Louvers 1
Louvers 1
1 . Introduction
Structure description :
The structure is a steel structure building
To check the structural stability of the louver support structure for all incident loads on it.
2) steel structures.
Wind load Data
Structure designed for worst combination of dead & wind loads on the structure..
3) All structural steel members conform to ASTM A36 / BS grade S275 steel or equivalent
Design codes::
Design of support structure for louvers has been done
conforming to following codes of practice.
Staad model
3D- View
Loads :
1) Dead load ( DL)
self weight of supporting structure is calculated by STAAD programme.
3) Load combinations:
(a) Service load combination :: ( for deflections)
1.0 DL
1.0 DL+1.0 WL
1.0 DL -1.0 WL
(b) Design load combination :: ( for design of steel members,design of connections etc.)
1.4 DL
1.0 DL + 1.4 WL
1.0 DL - 1.4 WL
Deflection check :
3 . Design of Connections
Fx = 12 kN Mx = 30 kN
Fy = 90 kN My = 4 kN
Fz = 40 kN Mz =6 kN
Shear capacity: (for 16 dia bolts) Refer catalogue:( page no:- 75)
o
VRd,c = V Rd,c.fB,V.fAR,V.fb,V VoRd,c.= 12.1 kN
min edge distance required Cmin = 85 mm fB,V.= 1.28 for C40 concrete grade
actual edge distance C = 200 mm fAR,V.= 1.89
spacing between bolts S = 120 mm
\ VRd,c = 12.1 * 1.28 * 1.89 *1.0 fb,V = 1.0
= 29 kN > actual shear in bolt
Hence safe
Combined capacity = 10/31.40 + 22.5/ 29 = 1.09 < 1.4
Hence safe
End plate :
max moment in end plate = 2 x 10 x 0.05 = 1kNm
Moment capacity of end plate per unit width = py.tp²/4 ..cl.6.3.4.3, BS5950-1:2000
\Moment capacity of end plate = py.b.tp²/4
= 275 x 230 x 16² /4 = 4.05 kNm > actual moment in end plate
Hence safe
Hence provided 4no. M16 fischer/equivalent anchor bolts/rod and the end plate are safe.
4. Conclusion :
** The proposed Louver support & the support structure and its members are safe for
given loads in combination with other loads.
** The proposed connections are structurally safe.
** The proposed anchors are structurally safe.
Beam Deflection