 63.0 67.3 46.3 58.5 58.5 58.4 58.4 61.8 44.3
90.0 75.9 75.9 75.8 75.8 78.6 64.3 71.7 71.7 71.6 71.6 73.6 62.5 67.2 67.2 67.2 67.2 68.5 60.9 62.5 62.5 62.5 62.5 63.1 59.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

36 RT-PRC023-EN
Performance Data
(3 Tons High Efficiency)

Table 24. Gross Cooling Capacities 3 Tons Single Phase High Efficiency T/YHC036E1
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 35.98 29.32 39.78 21.77 43.79 13.23 33.67 28.00 37.32 20.42 41.12 11.60 31.24 26.70 34.66 18.96 38.27 10.50 28.69 25.46 31.92 17.50 35.30 9.16
80 36.75 36.14 40.21 27.81 44.32 18.70 34.62 34.55 37.70 26.35 41.66 19.19 32.42 32.42 35.09 24.88 38.87 17.42 30.12 30.12 32.30 23.39 35.87 16.22
85 38.97 38.97 40.68 33.98 44.77 26.20 36.89 36.89 38.20 32.60 42.07 24.89 34.66 34.66 35.59 31.36 39.20 23.34 32.31 32.31 32.84 30.14 36.22 21.81
90 41.37 41.37 41.55 40.89 45.12 32.03 39.22 39.22 39.19 39.15 42.48 30.69 36.92 36.92 36.88 36.88 39.58 29.15 34.47 34.47 34.45 34.45 36.59 27.68
1200 75 36.80 31.29 40.58 22.70 44.56 13.08 34.51 30.19 38.04 21.35 41.82 12.07 31.94 28.81 35.33 19.89 38.93 10.74 29.36 27.53 32.47 18.40 35.89 8.96
80 37.98 37.98 41.02 29.37 45.25 19.91 35.87 35.87 38.49 27.95 42.46 19.36 33.61 33.61 35.81 26.49 39.52 18.36 31.22 31.22 32.95 25.14 36.47 16.48
85 40.43 40.43 41.60 36.52 45.62 27.66 38.29 38.29 39.06 35.26 42.84 26.24 35.97 35.97 36.43 34.19 39.90 24.63 33.50 33.50 33.70 32.88 36.84 23.18
90 42.94 42.94 42.92 42.92 46.01 34.09 40.67 40.67 40.69 40.69 43.25 32.66 38.29 38.29 38.28 38.28 40.34 31.25 35.78 35.78 35.75 35.75 37.28 29.77
1320 75 37.56 33.62 41.24 23.67 45.25 13.35 35.13 32.23 38.65 21.93 42.41 12.25 32.61 30.88 35.92 20.85 39.47 10.65 30.02 29.35 32.97 19.05 36.36 9.31
80 39.19 39.19 41.74 30.99 45.98 22.46 37.00 37.00 39.13 29.55 43.09 20.28 34.66 34.66 36.38 28.25 40.09 19.09 32.18 32.18 33.47 26.95 36.96 17.31
85 41.76 41.76 42.39 39.18 46.35 29.03 39.52 39.52 39.89 38.00 43.49 27.42 37.10 37.10 37.20 36.47 40.52 25.74 34.54 34.54 34.55 34.52 37.37 24.62
90 44.30 44.30 44.29 44.29 46.76 36.00 42.01 42.01 41.98 41.98 43.93 34.80 39.55 39.55 39.51 39.51 40.99 33.52 36.90 36.90 36.87 36.87 37.87 32.39
1440 75 38.21 35.56 41.79 24.49 45.87 13.71 35.79 34.23 39.17 23.63 42.95 12.14 33.22 32.55 36.38 21.75 39.93 10.77 30.66 30.61 33.40 20.29 36.76 9.40
80 40.26 40.26 42.38 32.66 46.51 22.10 38.00 38.00 39.72 31.36 43.60 20.97 35.58 35.58 36.92 30.15 40.56 19.85 33.03 33.03 33.96 28.89 37.38 18.26
85 42.94 42.94 43.26 41.79 46.93 30.25 40.60 40.60 40.67 40.12 44.03 28.88 38.09 38.09 38.12 38.10 41.01 27.36 35.46 35.46 35.43 35.43 37.85 25.96
90 45.57 45.57 45.52 45.52 47.42 38.18 43.15 43.15 43.15 43.15 44.56 37.07 40.63 40.63 40.60 40.60 41.57 36.03 37.89 37.89 37.86 37.86 38.47 34.85
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 25. Gross Cooling Capacities 3 Tons Three Phase High Efficiency T/YHC036E,3,4
Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1080 75 36.04 29.24 39.93 21.85 44.03 13.31 33.56 27.96 37.25 19.68 41.15 11.98 30.96 26.64 34.44 18.63 38.07 10.45 28.08 25.17 31.38 17.36 34.83 9.03
80 36.85 36.25 40.36 27.79 44.56 18.86 34.54 34.48 37.71 26.33 41.72 19.22 32.17 32.17 34.87 24.79 38.71 17.22 29.66 29.66 31.82 23.19 35.43 15.97
85 39.07 39.07 40.89 34.02 45.02 26.27 36.85 36.85 38.21 32.58 42.13 24.91 34.48 34.48 35.39 31.27 39.05 23.28 31.91 31.91 32.40 30.00 35.81 21.66
90 41.51 41.51 41.71 40.92 45.41 32.17 39.24 39.24 39.24 39.18 42.52 30.76 36.78 36.78 36.75 36.75 39.44 29.08 34.14 34.14 34.11 34.11 36.18 27.54
1200 75 36.89 31.39 40.75 22.78 44.80 13.19 34.36 30.13 38.02 21.34 41.86 12.08 31.63 28.72 35.11 19.72 38.73 10.53 28.80 27.28 31.99 18.16 35.42 8.84
80 38.07 38.07 41.22 29.43 45.44 21.73 35.82 35.82 38.49 27.94 42.51 19.35 33.39 33.39 35.57 26.40 39.36 18.31 30.78 30.78 32.47 24.98 36.01 16.40
85 40.58 40.58 41.79 36.51 45.90 27.82 38.27 38.27 39.04 35.24 42.91 26.26 35.80 35.80 36.22 34.00 39.75 24.57 33.12 33.12 33.29 32.64 36.43 23.02
90 43.14 43.14 43.10 43.10 46.32 34.18 40.75 40.75 40.71 40.71 43.32 32.62 38.18 38.18 38.15 38.15 40.20 31.10 35.44 35.44 35.41 35.41 36.88 29.78
1320 75 37.67 33.65 41.43 23.65 45.47 13.24 35.04 32.16 38.64 21.93 42.46 12.26 32.35 30.88 35.69 20.75 39.29 10.60 29.47 29.03 32.47 18.66 35.91 9.51
80 39.27 39.27 41.95 31.06 46.28 22.55 36.96 36.96 39.15 29.59 43.13 20.50 34.44 34.44 36.18 28.17 39.93 19.03 31.75 31.75 32.98 26.77 36.51 17.18
85 41.94 41.94 42.64 39.23 46.63 29.16 39.54 39.54 39.90 38.01 43.54 27.46 36.94 36.94 37.05 36.38 40.35 26.01 34.17 34.17 34.16 34.15 36.98 24.18
90 44.51 44.51 44.50 44.50 47.07 36.09 42.08 42.08 42.02 42.02 44.03 34.82 39.42 39.42 39.40 39.40 40.86 33.49 36.56 36.56 36.53 36.53 37.46 32.20
1440 75 38.28 35.59 42.01 24.58 46.08 13.79 35.73 34.21 39.17 23.62 43.00 12.15 32.96 32.43 36.15 21.66 39.73 10.77 30.16 30.15 32.90 20.10 36.30 9.28
80 40.43 40.43 42.60 32.73 46.77 21.55 37.97 37.97 39.77 31.36 43.69 20.99 35.39 35.39 36.72 30.03 40.41 19.49 32.60 32.60 33.49 28.79 36.94 17.90
85 43.13 43.13 43.49 41.88 47.26 30.64 40.62 40.62 40.78 40.21 44.14 28.86 37.94 37.94 37.95 37.94 40.89 27.31 35.10 35.10 35.07 35.07 37.48 25.84
90 45.81 45.81 45.77 45.77 47.72 38.26 43.26 43.26 43.23 43.23 44.68 37.16 40.53 40.53 40.49 40.49 41.48 35.99 37.55 37.55 37.52 37.52 38.10 34.84
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 37
Performance Data
(4 Tons High Efficiency)

Table 26. Gross Cooling Capacities 4 Tons Three Phase T/YHC048E1


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75 45.95 38.53 50.74 26.84 55.90 16.12 42.93 36.94 47.50 26.09 52.40 14.52 39.78 35.43 44.04 23.93 48.77 13.50 36.31 33.67 40.35 22.51 44.77 11.36
80 46.89 46.79 51.26 35.91 56.52 24.30 44.12 44.12 48.00 34.31 53.00 22.82 41.26 41.26 44.52 32.74 49.25 21.85 38.23 38.23 40.82 31.03 45.32 19.94
85 49.73 49.73 51.82 44.43 56.96 32.82 47.00 47.00 48.58 42.98 53.46 31.57 44.09 44.09 45.12 41.45 49.74 30.00 40.97 40.97 41.47 39.94 45.70 28.44
90 52.73 52.73 52.79 52.72 57.39 41.60 49.94 49.94 49.88 49.88 53.86 39.86 46.92 46.92 46.88 46.88 50.10 38.35 43.68 43.68 43.63 43.63 46.13 36.84
1600 75 46.99 41.23 51.75 28.58 56.91 16.22 43.87 39.64 48.39 27.17 53.34 14.69 40.62 38.08 44.86 25.58 49.54 13.15 37.12 36.16 41.07 23.90 45.49 11.53
80 48.44 48.44 52.28 38.10 57.59 25.94 45.69 45.69 48.93 36.67 53.95 24.16 42.78 42.78 45.34 35.00 50.14 21.89 39.58 39.58 41.58 33.38 46.04 21.37
85 51.56 51.56 52.94 47.80 58.01 35.11 48.72 48.72 49.67 46.46 54.43 33.62 45.68 45.68 46.17 44.82 50.58 31.94 42.39 42.39 42.46 42.41 46.45 30.42
90 54.71 54.71 54.66 54.66 58.50 44.49 51.77 51.77 51.74 51.74 54.89 42.95 48.63 48.63 48.56 48.56 51.07 41.40 45.23 45.23 45.11 45.11 46.95 39.82
1760 75 47.91 43.99 52.59 29.89 57.79 16.41 44.76 42.38 49.17 28.47 54.13 14.85 41.39 40.38 45.52 26.95 50.25 13.33 37.88 37.84 41.68 25.29 46.11 12.02
80 49.96 49.96 53.17 40.50 58.39 25.91 47.09 47.09 49.71 38.94 54.76 24.43 44.03 44.03 46.08 37.35 50.86 23.65 40.75 40.75 42.22 35.78 46.68 22.01
85 53.16 53.16 54.00 51.28 58.92 37.01 50.23 50.23 50.64 49.53 55.23 35.54 47.07 47.07 47.12 47.07 51.32 34.02 43.69 43.69 43.63 43.63 47.05 32.37
90 56.43 56.43 56.39 56.39 59.42 47.53 53.38 53.38 53.35 53.35 55.81 45.95 50.17 50.17 50.06 50.06 51.81 44.40 46.61 46.61 46.49 46.49 47.64 43.06
1920 75 48.70 46.51 53.33 31.37 58.51 16.55 45.48 44.48 49.84 29.84 54.84 15.12 42.16 42.08 46.13 28.31 50.89 14.62 38.76 38.76 42.17 26.62 46.62 12.24
80 51.26 51.26 53.94 42.84 59.16 27.60 48.33 48.33 50.45 41.30 55.45 26.28 45.15 45.15 46.77 39.82 51.47 24.70 41.77 41.77 42.84 38.18 47.21 23.25
85 54.60 54.60 54.93 54.03 59.66 39.09 51.54 51.54 51.63 51.62 55.94 37.52 48.28 48.28 48.26 48.26 51.90 35.98 44.78 44.78 44.79 44.79 47.67 34.47
90 57.93 57.93 57.89 57.89 60.25 50.33 54.77 54.77 54.71 54.71 56.53 49.14 51.48 51.48 51.43 51.43 52.60 47.64 47.78 47.78 47.77 47.77 48.33 46.15
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 27. Gross Cooling Capacities 4 Tons Three Phase T/YHC048E,3,4


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1440 75 46.71 38.85 51.74 27.73 57.13 16.82 43.61 37.29 48.41 26.50 53.54 14.96 40.36 35.67 44.85 24.15 49.73 13.25 36.86 34.00 41.06 22.65 45.66 11.65
80 47.59 47.35 52.25 36.26 57.76 25.58 44.68 44.68 48.90 34.65 54.15 23.34 41.84 41.84 45.38 33.05 50.30 21.26 38.74 38.74 41.56 31.33 46.24 19.65
85 50.50 50.50 52.85 44.98 58.26 33.44 47.72 47.72 49.53 43.27 54.64 31.95 44.77 44.77 46.01 41.82 50.80 30.34 41.58 41.58 42.21 40.24 46.65 28.73
90 53.61 53.61 53.82 53.53 58.70 42.00 50.76 50.76 50.72 50.72 55.04 40.23 47.69 47.69 47.65 47.65 51.21 38.72 44.41 44.41 44.31 44.31 47.05 37.10
1600 75 47.84 41.58 52.84 29.51 58.21 16.60 44.65 39.99 49.39 27.30 54.53 15.03 41.27 38.28 45.75 25.88 50.63 13.43 37.73 36.56 41.84 24.10 46.44 11.79
80 49.16 49.16 53.35 38.56 58.84 25.31 46.38 46.38 49.93 37.02 55.15 24.29 43.39 43.39 46.28 35.48 51.23 23.64 40.16 40.16 42.37 33.65 47.02 21.84
85 52.42 52.42 54.04 48.25 59.40 35.49 49.49 49.49 50.64 46.68 55.66 33.77 46.44 46.44 47.07 45.28 51.69 32.28 43.08 43.08 43.26 43.03 47.46 30.66
90 55.66 55.66 55.61 55.61 59.87 44.75 52.69 52.69 52.64 52.64 56.14 43.17 49.48 49.48 49.44 49.44 52.18 41.70 46.01 46.01 45.97 45.97 47.92 39.96
1760 75 48.78 44.24 53.71 30.62 59.15 16.79 45.51 42.63 50.19 28.83 55.38 15.23 42.13 40.85 46.45 27.27 51.40 13.65 38.50 38.36 42.48 25.56 47.09 11.97
80 50.78 50.78 54.29 40.96 59.83 27.31 47.85 47.85 50.76 39.29 55.99 25.63 44.74 44.74 47.02 37.68 52.00 24.76 41.39 41.39 43.06 36.07 47.68 22.17
85 54.11 54.11 55.11 51.57 60.33 37.49 51.12 51.12 51.70 50.06 56.53 35.92 47.90 47.90 48.04 47.80 52.47 34.31 44.41 44.41 44.38 44.38 48.08 32.71
90 57.46 57.46 57.42 57.42 60.91 47.89 54.28 54.28 54.24 54.24 57.06 46.26 51.13 51.13 51.07 51.07 53.02 44.70 47.44 47.44 47.38 47.38 48.65 43.22
1920 75 49.57 46.91 54.49 31.84 59.96 16.95 46.34 45.03 50.91 30.19 56.11 15.50 42.85 42.61 47.08 28.63 52.03 13.75 39.34 39.34 43.00 26.92 47.65 12.48
80 52.16 52.16 55.09 43.23 60.62 27.45 49.16 49.16 51.49 41.58 56.84 26.83 45.99 45.99 47.75 40.07 52.64 25.44 42.46 42.46 43.68 38.44 48.22 23.54
85 55.60 55.60 56.10 54.73 61.16 39.54 52.52 52.52 52.67 52.46 57.25 37.89 49.18 49.18 49.16 49.16 53.11 36.31 45.61 45.61 45.54 45.54 48.73 34.74
90 59.08 59.08 59.03 59.03 61.77 50.65 55.87 55.87 55.83 55.83 57.93 49.34 52.46 52.46 52.39 52.39 53.81 47.85 48.69 48.69 48.64 48.64 49.43 46.51
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

38 RT-PRC023-EN
Performance Data
(5 Tons High Efficiency)

Table 28. Gross Cooling Capacities 5 Tons Three Phase T/YHC060E1


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75 58.30 49.11 64.82 36.01 71.80 22.38 54.69 47.20 60.92 34.31 67.62 21.26 50.77 45.18 56.61 31.89 62.96 17.81 46.38 43.01 51.90 29.75 57.98 17.23
80 59.42 59.42 65.25 46.53 72.33 32.77 56.25 56.25 61.31 44.31 68.14 31.10 52.79 52.79 57.05 42.23 63.55 29.03 48.96 48.96 52.35 40.09 58.46 26.96
85 63.16 63.16 65.74 56.78 72.63 43.30 59.93 59.93 61.85 54.88 68.47 41.26 56.37 56.37 57.58 52.91 63.89 39.18 52.46 52.46 53.01 50.89 58.88 37.16
90 66.88 66.88 66.84 66.84 73.03 53.49 63.61 63.61 63.54 63.54 68.85 51.44 60.00 60.00 59.94 59.94 64.23 49.53 56.01 56.01 55.96 55.96 59.24 47.44
2000 75 59.61 52.43 66.05 37.54 73.14 22.70 55.88 50.55 62.04 35.65 68.78 20.78 51.79 48.42 57.62 33.57 63.96 19.43 47.42 46.28 52.81 30.85 58.89 16.74
80 61.61 61.61 66.59 48.99 73.65 34.02 58.33 58.33 62.49 47.13 69.30 32.43 54.68 54.68 58.13 45.12 64.55 30.41 50.75 50.75 53.34 43.01 59.42 28.29
85 65.50 65.50 67.13 60.90 73.98 46.03 62.15 62.15 63.13 58.96 69.71 43.84 58.48 58.48 58.80 57.04 64.92 41.61 54.38 54.38 54.38 54.38 59.85 39.61
90 69.44 69.44 69.35 69.35 74.37 57.11 65.99 65.99 65.92 65.92 70.11 55.11 62.24 62.24 62.19 62.19 65.36 53.13 58.05 58.05 58.02 58.02 60.23 51.15
2200 75 60.71 55.72 67.10 38.84 74.13 22.74 56.94 53.79 63.01 37.68 69.76 21.05 52.80 51.75 58.50 35.12 64.95 19.16 48.52 48.52 53.60 33.16 59.71 17.30
80 63.54 63.54 67.65 51.87 74.78 35.88 60.12 60.12 63.51 49.97 70.37 33.82 56.41 56.41 59.03 47.98 65.47 31.79 52.27 52.27 54.18 45.81 60.26 29.65
85 67.60 67.60 68.37 64.96 75.12 47.62 64.14 64.14 64.38 63.17 70.69 46.27 60.27 60.27 60.21 60.21 65.85 44.05 56.09 56.09 56.05 56.05 60.64 42.15
90 71.64 71.64 71.65 71.65 75.57 60.68 68.14 68.14 68.06 68.06 71.11 58.71 64.16 64.16 64.11 64.11 66.37 56.96 59.85 59.85 59.80 59.80 61.20 54.93
2400 75 61.71 58.91 67.98 41.14 75.01 23.72 57.92 57.05 63.81 39.16 70.61 21.34 53.87 53.87 59.23 36.47 65.63 20.09 49.75 49.75 54.27 34.65 60.39 17.26
80 65.23 65.23 68.54 54.70 75.72 37.17 61.72 61.72 64.41 52.84 71.13 35.16 57.90 57.90 59.90 50.86 66.24 33.11 53.58 53.58 54.88 48.84 60.95 30.94
85 69.37 69.37 69.63 69.09 76.08 50.15 65.90 65.90 65.83 65.83 71.63 48.28 61.88 61.88 61.86 61.86 66.66 46.63 57.52 57.52 57.45 57.45 61.24 44.63
90 73.64 73.64 73.58 73.58 76.59 64.31 70.00 70.00 69.93 69.93 72.17 62.57 65.92 65.92 65.86 65.86 67.26 60.67 61.46 61.46 61.39 61.39 62.12 58.89
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table 29. Gross Cooling Capacities 5 Tons Three Phase T/YHC060E3,4


Ambient Temperature
85 95 105 115
Air Ent Entering Wet Bulb
Flow DB 61 67 73 61 67 73 61 67 73 61 67 73
CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
1800 75 59.56 49.58 65.99 35.89 72.88 22.54 55.71 47.49 61.89 34.49 68.49 20.74 51.74 45.43 57.53 32.41 63.82 18.60 47.43 43.28 52.93 30.03 58.87 16.71
80 60.46 60.32 66.42 46.59 73.49 33.29 57.05 57.05 62.32 44.54 69.01 31.17 53.52 53.52 57.96 42.65 64.32 29.29 49.78 49.78 53.40 40.31 59.38 27.15
85 64.08 64.08 66.89 57.00 73.87 43.37 60.69 60.69 62.82 55.07 69.44 41.48 57.08 57.08 58.52 53.07 64.69 39.39 53.27 53.27 53.96 51.01 59.77 37.20
90 67.81 67.81 67.85 67.72 74.21 53.63 64.34 64.34 64.27 64.27 69.76 51.42 60.65 60.65 60.60 60.60 65.06 49.57 56.69 56.69 56.65 56.65 60.12 47.72
2000 75 60.83 52.78 67.28 37.85 74.20 22.90 56.93 50.81 63.03 35.70 69.61 21.19 52.84 48.74 58.59 33.81 64.89 18.98 48.47 46.53 53.82 31.65 59.84 16.97
80 62.57 62.57 67.73 49.35 74.82 34.58 59.12 59.12 63.49 47.33 70.20 32.64 55.45 55.45 59.03 45.41 65.39 30.54 51.57 51.57 54.36 43.23 60.35 28.45
85 66.45 66.45 68.38 61.14 75.15 45.81 62.92 62.92 64.16 59.19 70.62 43.78 59.18 59.18 59.74 57.16 65.78 41.83 55.17 55.17 55.30 55.11 60.73 40.17
90 70.36 70.36 70.32 70.32 75.55 57.08 66.77 66.77 66.69 66.69 71.02 55.15 62.89 62.89 62.83 62.83 66.22 53.24 58.74 58.74 58.72 58.72 61.22 51.25
2200 75 61.94 56.03 68.33 39.54 75.28 23.26 57.96 54.06 64.01 37.90 70.63 20.97 53.76 52.00 59.41 35.31 65.76 19.07 49.42 49.35 54.60 33.15 60.62 17.27
80 64.51 64.51 68.83 52.16 75.90 35.93 60.94 60.94 64.56 50.21 71.23 33.87 57.18 57.18 59.98 48.17 66.33 31.93 53.11 53.11 55.16 45.98 61.13 29.79
85 68.48 68.48 69.55 65.16 76.27 48.35 64.88 64.88 65.34 63.36 71.68 46.32 61.01 61.01 60.99 60.92 66.71 44.27 56.81 56.81 56.76 56.76 61.58 42.48
90 72.56 72.56 72.60 72.60 76.79 60.75 68.86 68.86 68.80 68.80 72.08 58.83 64.84 64.84 64.79 64.79 67.17 56.86 60.60 60.60 60.52 60.52 62.10 55.08
2400 75 62.94 59.31 69.23 41.24 76.12 22.87 58.90 57.26 64.84 39.07 71.44 21.67 54.79 54.68 60.19 36.97 66.53 19.50 50.67 50.67 55.27 34.98 61.27 17.50
80 66.23 66.23 69.85 55.03 76.88 37.13 62.54 62.54 65.44 52.99 72.05 35.12 58.63 58.63 60.76 51.02 67.10 33.05 54.47 54.47 55.91 49.04 61.81 31.05
85 70.45 70.45 70.82 69.31 77.29 51.04 66.65 66.65 66.65 66.62 72.52 48.51 62.62 62.62 62.52 62.52 67.61 46.75 58.32 58.32 58.24 58.24 62.28 44.92
90 74.58 74.58 74.53 74.53 77.77 64.34 70.73 70.73 70.66 70.66 72.91 62.47 66.57 66.57 66.53 66.53 68.23 60.73 62.17 62.17 62.12 62.12 62.89 58.75
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC023-EN 39
Performance Data

Table 30. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — No Electric Heat — TSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 TSC036E1 960 0.45 715 0.21 0.74 851 0.31 0.92 929 0.38 1.07 993 0.44 1.25 1053 0.52
Downflow 1020 0.39 695 0.20 0.66 826 0.30 0.84 905 0.37 0.99 969 0.43 1.17 1030 0.50
Airflow 1080 0.33 675 0.20 0.59 800 0.29 0.77 880 0.36 0.91 945 0.42 1.08 1007 0.49
1140 0.27 654 0.19 0.51 774 0.28 0.69 855 0.35 0.83 921 0.41 1.00 985 0.48
1200 0.21 634 0.18 0.43 749 0.27 0.61 831 0.34 0.75 898 0.40 0.91 962 0.47
1260 0.15 614 0.18 0.35 723 0.26 0.53 806 0.33 0.67 874 0.39 0.83 939 0.46
1320 0.09 593 0.17 0.28 697 0.25 0.45 782 0.32 0.59 850 0.38 0.74 916 0.45
1380 0.03 573 0.17 0.20 671 0.24 0.37 757 0.31 0.51 826 0.37 0.66 893 0.44
1440 — — — 0.12 646 0.23 0.29 732 0.30 0.43 802 0.36 0.57 871 0.43
TSC036E1 960 0.45 711 0.21 0.70 835 0.30 0.89 913 0.37 1.04 978 0.44 1.21 1037 0.51
Horizontal 1020 0.39 689 0.20 0.63 811 0.29 0.81 890 0.36 0.96 957 0.43 1.13 1016 0.50
Airflow 1080 0.32 667 0.19 0.56 787 0.28 0.73 868 0.35 0.88 935 0.42 1.04 996 0.49
1140 0.26 644 0.19 0.48 763 0.28 0.65 845 0.34 0.80 913 0.41 0.95 975 0.48
1200 0.20 622 0.18 0.41 739 0.27 0.57 823 0.33 0.72 892 0.40 0.87 955 0.47
1260 0.13 599 0.17 0.33 715 0.26 0.50 800 0.32 0.64 870 0.39 0.78 934 0.46
1320 0.07 577 0.17 0.26 691 0.25 0.42 777 0.32 0.56 848 0.38 0.69 913 0.45
1380 0.01 555 0.16 0.18 667 0.24 0.34 755 0.31 0.48 826 0.37 0.61 893 0.44
1440 — — — 0.11 642 0.23 0.26 732 0.30 0.40 805 0.36 0.52 872 0.43
4 TSC048E1 1280 0.60 865 0.36 0.84 977 0.47 1.02 1044 0.55 1.17 1090 0.63 — — —
Downflow 1360 0.48 833 0.35 0.72 944 0.45 0.90 1012 0.54 1.04 1062 0.61 — — —
Airflow 1440 0.37 802 0.34 0.60 912 0.44 0.77 980 0.52 0.92 1033 0.60 — — —
1520 0.25 770 0.32 0.48 879 0.42 0.65 948 0.50 0.80 1005 0.58 1.06 1100 0.69
1600 0.14 739 0.31 0.36 846 0.41 0.52 915 0.49 0.68 976 0.56 0.92 1069 0.67
1680 0.02 707 0.30 0.24 814 0.39 0.39 883 0.47 0.56 948 0.55 0.78 1038 0.65
1760 — — — 0.13 781 0.38 0.27 851 0.45 0.43 920 0.53 0.64 1006 0.63
1840 — — — 0.01 748 0.36 0.14 819 0.43 0.31 891 0.52 0.50 975 0.62
1920 — — — — — — 0.02 787 0.42 0.19 863 0.50 0.37 944 0.60
TSC048E1 1280 0.61 864 0.36 0.84 967 0.47 1.00 1038 0.55 1.16 1115 0.65 — — —
Horizontal 1360 0.51 831 0.35 0.73 935 0.45 0.88 1006 0.53 1.05 1084 0.63 — — —
Airflow 1440 0.40 798 0.33 0.62 904 0.44 0.77 974 0.52 0.94 1052 0.61 1.10 1114 0.70
1520 0.30 766 0.32 0.51 873 0.42 0.66 943 0.50 0.82 1020 0.59 0.99 1084 0.68
1600 0.19 733 0.31 0.40 842 0.41 0.55 911 0.48 0.71 989 0.57 0.87 1054 0.66
1680 0.09 701 0.29 0.29 810 0.39 0.44 879 0.47 0.60 957 0.55 0.75 1023 0.65
1760 — — — 0.18 779 0.38 0.32 848 0.45 0.48 925 0.54 0.64 993 0.63
1840 — — — 0.08 748 0.36 0.21 816 0.43 0.37 893 0.52 0.52 963 0.61
1920 — — — — — — 0.10 784 0.42 0.26 861 0.50 0.40 932 0.59
5 TSC060E1 1600 0.75 1006 0.60 0.91 1065 0.69 — — — — — — — — —
Downflow 1700 0.60 969 0.58 0.75 1024 0.66 0.96 1101 0.77 — — — — — —
Airflow 1800 0.45 933 0.56 0.58 982 0.63 0.78 1059 0.74 — — — — — —
1900 0.30 896 0.54 0.42 941 0.61 0.61 1017 0.71 0.82 1105 0.83 — — —
2000 0.14 860 0.52 0.25 899 0.58 0.43 975 0.68 0.64 1062 0.80 0.70 1083 0.85
2100 0.00 826 0.50 0.09 858 0.55 0.25 933 0.65 0.46 1019 0.77 0.54 1045 0.82
2200 — — — — — — 0.08 891 0.62 0.28 975 0.74 0.37 1007 0.79
2300 — — — — — — — — — 0.10 932 0.70 0.20 969 0.76
2400 — — — — — — — — — — — — 0.03 931 0.73
TSC060E1 1600 0.73 1003 0.60 0.90 1075 0.69 — — — — — — — — —
Horizontal 1700 0.60 968 0.58 0.74 1034 0.67 0.89 1104 0.77 — — — — — —
Airflow 1800 0.46 934 0.56 0.59 993 0.64 0.74 1064 0.74 — — — — — —
1900 0.33 899 0.54 0.44 952 0.62 0.59 1023 0.71 0.75 1095 0.83 — — —
2000 0.19 864 0.52 0.28 911 0.59 0.43 983 0.69 0.60 1053 0.79 0.69 1090 0.86
2100 0.05 829 0.50 0.13 870 0.56 0.28 942 0.66 0.44 1012 0.76 0.53 1051 0.83
2200 — — — 0.00 837 0.54 0.13 902 0.63 0.28 971 0.73 0.37 1012 0.80
2300 — — — — — — 0.00 868 0.61 0.12 930 0.70 0.21 972 0.77
2400 — — — — — — — — — 0.00 897 0.68 0.06 933 0.74
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16. For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

40 RT-PRC023-EN
Performance Data
(3-5 Tons Standard Efficiency)

Table 31. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — Low & Medium Gas Heat — YSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YSC036E1**L,M 960 0.43 718 0.19 0.64 825 0.27 0.88 923 0.35 1.12 1017 0.46 1.28 1074 0.52
Downflow 1020 0.37 696 0.18 0.57 800 0.26 0.80 900 0.35 1.04 997 0.45 1.20 1053 0.51
Airflow 1080 0.30 675 0.18 0.49 775 0.26 0.72 877 0.34 0.96 977 0.44 1.11 1033 0.50
1140 0.24 654 0.17 0.42 749 0.25 0.64 854 0.33 0.87 957 0.43 1.03 1013 0.49
1200 0.18 633 0.17 0.34 724 0.24 0.56 832 0.32 0.79 938 0.42 0.94 992 0.48
1260 0.11 612 0.16 0.26 698 0.23 0.48 809 0.31 0.71 918 0.41 0.86 972 0.47
1320 0.05 590 0.16 0.19 673 0.22 0.39 786 0.30 0.63 898 0.40 0.77 951 0.46
1380 — — — 0.11 647 0.21 0.31 763 0.29 0.55 878 0.39 0.68 931 0.45
1440 — — — 0.03 622 0.21 0.23 740 0.28 0.47 859 0.38 0.60 910 0.44
YSC036E1**L,M 960 0.42 715 0.19 0.67 842 0.28 0.90 937 0.36 1.15 1037 0.46 1.25 1062 0.51
Horizontal 1020 0.37 695 0.18 0.61 819 0.27 0.83 916 0.35 1.07 1014 0.45 1.18 1047 0.50
Airflow 1080 0.31 675 0.18 0.54 796 0.26 0.75 895 0.34 0.99 992 0.44 1.11 1032 0.50
1140 0.26 654 0.17 0.47 772 0.26 0.68 874 0.34 0.91 970 0.43 1.04 1017 0.49
1200 0.20 634 0.17 0.41 749 0.25 0.61 853 0.33 0.83 948 0.42 0.97 1002 0.48
1260 0.14 614 0.16 0.34 725 0.24 0.54 832 0.32 0.75 926 0.41 0.90 987 0.48
1320 0.09 594 0.16 0.27 702 0.23 0.47 811 0.31 0.67 903 0.40 0.83 972 0.47
1380 0.03 574 0.15 0.20 678 0.22 0.40 789 0.30 0.59 881 0.39 0.76 957 0.46
1440 — — — 0.14 654 0.22 0.33 768 0.29 0.51 859 0.38 0.69 942 0.45
4 YSC048E1**L,M 1280 0.71 933 0.42 0.89 1003 0.49 1.11 1094 0.59 — — — — — —
Downflow 1360 0.59 903 0.41 0.76 973 0.48 0.97 1061 0.57 1.14 1116 0.64 — — —
Airflow 1440 0.47 874 0.39 0.63 943 0.46 0.84 1027 0.56 1.00 1085 0.62 — — —
1520 0.34 845 0.38 0.50 913 0.45 0.70 993 0.54 0.86 1053 0.61 1.05 1122 0.70
1600 0.22 815 0.37 0.38 883 0.43 0.56 959 0.52 0.72 1021 0.59 0.90 1089 0.68
1680 0.10 786 0.36 0.25 852 0.42 0.42 926 0.50 0.58 990 0.57 0.76 1057 0.66
1760 — — — 0.12 822 0.41 0.28 892 0.48 0.45 958 0.55 0.61 1024 0.64
1840 — — — — — — 0.15 858 0.46 0.31 926 0.53 0.47 992 0.62
1920 — — — — — — 0.01 824 0.45 0.17 895 0.51 0.32 960 0.60
YSC048E1**L,M 1280 0.66 894 0.40 0.81 967 0.48 1.01 1051 0.57 1.14 1101 0.63 — — —
Horizontal 1360 0.54 863 0.39 0.70 935 0.46 0.88 1016 0.55 1.01 1069 0.61 — — —
Airflow 1440 0.43 831 0.38 0.58 904 0.45 0.76 982 0.53 0.89 1037 0.60 1.05 1101 0.69
1520 0.31 799 0.36 0.47 872 0.43 0.63 947 0.51 0.77 1006 0.58 0.93 1069 0.67
1600 0.20 768 0.35 0.35 840 0.41 0.51 912 0.49 0.64 974 0.56 0.80 1037 0.65
1680 0.08 736 0.33 0.24 809 0.40 0.38 877 0.47 0.52 942 0.54 0.67 1005 0.63
1760 — — — 0.12 777 0.38 0.26 842 0.46 0.40 911 0.52 0.55 973 0.61
1840 — — — 0.01 745 0.37 0.13 807 0.44 0.28 879 0.51 0.42 941 0.59
1920 — — — — — — 0.00 773 0.42 0.15 847 0.49 0.29 909 0.57
5 YSC060E1**L,M 1600 0.97 1110 0.71 — — — — — — — — — — — —
Downflow 1700 0.79 1068 0.68 0.91 1120 0.77 — — — — — — — — —
Airflow 1800 0.60 1026 0.66 0.73 1079 0.74 — — — — — — — — —
1900 0.42 984 0.63 0.54 1038 0.71 0.69 1093 0.78 — — — — — —
2000 0.24 942 0.60 0.36 997 0.68 0.50 1050 0.74 0.60 1079 0.82 — — —
2100 0.06 900 0.57 0.18 956 0.65 0.31 1006 0.71 0.42 1040 0.79 0.52 1078 0.86
2200 — — — 0.00 916 0.63 0.12 963 0.68 0.24 1001 0.76 0.32 1036 0.83
2300 — — — — — — 0.00 936 0.66 0.05 962 0.73 0.13 994 0.79
2400 — — — — — — — — — — — — 0.00 965 0.77
YSC060E1**L,M 1600 0.83 1054 0.67 — — — — — — — — — — — —
Horizontal 1700 0.67 1013 0.65 0.83 1084 0.74 — — — — — — — — —
Airflow 1800 0.51 971 0.62 0.65 1039 0.71 0.75 1075 0.76 — — — — — —
1900 0.36 930 0.59 0.48 995 0.68 0.57 1031 0.73 0.72 1086 0.82 — — —
2000 0.20 888 0.57 0.30 951 0.65 0.39 987 0.70 0.54 1045 0.79 0.67 1092 0.87
2100 0.04 847 0.54 0.12 907 0.62 0.21 942 0.67 0.36 1004 0.76 0.48 1051 0.84
2200 — — — 0.00 877 0.60 0.02 898 0.64 0.17 963 0.73 0.29 1010 0.81
2300 — — — — — — — — — 0.00 924 0.70 0.10 968 0.77
2400 — — — — — — — — — — — — 0.00 946 0.76
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

RT-PRC023-EN 41
Performance Data
(3-5 Tons Standard Efficiency)

Table 32. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — High Heat — YSC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YSC036E1**H 960 0.43 718 0.19 0.64 825 0.26 0.88 923 0.34 1.12 1017 0.44 1.28 1074 0.51
Downflow 1020 0.37 696 0.19 0.57 800 0.26 0.80 900 0.34 1.04 997 0.43 1.20 1053 0.50
Airflow 1080 0.30 675 0.18 0.49 775 0.25 0.72 877 0.33 0.96 977 0.42 1.11 1033 0.49
1140 0.24 654 0.18 0.42 749 0.24 0.64 854 0.32 0.87 957 0.42 1.03 1013 0.48
1200 0.18 633 0.17 0.34 724 0.23 0.56 832 0.31 0.79 938 0.41 0.94 992 0.47
1260 0.11 612 0.16 0.26 698 0.22 0.48 809 0.30 0.71 918 0.40 0.86 972 0.46
1320 0.05 590 0.16 0.19 673 0.21 0.39 786 0.29 0.63 898 0.39 0.77 951 0.45
1380 — — — 0.11 647 0.21 0.31 763 0.28 0.55 878 0.38 0.68 931 0.44
1440 — — — 0.03 622 0.20 0.23 740 0.28 0.47 859 0.37 0.60 910 0.43
YSC036E1**H 960 0.44 732 0.20 0.65 836 0.27 0.87 935 0.35 1.12 1033 0.45 1.25 1078 0.51
Horizontal 1020 0.37 708 0.19 0.58 811 0.26 0.80 911 0.34 1.03 1010 0.44 1.17 1059 0.50
Airflow 1080 0.31 684 0.18 0.51 787 0.25 0.72 886 0.33 0.95 987 0.43 1.09 1040 0.49
1140 0.24 660 0.18 0.43 762 0.24 0.64 862 0.32 0.87 964 0.42 1.01 1021 0.48
1200 0.18 636 0.17 0.36 737 0.24 0.56 838 0.31 0.79 941 0.41 0.93 1002 0.47
1260 0.11 612 0.16 0.29 712 0.23 0.48 814 0.30 0.70 918 0.40 0.85 983 0.47
1320 0.05 588 0.16 0.21 688 0.22 0.40 789 0.29 0.62 895 0.39 0.77 964 0.46
1380 — — — 0.14 663 0.21 0.32 765 0.28 0.54 872 0.38 0.69 945 0.45
1440 — — — 0.07 638 0.20 0.24 741 0.28 0.45 849 0.37 0.61 926 0.44
4 YSC048E1**H 1280 0.73 951 0.44 0.93 1025 0.52 1.10 1084 0.60 — — — — — —
Downflow 1360 0.61 917 0.42 0.80 991 0.50 0.96 1051 0.58 1.14 1116 0.67 — — —
Airflow 1440 0.48 883 0.41 0.66 957 0.49 0.82 1019 0.56 1.00 1085 0.65 — — —
1520 0.35 849 0.39 0.53 923 0.47 0.69 986 0.55 0.86 1053 0.63 — — —
1600 0.23 816 0.38 0.39 888 0.45 0.55 954 0.53 0.72 1021 0.61 0.91 1093 0.71
1680 0.10 782 0.36 0.26 854 0.43 0.42 922 0.51 0.58 990 0.59 0.76 1060 0.68
1760 — — — 0.12 820 0.42 0.28 889 0.49 0.45 958 0.57 0.62 1028 0.66
1840 — — — — — — 0.14 857 0.47 0.31 926 0.55 0.47 995 0.64
1920 — — — — — — 0.01 824 0.46 0.17 895 0.53 0.32 962 0.62
YSC048E1**H 1280 0.69 933 0.43 0.86 1005 0.51 1.04 1075 0.59 1.18 1124 0.67 — — —
Horizontal 1360 0.57 899 0.42 0.74 971 0.49 0.91 1041 0.57 1.05 1091 0.65 — — —
Airflow 1440 0.45 865 0.40 0.61 938 0.48 0.78 1006 0.56 0.92 1059 0.63 — — —
1520 0.33 831 0.38 0.49 904 0.46 0.65 972 0.54 0.79 1026 0.61 0.95 1091 0.70
1600 0.21 797 0.37 0.36 870 0.44 0.52 938 0.52 0.65 993 0.59 0.82 1060 0.68
1680 0.08 764 0.35 0.24 837 0.42 0.38 904 0.50 0.52 961 0.57 0.69 1030 0.66
1760 — — — 0.11 803 0.41 0.25 870 0.48 0.39 928 0.55 0.55 999 0.65
1840 — — — — — — 0.12 835 0.46 0.26 896 0.54 0.42 968 0.63
1920 — — — — — — — — — 0.12 863 0.52 0.29 937 0.61
5 YSC060E1**H 1600 0.97 1110 0.73 — — — — — — — — — — — —
Downflow 1700 0.79 1068 0.70 0.91 1120 0.78 — — — — — — — — —
Airflow 1800 0.60 1026 0.67 0.73 1079 0.75 — — — — — — — — —
1900 0.42 984 0.65 0.54 1038 0.72 0.69 1093 0.81 — — — — — —
2000 0.24 942 0.62 0.36 997 0.69 0.50 1050 0.78 0.60 1079 0.84 — — —
2100 0.06 900 0.59 0.18 956 0.66 0.31 1006 0.74 0.42 1040 0.81 0.52 1078 0.86
2200 — — — 0.00 916 0.64 0.12 963 0.71 0.24 1001 0.78 0.32 1036 0.83
2300 — — — — — — 0.00 936 0.69 0.05 962 0.75 0.13 994 0.79
2400 — — — — — — — — — — — — 0.00 965 0.77
YSC060E1**H 1600 0.95 1110 0.73 — — — — — — — — — — — —
Horizontal 1700 0.76 1064 0.70 0.87 1110 0.77 — — — — — — — — —
Airflow 1800 0.58 1019 0.67 0.69 1067 0.74 — — — — — — — — —
1900 0.40 973 0.64 0.51 1024 0.71 0.64 1075 0.79 — — — — — —
2000 0.21 927 0.61 0.32 982 0.68 0.45 1033 0.76 0.55 1069 0.83 0.64 1103 0.88
2100 0.03 882 0.58 0.14 939 0.65 0.26 991 0.73 0.37 1029 0.80 0.45 1060 0.85
2200 — — — 0.00 907 0.63 0.08 949 0.70 0.18 989 0.77 0.26 1017 0.81
2300 — — — — — — — — — 0.00 949 0.74 0.07 975 0.78
2400 — — — — — — — — — — — — — — —
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

42 RT-PRC023-EN
Performance Data
(3-5 Tons Standard Efficiency)

Table 33. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — WSC036, 048, 060E1
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 WSC036E1 960 0.43 707 0.21 0.70 843 0.38 0.88 919 0.38 1.02 979 0.36 1.15 1027 0.50
Downflow 1020 0.37 687 0.20 0.62 818 0.37 0.80 896 0.37 0.94 956 0.35 1.07 1006 0.49
Airflow 1080 0.31 668 0.19 0.55 792 0.36 0.73 872 0.36 0.87 933 0.34 0.99 985 0.48
1140 0.25 648 0.19 0.47 766 0.35 0.65 849 0.35 0.79 911 0.33 0.91 964 0.47
1200 0.19 628 0.18 0.39 740 0.34 0.57 826 0.34 0.71 888 0.32 0.83 943 0.46
1260 0.13 609 0.18 0.31 715 0.32 0.50 803 0.33 0.63 866 0.32 0.75 922 0.45
1320 0.07 589 0.17 0.24 689 0.31 0.42 780 0.32 0.56 843 0.31 0.68 901 0.44
1380 0.01 569 0.17 0.16 663 0.30 0.34 757 0.31 0.48 820 0.30 0.60 880 0.43
1440 — — — 0.08 637 0.29 0.26 734 0.30 0.40 798 0.29 0.52 859 0.42
WSC036E1 960 0.40 707 0.21 0.69 856 0.31 0.88 941 0.39 1.03 987 0.45 1.16 1034 0.50
Horizontal 1020 0.35 688 0.20 0.62 831 0.30 0.80 916 0.38 0.95 967 0.44 1.08 1011 0.49
Airflow 1080 0.30 669 0.19 0.55 806 0.29 0.73 891 0.37 0.87 947 0.43 1.00 989 0.48
1140 0.24 650 0.19 0.48 781 0.28 0.65 866 0.36 0.79 927 0.42 0.92 966 0.47
1200 0.19 631 0.18 0.41 756 0.28 0.58 841 0.35 0.71 906 0.41 0.84 943 0.46
1260 0.14 612 0.18 0.34 731 0.27 0.50 816 0.34 0.63 886 0.40 0.76 920 0.45
1320 0.09 593 0.17 0.26 706 0.26 0.43 791 0.33 0.55 866 0.39 0.68 898 0.44
1380 0.04 574 0.17 0.19 681 0.25 0.35 766 0.32 0.47 846 0.38 0.60 875 0.43
1440 — — — 0.12 655 0.24 0.28 741 0.30 0.40 826 0.37 0.52 852 0.42
4 WSC048E1 1280 0.60 865 0.36 0.84 977 0.47 1.02 1044 0.55 1.17 1090 0.63 — — —
Downflow 1360 0.48 833 0.35 0.72 944 0.45 0.90 1012 0.54 1.04 1062 0.61 — — —
Airflow 1440 0.37 802 0.34 0.60 912 0.44 0.77 980 0.52 0.92 1033 0.60 — — —
1520 0.25 770 0.32 0.48 879 0.42 0.65 948 0.50 0.80 1005 0.58 1.06 1100 0.69
1600 0.14 739 0.31 0.36 846 0.41 0.52 915 0.49 0.68 976 0.56 0.92 1069 0.67
1680 0.02 707 0.30 0.24 814 0.39 0.39 883 0.47 0.56 948 0.55 0.78 1038 0.65
1760 — — — 0.13 781 0.38 0.27 851 0.45 0.43 920 0.53 0.64 1006 0.63
1840 — — — 0.01 748 0.36 0.14 819 0.43 0.31 891 0.52 0.50 975 0.62
1920 — — — — — — 0.02 787 0.42 0.19 863 0.50 0.37 944 0.60
WSC048E1 1280 0.61 864 0.36 0.84 967 0.47 1.00 1038 0.55 1.16 1115 0.65 — — —
Horizontal 1360 0.51 831 0.35 0.73 935 0.45 0.88 1006 0.53 1.05 1084 0.63 — — —
Airflow 1440 0.40 798 0.33 0.62 904 0.44 0.77 974 0.52 0.94 1052 0.61 1.10 1114 0.70
1520 0.30 766 0.32 0.51 873 0.42 0.66 943 0.50 0.82 1020 0.59 0.99 1084 0.68
1600 0.19 733 0.31 0.40 842 0.41 0.55 911 0.48 0.71 989 0.57 0.87 1054 0.66
1680 0.09 701 0.29 0.29 810 0.39 0.44 879 0.47 0.60 957 0.55 0.75 1023 0.65
1760 — — — 0.18 779 0.38 0.32 848 0.45 0.48 925 0.54 0.64 993 0.63
1840 — — — 0.08 748 0.36 0.21 816 0.43 0.37 893 0.52 0.52 963 0.61
1920 — — — — — — 0.10 784 0.42 0.26 861 0.50 0.40 932 0.59
5 WSC060E1 1600 0.83 888 0.49 0.95 948 0.56 1.19 1048 0.67 — — — — — —
Downflow 1700 0.69 847 0.46 0.82 908 0.53 1.04 1004 0.64 1.33 1110 0.78 — — —
Airflow 1800 0.56 806 0.44 0.69 867 0.51 0.90 959 0.62 1.18 1063 0.75 — — —
1900 0.43 764 0.42 0.56 826 0.48 0.76 915 0.59 1.02 1016 0.71 — — —
2000 0.30 723 0.40 0.43 785 0.46 0.62 870 0.56 0.87 969 0.68 1.18 1089 0.88
2100 0.16 681 0.37 0.30 744 0.44 0.47 826 0.53 0.71 922 0.65 1.03 1044 0.84
2200 0.03 640 0.35 0.17 703 0.41 0.33 781 0.50 0.56 876 0.61 0.87 999 0.81
2300 — — — 0.04 663 0.39 0.19 737 0.47 0.41 829 0.58 0.72 954 0.77
2400 — — — — — — 0.05 693 0.44 0.25 782 0.55 0.56 909 0.73
WSC060E1 1600 0.76 884 0.48 0.82 932 0.55 0.98 1022 0.66 1.13 1104 0.77 — — —
Horizontal 1700 0.63 842 0.46 0.69 893 0.52 0.85 981 0.63 1.00 1061 0.74 — — —
Airflow 1800 0.50 801 0.44 0.57 854 0.50 0.72 941 0.60 0.87 1018 0.71 — — —
1900 0.36 759 0.42 0.45 815 0.48 0.60 900 0.58 0.74 975 0.68 — — —
2000 0.23 718 0.39 0.32 776 0.46 0.47 859 0.55 0.61 932 0.65 0.87 1069 0.86
2100 0.10 676 0.37 0.20 737 0.43 0.34 818 0.53 0.49 890 0.62 0.74 1025 0.83
2200 — — — 0.07 699 0.41 0.22 778 0.50 0.36 847 0.59 0.61 980 0.79
2300 — — — — — — 0.09 737 0.47 0.23 804 0.56 0.48 936 0.75
2400 — — — — — — — — — 0.10 761 0.53 0.35 892 0.72
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

RT-PRC023-EN 43
Performance Data
(3-5 Tons High Efficiency)

Table 34. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — No Electric Heat — THC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 THC036E1,3,4 960 0.45 715 0.21 0.74 851 0.31 0.92 929 0.38 1.07 993 0.44 1.25 1053 0.52
Downflow 1020 0.39 695 0.20 0.66 826 0.30 0.84 905 0.37 0.99 969 0.43 1.17 1030 0.50
Airflow 1080 0.33 675 0.20 0.59 800 0.29 0.77 880 0.36 0.91 945 0.42 1.08 1007 0.49
1140 0.27 654 0.19 0.51 774 0.28 0.69 855 0.35 0.83 921 0.41 1.00 985 0.48
1200 0.21 634 0.18 0.43 749 0.27 0.61 831 0.34 0.75 898 0.40 0.91 962 0.47
1260 0.15 614 0.18 0.35 723 0.26 0.53 806 0.33 0.67 874 0.39 0.83 939 0.46
1320 0.09 593 0.17 0.28 697 0.25 0.45 782 0.32 0.59 850 0.38 0.74 916 0.45
1380 0.03 573 0.17 0.20 671 0.24 0.37 757 0.31 0.51 826 0.37 0.66 893 0.44
1440 — — — 0.12 646 0.23 0.29 732 0.30 0.43 802 0.36 0.57 871 0.43
THC036E1,3,4 960 0.45 711 0.21 0.70 835 0.30 0.89 913 0.37 1.04 978 0.44 1.21 1037 0.51
Horizontal 1020 0.39 689 0.20 0.63 811 0.29 0.81 890 0.36 0.96 957 0.43 1.13 1016 0.50
Airflow 1080 0.32 667 0.19 0.56 787 0.28 0.73 868 0.35 0.88 935 0.42 1.04 996 0.49
1140 0.26 644 0.19 0.48 763 0.28 0.65 845 0.34 0.80 913 0.41 0.95 975 0.48
1200 0.20 622 0.18 0.41 739 0.27 0.57 823 0.33 0.72 892 0.40 0.87 955 0.47
1260 0.13 599 0.17 0.33 715 0.26 0.50 800 0.32 0.64 870 0.39 0.78 934 0.46
1320 0.07 577 0.17 0.26 691 0.25 0.42 777 0.32 0.56 848 0.38 0.69 913 0.45
1380 0.01 555 0.16 0.18 667 0.24 0.34 755 0.31 0.48 826 0.37 0.61 893 0.44
1440 — — — 0.11 642 0.23 0.26 732 0.30 0.40 805 0.36 0.52 872 0.43
4 THC048E1,3,4 1280 0.65 805 0.31 0.86 902 0.40 1.04 966 0.48 1.27 1042 0.58 — — —
Downflow 1360 0.55 769 0.30 0.76 866 0.38 0.94 934 0.46 1.17 1010 0.56 1.43 1113 0.68
Airflow 1440 0.46 733 0.28 0.66 830 0.37 0.84 902 0.44 1.06 977 0.54 1.31 1078 0.66
1520 0.36 696 0.27 0.56 794 0.35 0.74 869 0.43 0.95 944 0.52 1.20 1043 0.64
1600 0.27 660 0.25 0.46 758 0.33 0.63 837 0.41 0.85 912 0.50 1.08 1009 0.62
1680 0.17 624 0.24 0.36 722 0.32 0.53 805 0.40 0.74 879 0.49 0.97 974 0.60
1760 — — — 0.26 686 0.30 0.43 772 0.38 0.63 847 0.47 0.85 939 0.58
1840 — — — 0.16 650 0.29 0.33 740 0.36 0.53 814 0.45 0.74 905 0.55
1920 — — — 0.06 614 0.27 0.23 707 0.35 0.42 782 0.43 0.62 870 0.53
THC048E1,3,4 1280 0.56 795 0.31 0.77 880 0.39 0.95 967 0.48 1.16 1040 0.57 — — —
Horizontal 1360 0.48 760 0.29 0.67 847 0.37 0.86 935 0.46 1.06 1010 0.56 1.26 1105 0.68
Airflow 1440 0.39 725 0.28 0.58 814 0.36 0.76 903 0.44 0.96 980 0.54 1.16 1075 0.66
1520 0.30 690 0.27 0.48 780 0.34 0.66 871 0.43 0.86 951 0.53 1.06 1045 0.64
1600 0.22 655 0.25 0.39 747 0.33 0.57 838 0.41 0.76 921 0.51 0.96 1016 0.62
1680 0.13 619 0.24 0.30 714 0.31 0.47 806 0.40 0.66 891 0.49 0.86 986 0.60
1760 — — — 0.20 681 0.30 0.37 774 0.38 0.56 861 0.48 0.76 956 0.59
1840 — — — 0.11 647 0.29 0.28 742 0.37 0.46 831 0.46 0.66 926 0.57
1920 — — — 0.01 614 0.27 0.18 710 0.35 0.36 802 0.44 0.56 896 0.55
5 THC060E1,3,4 1600 0.82 918 0.50 1.04 1002 0.60 1.26 1087 0.72 — — — — — —
Downflow 1700 0.67 873 0.47 0.89 957 0.58 1.11 1043 0.69 — — — — — —
Airflow 1800 0.53 828 0.45 0.74 913 0.55 0.96 1000 0.66 1.16 1083 0.78 — — —
1900 0.39 782 0.42 0.59 869 0.52 0.82 957 0.63 1.02 1041 0.75 1.17 1099 0.85
2000 0.25 737 0.40 0.45 824 0.50 0.67 914 0.60 0.87 999 0.72 1.02 1056 0.82
2100 0.11 692 0.37 0.30 780 0.47 0.52 870 0.58 0.72 957 0.69 0.87 1014 0.78
2200 — — — 0.15 735 0.44 0.37 827 0.55 0.57 914 0.66 0.71 971 0.75
2300 — — — 0.00 691 0.42 0.22 784 0.52 0.42 872 0.63 0.56 929 0.72
2400 — — — — — — 0.07 741 0.49 0.27 830 0.60 0.41 886 0.68
THC060E1,3,4 1600 0.71 918 0.50 0.91 1001 0.60 1.09 1070 0.71 — — — — — —
Horizontal 1700 0.59 875 0.47 0.78 959 0.58 0.96 1029 0.68 1.11 1102 0.79 — — —
Airflow 1800 0.46 832 0.45 0.65 916 0.55 0.82 987 0.65 0.97 1063 0.77 — — —
1900 0.33 788 0.43 0.51 874 0.53 0.68 945 0.62 0.84 1023 0.74 1.01 1093 0.85
2000 0.21 745 0.40 0.38 831 0.50 0.54 903 0.60 0.71 984 0.71 0.87 1052 0.81
2100 0.08 701 0.38 0.25 788 0.47 0.41 861 0.57 0.57 944 0.68 0.73 1010 0.78
2200 — — — 0.12 746 0.45 0.27 819 0.54 0.44 904 0.65 0.59 968 0.75
2300 — — — — — — 0.13 778 0.51 0.31 865 0.62 0.45 926 0.72
2400 — — — — — — — — — 0.17 825 0.59 0.31 884 0.68
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

44 RT-PRC023-EN
Performance Data
(3-5 Tons High Efficiency)

Table 35. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — Low & Medium Gas Heat — YHC036, 048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YHC036E1,3,4**L,M 960 0.43 718 0.19 0.64 825 0.27 0.88 923 0.35 1.12 1017 0.46 1.28 1074 0.52
Downflow 1020 0.37 696 0.18 0.57 800 0.26 0.80 900 0.35 1.04 997 0.45 1.20 1053 0.51
Airflow 1080 0.30 675 0.18 0.49 775 0.26 0.72 877 0.34 0.96 977 0.44 1.11 1033 0.50
1140 0.24 654 0.17 0.42 749 0.25 0.64 854 0.33 0.87 957 0.43 1.03 1013 0.49
1200 0.18 633 0.17 0.34 724 0.24 0.56 832 0.32 0.79 938 0.42 0.94 992 0.48
1260 0.11 612 0.16 0.26 698 0.23 0.48 809 0.31 0.71 918 0.41 0.86 972 0.47
1320 0.05 590 0.16 0.19 673 0.22 0.39 786 0.30 0.63 898 0.40 0.77 951 0.46
1380 — — — 0.11 647 0.21 0.31 763 0.29 0.55 878 0.39 0.68 931 0.45
1440 — — — 0.03 622 0.21 0.23 740 0.28 0.47 859 0.38 0.60 910 0.44
YHC036E1,3,4**L,M 960 0.42 715 0.19 0.67 842 0.28 0.90 937 0.36 1.15 1037 0.46 1.25 1062 0.51
Horizontal 1020 0.37 695 0.18 0.61 819 0.27 0.83 916 0.35 1.07 1014 0.45 1.18 1047 0.50
Airflow 1080 0.31 675 0.18 0.54 796 0.26 0.75 895 0.34 0.99 992 0.44 1.11 1032 0.50
1140 0.26 654 0.17 0.47 772 0.26 0.68 874 0.34 0.91 970 0.43 1.04 1017 0.49
1200 0.20 634 0.17 0.41 749 0.25 0.61 853 0.33 0.83 948 0.42 0.97 1002 0.48
1260 0.14 614 0.16 0.34 725 0.24 0.54 832 0.32 0.75 926 0.41 0.90 987 0.48
1320 0.09 594 0.16 0.27 702 0.23 0.47 811 0.31 0.67 903 0.40 0.83 972 0.47
1380 0.03 574 0.15 0.20 678 0.22 0.40 789 0.30 0.59 881 0.39 0.76 957 0.46
1440 — — — 0.14 654 0.22 0.33 768 0.29 0.51 859 0.38 0.69 942 0.45
4 YHC048E1,3,4**L,M 1280 0.69 820 0.33 0.88 903 0.41 1.07 969 0.49 1.07 969 0.49 1.27 1039 0.58
Downflow 1360 0.59 785 0.32 0.78 869 0.40 0.96 936 0.48 0.96 936 0.48 1.16 1007 0.56
Airflow 1440 0.49 750 0.30 0.68 835 0.38 0.86 903 0.46 0.86 903 0.46 1.05 976 0.55
1520 0.40 714 0.29 0.58 801 0.37 0.75 870 0.44 0.75 870 0.44 0.94 944 0.53
1600 0.30 679 0.27 0.48 767 0.35 0.65 837 0.42 0.65 837 0.42 0.84 912 0.51
1680 0.20 643 0.26 0.38 733 0.34 0.54 804 0.41 0.54 804 0.41 0.73 881 0.49
1760 0.10 608 0.25 0.28 699 0.32 0.44 771 0.39 0.44 771 0.39 0.62 849 0.48
1840 0.01 572 0.23 0.18 666 0.31 0.33 738 0.37 0.33 738 0.37 0.51 817 0.46
1920 — — — 0.08 632 0.29 0.23 705 0.36 0.23 705 0.36 0.41 786 0.44
YHC048E1,3,4**L,M 1280 0.61 813 0.33 0.81 896 0.41 1.00 977 0.50 1.00 977 0.50 1.17 1044 0.58
Horizontal 1360 0.51 777 0.31 0.70 862 0.40 0.89 944 0.48 0.89 944 0.48 1.06 1011 0.57
Airflow 1440 0.42 742 0.30 0.60 828 0.38 0.79 911 0.46 0.79 911 0.46 0.95 979 0.55
1520 0.32 707 0.28 0.50 794 0.36 0.68 878 0.45 0.68 878 0.45 0.84 946 0.53
1600 0.22 671 0.27 0.40 760 0.35 0.57 845 0.43 0.57 845 0.43 0.73 913 0.51
1680 0.13 636 0.26 0.29 725 0.33 0.46 812 0.41 0.46 812 0.41 0.62 881 0.49
1760 0.03 600 0.24 0.19 691 0.32 0.36 779 0.40 0.36 779 0.40 0.51 848 0.47
1840 — — — 0.09 657 0.30 0.25 746 0.38 0.25 746 0.38 0.40 815 0.46
1920 — — — — — — 0.14 713 0.36 0.14 713 0.36 0.29 783 0.44
5 YHC060E1,3,4**L,M 1600 0.90 962 0.55 1.07 1027 0.64 1.28 1099 0.75 — — — — — —
Downflow 1700 0.76 919 0.53 0.93 985 0.61 1.14 1060 0.72 — — — — — —
Airflow 1800 0.62 875 0.50 0.78 943 0.59 0.99 1022 0.70 1.15 1092 0.81 — — —
1900 0.48 832 0.48 0.64 900 0.56 0.84 984 0.67 1.00 1051 0.78 1.18 1116 0.89
2000 0.34 788 0.45 0.49 858 0.53 0.70 945 0.65 0.86 1010 0.75 1.03 1076 0.86
2100 0.20 745 0.43 0.35 815 0.51 0.55 907 0.62 0.71 969 0.72 0.88 1037 0.83
2200 0.06 701 0.40 0.20 773 0.48 0.41 868 0.59 0.56 928 0.69 0.73 997 0.80
2300 — — — 0.06 730 0.46 0.26 830 0.57 0.41 887 0.66 0.58 958 0.77
2400 — — — — — — 0.12 792 0.54 0.26 846 0.63 0.43 918 0.73
YHC060E1,3,4**L,M 1600 0.75 944 0.54 0.91 1010 0.63 1.10 1094 0.75 — — — — — —
Horizontal 1700 0.61 899 0.52 0.77 969 0.60 0.96 1052 0.72 1.12 1114 0.82 — — —
Airflow 1800 0.48 855 0.49 0.63 927 0.58 0.82 1011 0.69 0.97 1074 0.79 — — —
1900 0.34 811 0.47 0.49 885 0.55 0.67 969 0.66 0.83 1035 0.76 1.01 1111 0.89
2000 0.20 766 0.44 0.35 843 0.53 0.53 928 0.63 0.68 995 0.74 0.87 1070 0.85
2100 0.07 722 0.42 0.21 801 0.50 0.39 887 0.61 0.54 956 0.71 0.72 1028 0.82
2200 — — — 0.07 759 0.47 0.25 845 0.58 0.39 916 0.68 0.57 987 0.79
2300 — — — — — — 0.10 804 0.55 0.25 877 0.65 0.42 945 0.76
2400 — — — — — — — — — 0.10 837 0.62 0.27 904 0.72
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

RT-PRC023-EN 45
Performance Data
(3-5 Tons High Efficiency)

Table 36. Multispeed Direct Drive Evaporator Fan Performance 3 – 5 Tons — High Heat — YHC036,048, 060E1,3,4
External Static Pressure (Inches of Water) & Motor Power (Bhp)(i)
Rated Standard Low Speed Mid Speed Standard High Speed High Speed
Unit Model Speed Set 1 Speed Set 2 Speed Set 3 Speed Set 4 Speed Set 5
Tons Number CFM ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP ESP RPM BHP
3 YHC036E1,3,4**H 960 0.43 718 0.19 0.64 825 0.26 0.88 923 0.34 1.12 1017 0.44 1.28 1074 0.51
Downflow 1020 0.37 696 0.19 0.57 800 0.26 0.80 900 0.34 1.04 997 0.43 1.20 1053 0.50
Airflow 1080 0.30 675 0.18 0.49 775 0.25 0.72 877 0.33 0.96 977 0.42 1.11 1033 0.49
1140 0.24 654 0.18 0.42 749 0.24 0.64 854 0.32 0.87 957 0.42 1.03 1013 0.48
1200 0.18 633 0.17 0.34 724 0.23 0.56 832 0.31 0.79 938 0.41 0.94 992 0.47
1260 0.11 612 0.16 0.26 698 0.22 0.48 809 0.30 0.71 918 0.40 0.86 972 0.46
1320 0.05 590 0.16 0.19 673 0.21 0.39 786 0.29 0.63 898 0.39 0.77 951 0.45
1380 — — — 0.11 647 0.21 0.31 763 0.28 0.55 878 0.38 0.68 931 0.44
1440 — — — 0.03 622 0.20 0.23 740 0.28 0.47 859 0.37 0.60 910 0.43
YHC036E1,3,4**H 960 0.44 732 0.20 0.65 836 0.27 0.87 935 0.35 1.12 1033 0.45 1.25 1078 0.51
Horizontal 1020 0.37 708 0.19 0.58 811 0.26 0.80 911 0.34 1.03 1010 0.44 1.17 1059 0.50
Airflow 1080 0.31 684 0.18 0.51 787 0.25 0.72 886 0.33 0.95 987 0.43 1.09 1040 0.49
1140 0.24 660 0.18 0.43 762 0.24 0.64 862 0.32 0.87 964 0.42 1.01 1021 0.48
1200 0.18 636 0.17 0.36 737 0.24 0.56 838 0.31 0.79 941 0.41 0.93 1002 0.47
1260 0.11 612 0.16 0.29 712 0.23 0.48 814 0.30 0.70 918 0.40 0.85 983 0.47
1320 0.05 588 0.16 0.21 688 0.22 0.40 789 0.29 0.62 895 0.39 0.77 964 0.46
1380 — — — 0.14 663 0.21 0.32 765 0.28 0.54 872 0.38 0.69 945 0.45
1440 — — — 0.07 638 0.20 0.24 741 0.28 0.45 849 0.37 0.61 926 0.44
4 YHC048E1,3,4**H 1280 0.69 833 0.35 0.90 924 0.43 1.07 989 0.51 1.07 989 0.51 1.27 1066 0.61
Downflow 1360 0.60 796 0.33 0.80 889 0.42 0.97 956 0.50 0.97 956 0.50 1.17 1033 0.59
Airflow 1440 0.50 759 0.32 0.71 855 0.40 0.87 922 0.48 0.87 922 0.48 1.06 1000 0.57
1520 0.40 722 0.30 0.61 820 0.39 0.77 889 0.46 0.77 889 0.46 0.96 966 0.56
1600 0.31 684 0.29 0.51 785 0.37 0.67 855 0.44 0.67 855 0.44 0.85 933 0.54
1680 0.21 647 0.27 0.41 751 0.35 0.57 822 0.43 0.57 822 0.43 0.75 900 0.52
1760 0.12 610 0.26 0.31 716 0.34 0.47 788 0.41 0.47 788 0.41 0.64 867 0.50
1840 — — — 0.22 681 0.32 0.37 755 0.39 0.37 755 0.39 0.54 834 0.48
1920 — — — 0.12 647 0.30 0.27 721 0.37 0.27 721 0.37 0.43 801 0.46
YHC048E1,3,4**H 1280 0.60 822 0.34 0.81 912 0.43 0.97 986 0.51 0.97 986 0.51 1.18 1063 0.61
Horizontal 1360 0.51 787 0.33 0.70 876 0.41 0.87 952 0.49 0.87 952 0.49 1.07 1031 0.59
Airflow 1440 0.41 752 0.31 0.60 840 0.40 0.76 918 0.48 0.76 918 0.48 0.96 998 0.57
1520 0.31 718 0.30 0.49 805 0.38 0.66 885 0.46 0.66 885 0.46 0.84 966 0.56
1600 0.22 683 0.29 0.38 769 0.36 0.55 851 0.44 0.55 851 0.44 0.73 933 0.54
1680 0.12 648 0.27 0.28 733 0.34 0.45 818 0.42 0.45 818 0.42 0.62 901 0.52
1760 0.03 613 0.26 0.17 697 0.33 0.34 784 0.41 0.34 784 0.41 0.51 868 0.50
1840 — — — 0.07 661 0.31 0.23 750 0.39 0.23 750 0.39 0.40 836 0.48
1920 — — — — — — 0.13 717 0.37 0.13 717 0.37 0.29 803 0.46
5 YHC060E1,3,4**H 1600 0.90 955 0.57 1.06 1022 0.66 1.25 1095 0.77 — — — — — —
Downflow 1700 0.76 910 0.54 0.92 977 0.63 1.11 1052 0.74 1.28 1113 0.85 — — —
Airflow 1800 0.62 865 0.52 0.77 932 0.60 0.96 1009 0.71 1.13 1072 0.82 — — —
1900 0.47 819 0.49 0.63 888 0.57 0.82 966 0.68 0.98 1031 0.79 1.18 1105 0.91
2000 0.33 774 0.46 0.49 843 0.54 0.67 922 0.65 0.83 990 0.75 1.02 1062 0.87
2100 0.19 729 0.44 0.34 798 0.52 0.52 879 0.62 0.68 949 0.72 0.87 1019 0.84
2200 0.04 683 0.41 0.20 754 0.49 0.38 836 0.59 0.54 908 0.69 0.71 976 0.80
2300 — — — 0.05 709 0.46 0.23 793 0.56 0.39 867 0.66 0.55 933 0.77
2400 — — — — — — 0.09 750 0.53 0.24 826 0.63 0.40 890 0.73
YHC060E1,3,4**H 1600 0.77 948 0.57 0.95 1016 0.66 1.10 1093 0.77 — — — — — —
Horizontal 1700 0.63 903 0.54 0.80 973 0.63 0.96 1052 0.74 — — — — — —
Airflow 1800 0.48 859 0.51 0.66 930 0.60 0.81 1012 0.71 1.00 1084 0.83 — — —
1900 0.34 814 0.49 0.51 888 0.57 0.67 971 0.68 0.85 1042 0.79 1.01 1106 0.91
2000 0.20 770 0.46 0.36 845 0.55 0.52 931 0.65 0.70 1000 0.76 0.86 1063 0.87
2100 0.06 725 0.43 0.22 803 0.52 0.38 890 0.62 0.55 959 0.73 0.70 1021 0.84
2200 — — — 0.07 760 0.49 0.23 850 0.60 0.39 917 0.70 0.54 979 0.80
2300 — — — — — — 0.09 809 0.57 0.24 875 0.67 0.39 937 0.77
2400 — — — — — — — — 0.00 0.09 833 0.63 0.23 894 0.73
For 036 Models, fan motor heat (MBH) = 2.72 x Fan Bhp + 0.16.
For 048 & 060 Models, fan motor heat (MBH) = 2.87 x Fan Bhp + 0.15.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
(i) Data includes pressure drop due to wet coil and filters.

46 RT-PRC023-EN
.

Performance Data

Table 37. Belt Drive Evaporator Fan Performance — 3 Tons — TSC036E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 608 0.17 676 0.22 734 0.27 785 0.32 833 0.37 878 0.42 922 0.47 963 0.53
1080 — — 557 0.15 629 0.20 697 0.25 757 0.30 809 0.36 857 0.42 901 0.47 944 0.53 983 0.59
1200 — — 588 0.18 653 0.23 718 0.29 777 0.35 832 0.41 881 0.47 925 0.53 967 0.59 1006 0.66
1320 553 0.17 621 0.22 681 0.27 741 0.33 799 0.39 854 0.46 903 0.53 948 0.59 990 0.66 1030 0.73
1440 591 0.21 655 0.27 712 0.32 766 0.38 821 0.44 873 0.51 923 0.58 970 0.66 1014 0.73 1053 0.80
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure drop due to
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1002 0.59 1039 0.65 1073 0.70 1107 0.76 1138 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1022 0.65 1059 0.71 1095 0.78 1129 0.84 1162 0.91 Using the full horsepower range of our fan motors as shown in our
1200 1044 0.72 1081 0.79 1115 0.85 1149 0.92 1183 0.99 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1068 0.80 1104 0.87 1138 0.94 1172 1.01 1205 1.08
1440 1091 0.88 1127 0.95 1161 1.03 1195 1.10 1227 1.18
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 38. Belt Drive Evaporator Fan Performance — 3 Tons — TSC036E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 619 0.16 680 0.20 738 0.25 791 0.30 840 0.35 885 0.39 927 0.44 968 0.49
1080 — — 570 0.14 647 0.19 708 0.24 762 0.29 814 0.34 863 0.39 908 0.45 950 0.50 991 0.55
1200 — — 595 0.17 674 0.23 736 0.28 789 0.33 839 0.39 885 0.44 931 0.50 973 0.56 1013 0.62
1320 551 0.16 622 0.20 698 0.26 764 0.33 817 0.38 866 0.44 911 0.50 954 0.56 997 0.62 1036 0.68
1440 588 0.20 653 0.24 722 0.30 789 0.37 846 0.44 894 0.50 938 0.56 980 0.63 1020 0.69 1060 0.76
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1005 0.54 1040 0.59 1074 0.64 1107 0.69 1139 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1029 0.61 1066 0.67 1100 0.72 1134 0.77 1165 0.83 Using the full horsepower range of our fan motors as shown in our
1200 1052 0.68 1088 0.74 1124 0.80 1157 0.86 1190 0.92 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1074 0.75 1112 0.82 1147 0.88 1181 0.95 1213 1.02
1440 1098 0.83 1134 0.90 1169 0.97 1203 1.04 1237 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 47
Performance Data
(3 Tons Standard Efficiency)

Table 39. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 600 0.15 664 0.19 722 0.23 774 0.27 824 0.31 870 0.36 913 0.41 952 0.45
1080 — — 560 0.14 625 0.17 687 0.22 743 0.26 795 0.31 844 0.36 890 0.40 933 0.45 973 0.51
1200 — — 593 0.17 655 0.21 712 0.25 767 0.30 817 0.35 865 0.40 910 0.45 952 0.51 993 0.56
1320 — — 626 0.20 685 0.25 740 0.29 791 0.34 841 0.40 887 0.45 931 0.51 974 0.56 1014 0.62
1440 592 0.20 660 0.25 718 0.29 769 0.34 818 0.39 866 0.45 911 0.51 955 0.57 996 0.63 1034 0.69
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.50 1025 0.55 1058 0.59 1091 0.64 1120 0.69 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1012 0.56 1047 0.61 1083 0.66 1116 0.72 1148 0.77 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.62 1069 0.67 1104 0.73 1138 0.79 1171 0.85 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1051 0.68 1088 0.74 1124 0.80 1159 0.86 1191 0.93
1440 1072 0.75 1108 0.81 1145 0.88 1179 0.94 1212 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 40. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 605 0.15 670 0.19 726 0.24 776 0.28 824 0.32 871 0.37 915 0.42 955 0.47
1080 — — 556 0.14 628 0.18 693 0.23 750 0.27 801 0.32 847 0.37 891 0.42 932 0.47 975 0.52
1200 — — 584 0.17 653 0.21 717 0.26 773 0.31 825 0.37 872 0.42 915 0.47 955 0.52 994 0.58
1320 — — 614 0.20 679 0.25 740 0.30 796 0.36 848 0.41 896 0.47 940 0.53 980 0.59 1018 0.65
1440 582 0.19 646 0.24 708 0.29 767 0.35 820 0.40 871 0.47 920 0.53 963 0.59 1005 0.66 1043 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 994 0.52 1031 0.58 1066 0.63 1101 0.69 1131 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously
1080 1013 0.58 1051 0.63 1087 0.69 1122 0.75 1155 0.81 at all cataloged conditions. Using the full horsepower range of our fan
1200 1032 0.63 1069 0.69 1105 0.75 1140 0.82 1175 0.88 motors as shown in our tabular data will not result in nuisance tripping
or premature motor failure. Our product’s warranty will not be
1320 1056 0.70 1090 0.76 1125 0.82 1159 0.89 1193 0.96 affected.
1440 1079 0.78 1114 0.84 1148 0.91 1181 0.97 1211 1.04
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

48 RT-PRC023-EN
Performance Data
(3 Tons Standard Efficiency)

Table 41. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 603 0.15 664 0.19 722 0.24 775 0.28 824 0.33 869 0.37 912 0.42 953 0.47
1080 — — 568 0.14 632 0.18 690 0.23 744 0.27 796 0.32 844 0.37 889 0.42 933 0.47 973 0.53
1200 — — 602 0.18 663 0.22 718 0.27 770 0.31 819 0.36 865 0.42 911 0.47 953 0.53 993 0.58
1320 572 0.17 638 0.22 695 0.26 748 0.31 798 0.36 845 0.41 889 0.47 932 0.53 974 0.58 1015 0.65
1440 611 0.21 674 0.27 729 0.31 779 0.36 827 0.42 872 0.47 915 0.53 957 0.59 997 0.65 1036 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.52 1026 0.58 1060 0.63 1092 0.68 1123 0.73 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1011 0.58 1047 0.63 1083 0.69 1115 0.75 1148 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1033 0.64 1069 0.70 1105 0.76 1138 0.82 1170 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1053 0.71 1089 0.77 1124 0.83 1159 0.90 1191 0.96
1440 1074 0.78 1109 0.84 1145 0.91 1178 0.98 1212 1.05
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 42. Belt Drive Evaporator Fan Performance — 3 Tons — YSC036E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 615 0.16 678 0.20 737 0.24 789 0.29 838 0.33 883 0.38 923 0.42 962 0.47
1080 — — 576 0.14 643 0.19 704 0.23 760 0.28 812 0.32 861 0.38 906 0.43 949 0.48 988 0.53
1200 — — 608 0.18 673 0.22 732 0.27 785 0.32 836 0.37 883 0.42 928 0.48 971 0.53 1012 0.59
1320 571 0.17 642 0.22 705 0.26 761 0.31 813 0.37 862 0.42 908 0.48 952 0.53 995 0.59 1034 0.66
1440 609 0.21 677 0.26 737 0.31 791 0.37 841 0.42 889 0.48 934 0.54 977 0.60 1017 0.66 1057 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 999 0.52 1034 0.57 1068 0.62 1100 0.67 1132 0.72 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1024 0.58 1061 0.64 1094 0.69 1126 0.74 1156 0.79 Using the full horsepower range of our fan motors as shown in our
1200 1050 0.65 1086 0.71 1120 0.77 1153 0.83 1183 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1072 0.72 1109 0.78 1145 0.85 1177 0.91 1209 0.98
1440 1095 0.79 1132 0.86 1167 0.93 1201 1.00 1234 1.07
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 49
Performance Data
(3 Tons Standard Efficiency)

Table 43. Belt Drive Evaporator Fan Performance — 3 Tons — WSC036E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — 570 0.14 635 0.19 697 0.23 756 0.28 809 0.34 858 0.39 900 0.44 939 0.49 976 0.54
1080 — — 606 0.18 669 0.23 726 0.27 780 0.33 834 0.38 883 0.44 929 0.50 970 0.56 1008 0.62
1200 572 0.18 644 0.23 705 0.28 758 0.33 809 0.38 858 0.44 907 0.50 953 0.57 997 0.63 1037 0.70
1320 613 0.22 682 0.28 741 0.33 793 0.39 842 0.44 889 0.50 933 0.56 977 0.63 1020 0.70 1062 0.78
1440 655 0.27 722 0.34 779 0.40 830 0.46 877 0.52 921 0.58 963 0.64 1004 0.71 1045 0.78 1086 0.86
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1011 0.59 1046 0.64 1081 0.69 1113 0.74 1146 0.80 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1042 0.67 1077 0.73 1109 0.79 1141 0.84 1173 0.90 Using the full horsepower range of our fan motors as shown in our
1200 1074 0.76 1108 0.83 1141 0.89 1172 0.95 1202 1.02 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1100 0.85 1137 0.92 1172 1.00 1203 1.06 1233 1.13
1440 1124 0.94 1161 1.01 1196 1.09 1231 1.18 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 44. Belt Drive Evaporator Fan Performance — 3 Tons — WSC036E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — 555 0.13 635 0.17 703 0.22 761 0.27 812 0.32 858 0.37 900 0.42 939 0.46 977 0.51
1080 — — 585 0.16 659 0.21 727 0.26 787 0.31 841 0.37 888 0.42 930 0.47 969 0.53 1007 0.58
1200 549 0.15 618 0.19 685 0.24 751 0.30 811 0.36 866 0.42 915 0.48 960 0.54 1001 0.60 1037 0.66
1320 590 0.19 654 0.24 716 0.29 777 0.35 836 0.41 890 0.47 940 0.54 986 0.60 1028 0.67 1068 0.74
1440 633 0.24 692 0.29 749 0.34 805 0.40 860 0.46 914 0.53 964 0.60 1010 0.67 1054 0.75 1094 0.82
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1014 0.57 1049 0.62 1082 0.67 1115 0.73 1149 0.78 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1044 0.64 1077 0.70 1110 0.75 1144 0.81 1175 0.87 Using the full horsepower range of our fan motors as shown in our
1200 1073 0.72 1108 0.78 1140 0.84 1172 0.90 1203 0.97 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1104 0.80 1139 0.87 1171 0.94 1203 1.01 1233 1.07
1440 1133 0.89 1169 0.97 1202 1.04 1234 1.11 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

50 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)

Table 45. Belt Drive Evaporator Fan Performance — 4 Tons — TSC048E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 613 0.20 672 0.24 725 0.29 778 0.34 830 0.39 879 0.45 923 0.51 965 0.56 1005 0.63
1440 592 0.20 657 0.25 716 0.30 765 0.35 812 0.40 859 0.46 906 0.52 952 0.58 995 0.65 1034 0.71
1600 644 0.26 703 0.32 760 0.37 809 0.43 853 0.49 895 0.54 936 0.60 980 0.67 1023 0.74 1062 0.81
1760 696 0.34 751 0.39 804 0.46 853 0.52 897 0.58 936 0.64 975 0.71 1012 0.77 1052 0.84 1091 0.91
1920 750 0.43 801 0.49 850 0.55 897 0.62 941 0.70 980 0.76 1017 0.83 1052 0.89 1087 0.96 1122 1.04
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1043 0.69 1080 0.75 1117 0.81 1152 0.88 1185 0.94 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1071 0.78 1107 0.84 1142 0.91 1176 0.98 1208 1.05 Using the full horsepower range of our fan motors as shown in our
1600 1101 0.88 1137 0.95 1171 1.03 1205 1.10 1237 1.17 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1129 0.99 1165 1.07 1200 1.14 1234 1.23 1266 1.31
1920 1157 1.11 1193 1.19 1227 1.27 1262 1.36 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 46. Belt Drive Evaporator Fan Performance — 4 Tons — TSC048E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 627 0.20 696 0.26 757 0.31 810 0.37 859 0.42 902 0.48 943 0.54 981 0.60 1019 0.66
1440 601 0.20 670 0.26 736 0.32 794 0.38 848 0.44 896 0.50 941 0.57 982 0.63 1020 0.70 1056 0.76
1600 653 0.27 715 0.32 776 0.39 834 0.45 886 0.52 935 0.59 979 0.66 1020 0.73 1059 0.80 1095 0.87
1760 706 0.34 763 0.40 820 0.47 874 0.54 925 0.61 972 0.69 1017 0.77 1058 0.84 1096 0.92 1134 1.00
1920 759 0.43 813 0.50 865 0.57 916 0.64 965 0.72 1011 0.80 1054 0.88 1096 0.97 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1054 0.71 1089 0.77 1122 0.83 1156 0.90 1187 0.97 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1090 0.82 1125 0.89 1157 0.96 1189 1.02 1220 1.09 Using the full horsepower range of our fan motors as shown in our
1600 1130 0.95 1162 1.02 1195 1.09 1225 1.16 1255 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1168 1.08 1201 1.15 1233 1.24 1263 1.31 1292 1.39
1920 1206 1.22 1239 1.30 1272 1.39 1302 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 51
Performance Data
(4 Tons Standard Efficiency)

Table 47. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 635 0.22 693 0.26 746 0.31 796 0.36 846 0.42 893 0.49 938 0.55 981 0.61 1020 0.67
1440 621 0.23 684 0.28 740 0.33 790 0.39 837 0.44 881 0.50 926 0.56 969 0.63 1011 0.70 1052 0.78
1600 675 0.30 734 0.35 787 0.41 836 0.47 880 0.53 923 0.59 963 0.66 1002 0.72 1042 0.80 1082 0.88
1760 731 0.38 786 0.44 836 0.51 883 0.58 927 0.64 967 0.71 1005 0.77 1043 0.84 1079 0.91 1114 0.99
1920 788 0.48 839 0.55 886 0.62 931 0.69 973 0.76 1012 0.84 1049 0.91 1085 0.98 1119 1.05 1153 1.13
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1057 0.73 1094 0.79 1128 0.85 1161 0.92 1192 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1089 0.85 1125 0.91 1160 0.98 1192 1.05 1224 1.11 Using the full horsepower range of our fan motors as shown in our
1600 1120 0.96 1156 1.04 1191 1.12 1223 1.19 1255 1.27 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1150 1.07 1186 1.16 1222 1.25 1255 1.34 1288 1.43
1920 1186 1.21 1219 1.29 1253 1.38 1285 1.48 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 48. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 632 0.21 696 0.26 756 0.31 812 0.37 862 0.42 908 0.48 952 0.54 993 0.60 1033 0.66
1440 618 0.22 679 0.26 738 0.32 794 0.38 847 0.44 897 0.50 944 0.56 987 0.63 1027 0.70 1066 0.76
1600 673 0.29 729 0.34 783 0.39 835 0.45 885 0.52 933 0.59 980 0.66 1023 0.73 1063 0.80 1101 0.87
1760 729 0.37 781 0.42 831 0.48 879 0.55 926 0.62 972 0.69 1015 0.76 1058 0.84 1098 0.92 1136 0.99
1920 785 0.47 834 0.53 880 0.59 926 0.66 970 0.73 1012 0.80 1055 0.88 1095 0.96 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1073 0.73 1109 0.79 1144 0.85 1179 0.92 1212 0.99 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1103 0.83 1139 0.90 1174 0.97 1210 1.04 1242 1.11 Using the full horsepower range of our fan motors as shown in our
1600 1138 0.95 1173 1.02 1206 1.09 1240 1.17 1273 1.25 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1173 1.07 1208 1.15 1241 1.23 1273 1.31 1304 1.40
1920 1208 1.21 1244 1.30 1278 1.39 1309 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

52 RT-PRC023-EN
Performance Data
(4 Tons Standard Efficiency)

Table 49. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 583 0.17 647 0.21 705 0.26 758 0.31 809 0.36 859 0.41 907 0.47 951 0.53 993 0.59 1033 0.65
1440 639 0.23 699 0.28 753 0.33 803 0.38 851 0.43 895 0.49 940 0.55 983 0.61 1025 0.68 1064 0.74
1600 696 0.30 752 0.36 803 0.41 850 0.47 895 0.53 937 0.58 979 0.65 1019 0.71 1058 0.78 1097 0.85
1760 754 0.39 807 0.45 855 0.51 900 0.57 942 0.63 982 0.70 1021 0.76 1059 0.83 1096 0.90 1132 0.97
1920 813 0.49 862 0.56 908 0.63 951 0.69 991 0.76 1029 0.82 1067 0.89 1102 0.96 1138 1.04 1172 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1071 0.71 1105 0.77 1139 0.83 1173 0.89 1202 0.94 Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
1440 1103 0.81 1139 0.88 1174 0.94 1207 1.01 1238 1.08 reliably and continuously at all cataloged conditions. Using the
1600 1135 0.92 1171 0.99 1207 1.07 1239 1.14 1271 1.21 full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
1760 1167 1.04 1203 1.12 1238 1.20 1271 1.28 1303 1.36 failure. Our product’s warranty will not be affected.
1920 1204 1.19 1238 1.27 1271 1.35 1303 1.43 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 50. Belt Drive Evaporator Fan Performance — 4 Tons — YSC048E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 583 0.18 653 0.23 715 0.28 772 0.33 825 0.39 874 0.45 919 0.51 962 0.57 1002 0.64 1041 0.70
1440 637 0.24 703 0.29 762 0.35 815 0.41 866 0.47 913 0.53 958 0.60 1000 0.67 1040 0.74 1077 0.81
1600 693 0.31 755 0.37 810 0.44 861 0.50 909 0.56 955 0.63 998 0.70 1039 0.78 1078 0.85 1115 0.92
1760 749 0.40 808 0.47 861 0.54 909 0.61 954 0.68 997 0.75 1039 0.82 1079 0.90 1117 0.98 1154 1.06
1920 807 0.50 861 0.58 912 0.66 959 0.73 1002 0.81 1043 0.88 1083 0.96 1121 1.04 1158 1.12 1194 1.21
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1079 0.76 1114 0.83 1149 0.89 1181 0.95 1213 1.02 Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
1440 1114 0.88 1148 0.95 1182 1.02 1216 1.09 1248 1.16 reliably and continuously at all cataloged conditions. Using the
1600 1151 1.00 1186 1.08 1218 1.16 1251 1.24 1281 1.31 full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor
1760 1189 1.14 1224 1.22 1256 1.31 1287 1.39 1319 1.48 failure. Our product’s warranty will not be affected.
1920 1229 1.29 1263 1.38 1295 1.47 — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 53
Performance Data
(4 Tons Standard Efficiency)

Table 51. Belt Drive Evaporator Fan Performance — 4 Tons — WSC048E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 613 0.20 672 0.24 725 0.29 778 0.34 830 0.39 879 0.45 923 0.51 965 0.56 1005 0.63
1440 592 0.20 657 0.25 716 0.30 765 0.35 812 0.40 859 0.46 906 0.52 952 0.58 995 0.65 1034 0.71
1600 644 0.26 703 0.32 760 0.37 809 0.43 853 0.49 895 0.54 936 0.60 980 0.67 1023 0.74 1062 0.81
1760 696 0.34 751 0.39 804 0.46 853 0.52 897 0.58 936 0.64 975 0.71 1012 0.77 1052 0.84 1091 0.91
1920 750 0.43 801 0.49 850 0.55 897 0.62 941 0.70 980 0.76 1017 0.83 1052 0.89 1087 0.96 1122 1.04
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1043 0.69 1080 0.75 1117 0.81 1152 0.88 1185 0.94 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1071 0.78 1107 0.84 1142 0.91 1176 0.98 1208 1.05 Using the full horsepower range of our fan motors as shown in our
1600 1101 0.88 1137 0.95 1171 1.03 1205 1.10 1237 1.17 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1129 0.99 1165 1.07 1200 1.14 1234 1.23 1266 1.31
1920 1157 1.11 1193 1.19 1227 1.27 1262 1.36 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 52. Belt Drive Evaporator Fan Performance — 4 Tons — WSC048E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 627 0.20 696 0.26 757 0.31 810 0.37 859 0.42 902 0.48 943 0.54 981 0.60 1019 0.66
1440 601 0.20 670 0.26 736 0.32 794 0.38 848 0.44 896 0.50 941 0.57 982 0.63 1020 0.70 1056 0.76
1600 653 0.27 715 0.32 776 0.39 834 0.45 886 0.52 935 0.59 979 0.66 1020 0.73 1059 0.80 1095 0.87
1760 706 0.34 763 0.40 820 0.47 874 0.54 925 0.61 972 0.69 1017 0.77 1058 0.84 1096 0.92 1134 1.00
1920 759 0.43 813 0.50 865 0.57 916 0.64 965 0.72 1011 0.80 1054 0.88 1096 0.97 1135 1.05 1172 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1054 0.71 1089 0.77 1122 0.83 1156 0.90 1187 0.97 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1090 0.82 1125 0.89 1157 0.96 1189 1.02 1220 1.09 Using the full horsepower range of our fan motors as shown in our
1600 1130 0.95 1162 1.02 1195 1.09 1225 1.16 1255 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1168 1.08 1201 1.15 1233 1.24 1263 1.31 1292 1.39
1920 1206 1.22 1239 1.30 1272 1.39 1302 1.47 — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

54 RT-PRC023-EN
Performance Data
(5 Tons Standard Efficiency)

Table 53. Belt Drive Evaporator Fan Performance — 5 Tons — TSC060E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 697 0.31 751 0.37 800 0.42 846 0.48 888 0.53 929 0.59 967 0.64 1005 0.71 1041 0.77
1800 704 0.35 758 0.41 808 0.47 854 0.53 898 0.59 938 0.66 977 0.72 1015 0.78 1050 0.85 1085 0.91
2000 771 0.46 820 0.53 866 0.60 910 0.67 951 0.73 991 0.80 1028 0.87 1064 0.94 1098 1.01 1131 1.08
2200 838 0.60 883 0.68 926 0.75 968 0.83 1007 0.90 1044 0.97 1081 1.05 1115 1.12 1148 1.20 1180 1.28
2400 906 0.77 948 0.85 989 0.93 1027 1.01 1065 1.09 1101 1.17 1135 1.25 1168 1.34 1200 1.42 1232 1.50
Continued For Standard Evaporator Fan Speed (RPM), reference Table 123.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 128 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1075 0.83 1110 0.90 1142 0.96 1176 1.03 1208 1.10 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1118 0.98 1151 1.05 1182 1.12 1212 1.19 1243 1.26 Using the full horsepower range of our fan motors as shown in our
2000 1163 1.15 1194 1.22 1225 1.30 1255 1.37 1283 1.45 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1211 1.35 1241 1.43 — — — — — —
2400 — — — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 54. Belt Drive Evaporator Fan Performance — 5 Tons — TSC060E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 707 0.31 763 0.37 815 0.42 862 0.48 905 0.54 946 0.60 984 0.65 1020 0.71 1056 0.78
1800 715 0.36 768 0.41 819 0.47 868 0.54 914 0.60 957 0.67 996 0.73 1034 0.79 1068 0.86 1103 0.92
2000 783 0.47 831 0.54 878 0.60 924 0.67 967 0.74 1009 0.81 1049 0.89 1085 0.96 1119 1.03 1152 1.10
2200 852 0.61 896 0.68 939 0.75 982 0.83 1023 0.90 1063 0.98 1100 1.06 1137 1.14 1172 1.22 1203 1.30
2400 921 0.78 963 0.86 1002 0.94 1041 1.01 1080 1.09 1118 1.18 1153 1.26 1189 1.35 1222 1.43 — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1091 0.84 1124 0.90 1156 0.97 1189 1.04 1220 1.11 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1135 0.99 1168 1.06 1199 1.13 1230 1.20 1260 1.27 Using the full horsepower range of our fan motors as shown in our
2000 1184 1.17 1215 1.24 1245 1.32 1273 1.39 1302 1.47 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1235 1.38 1264 1.45 — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 55
Performance Data
(5 Tons Standard Efficiency)

Table 55. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 699 0.31 755 0.36 805 0.42 849 0.47 891 0.53 932 0.58 971 0.64 1008 0.70 1046 0.76 1081 0.82
1800 773 0.42 823 0.48 871 0.54 914 0.60 953 0.67 991 0.73 1027 0.79 1063 0.86 1097 0.92 1131 0.98
2000 847 0.56 894 0.63 938 0.70 979 0.77 1018 0.83 1053 0.90 1087 0.97 1120 1.04 1153 1.11 1185 1.18
2200 923 0.73 966 0.81 1007 0.88 1046 0.96 1083 1.03 1118 1.10 1151 1.18 1182 1.26 1212 1.34 1242 1.41
2400 999 0.93 1039 1.01 1077 1.10 1114 1.18 1150 1.26 1183 1.34 1215 1.42 1245 1.50 — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1115 0.88 1149 0.95 1182 1.01 1213 1.08 1246 1.15 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1163 1.05 1196 1.12 1228 1.19 1257 1.26 1288 1.33 Using the full horsepower range of our fan motors as shown in our
2000 1215 1.25 1246 1.32 1276 1.40 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1271 1.49 — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.

Table 56. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 667 0.27 724 0.33 778 0.38 829 0.43 877 0.49 923 0.55 966 0.61 1006 0.68 1046 0.74 1082 0.80
1800 737 0.38 788 0.43 837 0.49 885 0.55 930 0.61 973 0.68 1014 0.74 1054 0.81 1092 0.88 1127 0.95
2000 807 0.50 854 0.57 900 0.63 943 0.69 986 0.76 1026 0.83 1066 0.90 1103 0.97 1140 1.05 1174 1.12
2200 879 0.65 922 0.72 963 0.79 1004 0.86 1044 0.94 1083 1.01 1119 1.08 1155 1.16 1191 1.24 1225 1.32
2400 951 0.83 991 0.91 1029 0.99 1067 1.06 1104 1.14 1141 1.22 1176 1.30 1210 1.38 1243 1.46 — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1117 0.87 1152 0.94 1185 1.00 1218 1.07 1247 1.14 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1162 1.02 1196 1.10 1228 1.17 1259 1.24 1290 1.32 Using the full horsepower range of our fan motors as shown in our
2000 1209 1.20 1242 1.28 1274 1.36 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1257 1.40 1290 1.49 — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.

56 RT-PRC023-EN
Performance Data
(5 Tons Standard Efficiency)

Table 57. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 709 0.32 766 0.37 818 0.43 862 0.48 902 0.54 944 0.60 985 0.66 1025 0.72 1063 0.79 1100 0.86
1800 784 0.44 835 0.50 885 0.56 928 0.62 967 0.68 1003 0.75 1040 0.81 1077 0.88 1113 0.95 1149 1.02
2000 859 0.58 907 0.65 952 0.72 995 0.79 1034 0.86 1069 0.93 1101 0.99 1134 1.07 1168 1.14 1201 1.22
2200 936 0.76 980 0.84 1022 0.92 1062 0.99 1101 1.07 1136 1.14 1167 1.21 1198 1.29 1228 1.37 1257 1.44
2400 1013 0.97 1054 1.05 1093 1.14 1131 1.22 1168 1.31 1202 1.39 1234 1.47 — — — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1134 0.92 1168 0.99 1200 1.06 1232 1.12 1262 1.19 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1184 1.10 1217 1.17 1247 1.24 1279 1.32 — — Using the full horsepower range of our fan motors as shown in our
2000 1233 1.29 1265 1.37 1297 1.46 — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 — — — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.

Table 58. Belt Drive Evaporator Fan Performance — 5 Tons — YSC060E3,E4,EW*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 706 0.30 762 0.36 813 0.41 862 0.47 908 0.53 951 0.59 993 0.65 1031 0.71 1068 0.78 1104 0.84
1800 780 0.42 832 0.48 879 0.54 924 0.60 968 0.67 1009 0.73 1049 0.80 1086 0.87 1121 0.94 1156 1.01
2000 855 0.56 903 0.63 947 0.69 989 0.76 1028 0.83 1068 0.90 1106 0.97 1143 1.05 1177 1.12 1210 1.20
2200 930 0.72 976 0.80 1017 0.88 1056 0.95 1093 1.03 1130 1.10 1166 1.18 1200 1.26 1235 1.34 1268 1.42
2400 1006 0.92 1049 1.01 1088 1.09 1126 1.17 1160 1.25 1194 1.33 1228 1.42 1261 1.50 — — — —
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1140 0.91 1173 0.98 1207 1.05 1240 1.12 1270 1.19 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1189 1.08 1221 1.15 1253 1.22 1284 1.30 — — Using the full horsepower range of our fan motors as shown in our
2000 1243 1.28 1274 1.35 — — — — — — tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 — — — — — — — — — —
2400 — — — — — — — — — —
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 57
Performance Data
(5 Tons Standard Efficiency)

Table 59. Belt Drive Evaporator Fan Performance — 5 Tons — WSC060E3,E4,EW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — — — 606 0.26 660 0.31 710 0.36 757 0.41 802 0.46 846 0.52 889 0.58 930 0.65
1800 — — 582 0.27 640 0.32 692 0.38 740 0.43 785 0.49 827 0.55 868 0.60 908 0.67 947 0.73
2000 564 0.28 622 0.34 675 0.40 725 0.46 772 0.52 815 0.58 856 0.64 895 0.71 933 0.77 969 0.84
2200 608 0.36 663 0.42 712 0.49 760 0.55 805 0.62 847 0.69 886 0.76 924 0.82 961 0.89 995 0.96
2400 653 0.45 705 0.52 752 0.59 796 0.66 839 0.74 880 0.81 919 0.88 955 0.96 990 1.03 1024 1.11
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 968 0.71 1005 0.78 1040 0.84 1076 0.91 1108 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 986 0.80 1022 0.87 1058 0.94 1092 1.02 1124 1.09 Using the full horsepower range of our fan motors as shown in our
2000 1005 0.91 1041 0.98 1075 1.05 1110 1.13 1142 1.21 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1030 1.03 1063 1.11 1095 1.18 1127 1.26 1160 1.34
2400 1057 1.18 1089 1.26 1120 1.34 1151 1.42 1180 1.49
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 60. Belt Drive Evaporator Fan Performance — 5 Tons — WSC060E3,E4,EW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 573 0.23 642 0.29 705 0.35 764 0.42 821 0.49 873 0.56 919 0.64 963 0.71 1004 0.79
1800 — — 611 0.29 674 0.36 733 0.43 790 0.49 843 0.57 894 0.65 943 0.73 988 0.81 1030 0.90
2000 593 0.31 651 0.37 710 0.44 766 0.52 819 0.59 869 0.66 917 0.74 965 0.83 1010 0.92 1053 1.01
2200 641 0.40 694 0.46 747 0.54 799 0.62 850 0.70 898 0.78 945 0.86 988 0.95 1032 1.04 1075 1.14
2400 690 0.50 738 0.57 787 0.65 836 0.74 884 0.82 929 0.91 974 1.00 1016 1.09 1057 1.18 1096 1.27
Continued For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 114 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1042 0.86 1076 0.93 1109 1.01 1141 1.08 1171 1.16 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1069 0.98 1106 1.06 1140 1.15 1173 1.23 1205 1.31 Using the full horsepower range of our fan motors as shown in our
2000 1094 1.10 1131 1.20 1168 1.29 1203 1.38 1235 1.48 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1116 1.24 1154 1.34 1191 1.44 — — — —
2400 1136 1.38 1175 1.48 — — — — — —
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

58 RT-PRC023-EN
Performance Data
(6 Tons Standard Efficiency)

Table 61. Belt Drive Evaporator Fan Performance 6 Tons TSC072E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — — — 588 0.35 643 0.43 693 0.50 738 0.57 782 0.65 823 0.73 862 0.81 900 0.89
2160 — — 564 0.37 618 0.44 672 0.52 721 0.60 765 0.68 806 0.76 847 0.85 885 0.93 922 1.02
2400 — — 602 0.47 652 0.54 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2640 589 0.50 642 0.59 690 0.67 734 0.76 779 0.85 822 0.95 864 1.05 901 1.15 936 1.24 971 1.34
2880 634 0.63 682 0.74 728 0.82 770 0.91 810 1.01 851 1.11 892 1.22 930 1.33 965 1.44 999 1.54
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 937 0.98 971 1.06 1004 1.14 1037 1.22 1068 1.30 1097 1.38 1127 1.47 1154 1.55 1182 1.64 1210 1.74
2160 957 1.12 991 1.21 1024 1.30 1057 1.40 1087 1.49 1117 1.58 1146 1.67 1174 1.76 1201 1.85 1227 1.95
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68 1137 1.78 1166 1.89 1194 1.99 1220 2.08 1248 2.19
2640 1004 1.44 1036 1.55 1067 1.65 1098 1.77 1129 1.88 1158 1.99 1185 2.10 1214 2.22 — — — —
2880 1030 1.64 1061 1.75 1092 1.86 1123 1.98 1151 2.09 1181 2.22 — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or
options are included in pressure drop data. Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial
equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horse
power range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not
be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.

Table 62. Belt Drive Evaporator Fan Performance 6 Tons TSC072E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 580 0.33 641 0.41 692 0.47 738 0.54 783 0.63 827 0.71 870 0.79 912 0.88 951 0.96
2160 578 0.37 623 0.43 679 0.51 731 0.59 775 0.67 817 0.74 857 0.83 896 0.93 935 1.02 974 1.12
2400 633 0.49 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2640 688 0.64 725 0.71 762 0.79 808 0.87 853 0.98 894 1.09 931 1.17 966 1.26 1000 1.36 1032 1.47(ii)
2880 743 0.81 778 0.90 811 0.98 848 1.06 891 1.16 932 1.28 970 1.40 1004 1.49 1037 1.59 1068 1.69
1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor)
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 990 1.05 1026 1.14 1062 1.24 1096 1.33 1130 1.43 1160 1.52 1190 1.61 1218 1.71 1247 1.80 1273 1.90
2160 1010 1.21 1047 1.31 1082 1.40 1116 1.50 1150 1.61 1182 1.71 1211 1.81 1242 1.92 1271 2.03 1298 2.14
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81 1201 1.92 1232 2.03 1261 2.14 1291 2.26 — —
2640 1065 1.59 1097 1.71 1129 1.82 1161 1.93 1192 2.05 1223 2.16 1252 2.27 — — — — — —
2880 1099 1.80 1130 1.93 1159 2.05 1188 2.18 1217 2.30 — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or
options are included in pressure drop data. Refer to Table 114 to determine additional static pressure drop due to other options accessories. 1-HP Fan Motor
Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 2-HP Oversized Motor & Field Supplied Drive
(iii) Field Supplied Fan Sheave AK56 and Belt AX30.

RT-PRC023-EN 59
Performance Data
(6 Tons Standard Efficiency)

Table 63. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — — — 597 0.37 652 0.44 700 0.51 745 0.58 788 0.66 829 0.74 869 0.82 906 0.91
2160 — — 575 0.38 629 0.46 683 0.54 730 0.62 774 0.70 815 0.78 854 0.86 893 0.95 929 1.04
2400 561 0.41 615 0.49 664 0.57 714 0.65 762 0.74 805 0.83 844 0.92 882 1.01 918 1.10 954 1.20
2640 606 0.53 657 0.62 703 0.70 747 0.79 792 0.88 835 0.98 875 1.08 912 1.18 947 1.27 980 1.37
2880 651 0.67 699 0.77 743 0.85 785 0.94 825 1.05 867 1.15 906 1.26 943 1.37 978 1.47 1010 1.58
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 941 0.99 977 1.07 1009 1.15 1041 1.23 1073 1.32 1103 1.40 1132 1.49 1159 1.57 1187 1.66 1213 1.75
2160 964 1.13 997 1.23 1031 1.32 1061 1.41 1093 1.50 1123 1.60 1151 1.69 1179 1.78 1207 1.87 1234 1.97
2400 988 1.29 1020 1.39 1054 1.50 1085 1.60 1114 1.70 1143 1.80 1171 1.90 1200 2.01 1227 2.11 1254 2.21
2640 1014 1.47 1046 1.58 1077 1.69 1107 1.80 1138 1.91 1166 2.02 1193 2.13 1222 2.25 — — — —
2880 1042 1.68 1073 1.79 1103 1.90 1132 2.02 1162 2.14 1190 2.26 — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.

Table 64. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 574 0.34 631 0.41 681 0.48 727 0.55 771 0.63 814 0.71 853 0.79 892 0.87 928 0.95
2160 562 0.36 616 0.44 671 0.52 719 0.60 763 0.68 805 0.76 845 0.84 884 0.93 921 1.02 957 1.11
2400 612 0.48 662 0.56 711 0.65 759 0.74 802 0.83 842 0.91 879 1.00 916 1.09 951 1.19 986 1.29
2640 663 0.63 709 0.71 754 0.80 798 0.90 842 1.00 881 1.10 917 1.19 951 1.29 986 1.39 1018 1.49(ii)
2880 715 0.80 758 0.88 799 0.98 840 1.08 880 1.19 920 1.30 955 1.41 990 1.51 1022 1.62 1053 1.72
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 963 1.04 997 1.12 1028 1.20 1061 1.28 1090 1.36 1119 1.45 1149 1.54 1177 1.63 1203 1.71 1229 1.80
2160 990 1.21 1023 1.30 1055 1.39 1086 1.48 1115 1.57 1144 1.66 1173 1.76 1200 1.85 1227 1.95 1253 2.04
2400 1019 1.39 1051 1.49 1083 1.60 1113 1.70 1141 1.80 1171 1.90 1199 2.01 1225 2.10 1252 2.20 — —
2640 1050 1.59 1081 1.70 1111 1.81 1141 1.93 1170 2.04 1198 2.15 1226 2.27 — — — — — —
2880 1084 1.83 1114 1.94 1143 2.06 1172 2.18 1199 2.30 — — — — — — — — — —
2-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor).

60 RT-PRC023-EN
Performance Data
(6 Tons Standard Efficiency)

Table 65. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 — — 591 0.34 649 0.42 699 0.48 745 0.56 789 0.64 834 0.72 877 0.81 918 0.89 957 0.97
2160 587 0.38 633 0.44 690 0.52 740 0.61 784 0.68 825 0.76 865 0.85 904 0.95 943 1.04 981 1.13
2400 643 0.51 682 0.58 732 0.65 781 0.75 825 0.84 864 0.92 902 1.01 938 1.11 974 1.21 1010 1.32(ii)
2640 700 0.66 736 0.74 775 0.81 822 0.90 866 1.01 906 1.11 942 1.20 976 1.29 1009 1.40 1042 1.51
2880 756 0.84 790 0.93 823 1.01 864 1.09 907 1.20 947 1.32 983 1.43 1017 1.53 1048 1.62 1080 1.73
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 996 1.06 1033 1.16 1067 1.25 1102 1.35 1134 1.44 1165 1.53 1195 1.63 1223 1.72 1251 1.82 1277 1.91
2160 1018 1.23 1054 1.32 1090 1.42 1123 1.52 1156 1.63 1188 1.73 1218 1.84 1247 1.94 1276 2.05 1304 2.16
2400 1044 1.42 1079 1.52 1112 1.62 1145 1.73 1177 1.83 1208 1.94 1240 2.06 1268 2.17 1298 2.29 — —
2640 1075 1.62 1107 1.74 1139 1.85 1170 1.96 1201 2.08 1232 2.19 — — — — — — — —
2880 1111 1.85 1140 1.97 1169 2.09 1200 2.22 — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied High Static Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 114
to determine additional static pressure drop due to other options/accessories. 1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor
Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive (or 2-HP Oversized Motor).
(iii) Field Supplied Fan Sheave AK56 and Belt AX30 required.

Table 66. Belt Drive Evaporator Fan Performance 6 Tons with Gas Heat YSC072E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1920 565 0.31 627 0.39 680 0.46 727 0.52 772 0.61 816 0.69 859 0.77 902 0.86 942 0.94 981 1.03
2160 621 0.43 677 0.50 729 0.59 774 0.66 816 0.74 856 0.83 895 0.93 934 1.02 973 1.11 1009 1.21(ii)
2400 680 0.57 729 0.65 778 0.74 823 0.84 862 0.92 900 1.00 936 1.10 972 1.20 1006 1.31 1041 1.41
2640 741 0.75 782 0.82 828 0.92 872 1.03 911 1.13 947 1.21 981 1.31 1014 1.41 1048 1.53 1079 1.64
2880 802 0.95 837 1.04 880 1.13 921 1.24 960 1.36 995 1.47 1028 1.56 1060 1.66 1091 1.77 1122 1.89
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor & Drive)
1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78 1268 1.88 1293 1.97
2160 1045 1.30 1081 1.40 1114 1.50 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03 1298 2.13 1324 2.24
2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28 — — — —
2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21 — — — — — — — — — —
2880 1151 2.02 1180 2.14 1209 2.27 — — — — — — — — — — — — — —
2-HP Oversized Motor & Drive 2-HP Oversized Motor & Field Supplied High Static Drive(iii)
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories. 1-HP Fan Motor Heat (MBH) = 2.829 x Fan
BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000. Factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(ii) 1-HP Standard Motor & High Static Drive Kit (or 2-HP Oversized Motor).
(iii) Field Supplied Fan Sheave AK56 and Belt AX30 required.

RT-PRC023-EN 61
Performance Data
(7½ Tons Standard Efficiency)

Table 67. Belt Drive Evaporator Fan Performance 7½ Tons TSC092E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit(i)
2400 — — 487 0.32 536 0.40 583 0.50 627 0.61 669 0.72 708 0.83 743 0.95 776 1.08 808 1.21
2700 — — 522 0.41 569 0.50 611 0.60 653 0.71 693 0.83 731 0.95 768 1.07 801 1.20 832 1.33
3000 — — 559 0.51 604 0.61 643 0.71 682 0.83 719 0.95 755 1.08 791 1.21 824 1.35 856 1.48
3300 — — 599 0.63 639 0.74 678 0.86 713 0.97 748 1.09 783 1.23 815 1.37 848 1.52 880 1.66
3600 601 0.68 640 0.79 675 0.89 713 1.02 748 1.14 780 1.26 811 1.40 844 1.55 874 1.70 904 1.86
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2400 839 1.34 868 1.48 898 1.61 926 1.75 953 1.89 980 2.04 1006 2.18 1032 2.34 1056 2.49 1080 2.64
2700 862 1.48 891 1.62 918 1.77 946 1.92 971 2.07 998 2.23 1023 2.38 1049 2.54 1074 2.70 1097 2.86
3000 886 1.63 915 1.78 942 1.93 968 2.09 994 2.25 1019 2.42 1044 2.59 1067 2.75 1092 2.93 1115 3.09
3300 910 1.81 939 1.96 967 2.12 993 2.28 1019 2.45 1043 2.62 1066 2.79 1091 2.98 1113 3.15 1136 3.34
3600 933 2.01 962 2.17 990 2.33 1016 2.49 1042 2.66 1067 2.84 1091 3.02 1114 3.21 1137 3.39 1158 3.58
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.

Table 68. Belt Drive Evaporator Fan Performance 7½ Tons TSC092E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Low Static Drive Accessory Kit(i)
2400 502 0.36 552 0.43 603 0.52 653 0.63 707 0.75 754 0.88 792 0.99 825 1.09 857 1.19 886 1.30
2700 554 0.49 595 0.56 644 0.66 686 0.77 732 0.89 780 1.03 824 1.17 863 1.30 895 1.42 925 1.54
3000 605 0.65 644 0.73 684 0.82 726 0.94 765 1.06 806 1.20 849 1.35 891 1.51 929 1.66 962 1.80
3300 658 0.84 694 0.93 728 1.02 767 1.15 805 1.28 840 1.40 876 1.55 916 1.71 955 1.89 991 2.06
3600 711 1.07 746 1.18 776 1.27 809 1.38 846 1.52 880 1.66 912 1.80 943 1.95 980 2.13 1016 2.30
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 913 1.40 941 1.51 966 1.61 991 1.71 1017 1.82 1040 1.92 1064 2.04 1087 2.14 1110 2.26 1132 2.37
2700 954 1.66 981 1.77 1006 1.89 1030 2.00 1054 2.12 1077 2.24 1100 2.36 1121 2.47 1144 2.60 1164 2.71
3000 992 1.94 1019 2.07 1045 2.20 1069 2.32 1094 2.46 1116 2.58 1138 2.71 1160 2.84 1181 2.97 1202 3.10
3300 1025 2.22 1055 2.38 1082 2.53 1108 2.67 1132 2.82 1156 2.96 1178 3.11 1200 3.25 1221 3.39 — —
3600 1052 2.50 1085 2.69 1117 2.88 1144 3.05 1170 3.21 1193 3.37 — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x
Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.

62 RT-PRC023-EN
Performance Data
(7½ Tons Standard Efficiency)

Table 69. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — — — — — 613 0.58 656 0.68 696 0.79 732 0.91 765 1.03 798 1.16 829 1.30
2700 — — — — 605 0.58 647 0.69 687 0.81 726 0.93 762 1.05 796 1.18 828 1.32 857 1.45
3000 — — 606 0.62 645 0.72 684 0.83 721 0.96 758 1.09 792 1.22 826 1.36 858 1.49 888 1.64
3300 609 0.66 650 0.77 688 0.89 723 1.00 758 1.13 792 1.27 825 1.41 857 1.56 888 1.70 918 1.85
3600 658 0.84 695 0.96 731 1.08 764 1.20 796 1.33 828 1.47 859 1.63 890 1.79 920 1.94 949 2.10
2-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 858 1.43 888 1.57 917 1.71 945 1.85 971 1.99 998 2.14 1023 2.28 1048 2.44 1072 2.59 1095 2.75
2700 886 1.60 915 1.75 942 1.90 969 2.05 995 2.21 1020 2.36 1045 2.51 1069 2.67 1093 2.83 1117 3.00
3000 916 1.79 944 1.94 970 2.10 995 2.26 1020 2.43 1044 2.59 1069 2.76 1092 2.93 1116 3.10 1139 3.27
3300 947 2.01 974 2.16 1000 2.33 1026 2.50 1050 2.67 1073 2.84 1097 3.02 1119 3.20 1141 3.38 — —
3600 976 2.25 1004 2.42 1030 2.58 1056 2.76 1080 2.94 1103 3.12 1126 3.30 — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table 70. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — — — — — 623 0.60 664 0.70 703 0.82 739 0.93 773 1.06 804 1.19 835 1.32
2700 — — — — 617 0.61 658 0.73 698 0.84 736 0.96 771 1.08 804 1.21 835 1.35 865 1.49
3000 — — 619 0.65 658 0.75 696 0.87 733 1.00 770 1.13 804 1.26 837 1.40 868 1.54 897 1.69
3300 625 0.70 666 0.82 702 0.93 737 1.05 771 1.19 805 1.33 838 1.47 870 1.62 900 1.76 929 1.91
3600 675 0.89 713 1.02 747 1.14 779 1.26 811 1.40 843 1.55 874 1.70 904 1.86 934 2.02 962 2.17
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 864 1.46 895 1.60 923 1.74 951 1.88 977 2.02 1003 2.17 1028 2.32 1053 2.47 1078 2.63 1100 2.78
2700 894 1.64 921 1.79 948 1.94 974 2.09 1001 2.24 1027 2.40 1052 2.56 1076 2.72 1100 2.88 1124 3.05
3000 925 1.83 952 1.99 978 2.15 1004 2.32 1029 2.48 1052 2.65 1076 2.82 1100 2.99 1123 3.15 1146 3.33
3300 958 2.06 984 2.22 1010 2.39 1035 2.56 1059 2.73 1082 2.91 1105 3.09 1128 3.28 — — — —
3600 990 2.33 1017 2.50 1043 2.66 1067 2.84 1091 3.02 1114 3.20 1137 3.39 — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

RT-PRC023-EN 63
Performance Data
(7½ Tons Standard Efficiency)

Table 71. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — 599 0.52 650 0.62 703 0.75 751 0.87 789 0.98 823 1.08 855 1.19 885 1.29 912 1.39
2700 604 0.58 651 0.68 694 0.79 741 0.91 789 1.06 832 1.19 868 1.32 900 1.44 931 1.56 959 1.68
3000 661 0.77 705 0.88 744 1.00 783 1.12 826 1.26 869 1.42 909 1.58 945 1.73 976 1.86 1004 1.99
3300 719 1.00 758 1.11 797 1.25 832 1.37 867 1.51 907 1.68 946 1.85 983 2.02 1017 2.18 1048 2.34
3600 779 1.28 813 1.39 850 1.54 883 1.68 915 1.82 948 1.97 984 2.15 1020 2.33 1055 2.52 1088 2.71
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 939 1.50 965 1.60 990 1.71 1014 1.81 1039 1.92 1063 2.03 1085 2.14 1108 2.25 1131 2.36 1154 2.49
2700 985 1.79 1010 1.91 1034 2.03 1058 2.14 1081 2.26 1104 2.38 1126 2.50 1148 2.62 1169 2.74 1190 2.86
3000 1031 2.12 1056 2.25 1081 2.39 1104 2.51 1127 2.65 1148 2.77 1169 2.90 1190 3.03 1210 3.16 1231 3.30
3300 1077 2.50 1102 2.64 1127 2.78 1151 2.93 1174 3.07 1194 3.21 1216 3.36 — — — — — —
3600 1120 2.89 1146 3.06 1172 3.22 1195 3.38 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table 72. Belt Drive Evaporator Fan Performance 7½ Tons with Gas Heat YSC092E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2400 — — 613 0.54 666 0.66 718 0.78 762 0.90 799 1.01 833 1.11 864 1.22 893 1.32 920 1.42
2700 621 0.61 667 0.72 710 0.83 759 0.97 804 1.10 846 1.24 880 1.36 911 1.48 941 1.60 968 1.72
3000 680 0.81 723 0.93 761 1.05 802 1.18 845 1.33 888 1.49 925 1.64 959 1.79 988 1.92 1016 2.05
3300 740 1.06 780 1.19 816 1.31 850 1.45 889 1.60 928 1.77 966 1.94 1002 2.11 1036 2.28 1063 2.42
3600 800 1.35 837 1.49 872 1.63 904 1.77 935 1.91 971 2.08 1007 2.27 1043 2.45 1077 2.64 1108 2.83
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2400 946 1.53 972 1.64 997 1.74 1022 1.84 1045 1.95 1069 2.06 1092 2.17 1115 2.28 1137 2.40 1160 2.52
2700 994 1.84 1019 1.95 1043 2.07 1066 2.18 1089 2.30 1112 2.42 1134 2.54 1155 2.66 1177 2.78 1197 2.90
3000 1043 2.18 1067 2.31 1091 2.44 1114 2.57 1137 2.70 1158 2.83 1178 2.96 1200 3.09 1220 3.22 1240 3.35
3300 1090 2.57 1116 2.72 1140 2.86 1162 3.00 1185 3.15 1206 3.29 1227 3.43 — — — — — —
3600 137 3.00 1163 3.17 1188 3.33 — — — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

64 RT-PRC023-EN
Performance Data
(8½ Tons Standard Efficiency)

Table 73. Belt Drive Evaporator Fan Performance 8½ Tons TSC102E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive Accessory Kit(i)
2720 — — 539 0.44 584 0.53 626 0.64 668 0.76 708 0.88 746 1.00 781 1.12 814 1.26 845 1.40
3060 — — 583 0.58 626 0.68 665 0.78 703 0.90 740 1.04 775 1.17 810 1.30 843 1.44 875 1.58
3400 — — 628 0.72 669 0.84 706 0.96 741 1.08 775 1.21 809 1.36 841 1.51 873 1.65 904 1.81
3740 641 0.81 677 0.92 713 1.04 749 1.17 781 1.30 813 1.43 845 1.58 875 1.73 905 1.89 935 2.06
4080 693 1.03 726 1.15 758 1.27 792 1.41 824 1.56 854 1.69 883 1.83 912 1.99 940 2.16 968 2.33
2-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 874 1.54 904 1.69 930 1.84 958 2.00 983 2.14 1010 2.30 1035 2.46 1060 2.62 1084 2.78 1109 2.95
3060 905 1.73 933 1.89 960 2.05 986 2.20 1010 2.37 1035 2.54 1059 2.71 1083 2.89 1107 3.06 1131 3.24
3400 933 1.96 962 2.11 990 2.27 1016 2.44 1041 2.62 1065 2.79 1089 2.97 1112 3.15 1134 3.34 — —
3740 964 2.22 992 2.39 1018 2.55 1045 2.72 1071 2.90 1095 3.08 1118 3.26 1141 3.45 — — — —
4080 995 2.51 1023 2.69 1048 2.86 1075 3.05 1100 3.23 1124 3.41 — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan
BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR009A Required.

Table 74. Belt Drive Evaporator Fan Performance 8½ Tons TSC102E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive Accessory Kit(i)
2720 570 0.52 612 0.60 660 0.71 703 0.81 751 0.95 798 1.09 841 1.23 877 1.36 909 1.48 939 1.60
3060 631 0.72 667 0.80 709 0.91 750 1.03 788 1.15 830 1.29 873 1.45 914 1.62 951 1.77 983 1.92
3400 692 0.96 726 1.05 760 1.15 800 1.29 836 1.42 870 1.56 907 1.71 945 1.88 984 2.06 1020 2.24
3740 754 1.26 786 1.36 815 1.46 850 1.59 886 1.74 918 1.88 949 2.03 980 2.19 1015 2.37 1052 2.57
4080 817 1.61 848 1.72 874 1.83 903 1.95 935 2.10 968 2.26 998 2.42 1026 2.58 1054 2.75 1085 2.94
2-HP Standard Motor & Drive 3-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 967 1.72 994 1.84 1018 1.96 1042 2.07 1066 2.19 1089 2.31 1112 2.43 1134 2.55 1155 2.67 1176 2.79
3080 1012 2.06 1039 2.19 1065 2.32 1090 2.46 1113 2.59 1136 2.73 1158 2.86 1179 2.99 1199 3.12 1220 3.26
3400 1052 2.41 1083 2.58 1109 2.73 1135 2.88 1159 3.04 1183 3.19 1204 3.33 — — — — — —
3740 1086 2.77 1119 2.96 1149 3.15 1178 3.34 — — — — — — — — — — — —
4080 1117 3.14 1151 3.36 — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan
BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR009A required.

RT-PRC023-EN 65
Performance Data
(8½ Tons Standard Efficiency)

Table 75. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*L Low Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — — — 621 0.62 662 0.74 703 0.86 741 0.98 777 1.11 810 1.24 841 1.38 871 1.52
3060 587 0.58 630 0.69 668 0.79 707 0.92 743 1.05 779 1.18 814 1.32 846 1.45 878 1.60 907 1.75
3400 643 0.77 683 0.89 718 1.00 753 1.13 787 1.26 820 1.41 853 1.56 884 1.71 915 1.86 944 2.02
3740 699 0.99 736 1.12 770 1.25 802 1.38 833 1.52 864 1.67 894 1.83 925 2.00 953 2.16 982 2.33
4080 757 1.26 790 1.40 823 1.55 853 1.69 882 1.83 910 1.98 938 2.15 967 2.32 994 2.50 1021 2.68
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 927 1.82 954 1.97 980 2.12 1006 2.28 1032 2.44 1057 2.60 1082 2.76 1105 2.92 1129 3.09
3060 936 1.90 962 2.06 989 2.22 1014 2.39 1039 2.56 1062 2.73 1085 2.90 1109 3.07 1133 3.25 1155 3.43
3400 973 2.17 999 2.34 1025 2.51 1050 2.68 1074 2.86 1097 3.04 1120 3.22 1142 3.41 — — — —
3740 1010 2.50 1036 2.66 1062 2.84 1087 3.01 1110 3.19 1134 3.39 — — — — — — — —
4080 1047 2.86 1073 3.04 1098 3.22 1123 3.40 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table 76. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*M Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — — — 623 0.63 664 0.75 704 0.87 742 0.99 778 1.11 811 1.24 842 1.38 872 1.53
3060 589 0.58 632 0.69 670 0.80 709 0.92 745 1.06 781 1.19 815 1.32 848 1.46 880 1.60 909 1.75
3400 645 0.77 685 0.89 721 1.01 755 1.13 789 1.27 822 1.42 854 1.57 886 1.72 916 1.87 945 2.02
3740 702 1.00 739 1.14 772 1.26 804 1.39 836 1.53 867 1.69 897 1.85 926 2.01 956 2.18 984 2.34
4080 759 1.27 793 1.42 826 1.56 856 1.70 884 1.84 913 2.00 941 2.16 969 2.34 996 2.52 1024 2.70
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
2720 900 1.67 928 1.82 955 1.98 982 2.14 1008 2.29 1033 2.45 1057 2.60 1083 2.77 1107 2.94 1129 3.10
3060 936 1.91 964 2.07 989 2.23 1015 2.39 1039 2.56 1063 2.73 1088 2.92 1111 3.09 1134 3.26 1157 3.44
3400 974 2.18 1001 2.35 1027 2.52 1051 2.69 1075 2.87 1098 3.05 1121 3.23 1144 3.42 — — — —
3740 1011 2.50 1038 2.68 1064 2.85 1089 3.03 1113 3.22 1135 3.40 — — — — — — — —
4080 1050 2.87 1076 3.05 1101 3.24 1126 3.43 — — — — — — — — — — — —
3-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

66 RT-PRC023-EN
Performance Data
(8½ Tons Standard Efficiency)

Table 77. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 — — 590 0.55 633 0.66 674 0.77 713 0.89 750 1.01 786 1.14 818 1.28 850 1.42 879 1.56
3060 602 0.62 643 0.72 682 0.83 719 0.96 756 1.09 791 1.23 825 1.36 857 1.50 889 1.65 917 1.80
3400 660 0.82 698 0.94 733 1.05 767 1.18 801 1.32 834 1.48 866 1.62 897 1.77 927 1.92 956 2.08
3740 718 1.06 754 1.19 787 1.32 818 1.45 849 1.60 880 1.76 910 1.92 939 2.08 968 2.24 996 2.41
4080 777 1.35 811 1.49 841 1.63 870 1.77 899 1.92 928 2.08 956 2.26 983 2.43 1011 2.61 1037 2.79
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 907 1.71 934 1.86 960 2.01 987 2.17 1014 2.33 1039 2.48 1063 2.64 1088 2.81 1112 2.97 1134 3.13
3060 945 1.95 971 2.11 997 2.28 1022 2.45 1047 2.62 1070 2.79 1094 2.96 1117 3.14 1141 3.31 — —
3400 985 2.24 1010 2.40 1036 2.58 1060 2.76 1084 2.93 1106 3.11 1130 3.31 — — — — — —
3740 1023 2.58 1049 2.75 1075 2.93 1099 3.11 1122 3.29 — — — — — — — — — —
4080 1063 2.96 1089 3.15 1114 3.34 — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table 78. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*L Low Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 622 0.62 669 0.73 711 0.84 760 0.97 807 1.12 849 1.26 884 1.38 915 1.50 944 1.62 972 1.74
3060 688 0.85 732 0.97 770 1.09 809 1.22 853 1.38 895 1.54 934 1.70 968 1.85 998 1.99 1026 2.13
3400 756 1.14 795 1.27 832 1.40 866 1.54 901 1.69 941 1.86 979 2.04 1015 2.22 1049 2.40 1079 2.56
3740 824 1.49 859 1.62 895 1.78 926 1.92 957 2.07 990 2.24 1025 2.42 1061 2.62 1095 2.82 1127 3.02
4080 893 1.90 925 2.05 958 2.21 988 2.37 1017 2.53 1046 2.70 1075 2.88 1108 3.08 1140 3.29 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 998 1.86 1024 1.98 1047 2.10 1071 2.22 1094 2.33 1115 2.45 1138 2.57 1159 2.69 1181 2.82 1201 2.94
3060 1053 2.26 1078 2.39 1102 2.53 1125 2.66 1146 2.79 1169 2.93 1190 3.06 1210 3.19 1230 3.32 1250 3.45
3400 1106 2.71 1131 2.86 1156 3.02 1179 3.16 1201 3.31 1223 3.45 — — — — — — — —
3740 1158 3.21 1185 3.39 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

RT-PRC023-EN 67
Performance Data
(8½ Tons Standard Efficiency)

Table 79. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*M Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i)
2720 625 0.62 671 0.73 714 0.84 763 0.98 809 1.13 851 1.27 885 1.39 917 1.51 946 1.63 974 1.75
3060 691 0.86 734 0.98 772 1.10 812 1.23 856 1.39 897 1.55 936 1.71 970 1.86 1001 2.00 1028 2.14
3400 759 1.15 798 1.28 835 1.41 868 1.55 904 1.70 943 1.87 982 2.05 1019 2.23 1052 2.41 1082 2.57
3740 827 1.50 863 1.64 898 1.79 930 1.94 960 2.09 994 2.26 1029 2.44 1064 2.64 1098 2.84 1130 3.03
4080 897 1.92 929 2.07 962 2.23 992 2.39 1021 2.55 1049 2.72 1079 2.90 1112 3.10 1144 3.31 — —
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 1000 1.87 1025 1.99 1048 2.10 1072 2.22 1095 2.34 1117 2.46 1139 2.58 1161 2.70 1182 2.82 1203 2.95
3060 1054 2.27 1080 2.41 1103 2.53 1126 2.67 1149 2.80 1170 2.93 1192 3.07 1211 3.20 1231 3.33 — —
3400 1108 2.73 1134 2.88 1158 3.03 1181 3.17 1204 3.33 — — — — — — — — — —
3740 1160 3.23 1187 3.41 — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

Table 80. Belt Drive Evaporator Fan Performance 8½ Tons with Gas Heat YSC102E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive(i) 2-HP Standard Motor & Drive
2720 640 0.66 684 0.77 729 0.89 778 1.03 823 1.17 863 1.31 896 1.43 926 1.55 955 1.67 982 1.79
3060 709 0.91 750 1.03 788 1.15 829 1.29 872 1.45 913 1.61 950 1.77 983 1.92 1011 2.05 1038 2.19
3400 778 1.21 817 1.35 851 1.48 885 1.62 924 1.78 963 1.96 1000 2.14 1035 2.30 1067 2.49 1095 2.65
3740 848 1.58 885 1.73 917 1.88 948 2.03 979 2.18 1014 2.36 1050 2.56 1084 2.76 1118 2.96 1148 3.15
4080 919 2.02 952 2.18 984 2.35 1012 2.50 1041 2.67 1070 2.84 1102 3.04 1135 3.25 — — — —
3-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive 3-HP Oversized Motor & Drive
2720 1007 1.90 1032 2.02 1056 2.14 1079 2.26 1101 2.38 1124 2.50 1146 2.62 1167 2.74 1189 2.86 1209 2.98
3060 1064 2.32 1090 2.46 1113 2.59 1135 2.72 1157 2.85 1178 2.98 1199 3.12 1220 3.26 1240 3.39 — —
3400 1121 2.80 1146 2.95 1170 3.10 1193 3.25 1215 3.40 — — — — — — — — — —
3740 1177 3.34 — — — — — — — — — — — — — — — — — —
4080 — — — — — — — — — — — — — — — — — — — —
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000. 3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Fan Sheave AK79 and Belt AX38 required.

68 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)

Table 81. Belt Drive Evaporator Fan Performance 10 Tons TSC102E3,4,W Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Low Static Drive Accessory Kit(i)
3200 576 0.57 618 0.67 659 0.79 697 0.90 734 1.03 770 1.17 804 1.31 839 1.45 871 1.60 901 1.74
3600 638 0.78 675 0.89 714 1.02 749 1.14 782 1.27 815 1.41 847 1.57 879 1.73 909 1.89 939 2.04
4000 701 1.04 734 1.16 768 1.30 803 1.44 834 1.58 863 1.72 894 1.87 923 2.04 952 2.21 979 2.39
4400 764 1.36 795 1.49 825 1.63 857 1.79 888 1.95 916 2.10 943 2.25 970 2.41 997 2.59 1024 2.78
4800 828 1.74 857 1.88 884 2.02 913 2.18 942 2.36 970 2.53 996 2.70 1021 2.86 1045 3.03 1070 3.22
3-HP Standard Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Oversized Motor & Drive
3200 931 1.89 959 2.06 986 2.22 1012 2.39 1037 2.56 1061 2.74 1084 2.91 1108 3.09 1131 3.28 1153 3.46
3600 969 2.21 997 2.37 1024 2.54 1050 2.72 1074 2.89 1098 3.08 1122 3.27 1145 3.46 1166 3.65 1188 3.85
4000 1007 2.57 1034 2.74 1062 2.93 1087 3.11 1112 3.29 1136 3.47 1159 3.66 1182 3.86 1204 4.07 1226 4.28
4400 1050 2.97 1075 3.17 1101 3.36 1126 3.55 1150 3.75 1173 3.94 1198 4.15 1219 4.34 1241 4.54 1264 4.77
4800 1095 3.42 1119 3.62 1143 3.83 1166 4.05 1189 4.26 1212 4.47 1235 4.68 1258 4.90 1280 5.12 1300 5.32
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR010A required.

Table 82. Belt Drive Evaporator Fan Performance 10 Tons TSC102E3,4,W Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Low Static Drive Accessory Kit(i)
3200 671 0.85 706 0.93 748 1.06 787 1.19 824 1.32 864 1.47 906 1.64 946 1.81 983 1.97 1015 2.13
3600 746 1.18 777 1.27 811 1.39 849 1.54 883 1.68 916 1.82 950 1.98 987 2.16 1024 2.35 1060 2.55
4000 822 1.59 850 1.70 879 1.81 912 1.95 946 2.12 977 2.28 1006 2.43 1035 2.60 1067 2.79 1101 2.99
4400 898 2.09 925 2.21 950 2.32 977 2.46 1008 2.63 1039 2.81 1067 2.98 1094 3.16 1121 3.33 1147 3.52
4800 974 2.69 1000 2.83 1023 2.95 1046 3.07 1072 3.23 1101 3.42 1130 3.62 1156 3.81 1181 4.00 1206 4.19
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1044 2.28 1072 2.42 1097 2.57 1122 2.71 1145 2.84 1168 2.99 1189 3.12 1210 3.27 1231 3.41 1250 3.54
3600 1093 2.74 1124 2.92 1151 3.09 1176 3.25 1201 3.42 1224 3.58 1246 3.74 1268 3.90 1289 4.06 1308 4.20
4000 1135 3.21 1167 3.42 1198 3.63 1227 3.84 1254 4.05 1278 4.23 1301 4.41 1323 4.60 1344 4.77 1365 4.95
4400 1177 3.73 1207 3.96 1239 4.19 1268 4.42 1297 4.67 1324 4.90 1351 5.12 1376 5.35 1398 5.56 1420 5.75
4800 1229 4.39 1254 4.59 1282 4.83 1310 5.07 1338 5.32 1365 5.58 — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes: Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) BAYLSDR010A required.

RT-PRC023-EN 69
Performance Data
(10 Tons Standard Efficiency)

Table 83. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*L,M Low & Medium Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i)
3200 — — — — — — 743 1.06 779 1.20 814 1.35 847 1.49 879 1.63 910 1.78 938 1.93
3600 — — 735 1.10 768 1.22 802 1.36 834 1.50 866 1.66 897 1.82 927 1.98 957 2.14 985 2.30
4000 767 1.29 802 1.44 833 1.58 863 1.71 892 1.87 922 2.04 951 2.21 979 2.39 1006 2.56 1034 2.74
4400 837 1.69 869 1.85 899 2.00 926 2.15 953 2.31 980 2.48 1007 2.66 1033 2.85 1059 3.04 1085 3.24
4800 908 2.16 937 2.33 965 2.50 991 2.67 1017 2.83 1041 3.00 1066 3.19 1090 3.38 1115 3.59 1139 3.80
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 966 2.10 992 2.26 1018 2.43 1042 2.60 1066 2.78 1091 2.96 1114 3.15 1136 3.33 1159 3.51 1182 3.70
3600 1013 2.47 1039 2.64 1065 2.82 1089 3.00 1113 3.19 1135 3.38 1157 3.56 1179 3.76 1201 3.97 1221 4.16
4000 1060 2.92 1086 3.10 1111 3.28 1135 3.47 1159 3.66 1182 3.86 1203 4.05 1224 4.26 1246 4.47 1266 4.68
4400 1110 3.43 1134 3.62 1159 3.82 1183 4.02 1205 4.22 1229 4.43 1251 4.64 1272 4.84 1292 5.05 1313 5.27
4800 1162 4.01 1185 4.22 1209 4.44 1231 4.64 1253 4.86 1276 5.07 1298 5.30 1319 5.51 1338 5.73 — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.

Table 84. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*H High Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i)
3200 — — — — 739 1.05 774 1.19 809 1.33 843 1.47 874 1.61 905 1.76 935 1.92 963 2.08
3600 738 1.11 772 1.23 805 1.37 838 1.52 869 1.68 900 1.84 930 2.00 960 2.16 988 2.32 1016 2.49
4000 813 1.49 844 1.63 873 1.77 903 1.93 932 2.10 961 2.27 989 2.45 1017 2.63 1043 2.80 1070 2.98
4400 889 1.95 917 2.10 944 2.25 971 2.42 998 2.59 1024 2.78 1050 2.97 1076 3.17 1101 3.37 1126 3.56
4800 964 2.50 991 2.66 1016 2.83 1040 3.00 1065 3.18 1090 3.38 1114 3.58 1138 3.79 1161 4.00 1184 4.22
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 989 2.24 1015 2.41 1039 2.58 1064 2.76 1087 2.93 1111 3.12 1133 3.30 1156 3.48 1179 3.68 1200 3.85
3600 1042 2.66 1067 2.84 1091 3.02 1115 3.21 1138 3.40 1160 3.59 1181 3.78 1203 3.98 1224 4.19 1244 4.39
4000 1095 3.17 1120 3.35 1145 3.54 1167 3.73 1190 3.93 1212 4.14 1233 4.35 1253 4.55 1273 4.76 1293 4.97
4400 1150 3.75 1174 3.95 1197 4.15 1221 4.36 1243 4.56 1265 4.77 1285 4.97 1306 5.20 1326 5.42 1345 5.65
4800 1208 4.42 1231 4.64 1253 4.86 1275 5.07 1297 5.29 1317 5.50 1338 5.72 — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.

70 RT-PRC023-EN
Performance Data
(10 Tons Standard Efficiency)

Table 85. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*L,M Low & Medium Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i) 3-HP Standard Motor & Drive
3200 — — 777 1.15 814 1.28 853 1.42 895 1.59 936 1.76 973 1.93 1008 2.09 1037 2.24 1064 2.38
3600 819 1.42 857 1.57 890 1.71 922 1.85 957 2.02 994 2.20 1032 2.39 1067 2.58 1099 2.77 1131 2.96
4000 902 1.91 936 2.07 968 2.23 998 2.39 1027 2.55 1058 2.73 1091 2.93 1124 3.14 1158 3.36 1189 3.57
4400 986 2.50 1016 2.68 1047 2.86 1075 3.03 1101 3.20 1128 3.39 1155 3.58 1186 3.80 1217 4.03 1246 4.25
4800 1070 3.22 1098 3.40 1127 3.60 1153 3.79 1178 3.98 1203 4.17 1227 4.37 1251 4.57 1279 4.80 1307 5.05
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1090 2.53 1115 2.67 1139 2.81 1161 2.95 1183 3.09 1205 3.23 1225 3.37 1246 3.51 1265 3.65 1284 3.78
3600 1157 3.13 1181 3.29 1205 3.45 1228 3.61 1250 3.77 1272 3.93 1293 4.09 1312 4.24 1331 4.40 1351 4.56
4000 1218 3.78 1246 3.99 1271 4.18 1294 4.36 1317 4.55 1338 4.72 1360 4.91 1379 5.07 1398 5.25 1418 5.43
4400 1276 4.49 1304 4.73 1333 4.97 1359 5.20 1383 5.42 1405 5.62 — — — — — — — —
4800 1336 5.30 1363 5.56 — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required.

Table 86. Belt Drive Evaporator Fan Performance 10 Tons with Gas Heat YSC120E3,4,W*H High Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive(i) 3-HP Standard Motor & Drive
3200 785 1.18 821 1.31 861 1.46 903 1.62 944 1.80 981 1.96 1014 2.12 1043 2.27 1070 2.41 1095 2.55
3600 874 1.64 907 1.78 939 1.93 977 2.11 1014 2.30 1050 2.49 1084 2.69 1115 2.87 1144 3.05 1169 3.21
4000 964 2.21 994 2.37 1023 2.53 1053 2.71 1087 2.91 1121 3.12 1154 3.33 1185 3.55 1215 3.76 1242 3.96
4400 1055 2.91 1082 3.08 1109 3.25 1135 3.43 1164 3.64 1194 3.86 1225 4.09 1255 4.32 1284 4.56 1312 4.79
4800 1146 3.74 1171 3.92 1196 4.11 1220 4.31 1244 4.51 1271 4.73 1298 4.97 1327 5.22 1354 5.47 1382 5.74
5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive
3200 1120 2.70 1143 2.84 1166 2.98 1188 3.12 1208 3.25 1229 3.39 1249 3.53 1269 3.67 1289 3.82 1308 3.96
3600 1194 3.37 1217 3.53 1240 3.69 1262 3.85 1282 4.01 1303 4.17 1322 4.32 1341 4.48 1361 4.64 1378 4.79
4000 1269 4.16 1292 4.34 1314 4.52 1335 4.70 1356 4.88 1377 5.06 1397 5.24 1415 5.41 — — — —
4400 1339 5.02 1365 5.25 1388 5.47 1410 5.67 — — — — — — — — — — — —
4800 — — — — — — — — — — — — — — — — — — — —
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 105.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 114 to determine additional static pressure drop due to other options/accessories.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
(i) Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89, and Belt AX40 required

RT-PRC023-EN 71
Performance Data
(3 Tons High Efficiency)

Table 87. Belt Drive Evaporator Fan Performance — 3 Tons — THC036E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 608 0.17 676 0.22 734 0.27 785 0.32 833 0.37 878 0.42 922 0.47 963 0.53
1080 — — 557 0.15 629 0.20 697 0.25 757 0.30 809 0.36 857 0.42 901 0.47 944 0.53 983 0.59
1200 — — 588 0.18 653 0.23 718 0.29 777 0.35 832 0.41 881 0.47 925 0.53 967 0.59 1006 0.66
1320 553 0.17 621 0.22 681 0.27 741 0.33 799 0.39 854 0.46 903 0.53 948 0.59 990 0.66 1030 0.73
1440 591 0.21 655 0.27 712 0.32 766 0.38 821 0.44 873 0.51 923 0.58 970 0.66 1014 0.73 1053 0.80
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1002 0.59 1039 0.65 1073 0.70 1107 0.76 1138 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1022 0.65 1059 0.71 1095 0.78 1129 0.84 1162 0.91 Using the full horsepower range of our fan motors as shown in our
1200 1044 0.72 1081 0.79 1115 0.85 1149 0.92 1183 0.99 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1068 0.80 1104 0.87 1138 0.94 1172 1.01 1205 1.08
1440 1091 0.88 1127 0.95 1161 1.03 1195 1.10 1227 1.18
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 88. Belt Drive Evaporator Fan Performance — 3 Tons — THC036E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 619 0.16 680 0.20 738 0.25 791 0.30 840 0.35 885 0.39 927 0.44 968 0.49
1080 — — 570 0.14 647 0.19 708 0.24 762 0.29 814 0.34 863 0.39 908 0.45 950 0.50 991 0.55
1200 — — 595 0.17 674 0.23 736 0.28 789 0.33 839 0.39 885 0.44 931 0.50 973 0.56 1013 0.62
1320 551 0.16 622 0.20 698 0.26 764 0.33 817 0.38 866 0.44 911 0.50 954 0.56 997 0.62 1036 0.68
1440 588 0.20 653 0.24 722 0.30 789 0.37 846 0.44 894 0.50 938 0.56 980 0.63 1020 0.69 1060 0.76
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 1005 0.54 1040 0.59 1074 0.64 1107 0.69 1139 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1029 0.61 1066 0.67 1100 0.72 1134 0.77 1165 0.83 Using the full horsepower range of our fan motors as shown in our
1200 1052 0.68 1088 0.74 1124 0.80 1157 0.86 1190 0.92 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1074 0.75 1112 0.82 1147 0.88 1181 0.95 1213 1.02
1440 1098 0.83 1134 0.90 1169 0.97 1203 1.04 1237 1.11
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

72 RT-PRC023-EN
Performance Data
(3 Tons High Efficiency)

Table 89. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 600 0.15 664 0.19 722 0.23 774 0.27 824 0.31 870 0.36 913 0.41 952 0.45
1080 — — 560 0.14 625 0.17 687 0.22 743 0.26 795 0.31 844 0.36 890 0.40 933 0.45 973 0.51
1200 — — 593 0.17 655 0.21 712 0.25 767 0.30 817 0.35 865 0.40 910 0.45 952 0.51 993 0.56
1320 — — 626 0.20 685 0.25 740 0.29 791 0.34 841 0.40 887 0.45 931 0.51 974 0.56 1014 0.62
1440 592 0.20 660 0.25 718 0.29 769 0.34 818 0.39 866 0.45 911 0.51 955 0.57 996 0.63 1034 0.69
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.50 1025 0.55 1058 0.59 1091 0.64 1120 0.69 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1012 0.56 1047 0.61 1083 0.66 1116 0.72 1148 0.77 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.62 1069 0.67 1104 0.73 1138 0.79 1171 0.85 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1051 0.68 1088 0.74 1124 0.80 1159 0.86 1191 0.93
1440 1072 0.75 1108 0.81 1145 0.88 1179 0.94 1212 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 90. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 605 0.15 670 0.19 726 0.24 776 0.28 824 0.32 871 0.37 915 0.42 955 0.47
1080 — — 556 0.14 628 0.18 693 0.23 750 0.27 801 0.32 847 0.37 891 0.42 932 0.47 975 0.52
1200 — — 584 0.17 653 0.21 717 0.26 773 0.31 825 0.37 872 0.42 915 0.47 955 0.52 994 0.58
1320 — — 614 0.20 679 0.25 740 0.30 796 0.36 848 0.41 896 0.47 940 0.53 980 0.59 1018 0.65
1440 582 0.19 646 0.24 708 0.29 767 0.35 820 0.40 871 0.47 920 0.53 963 0.59 1005 0.66 1043 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 994 0.52 1031 0.58 1066 0.63 1101 0.69 1131 0.74 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1013 0.58 1051 0.63 1087 0.69 1122 0.75 1155 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1032 0.63 1069 0.69 1105 0.75 1140 0.82 1175 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1056 0.70 1090 0.76 1125 0.82 1159 0.89 1193 0.96
1440 1079 0.78 1114 0.84 1148 0.91 1181 0.97 1211 1.04
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 73
Performance Data
(3 Tons High Efficiency)

Table 91. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 603 0.15 664 0.19 722 0.24 775 0.28 824 0.33 869 0.37 912 0.42 953 0.47
1080 — — 568 0.14 632 0.18 690 0.23 744 0.27 796 0.32 844 0.37 889 0.42 933 0.47 973 0.53
1200 — — 602 0.18 663 0.22 718 0.27 770 0.31 819 0.36 865 0.42 911 0.47 953 0.53 993 0.58
1320 572 0.17 638 0.22 695 0.26 748 0.31 798 0.36 845 0.41 889 0.47 932 0.53 974 0.58 1015 0.65
1440 611 0.21 674 0.27 729 0.31 779 0.36 827 0.42 872 0.47 915 0.53 957 0.59 997 0.65 1036 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 990 0.52 1026 0.58 1060 0.63 1092 0.68 1123 0.73 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1011 0.58 1047 0.63 1083 0.69 1115 0.75 1148 0.81 Using the full horsepower range of our fan motors as shown in our
1200 1033 0.64 1069 0.70 1105 0.76 1138 0.82 1170 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1053 0.71 1089 0.77 1124 0.83 1159 0.90 1191 0.96
1440 1074 0.78 1109 0.84 1145 0.91 1178 0.98 1212 1.05
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 92. Belt Drive Evaporator Fan Performance — 3 Tons — YHC036E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
960 — — — — 615 0.16 678 0.20 737 0.24 789 0.29 838 0.33 883 0.38 923 0.42 962 0.47
1080 — — 576 0.14 643 0.19 704 0.23 760 0.28 812 0.32 861 0.38 906 0.43 949 0.48 988 0.53
1200 — — 608 0.18 673 0.22 732 0.27 785 0.32 836 0.37 883 0.42 928 0.48 971 0.53 1012 0.59
1320 571 0.17 642 0.22 705 0.26 761 0.31 813 0.37 862 0.42 908 0.48 952 0.53 995 0.59 1034 0.66
1440 609 0.21 677 0.26 737 0.31 791 0.37 841 0.42 889 0.48 934 0.54 977 0.60 1017 0.66 1057 0.72
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
960 999 0.52 1034 0.57 1068 0.62 1100 0.67 1132 0.72 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1080 1024 0.58 1061 0.64 1094 0.69 1126 0.74 1156 0.79 Using the full horsepower range of our fan motors as shown in our
1200 1050 0.65 1086 0.71 1120 0.77 1153 0.83 1183 0.88 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1320 1072 0.72 1109 0.78 1145 0.85 1177 0.91 1209 0.98
1440 1095 0.79 1132 0.86 1167 0.93 1201 1.00 1234 1.07
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK71x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

74 RT-PRC023-EN
Performance Data
(4 Tons High Efficiency)

Table 93. Belt Drive Evaporator Fan Performance — 4 Tons — THC048E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — — — 574 0.17 635 0.21 692 0.26 745 0.30 795 0.35 842 0.40 886 0.45 930 0.51
1440 — — 533 0.17 598 0.21 657 0.26 711 0.30 762 0.35 811 0.40 857 0.45 900 0.51 943 0.57
1600 — — 563 0.21 625 0.26 681 0.31 734 0.36 782 0.41 828 0.46 874 0.51 917 0.57 957 0.63
1760 526 0.20 594 0.26 652 0.31 706 0.36 757 0.42 804 0.47 849 0.53 891 0.58 933 0.64 974 0.70
1920 561 0.25 624 0.31 682 0.37 734 0.43 783 0.49 829 0.55 871 0.60 913 0.66 953 0.72 992 0.79
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 971 0.56 1010 0.62 1049 0.68 1083 0.74 1118 0.80 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 981 0.62 1020 0.68 1058 0.74 1096 0.81 1131 0.87 Using the full horsepower range of our fan motors as shown in our
1600 997 0.69 1034 0.75 1070 0.82 1106 0.88 1140 0.95 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1012 0.77 1049 0.83 1086 0.90 1119 0.96 1153 1.03
1920 1029 0.85 1064 0.92 1100 0.99 1135 1.06 1168 1.13
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 94. Belt Drive Evaporator Fan Performance — 4 Tons — THC048E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 537 0.16 619 0.21 692 0.27 754 0.33 807 0.39 855 0.46 899 0.52 937 0.58 973 0.64
1440 — — 564 0.19 639 0.25 710 0.31 774 0.38 830 0.45 881 0.52 926 0.59 968 0.66 1007 0.73
1600 — — 593 0.24 663 0.30 729 0.36 793 0.44 851 0.51 903 0.59 950 0.67 993 0.74 1034 0.82
1760 555 0.23 623 0.29 690 0.35 751 0.42 812 0.50 869 0.58 922 0.66 972 0.74 1017 0.83 1059 0.91
1920 593 0.28 656 0.35 719 0.42 777 0.49 833 0.57 889 0.65 942 0.74 991 0.83 1038 0.92 1080 1.01
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1008 0.70 1041 0.76 1074 0.82 1106 0.89 1138 0.95 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1042 0.80 1074 0.86 1105 0.93 1135 1.00 1166 1.07 Using the full horsepower range of our fan motors as shown in our
1600 1072 0.90 1107 0.97 1139 1.05 1170 1.12 1198 1.20 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1097 1.00 1133 1.08 1169 1.17 1201 1.25 1233 1.34
1920 1121 1.10 1158 1.19 1194 1.29 1228 1.38 1260 1.47
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 75
Performance Data
(4 Tons High Efficiency)

Table 95. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — — — 583 0.18 644 0.23 700 0.27 752 0.32 799 0.37 845 0.42 891 0.47 933 0.53
1440 — — 542 0.18 608 0.22 667 0.27 721 0.32 772 0.37 818 0.42 863 0.48 906 0.53 946 0.59
1600 — — 572 0.22 636 0.27 692 0.32 744 0.37 793 0.43 839 0.49 883 0.55 924 0.60 964 0.66
1760 538 0.21 603 0.27 664 0.32 719 0.38 768 0.44 817 0.50 861 0.56 904 0.62 945 0.68 983 0.75
1920 574 0.27 636 0.32 692 0.38 746 0.45 795 0.51 841 0.57 885 0.63 927 0.70 966 0.77 1004 0.84
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 975 0.58 1014 0.64 1052 0.70 1087 0.76 1121 0.82 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 986 0.65 1025 0.71 1063 0.77 1098 0.83 1134 0.90 Using the full horsepower range of our fan motors as shown in our
1600 1002 0.72 1038 0.78 1075 0.85 1112 0.92 1145 0.98 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1020 0.81 1057 0.88 1091 0.94 1126 1.01 1158 1.08
1920 1041 0.91 1076 0.98 1110 1.05 1144 1.12 1176 1.19
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 96. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 552 0.16 619 0.21 680 0.26 735 0.31 785 0.36 833 0.42 878 0.47 921 0.53 962 0.59
1440 — — 589 0.21 649 0.26 708 0.31 762 0.36 811 0.42 857 0.48 901 0.54 943 0.60 982 0.66
1600 560 0.21 627 0.26 684 0.31 738 0.37 789 0.43 838 0.49 883 0.55 926 0.61 967 0.68 1006 0.75
1760 602 0.27 666 0.33 721 0.38 770 0.44 819 0.50 866 0.57 911 0.63 953 0.70 993 0.77 1031 0.84
1920 644 0.33 705 0.40 759 0.46 806 0.52 851 0.59 895 0.66 939 0.73 980 0.80 1019 0.87 1057 0.95
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1000 0.65 1038 0.72 1076 0.78 1113 0.85 1149 0.91 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1021 0.73 1058 0.80 1093 0.86 1128 0.94 1162 1.01 Using the full horsepower range of our fan motors as shown in our
1600 1043 0.82 1079 0.89 1114 0.96 1148 1.03 1182 1.11 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1068 0.91 1103 0.99 1137 1.06 1172 1.14 1203 1.22
1920 1094 1.02 1128 1.10 1161 1.18 1195 1.26 1227 1.34
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

76 RT-PRC023-EN
Performance Data
(4 Tons High Efficiency)

Table 97. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 524 0.15 595 0.19 653 0.23 708 0.28 760 0.33 809 0.38 856 0.43 901 0.48 945 0.54
1440 — — 553 0.18 621 0.23 680 0.28 732 0.33 781 0.38 828 0.43 873 0.49 917 0.55 959 0.61
1600 — — 584 0.22 647 0.28 706 0.34 759 0.39 805 0.44 849 0.50 892 0.55 935 0.61 975 0.68
1760 554 0.22 617 0.28 676 0.33 733 0.39 786 0.46 832 0.52 876 0.58 916 0.63 955 0.69 994 0.76
1920 593 0.28 652 0.34 707 0.39 760 0.46 811 0.53 859 0.60 903 0.66 942 0.73 980 0.79 1016 0.85
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 987 0.60 1027 0.66 1064 0.71 1100 0.77 1135 0.83 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 998 0.67 1037 0.73 1076 0.79 1114 0.86 1149 0.92 Using the full horsepower range of our fan motors as shown in our
1600 1014 0.74 1053 0.81 1089 0.87 1124 0.94 1160 1.01 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1033 0.82 1069 0.89 1105 0.96 1139 1.03 1173 1.11
1920 1052 0.92 1088 0.99 1122 1.06 1156 1.14 1190 1.21
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 98. Belt Drive Evaporator Fan Performance — 4 Tons — YHC048E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1280 — — 558 0.16 621 0.20 678 0.25 732 0.29 783 0.34 831 0.39 879 0.45 922 0.50 965 0.56
1440 — — 592 0.20 656 0.25 710 0.30 759 0.35 808 0.40 853 0.45 898 0.51 941 0.57 982 0.63
1600 561 0.20 627 0.25 691 0.31 744 0.36 792 0.41 836 0.47 880 0.52 922 0.58 963 0.64 1003 0.71
1760 603 0.26 664 0.31 724 0.37 778 0.43 825 0.49 868 0.54 909 0.60 949 0.67 988 0.73 1027 0.80
1920 647 0.32 704 0.38 759 0.44 813 0.52 859 0.58 902 0.63 942 0.70 980 0.76 1017 0.83 1053 0.90
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1280 1004 0.62 1042 0.68 1079 0.75 1114 0.81 1148 0.87 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1440 1023 0.69 1060 0.76 1097 0.82 1132 0.89 1166 0.96 Using the full horsepower range of our fan motors as shown in our
1600 1043 0.77 1079 0.84 1116 0.91 1149 0.98 1184 1.05 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
1760 1064 0.86 1100 0.93 1135 1.00 1169 1.07 1203 1.15
1920 1088 0.97 1123 1.04 1158 1.11 1191 1.19 1223 1.26
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK74x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 77
Performance Data
(5 Tons High Efficiency)

Table 99. Belt Drive Evaporator Fan Performance — 5 Tons — THC060E3,E4 Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 563 0.21 622 0.25 678 0.31 730 0.36 778 0.41 823 0.46 867 0.52 908 0.57 948 0.63
1800 — — 604 0.27 659 0.32 710 0.37 760 0.43 808 0.49 851 0.55 892 0.61 932 0.67 970 0.73
2000 588 0.29 645 0.35 698 0.40 746 0.46 791 0.52 837 0.58 880 0.65 921 0.71 959 0.78 995 0.84
2200 636 0.37 689 0.43 739 0.50 784 0.56 827 0.62 868 0.68 909 0.75 951 0.83 988 0.90 1024 0.97
2400 683 0.47 734 0.54 780 0.61 824 0.68 865 0.74 904 0.81 942 0.88 980 0.95 1017 1.03 1054 1.11
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 987 0.70 1024 0.76 1061 0.83 1095 0.89 1128 0.96 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1008 0.79 1043 0.86 1078 0.92 1113 1.00 1145 1.06 Using the full horsepower range of our fan motors as shown in our
2000 1031 0.90 1066 0.97 1100 1.05 1134 1.12 1167 1.19 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1059 1.04 1092 1.11 1124 1.18 1157 1.26 1187 1.33
2400 1088 1.19 1120 1.27 1152 1.34 1183 1.42 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 100. Belt Drive Evaporator Fan Performance — 5 Tons — THC060E3,E4 Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 619 0.24 681 0.29 745 0.35 810 0.42 868 0.48 916 0.55 959 0.62 998 0.68 1034 0.75
1800 597 0.25 664 0.31 723 0.37 777 0.42 834 0.49 893 0.57 947 0.64 996 0.72 1037 0.80 1075 0.87
2000 648 0.33 711 0.39 767 0.46 818 0.52 867 0.58 918 0.66 971 0.74 1021 0.83 1068 0.91 1110 1.00
2200 700 0.42 759 0.50 812 0.57 861 0.63 907 0.70 951 0.77 997 0.85 1045 0.94 1093 1.04 1137 1.13
2400 752 0.54 808 0.61 859 0.69 906 0.77 949 0.84 991 0.92 1032 0.99 1072 1.08 1117 1.17 1161 1.27
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1068 0.81 1101 0.88 1132 0.94 1161 1.00 1190 1.07 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1111 0.95 1143 1.02 1175 1.09 1205 1.16 1233 1.23 Using the full horsepower range of our fan motors as shown in our
2000 1147 1.08 1182 1.17 1215 1.25 1246 1.33 1276 1.41 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1179 1.23 1219 1.33 1252 1.42 — — — —
2400 1205 1.38 — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

78 RT-PRC023-EN
Performance Data
(5 Tons High Efficiency)

Table 101. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*L,M Low & Medium Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 — — 577 0.22 639 0.27 694 0.32 743 0.37 790 0.42 835 0.47 879 0.53 920 0.59 961 0.65
1800 557 0.23 618 0.28 676 0.34 729 0.40 778 0.45 822 0.50 864 0.56 905 0.62 945 0.68 984 0.74
2000 604 0.30 662 0.36 715 0.42 766 0.48 813 0.55 857 0.61 897 0.67 935 0.73 974 0.79 1010 0.86
2200 653 0.39 707 0.45 756 0.51 803 0.58 849 0.65 892 0.72 933 0.79 969 0.85 1005 0.92 1040 0.99
2400 702 0.49 753 0.56 799 0.63 843 0.70 887 0.77 928 0.85 968 0.93 1006 1.00 1041 1.07 1074 1.14
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 999 0.71 1037 0.77 1072 0.83 1107 0.90 1141 0.96 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1021 0.81 1058 0.88 1093 0.94 1126 1.01 1161 1.08 Using the full horsepower range of our fan motors as shown in our
2000 1046 0.93 1081 1.00 1115 1.07 1149 1.14 1181 1.22 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1075 1.06 1108 1.13 1140 1.21 1173 1.29 1204 1.36
2400 1106 1.21 1138 1.29 1168 1.37 1200 1.45 — —
1-HP Standard Motor & Field Supplied Low Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 102. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*L,M Low & Medium Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 565 0.21 630 0.26 689 0.31 740 0.36 791 0.41 839 0.47 884 0.52 927 0.58 968 0.65 1007 0.71
1800 620 0.28 678 0.33 735 0.39 784 0.45 830 0.51 875 0.57 918 0.63 960 0.69 1000 0.76 1038 0.82
2000 677 0.37 729 0.43 781 0.49 831 0.56 874 0.62 915 0.69 956 0.75 996 0.82 1034 0.89 1072 0.96
2200 733 0.48 782 0.54 830 0.61 876 0.68 921 0.75 959 0.82 997 0.90 1035 0.97 1071 1.04 1106 1.12
2400 791 0.61 837 0.68 880 0.75 923 0.82 966 0.90 1006 0.98 1042 1.06 1076 1.14 1110 1.22 1144 1.30
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1045 0.78 1082 0.85 1117 0.91 1151 0.98 1183 1.05 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1074 0.89 1110 0.96 1145 1.04 1178 1.11 1211 1.19 Using the full horsepower range of our fan motors as shown in our
2000 1108 1.03 1142 1.10 1176 1.18 1207 1.26 1239 1.34 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1141 1.19 1175 1.27 1208 1.35 1240 1.43 — —
2400 1178 1.38 1210 1.46 — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

RT-PRC023-EN 79
Performance Data
(5 Tons High Efficiency)

Table 103. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*H High Gas Heat Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 - - 590 0.22 651 0.27 706 0.32 755 0.37 802 0.42 848 0.47 891 0.53 933 0.59 974 0.65
1800 571 0.23 632 0.29 690 0.34 742 0.40 791 0.45 836 0.51 878 0.56 919 0.62 959 0.68 999 0.75
2000 620 0.31 676 0.36 731 0.42 782 0.49 828 0.55 871 0.61 913 0.67 952 0.73 988 0.79 1026 0.86
2200 671 0.39 723 0.46 773 0.52 822 0.59 866 0.66 908 0.72 948 0.79 987 0.86 1023 0.93 1058 1.00
2400 722 0.50 771 0.57 818 0.64 863 0.71 907 0.78 947 0.86 985 0.93 1023 1.00 1059 1.08 1093 1.15
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1013 0.72 1051 0.78 1087 0.85 1122 0.91 1157 0.98 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1036 0.82 1072 0.88 1108 0.95 1143 1.02 1176 1.09 Using the full horsepower range of our fan motors as shown in our
2000 1062 0.93 1097 1.00 1132 1.08 1164 1.15 1199 1.23 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1091 1.07 1124 1.14 1157 1.21 1190 1.29 1222 1.37
2400 1125 1.23 1157 1.30 1188 1.38 1219 1.46 — —
1-HP Standard Motor & Field Supplied High Static Drive(ii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

Table 104. Belt Drive Evaporator Fan Performance — 5 Tons — YHC060E3,E4*H High Gas Heat Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied Low Static Drive(i) 1-HP Standard Motor & Drive
1600 569 0.21 636 0.26 697 0.32 752 0.37 800 0.41 842 0.46 881 0.52 922 0.58 963 0.64 1002 0.70
1800 620 0.28 686 0.34 741 0.40 795 0.46 843 0.52 887 0.57 925 0.62 961 0.68 997 0.75 1033 0.81
2000 672 0.36 739 0.44 788 0.50 838 0.57 886 0.64 930 0.71 970 0.76 1006 0.82 1040 0.88 1072 0.95
2200 724 0.46 789 0.55 839 0.62 884 0.69 929 0.77 973 0.85 1013 0.92 1050 0.99 1084 1.05 1117 1.11
2400 778 0.58 840 0.68 892 0.76 933 0.84 974 0.91 1015 1.00 1055 1.09 1094 1.17 1129 1.25 1161 1.31
1-HP Standard Motor & Field Supplied High Static Drive(ii)
Continued For Standard Evaporator Fan Speed (RPM), reference Table 110.
Notes: Data includes pressure drop due to standard filters and wet
External Static Pressure (Inches of Water)
coils. No accessories or options are included in pressure drop data.
1.10 1.20 1.30 1.40 1.50 Data does not include pressure drop due to reheat coil.
Refer to Table 115 to determine additional static pressure
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
drop due to other options/accessories.
1-HP Standard Motor & Drive 1-HP Fan Motor Heat (MBH) = 2.7672 x Fan BHP+0.4705.
1600 1041 0.76 1078 0.83 1113 0.90 1147 0.96 1180 1.03 Factory supplied motors, in equipment, are definite purpose motors,
specifically designed and tested to operate at all cataloged conditions.
1800 1069 0.88 1104 0.95 1139 1.02 1173 1.09 1206 1.17 Using the full horsepower range of our fan motors as shown in our
2000 1103 1.02 1137 1.09 1170 1.17 1201 1.24 1233 1.32 tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
2200 1147 1.18 1177 1.25 1205 1.33 1234 1.41 — —
2400 1192 1.38 1221 1.45 — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive(iii)
(i) Field Supplied Fan Sheave AK69x3/4" required. Field Supplied Belt may be necessary.
(ii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.
(iii) Field Supplied Fan Sheave AK41x3/4" required. Field Supplied Belt may be necessary.

80 RT-PRC023-EN
Performance Data

Table 105. Standard Motor & Sheave/Fan Speed (Rpm)


Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
3 T/YSC036E3 AK51x3/4" N/A 765 835 905 975 1045 1115
4 T/YSC048E3 AK49x3/4" N/A 804 876 948 1020 1091 1163
5 T/YSC060E3 AK44x3/4" N/A 885 966 1049 1131 1212 1295
6 T/YSC072E AK64x1" N/A 723 779 835 890 946 1002
7½-8½ T/YSC092-102E AK59x1" N/A 787 847 908 968 1029 1089
10 T/YSC120E AK59x1" N/A 908 969 1029 1090 1150 1211
3 WSC036E3 AK51x3/4" N/A 761 835 909 982 1057 1125
4 WSC048E3 AK49x3/4" N/A 801 874 946 1019 1091 1164
5 WSC060E3 AK49X3/4" N/A 798 868 939 1010 1081 1152
Factory set at 3 turns open.

Table 106. Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
3 T/YSC036E3 AK71x3/4" N/A 556 606 657 707 757 808
4 T/YSC048E3 AK69x3/4" N/A N/A 624 675 727 779 832
5 T/YSC060E3 AK61x3/4" N/A N/A 708 765 823 880 938
7½ TSC092E AK99x1" N/A 462 498 533 569 604 640
AK79x1" N/A 582 627 672 716 761 806
8½ TSC102E AK99x1" N/A 462 498 533 569 604 640
AK79x1" N/A 582 627 672 716 761 806
10 TSC120E AK94x1" N/A 563 600 638 675 713 750
AK74x1" N/A 719 767 815 862 910 958
3 WSC036E3 AK71x3/4" N/A 549 600 650 701 751 802
4 WSC048E3 AK69x3/4" N/A 567 619 671 723 775 828
5 WSC060E3 AK69x3/4" N/A 566 617 668 719 770 821
Factory set at 3 turns open.

Table 107. Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Open Open Open Open Open Open Closed
3 T/YSC036E3 AK41x3/4" N/A 967 1040 1113 1187 N/A
4 T/YSC048E3 AK41x3/4" N/A 957 1033 1110 1187 1263
5 T/YSC060E3 N/A N/A N/A N/A N/A N/A N/A
6 T/YSC072E3,E4,EW N/A 831 895 959 1022 1086 1150
3 WSC036E3 AK41 x 3/4" N/A 966 1041 1115 1190 N/A
4 WSC048E3 AK41 x 3/4" N/A 958 1034 1110 1186 1261
5 WSC060E3 AK41 x 3/4" N/A 970 1034 1097 1161 1224
Factory set at 3 turns open.

RT-PRC023-EN 81
Performance Data

Table 108. Oversized Motor & Drive Sheave/Fan Speed (Rpm)


Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Open Open Open Open Open Open Closed
6 T/YSC072E N/A 958 1022 1086 1150 1214 1278
7½ T/YSC092E N/A 958 1022 1086 1150 1214 1278
8½ T/YSC102E N/A 958 1022 1086 1150 1214 1278
10 T/YSC120E 1050 1135 1200 1275 1350 1425 N/A
Factory set at 3 turns open.
* Indicates both standard and high efficiency units and both ReliaTel and Electromechanical controls.

Table 109. Outdoor Sound Power Level - dB (ref. 10 - 12 Watts)


Unit Model Octave Center Frequency Overall
Tons Number 63 125 250 500 1000 2000 4000 8000 dBA
3 T/YSC036E1, E3, E4, EW 79 85 79 79 77 71 67 58 81
4 T/YSC048E1, E3, E4, EW 82 84 83 80 76 72 66 58 82
5 T/YSC060E1, E3, E4, EW 85 82 81 81 77 72 67 61 82
6 T/YSC072E 91 95 90 87 84 79 75 68 89
7½ T/YSC092E 92 96 92 89 85 80 76 69 91
8½ T/YSC102E 91 95 90 87 84 79 75 68 89
10 T/YSC120E 94 89 87 85 84 78 75 69 88
3 WSC036E1 79 85 80 79 77 72 67 59 81
WSC036E3, E4, EW 77 85 79 78 75 71 66 59 80
4 WSC048E1, E3, E4, EW 81 82 83 81 77 72 66 59 82
5 WSC060E1, E3, E4, EW 81 87 84 85 83 78 73 67 87
Tests follow ARI270-95.

Table 110. Standard Motor & Sheave/Fan Speed (Rpm)


Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
15 SEER High Efficiency
3 T/YHC036E AK51x3/4" N/A 765 835 905 975 1045 1115
4 T/YHC048E AK54x3/4" N/A 729 794 860 926 991 1057
5 T/YHC060E AK49x3/4" "N/A 801 871 942 1012 1083 1154
Factory set at 3 turns open.

Table 111. Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model Fan 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Sheave Open Open Open Open Open Open Closed
3 T/YHC036E AK71x3/4" N/A 556 606 657 707 757 808
4 T/YHC048E AK74x3/4" N/A 528 576 625 673 722 770
5 T/YHC060E AK69x3/4" N/A 565 617 669 721 773 825
Factory set at 3 turns open.

82 RT-PRC023-EN
Performance Data

Table 112. Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Number Open Open Open Open Open Open Closed
3 T/YHC036E AK41x3/4" N/A 967 1040 1113 1187 N/A
4 T/YHC048E AK41x3/4" N/A 966 1048 1132 1215 N/A
5 T/YHC060E AK41x3/4" N/A 961 1041 1122 1203 N/A
Factory set at 3 turns open.

Table 113. Outdoor Sound Power Level - dB (ref. 10 - 12 Watts)


Unit Model Octave Center Frequency Overall
Tons Number 63 125 250 500 1000 2000 4000 8000 dBA
3 YHC036E1,E3 79 85 79 79 77 71 67 58 81
4 YHC048E1,E3 80 86 84 85 83 79 73 67 87
5 YHC060E1,E3 80 86 84 85 83 79 73 67 87
Tests follow ARI270-95.

Table 114. Static Pressure Drop Through Accessories (Inches Water Column) —3-10 Tons
Economizer with OA/RA Dampers(i) Electric Heater Accessory (kW)(ii),(iii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36 54
Tons Number Filters(iv) Filter OA RA OA RA
Downflow Horizontal
3 T/YSC036E1 960 0.01 0.03 0.04 0.01 0.04 0.01 0.01 0.01 0.01 —
1200 0.02 0.04 0.06 0.01 0.06 0.01 0.02 0.02 0.02 —
1440 0.03 0.05 0.08 0.02 0.08 0.01 0.02 0.03 0.03 —
T/YSC036E3 960 0.01 0.03 0.04 0.01 0.04 0.01 0.01 0.01 0.01 —
1200 0.02 0.04 0.06 0.01 0.06 0.01 0.02 0.02 0.02 —
1440 0.03 0.05 0.08 0.02 0.08 0.01 0.02 0.03 0.03 —
4 T/YSC048E1 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
T/YSC048E3 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
5 T/YSC060E1 1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
2000 0.06 0.10 0.18 0.07 0.18 0.02 0.06 0.07 0.08 —
2400 0.08 0.13 0.25 0.11 0.25 0.03 0.08 0.10 0.12 —
T/YSC060E3 1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
2000 0.06 0.10 0.18 0.07 0.18 0.02 0.06 0.07 0.08 —
2400 0.08 0.13 0.25 0.11 0.25 0.03 0.08 0.10 0.12 —
6 T/YSC072E 1920 0.04 0.07 0.10 0.01 0.06 0.02 0.02 0.011 0.021 —
2400 0.06 0.09 0.11 0.02 0.08 0.02 0.02 0.020 0.034 —
2880 0.09 0.12 0.13 0.04 0.10 0.04 0.04 0.033 0.052 —
7½ T/YSC092E 2400 0.04 0.06 0.11 0.02 0.08 0.02 0.02 0.016 0.021 —
3000 0.06 0.09 0.14 0.05 0.12 0.05 0.05 0.025 0.032 —
3600 0.09 0.13 0.21 0.07 0.25 0.08 0.08 0.036 0.046 —
8½ T/YSC102E 2720 0.05 0.08 0.12 0.03 0.09 0.04 0.04 0.020 0.026 —
3400 0.08 0.11 0.19 0.06 0.18 0.06 0.06 0.032 0.041 —
4080 0.12 0.16 0.30 0.07 0.31 0.09 0.09 0.047 0.059 —
10 T/YSC120E 3200 0.07 0.10 0.17 0.05 0.14 0.05 0.05 0.028 0.036 0.042
4000 0.11 0.15 0.26 0.07 0.30 0.08 0.08 0.045 0.056 0.070
4800 0.16 0.20 0.34 0.09 0.35 0.10 0.10 0.065 0.081 0.106

RT-PRC023-EN 83
Performance Data

Table 114. Static Pressure Drop Through Accessories (Inches Water Column) —3-10 Tons (continued)
Economizer with OA/RA Dampers(v) Electric Heater Accessory
(kW)(vi),(vii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36 54
Tons Number Filters(viii) Filter OA RA OA RA
Downflow Horizontal
3 WSC036E1 960 0.02 0.03 0.05 0.01 0.05 0.01 0.01 0.02 0.02 —
1200 0.03 0.05 0.07 0.02 0.07 0.01 0.02 0.03 0.03 —
1440 0.03 0.06 0.10 0.03 0.10 0.01 0.03 0.04 0.04 —
WSC036E3 960 0.02 0.03 0.05 0.01 0.05 0.01 0.01 0.02 0.02 —
1200 0.03 0.05 0.07 0.02 0.07 0.01 0.02 0.03 0.03 —
1440 0.03 0.06 0.10 0.03 0.10 0.01 0.03 0.04 0.04 —
4 WSC048E1 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
WSC048E3 1280 0.03 0.05 0.09 0.02 0.09 0.01 0.02 0.03 0.03 —
1600 0.04 0.07 0.13 0.04 0.13 0.02 0.04 0.05 0.05 —
1920 0.06 0.10 0.17 0.06 0.17 0.02 0.05 0.06 0.08 —
5 WSC060E1 1600 0.03 0.06 0.09 0.01 0.05 0.01 0.01 0.01 0.02 —
2000 0.05 0.08 0.11 0.01 0.07 0.02 0.02 0.01 0.03 —
2400 0.07 0.10 0.12 0.03 0.09 0.03 0.03 0.02 0.04 —
WSC060E3 1600 0.03 0.06 0.09 0.01 0.05 0.01 0.01 0.01 0.02 —
2000 0.05 0.08 0.11 0.01 0.07 0.02 0.02 0.01 0.03 —
2400 0.07 0.10 0.12 0.03 0.09 0.03 0.03 0.02 0.04 —
(i) OA = Outside Air and RA = Return Air.
(ii) Nominal kW ratings at 240, 480, 600 volts.
(iii) Electric heaters restricted on applications below 320 CFM/Ton.
(iv) Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing
optional 2” pleated filters.
(v) OA = Outside Air and RA = Return Air.
(vi) Nominal kW ratings at 240, 480, 600 volts.
(vii) Electric heaters restricted on applications below 320 CFM/Ton.
(viii) Tested with standard filters (3-5 tons 1” filters, 6-10 tons 2” filters). Difference in pressure drop should be considered when utilizing
optional 2” pleated filters.

Table 115. Static Pressure Drop Through Accessories (Inches Water Column) —3-5 Tons
Economizer with OA/RA Dampers(i) Electric Heater Accessory (kW)(ii)
Unit Model CFM Standard 2" Pleated 100% 100% 100% 100% 5-6 9-15 17-36
Tons Number Filters(iii) Filter OA RA OA RA
Downflow Horizontal
3 T/YHC036E1 960 0.013 0.027 0.041 0.007 0.041 0.006 0.010 0.012 0.014
1200 0.020 0.037 0.059 0.013 0.059 0.008 0.015 0.019 0.022
1440 0.027 0.048 0.080 0.021 0.080 0.010 0.022 0.027 0.032
T/YHC036E3,4 960 0.013 0.027 0.041 0.007 0.041 0.006 0.010 0.012 0.014
1200 0.020 0.037 0.059 0.013 0.059 0.008 0.015 0.019 0.022
1440 0.027 0.048 0.080 0.021 0.080 0.010 0.022 0.027 0.032
4 T/YHC048E1 1280 0.015 0.042 0.081 0.000 0.038 0.009 0.009 0.001 0.006
1600 0.031 0.059 0.092 0.006 0.052 0.015 0.015 0.008 0.016
1920 0.046 0.076 0.102 0.014 0.066 0.020 0.020 0.014 0.025
T/YHC048E3,4 1280 0.015 0.042 0.081 0.000 0.038 0.009 0.009 0.001 0.006
1600 0.031 0.059 0.092 0.006 0.052 0.015 0.015 0.008 0.016
1920 0.046 0.076 0.102 0.014 0.066 0.020 0.020 0.014 0.025
5 T/YHC060E1 1600 0.031 0.059 0.091 0.007 0.052 0.015 0.015 0.008 0.016
2000 0.049 0.079 0.105 0.014 0.069 0.021 0.021 0.015 0.026
2400 0.070 0.101 0.118 0.026 0.086 0.029 0.029 0.024 0.040
T/YHC060E3,4 1600 0.031 0.059 0.091 0.007 0.052 0.015 0.015 0.008 0.016
2000 0.049 0.079 0.105 0.014 0.069 0.021 0.021 0.015 0.026
2400 0.070 0.101 0.118 0.026 0.086 0.029 0.029 0.024 0.040
(i)OA = Outside Air and RA = Return Air.
(ii)
Nominal kW ratings at 240, 480, 600 volts. Heaters only available on T_C units.
(iii)
Tested with standard filters (1” filters). Difference in pressure drop should be considered when utilizing optional 2” pleated filters.
Unit applications below 320 CFM/Ton are not applicable with Gas Heat or Electric Heaters.

84 RT-PRC023-EN
Performance Data

Table 116. Gas Fired Heating Capacities — Standard Efficiency


Unit Model Heating Heating Air Temp.
Tons Number Input MBH(i) Output MBH Rise, F
3 YSC036E1*(L,X) 60 48 25-55
YSC036E1*(M,Y) 80 65 35-65
YSC036E1*(H,Z) 120 96 55-85
YSC036E(3,4,W)*(L,X) 60 48 25-55
YSC036E(3,4,W)*(M,Y) 80 64 35-65
YSC036E(3,4,W)*(H,Z) 120 96 55-85
4 YSC048E1*(L,X) 60 49 15-45
YSC048E1*(M,Y) 80 65 20-50
YSC048E1*(H,Z) 120 96 40-70
YSC048E(3,4,W)*(L,X) 60 48 15-45
YSC048E(3,4,W)*(M,Y) 80 64 20-50
YSC048E(3,4,W)*(H,Z) 120 96 40-70
5 YSC060E1*(L,X) 60 48 10-40
YSC060E1*(M,Y) 80 65 15-45
YSC060E1*(H,Z) 130 104 35-65
YSC060E(3,4,W)*(L,X) 60 48 10-40
YSC060E(3,4,W)*(M,Y) 80 64 15-45
YSC060E(3,4,W)*(H,Z) 130 104 35-65
6 YSC072E(3,4,W)*(L,X) 80.0 64.8 15-45
YSC072E(3,4,W)*(M,Y) 120.0 97.2 20-50
YSC072E(3,4,W)*(H,Z) 150.0/105 121.5/85 25-55
7½ YSC092E(3,4,W)*(L,X) 120.0 97.2 20-50
YSC092E(3,4,W)*(M,Y) 150.0/105 121.5/85 25-55
YSC092E(3,4,W)*(H,Z) 200.0/140 160.0/112 35-65
8½ YSC102E(3,4,W)*(L,X) 120.0 97.2 15-45
YSC102E(3,4,W)*(M,Y) 150.0/105 121.5/85 20-50
YSC102E(3,4,W)*(H,Z) 200.0/140 160.0/112 35-65
10 YSC120E(3,4,W)*(L,X) 150.0/105 121.5/85 20-50
YSC120E(3,4,W)*(M,Y) 200.0/140 162.0/113 25-55
YSC120E(3,4,W)*(H,Z) 250.0/175 202.5/141.8 35-65
Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000 ft. elevation.
(i) For two stage heaters (input or output), Second stage is total heating capacity. Second Stage/First Stage.

Table 117. Gas Fired Heating Capacities — High Efficiency


Unit Model Heating Heating Air Temp.
Tons Number Input MBH Output MBH Rise, F
3 YHC036E1*(L,X) 60 48 25 - 55
YHC036E1*(M,Y) 80 65 35 - 65
YHC036E1*(H,Z) 120 96 55 - 85
YHC036E(3,4)*(L,X) 60 48 25 - 55
YHC036E(3,4)*(M,Y) 80 64 35 - 65
YHC036E(3,4)*(H,Z) 120 96 55 - 85
4 YHC048E1*(L,X) 60 49 10 - 40
YHC048E1*(M,Y) 80 64 20 - 50
YHC048E1*(H,Z) 120 96 40 - 70
YHC048E(3,4)*(L,X) 60 48 10 - 40
YHC048E(3,4)*(M,Y) 80 64 20 - 50
YHC048E(3,4)*(H,Z) 120 96 40 - 70
5 YHC060E1*(L,X) 60 49 10 - 40
YHC060E1*(M,Y) 80 64 15 - 45
YHC060E1*(H,Z) 130 104 35 - 65
YHC060E(3,4)*(L,X) 60 48 10 - 40
YHC060E(3,4)*(M,Y) 80 64 15 - 45
YHC060E(3,4)*(H,Z) 130 104 35 - 65
Ratings shown are for elevations up to 2,000 ft. For higher elevations, reduce ratings at a rate of 4% per 1,000 ft. elevation.

RT-PRC023-EN 85
Performance Data

Table 118. Auxiliary Electric Heat Capacity


Total(i) Stage1 Stage 2
Unit Model kW MBH No. of kW MBH kW MBH
Tons Number Input(ii) Output Stages Input Output Input Output
3 T*C036E1 5.00 17.07 1 5.00 17.07 — —
WSC036E1 10.00 34.14 2 5.00 17.07 5.00 17.07
13.80 47.11 2 5.00 17.07 8.80 30.04
T*C036E3, E4, EW(iii) 6.00 20.48 1 6.00 20.48 — —
WSC036E3, E4, EW 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
4 T*C048E1 5.00 17.07 1 5.00 17.07 — —
WSC048E1 10.00 34.14 2 5.00 17.07 5.00 17.07
13.80 47.11 2 5.00 17.07 8.80 30.04
17.60 60.09 2 8.80 30.04 8.80 30.04
T*C048E3, E4, EW(iii) 6.00 20.48 1 6.00 20.48 — —
WSC048E3, E4, EW 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
5 T*C060E1 5.00 17.07 1 5.00 17.07 — —
WSC060E1 10.00 34.14 2 5.00 17.07 5.00 17.07
13.80 47.11 2 5.00 17.07 8.80 30.04
17.60 60.09 2 8.80 30.04 8.80 30.04
T*C060E3, E4, EW(iii) 6.00 20.48 1 6.00 20.48 — —
WSC060E3, E4, EW 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
23.00 78.52 2 8.70 29.70 14.30 48.82
6 TSC072E3,4,W 9.00 30.73 1 9.00 30.73 — —
18.00 61.45 1 18.00 61.45 — —
27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
7½ TSC092E3,4,W 9.00 30.73 1 9.00 30.73 — —
18.00 61.45 1 18.00 61.45 — —
27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
8½ TSC102E3,4,W 9.00 30.73 1 9.00 30.73 — —
18.00 61.45 1 18.00 61.45 — —
27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
10 TSC120E3,4,W 27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
54.00 184.36 2 36.00 122.90 18.00 61.45
(i) Heaters are rated at 240v,380v,480v and 600v. For other than rated voltage, CAP= (voltage/rated voltage)2 x rated cap.
(ii) All input/output does not include indoor fan power or heat.
(iii) 600v is not available on high efficiency units.

86 RT-PRC023-EN
Performance Data

Table 119. Electric Heater Voltage Correction Factors


(Applicable to Auxiliary Heat Capacity)
Nominal Distribution Capacity
Voltage Voltage Multiplier
208 0.751
240 230 0.918
240 1.000
440 0.840
480 460 0.918
480 1.000
540 0.810
600 575 0.918
600 1.000

Table 120. Air Temperature Rise Across Electric Heaters (Degrees F)


3 Tons(i) 4 Tons 5 Tons(ii)
1200 CFM 1600 CFM 2000 CFM
Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase
kW Stages T*C036E1 T*C036E3,E4,EW(iii) T*C048E1 T*C048E3, E4, EW(iii) T*C060E1 T*C060E3, E4, EW(iii)
WSC036E1 WSC036E3,E4,EW WSC048E1 WSC048E3, E4, EW WSC060E1 WSC060E3, E4, EW
5.00 1 13.8 — 10.5 — 8.5 —
6.00 1 — 18.5 — 10.5 — 11.4
10.00 2 26.8 — 20.3 — 16.3 —
12.00 2 — 36.2 — 22.3 — 21.5
13.80 2 36.9 — 27.8 — 22.3 —
17.40 2 — 48.2 — 33.0 — 30.0
17.60 2 — — 35.5 — 28.3 —
23.0 2 — — — — — 38.8
For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula:
Temp. rise across Electric Heater = kWx3414/1.08xCFM.
(i) The minimum allowable airflow for a 3 ton with a 17.4 kW heater is 1080 CFM.
(ii) The minimum allowable airflow for a 5 ton unit with a 23.0 kW heater is 1900 CFM.
(iii) 600v is not available on high efficiency units.

Table 121. 6-10 Tons Air Temperature Rise Across Electric Heaters (Degrees F)
6 Tons 7½ Tons 8½ Tons 10 Tons
2000 CFM 3000 CFM 3400 CFM(i) 4000 CFM
kW Stages TSC072A3, A4, AW TSC092E3,4,W TSC102E3,4,W TSC120E3,4,W
9.00 1 14.2 9.5 8.4 —
11.30 1 — — — —
16.90 2 — — — —
18.00 1 28.5 19.0 16.7 14.2
22.60 2 — — — —
27.00 2 42.7 28.5 25.1 21.3
33.80 2 — — — —
36.00 2 56.9 37.9 33.5 28.5
54.00 2 — — — 42.7
For minimum design airflow, see airflow performance table for each unit. To calculate temp
rise at different airflow, use the following formula:
Temp. rise across Electric Heater = kWx3414/1.08xCFM.
(i) Minimum allowable airflow with a 17.4 or 17.6 kW heater is 1440 cfm.

RT-PRC023-EN 87
Performance Data

Table 122. 3 Tons Single Phase Heating Capacities (Net) WSC036E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 12.3 11.4 11.0 10.5 2.54 2.82 2.96 3.11
-3 14.3 13.5 13.0 12.5 2.58 2.85 3.00 3.17
2 16.5 15.7 15.2 14.8 2.61 2.89 3.05 3.21
7 17.6 16.6 16.0 15.4 2.62 2.90 3.05 3.21
12 20.0 18.9 18.2 17.7 2.67 2.96 3.10 3.26
17 22.4 21.2 20.6 20.0 2.71 2.99 3.14 3.30
22 25.0 23.7 23.1 22.5 2.75 3.03 3.19 3.36
27 27.7 26.4 25.6 25.0 2.80 3.10 3.26 3.43
32 30.3 28.8 28.2 27.4 2.84 3.13 3.30 3.47
37 33.1 31.6 30.8 30.1 2.89 3.20 3.37 3.54
42 35.8 34.2 33.4 32.6 2.94 3.24 3.42 3.60
47 38.8 37.0 36.2 35.4 3.00 3.31 3.49 3.67
52 41.5 39.7 38.8 37.9 3.05 3.37 3.54 3.73
57 44.6 42.6 41.7 40.7 3.12 3.44 3.62 3.81
62 47.4 45.3 44.3 43.3 3.17 3.51 3.69 3.88
67 50.5 48.3 47.4 46.2 3.23 3.59 3.78 3.96
72 53.4 51.0 49.9 48.7 3.30 3.65 3.84 4.04
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

Table 123. 3 Tons Three Phase Heating Capacities (Net) WSC036E3,E4,EW at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 11.7 11.0 10.5 10.2 2.41 2.68 2.81 2.97
-3 13.8 13.0 12.6 12.1 2.45 2.72 2.87 3.02
2 15.9 15.0 14.7 14.3 2.48 2.75 2.92 3.07
7 16.9 15.8 15.3 14.7 2.48 2.76 2.91 3.05
12 19.5 18.3 17.8 17.1 2.53 2.81 2.94 3.12
17 21.8 20.7 20.1 19.5 2.57 2.85 3.02 3.17
22 24.4 23.1 22.6 21.9 2.62 2.90 3.06 3.22
27 27.2 26.0 25.3 24.7 2.66 2.96 3.11 3.29
32 29.9 28.5 27.8 27.1 2.71 3.01 3.18 3.35
37 32.9 31.4 30.7 30.0 2.77 3.08 3.25 3.42
42 35.5 34.0 33.2 32.5 2.82 3.14 3.31 3.49
47 38.7 37.0 36.2 35.5 2.90 3.21 3.38 3.58
52 41.4 39.7 38.8 38.1 2.95 3.27 3.45 3.65
57 44.7 42.9 41.9 41.1 3.02 3.35 3.53 3.73
62 47.5 45.6 44.6 43.8 3.09 3.42 3.61 3.82
67 50.7 48.7 47.8 46.8 3.16 3.51 3.70 3.91
72 53.5 51.5 50.5 49.5 3.22 3.59 3.79 3.99
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

88 RT-PRC023-EN
Performance Data
(4 Tons)

Table 124. 4 Tons Single Phase Heating Capacities (Net) WSC048E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 15.2 14.0 13.4 12.8 3.23 3.60 3.81 4.02
-3 17.6 16.5 15.8 15.2 3.24 3.61 3.81 4.03
2 20.3 19.0 18.5 17.8 3.28 3.62 3.83 4.07
7 20.8 19.2 18.3 17.6 3.24 3.59 3.77 3.97
12 23.9 22.2 21.4 20.6 3.27 3.61 3.80 4.01
17 26.6 25.0 24.2 23.4 3.28 3.63 3.82 4.03
22 29.8 28.2 27.3 26.4 3.33 3.68 3.88 4.08
27 33.2 31.5 30.6 29.8 3.37 3.72 3.91 4.13
32 36.2 34.5 33.5 32.6 3.41 3.77 3.95 4.17
37 39.8 37.9 36.9 36.0 3.46 3.81 4.01 4.22
42 42.9 40.9 39.9 38.9 3.50 3.86 4.06 4.27
47 46.6 44.4 43.3 42.3 3.56 3.91 4.11 4.34
52 49.9 47.6 46.4 45.5 3.61 3.97 4.17 4.39
57 53.8 51.2 50.2 49.1 3.67 4.02 4.24 4.46
62 57.3 54.6 53.4 52.2 3.72 4.09 4.30 4.52
67 61.4 58.5 57.1 55.8 3.79 4.16 4.37 4.59
72 64.9 61.9 60.4 59.0 3.85 4.22 4.44 4.67
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

Table 125. 4 Tons Three Phase Heating Capacities (Net) WSC048E3,E4,EW at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 13.9 12.3 11.4 10.4 3.02 3.33 3.51 3.69
-3 16.7 15.0 14.1 13.2 3.06 3.38 3.55 3.74
2 19.5 17.8 17.1 16.1 3.11 3.44 3.61 3.81
7 20.7 19.0 17.9 16.9 3.11 3.44 3.61 3.80
12 23.8 22.0 21.1 20.0 3.16 3.49 3.67 3.85
17 26.6 24.9 23.9 22.9 3.20 3.53 3.71 3.90
22 29.9 28.1 27.1 26.1 3.24 3.59 3.77 3.96
27 33.3 31.4 30.4 29.3 3.29 3.65 3.82 4.02
32 36.2 34.3 33.3 32.3 3.33 3.69 3.88 4.07
37 39.8 37.8 36.8 35.8 3.39 3.74 3.94 4.15
42 42.9 40.8 39.8 38.7 3.44 3.79 3.99 4.20
47 46.6 44.4 43.3 42.1 3.50 3.86 4.05 4.26
52 50.0 47.6 46.5 45.3 3.55 3.92 4.12 4.33
57 53.9 51.3 50.3 49.0 3.62 3.98 4.19 4.41
62 57.5 54.7 53.4 52.2 3.69 4.05 4.25 4.48
67 61.5 58.7 57.4 56.0 3.75 4.13 4.34 4.56
72 65.0 62.3 60.8 59.3 3.82 4.21 4.42 4.64
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

RT-PRC023-EN 89
Performance Data
(5 Tons)

Table 126. 5 Tons Single Phase Heating Capacities (Net) WSC060E1 at 1200 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 18.6 17.1 16.4 15.7 3.73 4.16 4.37 4.60
-3 22.2 20.9 20.1 19.4 3.82 4.26 4.49 4.71
2 26.0 24.6 23.8 23.0 3.88 4.31 4.55 4.79
7 28.4 26.7 25.7 24.9 3.92 4.36 4.58 4.80
12 32.3 30.2 29.5 28.6 3.97 4.45 4.66 4.91
17 36.2 34.5 33.6 32.7 4.03 4.46 4.69 4.97
22 40.1 38.3 37.4 36.4 4.08 4.52 4.75 5.01
27 44.1 42.2 41.3 40.4 4.15 4.61 4.84 5.08
32 48.2 46.2 45.2 44.2 4.21 4.66 4.90 5.15
37 52.4 50.3 49.2 48.2 4.27 4.72 4.97 5.24
42 56.5 54.3 53.2 52.1 4.33 4.79 5.04 5.31
47 60.7 58.5 57.4 56.2 4.41 4.86 5.12 5.39
52 64.9 62.7 61.4 60.1 4.48 4.94 5.20 5.47
57 69.7 67.0 65.6 64.3 4.55 5.03 5.28 5.57
62 74.1 71.2 69.8 68.4 4.62 5.11 5.38 5.66
67 79.0 75.6 74.1 72.6 4.72 5.19 5.47 5.76
72 83.3 79.9 78.2 76.6 4.80 5.29 5.58 5.88
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

Table 127. 5 Tons Three Phase Heating Capacities (Net) WSC060E3,E4,EW at 1600 CFM
Outdoor Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp(i) at Indicated Indoor Dry Bulb Temp
F. 60 70 75 80 60 70 75 80
-8 20.4 19.4 18.8 18.3 3.68 4.13 4.37 4.64
-3 23.7 22.6 22.0 21.5 3.76 4.21 4.45 4.73
2 27.1 26.0 25.4 24.8 3.84 4.30 4.53 4.81
7 28.6 27.2 26.4 25.7 3.85 4.29 4.54 4.80
12 32.4 30.8 30.1 29.3 3.92 4.37 4.63 4.89
17 36.0 34.4 33.6 32.8 3.98 4.44 4.69 4.96
22 39.9 38.2 37.4 36.6 4.06 4.52 4.77 5.05
27 44.0 42.3 41.3 40.4 4.13 4.61 4.85 5.13
32 47.9 46.1 45.1 44.2 4.20 4.68 4.94 5.21
37 52.2 50.2 49.3 48.3 4.28 4.76 5.03 5.31
42 56.3 54.2 53.2 52.2 4.36 4.84 5.12 5.41
47 60.8 58.5 57.4 56.4 4.45 4.94 5.21 5.50
52 65.0 62.6 61.5 60.3 4.54 5.03 5.30 5.60
57 69.7 67.1 65.9 64.7 4.64 5.13 5.40 5.70
62 74.0 71.3 70.0 68.8 4.74 5.24 5.51 5.81
67 78.8 75.9 74.6 73.2 4.85 5.36 5.63 5.93
72 83.1 80.2 78.7 77.2 4.95 5.48 5.75 6.04
For other airflow conditions, see heating capacity correction factor Table 119.
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other
conditions, subtract fan heat at this condition and add fan heat at new condition.
(i) Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power
(kw) are at 70% OD relative humidity and demand defrost cycle.

90 RT-PRC023-EN
Controls

ReliaTel™ Controlled Integrated Comfort™ System Programmable Night Setback


Units Sensor(s) Auto or manual changeover with
available with seven-day programming. Keyboard
Zone Sensors are the building optional selection of Heat, Cool, Fan, Auto, or
occupant’s comfort control devices temperature On. All programmable sensors have
for Precedent™ units with the Micro adjustment System On, Heat, Cool, Service LED/
control: and override indicators as standard. Night Setback
buttons to Sensors have one (1) Occupied, one
Manual Changeover provide central (1) Un-occupied, and two (2)
Heat, Cool or Off control Override programs per day.
System Switch. through a
Fan Auto or Off Trane Mo

Switch. One Integrated PM


MODE
OCCUPIED

temperature Comfort™ system. AUTO


FAN

setpoint lever.
AUTO

Dual Thermistor Remote Zone MODE

Sensor
This sensor will allow the customer
to reduce the total number of remote
sensors to obtain space temperature Humidity Sensor
Manual/ averaging. This sensor should be Field installed,
Automatic Changeover utilized with ReliaTel controls. wall-mounted or
Auto, Heat, Cool duct-mounted
or Off System Digital Display Zone Sensor humidity sensor
Switch. Fan The Digital LCD is used to control
Auto or Off (Liquid Crystal activation of the
Switch. Two Display) zone hot gas reheat
temperature sensor has the dehumidification
setpoint levers. look and option. The
Optional Status functionality of humidity sensor
Indication LED standard zone can be set for
lights, System sensors. This humidity levels
On, Heat, Cool, sensor includes a between 40% and 60% relative
or Service. digital display of humidity by adjusting the ReliaTel
set point Options Module.
Remote Sensor adjustment and
space CO2 Sensing
Sensor(s) available for all zone temperature in F (Fahrenheit) or C
sensors to provide remote sensing The CO2
(Celsius). Includes FAN and SYSTEM sensor shall
capabilities. buttons (supports the service have the
functions of the standard sensor). E- ability to
squared memory stores last monitor space
programmed set points. Requires 24 occupancy
VAC (Volts AC). This sensor should levels within
be utilized with ReliaTel™ controls. the building
by measuring
the parts per
million of CO2
(Carbon
Dioxide) in the air. As the CO2 levels
increase, the outside air damper
modulates to meet the CO2 space
ventilation requirements. The CO2
accessory shall be available as field
installed.

RT-PRC023-EN 91
Controls

Digital Display Programmable Digital Display Thermostat


Thermostat (2H/2C) (3H/2C)
Two Heat/Two Cool digital display Three Heat, Two Cool digital display
thermostat. 7-day programmable stat thermostat. Easy access battery
with night setback shall be available. replacement. Flip-out door for easy
battery replacement without
removing or disassembling the
Tue
thermostat.
Hold Until

Auto
Heat

System & Fan Override More

Touchscreen Programmable
Thermostat (2H/2C)
RA Remote Sensor
Two Heat/Two Cool programmable
thermostat with touch screen digital Return Air Remote Sensor which can
display. Menu-driven programming. be mounted in the return air duct to
Effortless set-up. Program each day report return air temperature.
separately with no need to copy
multiple days. All programming can Room Remote Sensor
be done on one screen. Easy to read
and use. Large, clear backlit digital Space Remote Sensor which can be
display. mounted on the wall to report/control
from a remote location in the space.

MON TUE WED THU FRI SAT SUN

FAN
ON
HEAT
AUTO
CIRC

SYSTEM RESET CANCEL


EM HEAT PERIOD DEHUMIDIFIER
HEAT
OFF
COOL
COOL PM
AUTO

DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL

Digital Display Programmable


Thermostat with Built-In Relative
Humidity Sensing (3H/2C)
Three Heat/Two Cool digital display
thermostat with built-in humidity
control and display. This thermostat
combines both humidity and dry
bulb into one. Fully programmable
with night setback.
Tue

92 RT-PRC023-EN
Electrical Data

Table 128. Unit Wiring — Standard Efficiency


Standard Indoor Fan Motor(i) Oversized Indoor Fan Motor
Max Fuse Size Max Fuse Size
Unit Model Voltage or Max Circuit or Max Circuit
Tons Number Range MCA Breaker MCA Breaker
3 T/YSC036E1 187-253 27.2 40 — —
T/YSC036E3 187-253 21.4 30 — —
T/YSC036E4 414-506 10.1 15 — —
T/YSC036EW 517-633 8.0 15 — —
4 T/YSC048E1 187-253 35.2 50 — —
T/YSC048E3 187-253 25.2 35 — —
T/YSC048E4 414-506 12.5 15 — —
T/YSC048EW 517-633 9.0 15 — —
5 T/YSC060E1 187-253 43.8 70 — —
T/YSC060E3 187-253 29.5 45 — —
T/YSC060E4 414-506 15.5 25 — —
T/YSC060EW 517-633 10.1 15 — —
6 T/YSC072E3 187-253 36.5 50 37.8 60
T/YSC072E4 414-506 18.2 25 18.8 25
T/YSC072EW 517-633 12.7 20 13.5 20
7½(ii) T/YSC092E3 187-253 43.3 50 46.4 60
T/YSC092E4 414-506 21.5 25 23.0 30
T/YSC092EW 517-633 15.9 20 17.1 20
8½ T/YSC102E3 187-253 46.3 60 49.4 60
T/YSC102E4 414-506 21.9 25 23.4 30
T/YSC102EW 517-633 17.5 20 18.7 20
10 T/YSC120E3 187-253 55.9 60 59.9 60
T/YSC120E4 414-506 26.5 35 28.5 35
T/YSC120EW 517-633 21.2 25 22.9 30
3 WSC036E1 187-253 31.2 45 — —
WSC036E3 187-253 23.8 35 — —
WSC036E4 414-506 11.4 15 — —
WSC036EW 517-633 8.8 15 — —
4 WSC048E1 187-253 38.9 60 — —
WSC048E3 187-253 27.5 40 — —
WSC048E4 414-506 12.3 15 — —
WSC048EW 517-633 9.5 15 — —
5 WSC060E1 187-253 44.6 70 — —
WSC060E3 187-253 30.2 45 — —
WSC060E4 414-506 14.7 20 — —
WSC060EW 517-633 11.0 15 — —
(i) No optional motors available for 3-5 Tons. The standard motor for the single phase models is a Multispeed Direct Drive Motor.
The standard motor for the 3-phase models is a Belt Drive Motor.
(ii) Dual refrigeration system.

RT-PRC023-EN 93
Electrical Data
(Standard Efficiency)

Table 129. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency
Standard Indoor Motor Oversized Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size or Max Fuse Size or
Tons Number Number Rating(i) Stages MCA Max Circuit Breaker MCA Max Circuit Breaker
208/230 Volts Single Phase
3 TSC036E1 BAYHTRE105A 3.8/5.0 1 30.1/33.5 40.0/40.0 — —
BAYHTRE110A 7.5/10.0 2 52.6/59.6 60.0/60.0 — —
BAYHTRE114A 10.4/13.8 2 69.8/79.4 70.0/80.0 — —
4 TSC048E1 BAYHTRE105A 3.8/5.0 1 35.2/35.5 50.0/50.0 — —
BAYHTRE110A 7.5/10.0 2 54.6/61.6 60.0/70.0 — —
BAYHTRE114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRE118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
5 TSC060E1 BAYHTRE105A 3.8/5.0 1 43.8/43.8 70.0/70.0 — —
BAYHTRE110A 7.5/10.0 2 54.6/61.6 70.0/70.0 — —
BAYHTRE114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRE118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
208/230 Volts Three Phase
3 TSC036E3 BAYHTRE306A 4.5/6.0 1 21.9/24.3 30.0/30.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 40.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
4 TSC048E3 BAYHTRE306A 4.5/6.0 1 25.2/25.2 35.0/35.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 40.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
5 TSC060E3 BAYHTRE306A 4.5/6.0 1 29.5/29.5 45.0/45.0 — —
BAYHTRE312A 9.0/12.0 2 37.5/42.4 45.0/45.0 — —
BAYHTRE318A 13.1/17.4 2 51.6/58.6 60.0/60.0 — —
BAYHTRE323A 17.3/23.0 2 66.3/75.4 70.0/80.0 — —
6 TSC072E3 BAYHTRS309A 6.8/9.0 1 36.5/36.5 50/50 37.8/37.8 60/60
BAYHTRS318A 13.5/18.0 1 53.1/60.4 60/70 54.8/62.0 60/70
BAYHTRS327A 20.3/27.0 2 76.6/87.5 80/90 78.3/89.1 80/90
BAYHTRS336A 27.0/36.0 2 100.1/114.5 110/125 101.8/116.1 110/125
7½(ii) TSC092E3 BAYHTRT309A 6.8/9.0 1 43.3/43.3 50/50 46.4/46.4 60/60
BAYHTRT318A 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
BAYHTRT327A 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
BAYHTRT336A 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
8.5 TSC102E3 BAYHTRT309A 6.8/9.0 1 46.3/46.3 60/60 49.4/49.4 60/60
BAYHTRT318A 13.5/18.0 1 54.8/62.0 60/70 58.6/65.9 60/70
BAYHTRT327A 20.3/27.0 2 78.3/89.1 80/90 82.1/93.0 90/100
BAYHTRT336A 27.0/36.0 2 101.8/116.1 110/125 105.6/120.0 110/125
10 TSC120E3 BAYHTRT318A 13.5/18.0 1 58.6/65.9 60/70 63.6/70.9 80/80
BAYHTRT327A 20.3/27.0 2 82.1/93.0 90/100 87.1/98.0 90/100
BAYHTRT336A 27.0/36.0 2 105.6/120.0 110/125 110.6/125.0 125/125
BAYHTRT354A 40.6/54.0 2 152.5/141.7 175/150 157.5/146.7 175/150
480 Volts Three Phase
3 TSC036E4 BAYHTRE406A 6.0 1 12.1 15.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
4 TSC048E4 BAYHTRE406A 6.0 1 12.5 15.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
5 TSC060E4 BAYHTRE406A 6.0 1 15.5 25.0 — —
BAYHTRE412A 12.0 2 21.1 25.0 — —
BAYHTRE418A 17.4 2 29.3 30.0 — —
BAYHTRE423A 23.0 2 37.8 40.0 — —
6 TSC072E4 BAYHTRS409A 9.0 1 18.2 25 18.8 25
BAYHTRS418A 18.0 1 30.3 35 31.0 35
BAYHTRS427A 27.0 2 43.8 45 44.5 45
BAYHTRS436A 36.0 2 57.3 60 58.0 60

94 RT-PRC023-EN
Electrical Data
(Standard Efficiency)

Table 129. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency (continued)
Standard Indoor Motor Oversized Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size or Max Fuse Size or
Tons Number Number Rating(i) Stages MCA Max Circuit Breaker MCA Max Circuit Breaker
7½(ii) TSC092E4 BAYHTRT409A 9.0 1 21.5 25 23.0 30
BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
8½ TSC102E4 BAYHTRT409A 9.0 1 21.9 25 23.4 30
BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
10 TSC120E4 BAYHTRT418A 18.0 1 32.9 35 35.4 40
BAYHTRT427A 27.0 2 46.4 50 48.9 50
BAYHTRT436A 36.0 2 59.9 60 62.4 70
BAYHTRT454A 54.0 2 70.8 80 73.3 80
575 Volts Three Phase
3 TSC036EW BAYHTREW06A 6.0 1 9.4 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
4 TSC048EW BAYHTREW06A 6.0 1 9.4 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
5 TSC060EW BAYHTREW06A 6.0 1 10.1 15.0 — —
BAYHTREW12A 12.0 2 16.5 20.0 — —
BAYHTREW18A 17.4 2 23.0 25.0 — —
BAYHTREW23A 23.0 2 29.8 30.0 — —
6 TSC072EW BAYHTRSW09A 9.0 1 13.0 20 14.0 20
BAYHTRSW18A 18.0 1 23.8 25 24.8 25
BAYHTRSW27A 27.0 2 34.6 35 35.6 40
BAYHTRSW36A 36.0 2 45.4 50 46.4 50
7½(ii) TSC092EW BAYHTRTW18A 18.0 1 24.8 25 26.3 30
BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
8½ TSC102EW BAYHTRTW18A 18.0 1 24.8 25 26.3 30
BAYHTRTW27A 27.0 2 35.6 40 37.1 40
BAYHTRTW36A 36.0 2 46.4 50 47.9 50
10 TSC120EW BAYHTRTW18A 18.0 1 26.3 30 28.4 30
BAYHTRTW27A 27.0 2 37.1 40 39.3 40
BAYHTRTW36A 36.0 2 47.9 50 50.0 50
BAYHTRTW54A 54.0 2 56.6 60 58.8 60
(i) No optional motors available for 3-5 tons. The standard motor for 1-Phase models is a Multispeed, Direct Drive Motor. The Standard Motor for the 3-
Phase models is a Belt Drive Motor.
(ii) Dual refrigeration system.

RT-PRC023-EN 95
Electrical Data
(Standard Efficiency)

Table 130. Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency
Standard
Indoor Motor(i)
Unit Model Heater Model Heater kW Control Max Fuse Size or Max
Tons Number Number Rating Stages MCA Circuit Breaker
208/230 Volts Single Phase
3 WSC036E1 BAYHTRE105A 3.8/5.0 1 53.9/57.2 60.0/70.0
BAYHTRE110A 7.5/10.0 2 76.4/83.4 80.0/90.0
BAYHTRE114A 10.4/13.8 2 93.5/103.1 100.0/110.0
4 WSC048E1 BAYHTRE105A 3.8/5.0 1 61.6/64.9 80.0/80.0
BAYHTRE110A 7.5/10.0 2 84.1/91.1 90.0/100.0
BAYHTRE114A 10.4/13.8 2 101.2/110.8 110.0/125.0
BAYHTRE118A 13.2/17.6 2 118.4/130.6 125.0/150.0
5 WSC060E1 BAYHTRX105A 3.8/5.0 1 67.2/70.6 90.0/90.0
BAYHTRX110A 7.5/10.0 2 89.7/96.7 100.0/110.0
BAYHTRX114A 10.4/13.8 2 106.8/116.4 110.0/125.0
BAYHTRX118A 13.2/17.6 2 124.1/136.2 125.0/150.0
208/230 Volts Three Phase
3 WSC036E3 BAYHTRE306A 4.5/6.0 1 39.5/41.8 45.0/50.0
BAYHTRE312A 9.0/12.0 2 55.1/60.0 60.0/60.0
BAYHTRE318A 13.1/17.4 2 69.2/76.2 70.0/80.0
4 WSC048E3 BAYHTRE306A 4.5/6.0 1 43.2/45.5 50.0/50.0
BAYHTRE312A 9.0/12.0 2 58.8/63.7 60.0/70.0
BAYHTRE318A 13.1/17.4 2 72.9/79.9 80.0/80.0
5 WSC060E3 BAYHTRX306A 4.5/6.0 1 45.8/48.2 60.0/60.0
BAYHTRX312A 9.0/12.0 2 61.4/66.3 70.0/70.0
BAYHTRX318A 13.1/17.4 2 75.6/82.6 80.0/90.0
BAYHTRX323A 17.3/23.0 2 90.2/99.3 100.0/100.0
480 Volts Three Phase
3 WSC036E4 BAYHTRE406A 6.0 1 20.4 25.0
BAYHTRE412A 12.0 2 29.4 30.0
BAYHTRE418A 17.4 2 37.5 40.0
4 WSC048E4 BAYHTRE406A 6.0 1 21.3 25.0
BAYHTRE412A 12.0 2 30.3 35.0
BAYHTRE418A 17.4 2 38.4 40.0
5 WSC060E4 BAYHTRX406A 6.0 1 23.7 30.0
BAYHTRX412A 12.0 2 32.7 35.0
BAYHTRX418A 17.4 2 40.8 45.0
BAYHTRX423A 23.0 2 49.3 50.0
575 Volts Three Phase
3 WSC036EW BAYHTREW06A 6.0 1 16.1 20.0
BAYHTREW12A 12.0 2 23.2 25.0
BAYHTREW18A 17.4 2 29.7 30.0
4 WSC048EW BAYHTREW06A 6.0 1 16.7 20.0
BAYHTREW12A 12.0 2 23.8 25.0
BAYHTREW18A 17.4 2 30.3 35.0
5 WSC060EW BAYHTRXW06A 6.0 1 18.2 20.0
BAYHTRXW12A 12.0 2 25.4 30.0
BAYHTRXW18A 17.4 2 31.9 35.0
BAYHTRXW23A 23.0 2 38.6 40.0
(i) No optional motors available for 3-5 Tons. The standard motor for the 1 Phase Models is a Multispeed Direct Drive Motor. The
standard motor for the 3 Phase Models is a Belt Drive Motor.

96 RT-PRC023-EN
Electrical Data
(Standard Efficiency)

Table 131. Electrical Characteristics — Compressor Motor and Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motors Condenser Fan Motors
Unit Model Amps(i) Amps(i)
Tons Number No. Volts Phase HP(ii) RPM RLA LRA No. Volts Phase HP FLA LRA
3 T/YSC036E1 1 208-230 1 2.8 3500 15.4 83.0 1 208-230 1 0.33 2.0 6.6
T/YSC036E3 1 208-230 3 2.8 3500 11.5 77.0 1 208-230 1 0.33 2.0 6.6
T/YSC036E4 1 460 3 2.7 3500 5.1 35.0 1 460 1 0.33 1.2 2.5
T/YSC036EW 1 575 3 2.8 3500 4.3 31.0 1 575 1 0.33 0.9 1.3
4 T/YSC048E1 1 208-230 1 3.6 3500 20.5 109.0 1 208-230 1 0.33 2.0 6.6
T/YSC048E3 1 208-230 3 3.6 3500 14.6 91.0 1 208-230 1 0.33 2.0 6.6
T/YSC048E4 1 460 3 3.6 3500 7.1 46.0 1 460 1 0.33 1.2 2.5
T/YSC048EW 1 575 3 3.5 3500 5.1 34.0 1 575 1 0.33 0.9 1.3
5 T/YSC060E1 1 208-230 1 4.4 3500 26.9 145.0 1 208-230 1 0.40 2.5 6.6
T/YSC060E3 1 208-230 3 4.3 3500 17.6 123.0 1 208-230 1 0.40 2.5 6.6
T/YSC060E4 1 460 3 4.3 3500 9.6 62.0 1 460 1 0.40 1.0 2.8
T/YSC060EW 1 575 3 4.3 3500 6.1 40.0 1 575 1 0.40 0.8 2.0
6 T/YSC072E3 1 208-230 3 5.6 3500 22.4 149.0 1 208-230 1 .70 3.5 10.9
T/YSC072E4 1 460 3 5.6 3500 10.6 75.0 1 460 1 .70 2.4 6.6
T/YSC072EW 1 575 3 5.6 3500 7.7 54.0 1 575 1 .70 1.4 3.60
7½ T/YSC092E3 2 208-230 3 3.7/3.1 3500/3500 16/13.5 91.0/88.0 1 208-230 1 .70 3.5 10.9
T/YSC092E4 2 460 3 3.7/3.1 3500/3500 7.1/7.1 46.0/46.0 1 460 1 .70 2.4 6.6
T/YSC092EW 2 575 3 3.7/3.1 3500/3500 5.6/5.0 34.0/34.0 1 575 1 .70 1.4 3.60
8½ T/YSC102E3 2 208-230 3 3.7/3.7 3500/3500 16/16 91.0/96.0 1 208-230 1 .75 4.0 9.4
T/YSC102E4 2 460 3 3.7/3.7 3500/3500 7.1/7.1 46.0/46.0 1 460 1 .75 2.8 6.8
T/YSC102EW 2 575 3 3.7/3.7 3500/3500 5.6/5.6 37.0/37.0 1 575 1 .75 2.4 6.2
10 T/YSC120E3 2 208-230 3 4.8/3.7 3500/3500 20.5/16.9 155.0/91.0 1 208-230 1 .75 4.0 9.4
T/YSC120E4 2 460 3 4.8/3.7 3500/3500 9.6/7.1 75.0/46.0 1 460 1 .75 2.8 6.8
T/YSC120EW 2 575 3 4.8/3.7 3500/3500 7.6/5.6 54.0/37.0 1 575 1 .75 2.4 6.2
3 WSC036E1 1 208-230 1 3.2 3500 18.6 105.0 1 208-230 1 0.25 2.0 4.4
WSC036E3 1 208-230 3 3.2 3500 13.5 88.0 1 208-230 1 0.25 2.0 4.4
WSC036E4 1 460 3 3.2 3500 6.4 39.0 1 460 1 0.25 0.9 2.2
WSC036EW 1 575 3 3.2 3500 5.1 34.0 1 575 1 0.25 0.7 1.4
4 WSC048E1 1 208-230 1 3.8 3500 23.1 134.0 1 208-230 1 0.40 2.5 6.6
WSC048E3 1 208-230 3 3.8 3500 16.0 91.0 1 208-230 1 0.40 2.5 6.6
WSC048E4 1 460 3 3.8 3500 7.1 46.0 1 460 1 0.40 1.0 2.8
WSC048EW 1 575 3 3.8 3500 5.6 37.0 1 575 1 0.40 0.8 2.0
5 WSC060E1 1 208-230 1 4.8 3500 27.6 158.0 1 208-230 1 0.40 2.5 6.6
WSC060E3 1 208-230 3 4.7 3500 18.1 137.0 1 208-230 1 0.40 2.5 6.6
WSC060E4 1 460 3 4.7 3500 9.0 62.0 1 460 1 0.40 1.0 2.8
WSC060EW 1 575 3 4.7 3500 6.8 50.0 1 575 1 0.40 0.8 2.0
(i) Amp draw for each motor; multiply value by number of motors to determine total amps.
(ii) HP for each compressor.

RT-PRC023-EN 97
Electrical Data
(Standard Efficiency)

Table 132. Electrical Characteristics — Standard Evaporator Fan Motor — 60 Cycle — Direct or Belt Drive— Standard Efficiency
Unit Model Direct or Belt Amps
Tons Number Drive No. Volts Phase HP FLA LRA
3 T/YSC036E1 Direct Drive 1 208-230 1 0.75 6.0 —
T/YSC036E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC036E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC036EW Belt Drive 1 575 3 1.00 1.7 13.2
4 T/YSC048E1 Direct Drive 1 208-230 1 1.00 7.6 —
T/YSC048E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC048E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC048EW Belt Drive 1 575 3 1.00 1.7 13.2
5 T/YSC060E1 Direct Drive 1 208-230 1 1.00 7.6 —
T/YSC060E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
T/YSC060E4 Belt Drive 1 460 3 1.00 2.5 16.1
T/YSC060EW Belt Drive 1 575 3 1.00 1.7 13.2
6 T/YSC072E3 Belt Drive 1 208-230 3 1.00 5.00 32.20
T/YSC072E4 Belt Drive 1 460 3 1.00 2.50 16.10
T/YSC072EW Belt Drive 1 575 3 1.00 1.70 13.20
7½ T/YSC092E3 Belt Drive 1 208-230 3 2.00 6.30 48.00
T/YSC092E4 Belt Drive 1 460 3 2.00 3.10 24.00
T/YSC092EW Belt Drive 1 575 3 2.00 2.50 18.20
8½ T/YSC102E3 Belt Drive 1 208-230 3 2.00 6.30 48.00
T/YSC102E4 Belt Drive 1 460 3 2.00 3.10 24.00
T/YSC102EW Belt Drive 1 575 3 2.00 2.50 18.20
10 T/YSC120E3 Belt Drive 1 208-230 3 3.00 9.40 83.00
T/YSC120E4 Belt Drive 1 460 3 3.00 4.60 42.00
T/YSC120EW Belt Drive 1 575 3 3.00 3.70 31.00
3 WSC036E1 Direct Drive 1 208-230 1 0.75 6.0 —
WSC036E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC036E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC036EW Belt Drive 1 575 3 1.00 1.7 13.2
4 WSC048E1 Direct Drive 1 208-230 1 1.00 7.6 —
WSC048E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC048E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC048EW Belt Drive 1 575 3 1.00 1.7 13.2
5 WSC060E1 Direct Drive 1 208-230 1 1.00 7.6 —
WSC060E3 Belt Drive 1 208-230 3 1.00 5.0 32.2
WSC060E4 Belt Drive 1 460 3 1.00 2.5 16.1
WSC060EW Belt Drive 1 575 3 1.00 1.7 13.2

Table 133. Electrical Characteristics — Oversized Evaporator Fan Motor — 60 Cycle — Belt Drive — Standard Efficiency
Unit Model Amps
Tons Number No. Volts Phase HP FLA LRA
6 T/YSC072E3 1 208-230 3 2.00 6.30 48.00
T/YSC072E4 1 460 3 2.00 3.10 24.00
T/YSC072EW 1 575 3 2.00 2.50 18.20
7½ T/YSC092E3 1 208-230 3 3.00 9.40 83.00
T/YSC092E4 1 460 3 3.00 4.60 42.00
T/YSC092EW 1 575 3 3.00 3.70 31.00
8½ T/YSC102E3 1 208-230 3 3.00 9.40 83.00
T/YSC102E4 1 460 3 3.00 4.60 42.00
T/YSC102EW 1 575 3 3.00 3.70 31.00
10 T/YSC120E3 1 208-230 3 5.00 13.40 112.00
T/YSC120E4 1 460 3 5.00 6.60 56.00
T/YSC120EW 1 575 3 5.00 5.40 44.00

98 RT-PRC023-EN
Electrical Data
(Standard Efficiency)

Table 134. Electrical Characteristics — Power Exhaust (Cooling and Gas/Electric)


Tons Volts Phase HP RPM(i) FLA LRA
6-10 208-230 1 0.87 1075 5.7 16.3
6-10 460 1 0.87 1075 3.3 6.8
6-10 575 1 0.87 1075 2.3 5.4
(i) Two speed.

Table 135. Electrical Characteristics — Inducer Motor


Unit Model Number Stages HP RPM Volts Phase LRA
YSC(036-060)E**(L,M,X,Y) 1 1/35 3000 208-230 1 0.6
YSC072E**(L,M,X,Y) 1 1/35 3000 208-230 1 0.6
YSC(092,102)E**(L,X)
YSC072E**(H,Z) 2 1/15 2800/3350 208-230 1 0.5
YSC(092,102)E**(M,H,Y,Z)
YSC120E**(L,M,H,X,Y,Z)
YSC(036-060)E**(H,Z) 1 1/15 3300 208-230 1 0.4

RT-PRC023-EN 99
Electrical Data
(High Efficiency)

Table 136. Unit Wiring — High Efficiency


Standard Indoor Fan Motor Optional Belt Drive
Indoor Fan Motor(i)
Max Fuse Size Max Fuse Size
Unit Model Voltage or Max Circuit or Max Circuit
Tons Number Range MCA Breaker MCA Breaker
3 T/YHC036E1 187-253 26.7 40 (i) (i)
T/YHC036E3 187-253 21.9 30 20.9 30
T/YHC036E4 414-506 10.0 15 9.5 15
4 T/YHC048E1 187-253 35.7 50 (i) (i)
T/YHC048E3 187-253 28.3 40 25.7 40
T/YHC048E4 414-506 13.6 20 12.3 15
5 T/YHC060E1 187-253 43.8 70 (i) (i)
T/YHC060E3 187-253 32.1 45 29.5 45
T/YHC060E4 414-506 16.8 25 15.5 25
(i) No optional motors available for 3-5 Tons. The standard motor for the single phase models is a Multispeed
Direct Drive Motor.

Table 137. Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency
Standard Optional Belt Drive
Indoor Motor Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size Max Fuse Size
Tons Number Number Rating(i) Stages MCA or Max Circuit MCA or Max Circuit
Breaker Breaker
208/230 Volts Single Phase
3 THC036E1 BAYHTRE105A 3.8/5.0 1 30.1/33.5 40.0/40.0 — —
BAYHTRE110A 7.5/10.0 2 52.6/59.6 60.0/60.0 — —
BAYHTRE114A 10.4/13.8 2 69.8/79.4 70.0/80.0 — —
4 THC048E1 BAYHTRX105A 3.8/5.0 1 35.7/35.7 50.0/50.0 — —
BAYHTRX110A 7.5/10.0 2 54.6/61.6 60.0/70.0 — —
BAYHTRX114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRX118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
5 THC060E1 BAYHTRX105A 3.8/5.0 1 43.8/43.8 70.0/70.0 — —
BAYHTRX110A 7.5/10.0 2 54.6/61.6 70.0/70.0 — —
BAYHTRX114A 10.4/13.8 2 71.8/81.4 80.0/90.0 — —
BAYHTRX118A 13.2/17.6 2 89.0/101.1 90.0/110.0 — —
208/230 Volts Three Phase
3 THC036E3 BAYHTRE306A 4.5/6.0 1 23.1/25.5 30.0/30.0 21.9/24.3 30.0/30.0
BAYHTRE312A 9.0/12.0 2 38.8/43.6 40.0/45.0 37.5/42.4 40.0/45.0
BAYHTRE318A 13.1/17.4 2 52.9/59.9 60.0/60.0 51.6/58.6 60.0/60.0
4 THC048E3 BAYHTRX306A 4.5/6.0 1 28.3/28.3 40.0/40.0 25.7/25.7 40.0/40.0
BAYHTRX312A 9.0/12.0 2 40.8/45.6 45.0/50.0 37.5/42.4 40.0/45.0
BAYHTRX318A 13.1/17.4 2 54.9/61.9 60.0/70.0 51.6/58.6 60.0/60.0
5 THC060E3 BAYHTRX306A 4.5/6.0 1 32.1/32.1 45.0/45.0 29.5/29.5 45.0/45.0
BAYHTRX312A 9.0/12.0 2 40.8/45.6 45.0/50.0 37.5/42.4 45.0/45.0
BAYHTRX318A 13.1/17.4 2 54.9/61.9 60.0/70.0 51.6/58.6 60.0/60.0
BAYHTRX323A 17.3/23.0 2 69.5/78.6 70.0/80.0 66.3/75.4 70.0/80.0
460 Volts Three Phase
3 THC036E4 BAYHTRE406A 6.0 1 12.8 15.0 12.1 15.0
BAYHTRE412A 12.0 2 21.8 25.0 21.1 25.0
BAYHTRE418A 17.4 2 29.9 30.0 29.3 30.0
4 THC048E4 BAYHTRX406A 6.0 1 13.8 20.0 12.3 15.0
BAYHTRX412A 12.0 2 22.8 25.0 21.1 25.0
BAYHTRX418A 17.4 2 30.9 35.0 29.3 30.0
5 THC060E4 BAYHTRX406A 6.0 1 16.8 25.0 15.5 25.0
BAYHTRX412A 12.0 2 22.8 25.0 21.1 25.0
BAYHTRX418A 17.4 2 30.9 35.0 29.3 30.0
BAYHTRX423A 23.0 2 39.4 40.0 37.8 40.0
(i) Heater kW ratings are at 208/240v for 208/230v units, 480v for 460v units.

100 RT-PRC023-EN
Electrical Data
(High Efficiency)

Table 138. Electrical Characteristics — Compressor Motor and Condenser Fan Motor — 60 Cycle — High Efficiency
Unit Model Compressor Motors Condenser Fan Motors
Tons Number No. Volts Phase HP RPM RLA LRA No. Volts Phase HP FLA LRA
3 T/YHC036E1 1 208-230 1 2.8 3500 15.4 83.0 1 208-230 1 0.20 1.5 2.4
T/YHC036E3 1 208-230 3 2.8 3500 11.5 77.0 1 208-230 1 0.20 1.5 2.4
T/YHC036E4 1 460 3 2.7 3500 5.1 35.0 1 460 1 0.20 0.6 1.3
4 T/YHC048E1 1 208-230 1 3.6 3500 20.5 109.0 1 208-230 1 0.40 2.5 6.6
T/YHC048E3 1 208-230 3 3.6 3500 14.6 91.0 1 208-230 1 0.40 2.5 6.6
T/YHC048E4 1 460 3 3.6 3500 7.1 46.0 1 460 1 0.40 1.0 2.8
5 T/YHC060E1 1 208-230 1 4.4 3500 26.9 145.0 1 208-230 1 0.40 2.5 6.6
T/YHC060E3 1 208-230 3 4.3 3500 17.6 123.0 1 208-230 1 0.40 2.5 6.6
T/YHC060E4 1 460 3 4.3 3500 9.6 62.0 1 460 1 0.40 1.0 2.8

Table 139. Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Direct Drive — High Efficiency
Unit Model
Tons Number Volts Hz. Phase No. FLA LRA BHP
3 T/YHC036E1 208-230 60 1 1 6.0 — 0.75
T/YHC036E3 208-230 60 1 1 6.0 — 0.75
T/YHC036E4 460 60 1 1 6.0 — 0.75
4 T/YHC048E1 208-230 60 1 1 7.6 — 1.00
T/YHC048E3 208-230 60 1 1 7.6 — 1.00
T/YHC048E4 460 60 1 1 7.6 — 1.00
5 T/YHC060E1 208-230 60 1 1 7.6 — 1.00
T/YHC060E3 208-230 60 1 1 7.6 — 1.00
T/YHC060E4 460 60 1 1 7.6 — 1.00

Table 140. Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Optional Belt Drive — High Efficiency
Unit Model
Tons Number Volts Hz. Phase No. FLA LRA BHP
3 T/YHC036E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC036E4 460 60 3 1 2.5 16.1 1.00
4 T/YHC048E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC048E4 460 60 3 1 2.5 16.1 1.00
5 T/YHC060E3 208-230 60 3 1 5.0 32.2 1.00
T/YHC060E4 460 60 3 1 2.5 16.1 1.00

Table 141. Electrical Characteristics — Power Exhaust (Cooling and Gas/Electric)


Tons Volts Phase HP RPM(i) FLA LRA
6-10 208-230 1 0.87 1075 5.7 16.3
6-10 460 1 0.87 1075 3.3 6.8
6-10 575 1 0.87 1075 2.3 5.4
(i) Two Speed.

Table 142. Electrical Characteristics — Inducer Motor


Unit Model Number Stages HP RPM Volts Phase LRA
YHC036E(L,M,X,Y) 1 1/35 3000 208-230 1 0.6
YHC(048,060)E
YHC036E(H,Z) 1 1/15 3300 208-230 1 0.4

RT-PRC023-EN 101
Jobsite Connections

Table 143. Typical Number of Wires


Zone Sensors
A Manual Changeover.............................. 4
Manual/Auto Changeover...................... 5
Manual/Auto Changeover with
Status Indication LED’s......................... 10
Programmable Night Setback
with Status Indication LED’s................... 7
Thermostats
A 3 Wires, 24-volts, Cooling only
4 Wires, 24-volts, with Electric Heat
B 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)

DISCONNECT
SWITCH
(BY OTHERS)

ZONE SENSOR OR A
THERMOSTAT
ROOFTOP
UNIT

For specific wiring information, see the installation instructions.


All wiring except power wire is low voltage.
All customer supplied wiring to be copper and must conform to applicable electrical codes
(such as NEC or CEC) and local electric codes. Wiring shown dotted is to be furnished and
installed by the customer.

102 RT-PRC023-EN
Dimensional Data

Figure 1. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/Electric;
3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
* All dimensions are in inches/millimeters.
**1/2 NPT Gas Connection = (Y_C Models only); 2" Electrical Connection: Single Point Power When Heat Installed (T_C Models only.)

3 5/8” 14” 9 1/4” 15 1/2”


92 MM 356 MM 235 MM 394 MM
4”
102 MM

SUPPLY

16”
457 MM
24” RETURN
610 MM

TBU CONDENSATE 27 9/16”


701 MM
2 13/16”
71 MM 6 1/2”
4 3/16” 4 9/16” 3 11/16” 165 MM
106 MM 116 MM 94 MM
4 7/8”
124 MM
23 1/2” THROUGH 5 1/16”
597 MM THROUGH THE BASE 128 MM
THE BASE GAS ELECTRICAL
(Y_C MODELS 9 15/16”
ONLY) 253 MM

Figure 2. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Downflow Airflow Supply/Return - Through the Base Utilities
* All dimensions are in inches/millimeters.

RT-PRC023-EN 103
Dimensional Data
(3-5 Tons)

Figure 3. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Horizontal Airflow Supply/Return
* All dimensions are in inches/millimeters.

Figure 4. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and Gas/
Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Unit Clearance and Roof Opening
* All dimensions are in inches/millimeters.

104 RT-PRC023-EN
Dimensional Data
(3-5 Tons)

44 MM

44 MM
7

1038 MM

1053 MM

Figure 5. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and
Gas Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Roof Curb
* All dimensions are in inches/millimeters.

7
(433 MM)

Figure 6. Cooling and Gas/Electric - 3-5 Tons Standard Efficiency; Cooling and
Gas/Electric - 3 Tons High Efficiency; Heat Pump - 3-4 Tons Standard Efficiency
Downflow Duct Connections - Field Fabricated
* All dimensions are in inches/millimeters.

RT-PRC023-EN 105
Dimensional Data
(3-5 Tons)

Figure 7. Cooling and Gas/Electric - 3-5 Tons


Standard Efficiency; Cooling and Gas/Electric - 3
Tons High Efficiency; Heat Pump - 3-4 Tons
Standard Efficiency - Economizer, Manual or
Motorized Fresh Air Damper
* All dimensions are in inches/millimeters.

Figure 8. Gas/Electric Models - 3-5 Tons


Standard Efficiency; 3 Tons High Efficiency
Height of Gas Pipe required from Inside Base of
Unit to Gas Shut off assembly (Factory
Provided) - Y_C Models only
* All dimensions are in inches/millimeters.

Figure 9. Cooling and Gas/Electric - 3-5 Tons


Standard Efficiency; Cooling and Gas/Electric - 3
Tons High Efficiency; Heat Pump - 3-4 Tons
Standard Efficiency
Economizer & Barometric Relief Damper Hood
* All dimensions are in inches/millimeters.

106 RT-PRC023-EN
Dimensional Data
(3-5 Tons)

17 7/8" 16"
(454 MM) (406 MM)
Applicable to 22 1/4"
Y_C models only (565 MM)

Figure 10. Cooling and Gas/Electric Models - 3-5 Tons


Standard Efficiency; Cooling and Gas/Electric Models - 3
Tons High Efficiency; Heat Pump - 3-4 Tons Standard
Efficiency
Swing Diameter for Hinged Door(s) Option
* All dimensions are in inches/millimeters.

RT-PRC023-EN 107
Dimensional Data
(4-6 Tons)

Figure 11. Cooling and Gas/Electric 4-5 Tons High Efficiency;


Cooling and Gas/Electric - 6 Tons Standard Efficiency- Heat Pumps - 5 Tons Standard Efficiency
* All dimensions are in inches/millimeters.

Figure 12. Cooling and Gas/Electric 4-5 Tons High Efficiency;


Cooling and Gas/Electric - 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Downflow Airflow Supply/Return - Through the Base Utilities
* All dimensions are in inches/millimeters.

108 RT-PRC023-EN
Dimensional Data
(4-6 Tons)

Return

Supply

Figure 13. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Horizontal Airflow Supply and Return
* All dimensions are in inches/millimeters.

Figure 14. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Unit Clearance and Roof Opening
* All dimensions are in inches/millimeters.

RT-PRC023-EN 109
Dimensional Data
(4-6 Tons)

(356 MM)
(2130 MM)

Figure 15. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Roof Curb
* All dimensions are in inches/millimeters.

857

857

ALL FLANGES 1 1/4" (31 MM)


N
UR
RET

PLY
SUP

Figure 16. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and
Gas/Electric - 6 Tons Standard Efficiency - Heat Pumps - 5 Tons
Downflow Duct Connections Field Fabricated
* All dimensions are in inches/millimeters.

110 RT-PRC023-EN
Dimensional Data
(4-6 Tons)

Figure 17. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and Gas/
Electric - 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Barometric Relief Damper Hood
* All dimensions are in inches/millimeters.

17”
(432 MM)
21 3/8”
(543 MM)

34 5/8”
(879 MM)

Figure 18. Cooling and Gas/Electric 4-5 Tons High Efficiency; Cooling and
Gas/Electric 6 Tons Standard Efficiency; Heat Pumps - 5 Tons
Swing Diameter for Hinged Door(s) Option
* All dimensions are in inches/millimeters.

RT-PRC023-EN 111
Dimensional Data
(7½-10 Tons)

Figure 19. Cooling and Gas/Electric Models - 7½, 8½ and 10 Tons Standard Efficiency
* All dimensions are in inches/millimeters.
**1/2 NPT & 3/4" Gas Connection = (Y_C Models only); 2" Electrical Connection: Single Point Power When Heat Installed
(T_C Models only.)

Figure 20. Cooling and Gas/Electric - 7½-10 Tons Standard Efficiency


Downflow Airflow Supply/Return Through the Base Utilities
* All dimensions are in inches/millimeters.

112 RT-PRC023-EN
Dimensional Data
(7½-10 Tons)

Return

Supply

Figure 21. Cooling and Gas/Electric - 7½-10 Tons Standard Efficiency


Horizontal Airflow Supply and Return
* All dimensions are in inches/millimeters.

Figure 22. Cooling and Gas/Electric - 6-10 Tons Standard Efficiency


Unit Clearance and Roof Opening
* All dimensions are in inches/millimeters.

RT-PRC023-EN 113
Dimensional Data
(7½-10 Tons)

(356 MM)
(2130 MM)

Figure 23. Cooling and Gas/Electric - 7½-10 Tons Standard Efficiency


Roof Curb
* All dimensions are in inches/millimeters.

857

857

ALL FLANGES 1 1/4" (31 MM)


N
UR
RET

PLY
SUP

Figure 24. Cooling and Gas/Electric - 7½-10 Tons Standard Efficiency


Downflow Duct Connections Field Fabricated
* All dimensions are in inches/millimeters.

114 RT-PRC023-EN
Dimensional Data
(7½-10 Tons)

Figure 25. Cooling and Gas/Electric - 7½-10 Tons


Standard Efficiency - Power Exhaust
* All dimensions are in inches/millimeters.

Figure 26. Cooling and Gas/Electric - 7½-10 Tons


Standard Efficiency
Economizer & Barometric Relief Damper Hood
* All dimensions are in inches/millimeters.

Figure 27. Gas/Electric - 7½-10Tons Standard


Efficiency
Height of Gas Pipe required from Inside Base of
Unit to Gas Shut off assembly (Factory
Provided) - Y_C Models only
* All dimensions are in inches/millimeters.

RT-PRC023-EN 115
Dimensional Data
(7½-10 Tons)

17"
432 MM
21 3/8"
543 MM
Applicable to
Y_C models only

34 5/8"
879 MM

Figure 28. Cooling and Gas/Electric Models - 7½-10


Tons Standard Efficiency
Swing Diameter for Hinged Door(s) Option
* All dimensions are in inches/millimeters.

116 RT-PRC023-EN
Weights

Table 144. Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.)
Unit Maximum Model Corner Weights(ii) Center of Gravity (in.)
Weights(i)
Tons Model No. Shipping Net A B C D Length Width
3 TSC036E1,3,4,W 555 480 157 122 95 107 31 19
YSC036E1,3,4,W 607 532 165 137 95 134 31 19
WSC036E1,3,4,W 589 514 177 107 113 117 29 20
4 TSC048E1,3,4,W 586 511 167 129 101 114 31 19
YSC048E1,3,4,W 638 563 175 145 101 142 31 19
WSC048E1,3,4,W 600 525 181 109 115 119 29 20
5 TSC060E1,3,4,W 636 561 183 142 111 125 31 19
YSC060E1,3,4,W 688 613 190 158 110 155 31 19
WSC060E1,3,4,W 825 682 228 177 114 163 38 24
6 TSC072E 898 755 295 136 209 115 40 23
YSC072E 936 793 304 146 219 124 41 23
7½ TSC092E 1009 866 358 147 252 109 41 22
YSC092E 1059 916 370 160 265 121 41 22
8½ TSC102E 1048 905 359 161 265 120 42 23
YSC102E 1096 953 371 173 277 132 42 23
10 TSC120E 1139 996 388 185 281 142 41 23
YSC120E 1201 1058 403 201 297 157 42 23
(i) Weights are approximate.
(ii) Corner weights are given for information only.

Table 145. Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.)
Unit Maximum Model Corner Weights(ii) Center of Gravity (in.)
Weights(i)
Tons Model No. Shipping Net A B C D Length Width
3 THC036E1,3,4 566 472 109 85 186 92 40 26
YHC036E1,3,4 637 544 127 103 204 110 39 26
4 THC048E1,3,4 798 653 155 127 248 123 40 25
YHC048E1,3,4 869 725 173 145 266 141 40 25
5 THC060E1,3,4 823 676 204 74 327 71 41 26
YHC060E1,3,4 894 748 222 92 345 89 41 26
(i) Weights are approximate.
(ii) Corner weights are given for information only.

RT-PRC023-EN 117
Weights

Table 146. Factory Installed Options (FIOPS)/Accessory Net Weights (Lbs)(i),(ii)


T/YHC T/YHC T/YSC WSC***E
Net Weight Net Weight Net Weight Net Weight
Accessory 3 Tons 4-5 Tons 6-10 Tons 3-4 Tons 5 Tons
460 V IDM Transformer(iii) 29 29 — 29 29
Barometric Relief 7 10 10 7 10
Belt Drive Option 38 — — 38 —
Coil Guards 12 20 20 12 20
Economizer 26 36 36 26 36
Electric Heaters(iv) 15 30 15 15 30
Hinged Doors 10 12 12 10 12
Manual Outside Air Damper 16 26 26 16 26
Motorized Outside Air Damper 20 30 30 20 30
Novar Control 8 5 8 5 5
Oversized Motor — 8 8 5 8
Powered Convenience Outlet 38 38 38 38 38
Powered Exhaust — — 80 — —
Roof Curb 70 115 115 70 115
Smoke Detector, Supply 5 5 5 5 5
Smoke Detector, Return 7 7 7 7 7
Stainless Steel Heat Exchanger(v) 4 — 6 — —
Through the Base Electrical 8 13 13 8 13
Through the Base Gas 5 — 5 — —
Unit Mounted Circuit Breaker 5 5 5 5 5
Unit Mounted Disconnect 5 5 5 5 5
(i) Weights for options not listed are <5 lbs.
(ii) Net weight should be added to unit weight when ordering factory-installed accessories.
(iii) Apply weight with all 460V units with the Standard Direct Drive Motor.
(iv) Applicable to Cooling and Heat Pump units only.
(v) Applicable to Gas/Electric units only.

118 RT-PRC023-EN
Mechanical Specifications

General forklift and crane lifting, with forklift have single point power entry as
capabilities on three sides of the standard.
The units shall be convertible unit.
airflow. The operating range shall be
Evaporator and Condenser Coils
between 115°F and 0°F in cooling as
Compressors
standard from the factory for units Internally finned, 5/16” copper tubes
with microprocessor controls. All units shall have direct-drive, mechanically bonded to a configured
Operating range for units with hermetic, scroll type compressors aluminum plate fin shall be
electromechanical controls shall be with centrifugal type oil pumps. standard. Coils shall be leak tested at
between 115°F and 40°F. Cooling Motor shall be suction gas-cooled the factory to ensure the pressure
performance shall be rated in and shall have a voltage utilization integrity. The evaporator coil and
accordance with ARI testing range of plus or minus 10 percent of condenser coil shall be leak tested to
procedures. All units shall be factory unit nameplate voltage. Internal 575 psig and pressure tested to 450
assembled, internally wired, fully overloads shall be provided with the psig. The condenser coil shall have a
charged with R-410A, and 100 scroll compressors. patent pending 1+1+1 hybrid coil
percent run tested to check cooling designed with slight gaps for ease of
All standard and high efficiency units
operation, fan and blower rotation, cleaning. A removable, reversible,
shall have direct-drive, hermetic,
and control sequence before leaving double-sloped condensate drain pan
scroll type compressors with
the factory. Wiring internal to the with provision for through the base
centrifugal type oil pumps. Motor
unit shall be colored and numbered condensate drain is standard.
shall be suction gas-cooled and shall
for simplified identification. Units
have a voltage utilization range of
shall be UL listed and labeled,
plus or minus 10 percent of unit Filters
classified in accordance to UL 1995/
nameplate voltage. Internal One inch, throwaway filters shall be
CAN/CSA No. 236-M90 for Central
overloads shall be provided with the standard on all 3-4 ton standard
Cooling Air Conditioners. Canadian
scroll compressors. Crankcase efficiency heat pumps and 3 ton high
units shall be CSA Certified.
heaters shall be included on 6-10 ton efficiency units. Two inch throwaway
standard efficiency units. filters shall be standard on all 4-5 ton
Casing
high-efficiency units and 5 ton
Unit casing shall be constructed of Controls standard efficiency heat pumps.
zinc coated, heavy gauge, galvanized
Unit shall be completely factory- Two inch filters shall be factory
steel. Exterior surfaces shall be
wired with necessary controls and supplied on all 6-10 ton units.
cleaned, phosphatized, and finished
contactor pressure lugs or terminal Optional 2-inch pleated filters shall
with a weather-resistant baked
block for power wiring. Unit shall also be available.
enamel finish. Unit’s surface shall be
provide an external location for
tested 1000 hours in a salt spray test
mounting a fused disconnect device. Gas Heating Section
in compliance with ASTM B117.
Cabinet construction shall allow for A choice of microprocessor or The heating section shall have a
all maintenance on one side of the electromechanical controls shall be progressive tubular heat exchanger
unit. Service panels shall have lifting available. design using stainless steel burners
handles and be removed and and corrosion resistant steel
Microprocessor controls provide for
reinstalled by removing two throughout. An induced draft
all 24 volt control functions. The
fasteners while providing a water combustion blower shall be used to
resident control algorithms shall
and air tight seal. All exposed pull the combustion products
make all heating, cooling, and/or
vertical panels and top covers in the through the firing tubes. The heater
ventilating decisions in response to
indoor air section shall be insulated shall use a direct spark ignition (DSI)
electronic signals from sensors
with a cleanable foil-faced, fire- system. On initial call for heat, the
measuring indoor and outdoor
retardant permanent, odorless glass combustion blower shall purge the
temperatures. The control algorithm
fiber material. The base of the unit heat exchanger for 20 seconds
maintains accurate temperature
shall be insulated with 1/8 inch, 1 before ignition After three
control, minimizes drift from set
pound density foil-faced, closed-cell unsuccessful ignition attempts, the
point, and provides better building
material. All insulation edges shall entire heating system shall be locked
comfort. A centralized
be either captured or sealed. The out until manually reset at the
microprocessor shall provide anti-
unit’s base pan shall have no thermostat/zone sensor. Units shall
short cycle timing and time delay
penetrations within the perimeter of be suitable for use with natural gas
between compressors to provide a
the curb other than the raised 11/8 or propane (field-installed kit) and
higher level of machine protection.
inch high downflow supply/return also comply with the California
openings to provide an added water 24-volt electromechanical control requirement for low NOx emissions
integrity precaution, if the circuit shall include control (Gas/Electric Only).
condensate drain backs up. The base transformer and contactor pressure
of the unit shall have provisions for lugs for power wiring. Units shall

RT-PRC023-EN 119
Mechanical Specifications

High Pressure Control CompleteCoat™ Coils Powered or Unpowered


All units include High Pressure The cathodic epoxy type Convenience Outlet
Cutout as standard. electrodisposition coating is This is a GFCI, 120v/15amp, 2 plug,
formulated for high edge build to convenience outlet, either powered
Indoor Fan plate fin and tube heat exchangers. or unpowered. When the
The coating is selected to provide convenience outlet is powered, a
3-5 ton units (standard efficiency 3- excellent resistance and durability to service receptacle disconnect will be
phase or high efficiency 3-phase with corrosive effects of alkalies, acids, available. The convenience outlet is
optional motor) are belt driven, FC alcohols, petroleum, seawater, salt powered from the line side of the
centrifugal fans with adjustable air and corrosive environments. disconnect or circuit breaker, and
motor sheaves. 3-5 ton units (1-phase
The option shall be equipped with therefore will not be affected by the
or high efficiency 3-phase) have
crankcase heater(s), low pressure position of the disconnect or circuit
multispeed, direct drive motors. All
switch(es), Frostat™, and a breaker. This option can only be
6-10 ton units shall have belt drive
thermostatic expansion valve(s) ordered when the Through the Base
motors with an adjustable idler-arm
(TXV) as standard. Electrical with either the Disconnect
assembly for quick-adjustment to fan
Switch or Circuit Breaker option is
belts and motor sheaves. All motors
ordered.
shall be thermally protected. All Heat Exchanger
indoor fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT).
The compact cabinet features a Stainless Steel Heat Exchanger
tubular heat exchanger in low,
medium and high heat capacities. The optional stainless steel heat
Outdoor Fans exchanger is constructed of 304
The heat exchanger is fabricated stainless steel. It is resistant to
The outdoor fan shall be direct-drive, using stainless steel burners and corrosion and oxidation and easy to
statically and dynamically balanced, corrosion-resistant aluminized steel clean.
draw-through in the vertical tubes as standard on all models. It
discharge position. The fan motor has an induced draft blower to pull The high strength to weight ratio
shall be permanently lubricated and the gas mixture through the burner allows for high ventilation rates with
shall have built-in thermal overload tubes. The heater has a direct spark gas units. It is an excellent option to
protection. ignition system which doubles as a compliment the dehumidification
safety device to prove the flame. option as a high outside air
Refrigerant Circuits ventilation unit.
Gas/Electric Precedent models
Each refrigerant circuit offer thermal exceed all California seasonal With this option, a 10-year stainless
expansion valve as standard. Service efficiency requirements. They also steel heat exchanger warranty is
pressure ports, and refrigerant line perform better than required to meet standard.
filter driers are factory-installed as the California NOx emission
standard. An area shall be provided requirements. Supply and/or Return Air Smoke
for replacement suction line driers. Detector
Hinged Access Doors With this option, if smoke is detected,
Unit Top
Sheet metal hinges are available on all unit operation will be shut down.
The top cover shall be one piece the Filter/Evaporator, Supply Fan/ Reset will be manual at the unit.
construction or where seams exist, it Heat, and the Compressor/Control Return Air Smoke Detectors require
shall be double-hemmed and gasket- Access Doors. minimum allowable airflow when
sealed. The ribbed top adds extra used with certain models. See the
strength and prevents water from Novar Return Air Sensor Installation, Operation, and
pooling on unit top. Maintenance (IOM) manual for the
This option, when used in models affected and the minimum
conjunction with Novar Controls, will allowable airflow required.
Factory Installed Options contain a factory provided and wired
zone temperature sensor located in Thermal Expansion Valve
Black Epoxy Pre-Coated Coils the return air stream.
Thermal Expansion Valve is standard
The black epoxy coils have a for all models.
thermoset vinyl coating that is Novar Unit Controls
bonded to the aluminum fin stock Optional Novar rooftop unit controls Through the Base Electrical
prior to the fin-stamping process. shall be installed and tested. The
The pre-coated coils are an Access
Novar electronic thermostat module
economical option for protection in will interface to the unit An electrical service entrance shall be
mildly corrosive environments. microprocessor and will control the provided allowing electrical access
unit to the desired stage of cooling or for both control and main power
heating. connections inside the curb and
through the base of the unit. Option
will allow for field installation of

120 RT-PRC023-EN
Mechanical Specifications

liquid-tight conduit and an external will be registered with either a zone meet all NEC and CEC requirements
field-installed disconnect switch. sensor with status indication lights or when properly installed. Power
an Integrated Comfort™ System. assemblies shall provide single-point
Through the Base Electrical with This option is available for connection. Electric heat modules
Circuit Breaker microprocessor controlled units. shall be UL listed or CSA certified.
This option is a thermal magnetic, Differential Pressure Switches Frostat
molded case, HACR Circuit Breaker
with provisions for through the base These sensors allow individual fan This option is to be utilized as a
electrical connections. The circuit failure and dirty filter indication for safety device. The Frostat opens
breaker will be installed in a water microprocessor controlled units. The when temperatures on the
tight enclosure in the unit with fan failure switch will disable all unit evaporator coil fall below 10°F. The
access through a swinging door. functions and “flash” the Service temperature will need to rise to 50°F
Wiring will be provided from the LED on the zone sensor. The dirty before closing. This option should be
switch to the unit high voltage filter switch will light the Service LED utilized in low airflow or high outside
terminal block. The circuit breaker on the zone sensor and will allow air applications (Cooling Only).
will provide overcurrent protection, continued unit operation.
be sized per NEC and UL guidelines, LonTalk® Communication
and be agency recognized by UL/ Discharge Air Sensing Interface
CSA.
This option provides true discharge This option shall be provided to allow
air sensing in heating models. This the unit to communicate as a
Through the Base Electrical with sensor is a status indicator readable Tracer™LCI-R device or directly with
Disconnect Switch through Tracer™ or Tracker™. This generic LonTalk Network Building
This 3-pole, molded case, disconnect option is available for Automation System Controls.
switch with provisions for through microprocessor controlled units.
the base electrical connections are Reference or Comparative
available. The disconnect switch will Economizer Enthalpy
be installed in the unit in a water tight This accessory shall be available with
enclosure with access through a Reference Enthalpy is used to
or without barometric relief. The measure and communicate outdoor
swinging door. Wiring will be assembly includes fully modulating
provided from the switch to the unit humidity. The unit receives and uses
0-100 percent motor and dampers, this information to provide improved
high voltage terminal block. The minimum position setting, preset
switch will be UL/CSA agency comfort cooling while using the
linkage, wiring harness with plug, economizer. Comparative Enthalpy
recognized. Note: The disconnect spring return actuator and fixed dry
switch will be sized per NEC and UL measures and communicates
bulb control. The barometric relief humidity for both outdoor and return
guidelines but will not be used in shall provide a pressure operated
place of unit overcurrent protection. air conditions, and return air
damper that shall be gravity closing temperature. The unit receives and
and shall prohibit entrance of outside uses this information to maximize
Through the Base Gas Piping air during the equipment “off” cycle. use of economizer cooling, and to
The unit shall include a standard Optional solid state or differential provide maximum occupant comfort
through the base gas provision. This enthalpy control shall be available for control. Reference or Comparative
option shall have all piping necessary either factory or field installation. The Enthalpy option shall be available
including, black steel, manual gas economizer arrives in the shipping when a factory or field installed
shut-off valve, elbows, and union. position and shall be moved to the Downflow Economizer is ordered.
The manual shut-off valve shall operating position by the installing This option is available on all
include a 1/8” NPT pressure tap. This contractor. downflow models.
assembly will require minor field
labor to install (Gas/Electric Only). Electric Heaters Tool-less Hail Guards
Electric heat modules shall be Tool-less, hail protection quality coil
Two-Inch Pleated Filters available for installation within basic guards are available for condenser
Two inch pleated media filters shall unit. Electric heater elements shall be coil protection.
be available on all models. constructed of heavy-duty nickel
chromium elements internally delta Trane Communication Interface
connected for 240 volt, wye
Factory or Field Installed connected for 480 and 600 volt. This option shall be provided to
Options Staging shall be achieved through interface ReliaTel™ controlled units
ReliaTel™. Each heater package shall with the Trane Integrated Comfort™
have automatically reset high limit systems.
Clogged Filter/Fan Failure Switch
control operating through heating
A dedicated differential pressure element contactors. All heaters shall
switch is available to achieve active be individually fused from the
fan failure indication and/or clogged factory, where required, and shall
filter indication. These indications

RT-PRC023-EN 121
Mechanical Specifications

Field Installed Options Manual Outside Air Damper Zone Sensor


This rain hood and screen shall This control shall be provided to
CO2 Sensing provide up to 50 percent outside air. interface with the Micro equipped
The CO2 sensor shall have the ability units and shall be available in either
to monitor space occupancy levels Motorized Outside Air Damper manual, automatic programmable
within the building by measuring the with night setback, with system
Manually set outdoor air dampers malfunction lights, or remote sensor
parts per million of CO2 (Carbon shall provide up to 50 percent outside
Dioxide) in the air. As the CO2 levels options.
air. Once set, outdoor air dampers
increase, the outside air damper shall open to set position when
modulates to meet the CO2 space indoor fan starts. The damper shall
ventilation requirements. close to the full closed position when
indoor fan shuts down.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Remote Potentiometer
Display) zone sensor has the look and The minimum position setting of the
functionality of standard zone economizer shall be adjusted with
sensors. This sensor includes a this accessory.
digital display of set point
adjustment and space temperature in Roof Curb
F (Fahrenheit) or C (Celsius). Includes
FAN and SYSTEM buttons (supports The roof curb shall be designed to
the service functions of the standard mate with the unit’s downflow supply
sensor). E-squared memory stores and return and provide support and a
last programmed set points. Requires water tight installation when installed
24 VAC (Volts AC). This sensor should properly. The roof curb design shall
be utilized with ReliaTel™ controls. allow field-fabricated rectangular
supply/return ductwork to be
Dual Thermistor Remote Zone connected directly to the curb. Curb
Sensor design shall comply with NRCA
requirements. Curb shall be shipped
This sensor will allow the customer knocked down for field assembly and
to reduce the total number of remote shall include wood nailer strips.
sensors to obtain space temperature
averaging. This sensor should be Thermostat
utilized with ReliaTel controls.
Two stage heating and cooling
High Static Drive operation or one stage heating and
cooling shall be available in either
The high static drive option shall manual or automatic changeover.
allow the standard motor to operate Automatic programmable electronic
with improved external static with night set back shall also be
capabilities. available.

Humidity Sensor Ventilation Override Accessory


This wall-mounted humidity sensor With the Ventilation Override
is used to control activation of the Accessory installed, the unit can be
hot gas reheat dehumidification set to transition up to 3 different pre-
option. The humidity sensor can be programmed sequences for Smoke
set for humidity levels between 40% Purge, Pressurization, and Exhaust.
and 60% relative humidity by The transition occurs when a binary
adjusting the ReliaTel Options input on the RTOM is closed
Module. (shorted). This would typically be a
hard wired relay output from a
Humidity Sensor smoke detector or fire control panel.
The ventilation override accessory
This duct-mounted humidity sensor
shall be available as field installed.
is used to control activation of the
hot gas reheat dehumidification
option. The humidity sensor can be
set for humidity levels between 40%
and 60% relative humidity by
adjusting the ReliaTel Options
Module.

122 RT-PRC023-EN
Literature Order Number RT-PRC023-EN
Trane Date 05/01/07
A business of American Standard Companies
Supersedes RT-PRC023-EN (11/01/06)