Draft Spect No. TI-SPC-PSI-LVCBIN-0121
Draft Spect No. TI-SPC-PSI-LVCBIN-0121
Draft Spect No. TI-SPC-PSI-LVCBIN-0121
Effective from
77860/2020/O/o PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 1 of 51
GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
SPECFICATION FOR
ISSUED BY
Date
Designation
87
Effective from
77860/2020/O/o PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 2 of 51
Table of Contents
1. SCOPE
1.1. This Specification applies to following, for use in Railway Traction Sub-
Stations / SPs / SSPs, for controlling Power Supply to the 25kV AC 50 Hz
single phase Traction Overhead Equipment and 2x25 kV AC 50 Hz AT
Feeding System for Traction Overhead Equipment (OHE):
1.1.1. Outdoor Type Single Pole, Vacuum Circuit Breaker (CB) and Vacuum
Interrupter (BM).
1.1.2. Outdoor Type Double Pole, Vacuum Circuit Breaker (CB) and Vacuum
Interrupter (BM).
1.1.3. Outdoor Type Single Pole, Pole Mounted Vacuum Circuit Breaker (CB)
and Vacuum Interrupter (BM).
1.1.4. Outdoor Type Single Pole, Vacuum Circuit Breaker (CB) for automatic
phase switching section (APSS) system.
1.2. All the provisions contained in RGSO’s ISO procedures laid down in
Document No. - QO - D-8.1-11 Ver. 1.2 dated 22.06.2020 (titled “Vendor-
changes in approved status") and subsequent versions/amendments
thereof, shall be binding and applicable on the successful vendor/vendors in
the contracts floated by Railways to maintain quality of products
supplied to Railways.
1.4. The Vacuum Circuit Breaker/Interrupter shall be complete with all Parts,
Fittings, Vacuum Bottle and accessories necessary for its efficient operation
including mounting, frame work of steel. All such Parts, Fittings and
Accessories shall be deemed to be within the scope of this Specification,
whether specifically mentioned or not. The Vacuum Circuit Breaker/
Interrupter shall be of proven design. If there is any additional change in
design, it shall be advised by RDSO as and when the need arises.
2.2. Any deviation from this Specification as proposed by the Tenderer Vendor
to improve upon the performance, utility and efficiency of the Equipment
shall be given due consideration, provided full particulars of the deviation
along with justification are furnished thereof; subject to approval of RDSO.
In case of any contradiction between the provision of the Indian
Standards/IEC standards and this Specification, the this Specification
latter shall prevail.
3.1.1. The Vacuum Circuit Breaker is used at the following locations in the 25
kV AC, 50Hz Traction System.
(i) As 25 kV Transformer VCB on the secondary side of Traction Power
Transformer.
(ii) As 25 kV Feeder VCB for controlling Power Supply to Overhead
Equipment through Interrupters.
(iii) As 25 kV Shunt Capacitor Bank VCB for controlling Power Supply to
Shunt Capacitor Bank.
(iv) For controlling 25 kV Power Supply to major yard or Electric Loco
Sheds.
(i) The 25 kV VCB shall be called upon to trip under Short- Circuit
conditions. On an average, the number of fault tripping seen by the
Feeder Vacuum Circuit Breaker per month is about 40, but in
exceptional cases the number of fault trappings trippings per month
may go as high as 120 numbers. The magnitude of short circuit
current to be interrupted is generally in the range of 2 kA to 8 kA.
The, VCB shall also be called upon to clear Wrong Phase Coupling on
the OHE when two Sections of the OHE fed by different Phases from
adjacent Traction Sub-Stations are accidentally shorted.
(ii) The design and construction of the 25 kV VCB shall be such that, it is
capable of a cumulative duty nl² (where ‘n’ is the number of ‘C - O’
Operations at a current of l kA rms) of 20,000 kA2 in service without
adjustment/ change of any part/ contacts of Vacuum Bottle.
92
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 7 of 51
4. TECHNICAL SPECIFICATION
4.1. The VCB shall be designed for the following ratings and other particulars
(both for Normal and Automatic Phase switching Section (APSS)
application):
4.2. CLEARANCES
SN Clearance/distance 25kV
Minimum height of lowest live part of the
(i) VCB/BM from ground level 3800 mm
No. of operations
SN Equipment Name
Mechanism Vacuum Bottle
25kV SP / DP /Pole Mounted
1. Vacuum Circuit Breaker/ 10,000 20,000
Interrupter with spring spring
operating mechanism.
25kV SP / DP /Pole Mounted
2. Vacuum Circuit Breaker/ Interruptor 20,000 20,000
with magnetic Actuated Operating
Mechanism.
shields will also control the electric field when contacts are open and
voltage is appearing across the Vacuum Circuit Breaker/Interrupter
contacts. This will mask high internal stress points and produce an almost
linear axial grading of the external insulating surfaces. A shield shall also
be provided to protect the bellows. The design and construction of
Vacuum Bottle of the Vacuum Circuit Breaker/Interrupter shall be such
that the current chopping level is kept to the minimum and shall not
produce any appreciable switching over voltages.
(ii) The motor for spring charging shall be suitable for operation on 110V
DC power from a Battery. The voltage at motor terminal is likely to
vary between 110% and 85% of the normal value. The Carbon
brushes, shall have copper pigtails for carrying motor current. A
miniature Circuit Breaker / HRC Fuses, of adequate ratings and of
reputed make, shall be provided in the motor circuit for protection of
the motor against over current and earth faults.
(c) The operating mechanism shall be designed so that the Vacuum Circuit
Breaker/Interrupter can be operated from the operating mechanism
cubicle itself as well as remotely from the Control Panel of the Traction
Sub-station and also from the Remote Control Centre (RCC), which is
situated away from the Vacuum Circuit Breaker/Interrupter.
For this purpose ‘LOCAL/REMOTE’ two way Selector switch shall be
provided in the operating mechanism cubicle. When the switch is in the
‘LOCAL’ position, the Vacuum Circuit Breaker/Interrupter can be operated
locally and when it is in the ‘REMOTE’ position the Vacuum Circuit
Breaker/Interrupter can be operated from the Control Panel or from the
Remote Control Centre. The Selector switch shall be shall be spring loaded
for snap action and stay put type so that it stays to the ‘LOCAL’ or
'REMOTE’ position.
For closing and opening the Vacuum Circuit Breaker/Interrupter
from the Operating Mechanism cubicle itself, the Switch shall be of the
Push Button type or Knob type.
(e) The operating mechanism shall also be provided with a suitable device to
close the Vacuum Circuit Breaker/Interrupter in spring-spring operating
mechanism manually. In addition, a detachable handle/ crank shall be
provided for manual charging the closing spring in spring spring operating
mechanism. The height from ground/ platform level at which the handle/
crank is to be inserted in the operating mechanism shall be between 1500
mm and 2000 mm so as to enable its operation conveniently by the
operator standing on the Ground/Platform. The height of other devices
like interlock, ON-OF switches, selector switches etc. to be operated from
ground/ Platform. Platform shall also be at a height between 1500 mm
and 2000 mm.
(f) In addition to the manually operated local mechanical opening and Closing
devices as indicated in clause d & e above, provision shall also be made
by means of a suitable crank or handle for slow closing and slow opening
of the Vacuum Circuit Breaker/Interrupter in spring- spring operating
mechanism for Maintenance purposes.
(g) The closing coil and opening coil in the operating mechanism shall be
suitable for operation from 110V dc power supply from a battery. The
closing coil shall be suitable for operating at a Voltage variation of +10%
to -15%, while the opening coil shall be suitable for operating at a voltage
variation of +10% to -30%.
(h) The VCB shall be fitted with an electrical anti-pumping device, to give
priority to tripping command in case of a persisting closing Command
being simultaneously present.
(i) Facility for trip circuit supervision shall be provided in Control Panel of TSS
with indication to Remote location (RCC) in Vacuum Circuit Breaker.
99
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 14 of 51
(j) An operation counter having minimum five digit recording mechanism for
the number of tripping operation shall be provided at a suitable place so
as to be conveniently read by the operator standing on the Ground. The
operation counter shall be of lock type and shall not have reset.
(k) Mechanical indicators clearly visible from ground shall be provided for
‘CLOSED’ and ‘OPEN’ conditions of the Vacuum Circuit Breaker/
Interrupter.
(n) In the event of 110V battery supply voltage dropping below 85V ± 3 Volts
which is the minimum voltage prescribed for operation of Tripping coil to
trip the Vacuum Circuit Breaker, the Vacuum Circuit Breaker should Trip
automatically by means of a suitable arrangement like Capacitive Trip
Device(CTD).
(o) Shock absorbers used (if any) shall not require any maintenance during
the entire life of the Vacuum Circuit Breaker / Interrupter.
(r) The entry of all cables into the operating mechanism cubicle shall be only
through suitable cable glands which shall not allow ingress of vermin etc.
into the cubicle. The cable glands shall be supplied with the Vacuum
Circuit Breaker/Interrupter. Five cable glands shall be provided of which
three shall be of 16.5 mm outside diameter while the Balance two glands
shall be for cable of 14 mm outside diameter.
100
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 15 of 51
(s) The wiring inside the operating mechanism cubicle shall be with 1100 V
grade PVC insulated single core / multistrand cable conforming to IS:
1554 (Pt. I- 1988) or latest or IS 694 (2010) or latest, with stranded
copper conductors of adequate cross-section (with min 2.5 sq.mm strand
copper) so proportioned as to reduce voltage drop and I²R losses to
minimum. Wiring for electronic controller & proximity switches shall be of
660V grade insulation with stranded copper conductor with at least 0.5
sq. mm cross section. The ends of wires shall be terminated with crimped
eye type lugs or without crimping in self-locking spring loaded terminal
blocks. The wiring of 110V dc control circuit and 240V ac circuit shall be
segregated and properly identified. The positive and negative wires of dc
circuits shall also be segregated. The length of the cables used shall be
kept to the minimum. Wire inside the cubicle shall be properly laid on
trays or anchored to avoid breakage during vibration.
(t) The terminal end of all wires shall be provided with numbered interlock
type Ferrules which shall be of PVC or other durable material with
marking (numbers) either engraved or punched so as to be indelible. The
ferrules shall be of white/yellow color with lettering thereon black. All
wiring shall be properly supported and suitably protected to avoid
rubbing against any Metallic part.
(v) For earthling of the operating mechanism cubicle, two earthing terminals
of adequate capacity to carry the rated short circuit current shall be
provided with 17.5 +0.5/-00 mm diameter stud/hole for fixing the
Earthling Flat.
6.1. The steel supporting frame for Vacuum Circuit Breaker/Interrupter shall be
designed with a factor of safety not less than 2.5 with respect to the yield
point under conditions of maximum loading for a basic wind pressure of 200
kg/m² on 1.5 times the projected area of each member of one face and
taking into account to IS: 808 (1989) and test certificate shall be furnished
to RDSO. The required fixing distance for steel supporting frame on the
foundation is tabulated below:
6.2. Typical design calculations for the steel supporting frame shall be furnished
by the manufacturer to the RDSO during design approval stage for checking
the safety of the supporting frame proposed to be used.
6.3. For earthing at least 2 legs of the steel supporting frame shall be provided
with stud/hole type earthing terminals of adequate capacity to carry the
rated short circuit current safely. The earthing shall be provided with 50 x
8 mm MS flat. The terminal shall be provided with 17.5 +0.5mm diameter
stud/hole for fixing the earthling flat.
7. FOUNDATIONS
Gravity foundation of plain mass concrete to M10 mix as per IS: 456 (2000) or
latest shall be designed considering the normal impact loading in
opening/closing operations. The basic wind pressure shall be taken as 200
kgf/m². Two alternative design of foundations, one for a normal soil of bearing
capacity 5500 kgf/m² and other for black-cotton soil of bearing capacity 16500
kgf/m² shall be furnished by the manufacturer. The foundation block design
shall give complete details of its size and size of pockets provided for grouting
the fixing bolts. Detailed design calculation for proposed foundation shall be
submitted to DG (TI) RDSO for scrutiny and approval.
9.1. The pole (mast) for mounting the Interrupter shall be either steel Mast or a
round tapered prestressed spun concrete mast. The detail of pole (mast)
for mounting the Interrupter shall be supplied by the purchaser. Mounting
Brackets of the Pole Mounted Vacuum Circuit Breaker/Interrupter shall form
the part of in the scope of supply of Vacuum Circuit Breaker/Interrupter.
Bracket shall be suitable for mounting on the Mast.
10.1. GALVANIZING
The operating mechanism cubicle and steel supporting frame shall be hot
dip galvanized in accordance with RDSO Specification No.
ETI/OHE/13(4/84) with A&C Slip No.1 to 3 4 or latest and the weight of
zinc coating shall not be less that 1000 gm/m².
10.2. PAINTING
10.3. FASTENERS
11.1. The following parts, fittings and accessories shall be provided for each
Circuit Breaker/Interrupter:
(i) Contacts wear indication as per Clause No. 5.3 (d) 5.2 (e) (i).
(ii) Operating mechanism cubicle door padlocking arrangement with
padlock.
(iii) Local operated mechanical opening and closing device for spring-
spring operating mechanism.
(iv) Local/Remote Selector Switch as per Clause No. 5.3(c).
(v) Local operated electrical closing and opening device
(push or knob).
(vi) Operation counter.
(vii) Interlocking device (as required)
(viii) Terminal connectors.
(ix) Earthing terminals
(x) Name/ rating plate.
(xi) Mechanical ‘ON’ and ‘OFF’ position indicators.
(xii) Handle/crank for closing and opening of Vacuum
Circuit Breaker/Interrupter for spring-spring operating mechanism.
(xiii) Supporting frame work.
103
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 18 of 51
11.2. Each Vacuum Circuit Breaker/ Interrupter shall be provided with rating
plates (Hindi /English) of weather proof material fitted in a visible position
showing the items Indicated below. The letters/numbers on the plate shall
be indelibly marked by etching/engraving.
12. TESTING
12.1. GENERAL
The successful Tenderer Vendor has to offer drawing & design for
approval of RDSO including QAP, SOGP, and Design Calculations as
required and mentioned in relevant Clauses of Specification.
Only after all submitted documents have been approved and
clearance given to this effect by RDSO, the manufacturer shall take up
manufacture of the prototype for inspection/testing by RDSO. It is to
be clearly understood that any changes to be done on the prototype as
required by RDSO, the same shall be done expeditiously.
12.1.3. In the event of the test not being carried through to completion at one
stretch for any reason attributable to the successful Tenderer
/manufacturer and it is required for the representative of the
Purchaser /DG/TI/ RDSO to go again or more numbers of times to the
works of the successful Tenderer /manufacturer or to any reputed
testing house/laboratory where tests are being done for continuing
and/ or completing the tests on the prototype(s) of the equipment, the
successful Tenderer /manufacturer shall reimburse to the Purchaser
/DG/TI/ RDSO the cost for the representative(s) having to visit the
works or other place(s) for the tests more than once. The cost as
claimed by the Purchaser /DG/TI/ RDSO ,Lucknow shall be paid
thorough a Demand Draft to the concerned Accounts Officer of the
Purchaser/ Purchaser /DG/TI/ RDSO, Lucknow as shall be advised to
105
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 20 of 51
12.1.4. The tests shall be conducted on the prototype of the Vacuum Circuit
Breaker/ Interrupter at the works of the successful Tenderer Vendor/
manufacturer or at any reputed testing laboratory in the presence of
Purchaser /DG/TI/ RDSO, Lucknow or his authorized representative.
The prototype shall be complete in all respects, including the terminal
connectors as would be supplied if it had passed the tests. The tests
shall be conducted as per relevant governing Specification and as
modified or amplified herein. In case of test being conducted at
government test laboratory, the presence of Purchaser’s
representative for witnessing the test may be waived off subject to the
discretion of the Purchaser /DG/TI/ RDSO, Lucknow.
12.1.5. For the tests which are conducted in the laboratories of Central Power
Research Institute, Bhopal/Bangalore, Electrical Research Development
Association, Vadodara or any such testing house or laboratory a clear
certificate to the effect that the equipment has passed the tests as per
the Specification shall be obtained by the manufacturer and submitted
to the Purchaser/DG (TI)/RDSO, Lucknow. Full details of the tests and
the test parameters shall be furnished along with the test reports.
12.2.2.1. The test shall be conducted in accordance with clause 6.101 of IEC
62271-100 or latest but the number of operations shall be 10,000
in case of 25kV Vacuum Circuit Breaker/ Interrupter instead of
2000 specified therein for 25 kV VCB/BM with spring – Spring
Mechanism and 20,000 for Vacuum Circuit Breaker/ Interrupter
with Magnetic Actuator Mechanism. For this purpose, Vacuum
Circuit Breaker/ Interrupter shall be tested in accordance with
Table XII of IEC 62271- 100 or latest However, the sequence shall
be repeated 5 times to complete 10,000 operations in case of
25kV Vacuum Circuit Breaker/ Interrupter with spring – spring
mechanism and 10 times to complete 20,000 operations for
Vacuum Circuit Breaker/ Interrupter with Magnetic Actuator
Mechanism.
12.2.2.2. The measurement of items (v) & (vii) above shall be repeated
after every 5000 operations for 25kV Vacuum Circuit Breaker/
Interrupter and observations made/ results obtained shall be
evaluated by comparing with the figures and the tolerances given
by the successful Tenderer Vendor/manufacturer in the SOGP.
(a) The temperature rise test on the main circuit (contacts) and
terminal connectors of shall be carried out IEC 62271-1(2007)
or latest. Contact resistance of the main circuit shall be
determined by dc voltage drop and recorded before and after
this test.
110
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 25 of 51
(b) Procedure
Unless otherwise specified, temperature rise on the main circuit
shall be made on a new Vacuum Circuit Breaker/ Interrupter in
closed position with clean contacts. The test shall be made with
rated normal current. The test shall be done in indoor
environment substantially free from air currents, except those
generated by heat from the Vacuum Circuit Breaker being
tested. Temporary connections to the Vacuum Circuit Breaker
terminals shall be such that no significant amount of heat is
conducted away from, or conveyed to the Vacuum Circuit
Breaker/ Interrupter during the test. The temperature rise at
the terminal of main circuit and the temporary connections at a
distance of 1m from the terminal shall be measured. The
difference of temperature rise shall not exceed 5˚C. The type
and sizes of temporary connections shall be recorded in the test
report.
(a) The temperature rise test on the coils shall be carried out as
per IEC 62271-1(2007) or latest.
(b) Procedure
The temperature rise on auxiliary equipment (Closing and
Opening coils) shall be made by the method of measuring
Variation of resistance before and after energisation at 110V
dc. For this purpose the coil(s) shall be energized 10 times for
1 second, the interval between the instant of each energizing
being 2 second. The resistance of the coil shall be measured
immediately before and after such energisation. The value of
Temperature rise, over the ambient shall be computed.
(c) The maximum temperature rise shall be as per IEC:
62271-1(2007) or latest considering the insulating
material of the Coil. The temperature rise shall not
exceed the value as Guaranteed by the manufacturer in
SOGP.
12.2.4. Dielectric tests Vacuum Circuit Breaker/ Interrupter
12.2.6.1. Making and breaking test at 100% mainly active load (Test duty
No.1.0)
Five hundred make-break operations shall be conducted at
800A/1600A/2000A (rms) at a test voltage of not less than 27.5
kV. The supply circuit shall have a power factor not exceeding 0.2
and the load circuit shall have a power factor between 0.65 and
0.75. Prospective TRV Parameters shall be set in accordance with
Table III of IEC-62271-104- 1(2009).The test may be interrupted
after every 10 operations, if necessary, to enable the components
to cool down to the ambient temperature.
12.2.6.2. Closed loop make –break operations (Test Duty No.2a & 2b)
If TRV parameters achieved in test duty 1 are equal or more
severe than the TRV parameters prescribed in Table IV-A of IEC
62271-104-1(2009)for test duty 2a and 2b then test duty 2a and
2b need not be performed, otherwise tests comprising test duties
2a and 2b described as under shall be performed:
(i) Transmission circuit closed loop make-break operation test
(Test Duty No.2a)-10 make-break operations shall be
performed at 800A/1600A/2000A.
(ii) Parallel transformer circuit make-break operation (Test Duty
No.2b)-10 make break operation shall be performed at
800/1600/ 2000 A.
12.2.10. Line charging current switching test for Vacuum Circuit Breaker.
This test shall be conducted as per clause 6.111.5.1 of IEC 62271-100
or latest. Test values shall conform as given in SOGP.
113
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 28 of 51
12.2.11. Test to prove rated transient recovery voltage (TRV) for Vacuum
Circuit Breaker The measurement shall be done as per IEC: 62271-100
or latest.
12.2.12. Out of phase making and breaking test for Vacuum Circuit Breaker
This test shall be conducted as per IEC 62271-100or latest at its rated
out of phase breaking current.
12.2.13. Capacitor bank breaking current test for Vacuum Circuit Breaker
The test shall be carried out at rated single Capacitor Bank Breaking
Current generally as per IEC 62271-100 or latest. No restrike shall
occur during the test. The breaking current shall conform to the
guaranteed value.
12.2.15. Condition of Vacuum Circuit Breaker during the tests conducted as per
clause no. 12.2.5, 12.2.9, 12.2.10, 12.2.11, 12.2.12, 12.2.13, and
12.2.14 of this Specification shall conform as under:
12.2.15.1. During these tests the Vacuum Circuit Breaker shall neither show
signs of excessive distress nor endanger the operator. No
disruptive discharge between energized parts and earth shall
occur during the test. There shall be no indication of significant
leakage current to the earth structure or screens whenever fitted
during the test. The earthed part shall be connected to earth
through a fuse consisting of copper wire of 0.11mm diameter and
5cm length. The fuse wire shall be intact after the test.
12.2.16. Condition of Vacuum Circuit Breaker during the tests conducted as per
clause No.12.2.5, 12.2.9, 12.2.10, 12.2.11, 12.2.12, 12.2.13, and
12.2.14 of this Specification shall conform as under:
12.2.16.1. The mechanical functions and insulation of Vacuum Circuit
Breaker shall be essentially in the same condition as before the
test. The wear of the contacts shall not be disproportionate to its
original shape and size. The Vacuum Circuit Breaker shall be
capable of carrying its rated normal current and also capable of
performing its assigned duty provided in clause 3.7 3.1 of the
Specification The Vacuum Circuit Breaker shall withstand for 1
minute dry power frequency withstand voltage 95KV rms.
12.3. The Tenderer may quote separately the charges for short circuit test Duties,
short time withstand current and peak current withstand test, line charging
breaking current tests, test to prove rated TRV, short line fault tests, out of
phase making and breaking tests, capacitor bank breaking current test,
measurement of RIV level and special electrical tests as per clause 12.2.5,
12.2.6, 12.2.7, 12.2.8, 12.2.9, 12.2.10, 12.2.11, 12.2.12. No test charge
shall be payable for any other test.
12.8. The requirement of Type Testing on Double Pole VCB/VI if Single pole
VCB/VI is already Type Tested as per Clause no. 12.2.
If a Single Pole VCB/VI is already Type Tested as per clause 12.2 and
Vendor offer the Double VCB/VI identical to single pole unit operated
through two operating mechanism suitably connected for instep
operation, then only following test shall be carried out on Double pole
VCB/VI.
SN Description of Test Refer in
i. Mechanical operation test with Vacuum Bottle Clause
12.2.2
116
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 31 of 51
12.9.1. Rated one –minute Power Frequency Dry withstand Voltage Test
The VCB/BM Power frequencies dry withstand voltage. Test on
complete Circuit Breaker/Interrupter by applying 95kV for 1
117
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 32 of 51
minute.
13. The Tenderer Vendor shall specifically indicate in a statement attached with his
offer, his compliance with each clause and sub clause of the Specification. A
separate statement shall be attached either the offer indicating references to
the clauses where the Tenderer Vendor deviate there from together with the
detailed remarks/justification. If either the statements of the compliance or a
119
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 34 of 51
(vi) Type test report for relevant rating as per RDSO /IEC Specification.
(vii) List of supplies and performance reports for the tendered equipment
from user railway/ other customer.
(v) Details of main, fixed and moving contacts and arcing contacts.
120
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 35 of 51
(viii) Full details of all sealing points with details of O rings and gaskets.
(xii) Design calculation for structural safety along with the details of
Supporting Structure.
15.4. Cross reference of identical drawing, if approved for earlier contract shall be
given in the drawing information required during commissioning and
maintenance of equipment shall be shown in greater detail.
15.5. After approval, six copies of approved drawings along with 2 set of
reproducible prints shall be supplied to each consignee. Drawings shall be
made in Auto CAD, for approval to RDSO. Two One sets of approved
drawings of hard copy one copy of RTF and one set in pen drive in Auto CAD
R14 / latest shall be sent to RDSO for record.
15.6. Space earmarked for assigning RDSO’s drawing number shall be available on
the right hand top side of each drawing. Numbering shall be allotted by
RDSO after approval of drawing.
more than 10 nos. In case order is less than 10 nos two copies of manual
shall be supplied. Two copies of manuals shall be supplied to the
Purchaser/DG (TI), RDSO, Lucknow (India) for record.
15.8. Drawings approved by RDSO after prototype approval shall be submitted for
the future contracts also till the validity of prototype approval with a clear
certification on the drawing that design, process and material have not been
changed in the design of the subject equipment from the prototype already
approved by RDSO.
17. Spares
The Tenderer Vendor shall furnish along with his offer, a list of spares (with
cost) Recommended by him for maintenance of Circuit Breaker/Interrupter for
a period of 10 years. The list should include gaskets/ O rings, parts which are
likely to wear and items requiring replacement/ replenishment, besides other
items recommended by the manufacturer. The successful Tenderer Vendor
shall give an undertaking to the effect that he shall supply the required spares
for the total life of the equipment (i.e. 25 years approx.).
20.2. As far as possible, the gross weight of a crate/ box shall be so kept that it
shall be possible to manually handle it by two persons.
20.3. In case of overseas supplies, packing shall be sea worthy.
20.4. Necessary instructions for handling and storage shall also be furnished for
use at receiving end.
20.5. Porcelain housing/ support insulator shall be supplied securely packed in
wooden crates. Not more than two porcelain housing/ support insulators
shall be packed in a crate in order to facilitate manual loading and
unloading.
123
Effective
77860/2020/O/o from
PED/TI/RDSO Draft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 38 of 51
Annexure ‘A’
C OPERATING PARTICULARS
34. Closing time from the instant of closing coil Ms
energisation (max)
35. Opening time from the instant of trip coil Ms
energisation(max)
36. Make Time (max) Ms
37. Arcing Time
(i) At rated normal current Ms
Annexure- ‘B’
6. Auxiliary contact
(i) Description and type Designation
(ii) Make
(iii) Identification mark
(iv) Item drawing No.
(v) Governing Specification No.
(vi) Rating
(a) Voltage
(b) Continuous Current
(c) Breaking and making Current
(d) Electrical & Mechanical life (No. of
operations)
7. Motor limit switch
(i) Description and type
(ii) Type designation
(iii) Make
(iv) Identification mark
(v) Governing Specification No.
(vi) Rating
(a) Voltage
(b) Continuous Current
(c) Breaking and making Current
(d) Electrical & Mechanical life (No. of
operations)
8. MCIRCUIT BREAKER’s
14. Interlock
Annexure- I
134
Effective from
77860/2020/O/o PED/TI/RDSODraft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 49 of 51
Annexure-II
135
Effective from
77860/2020/O/o PED/TI/RDSODraft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 50 of 51
Annexure-III
136
Effective from
77860/2020/O/o PED/TI/RDSODraft SPEC. No. TI/SPC/PSI/LVCBI/0121 Page 51 of 51
Annexure-IV