Hand Held Programmer Reference Guide

This document provides instructions for operating a SmartOne hand-held device programmer. It can program smoke detectors, heat detectors, and input/output modules. The programmer uses rechargeable batteries that must be charged for at least one hour using the included AC adapter before first use. Various accessories are included to connect the programmer to different devices. The menu is navigated using up, down, enter and back buttons. More detailed instructions are available in the user's guide.

Uploaded by

ijas ahmed
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
140 views

Hand Held Programmer Reference Guide

This document provides instructions for operating a SmartOne hand-held device programmer. It can program smoke detectors, heat detectors, and input/output modules. The programmer uses rechargeable batteries that must be charged for at least one hour using the included AC adapter before first use. Various accessories are included to connect the programmer to different devices. The menu is navigated using up, down, enter and back buttons. More detailed instructions are available in the user's guide.

Uploaded by

ijas ahmed
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

®

SMARTONE® HAND-HELD DEVICE PROGRAMMER Quick Reference Guide


SLC Interface RS 232 Connector
BATTERY CHARGING Index
Adaptor Connector (For Future Use) Before you operate the Programmer for the first time Marker
using the supplied rechargeable batteries, OR if the
AC Adaptor
Connector “Low Battery” message is showing on the LCD display,
Detector Base
you may charge your batteries by operating the unit on
AC power. If no batteries are installed, the Programmer
can still be operated on AC power. Addressable Input/Addressable Output Modules
To charge the supplied rechargeable batteries: 1. Connect the AI/AO Module Adaptor to the detector
Hand Grips base, orient the index marker on the device to the
LCD Display
1. Connect the small plug of the AC Adaptor to the AC
five o’clock position, then rotate clockwise.
Adaptor Connector on the top of the Programmer.
Keypad 2. Plug the AC Adaptor into a 115VAC, 60 Hz outlet.
3. Charge the batteries for at least one (1) hour.
4. Turn on the Programmer.
5. Ensure that the “Low Battery” message is no AI/AO
ACCESSORIES longer displaying. Module
Ensure that you have the following accessories: 6. If the “Low Battery” message is still lit, the Adaptor
• SLC Interface Adaptor rechargeable batteries may have exceeded their life
• AC Adaptor (120V) span, and must be replaced.
• AI/AO Module Adaptor TURNING THE PROGRAMMER ON/OFF 2. Insert the AI or AO module so that the terminal
• 4 NiMH Rechargeable AA Batteries (For detailed programming instructions, please access the User’s block faces left. Tilt the module into the recess of
• Storage Case Guide on the Secured Distributor Extranet, under Technical the adaptor so that the terminal block screws make
Manuals→Control Products.) contact with the spring-loaded probes; then snap
BATTERY INSTALLATION
Before you operate the Programmer using internal bat- To turn the Programmer ON, press the button labeled the back of the module into the right half of the
teries, you must install the batteries in the Programmer. “ON.” Verify that the LCD display message reads recess.
“SmartOne Programmer.” After 4 seconds, the first Main
To install the four (4) NiMH rechargeable AA batteries:
Menu option appears — “Single Addressing.” To turn
1. Ensure that the AC Adaptor is disconnected from the Programmer OFF, from the Main Menu, press <←>
the Programmer. Terminal
or <→> until the LCD display reads “Power Off”; then Block
2. Remove the two (2) Phillips screws on the battery press < E > (Enter), and the Programmer will turn off.
compartment on the rear of the Programmer. The Programmer turns off by itself if left idle for (the pre-
Terminal
3. Remove the battery cover. set default time of) 5 minutes. Block Screws
4. Insert four (4) NiMH rechargeable AA batteries, and CONNECTING TO VARIOUS SMARTONE DEVICES
Spring-Loaded
orient them as shown below: Smoke/Heat Detectors Recess of AI/AO
Probes
- Module Adaptor
- Snap the detector into the detector base, orient the index
Back of Unit
- marker on the device to the five o’clock position, then
Battery
- rotate clockwise.
Compartment
Other Devices
5. Replace the battery cover and the two (2) Phillips
screws. Plug the SLC Interface Adaptor jack into the Programmer
Smoke Detector Connector marked “SLC OUT.” Locate terminal blocks
If using alkaline batteries, the Hand-Held Program- Detector Base on device labeled “SLC” or “PC Line.” Connect one SLC
mer must NOT be plugged into AC power. This Interface Adaptor wire to Terminal “A” on the device, and
could damage the Programmer. the other wire to Terminal “B.”
CAUTION
General Menu Navigation
SmartOne® Hand-Held Programmer Navigation Menu
1. Press the <↑> and <↓> buttons to navigate the menu levels.
2. Press the <E> (Enter) button to enter any sub-menu from any hierarchical level.
3. Press the <←> button to return to a previous menu.
For detailed programming instructions,
please access the User’s Guide on the
Secured Distributor Extranet, under
Technical Manuals→Control Products.

These instructions do not purport to cover all the details or variations in the
equipment described, nor do they provide for every possible contingency to
be met in connection with installation, operation, and maintenance. All speci-
fications subject to change without notice. Should further information be
desired, or should particular problems arise which are not covered sufficiently
for the purchaser’s purposes, the matter should be referred to KIDDE-FEN-
WAL, INC., Ashland, MA 01721.

KIDDE-FENWAL, INC.
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-8920
WWW.KIDDE-FENWAL.COM

These instructions do not purport to cover all the details or variations in


the equipment described, nor do they provide for every possible contin-
gency to be met in connection with installation, operation, and mainte-
nance. All specifications subject to change without notice. Should further
information be desired, or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter should be
referred to KIDDE-FENWAL, INC., Ashland, MA 01721.

06-236799-001 Rev AC ©2008 Kidde-Fenwal, Inc. Printed in U.S.A.