Electrical Question Bank
Electrical Question Bank
Owner:
SATISH PANCHAL
([email protected])
1. What do you understand by electro static discharge?
Ans-The process of electron transfer as a result of two object at different potential coming into contact
with each other is called electrostatic discharge.
Static Electric Charge - Static Electric Charge build up occurs on an imbalance of electrons on the
surface of the materials. OR The electric charge at rest on the surface of an insulator body.
2. How would you ensure that bolts have been tightened sufficiently on busbar?
Ans-For the busbar bolt tightness Torque ranch spanner is used. Set the actual required torque setting
on Torque ranch and tight the bolt. When torque ranch spanner movement feels free that is sufficient
bolt tightness.
Flam Proof (EX Code-d) - Motor, Lighting, Junction Box – For Zone 1.
Encapsulated (EX Code-m) - Electronic equipment (No heat) – For Zone 0.
Oil Filled (EX Code-o) - Heavy Current Equipments -Zone 2 or 1.
Increased Safety (EX Code-e) – Motor, Junction Box -
Pressurized/Purged (Ex Code-p)–Motor control box, computer, analyzer-Zone 1.
Special Protection Ex Code-s) - Depends upon manufactures certificates-Zone-1
Motors- Ex d, Ex p Intrinsically Safe (Ex i )
Transformers & Capacitors - Ex d Flameproof (EX d)
Control & Instrument Transformers - Ex I Increased Safety (Ex e )
Lighting Fitting - Ex d Non-Sparking (Ex n )
Switch Gear & Control Gear - Ex d Pressurization (Ex p )
Communication/ Telephone equipment/Meters - Ex i
Portable Hand Lamps- Ex I For symbol of fire hazards:
Class –A = <23˚C flash point R = Fire Hazard
Class –B = 65˚C <class B> 23˚C B = Health Hazard
Class –C = 93˚C <class C> 65˚C C = Reactive Hazard
For Numerical 4=max hazard and 0=least hazard
Gas Group and Temp Class for Hazardous Area:-
If a piece of equipment has just II and no A, B, or C after then it is suitable for any gas group. A list
must be drawn up of every chemical gas or vapour that is on the refinery /chemical complex and
included in the site plan of the classified areas. The above groups are formed in order of how volatile
the gas or vapour would be if it was ignited, IIC being the most volatile and IIA being the least. The
groups also indicate how much energy is required to ignite the gas by spark ignition, Group IIA
requiring the most energy and IIC the least.
• Temperature Class :
Besides the danger of explosion caused by an electrical spark or arc, there is also a danger of ignition
at a hot surface exposed to a flammable atmosphere. The maximum surface temperature of any
unprotected surface of electrical equipment should not exceed the ignition of the gas or vapour.
Flammable gases and vapours fall into fairly well defined groups when classified with reference to
their ignition temperature. To simplify the manufacture of apparatus therefore the permitted
maximum surface temperature have been classified in IS:8239-1976 as follows:---
Temp Class – Min Surface Temp. Temp Class – Min Surface Temp.
T1 - 450˚C T4 - 135˚C
T2 - 300˚C T5 - 100˚C
T3 - 200˚C T6 - 85˚C
For example electrical equipment with a T5 rating can be used in all areas where gases have a
temperature rating from T1 to T5 but not T6 classification.
7. What is the concept of an explosion proof junction box & what symbol does it tell so?
Ans-Junction boxes are used for carrying and distributing electrical power in hazardous areas (zone 1
& zone2. Explosion protection to CENELEC, IEC For use in Zone 1 and Zone 2, Enclosure in glass fiber
reinforced polyester resin Degree of protection IP 66. An explosion-proof and corrosion resistant
junction box for electrical connection junctures and the like including a cap portion having a downwardly
extending external screw portion.
10. What is the difference between float Voltage & boost charger?
Ans-Float voltage charging is a low rate voltage & current charging. Voltage is constant & initial charging
current is higher then final charging. Flat voltage charging is continue charging method. Boost voltage
charging is a high rate charging. Voltage & current both are higher then float charging. It is able to
charge the battery apto full charge. It is used for first time charging of newly battery and if the battery
is fully discharged condition or after maintenance or battery discharge test.
11. Draw a Single Line Diagram of UPS with bypass system.
12. What should be the specific gravity of the electrolyte fully charged lead acid battery?
Ans-Sp. Gravity in Lead Acid Battery = 1.28 & Ni Cadmium battery is = 1.20
13. What is the difference between lead acid battery and Ni Cadmium Battery?
Ans-Lead Acid Battery -Ni Cadmium battery
-Electrolyte: Sulphuric acid - Electrolyte: Potassium Hydroxide
-Sulphation effect occurs - no Sulphation effect
- Acidic & shorter life - Basic & longer life
- High rate charge/discharge not possible - High rate charge/discharge possible
-Anode: Peroxide PBO2 - Anode: Nickel Oxide
-Cathode: Sponge Lead Pb - Cathode: Cadmium
-Full Charge 2.5V, discharge 1.75VDC - Full Charge 1.4V, discharge 1.1 VDC
-Automobiles vehicle & UPS, emg power -Emg. power, Ind. power, Comm equip.
21. What is the difference between restricted earth fault & non restricted earth fault relay?
Ans-Restricted E/F Protection operates only in certain selected zone and it is unit protection. Non
restricted E/F operates on outside or inside E/F in all circuit.
Ans-
29. What is the function of Lightning Arrester & Wavetrap in Power system?
Ans- Wave Trap : This is varying the impedance...
The Application of wavetrap is in PLCC (power line career communication)
Lightening Arrester : This is grounding the surge voltage.
31. Why Power generation in India is at 50Hz while in America its 60Hz so is there any
advantage/Disadvantage of this ?
Ans- in US the frequency is 60hz and 110v supply. but in india is about 240v,50hz supply. for a particular
load say 100kw the current will be 0.416A. but in US the same load will consume about 0.9A. here the
thing is the heat produced in the cable bcoz of the flow of current will be large in US compare to india.
since US is a cold country they can use this level but not by india.
32. Why Human body feel Electric shock? and in an Electric train during running , We didn’t
feel any Shock ? Why…
Ans- Unfortunately our body is a pretty good conductor of electricity, The golden rule is Current takes
the lowest resistant path if you have insulation to our feet as the circuit is not complete(wearing rubber
footwear which doingsome repairs is advisable as our footwear is a high resistance path not much
current flows through our body)The electric train is well insulated from its electrical system.
35. Why P.F. of the system decreases when it is connecting across induction motor? & how
to maintain the PF of system to unity?
Ans- induction motor is an inductive device and we know that in inductive circuit current lags behind
voltage due to the inductive reactance of the motor. so that the phase angle between voltage and
current will increase. and the cosine angle i.e. P.F. will decreases.to improve the p.f we have to supply
leading Kvar to the system. it is possible by different way. either use capacitor bank which will supply
leading kvar to the system and overall lagging kvar will decreases and if we see the power triangle then
the angle between KW and KVA will decrease so that the p.f. will improve. second method is to run
synchronous motor on leading p.f. in parallel with the system.
39. What you mean by +Ve sequence, -Ve seq. and zero sequence of voltage?
Positive phase sequence
A system of vectors is said to have positive sequence if they are all of equal
magnitude and are displaced by 120° with same time interval to arrive at fixed axis
of reference as that of generated voltage. The positive phase sequence is represented
below and the vectors arrive along X-axis in order 1, 2, 3 and conscript P has been
used to designate as positive sequence.
Negative phase sequence
A system of vectors is said to have a negative phase sequence if they are of equal
magnitude displaced at an angle of 120° but arrive at the axis of reference at the
regular interval same as that of positive phase sequence but in order of 1, 3, 2. That
is the order is reversed.
Zero sequence
A system of vectors in a phase system is said to have zero phase sequence if all the
three vectors are not displaced from each other and there will be no phase sequence
in such cases. The current or voltages in the 3-phase circuit vary simultaneously in
all the 3- phases. Such phase sequence is zero phase sequence.
40.What is the difference b/w winding insulation class and winding temperature class?
43.What is ment by KVAR & what are the advantage & disadvantages of KVAR
Ans- KVAR - Reactive Power
It's Present only in Inductive load, i.e. X-mer, Motor, X-mission Line..etc And This power is required for
generating Magnetic field in inductive load. Here, i want to explain some formuls KVA = Sqrt((kw)^2
+ (Kvar)^2)
Where , KVA = Apparant Power,KW= Actual Power, Kvar= Reactive Power,
PF=KW/Kva = KW/(KW+Kvar) = COS$
1. If the value of kvar is more. it means PF is Less.
2. If the value of Kvar is zero. It means Unity PF (PF=1). it means Apparant Power is Maxi. and over
KW Loading is Maxi.
--> Practically PF is not Unity (PF=1). its near about One.
For Reducing Kvar Demand We install Capacitor In Ckt.
Dis-Advantage (If Kvar is More)
1. less KW Loading(Low load Allow) in system.
2.Power Factor will Poor.
3.High current in system so Conductor & Cable size increase.
4.Electricity bill will more (Money Loss)
53.Why Resistance grounding is prefer for less then 33KV & more then 415V?
Ans- a) To limit the earth fault current for equipment safety else, high short ckt forces dislocate in
windings/ busbar etc.
b) Over voltage due to arcing ground reduce.
c) Permit E/F protection (not possible in ungrounded system)
68. What are the factors on which the capacity of the battery depends?
The capacity of the battery is measured in ampere-hour. The capacity of the battery
depends upon the following factors.
a. Number and area of the positive plate.
b. Discharge voltage. A cell should not be discharged below 1.8 V. If it is
discharged below 1.8 V it may cause to reduce the capacity.
c. Discharge rate. Capacity decreases with increase rate of discharge.
d. Specific gravity of electrolyte. With rapid rate of discharge causes to weaken
the electrolyte so the chemical action also weakens and there by the capacity
decreases. When the specific gravity increases the capacity of the battery
increases.
e. Quantity of electrolyte. Electrolyte level should be at the top plate level.
f. The design of separator. The design of the separator should be thin.
g. Temperature. When the temperature increases the resistance of the battery
decreases and the capacity increases.
Equipment Earthing: - is connecting non current carrying metallic parts of electric plant to station
earth (earth electrode or earth mat). It is mandatory as per safety rules. It prevents several electric
shocks & protection of equipment from earth leakage current, discharge of earth leakage current
and capacitive charging current. Safe to touch the equipment.
Neutral Earthing: -Connecting the Neutral point of Three phase AC system to earth (Earthing electrode
or earthing mesh) by low resistance conductor is called neutral earthing or system neutral earthing.
It is done to limit the earth fault current. It is earthed in order to obtain a balance voltage from each
phase. Easy for earth fault protection. In single earth fault the voltage of two healthy phase with
respect ground raise to √3 times normal phase voltage to ground volt. Such sustained over voltage
is harmful for insulation of motor in this case neutral earthing is required. Any types (switching or
lightning) over voltage easily dissipated to earth.
Copper or iron plate buried at the depth of 2.5 to 3 mtrs act as a good earthig.
Earth resistance should be less then <1 ohm, In domestic low voltage: 3 ohm, In low /medium voltage
substation: 0.5 ohm and for 220KV & 400KV substation below 0.1 ohm. If it is more the add charcoal,
Sault and pour sufficient water in earth pit.
Touch Potential (potential diff between raise finger & the feet) & Step Potential (potential diff b’ween
two step of person standing on ground) should be below 45V.
15. What are the protections provided for 220 kV lines and bus bars?
Ans- a. Bus bar differential protection.
b. Distance protection.
c. Over current protection.
d. Earth fault protection.
19. Standard clearance for 220KV system. (For Effectively earth system)
Ans- For 900KV Impulse withstand:
Minimum phase to earth = 178 cms
Minimum clearance between phase in air = 225 cms
For 1050KV Impulse withstand:
Minimum phase to earth = 207 cms
Minimum clearance between phase in air = 252 cms
Phase to Phase = 2.5 mts. And Ph to earth = 2.0 mtr.
21. What is the function of Lightning Arrester & Wave trap in Power system?
Ans-Wave Trap: This is varying the impedance...
The Application of wavetrap is in PLCC (power line career communication)
Lightening Arrester: This is grounding the surge voltage. (Gapless Zinc Oxide)
23. What type of protection and safety req. in the 220kv substation and area around the
substation?
Ans-(I) always wear industrial safety hamlet. (II)Don't raise hands & don’t use ladder.
(III) Don’t use umbrella in rainy days. (IV) Always go with one collogue.
(V)Don’t walk on trenches.(VI) Never operate Iso.& E/S without wearing hand gloves.
30. CT Data and Testing: Areva meke Hermetically sealed (Post Type)
Ans-For BB Diff-core 5,6 = 2500/1A, Metering-core3=600/1A, Prot.Core1,2,4=600/1A
IR Test = 1GΩ, 2. Wdg resi=5Ω, 3. Continuity test,
4. Polarity test, 5. Ratio Test 6. Megnetiging Curve test (Knee point)
31. LA Testing : Ans-198KV (72+120), Counter meter test, Megger (IR) test =1GΩ
33. What is GIS S/S & how it operate? Where these type of S/S installed?
Ans-GIS means gas insulated substations. SF6 Gas Insulated Substations (GIS) are preferred for voltage
ratings of 72.5 kV, 145 kV, 300 kV and 420 kV and above. In such a substation, the various equipments
like Circuit Breakers, Bus-Bars. Isolators, Load Break Switches, Current Transformers, Voltage
Transformers Earthing Switches, etc. are housed in metal enclosed modules filled with SF6 gas.
The SF6 gas provides the phase to ground insulation. As the dielectric strength of SF6 gas provides the
phase to ground insulation. As the dielectric strength of SF6 gas is higher than air, the clearances
required are smaller. Hence, the overall size of each equipment and the complete substation is reduced
to about 10 % of conventional Air-insulated substations. As a rule GIS are installed indoor. However
outdoor GIS have also been installed earlier
13. What is the static pressure of diaphragm in the transformer explosion vent? 5 psi.
14. In buchholz relay how the top and bottom mercury switches are connected? Top mercury
switch is connected for alarm and bottom switch for trip.
15. What are the losses in a power transformer and mention how these losses can be
minimized?
There are two losses in a transformer.
a. Iron losses.
b. Copper losses.
Iron losses – Iron losses constitutes of two losses.
a. Eddy current losses, these are due to the induced emf in the core, which
constitutes a current in the core. These will heats up the core.
Eddy current losses can be minimized by using laminated core immersed in
varnish. This provides a high resistance between the laminations and thus eddy current in reduced.
b. Hysterisis losses, these are due to the magnetic reversal of current by which there is friction between
molecules of core and heat is generated.
Hysterisis losses can be minimized by selecting proper magnetic material, like silicon steel.
Copper losses – these losses are due to the resistance of the winding, which is equal to I2rt (calories).
These losses are depends on load. That is the losses are increased to the square of the load current
I – current through winding.
r – resistance of winding.
t – time duration.
16. Define the percentage voltage regulation and efficiency of a power transformer.
Voltage regulation is the difference between no load voltage and full load voltage by no load voltage.
Voltage regulation = No load voltage – Full load voltage / No load voltage.
Voltage regulation is mentioned in % (percentage).
% Voltage regulation = No load voltage – Full load voltage * 100 / No load voltage.
Efficiency of a transformer is the ratio of output in watts and input in watts.
Efficiency = Output in watts / Input in watts.
% Efficiency = Output in watts * 100 / Input in watts.
% Efficiency = Output in watts * 100 / Output in watts + losses.
19. Why all the transformers are having different vector group?
UT and SUT are getting paralleled at 6.6 kV bus. Hence they should have voltage of same phase
relationship. This is achieved by assigning different vector group to the transformers.
33. Why motor starting current is high compared to transformer charging current?
Transformer charging current is only 1% and that of motor starting current is 30 to 40%. Because of
air gap between stator and rotor. If the air gap is more load taking capacity increases and if air gap is
less the load taking capacity reduces.
Breather: It provides dry sir to conservator when transformer breathes. That is when
there is shrinkage of oil atmospheric air enters conservator through breather. The
moisture is absorbed in breather by silica gel.
Buchholz relay (gas operated): If there is an initial fault, heating up of core, high
resistance joints heating up by conduction through insulation and supports. There is
heating up of oil, which breaks down and gases are released. This gas actuates the
mechanics in the relay, There by closing contacts of mercury switches for alarm.
Also if there is a short circuit, the buchholz relay will trip the transformer. Also if
there is any leakage of oil through bushing etc and oil level comes down the relay
will give alarm and also will trip the transformer if transformer oil level comes down
the point. Gases can be taken from the relay to identify nature of fault.
Explosion vent: It provided on transformer main tank, provided with two Bakelite
diaphragm which break when the pressure exceeds 5 psi in the transformer tank and
relieve the pressure.
Core: To provide low reluctance path for the magnetic lines of force. It carries both
the HV and LV windings.
HV Winding: High voltage is given to HV winding and low voltage is taken from
the LV winding.
LV Winding: Low voltage is given to LV winding and high voltage is taken from the
HV winding.
Cooling tubes: These are provided to cool the transformer oil so that the heat of oil
will be given to the atmosphere.
HT bushing: Carries the HV terminals.
LT bushing: Carries the LV terminals.
Tap changer: this is provided so that we can get the required voltage out put. There
are two types of tap changer. Online tap changer and off line tap changer.
38. Transformer OIL Property as per IS 335. (2.5mm Gap in Oil BDV Test kit)
Ans-The Oil should have a minimum breakdown voltage & Moisture Content as below:
<72.5 KV = BDV 40KV (rms) = 25 ppm moisture content
72.5KV to 145KV = BDV 50KV (rms) = 20 ppm moisture content
>145 KV = BDV 60KV (rms) = 15 ppm moisture content
RST Trans. Setting = Oil Temp Alarm at 95°C & Tripping at 105°C (small Xmer85&95)
Wdg Temp Alarm at 105°C & Tripping at 115°C (small Xmer 95 & 105)
4. How many types of fire extinguishers are there and state their suitability?
a. Soda acid type – suitable for Class A type of fires.
b. Foam type – suitable for Class A and Class B type of fires.
c. Carbon-di-oxide type – suitable for Class B, Class C and for Class E type of fires.
d. Dry chemical powder – suitable for Class B, Class C, Class D and Class E fires.
e. Halons BCF (bromo chloro difluoro methane) – suitable for Class A, Class B,
Class C and Class E types of fires.
5. At what areas of risk the Co2 flooding system, mulsifyre systems are provided?
Co2 flooding system is provided in diesel generator and turbine oil tank area.
Mulsifyre system is provided in generator transformer, start up transformer and unit transformer
areas.
33KV BO AR D LEG EN D :
1 . 2 1 A B C - B c k u p im p e d a n c e
3 3 K V /1 1 0 V 2 . 2 4 -T rfo . o v e r flu x in g
3 . 2 7 - U n d e r v o lta g e
4 . 3 2 - R e v e rs e p o w e r
5 . 4 0 - F ie ld fa ilu re
3 3 K V /1 1 0 V
6 . 4 6 - N e g a tiv e p h a s e s e q u e n c e
S Y N C H R O N IS A T IO N 7 . 5 1 V -V o lta g e re s tra in O /C
P1
8 . 5 9 N - N e u tra l d is p la c e m e n t
KBC H 130 HV O /A D IF F .+ R E F 1 2 5 0 /1 A 9 . 5 9 - O v e r v o lta g e
8 7 G T ,6 4 F ,2 4 CL: PS 1 0 . 6 0 - V o lta g e b a la n c e
1 1 . 6 4 S - S ta to r e a rth fa u lt
A L A R M + T R IP M A R S H A L L IN G B O X M E T E R IN G 1 2 . 6 4 R - R o to r e a rth fa u lt
1000/1A
B U C H ,W T I,O T I,P R V ,M O G 1 3 . 6 4 H - T ra fo . R E F
LV1
LV2
REF
O /C + E /F P R T N . 7 S J 5 5 1
1 4 . 7 8 - P o le s lip p in g
3 3 K V B U S D IF F . P R T N . 1 5 . 8 1 U /O u n d e r/o v e r F re q u e n c y
KC G G 110 1 6 . 8 7 G - G e n . d iff.
S /B E F P2 1 7 . 8 7 G T G e n . & T ra fo . O /A d iff.
O/A DIFF.
1 8 . 2 7 /4 0 - L o s s o f fie ld w ith U /V
P2 CT27 CT26 P1
G e n .T ra f: 5 3 M V A
1 1 /3 4 .5 K V
1 2 5 0 /1 A 1 2 5 0 /1 A
CL: PS C L :5 P 2 0 , 3 0 V A Conn. Ynd11
Z = 1 7 .2 3 %
U A T -6 3 0 K V A
C T 2 0 ,2 1 ,2 2
P2 P1 O F F L O A D IS O .
3 0 0 0 /1 A 1 0 0 /1 A
CL: PS C L :5 P 1 5 ,2 0 V A
C T 1 7 ,1 8 ,1 9 LA+SC
P T 7 ,8 ,9
P1 CT23 KCG G 142
U A T O /C a n d 1 1 K V /R o o t3 /1 1 0 V /R o o t3
S /B E /F A V R P T s ,C L :0 .5 ,4 0 V A
1 1 K V /R o o t3 /1 1 0 v /R o o t3
P2 1 0 0 0 /1 A P R O T E C T IO N P T s
C L 5 P 2 0 ,1 5 V A C L :3 P /0 .5 ,1 0 0 V A
P T 1 ,2 ,3
1 1 K V /R o o t3 /1 1 0 V /R o o t3
M E T . P T s ,C L :0 .2 ,1 0 0 V A
P T 4 ,5 ,6
P2
C T 1 1 ,1 2 ,1 3
MET. CTs
F R O M P C C -4 AVR M E T E R IN G
3 0 0 0 /1 A
C L : 0 .2 , 6 0 V A
CT10
3 0 0 0 /1 A
415V M CC C L : 0 .5 ,4 0 V A
VTU21
O NLY Yph
59
CDG 31 CDG 31
O /C O /C
V T IG M
C T 7 ,8 ,9 2 7 /4 0
G E N . D IF F .
3 0 0 0 /1 A
CL: PS
P1
Voltage Balance+Reverse Power
For Reverse Power- Rph only
MW TU
32R
P
30M W
M
GEN. MZTU
G 21ABC
EXTR DW GF
CTU12
5 1 -1 G
P2 C T 4 ,5 ,6
G E N . D IF F .
3 0 0 0 /1 A YTGM
CL: PS
78G Y
7U R
CT1,2,3
64R
C T 1 ,2 ,3 LG PG 111
ALL PRTN. 2 7 ,3 2 R ,4 0 ,4 6 ,5 1 V ,5 9 ,5 9 N
ZTO 11
( 6 4 S 1 ) ,6 0 ,8 1 U /O ,8 7 G 78G
3 0 0 0 /1 A
CL: 5P15
C T 1 4 ,1 5 ,1 6
O /A D IF F . 3 0 0 0 /1 A
CL: PS
P1
NGT
1 1 K V /2 0 0 V , 1 P H R PVM M 163
3 6 K V A F O R 1 0 m in . 64S2
0 - 9 5 % & 9 5 - 1 0 0 % S T A .W D G . P R T N .
R = 0 .7 o h m
1 6 5 A fo r 1 0 m in .
S .H . S O L A N K I J .G . D H A B A L IA S. DASGUPTA
R E V IS IO N : 0 D A T E O F IS S U E : 0 5 /1 2 /2 0 0 1
PREPARED BY CHECKED BY APPROVED BY
The purpose of the protections of the machine is to protect the generator against electrical faults coming from
the generator itself (internal fault), or from the grid (external fault) : short-circuit, earth fault and so on.
The protections must be fast and selective, fast to avoid any physical damage to the machine, selective to
ensure a continuous production on the grid.
• Internal faults :
• earth fault
• fault between phases
• fault between coil turns of a same phase
• unbalance
• loss of excitation
• rotor earth fault
• over or under excitation
• heating
• External faults :
• Earth fault
• overload or fault between phases
• unbalanced loads
• over or under voltage
• over or under frequency
• mechanical fault (turbine,…)
•
• Excitation faults:
• Rotating diodes fault
• Min. & max. excitation faults
•
THE DIFFERENT ACTIONS
• Trip of the generator breaker whatever the fault : directly connected from the protection panel to the
breaker panel
• Trip of the excitation contactor whatever the fault : internal to the panel
• To the turbine : 3 signals
1) an alarm signal (without any trip ) : first treshold
2) an alarm signal to indicate that the protection panel tripped the generator breaker (and
the excitation too)
3) a trip signal to shutdown the turbine
In Jerp Gas turbine is having Two G60A/B protective relay for generator related fault & T60A/B for MSU (Main
step up ) Transformer related fault .Also lockout relay
The operating limits specified by the manufacturer may be inadvertently exceeded for a number of reasons.
These include, among others:
The protection methods and equipment in place should be able to safely protect the generator no matter
which of these circumstances, or combination of them, causes the abnormal operation.
OPERATION OF GENERATOR
Those protective relays or devices that trip the generator should alert an operator as to the cause of any
trip, and be able to take direct action if this should prove necessary. In addition to the tripping relays there
are other relays or devices that initiate only an alarm or data logging. In these cases it becomes an operator’s
responsibility to decide what corrective action is required and to take it.
Alarms
Many of the “alarm only” devices are for temperature measurement. These are Resistance Temperature
Detectors (RTDs) and Thermocouples (TCs).
The need for protecting a generator while on line is well known, but the need when off line may not be as
well understood. Nevertheless, there are circumstances under which a generator could be damaged while
off line. For this reason, it is recommended that, as a general rule, all alarms and protections be kept
operative at all times. Exceptions to this rule are those protections which would mis-operate or give false
signals when the unit is below rated speed, not excited, or not synchronized. Relaying and interlocking
circuitry that operates when the unit is off line should be reviewed to make certain it does not inadvertently
incapacitate any essential protection.
. Protection Recommendations
1. Stator Overcurrent
a. Description
Generators are designed to operate continuously at rated kVA, frequency and power
factor over a range of 95 to 105% of rated voltage. Operation beyond rated kVA may re
sult in harmful stator overcurrent. Note that at rated kVA, 95% voltage, stator current will
be 105%. This is permissible.
Normally, generator load is under the control of an operator. Situations can arise during
System disturbances, such as accompanying generator or line tripouts, which can result
in an overcurrent condition. For short times, it is permissible to exceed the current corresponding to rated
kVA. This Capability is specified in ANSI Standard C50.13 as follows:
b. Detection
Stator current should be monitored by an operator, and kept within rated value by
Adjustment of the turbine-generator controls.
A consequence of over current is stator winding overheating, which should be detected by winding
temperature detectors, usually TCs measuring stator cooling water temperature, and/or RTD’s in slots with
the stator winding (if applicable). All functioning TCs and RTDs should be continuously monitored and
alarmed .How ever, even though it may not result in excessive stator winding temperatures, operating above
c. Recommendation
Automatic tripping is not provided for protection against stator over current. In cases when a generator will
operate in an unattended station. An alternative is stator
over temperature which provides similar protection.
a. Description
The generator stator neutral normally operates at a potential close to ground, generally
Through a high impedance grounding transformer/resistor. In some cases a reactor is
used in a resonant grounding arrangement. Should a phase winding or any equipment
connected to it fault to ground, the normally low neutral voltage could rise as high as lineto-neutral voltage,
depend-ing on fault location. Although a single ground fault w ill not necessarily cause immediate damage,
the presence of one increases the probability of a second. This is because the occurrence of such a fault is
probably the result of damage which is not confined to one spot. In fact, the existence of a ground fault
through tough, high-voltage insulation is usually a result of another, potentially catastrophic, trouble. A
second fault, even if detected by differential relays, may cause serious damage. A second fault in the same
phase will not be detected by differential relays, and could cause serious damage as a result.
b. Detection
The usual method of detection is by a voltage relay across the grounding resistor. A
current relay is sometimes used in place of a voltage relay or as a back-up. The relay
should be insensitive to third harmonic voltage, but should have as low a pick-up level at
line frequency as is practical to reduce the unprotected zone at the neutral end of the
windings. Methods are available w hich are designed to protect the entire winding. These schemes make
use of the relationship of third harmonic voltages at the line and neutral terminals of the generator. These
schemes supplement the fundamental frequency protection.
c. Recommendations
The grounding impedance should limit the ground fault current to less than 25 amperes.
The usual criterion based on circuit capacitance w ill normally result in less than 10
amperes. The stator ground fault relay should be connected to trip the unit within several
seconds, using a si-multaneous trip,
a. Description
A stator phase-to-phase fault is any electrical fault between two phases of the armature
winding. This type of fault is very serious because very large currents can flow and produce large amounts
of damage to the winding if allowed to persist. Because of the nature of the construction of the armature it
is very likely that this type of fault will grow to include ground, thereby causing significant damage to the
stator core.
c. Recommendations
Upon detection of a phase-to-phase fault in the winding, it is imperative that the unit be
Tripped without delay, using a simultaneous (Type 1) trip.
4. Over-Voltage
a. Description
Per missible voltage limits under various operating conditions are given in the Generator
Operation instructions (Ref. 1). It is normally an operator’s responsibility to maintain voltage (and the
corresponding kVA) w ithin specified limits. With turbine-generators it is unlikely that voltage w ill depart
significantly from the preset value. If it does, due to a regulator failure or a system disturbance, a trip signal
will usually be produced by one of the protective relays, such as volts/Hertz or maximum excitation limit.
b. Recommended Action
Therefore, specific over-voltage protection is generally not required for the generator. Depending on the
circumstances, it may be desirable to protect other equipment connected to the generator. For unmanned
generating stations, consideration should by given to implementing automatic overvoltage protection.
a. Description
Per unit voltage divided by per unit frequency, commonly called volts/Hertz, is a readily
Measurable quantity that is proportional to flux in the generator and step-up transformer cores.Moderate
overfluxing (105%–110%) increases core loss, elevating core temperatures for all generator designs and
armature temperatures for generators with conventionally cooled stator windings. Long term operation at
elevated temperatures can shorten the life of the stator insulation systems. More severe overfluxing (above
110%) further increases core loss, and saturates portions of the core to the point that flux flows out into
adjacent structures. The resulting induced voltages can be coupled to stator punchings due to the manner
in which cores are assembled and clamped. Severe overfluxing can breakdown interlaminar insulation,
follow ed by rapid local core melting. Over-volts/Hertz can be caused by regulator failure, load rejection w
hile under control of The dc regulator, or excessive excitation w ith the generator off line. It can also result
from decreasing speed while the ac regulator or the operator attempts to Maintain rated stator voltage.
b. Detection
Volts per Hertz is calculated in a static circuit incorporated in a volts/Hertz relay or sensor. Timing circuits
are also incorporated. The volts/Hertz sensor is normally included as part of the excitation system.
6. Field Overexcitation
a. Description
The generator field winding is designed to operate continuously at a current equal to that Required to
produce rated kVA at rated conditions. In addition, higher currents are permitted for short times, to permit
field forcing during transient conditions. These limits are specified in terms of a curve of field voltage vs. time
defined by the following points in ANSI Standard C50.13-1977:
Time (seconds) 10 30 60 120
Field voltage (percent) 208 146 125 112
b. Detection
Most excitation systems now being furnished include a Maximum Excitation Limit function. Its purpose is to
prevent prolonged field overcurrent by recalibrating the current regulator, transferring to another regulator,
and, finally, producing a trip signal, as required.
c. Recommendation
The owner’s responsibility with respect to this function is to see that the Maximum Excitation Limit is properly
adjusted and maintained, and properly connected to trip the unit when required. Protection Type 4,
sequential trip, or Type 1, simultaneous trip, is recommended. For high response exciters, a Type 1 trip may
be required to avoid rapid overheating of the field should the exciter stay at ceiling for an extended period
of time. In such cases a sequential trip w ould take too long. Since loss of potential transformer signal to the
voltage regulator is one cause of field overcurrent, relaying to detect this situation and automatic transfer to
another regulator is suggested. Sensing and transfer functions are part of most modern excitation systems.
7. Field Ground
a. Description
The generator field winding is electrically isolated from ground. Therefore the existence of One ground fault
in the w inding will usually not damage the rotor. However, the presence of two or more grounds in the
winding will cause magnetic and thermal imbalances plus localized heating and damage to the rotor forging
or other metallic parts. Unfortunately, the presence of the first ground fault makes detection of a second fault
difficult, if not impossible. In addition, modern rotor winding insulation systems have achieved a level of
quality that reduces the likelihood of a field ground except under unusual circumstances where the
probability of occurrence of a second ground or other serious problem is high.
b. Detection
The relay necessary to detect a field ground is normally supplied w ith the excitation system.
8. Loss of Excitation
a. Description
Loss of excitation (or loss of field) results in loss of synchronism and operation of the Generator as an
induction machine. This will result in the flow of slip frequency currents in the rotor body, wedges, and
armature windings (if so equipped), as well as severe torque oscillations in the rotor shaft. The rotor is not
designed to sustain such currents, nor is the turbine-generator shaft designed to long withstand the
alternating torques. The result can be rotor overheating, coupling slippage and even rotor failure. The length
of time before serious damage occurs depends on the generator load at the time of the incident, slip
frequency, and whether the field winding is open circuited or shorted, and may be a matter of seconds. A
loss of excitation normally indicates a problem with the excitation system which, Depending on its nature,
could be serious (e.g., collector ring flashover, if so equipped). Because of the VARs absorbed to make up
for the low or lost excitation, some systems cannot tolerate the continued operation of a generator without
excitation. Consequently, if the generator is not disconnected immediately when it loses excitation,
widespread instability may very quickly develop, and major system shut-down may occur.
b. Detection
Since loss of excitation results in a marked change in reactive kVA, a loss of excitation relay of the
impedance or mho type is usually used (Ref. 6).
c. Recommendation
The generator should be tripped from the power system, using a simultaneous trip (Type 1), or a generator
trip (Type 2). It is important that all excitation pow er be removed. It should not be assumed that, since there
is loss of excitation, the exciter is not supplying power to an internal fault.
a. Description
When the generator is supplying an unbalanced load, the phase currents and terminal Voltages deviate from
the ideal balanced relationship, and a negative phase sequence armature current (I2) is imposed on the
generator. The negative sequence current in the armature winding creates a magnetic flux wave in the air
gap which rotates in opposition to the rotor at synchronous speed. This flux induces currents in the rotor
body iron, wedges, retaining rings and armature windings, if so equipped, at twice the line frequency.
Heating occurs in these areas and the resulting temperatures depend upon the level and duration of the
unbalanced currents. Under some conditions, it is possible to reach temperatures at w hich the rotor
materials no longer contain the centrifugal forces imposed on them, resulting in serious damage to the
turbine-generator set (Ref. 11). There is always some low level unbalance in any power system and
therefore limits on the continuous unbalance have been established. For currents above the permissible
continuous levels, a limit on the time-integral of I2 has been established for times up to 120 seconds. Such
levels w ill often result from faults, open lines or breaker failures. where I2 is the per unit negative sequence
current on the generator base and it is the time in seconds.
b. Detection
The protection scheme should be designed such that it will permit negative sequence Currents up to the
continuous limit, but produce a trip signal if the level exceeds this value long enough to reach the permissible
I2 2t limit (Ref 13). It is also desirable to alert an operator when I2 exceeds a normal level, which may be
lower than the permissible continuous negative sequence current. This enables him to adjust load in order
to prevent a trip. Ref. 1 describes in more detail the actions an operator may take.
a. Description
Loss of synchronism, also referred to as out-of-step operation or pole slipping, can occur as a result of
steady-state transient or dynamic instability. It also may occur as a result of loss of excitation or
synchronizing errors.
b. Detection
The majority of users do not apply specific loss-of-synchronization relaying. However, a skilled relay
engineer can adjust impedance relaying to reliably detect loss of synchronism. Loss of excitation relays may
provide detection, but cannot be relied upon under all conditions. If the electrical center during loss of
synchronism is in the transmission system, line relays may detect it. If they do not, specific relaying should
be provided.
c. Recommendation
Out-of-step operation can result in pulsating torques and winding stresses and high rotor iron currents that
are potentially damaging to the generator. Excessive stator winding and core end heating can also result if
the out-of-step operation is caused by reduced or lost excitation. Therefore, it is recommended that the
generator be separated from the system without delay, preferably during the first slip cycle. A breaker trip,
Type 3, is recommended, and permits the fastest resynchronization after conditions have stabilized.
a. Description
For a generator connected to a power system, abnormal frequency operation is a result of a severe system
disturbance. An isolated or unconnected unit could operate at low or high frequency due to improper speed
control adjustment or misoperation of the speed control.There are two effects to be considered. The
generator can tolerate underfrequency operation for long periods, provided load and voltage are sufficiently
reduced, The generator can also tolerate overfrequency operation provided voltage is within an Acceptable
range.
B Recommendation
For the generator, specific protection for abnormal frequency operation is not required. However, the turbine
is very sensitive to abnormal frequencies and recommendations given for it should be carefully studied and
followed (Ref. 24, 25). Detection of abnormal frequency operation may also be used to identify system
problems.
a. Description
Since most faults involving the generator require tripping of the generator/line breakers, Failure of any of
them to open properly results in loss of protection and/or other problems, such as motoring. If one or two
poles of a generator line breaker fail to open, the result can be a single-phase load on the generator and
negative sequence currents on the rotor.
b. Detection
Both types of failure described above will cause conditions that may be detected by other Protective devices,
e.g., reverse power, loss of synchronism or negative sequence relays. However, a more direct method is
the use of Breaker Failure Protection (BFP) which is energized when the breaker trip is initiated. After a
suitable time interval, if confirmation of breaker tripping in all three lines is not received, a signal is generated.
c. Recommendation
Industry past practice has not always recognized the need for breaker failure protection Because of the
reliability of line breakers. How ever, it is recommended that BFP be used with all tripping relays that can
trip a generator line breaker. The BFP signal should trip all line breakers that can feed current to the
generator through the failed breaker
a. Description
System back-up protection is also known as external fault back-up protection. As this name implies, it is
used to protect the generator from supplying short circuit current to a fault in an adjacent system element
because of a primary relaying failure
b. Detection
Either voltage restrained or current restrained inverse-time over current or distance relays May be used,
depending on the kind of relaying with which the back-up relays must be selective. Negative sequence
relays, in addition to their primary protective role, are sometimes considered for system back-up protection.
How ever, these will not provide protection against balanced faults.
c. Recommendation
System back-up protection is recommended. The relays should be connected to trip the
unit, using a breaker trip (Type 3), or simultaneous trip (Type 1).
a. Description
Certain abnormal conditions could occur which might subject the generator to high voltages surges. Among
these are:
• Switching surges from circuit breakers at generator voltage
• Positive and negative surges arriving simultaneously on two phases
• Ineffective direct stroke shielding
• Failure of high side surge protective equipment
• Accidental connection between high and low side transformer windings, due to internal failure, external
flashover or other cause.
The latter category is not a normal protective function of low voltage arrestors and would Subject them to
excessive duty which could cause their failure. In view of the potential personnel hazard in the event of surge
arrestor failure, the user should consider physically isolating the surge arrestor cubicles and limiting access
to them.
a. Description
The switching of transmission lines at or near generating stations for maintenance purposes, or simply
restoring a line to service after a relayed trip out, are recognized as normal functions in the course of
operating a power system. In some cases these line switching operations can subject nearby generating
units to excessive duty. The effect on the generator in severe cases is the same as for poor synchronizing
in causing possible stator winding and shaft fatigue damage.
b. Detection
A measure of the severity of a switching event is the sudden step change in power (P) seen by the
generator at the instant of switching. As a general guide, studies have shown that where P does not exceed
0.5 per unit on the generator kVA base the duty w ill be negligible Values of P greater than 0.5 per unit
may be determined to be non-harmful to the generator, for specific units and system switching events, but
these cases should be carefully studied and identified. Predetermination of duties associated w ith line-
switching operations and operating Procedures which limit these duties to acceptable values can be found
from simulating these operations, using a computer program such as that normally used for stability
studies
c. Recommendation
The recommended procedure for avoiding excessive duty for the normal planned line switching operation is
to establish, where necessary, operating procedures which limit the machine P to either the general 0.5
per unit level or an individually determined level for that unit. As an adjunct to established operating
procedures, phase angle check relays at key breaker locations can prevent line closings under
circumstances predetermined to be excessive. Note, however, that such check relays should not be applied
without reliable means of overriding which would permit necessary line closing operations under emergency
circumstances.
a. Description
High speed reclosing of transmission circuits directly out of generating stations or electrically close to the
station may cause significant shaft fatigue damage to the turbine generator unit, particularly where high
speed reclosing following severe multi-phase faults is permitted .The actual fatigue duty which a unit may
experience during its lifetime from this cause depends on many factors, including both the unit’s and the
system’s characteristics, the frequency of fault occurrence, etc. Studies substantiate that significant shaft
damage could occur with un-successful reclosing for close-in three phase faults.
b. Recommendation
In order to eliminate or reduce the potential effects of unrestricted high speed reclosing of Lines near
generating stations, an alternative reclosing practice such as one of the following is recom-mended:
• Delayed reclosing, with a delay of 10 seconds or longer.
• Sequential reclosing, i.e., reclose initially only from the remote end of the line and block closing at the
station if the fault persists. This is recommended only if the remote end of the line is not electrically near
other turbine-generator units.
a. Description
When a turbine-generator is connected to a transmission network that has series capacitor compensation
or a high voltage dc (HVDC) transmission system, it is possible to develop subsynchronous (under line
frequency) current oscillations in the lines and in the generator armature. In the case of series compensated
ac systems, these currents interact with the synchronously rotating flux to produce torque pulsation on the
generator rotor. If these pulsations are at a frequency close to one of the torsional natural frequencies of the
turbine-generator, high levels of torsional vibration can be induced in the shafts. Torsional instability of the
turbine-generator shaft system has the potential for being extremely damaging to the turbine-generator
shafts. A more recently observed phenomenon in-volves interaction between torsional modes and HVDC
controls. This could lead to an unstable situation, resulting in spontaneous grow th of torsional vibrations
and potential damage to the shaft.
b. Detection
Unstable or high levels of torsional vibration may be detected by observing the variations In angular velocity
of the turbine-generator. A common measuring system involves a toothed wheel, a magnetic pickup and a
frequency demodulator. Strain gauge telemetry systems have also been utilized in short-term tests to detect
shaft torsional oscillations. Indirect methods of identifying sub synchronous resonance steady-state
instability problems involve monitoring generator electrical terminal quantities. The armature current
.
c. Responsibility for Detection
It should be understood by those utilities that utilize series capacitor compensation, or Have HVDC
transmission in their system, that the potential for damaging torsional vibrations is a consequence of the
special electrical characteristics of the transmission network. It is, therefore, the owner’s responsibility to
implement devices to detect, and protect the machine from, the influences of subsynchronous torsional
interaction. In the case of HVDC transmission lines, the potential for interaction between the HVDC controls
and the turbine-generator rotor system needs to be accounted for in HVDC control design. VATECH HYDRO
has worked closely with many utilities on system studies to define the requirements for protective devices
on particular systems.
In addition, generators that are applied for use in series capacitor compensated systems or systems
containing HVDC transmission are sometimes furnished with pole-face armature windings. The addition of
pole-face armature windings does not necessarily enhance negative sequence capability. The function of
armature windings is to reduce the machine electrical resistance in the sub synchronous frequency range,
which reduces the potential for torsional interaction at sub synchronous frequencies.
d. Recommendation
It is vital that the electric utility work closely with the manufacturer at the planning stage to
a. Description
When a generator is energized three-phase while at standstill or reduced speed, it will behave and
accelerate as an induction motor. The equivalent machine impedance during the high slip interval can be
represented by negative sequence reactance (X2 ) in series with negative sequence resistance (R2). The
machine terminal voltage and current during this interval will be a function of generator, transformer and
system impedances. If the generator-transformer is connected to an infinite system, the machine currents
will be high (several per unit), and conversely, if the unit is connected to a weak system, the machine current
could be low (1–2 per unit). During the period the machine is accelerating, high currents will be induced in
the rotor and the time to damage may be on the order of a few seconds. A number of generators have been
accidentally energized while at standstill or very low speed. While many have survived the experience with
minor damage, others have not.
b. Detection
While there are several generator zone relays that may detect this contingency, their Performance may be
marginal. Therefore, the preferred approach is to provide detection means specifically designed for this
purpose. One such method is to use overcurrent relays that are armed by a speed relay when the generator
is off line.
c. Recommendation
It is recommended that the detection scheme described above be used to protect every generator. To
prevent damage to the rotor, stator bearings, etc., it is desirable that high speed protection be provided for
this contingency. The relaying should be connected to trip the main generator breaker, trip any breakers
which could feed current to the generator if breaker failure is detected, and be so implemented that it is
never taken out of service when the unit is shut down for any purpose, even with the rotor removed.
a. Description
High vibration (as defined below) on a generator is a symptom of a problem. There are
many possible causes of vibration, including:
• Unbalance, • Misalignment
• Thermal sensitivity • Damaged bearings
• Oil whip • Rubbing
• Bent overhangs • Out-of-round journals or collectors
• Stiffness dissymmetry.
c. Recommendation
For both generator and alternator bearings provided with proximity probes, the table below summarizes
recommendations for various levels of shaft vibration. The vibration levels are given in mils [mm], peak-to-
peak, unfiltered. For generators provided with velocity probes which monitor endshield or pedestal Deflection
in the vicinity of the bearing, the alarm level is 0.5 in/sec, and the trip level is 1in/sec.
a. Description
Improper synchronizing of units to the line may occur for a number of reasons. The most Severe of these
results from incorrect connection of potential transformer or synchronizing aids such that gross out-of-phase
synchronizing, such as a 120° error, may occur. A failure of automatic synchronizing equipment may also
result in large synchronizing errors. While turbine-genera-tors are designed to withstand these rare
occurrences without catastrophic results, provided stator current does not exceed the three-phase short
circuit value, they can result in damage, such as slipped couplings, with resulting high vibration, loosened
stator windings, and fatigue damage to the shaft and other mechanical parts Careless synchronizing, w hile
generally a less severe incident, may, on an accumulated basis, have the same result.
b. Detection
A severe out-of-phase synchronizing incident will be evident from the physical effects of Noise and turbine-
generator foundation vibration. In addition, a tripout may result from the Vibration trips or from electrical
protective relays. Poor synchronizing routine is less evident but would be observable by the synchroscope
and an oscillation of electrical quantities (power, VARs) subsequent to the synchronizing.
c. Recommendations
Careful checking of circuits during initial installation or equipment change out and the establishment of well-
adhered-to procedures for manual synchronizing are key elements in minimizing out-of-phase synchronizing
incidents. A Synch Check function should monitor manual synchronizing to prevent large errors Automatic
synchronizing relays can provide very high accuracy. Where such relays are used, however, it is important
that a check function be applied to provide an independent back-up. Failure of the primary relays to perform
should be alarmed, since this might otherwise not be noticed.
a. Description
Motoring of a generator will occur when turbine output is reduced such that it develops less than no-load
losses while the generator is still on line. Assuming excitation is sufficient, the generator will operate as a
synchronous motor driving the turbine. The generator will not be harmed by synchronous motoring, but, if it
occurs as a result of failure to complete a sequential trip, protection for the fault originating that trip is lost.
In addition, a steam turbine can be harmed through overheating during synchronous motoring.If field
excitation is lost, along with turbine output, the generator will run as an induction motor, driving the turbine.
In addition to possible harm to the turbine, this will produce slip-frequency currents in the rotor and could
cause it to overheat if continued long enough.A third type of motoring occurs when the generator is
accidentally energized when at low speed. This is discussed separately under “Accidental Energization”.
b. Detection
Motoring following loss of turbine output can be detected with a reverse power relay. To Avoid false trips
due to power swings, a time-delay pick-up of 10 to 30 seconds is suggested. This is the backup relay
suggested in the description of Trip 4 – sequential trip. Measurement of very low pow er levels at very low
power factors will require relatively high precision. Reduction in reactive power flow in the generator will
reduce the requirement for high precision. This may be accomplished through control action of the excitation
system or by operator action.
c. Recommendation
It is recommended that the reverse power relay referred to above be used and connected to produce a Type
1, simultaneous trip. Alternatively, a Type 2 generator trip or Type 3 breaker trip could be used. Breaker
Failure Protection should be initiated, since line breaker failure may be the cause of the motoring.
a. Description
Stator overheating may result from over current operation, improper gas pressure or purity (if applicable),
gas or water cooling system malfunction, internal cooling passage blockage, etc.
b. Detection
Armature bar temperatures are monitored by either TCs measuring stator cooling water temperature and/or
RTD’s in the stator slots (if applicable). All functioning RTDs and TCs should be constantly monitored and
alarmed As pointed out in the stator overcurrent section, these temperature detectors do not provide
complete protection against damage due to overcurrent operation, because temperatures in other parts of
the winding, winding forces, abnormal magnetic fields, etc. may become excessive.
c. Recommendation
Automatic shutdown is not always provided for protection against stator overheating on generators with
conventionally cooled stator windings. All operators should be made aware of the importance of operating
the generator within its rated capability. In cases where a generator will operate in an unattended station,
some form of overtemperature protection should be provided. Implementation of an automatic stator
overtemperature protection scheme also provides some overcurrent protection, and is generally easier to
implement than overcurrent relaying.
a. Description
Before synchronization, there are at least tw o areas of possible overheating in the generator which are a
function of field excitation:
• Stator core heating, which is related to the stator flux (volts/Hertz)
• Generator field heating, which is related to field current.
After synchronization, in addition to these two, there is also the possibility of stator win Ding heating
(including end windings, connection rings, leads, and high voltage bushings), which is related to armature
current. Local overheating can be caused in a number of ways. One is damage to the laminations at the
inner diameter of the stator core. This might cause electrical contact between laminations leading to a flow
of current and therefore heating. This type of damage may be caused by a foreign object striking the core
under the influence of electromagnetic forces in the machine. Overheating may also be caused by improper
cooling or by faulty or damaged insulation, allowing excessive leakage current to flow. It can also be caused
by operating outside the capability limits, especially in underexcited regions.
b. Detection
On hydrogen-cooled steam turbine-generators, overheating can be detected by the use of the Generator
Gas Monitoring System (GGMS). The GGMS consists of a generator Core Monitor, a Signal Validation
Control and a Pyrolysate Collector. The generator Core Monitor is an ionization-type particulate detector
that is connected to the generator so that a constant flow of cooling gas passes through it. The cooling gas
is monitored for the presence of submicron particles (particulates). Under normal conditions, the gas coolant
contains no particulates that can be detected by the monitor. When overheating occurs, the thermal
decomposition of organic material, epoxy paint, core lamination enamel or other insulating materials
produces a large number of particulates which can be detected by the monitor to produce an alarm. The
particulates can be collected by the Pyrolysate Collector which is designed to operate when a generator
Core Monitor alarm occurs. Confirmation of overheating may be accomplished by laboratory analysis of the
particulates.
The Validation Control is used to automatically discriminate between a Core Monitor alarm caused by an
instrument malfunction and one caused by local overheating. When the alarm is verified, the Validation
Control actuates a machine heating alarm.
c. Recommendation
When a machine heating alarm occurs, load should be reduced by manual runback (Type
8) until the alarm signal clears. If the alarm signal does not clear within five minutes the
generator should be tripped manually (Type 5). Contacts are provided in the Validation Control which can
be used to actuate runback or trip circuits if this feature is desired.
Directional Relay Comparing the direction of current flow in the line with reference to the bus voltage.
In other words the direction relay measures the phase angle between voltage & current vector. Relays
gets voltage from bus Pt and current from line CT. Directional O/C relay operates only when the current
flowing through the relay is more then plug setting and also current flowing in current (operative)
direction.
Directional Over Current & Directional Earth Fault relay:- (67R/Y/B & 67N)
67R/Y/B directional over current relay current coil connected in secondaries of related line CT. Current
coil of directional E/F relay (67N) is residually connected. The potential coil of 67R is connected across
Y & B phase of bus PT secondary. Similar that 67Y connected across R & B and 67B connected across R
& Y phase. Phase advancing resistance (not shown) is in built with potential connected of relay. Potential
coil of Directional E/F (67N) relay is connected across open delta of intermediate voltage transformer
(IVT). IVT having a ratio 110/√3 = 110/3 will give voltage 3Vο/3 = Vο (Zero Sequence Voltage) across
open delta.
67N Relay is fed with residual current voltage (i.e. open delta voltage VR+VY+VB) is zero under normal
condition and during fault (L-L-L & L-L). In case of ground fault (L-g) the residual voltage is equal to
depression of voltage in faulted phase for solidly earthed system. This voltage causes the E/F relay to
operate.
The operating principle of busbar differential is hired on kirchoff’s low. The algebraic sum of all the
current entering and leaving the busbar zone must be zero, unless there is a fault there in. In this case
I/C current sum= O/G current sum= 0. To avoid Ct saturation high impendence relay is used. For fault
in bus section sum of the current as seen by CTs will no longer be zero. The corresponding zone will
operate and check zone also operate. To avoid a malfunction check zone operation is added with the
operation of individual bus section zone.
It is an over current relay connected in generator winding. If there is an over current beyond the rated
current of generator because of over loading it will be actuated through heating characteristic of
generator.
If there is unbalance in current vector in generator phase due to unbalance loading or fault in any phase,
it will induce double frequency eddy current in rotor. These current is allow to persist can cause over
heating of rotor. So the purpose of negative phase sequence is to disconnect the generator from grid
before such excess temp is reached.
Unbalance loading or fault in any phase will unbalance the stator current. In one phase it
will be high where as other phase it will be low or medium.
Normal over current relay is not used to detect such over voltage because with unbalance
load, load current may go high or some time beyond the full load current. That’s why negative sequence
relay is used to detect such fault (Unbalance loading or fault in any phase).
This relay detects two & three phase short circuit between the zone of Generator terminal and unit
Transformer (21G2) and beyond the above zone up to Grid (21G1) by the method of impedance.
Conventional method of detecting it by over current relay is not safe because of time lag response of
O/C relay. In this method where impedance between Generator terminal and unit Transformer and
above the zone is only measured, is suitable & prompt. The time log of this relay is very short (500ms)
and impedance of the graduation of the distance protection of the system.
21G1 relay measure the impedance Z1 = V/I = 3Ω/phase from the generator neutral side. If
any fault occurs between generator winding and 400KV Bus measure impedance will be less then
3Ω/phaseand operating points came under 21G1 relay circle. Thus it sets actuated and initiated class-
C protection.
21G2 relay measure the impedance Z2=V/I = 1.72Ω/phase between generator terminal and
unit transformer. If any fault occurs in this zone impedance by 21G2 relay will be less than 1.72Ω/phase.
This operating point enters into 21G2 circles and actuates class-A protection.
Relay current IN = 5A
Pick Up value = V/I = 0.5 to 5Ω/phase.
Time Log = T = 0.5 to 5 Sec.
7. Gen. Stator E/F : (i) 95% (ii) Standby (ii) 100 % (64G / 51NG / 64G1)
If there is E/F occurs in any stator winding leakage current will starting flowing through NGT. The
intensity of leakage current will be dependent on the % of stator coil. If E/F is between 0 to 95% wdg
leakage current will be high. To detect by normal relay, but it is between 95 to 100 % due to less
intensity of leakage current special provision of injection transformer has been arranged to detect it.
In Reliance 95% E/F measured by Ct which is located in NGT secondary side and 100% E/F measured
by third harmonic voltage from NGT secondary side voltage.
If 1st E/F occurs in field winding small earth leakage current will circulate between stator earth and
winding earth. As leakage current is very small - it will not create any major abnormality in generator
operation. Except following mild effect.
1. Slight increase in field current.
2. Vibration in bearing may so high.
But in case of second E/F in rotor due to lower resistive path, field current will start flowing between
two earth (1st & 2nd earth) by passing in between field winding. If some part of field is bypassed due to
2nd E/F, flux gap will form in rotor – which inturn produce abnormal flux distribution in the stator winding.
This will cause -----
--- (i) Heavy vibration
(ii) Distorted phase current in stator (abnormal current – No signwave)
(iii) Pole sleep
(iv) High field current and abnormal temp rise in rotor.
1st E/F is not harmful but second E/F is very danger. Second E/F relay actuate to trip the unit trough
class-A protection. Standard rotor IR value should be greater than 70 MΩ. If it is less than 5 MΩ E/F
relay will act.
Loss of field supply to a synchronous generator can be caused by – following reason a) A fault in
excitation system
b) Incorrect opening of field breaker. (F.B)
Following effect observed in case of loss of excitation
a) Machine will operate as an induction generator drawing reactive power from grid.
b) Instability in grid. c) Abnormal rotor heating
When loss of excitation occurs – The machine begins to draw reactive power from the grid. This property
is used for detecting loss of excitation by measuring impedance at generator terminal.
The relay is offset impedance type measuring MHO at the generator terminal. In case of loss of
excitation, generator impedance falls within the tripping zone and relay will actuate.
When ever there is a power swing in the grid, MVAR may be imported from the grid through the
excitation is alive. (ie. In case of pole slip and loss of synchronism) in such case generator impedance
falls momentarily in this zone. However, by time integrator it is possible to ensure that despite
intermittent pick-up a definite trip command is imparted by the protective relay. This impedance relay
can be made offset type by varying point A & B with relay adjustment. Pick-up at A (%) = (87.5/S1 x
d) k
Pick-up at B (%) = (8.75/S2 x d’) k,
S1 = 1 & S2 = 0.5 for turbo generator.
When ever Earth Fault occurs (within the winding or out side the winding) zero sequence current will
pass through the neutral. If the fault is located outside the winding, only 51N will set actuated and
initiated class-C protection.
Over current protection at HV side of generator transformer has been provided. If it sets actuated on
O/C class-A protection will be initiated.
In a transformer E/F may occurs outside or inside the winding. When the fault (E/F or short ckt) occurs
out side the winding, it will detect by sensing O/C at HV side through IDMT relay. This type of fault
detection is known as unrestricted – because IDMT (O/C) will act where ever the fault is (inside, outside
or in the load). In such case IDMT sensing should be more than over current limit and less than short
ckt limit.
For detecting E/F within winding of high rating transformer (1600KVA onwards) Restricted
E/F method is used at star side of the winding.
Fault at F1 (out side of wdg) increased resultant current in CT’s which is neutralized
by zero sequence current in neutral. Thus 64RGT will not have any operating current. But when fault
occurs at F2 (within the wdg) only zero sequence current through neutral will operate the relay, because
resultant CT current will be more and less zero. Thus 64RGT sets actuated only when fault occurs within
the winding and actuate class-A protection.
Normally V/f ratio = V/f = 110 /50 = 2.1, if because of any reason over fluxing occurs and V/f ratio
cross the limit point – following operation are carried out in SES panel automatically.
a) To change AVR from Auto to manual
b) To restrict the raise excitation impulse in manual mode.
c) To reduce excitation in manual mode.
All the Operation carried out automatically to restrict the raise of voltage – so that V/f ratio is within
limit. If after these operations excitation control fails to maintain V/f ratio – unit will trip on class-A
protection. For this protection (relay – 61GT1/GT2) voltage is taken from VT (PT=110V) and frequency
is taken from m/c.
The Flux density in the core depends on the ratio of terminal voltage (V) divided by the freq (f).
Normally the over fluxing withstands characteristics of the transformer are:--
120% over fluxing for 2 minutes
135% over fluxing for 1 minute
140% over fluxing for 5 seconds.
If generator breaker fails to trip on protection, LBB will come into service to energies BUSBAR protection
relay of all the elements (Breaker) connected to the bus to which generator is connected and actuated
class A protection. As long as power flow is there- 50LBB contactor is in picked up condition. Suppose
unit got tripped on protection and generator breaker did not trip – in such case timer T will start
energizing through master trip relay contact and 50LBB contact 9Becouse power flow in these for not
operating the generator breaker) after 200ms timer will energize tripping relay of all connected elements
to trip particular breaker.
16. Reverse Power and Low Forward Power Relay : ( 32R & 32F)
This s basically protection provided for prime mover (Turbine). When a turbo generator is shut down
in an emergency there is a risk of over speeding if the GB (Gen Bkr) open before the steam / fuel stop
valve is completely closed. Even if both action are simultaneous steam / fuel trapped in the casing
may be sufficient to cause over speeding. To avoid that Reverse power relay is used. In reverse power
generator drawing active power from grid. Generator is not designed for motoring action it should be
immediately tripped when the steam / fuel valve / flow is stopped and to avoid damage to the turbine.
In actual Generator reverse power setting for steam turbine 2% And For GT 3 to 5%.
• Purpose of Directional inverse Over current & earth fault relay; type- CDD
Directional phase or earth fault protection of ring-mains, parallel transformers,
transformer feeders, parallel feeders etc., employing the time graded principle.; This
relay comprises an inductive disc over current unit with wound shading coils and a
directional high speed induction cup unit. The cup-unit contact is wired across the
shading coils so that no torque is exerted on the disc of the over current unit until the
cup unit contact closes. The inductive disc unit is thus directionally controlled and it
operates only when the current flows in the tripping direction. The directional unit is
a high speed, low inertia four pole induction cup movement designed to give a high,
steady and non-vibrating torque. its current coil is connected in series with the
operating coil of the induction disc unit. The directional unit is normally provided
with voltage polarizing coils.
• Purpose of definite time Over current & earth fault relay: Type-CTU
This relay can be used for definite time over current protection against phase and
Earth faults on medium and low voltage distribution systems. The definite time relay
offers a considerable advantage over inverse time relays in instances where there ia a
wide variation in line impedance. Another application is in the field of stalling protection of motors.
When the thermal overload relay does not provide protection
against stalling, separate definite time O/C relay type CTU can be used to provide
the same. This relay comes in following nomenclature: CTU-12/22/32/52/62/15.
CTU relay combines the advantage of complete static measurements with characteristic of the robust,
well proved attracted armature unit. These relays measure current and time accurately, imposes low
burden on CT's. Each phase comprises a static overload detector and timer, which is accurate over a
10:1 time setting range. When the positive peak of the input signal exceeds the reference level, the
time delay circuit starts and after a preset time, drives the output relay. Instantaneous high set unit
when fitted uses alternate half cycle for measurement and through a separate level detector drives a
separate output relay.
• Purpose of Over fluxing Relay: Type-GTTM
o Authorized engineer will accept the Electrical work permit along with the lock out key
o Ensure the correct Generator is identified in the field.
o Ensure LOTO system is followed and collect the keys from Electrical operation.
o Confirm the isolation of Generator at 33 kV breaker end, starting motor and ratchet motor (turning
gear / baring motor)
o Ensure that 11kV cable at GAC end is earthed.
o Ensure that the transformer discharged and kept earthed at both the sides.
• Generator
3 Measure Generator IR Value with and without surge Ok/Not Ok-Surge arrestor to
arrestor and Capacitor ( 2.5 kV- 1 Min ) ground O/V due to switching /
With Surge arrestor & capacitor min value- >15 M lightning surge. And Capacitor
ohms to reduce high freq signal.
W/o surge arrestor & capacitor min value- > 250M
ohms
4 Measure the Rotor IR value with diode bridge ( by 100 Ok/Not Ok
V ) Min value->20 M ohms
5 Measure the main Exciter Field and PMG stator IR Ok/Not Ok
and WR value
1. Clean the Generator air duct chamber and remove any accumulated oil
2. Inspection of the space heater for any damage.
3. Check the space heater for IR value and give clearance to operation for switching on and
keep that in on condition.
4. Remove the carbon brush holders on shaft for both DE and NDE side of the generator.
5. Measure initial IR value of Generator Rotor, stator and PMG stator for reference
6. Noting down the connection details of PMG, Q-axis, rotor earth fault, RTD, and other JB
terminations, with details of ferrule number and colour code.
7. Remove and kept secure this connection leads.
8. Open the Generator side flexible connection of 11kV bus bar.
9. Take the meggar value and PI value of the generator.
10. Measure the meggar value and PI of Main generator stator daily during shut down.
11. Measure the Exciter air gaps before dismantling of Exciter rotor and stator.
AIR GAP Between Stator & Rotor = 20–25mm, Exciter =10-15mm, PMG= 5-8mm
19. Before installing the rotor of exciter, make sure that, the silver contacts of rotor winding are
in position.
20. After exciter rotor is fixed and before exciter stator installed, cover the rotor portion with thick
insulation paper for protection from any mechanical.
21. After exciter stator is installed, remove the paper from air gap.
For assessing the healthiness and condition of the Generator and to find out any preventive steps
to be taken, during or in the future shutdowns, a set of diagnostic tests are done on the generator
as detailed below.
These are done by engaging testing agencies, who analyze and gives recommendations.
Generally the following tests are carried out during the overhauling.
1. DC Absorption on stator.
2. Measurement of Capacitance & Tan delta on stator.
3. Recording of PD on stator.
4. Study of Non-linear Behavior of winding Insulation on stator.
5. Measurement of winding resistance of stator.
6. Checking of RTD's of stator.
7. Wedge mapping using deflection method suitable for ripple spring wedges on stator-after
threading out the generator rotor
8. Microscopic & Endoscopic Inspection – After threading out the generator rotor
9. Visual Inspection of generator Stator & rotor, exciter stator & rotor
10. Measurement of winding resistance of rotor
11. Measurement of impedance of generator rotor
12. Recurrent surge oscillograph
13. Measurement of Impedance, winding resistance and IR of exciter stator
14. Measurement of Impedance, winding resistance and IR of exciter rotor
15. Diode and fuse checking 16. RTD checking
• Job closure
Introduction
We have 8 numbers of Refinery Service Transformers (RSTs) of M/s ABB Make in JERP CPP, which
interconnect the 220 KV switchyard and the GIS 33kV switchboards. The details of the transformers are
220/34.5/11 KV, 174 MVA and YNyn0d11.
Purpose
This document deals with the different types of checks, inspections and other maintenance activities,
which are to be carried out for the transformers.
Scope
This document is applicable for the periodic maintenance of the transformers installed in MRS 1 and
MRS 2.
For any major maintenance activities to be carried out on transformers, manufactures operation and
maintenance manual shall be referred.
References
1. Operation and Maintenance manual of M/S ABB.
Operation and maintenance manual of M/S MR make On Load Tap Changer
Oil testing specifications procedure as per IS 1866
Oil Quality specifications as per IS 335
Safety
Before carrying out any job on the transformer, obtain PTW & Barricade the area.
Ensure the 220 KV-side Breaker and Isolator are kept open and the earth switch is on and tagged.
Ensure the 33kV side breaker is opened. Isolator is in earth position
Ensure the transformer is discharged after de-energising and discharge rods are kept connected at
transformer terminals throughout the job.
Ensure all PPE and safety belts are available and proper use of the same by the persons carrying out
the job.
Conduct ‘toolbox talk’ to the persons doing the job.
Procedure
The maintenance of the transformer includes regular condition monitoring, shutdown maintenance and
any major maintenance activities.
Following items are to be checked along with the periodic maintenance of transformers. For any
major maintenance activities, MR’s operation and maintenance manual shall be referred.
1. Tightness of sealings of the tap changer head, the protective relay and pipe connections to be
done.
2. Tightness of the motor drive housing.
3. Tightness of all electrical connections, cleanliness of the TB’s also to be checked, if required same
is to be tightened.
4. Proper setting and connection of the electrical space heater in the motor unit.
5. The appearances of the control appliances in the motor drive unit.
6. The oil level in the motor drive gear box.
7. Quality of the oil in the diverter switch.
8. Oil quality shall be increased, by fresh oil replacement, if the BDV is found to be less than 60 V.
9. Preventive maintenance of the motor.
10. Examine the silica gel breather and re activate if necessary.
11. Monsoon protection of the control/driving cubicle.
Following maintenance activities are to be carried out during the yearly shut down.
1. RTCC panel to be opened and remove the dust using the vacuum cleaner.
2. Tightness of all control wiring and fuses.
3. Healthiness of all the indication lamps.
4. Operation of the tap changer (from remote and local) and after the checking bring it back to normal.
5. Tap changer position indicator in RTCC shall be checked.
6. Connection and setting of the space heater.
7. Vermin proofing of the panel.
8. Flexi separator commissioning
Introduction
JERP switchyard has 4 numbers of capacitor voltage transformers, which are having application of
metering, synchronizing and protections. These CVTs are of M/S AREVA make.
Purpose
This document describes various checks, which shall be carried out during maintenance of CVTs.
Scope
This document is applicable for the maintenance of CVTs installed in switchyard.
The manufacturer’s manual for CVT shall be referred to for any major jobs, which can occur for these
instruments.
Reference. Installation and maintenance manual for CVTs of M/S.
Safety
1. Before carrying out any job on CVTs, obtain the electrical PTW.
2. Ensure that, CVT is isolated ,de-energized & discharged.
3. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
4. Proper ‘toolbox talk’ to the persons doing the job.
5. Barricade the working area around the CVT under maintenance from other yard equipment/Bays,
which could be live.
6. No person shall carry ladders or any such long poles etc. to switch yard, unless specifically
instructed.
7. Procedure
General inspection includes checking for any oil leakage, dust accumulation, and healthiness of oil level.
Inspection checks during PM:
The following maintenance aspects shall be looked into while doing the maint. of CVTs.
1. Inspection for any cracks in HV bushings.
2. Inspection for any oil leakage.
3. Inspection of the healthiness of rubber gaskets.
4. Cleaning of the CVT capacitor stacks and tightness of terminal connections, ensure that, the jumpers
are tightly connected to the primary terminals of CVT.
5. Inspection of the neutral earthing in CVT marshalling box and tighten all connections.
6. Cleaning of marshalling box & junction box.
7. Check for secondary fuses and if required replace the same.
8. Check for the earthing connection firmness.
Note - The units are hermetically sealed hence oil does not deteriorate in service. So in no case oil
sample should be drawn for testing the di electric strength.
Note - The units are hermetically sealed hence oil does not deteriorate in service. So in no case oil
sample should be drawn for testing the di electric strength.
Introduction
We have many HT motors installed in CPP
Purpose
This document describes the different checks and step by step procedures, which shall be carried out
for the preventive maintenance of HT motors
Scope
This document is applicable for all the HT motors
Reference
1. Operation and maintenance manual for motors of M/S ABB/SIEMENS/Hyundai
2. Operation & maintenance manual of switchboard & breakers of M/s Siemens.
3. Check sheet for Motor maint. No.
Safety
1. Before carrying out any job on motor, obtain electrical PTW.
2. Ensure that Switch gear for particular motor is de-energized, discharged and isolated.
3. Verification of safe isolation from supply: The panels are equipped with position of the breakers i.e.
service/test positions
4. The breaker should be in test position & plug disconnected.
5. Control supply should also be disconnected by means of fuse removal.
6. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
7. Proper ‘toolbox talk’ to the persons doing the job.
8. Ensure proper use of tools.
9. Barricade the working area around the motor under maintenance from other equipment, which could
be live
DANGER
Baricate adjacent live equipments
Residual charge could be present in the cables or motor windings. Make sure to discharge them by
means of earthing rod.
Pl. make sure the panel no. before opening cable chamber as it could lead to severe accidents.
Before placing earthing rod for discharging be sure for no live part or voltage on the cable to be
discharged by non contact type voltage detector.
Procedure
Following aspects of maintenance shall be looked into, while carrying out the general maintenance of
the HT motor.
Before going to the field pl. make sure the breaker is isolated, control plug is disconnected & panel
door is locked out.
21. For grease lubricated motors check lubrication nipple for bearing is clean and not clogged.,closed
with cap.
22. For Hyundai motors sevogem 2 or silvania RL2
For Siemens motors shell alvania RL3
23. Remove the cap & do greesing of the motor if required if possible by rotating the shaft by hand. Cap
the nipple again.
24. Clean Motor body thoroughly.
25. Check motor bearing temperature indicator indicating reading near to ambient.
26. Check Motor IR Value with 2.5 KV Meggar between PH – E & PH – PH (winding star point isolated )
and also measure winding resistance& inductance and record them in check sheet (By EMcElectric
Motor Checker) or LCRM Meter (Indu cap & Resi.)
After completion of job ensure that all waste material has been positively removed from site and site
is clean.
Introduction
We have nos of SF6 circuit breakers of M/S Siemens make installed in JERP switchyard.
The details of the circuit breakers are 245 KV, 3150 Amps, 40 KA and 3AP1F1 type.
Purpose
This document describes various types of checks, which shall be carried out during the preventive
maintenance of SF6 circuit breakers.
Scope
This document is applicable for the preventive maintenance of all the SF6 insulated 245kV rated outdoor
duty circuit breakers in the switchyard. The operation and maintenance manual of circuit brakers shall
be referred to for any major overhauling of the circuit breakers.
References
Operation and maintenance manual for the 245kV SF6 of circuit breaker: - M/S SIEMENS
Safety
1. Before carrying out any job on Circuit Breakers, obtain electrical PTW.
2. Ensure that, both ends of the Breaker are isolated, de-energized, discharged and kept earthed.
3. Control and heating supply must be switched off.
4. Ensure all PPE and safety belts are available and proper use of the same by the personal carrying
out the job.
5. Proper ‘toolbox talk’ to the persons doing the job.
6. Barricade the working area around the circuit breaker under maintenance from other yard
equipment/Bays, which are live.
7. No person should carry any ladder or any such long poles inside the switchyard, without the
instructions.
Procedure.
Following activities are done during the preventive maintenance of SF6, as per the check sheet
ZCPP/ELE/4009
1. Thorough cleaning of the CB shall be made.
2. Power conductor tightness shall be checked.
3. Breaker cubical all control connection to tighten.
4. Breaker ON/OFF operations shall be checked from both remote and local.
5. Spring charging indication to be check.
6. SF6 level/pressure shall be checked.
7. Record the meggar value of breaker poles.
8. Trip coil and close coil resistance shall be measured and recorded.
9. Breaker contact resistance shall be measured.
10. Closing time and tripping time of the breaker shall be measured and recorded.
Check sheet
Refer check sheet ZCPP/ELE/4010 for the preventive maintenance of SF6 circuit breakers.
Introduction
We have isolators of 1250A (bay isolator) and 2500A (main bus isolator) capacity of M/S SIEMENS make
installed in JERP switchyard. All the isolators are of horizontal, center break, gang operated isolators.
Safety
Before carrying out any job on isolators, obtain electrical PTW.
1. Ensure that, both ends of the isolator are de-energized, discharged and kept earthed.
2. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
3. Proper ‘toolbox talk’ to the persons doing the job.
4. Ensure proper use of tools.
5. Barricade the working area around the isolator under maintenance from other yard equipment/Bays,
which could be live.
6. No person should carry any ladder or any such long poles to the switchyard, unless instructed
specifically.
Procedure
Following aspects of maintenance shall be looked into, while carrying out the general maintenance of
the isolators.
• Operating Mechanism
1. Maintenance of linkages including transmission gears.
2. Maintenance of stopper bolts.
3. Cleaning of the auxiliary switch contacts and grease with silicon grease.
4. Electrical and Mechanical interlock with earth switch and Isolator.
5. Lubrication of the operating mechanism hinges, lock joints, on levers and bearings shall be done.
6. Tightness of all mounting bolts shall be done.
7. Movement and alignment of all arms for simultaneous operation shall be verified.
8. Ensure proper interlock indications with the EDMS panel.
• Main Contacts.
1. Cleaning and lubrication of all main Contacts.
2. Alignment of structure with respect to the contacts and uniformity of the movement of arms shall
be attended if required.
3. Tightness of all bolts, nuts, pins etc.
4. Cleaning of the support insulators and checking for cracks in insulators, if any.
5. Measuring of the contact resistance of all three phases, and shall be less than 300 micro Ohms.
• Earth Switches.
Alignment of earthing blades.
Contact cleaning.
Check the operation of earth switches.
Check the earth connection of structure and marshalling box.
• Marshalling boxes of Isolators and earth switches.
Visual check of auxiliary contacts and ensure contact healthiness
Cleaning and checking of the terminal tightness in marshalling box.
Tightening Torque for the various assemblies and subassemblies.
For M10 bolt 19Nm
For M12 bolts 33Nm
Introduction
The lightning arrestors are used for limiting the surge voltages to a safe value by discharging the surge
current to ground. We have 84 nos. of lightning arrestors in JERP 220 KV switchyard. In any one
phase, there are two individual stacks of rating 120 KV and 78 kV installed one above the other. These
lightning arresters are manufactured by M/S Crompton.
Purpose
This document describes various checks, which shall be carried out during the periodic maintenance of
lightning arrestors.
Scope
This document is applicable for the periodical maintenance of lightning arrestors, installed in JERP 220
KV switchyard.
Reference
The manufacturers (of M/S Elpro international Ltd) O&M manual shall be referred to for any major jobs
on Lightning arrestors.
Safety
1. Before carrying out any job on LAs, take electrical PTW.
2. Ensure that LA is discharged.
3. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
4. Proper ‘toolbox talk’ to the persons doing the job.
5. Barricade the working area around the LA under maintenance from other yard equipment/Bays,
which could be live.
6. Keep a temporary earthing on the line.
7. Before returning the permit after completion of the job, remove the temporary earthing.
8. No person shall carry any ladder or any such long poles in the switchyard, unless specifically
instructed.
Procedure
The following maintenance aspects of LA shall be looked into while doing the maintenance of lightning
arrestors.
1. Visual inspection shall be done for any cracks on insulator surface and any flash over at the vent.
2. Cleaning the insulator of LA stack.
3. The power conductor connection tightness shall be checked.
4. Stack to stack bolt tightness checking shall be done.
5. Ensure proper alignment of LAs.
6. Ensure earthing connection tightness.
7. Inspect discharge counter for any physical damage and Earth link continuity at the discharge
counter.
8. Record the IR value the entire stack using 5kV meggar.
9. Record the leakage current of the monitor. (Compare reading of the leakage current with that of
the latest reading taken during condition monitoring. If the leakage current is found to be double of
that value, clean the arrester housing. The leakage current again is to be noted after charging. If it is
still on higher side, replace the arrester at the earliest opportunity).
10. Ensure monsoon protection of leakage current monitor.
11. Ensure earth connectivity to Earth pit/ Ground is ok.
12. Remove all material, tools, men and temporary earthing.
13. Return the electrical PTW.
Introduction
We have 2 numbers of 38MVA Distribution transformer of M/s ABB Make in JERP CPP, which interconnect
the MRS board’s supply at 33KV to the 11 KV STG output terminals. The details of the transformers are
33/11 KV, 38 MVA and YNd11.
Purpose
This document deals with the different types of checks, inspections and other maintenance activities,
which are to be carried out for the transformers.
Scope
This document is applicable for the periodic maintenance of the transformers installed in STG area.
For any major maintenance activities to be carried out on transformers, manufactures operation and
maintenance manual shall be referred.
References.
1. Operation and Maintenance manual of M/S ABB.
Oil testing specifications procedure as per IS 1866
Oil Quality specifications as per IS 335
Safety
1. Before carrying out any job on the transformer, obtain PTW & Barricade the area.
2. Ensure the 33 KV-side Breaker is kept open and the earth switch is on and tagged.
3. Ensure the transformer is discharged after de-energising and discharge rods are kept connected at
transformer terminals throughout the job.
4. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
5. Conduct ‘toolbox talk’ to the persons doing the job.
Procedure
The maintenance of the transformer includes regular condition monitoring, shutdown maintenance and
any major maintenance activities.
Condition monitoring of transformers.
The major items to be checked during normal operation of transformers are as per the check list.
Preventive maintenance
Apart from condition monitoring of transformer, preventive maintenance is also done for the grid
transformers. The frequency of this transformer preventive maintenance is fixed as decided by CES.
The check points during the preventive maintenance of these transformers are as per the check sheet.
General: Transformer tank, cover, bushings and other parts should be inspected periodically for any
oil leakage, peeling of paint or rust formation. Rusted portion should be properly cleaned and painted.
Oil leakages should be immediately attended to. Clamping bolts on gasketed joints should be tightened
properly and if necessary gaskets should be replaced.
Check sheets
Refer following check sheet for carrying out the preventive maintenance of the transformer.
Technical details
220 KV Terminations:
Surge Arrester:
Purpose
This document describes the different checks and step by step procedures, which shall be carried out
for the terminal of the 220 KV cable
Scope
This document is applicable for the entire 220KV cable terminal in JERP
Manufacturer’s manual (of M/S SAUDI CABLES) for the terminals of 220 kV shall be referred for any
major activities or overhauling.
Reference
Termination catalog of M/S SAUDI CABLES.
Safety
1. Before carrying out any job on 220 kV CABLE, obtain electrical PTW.
2. Ensure that, Cable is de-energized, discharged and kept earthed.
3. Verification of safe isolation from supply
4. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
5. Proper ‘toolbox talk’ to the persons doing the job.
6. Ensure proper use of tools.
7. Barricade the working area around the switchgear under maintenance from other equipment, which
could be live.
8. Do not enter with ladder or any other equipment which has long extension unless and until it is
required and have permitted to enter those equipments.
Procedure
Following aspects of maintenance shall be looked into, while carrying out the general maintenance of
the 220 KV terminals. It includes check for any oil leakage, dust accumulation on the insulator.
Note - The units are hermetically sealed hence oil does not deteriorate in service. So in no case oil
sample should be drawn for testing the dielectric strength.
Introduction
We have highmast lighting system of M/S make in the switchyard. These highmasts are providing
lighting to the switchyard as well as function as a shielding from lightning for the switchyard.
Purpose
This document describes different types of checks, which shall be carried out during the periodic
maintenance of lighting highmasts.
Safety
1. Before carrying out any job on lighting highmast, obtain electrical PTW.
2. Ensure all PPE and safety belts are available and proper use of the same by the persons carrying
out the job.
3. Proper ‘toolbox talk’ to the persons doing the job.
4. Ensure proper use of tools.
5. No person shall carry any ladder or long poles into switchyard unless specifically instructed.
Procedure:--
The following maintenance aspects shall be considered while doing maintenance of the lighting
highmasts.
1. Open the terminal cover at the base of the highmast.
2. After opening the cover check the condition of plug and socket for any burning/heating.
3. Inspect the Level / condition of gear oil.
4. Put the rester.
5. Put the gear properly on the raising/lowering arrangement of the highmast.
6. Put torque gear to the power tool and fix it to the gear.
7. Check the alignment and tie it to the highmast.
8. Put starter plug to the highmast socket and place the starter softly on ground, little away from the
highmast.
9. Ensure that both plug top of the highmast are not at the same level.
10. Start lowering the mast and after completely lowering the highmast, ensure that the highmast is
just resting on the rester.
11. Remove the plug top of the starter.
12. Open both the highmast JBs on the lantern carriage and check the condition of the circuit by
meggaring.
13. Check the individual ckt and Identify & rectify the fault in the circuit and fitting, if any.
14. Ensure cleanliness of all fittings and provide monsoon protection.
15. Check the condition of wire rope ferrules and if required replace it.
16. Check the condition of the wire rope for any mechanical damage.
17. Before raising the lantern check that power cable is free from the rope.
18. Start raising the lantern carriage and ensure that lantern is sitting properly in its position.
19. Check the level of the lantern from distance and if level is not ok, adjust the level manually.
20. Ensure the highmast gear is latched properly.
21. Put both the plug top of the highmast.
22. Check the condition of power JB and check for any looseness. Rectify the same, if any.
23. Provide monsoon protection to the power JB.
24. Ensure that the highmast earthing is in good condition.
Is there any relation of CT saturation with frequency variation. If yes what is the +/- frequency range.
Ans- A CT by design and theory would attempt to balance the Ampere turns (AT). That is, if it is a 200 / 1 A CT then
with 200 A in the primary, it will give 1 A in the secondary.
To enable 1 A in the CT secondary , the core should be capable of developing the required voltage at the secondary
terminal = 1 x (Ct resistance + lead resistance + burden) and proportionally higher voltage during fault condition.
The voltage generated is proportional to the Flux(Flux density x no. of turns) x frequency. From this equation you can
see that as the frequency is reduced the generated voltage is reduced. But to maintain the AT balance, the CT would
like to maintain the same secondary current, that is 1 A in this case.
To maintain 1A, we have to maintain the same level of voltage at the CT secondary.
To maintain the same level of voltage the flux has to increase to make up for the decrease in frequency.
If the flux increases, depending on the CT characteristics the core may get saturated.
Normally a protection CT has a very high knee point voltage. Therefore, it would not saturate under normal condition
but may do so under fault condition.
A metering CT has a low knee point voltage. It is possible that some degree of saturation may set in.
With a higher frequency, it is obvious that the CTwould need a lower flux to maintain the same terminal voltage.
However in this case the core loss which is proportonal to the frequency will increase slightly.
There is also an effect of frequency on the burden. In an inductive burden the reactance is proportional to the
frequency. That is, at a higher frequency the inductive part of the burden will increase thereby demanding a higher
CT secondary voltage. Normally the CT burden being predominantly resistive, this phenomenon can be neglected.
The important question however remains at what frequency would the saturation set in. I am not in a position to
answer that straight away. It would depend in the design margin. Normally we specify the electrical instruments to
work satisfactorily within a +/- 10% voltage and +/- 5% frequency margin.
Example:
Load current is A =66 Amps, B= 70 Amps and C= 59 Amps.
Average Current: (66 +70 + 59)/3=65
Maximum deviation from average Current:
(A) 66 – 65 = 1 Amps
(B) 70 – 65 = 5 Amps
(C) 65 – 59 = 6 Amps
Maximum deviation is 6 Amps
The unbalance current in three phase systems can be represented by a set of vectors referred to as the
sequencing components. An example of such is represented in the below example
Primary
cause of
motor failure
is excessive
heating due
to unbalance
current,
which if
sustained
over long
time periods
will result in motor burn out. Over heating also reduces the life of motor. If a motor is continuously
over heated by just10 degrees, its life can get reduced by almost 50%.
Current unbalance in a motor is best represented by the presence of excessive negative sequence
component in the motor current.
Unbalanced currents in a three phase motor can be resolved into three balanced components as
follows
a) Positive Sequence component: This component is in the same phase sequence as that of the motor
current. All its three phases are perfectly balanced - they are equal in magnitude and are displaced by
120 degrees. The positive sequence component epresents the amount of balance in the power supply
and consequently is instrumental in delivering useful power.
b) Negative Sequence component: This component has a phase sequence opposite to that of the
motor current hence the name negative sequence. It represents the amount of unbalance in the
c) Zero Sequence components: This, if present, represents extent of earth fault in the feeder. All its
three phases are in the same direction.
During current unbalance, negative sequence currents flow through the stator windings. This results
in induction of negative sequence voltage in the rotor windings. Since the rotor is short circuited, this
will result in abnormal current flow in the rotor and damage the rotor winding. A voltage unbalance of
the order of 3% can increase the heating by nearly 20% in the rotor.
The negative sequence impedance of the motor is approximately same as the locked rotor impedance
which in turn is approximately one sixth of normal motor impedance. Due to this even small voltage
unbalance can produce large negative sequence current in the motor.
The frequency of the negative sequence current induced in the rotor will be equal to (supply
frequency) x (2-slip) Hz. This is due to the fact that it is revolving in the opposite direction. This
frequency will be typically around 99 Hz during normal motor operation. Due to skin effect, high
frequency negative sequence currents encounter high rotor resistance. This in turn results in over
heating. The increased resistance is typically 5 times the normal positive sequence resistance.
2. What is torque?
Whenever a current carrying conductor placed in a magnetic field, a mechanical force will be acts upon
that conductor and the conductor tends to rotate, if it is arranged freely to rotate. This rotation is due
to the turning or twisting force acted on that conductor. This turning or twisting movement of a force
about an axis is called torque ‘T’. T = force * radius Newton-meter.
Work done per revolution = force * distance covered in one revolution.
∴ Work done per revolution = force * 2πr.
Work done per second = force * 2πr N (r.p.s)
Work done per second = 2π N T (äT = F * r)
So power developed in metric horsepower is equal to force 2πNT/735.5 hp.
14. What are the types starters used for starting of induction motor?
a. Direct on line starter (air break) mechanically.
b. Direct on line starter (air break or oil immersed) electrically.
c. Star delta starter.
d. Slipring motor starter.
e. Auto transformer starter.
26. What are the methods to control the speed of single phase motor?
In AC single-phase motors speed control can not be achieve as smooth as in DC motor. There are
following few methods of speed control.
a. By changing the number of poles of stator. b. By changing the applied voltage to the stator.
c. Frequency control method. d. Rotor rheostat control.
e. By operating two motors in concatenation or cascade or tandem method.
f. By injecting an emf in the rotor circuit. g. By changing slip.
27. What is the effect of frequency and high voltage at the start of motor.
For a constant load if frequency decreases motor current will increase and at the start if voltage is
more motor current also increases.
28. What is the minimum voltage required for starting of 6.6 kV motors?
Minimum 80% of rated voltage.
34. What is the effect of increased load on power factor of induction motor?
Power factor of an induction motor increases with loading.
41. What are the reasons for winding temperature high in the motor?
For motors having class – B insulation the temperature should not be more than 110°C and for motors
having class – F insulation the temperature should not be more than 130°C. In case temperature is
more, then the following could be the possible reasons.
• Electrical overloads.
a. Over and under voltage. b. Over and under frequency.
c. Voltage unbalance. Voltage unbalance create unbalance of currents and
increase in temperature which will be 2*(% voltage unbalance)* (% voltage unbalance)*.
(% Voltage unbalance) = 100 * maximum deviation from average voltage average voltage.
For instance if voltages are 390V, 410V & 440V,
% Voltage variation = 100*(440-390+410+440) (440-390+410+440) = 6.45%.
Therefore increase in temperature rise = 2*(6.45)*(6.45) = 83°C (approximately).
d. Voltage transients and interruptions. e. Loose connection at motor terminals.
f. Unbalance current. g. Single phasing (if OLR protection is not working).
h. Long acceleration cycle. i. Unusual system grounding conditions.
• Mechanical overloads.
a. Locked rotor. b. Heavy starting. c. Bearing problem.
d. Overload in continuous duty and intermittent duty.
• Environmental overloads.
a. Excessive temperature of cooling medium or ambient temperature.
b. Restricted flow of cooling.
c. Reduction in the density of cooling medium.
d. Heat transfer from machine parts connected to the motor.
4. Others.
a. Excessive number of switching operations.
45. What are the possible reasons for motor not coming of rated speed during start?
In case motor does not come to its rated speed then following could be the probable causes.
a. Starting load is too high. b. Broken rotor bars (look for cracks near rings).
c. Open primary circuit. d. Voltage is too low.
46. What are the possible reasons for motor to take long acceleration time?
Following may the possible reasons for motor to take long acceleration time.
a. Excess loading.
b. May be rewound motor with poor quality of winding conductor having high resistance.
c. Defective squirrel cage rotor. d. Applied voltage is too low.
47. What are the points contributes in insulation resistance of the motor?
If the measured insulation resistance of the motor is less than 1 MΩ / kV with a minimum of 1MΩ, when
the machine is cold it is to be dried out before full voltageis applied to the terminals of the motors and
the drying out is to be continued as long as the insulation resistance rises or until a sufficiently high
value that is not less than 1 MΩ / kV with minimum of I MΩ at 75°C is reached.
While proceeding for point as above said, following factors are to be kept in mind which affect the
insulation resistance measurement.
They are, a. Surface condition. b. Moisture. c. Temperature.
d. Magnitude of test voltage. e. Duration of application of test voltage.
f. Residual charge in the winding. g. Ageing of the insulation. h. Mechanical stresses.
48. What are the minimum recommended PI values for AC and DC rotating machines?
Following minimum recommended PI values criteria is to be followed.
a. 1.5 for class – A insulation.
b. 2.0 for class – B insulation.
c. 2.5 for class – F insulation.
49. What is the minimum recommended absorption coefficient value for AC and DC rotating
machines?
Absorption coefficient = IR value for 60 seconds = 1.3 (minimum recommended value) IR value for
15 seconds
Tips:
a. IR value decreases some what with an increase I applied voltage. However for machines in good
condition substantially the same IR is obtained for any test voltage up to the peak value of the rated
operating voltage.
b. If the IR value decreases significantly with an increase in applied voltage it is an indication of
imperfections or fractures of the insulation aggravated by the presence of dirt or moisture or may be
due to the effects of dirt or moisture alone, or may result from numerous other phenomena not
necessarily associated with any defect or weakness.
c. IR value for good dry winding continue to increase for hours with constant test voltage continuously
applied, however a fairly steady value is usually reached in 10 to 15 minutes. If the winding is wet or
dry or dirty the steady value is usually reached in 1 or 2 minutes after the test voltage is applied.
d. The recommended minimum IR value for AC and DC machines is determined by
the following empirical relationship.
50. What is use of Tan – Delta test? And what are the recommended values?
The very purpose of this test is to detect moisture content, voids, cracks and deterioration in the
insulation and same is to be conducted on HT motors. Based on the guidelines given in the article
‘Diagmistic testing on the winding insulation’ by J. S. Simon (IEE vol. 127 may 1980) the contamination
level of motor winding is to be assessed from the given Tan – Delta value.
Starting Tan – Delta values Degree of contamination
0 – 4%. Low void content.
4 – 6%. Clean.
6 – 10%. Some dirt.
10 – 14%. Dirt and moisture.
14 – 16%. Gross contamination.
16 – 20%. Heavy deposit of oil dirt.
Above 20%. Severe oil and carbon contamination.
66. What are the effects of excessive starts and repetitive surges?
Repetitive surges may give impact to the insulation of the motor and dielectric capability of the motor.
Excessive starts may subject stator winding to high current for more time. Subsequently in HT motor
due to High Mass rotor bar and rotor short ring may loose or fail. Bearing also may damage.
67. What are the effects of broken rotor bars and broken shaft parts?
Broken rotor bars
a. High stator current and over heat of stator winding.
b. More harmonic currents in end parts.
c. High vibration.
Broken shaft or parts
a. Stator winding loose bracing.
b. Rotor high vibration and bearing vibration.
c. Frame vibration and more harmonics in side bands.
73. Why motor starting current is high compared to transformer charging current?
Transformer charging current is only 1% and that of motor starting current is 30 to 40%. Because of
air gap between stator and rotor. If the air gap is more load taking capacity increases and if air gap is
less the load taking capacity reduces.
75. Why under voltage tripping of motor is incorporated in motor feeder breakers?
The under voltage can occur in case of bus fault. If the motors are kept connected they will feed the
fault which may cause the damage. Due to the back feeding from the motor the motor will slow down
very fast. Hence process system will come to halt very fast. (In case HT motor will not rotate for the
designed 3 to 5 minute period in case of bus under voltage).
76. What is the purpose of static starter? How current setting adopted?
The static starter limits the starting current of the motor to 2.5 times the motor rated current instead
of 6 times the rated current. If the motor is directly on UPS, the UPS fuse will blow, since the UPS
cannot supply so much starting current. Hence the static starter is set to limit the starting current. This
is achieved by firing angle control of back to back thyristor
82. What are the checks on the motor during the preventive maintenance?
IR Value, Resistance and Inductance measurement and PI value (should > 1.5)
Spectrum Analysis of the motor’s current & voltage signals can detect various faults without taking
shutdown.
Typical faults detectable by this technique are:
✓ Rotor bar damage
✓ Misalignment / unbalance
✓ Foundation looseness
✓ Static or Dynamic eccentricity
✓ Core damage, Loose wedges
✓ Interturn short , Defective bearings
✓ Bent shafts
❖ Faults in the motor changes the flux distribution inside the motor.
❖ This leads to Harmonics generation.
❖ Current & voltage signals are captured during operation.
Electrical Question Bank By : Satish Panchal 95
❖ FFT (Fast Fourier Transform) analyzer displays various harmonics components (called Elect.
Signature)
❖ It contains Supply Harmonics ( seen both in V & I) and Fault Frequency Harmonics (seen in
current only)
❖ Superimposing the I & V FFT signals enables to identify the Fault Frequency Harmonics (FFH)
❖ Analysis of FFH identifies the nature of fault.
THERMOGRAPHY
❖ Infra red imaging & temp. measurement camera (cost @Rs.30lakhs) is used..
❖ It SEES, MEASURES and RECORDS hotspot temperatures.
❖ Colored bar code (on left or right side) indicates temperatures figures.
❖ On hotspots, temperature are also written in figures.
❖ The results can be down loaded on floppy or CD.
The transfromer's secondary which is feeding 3 phase motor is already earthed.so there is no need to
earthe the motors star point again. Because earth resistance wont be same every where.If we
eartherd both the ends,there will be a current flow between two neutrals.
universaly,in industries 70% of loads are inductive tupr which are having lagging PF nature.Always
load only decides the power factor not source(Alternator).So that only the rating always mentioned as
VA and not watts.
❖ why circuit breaker closing time is always higher then tripping / opening time
Whenever a Loaded circuit breaker is interrupted / tripped / opened an arc is inevitably (Certainly)
formed between the contacts. But in the closing time there is no current carrying by Circuit Breaker
and no any other effect on contacts. So, circuit breaker closing time is always higher then
tripping/opening time.
- INTRODUCTION
- CURRENT TRANSFORMER
- POTENTIAL TRANSFORMER
- CIRCUIT BREAKER
- BUSBAR
- BUSDUCT
4. TESTING REPORT.
INTRODUCTION
1. EARTHING
To start testing of Any Electrical system / equipment, we have to ensure the earthing of
the electrical system is ready. So first we should know what is its importance of earthing & how to
check earthing .
The testing of earthing system is generally required for all electrical equipment/ system ( like
substation, PIB, HT motors, lightening protection, Plant earthing grid). The primary condition to
carry out test is the installation must be completed and each earth pit should identified with proper
tag number. The tests are e carried out on the earthing system are as follows.
► Earth Megger
► Multimeter
Maximum values of resistance of equipment earthing systems to the body of
Topic – 1
►CURRENT TRANSFORMERS
►POTENTITAL TRANSFORMERS
►BREAKER
►BUS BAR
►BUS DUCT
►RELAY
► CT used in panels are bar type, for our application mounted on bus bars, fixed firmly. As
per standard the polarity is marked on CT, by marking P1, P2 for primary winding, and S1,S2 for
secondary winding. P1, P2 means the power flow is from P1 to P2 and accordingly the CT is
mounted on bus bar. With primary correctly fixed, the induced current will flow from S1 to S2 in
secondary side. The direction of current in secondary and decision to make S1 or S2 as star point is
very important in Protection.
This is best done by taking 1.5 / 9v dry cell with wire soldered at positive and negative
pole, multi meter in voltage range connected to secondary terminal, positive to S1 and negative to
S2. With multi meter connected, hold positive terminal wire of cell near P1 – actual and
not marked P1 of CT - and touch the negative wire of cell to P2, at the same time observe the
deflection on multi meter. If the deflection is in positive direction, then the polarity of CT mounted
is correct.
– Repeat the test for other CTs of Panel and then for All Panels’ CTs.
– This check is usually carried out during primary injection test to ascertain the ratio of the CT.
► Inject the current in Primary side (Say 25 %, 50 %, 75% and 100 % of rated current) by Auto
Variable Transformer / 1 phase primary injection kit and measure the secondary side current by
suitable multi meter / ammeter/ clamp on meter in measuring core, compare the secondary current
measured with theoretical values and calculate the percentage error. Repeat the test for Protection
Core, of all CTs of panel and CTs of all remaining panels.
► This can be done by energising the secondary winding from the local main 230V supply through a
variable auto transformer and connecting Ammeter in series to
measure the current and a voltmeter / multimeter for measuring voltage.
► Take several readings of voltage and current simultaneously. Preferable voltage value of 100, 150,
200, 220, 250 and 260V. Utmost care and attention is to be taken to limit the applied voltage for the
test. Applied voltage should not be more than SECONDARY LIMITING VOLTAGE, which is calculated
by a formula using secondary winding resistance at 75 degrees centigrade.
►Plot the graph of measured current on x-axis and applied voltage on y-axis and locate knee point.
► GENERAL
► LIST OF TESTS
► TESTING EQUIPMENTS
GENERAL
► Two types of PTs are there in any HT/LT panel Line PT and Bus PT.
► Line PTs are mounted on incomer breaker trolley where as Bus PTs are mounted on separate
panel in each Bus section.
► Line PTs gives indication of presence of supply in incomer breaker panels, from upstream source.
► Bus PT senses the respective bus voltage and are useful for under voltage tripping and other
metering and protective circuits.
► Ensure that PT fuses are removed before starting the testing of PT
► Convert secondary phase to neutral measured reading (based on test voltage of 415 volts) to
system voltage of the panel. It should be 110 (for delta connection) or 110/√3 volts (for star
connection).
► Repeat the test with other Line PT and Bus PT units.
1.2.4 TESTING EQUIPMENTS
► Multimeter.
► Megger (1 kV and 500 V ).
► Clamp on meter.
► Dry Battery cell 1.5 / 3V with soldered wire at positive and
negative terminals.
► Cut pieces of copper flexible wires.
► Hand tools, etc.
► GENERAL
► PRE-CONDITIONS
► TESTING
► TESTING EQUIPMENTS
GENERAL
The module is limited for different tests carried out on breakers only and remote tripping or
inter tripping scheme for out going breakers is excluded. Where as, scheme of operation of two
Incomers with one Bus Coupler and tripping through its own tripping devices is included.
► Take breaker name plate details for each test.
This test is useful to minimize the voltage drop in the bus bars. The resistance will depend on number
of joints each Ph. This test can be carried out, all joints of same phase & for other phase also.
Connect one lead Micro-Ohm Meter on one end of R phase bus and second lead on R phase of the
other end of the bus bar (through a connecting lead wire) and note down the reading Repeat the
above procedure for Y-phase, B-Phase and neutral bus bar (for LT) and record the readings.
The measured value of bus resistance should be around 20 micro ohm * Number of Joints.
1.4.2 INSULATION RESISTANCE TEST :
The test should be carried out up to outgoing terminals of each feeder, meaning all out
going and bus coupler breakers must be closed, incomers and PT trolleys inserted but PT fuses
removed. Take the test from any incomer breaker out going terminals.
►Then measure insulation resistance by Megger (2.5 kV) between Phase to Phase. Note down the
value.
►Repeat the procedure 2.2.1 for Phase to Earth and note down the readings in record sheet. The
value must be in Giga ohms.
The testing of Bus Ducts can be taken up either after the installation is totally complete, including
connections at transformer and switchgear end or at a stage where all the installation is complete and
only connections at transformer and switchgear is balance.
The following tests are to be done :
Insulation Resistance Test, Contact resistance Test
High Voltage Test. Functional Test. Functional test of space heater
Functional test of silica gel breather
1.5.2 INSULATION RESISTANCE TEST
► This test is taken to check the effectiveness of each joint and to ensure minimum voltage drop
in bus duct.
► Open bus duct covers at all busbar joints.
► Contact resistance can be measured using micro-ohm meter.
► To test, connect the leads of micro-ohm meter across busbar joint, taking care that complete
joint along with all coupler plates is covered.
► Read the resistance value when the reading is steady. Also note down the atmospheric
temperature at which test is done.
► Repeat the test for all joints and in all phases (and neutral for LT).
► Ideal value of resistance for each joint is 20 micro ohm.
► Result of each joint must be almost same.
► Check the clearance of each phase flexibles at both ends of Bus Duct with transformer bushing
and switchgear busbars.
► Apply 10.5KV voltage for 5 minutes to 6.6kv bus duct to each phase and earth and 2kv for LV
Bus Duct.
► Read value of leakage current for each test.
► Test the entire space heater circuit for insulation resistance using 500V megger with 2 Pole main
supply ELCB off.
► Check the continuity of wires of the space heater circuit.
► Measure the resistance of each heater element individually after disconnection of each element
and also total resistance with all heating elements in circuit.
*TESTING OF RELAYS
The present testing module covers only Siemens relays installed on 6.6kv panels of Siemens and PCCs
of Larsen & Toubro make.
INDEX
►GENERAL
► Set the value of I >> 1A (Address mode 1202) and set trip time TI >>1Sec (Address mode
1203).
► Select the value of I > at high value (Address mode 1204), compared to I >>.
► Gradually increase the current till LED1 & 2 appears. Note the pick up current & Actual trip time
from relay. It will be at around set time –1.0 sec.
► Similarly take reading for other two phases.
► Set current Ip=1A & set trip time TIp=1 (Address mode1208) Sec.
► Inject 2 times of set current (Ip=1A), (Address mode 1207) & note its tripping time to be nearly
equal to 10.03Sec.
► Inject 5 times of set current (Ip=1A), (Address mode 1207) & note down tripping time. It will be
nearly equal to 4.28 Sec.
► Check LED 1 for pick up and LED 2 for over current which will glow.
► Similarly take readings for remaining two phase.
► At the end of test change the setting of O/C mode to “OFF” condition.
► Set the value of IE >>1 (Address mode 1302) amps and TI E >> 1 Sec (Address mode 1303).
► Select the value of IE > at high Set. (Address mode 1304).
► Gradually increase current from 0.90A & note the pick up current and Actual trip time.
► Check LED 1 for pick up and LED 3 for earth fault which will glow.
► Set current IEp =1A & set time TI Ep=1 (Address mode1305) Sec.
► Inject 2 times of set current I Ep=1A,(Address mode1307)& and note down its tripping time
nearly equal to10.03 Sec.
► Then Inject 5 times of set current (IE p=1A) (Address mode 1307) & note down its tripping time
nearly equal to 4.27 Sec.
► Check LED 1 for pick up and LED 3 for earth fault which will glow.
► At the end of test change the setting of E/F mode to “OFF” condition.
► Set value of U >>125V (Address mode 5005) & set time TU >> 1.5 S (Address mode 5007). Set
U> at 130V. Marshall BO1 and LED 6 for U>>.
► By using 3 Ph variac, apply 110V to the primary side wires 1,3,5 of F25 MCB.
► Note voltage and time value from set when LED 6 glows trip command is issued.
► Set the value of U<< 70 V (Address mode 5110) set time TU<< 1.5 (Address mode 5112)
► By using 3 phase variac, apply 110V to wires 1,3 and 5 of MCB.
► Decrease the voltage slowly to 70V and observe status of LED. Note down the time taken for trip
from relay test set.
►GENERAL
►TESTING OF RELAY
►LIST OF TESTING EQUIPMENTS
1.6.4.1 GENERAL
► Set current Ip =1A & set trip time TI p=1 (Address mode 1208) Sec.
► Inject 2 times of set current (Ip =1A), (Address mode 1207) at R Ph terminals & note down its
tripping time nearly equal to 10.3Sec.
► Inject 5 times of set current (Ip =1A), (Address mode 1207) & note down its tripping time to be
nearly equal to 4.28 Sec.
► Check LED 1 for pick up and LED 2 for over current which will glow.
► Similarly take reading for remaining two phases.
► At the end of test change the setting of O/C mode to “OFF” condition.
► 2.1.1 Connect the terminals of Ducter / Micro Ohm Meter on 1U1V, 1V1W and 1U1W one by one.
Read the meter when reading on meter stabilizes.
► 2.1.2 Next connect the terminals to 2U2N,2V2N,2W2N, one by one and measure the resistance
respectively, and note down in record sheet.
► 2.1.3 Note the temperature of oil at the time of test from OTI.
2.2 INSULATION RESISTANCE TEST
► 2.2.1 Before taking megger value ensures that the all HT and LT side connection are
Disconnected.
► 2.2.2 Take IR using (0 to 5 KV megger) hand or motor operated as under: HV to Earth, LV to
Earth and HV to LV Though HT / LT windings are internally connected to form the star or Delta as
the case may be, the test should be repeated for all phases, each time discharging the terminal to
earth after meggering and before testing next phase.
► 2.2.3 Note down the ambient temperature at the time of test, as the insulation resistance is
dependent on oil temperature.
► 2.2.4 The PI of HV and LV windings can be taken at this stage by noting 1 minute and 10 minute
readings of Megger and dividing 10 minute reading by 1 minute reading.
► 2.2.5 Record the readings for future reference.
► 2.3.1 Connect the three phase 415V Power Supply RYB at the HT side bushing 1U,1V,1W
respectively. Check that the disconnected cable leads does not touch the transformer terminals.
Keep the tap on center tap position.
► 2.3.4 Now switch OFF the ELCB and change the tap position to one step lower.
► 2.3.5 Repeat above steps 2.4.3 to 2.4.4 for all taps, all below and above center tap, each time
switching off the isolator for changing tap position
► 2.3.6 Calculate the ratio of applied HT (415V) and LT measured voltage for phase to phase
values and compare with the name plate value of voltage ratio. Secondary phase to neutral
measured voltage shall be 1/ √ 3 times secondary phase to phase voltage.
► 2.3.7 Record the value for future reference.
►2.4.2 Repeat the above step for applied voltage between b)1V,1W
and measuring the voltage between 1U1V,1W1U
c) 1W1U and measuring the voltage between 1U1V,1V1W
►2.5.1 Keep the secondary terminals 2U , 2V , 2W and N open and tap position at center tap.
►2.5.2 Connect the ammeter ( with mA range ) in series with power lead of 415V supply to HV or
use low range clamp on meter.
►2.5.3 Apply 415V AC to 1U,1V,1W note down the Magnetising current taken by HT side in all three
phases and Voltage applied to HT side.
► 2.5.4 Convert this current value at 415V, to rated primary voltage level.
►2.5.5 Compare calculated reading with the No Load test reading at vendor’s testing lab.
►2.5.6 Record the value for future reference.
➢ 1w2w = 1v2v
➢ 1w2n = 1v2n
➢ 1w2v = 1v2w
➢ Confirms vector group as Dyn0
►2.7.1 Collect two samples each of bottom of Main Tank and Diverter Compartment (in case of on
load tap changer) in Vacuum dried, air tight glass or metallic bottles. While taking oil samples,
observe following points strictly.
2.7.1.4 Sample bottles are to be clean and dry and to be fresh or used previously only for
. transformer oil sampling
2.7.1.2 While taking samples, first allow some oil to flow out of the valve
2.7.1.3. Allow the oil from valve to fall on the side wall of the bottle. Fill the bottle fully and allow
it to overflow, rinse the cap of the bottle and close the bottle while still oil is flowing
. Close the bottom drain valve
►2.7.2 Test the samples taken, on oil testing set as follow :
1 Rinse the pot of oil testing set with oil sample by filling it
completely and then throwing away the oil.
2 Next pour slowly the oil in the pot from same sample,bottle, taking care not
to cause bubbling. Pour on side of pot.
3 Power up the oil testing set.
4 Allow the oil sample under test to settle for about 15 minutes.
5 After the settlement time of sample under test is over, increase the voltage of testing
set
slowly, observing any tracking between electrodes and hearing rattling/chattering
sound, till the sample breaks. Note down this value as the 1st test reading. If oil
sample
does not break, then continue raising voltage to full value of set and then decrease it
slowly to zero.
6 Repeat the test for 4 more times giving 5 readings.
7 Average of five readings is the Di-electric strength of oil. Accepted value of Di-electric
of transformer oil is 60kv
8 Ensure correct spark gap as per go / no go gauge Next test the oil sample from other
sample bottle for moisture content, in moisture analyzer test set. Accepted value 20-30 ppm for
distribution transformers and 15ppm for power transformers.
►2.7.4 Record the reading for future reference.
► 2.8.2.1 Functionality test for level switch is better taken when conservator is empty , when alarm
/ trip contact will close or low oil level.
► 2.8.2.2 When conservator gets filled up to half level the low oil level alarm / trip contact will
open.
► 2.8.2.3 The status of alarm / trip contact can either be checked at conservator junction box or at
marshalling box.
►2.8.3.1 Open the OTI cover, Set the alarm and trip setting on OTI and WTI as per Engineering
guidelines
►2.8.3.2 Hold the dial and slowly rotate clockwise, till mercury switch for alarm operates, note the
temperature at this point compare with the set value .Difference between operating and set values
should not be significant. Rotate the dial further till mercury switch for trip operates. Note the
temperature value at this point and compare it with the set value.
► 2.8.3.3 Repeat the test with WTI. The alarm generated by OTI and WTI can be checked at
respective terminals in marshalling box. Close the covers of the OTI, WTI and marshalling box.
►2.8.3.4 Check the calibration certificate given by vendor for accuracy of OTI, WTI readings. If this
is not available, then
►2.8.3.5 Calibrate both OTI and WTI by water bath taking readings of OTI / WTI and standard
thermometer with its bulbs inserted in water bath, when water is cooling down from boiling point
– 100°C, at every 10°C.
►2.8.3.6 Draw graph of percentage error at every reading versus standard reading. Use this graph
to correct the reading every time the meter is read.
► 2.8.4.1 Open the top cover of the PRV JB and operate the plunger of limit switch manually. Check
the tripping command has generated at respective terminals of JB and Marshalling Box.
►2.8.4.2 Release the plunger back to its earlier position. Check the trip command resets. Close the
cover of JB.
2.9. LIST OF TESTING EQUIPMENTS
►2.9.1 Multimeter.
►2.9.2 Clamp on meter.
►2.9.3 Micro ohm meter / Ducter tester.
►2.9.4 Megger (1kV, 5kV).
►2.9.5 Oil Testing Set 100kv
►2.9.6 Moisture Analyzer
►2.9.7 Hot water bath with standard thermometer, 0 to 120°C.
►2.9.8 Hand Tools, 63A TP Load Break Switch Fuse Unit and cut pieces of wires and copper flexible
cables.
TESTING OF HV/LVMOTOR
Motor remains disconnected from previous tests. This test is, continuation of IR Test.
► PI ratio is the ratio of 10 minute IR reading to 1 minute IR reading.
► Both 1 minute and 10 minute readings are taken in previous test of Insulation Resistance
Measurement. Find PI value, as suggested above.
► The ratio arrived, must not be less than 1.2.
The testing has been covered under winding resistance measurement test. It has been tested for
continuity, total resistance value and insulation resistance.
► Connect back the space heater wires.
► Put back delta links.
► Connect back power cables power cables, as per earlier connections. Make sure to use correct
size washers and spring washers.
when we give supply to transformer, transformer charge and flux is produced and when the
supply is cutoff some flux is been remained which is known as residual flux.
when we again charge the transformer the flux produce is combination of charging flux and
residual flux and the current produced due to it is known as inrush current
Then, using ohm's law, the resistance value is calculated. The resistance value needs to be
compared with the value given by the manufacturer. The value should also be compared
with previous records.
Q-The Synchroscope is a device to check the phase angles of the two sources during the
process of synchronization. It plays a vital role in ensuring that the two power supplies
which are being synchronized are "in phase" with each other. The Synchroscope has a dial
with a pointer which can occupy different positions according to the difference in the phase
angle.
The positions are usually compared with the markings on the clock. Thus a 3 'O'clock
position would indicate that the voltages are apart by an angle of 30 degrees. The 6 'O'clock
position would indicate that the sources are apart by 180 degrees. When the pointer is at
the 12'O'clock position, it indicates that the difference in phase angle between the two
sources is zero. The breaker connecting the two sources can now be closed.
The dial of the synchroscope is marked with two arrows indicating the direction of rotation
of the pointer. These arrows indicate the clockwise and the anti-clockwise direction. The
clockwise indicating arrow is marked "Too Fast" while the anti-clockwise indicating arrow is
marked "Too Slow".
These arrows indicate the speed of the incoming source as compared to the bus bar. If the
incoming generator's frequency is more than that of the bus bar, the pointer rotates in the
"Too fast" clockwise direction. The machine then needs to be slowed down. If the frequency
of the incoming machine is less that that of the bus bar, the rotation of the pointer is in the
opposite "Too Slow" direction.
122
During forward synchronization when the incomer is intended to supply power to the grid,
the pointer of the synchroscope is allowed to rotate in the clockwise direction before it
stabilizes at the 12'O'clock position after which the breaker can be closed. This is essential
to prevent the machine from tripping on reverse power should power flow from the bus bar
to the grid.
In the case of reverse synchronization, the direction of the rotation depends on whether
power needs to be exported from the bus bar to the grid or imported from the grid to the
bus bar. In the former case, the direction has to be clockwise in the latter case it is to be
anticlockwise.
In newer models of the synchroscope, the pointer is replaced by LEDS which blink
depending on the phase angle and give the appearance of "running lights".
Forward Synchronization
In Forward Synchronization, the voltage, frequency and phase angle of the incoming
generator is synchronized to match the values of the bus bar. This is generally used when a
generator needs to be synchronized with an already charged bus bar. as shown in the
diagram.
Reverse Synchronization
123
Q-Transformer Oil Deterioration
The Oil inside power transformers have a vital role to play in the transformer's functioning.
The function of the transformer oil is two-fold, to provide cooling to the transformer
windings and to provide insulation. However, over a period of many years, the transformer
oil deteriorate owing to many factors. This deterioration causes a change in the physical and
chemical properties of the oil.
Some of the reasons for transformer oil deterioration are
Thermal Decomposition
At high temperatures, the organic compounds in the transformer oil break down due to a
phenomenon known as pyrolysis. This results in the formation of unwanted carbon
compounds, sludge, etc.
Moisture contamination
Under ideal conditions, the oil in a transformer is protected against the entry of moisture by
means of the silica gel filter in the breather. The silica gel changes color from blue to pink
when it gets saturated with moisture. If the silica gel is not renewed in time, moisture may
pass through the filter contaminating the oil.
Overload:-
Excessive loading can cause overheating. Transformers are rated in kVA. This kVA rating is
dependent on temperature. Some transformers have two kVA ratings. One rating is for
below a specific ambient temperature; say 45 degrees while another rating is above the
ambient temperature.
Excess current in the neutral of the transformer:-
Excess current in the neutral of the transformer is usually caused by high zero sequence
harmonic components. This can be resolved by proper grounding usually through a zig zag
transformer.
Problems in the Cooling system:-
Malfunctioning of the cooling equipment such as blockages in the cooling oil circuit. Failure
of the cooling fans to operate in the case of Forced Air cooling systems.
High Harmonic content in the power supply:-
High harmonic loads can also cause heating in the transformer. These loads need to be
identified and suitable remedial measures such as harmonic filters can be implemented.
Sustained Overvoltages;-
Overvoltages which exist for a long period of time can overexcite the transformer and cause
overheating.
124
Q- Fault Level Calculation
When a short circuit occurs in an electric system, heavy current flows through all the sections
of the system which are in the path between the power source and the equipment. The short
circuit current is limited only by the impedance of the system.
This heavy current can damage the components of the electric system if they are not properly
rated. If circuit breakers are not able to interrupt the high short circuit currents in a system,
arcing and explosions may occur
.
The Rating of the components is done based on the maximum short circuit current. The short
circuit current is calculated from the fault level KVA of the System. The Fault Level in a
distribution system is a very important parameter. The kVA at the instant of a Fault should
be correctly calculated and the components of the distribution system such as bus bars, circuit
breakers, isolators, etc should be properly sized.
To calculate the fault current in a system it is first necessary to calculate the MVA during a
fault.
From this, the maximum current during the fault can be deduced as
All the equipments should be rated to withstand this current. The fault level should be
calculated every five years and after any modification to the system such as the addition of
any load or the installation of further sources of power such as transformers and alternators.
Q-Arcing Horns
Transmission and other electrical equipment can be exposed to overvoltages. Overvoltages
can be caused by a number of reasons such as lightning strikes, transient surges, sudden
load fluctuation, etc. In the event of an overvoltage, the insulating equipment such as the
insulators on a transmission line or bushings in a transformer can be exposed to high
voltages which may lead to their failure.
Arcing horns are protective devices that are constructed in the form of projections in the
conducting materials on both sides of an insulator. Arcing horns are fitted in pairs. Thus in
125
transmission lines they are found on the conducting line and the transmission tower across
the insulators. In transmission lines, in the event of a lightning strike on the tower, the
tower potential rises to dangerous levels and can result in flashovers across the insulators
causing their failure. Arcing horns prevent this by conducting the arc across the air gap
across them.
Arcing horns function by bypassing the high voltage across the insulator using air as a
conductive medium. The small gap between the horns ensures that the air between them
breaks down resulting in a flashover and conducts the voltage surge rather than cause
damage to the insulator. The horns are constructed in pair so that one horn is on the line
side and the other is on the ground side.
Arcing Horns are also used along with air insulated switchgear equipment. Air insulated
switchgear are vulnerable to damage due to arcing. Arcing horns serve to divert the arc
towards themselves thus protecting the switching equipment. The arcing horns serve to
move the arc away from the bushings or the insulators.
Another reason for earthing the secondary would be functional. For applications such as
synchronization where two PT voltages need to be compared, the synchronizing equipment
(dark lamp method and bright lamp methods) would function only if the star point of the
PTs are grounded.
126
Q-Thermography in Sub-stations
Thermography is an extremely useful tool in the maintenance of substations. Thermography
helps monitor the components in the substation. Using temperature-based imaging, it
identifies hot spots which can indicate potential problems. Thermography is an integral part
of predictive maintenance schedule. Thermography involves monitoring devices with a
thermal imaging camera. Thermal imaging cameras operate on the infrared spectrum which
is invisible to the human eye. The images formed by these devices show variations in
temperature in the object. These variations in temperature can be interpreted as
Thermal cameras work by measuring the wavelength of the radiation emitted by hot bodies.
The wavelength of the radiation depends on the temperature of the equipment.
Most electrical problems such as loose connections, overloading, etc are accompanied by a
rise in temperature. This rise in temperature can give timely warnings, which, if heeded can
avoid major failures and breakdowns.
Thermography is usually carried out in the early mornings to enable clearer differentiations
of the hot spots from the surrounding temperature. The components which are being
inspected should be in the normally loaded condition.
Thermal images of all components should be recorded and temperatures noted. The
temperatures of two similar components carrying similar loads should not differ by more
than 17 degrees and the difference between any component and the surrounding
air(ambient temperature) should not exceed 40 degrees.
If any anomaly is detected, the thermal image should be recorded along with a ordinary
127
photograph. It is advisable to take the thermal images from different angles to obtain a
good perspective.
Thus a transformer with a primary rating of 110V which requires a voltage of 10V to
circulate the rated current in the short-circuited secondary would have an impedance of 9%.
The Open Delta connection can be used where one transformer of a three phase PT
assembly has failed.
128
The open delta connection is cheaper that a conventional delta connected PT. Another
advantage of the open delta connection is that it can be used service one transformer in a
connection while the system runs on the other two.
Float charging of a battery involves charging the battery at a reduced voltage. This reduced
voltage reduces the possibility of over charging. The Float charger ensures that the battery
is always in the charged condition and is therefore considered "floating". The Float charger
starts by applying a charging voltage to the battery. As the battery gets charged, its
charging current reduces gradually. The float charger senses the reduction in charging
current and reduces the charging voltage.
If the battery gets drained, the float charger will again increase the charging voltage and
process continues. Float chargers can be connected indefinitely to the batteries.
Boost charging involves a high current for short period of time to charge the battery. It is
generally if the battery has been discharged heavily. Boost charge enables the quick
charging of depleted batteries.
For instance, a two volt lead acid battery which has been discharged will initially be boost
charged with a charging voltage of around 2.35-2.4 volts. However, as the battery voltage
rises, the charger will switch over to the float charge mode with a float voltage of 2.25
volts.
Most battery chargers come equipped with provisions for both boost and float charging.
Overvoltage relays can be used to identify overvoltages and isolate equipment. These
relays operate when the measured voltage exceeds a predetermined set-point. The voltage
129
is usually measured using a Potential Transformers. The details of the ratio of the potential
transformer are also entered into the relay. These relays are usually provided with a time
delay. The time delay can be either instantaneous, fixed time or for IDMT (inverse definite
minimum time) curves.
Generally, overvoltage relays are provided with sufficient time delay in order to avoid
unwanted trippings due to transients (See article on Transients).
These relays can be used to isolate feeders and other equipment connected to the
network. In the case of generators, these relay also switch off the excitation system to the
generators thereby preventing voltage build-up.
Negative phase sequence currents cause heating of the motor and consequently motor
failure. Single phasing is caused by the use of single-phase protection devices such as fuses
and circuit breakers. Three phase loads should be protected by devices which cause the
interruption of power to all three phases simultaneously when a fault occurs.
Defective contacts in three phase breakers can also cause single phasing.
Single phasing can be identified by special protective relays which can identify and isolate
the connected loads. Smaller motors rely on overcurrent and negative phase sequence
relays. Motor protection relays for larger motors come readily fitted with protection against
single phasing.
Single phasing can sometimes cause excessive noise and vibration in motors.
Specific gravity of any substance is the ratio of the density of that substance to the density
of water. It does not have any unit as it is a ratio. Specific Gravity is also known as
Relative Density. Specific gravity is measured using a hydrometer (see picture).
A higher specific gravity of an electrolyte is caused when the water content in the electrolyte
is reduced either due to electrolysis or evaporation. A lower specific gravity would indicate
undercharging.
During the charge-discharge cycle of a battery, the specific gravity varies continually. It
increases when the battery gets charged and decreases when the battery gets discharged.
Specific gravity of the electrolyte also varies in accordance with temperature; it decreases
with increase in temperature and increases in colder conditions.
130
Low resistance Grounding is used in situations where quick operation of ground fault relay is
required. This form of earthing is used when faults need to be cleared quickly.
Low resistance grounding resistors have a time rating beyond which they may not be able to
maintain thermal stability due to the heat generated by the fault currents.
Low resistance grounding ensures that equipment and conductors are not exposed to the
electric and mechanical stresses during an earth fault.
However, the downside of low resistance grounding is that the system needs to be de-
energized after a ground fault.
Q- Resistance Grounding
High Resistance Grounding restricts the ground fault current to less than 10A. These
systems are advantageous because the system can continue to run when there is a
fault between a phase and the earth. This ensures the system reliability and the system
continues to run while the fault can be identified and rectified. However, care must be
taken to ensure that the permitted ground fault current is greater than the charging current
of the line capacitances.
131
This is essential to ensure that there are not transient overvoltages during
intermittent earth faults. The series resistors used in High resistance grounding are
designed for longer time rating as they may have to be in circuit as long as the system is
running with the fault still present.
High Resistance grounding Systems are not permitted in systems which feed single
phase loads.
Modern High Resistance Grounding Systems are equipped with a pulser circuit which
is activated when a ground fault is detected. This pulser circuits generates a
pulsating current which can be used to identify the exact location of the ground fault with a
handheld device. This is extremely useful in identifying the fault within a short period
and restoring the system.
Types of Earthing
A proper grounding scheme is vital component of any power system. Improperly grounded
systems can result in equipment failures, overvoltages, and flashovers. Grounding uses the
earth as a return conductor in the event of a fault. This helps to identify the
fault. Resistances can be used to limit the fault current to desired levels. Grounding
ensures system stability and prompt identification and clearing of faults.
In three phase systems, the neutral of the Star Point is usually grounded. In the case of
delta connected systems, a special grounding arrangement such as Earthing Transformers
or Zig-zag transformers are used.
On the basis of the grounding used, Power Systems can be classified into
• Ungrounded Systems
• Solidly Grounded Systems
• Low Resistance Grounded Systems
• High Resistance Grounded Systems
Q- Ungrounded Systems
Ungrounded Systems can function normally in the healthy condition. In the fault condition,
as one phase gets earthed, the voltage between the other two phases and the ground
increases to the line voltage(phase to phase voltage). This places the insulation of the
equipment connected to the system under excessive electrostatic stress. Ungrounded
systems are the most expensive for this reason.
Electric Equipment connected to ungrounded systems need to have insulation rated for the
line voltage. In the event of a fault on one phase, the fault current is fed by the
capacitance charging current flowing the other two un-faulted phases.
This current is usually less and power can continue to flow in the other two
132
phases. However, if the fault is intermittent and the contact with the ground is of the
make-break type. The capacitances which form in the other two phases may charge and
discharge into the system causing high overvoltages, sometimes 5 to 7 times the normal
voltage. This can cause extensive damage to other devices connected elsewhere in the
system.
While the ungrounded system can run with the other two phases even when one phase is
faulty, a fault in any of the other two phases can cause a phase-to-phase short circuit via
the ground.
Besides, the intensity of a ground fault will be greater and will be accompanied by a
flashover. This may be dangerous to personnel who are in the vicinity.
The damage to the equipment is also extensive as a higher current flows in solidly grounded
system. The conductors carrying the current are subjected to extensive electrical and
mechanical stresses.
The ground current which flows through the soil can pose a danger to people if the step
potential exceeds the safe limits.
In high resistance grounding, the fault current is limited to less than 10 amperes. While, in
low resistance grounding, the current is limited to a value from 25 amperes or more.
The resistances are also categorized on the basis of time they can withstand the fault
current. Typical durations are 1 second, 10 second, one minute and 10 minute rating.
The Extended Time rating resistor is used in systems where the reliability of the system is
critical. This is true in petroleum industries, mines etc. In these situations, a high resistance
which can sustain the fault for a long period is used. When an earth fault occurs of one
phase, an alarm is generated. However, the system continues to run until the next
scheduled shutdown.
Resistance grounding is not used in systems where the phase voltage exceeds 15kV for cost
reasons.
133
These asymmetrical magnetic fields which are varying over time can induce currents in the
shaft of the motor or generator. These currents which are induced in the shaft tend to flow
from one end of the shaft to the other through the bearings and then through the earth.
When these currents flow through the bearings, the tend to cause arcing and consequent
pitting in the bearings. This can lead to failure of the bearings.
Shaft currents can be prevented by insulating one of the bearings. A Teflon layer is usually
placed between the shell of the bearing and the bearing housing. This ensures that the shaft
voltage induced does not have a return path. This prevents shaft currents from flowing.
Reversing a single phase motors cannot be done by reversing the polarity of the supply to
the entire motor. To reverse the single phase motor, the polarity of the supply to only one
of the windings needs to be changed.
This can be done by reconfiguring special links which may be provided in the terminal box of
the motor.
The objective of a shield is to ensure that the cable insulation is subjected to a uniform
electric stress. The shielding also prevents transient overvoltages which are induced along
the cable by ensuring a eliminating surge potentials and ensuring a uniform surge
impedance.
Shielding also protects personnel from dangerous shocks which may be caused by intense
electric fields.
Q- Proximity Effect
Proximity Effect is a phenomenon which is observed in conductors carrying alternating
current. When a conductor carries ac power, the constantly varying magnetic field induces
eddy currents in the nearby conductors. In conductors where the current flows in the same
direction, this results in increased current density in the nearby conductors due to the
changes in the current distribution across the cross-section of the conductor. Thus the
resistance of the conductor increases.
In the picture, the blue zone inducts the areas with high current density, the white zone
indicates low current density caused by mutual induction.
134
When two conductors carrying current in the same direction are located close by, the
current density on the sides of the conductor adjacent to each other will be lesser than the
sides on the outside.
The reduces the net current carrying capacity of the conductor. This phenomenon is not
observed when dc current flows through the conductor as there is no induction in dc.
Thus the AC resistance of a conductor may be many times the DC resistance. The AC
resistance is directly proportional to the frequency of the power supply. The proximity effect
is an important factor considered during the design of transformers, motors and multi-core
cables.
Q- Noise in Transformers
Transformer Noise is caused by a phenomenon called magnetostriction which occurs inside
the transformers. Magnetostriction is a phenomenon by which a metallic objects experiences
a distortion in its shape when it is placed inside a magnetic field. The objects can experience
a change in the dimensions, expansion or contraction.
Inside a transformer, the core which is made in the form of laminated sheets also
undergoes expansion and contraction due to the changing magnetic flux. This expansion
and contraction occurs twice in an ac cycle. The fundamental frequency of the noise or
vibration is double that of the frequency of the power supply. Thus a supply with a
frequency of 50 Hz will cause noise or vibration whose fundamental frequency is 100 Hz.
In addition to the fundamental frequency, there are also harmonics whose frequencies are
odd multiples of the fundamentals such as the 3rd harmonic, 5th harmonic, etc. A proper
study of the noise and vibration spectrum is necessary to devise methods of reducing them.
Since, the core of the transformer is made of laminated steel sheets; these sheets
experience unequal expansion and contraction when exposed to the magnetic flux. Hence,
they rub against each other causing the distinct hum. The constant cyclic forces generated
in the transformer core cause vibration which is carried to the different parts of the
transformer body. In addition, they also cause noise. Thus when trying to reduce the hum
of the transformer, both noise and vibration needs to be addressed. The noise of the
transformer is measured in decibels (dB).
People can find the noise of a transformer disturbing and may oppose locating a transformer
near their residence. In such circumstances, measures for reducing the impact of the sound
may be explored.
Vibrations can be addressed by the fitment of supports or dampers. Noise can be reduced
by mounting baffles and planning the location of the transformer.
Location of a transformer plays a crucial part in the level of noise. A transformer located in a
corner of a building with walls on three sides will have its noise amplified.
135
If the transformer is to be placed in a solid mass such as concrete which cannot vibrate, a
solid mounting is preferred.
The construction of a Wall around the Transformer can help contain the transformer noise
within a small area.
Use of Double Walls: Double Walls or limp walls are arrangements which contain two glass
plates between which is a viscous liquid. The viscous liquid helps in damping the noise as it
passes through.
All the components inside the transformer should be rigidly fixed by using spacers.
All external connections such as cables, etc should be attached by means of flexible
couplings.
Q- Ampacity - an introduction
Ampacity or 'ampere-carrying capacity' refers to the ability of a conductor such as wires,
cables or busbars to carry current without getting damaged due to overheating.
The ampacity of a conductor should be optimimum with respect to the application. A lower
ampacity would result in heating and damage to the insulation. An excessive ampacity
selection would result in unnecessarily high costs.
Lightning arrestors can deteriorate over a period of time due to factors such as dust, cracks,
moisture ingress, degradation of the zinc oxide elements inside, etc. This can lead to failure
of the lightning arrestor. When a lightning arrestor fails, it usually explodes causing a
flashover and damage to the other equipment such as PTs, CTs, etc. Hence, it is imperative
that the lightning arrestors in the system are kept in a healthy condition.
The usual tests carried out on Lightning arrestors are the Insulation Resistance Tests and
136
the Hipot Test.
Hipot Test:
The Hipot test is conducted at about 175% of the rated voltage. In addition to these tests, a
visual inspection of the lightning arrestors for cracks, dust accumulation, broken fitments is
also useful. In the event of system overvoltages or adverse weather conditions such as
thunderstorms, the lightning arrestors need to be tested more frequently
Surge capacitors are special capacitors connected to transmission lines. The function of
these capacitors is to absorb the surge caused by waves which travel along the transmission
lines.
The Surge Capacitor is always connected to the power supply. When the Surge appears it
absorbs the surge, holds it on for sometimes and then releases it into the system.
Surge Capacitors have a very fast response time as they are continually in circuit. However,
the limitation of the Surge capacitors is that it cannot absorb a high current surge. High
current surges can only be discharged by lightning arrestors. Hence, the Surge capacitor is
usually connected along with a lightning arrestor.
Thus, when a capacitor is switched off, it still contains charge. Hence, an engineer working
on a capacitor that has not been discharged can get an electric shock. It is, therefore, vital
that all capacitors and other energy storage devices be discharged prior to service. Power
capacitors usually have a resistor known as a bleeder resistor connected in parallel. The
137
function of this resistor is to discharge the capacitor once the power supply has been
removed.
These resistors are usually designed to reduce voltage across the capacitor to less than 50V
(the permissible safe voltage for humans) within 5 minutes.Hence, service work in a
capacitor should be started only after five minutes. As a final precaution, the capacitors
need to be discharged manually prior to starting the work.
Such capacitors need to be handled carefully. Always contact the capacitor manufacturers
on handling or disposing the capacitor units.
Vents are provided in some capacitors as a defence against bulging. Vents need to be
periodically checked for rupture which may indicate failure.
Q- Overfluxing in Transformers
The transformer works on the principle of mutual induction between the primary and
secondary windings. The induction is caused by the constantly varying magnetic flux that
links the two windings. The flux density in the windings is directly proportional to the
induced voltage and inversely proportional to the frequency and the number of turns in the
winding.
magnetostrictive forces can also cause damage. The winding temperatures may also
increase due to the heat produced.
The magnetic flux density is dependent on the current flowing through the primary windings
in a transformer. This current is dependent on the voltage applied across the windings and
the winding impedance. The impedance is dependent on the frequency of the applied
voltage. If the nominal voltage is applied at a reduced frequency, the low inductive
reactance will cause a higher current to flow through the windings.
138
the generator and consequently the frequency of the power falls, the same system voltage
induces a higher magnetic flux. Modern Automatic Voltage regulators are equipped with
V/Hz limiters which limit the voltage in accordance with the frequency.
These relays are faster than electromagnetic relays. More importantly, the provide isolation
between the control and the power circuits.
These relays do not have any moving parts which can deteriorate due to arcing or
operational wear. However, they are expensive over conventional relays and hence still find
limited application.
• Smaller Size
• Faster Response time
• Noiseless operations as there is no mechanical movement of the contacts.
• Optocoupler relays can withstand high vibration compared to conventional relays
• They do not generate Electromagnetic radiation as there is no coils to be energized.
139
Q- Zero-Switching of Transformers
When inductive loads such as transformers or motors are switched on, a sudden rush of
current into the winding is observed. This is known as the inrush current. Typically, the
inrush current is around 5 to 6 times of the rated value. This is due to the absence of the
back-emf when the winding when the power is first applied. This sudden surge of current
causes disturbances in the system voltage and sometimes spurious operation of relays. The
high current also causes stress on the windings of the machines.
There are a number of methods to address this problem. Adding resistors in series to the
winding and then gradually taking them out of circuit is one option. Another option is the
use of softstarters which raise the terminal voltage of the machines gradually. Zero
crossover switching is one method of addressing the issue of high inrush current when
switching on inductive equipment. The method involves the use of Static Relays consisting
of devices such as SCR or TRIACs. These devices switch on when the sinewave crosses the
zero point so that the voltage is gradually increased. This, in some circumstances, reduce
the inrush current.
However, this methods has its downsides too. There have been reports that if the zero cross
over switching is carried out on a core that is already saturated from previous operation,
extremely high currents can result.
Apart from inductive loads, inrush currents is also observed in resistive loads such as
filament lamps. In filament lamps the resistance when the filament is in the cold, that is,
switched off condition is lesser than the resistance when the lamp is in the switched on
condition. This is due to the positive temperature co-efficient of resistance. When the lamp
is switched on from the cold condition, there is a high surge of current which continues till
the temperature of the resistance increases. Zero-crossover switching in resistive loads can
ensure a smoother increase in current value to the steady-state condition.
Q- Zero-Switching of Transformers
When inductive loads such as transformers or motors are switched on, a sudden rush of
current into the winding is observed. This is known as the inrush current. Typically, the
inrush current is around 5 to 6 times of the rated value. This is due to the absence of the
back-emf when the winding when the power is first applied. This sudden surge of current
causes disturbances in the system voltage and sometimes spurious operation of relays. The
high current also causes stress on the windings of the machines.
There are a number of methods to address this problem. Adding resistors in series to the
winding and then gradually taking them out of circuit is one option. Another option is the
use of softstarters which raise the terminal voltage of the machines gradually. Zero
crossover switching is one method of addressing the issue of high inrush current when
switching on inductive equipment. The method involves the use of Static Relays consisting
of devices such as SCR or TRIACs. These devices switch on when the sinewave crosses the
zero point so that the voltage is gradually increased. This, in some circumstances, reduce
the inrush current.
However, this methods has its downsides too. There have been reports that if the zero cross
over switching is carried out on a core that is already saturated from previous operation,
extremely high currents can result.
Apart from inductive loads, inrush currents is also observed in resistive loads such as
filament lamps. In filament lamps the resistance when the filament is in the cold, that is,
140
switched off condition is lesser than the resistance when the lamp is in the switched on
condition. This is due to the positive temperature co-efficient of resistance. When the lamp
is switched on from the cold condition, there is a high surge of current which continues till
the temperature of the resistance increases. Zero-crossover switching in resistive loads can
ensure a smoother increase in current value to the steady-state condition.
Q- AutoTransformers
Autotransformers are transformers which contain only one winding unlike two windings in
the conventional transformer. The same winding, therefore, serves as the primary and
secondary windings.
141
Autotransformers are used generally for voltage conversion of equipments from one voltage
to another such as from 110V to 220V or vice versa.
However, the autotransformer does not provide isolation between the primary and the
secondary. Hence, there may a need to connect external filtering or suppression circuits.
Thus, in the event of a failure of the insulation between the turns of the winding, there are
chances of the primary voltage appearing on the secondary.
Another aspect which needs to be checked is the neutral point. If the neutral point is not at
ground potential in the primary, the secondary neutral wil also not be at ground potential.
The autotransformer has higher voltage stability and better overload transformers than the
ordinary transformers.
A Variac is a variable autotransformer with movable taps. Thus, it provides variable output
voltage for a steady input voltage. The taps can be adjusted by a movable knob.
In the autotransformer the primary and secondary windings are joined together, with part
of the winding belonging to both primary and secondary, and are wound on a single "leg" of
laminated core. The autotransformer uses the principle of self-induction.
142
oriented so that its voltage directly adds to the primary voltage:
Next, the "bucking" configuration. Here, the secondary coil's polarity is oriented so that its
voltage directly subtracts from the primary voltage:
The prime advantage of an autotransformer is that the same boosting or bucking function is
obtained with only a single winding, making it cheaper and lighter to manufacture than a
regular (isolating) transformer having both primary and secondary windings.
When power to inductive loads such as coils and inductors is turned off, there is a sharp
voltage spike. The direction of this voltage is opposite to the applied voltage in accordance
with Lenz’s Law.
When a current flows through the coil of a relay, the coil gets electromagnetically charged.
The energy is stored in the magnetic field around the coil. When the power supply to the
coil is interrupted and the current in the coil tends to decrease, the magnetic field
discharges causing a surge in the voltage.
The voltage, thus induced, can jump across the contacts of relays connected to the coils.
The sparks and arcing produced can affect the life of the contacts. The voltage spikes can
also damage electronic components like transistors which may be driving the relay coils.
Freewheel diodes are connected in reverse bias vis-à-vis the supply voltage. Hence, when
the voltage spike appears in the opposite direction, they are short-circuited through the
diode. The voltage spike is thus short-circuited across the coil. This protects the connected
circuits.
143
Q- What is the difference between Salient and Non-Salient Pole Rotors used in
Synchronous Generators
Rotors used in Synchronous alternators can be classified into 1)Salient and 2)Non-Salient
Pole Rotors. Salient pole rotors are used in application with speeds from 100 to 1500rpm.
They are alternative known as "projected pole" type of rotors. The poles mounted on the
rotor are made of laminations made of steel. The poles are connected to the rotor shaft by
means of dovetail joints. Each pole has a pole shoe around which the winding is wound. The
salient pole rotor is generally used in applications where the prime mover is a hydel turbine
or a combustion engine which have low or medium speeds. Salient pole rotors usually
contain damper windings to prevent rotor oscillations during operation.
Non-salient pole rotors are generally used in application which operate at higher speeds,
1500rpm and above.
The prime movers in these applications are generally gas or steam turbines. These are
sometimes known as "drum rotors". The rotor is a cylinder made of solid forged steel. The
slots on which the windings are fixed are milled on the rotor. The number of poles is usually
2 or 4 in number. Since these rotors are cylindrical, the windage loss is reduced. The noise
produced is also less. These rotors have higher axial length. These rotors do not need
damper windings.
144
when a conductor carrying current is placed in a magnetic field, a potential is induced across
the conductor, transverse to an electric current in the conductor and a magnetic field
perpendicular to the current. It is caused as the charge
A clampmeter which works on the Hall effect has a sensor known as the Hall element. The
Hall element is subjected to the magnetic field caused by the flow of current to be
measured. This causes a small voltage across the Hall element. This voltage is amplified and
measured.
Corona are caused when the air around an energized conductor gets ionized, causing a
discharge. Corona are caused when defects are present in the conductors such as jagged
edges or cracks which cause high local electric field. A hissing sound can also be heard
during the occurence of Corona.
The Nitrogen molecules in the air get excited and result and cause ultraviolet radiation.
Corona is sometimes visible as a hazy blue light around conductors, especially during the
night.
Effects of Corona
1. Corona is accompanied by the creation of ozone and nitrogen oxides. Nitrogen oxides
may react with moisture in the air and form nitric acid a potentially corrosive
substance.
2. Corona can cause damage to insulators used in High voltage applications.
3. Corona emissions are accompanied by the generation of radio waves which can
interfere with commercial radio transmission. Sometimes, Corona can also result in
noise which may disturb the neighborhood.
4. It can sometimes cause carbon deposits which may later result in arcing.
Corona can also be used to identify problems. Corona in power transmission lines indicate
the presence of dirt or other substances on power lines and may require cleaning.
The degree of corona will vary with the humidity. In high humidity conditions, corona can
develop into a flashover which can cause trippings and damage to equipment.
145
Prevention of Corona
One of the means of reducing corona in transmission lines has been to increase the radius
of the conductors. This leads to decreased electrostatic field stress on the air around the
conductor and prevents the initation of the corona. ACSR conductors ( see article on ACSR
conductors) which have a greater radii than steel conductors suffer less from the effects of
corona.
Q- Skin Effect
Skin Effect refers to the tendency of alternating current(AC) to flow along the outer
surface(skin) of the conductor rather than through the entire cross-section of the conductor.
Skin Effect is caused due to eddy currents form due to the magnetic fields created when
current flows through the conductor. These eddy currents are strongest near the centre.
The magnetic fields oppose the flow of the current. Hence, the current finds it easier to flow
across the periphery of the conductor.
Conductors which carry AC such as busbars in substations are made hollow for this reason
as current flows only along the surface. The Skin effect becomes more pronounced at higher
frequencies. That is why radio antennae are made hollow.
Conductors in overhead lines and in cables are generally made of strands instead of one
solid conductor. Skin Effect does not occur when conducting DC.
Q- Partial Discharge
Partial Discharge is a type of electrical discharge which occurs in insulating materials which
are located between two conductors as in cables or windings. As the name suggests, the
discharge is partial without completely bridging the two conductors.
Partial discharges usually occur in voids in the insulation of cables and windings as the di-
electric constant of the voids are significantly lesser than the surrounding insulating media.
They can also appear across bubbles in liquid insulating media such as in breakers or
transformers. In gaseous media, they can appear as corona around an electrode. Corona
can be seen in wet weather in power lines.
Partial Discharge occurs usually in insulation which has been subjected to mechanical and
electrostatic stress or which has been weakened by premature aging due to adverse
environmental conditions. Once initiated, Partial Discharge results in the formation of
electrical trees which can accelerate the failure of the cable causing a short-circuit between
two conductors or an earth fault. They can appear as "tracking" or distinct pathways in the
cable insulation. Partial discharge can also be caused by improperly terminated/jointed
connections in HV cables and windings.
The currents which flow during Partial discharge are extremely small and last for very short
periods of time of the order of nanoseconds. This makes them difficult to measure. Partial
Discharges generally dissipate energy in the form of heat, light and sound.
There are a wide range of methods(Partial discharge Analtysis) to detect and monitor Partial
Discharge. Acoustic sensors detect the ultrasonic frequency noises which occur when a
partial discharge is taking place. There are also inductive and capacitive sensors which can
detect Partial Discharges
146
Q- Flash-Overs
A Flashover or an arcing fault occurs when current flows between two conductors or
between the conductor and the ground or a neutral line. A sudden burst of Energy is
released during an arcing fault.
The high current which flows during a flash over can cause a sudden blast of energy in the
form of heat, light and sound.
Personnel who come in contact with the arc or are in the vicinity of the fault can face
serious injuries such as burns, damage to sight and hearing. Sometimes, Flashovers can
lead to death of personnel. The Flashover is usually accompanied by a tremendous pressure
blast which may throw pieces of equipment (shrapnel) over large distances increasing the
chance of injury to people nearby
Flashovers can be caused by a number of reasons such as making contact with energized
equipment accidentally, dropping tools into energized equipment such as busbars,
transformers when working on them. The accumulation of dirt, dust and moisture over
extended periods of time can also trigger flashovers in equipment.
During normal operation, the fuse has a low resistance. However, when the fault occurs and
the fuse ruptures, the heat created by the arcing inside the fuse causes the compacted
quartz sand to create a high resistance environment. This quenches the arc and ensures
that a very rapid fall in current.
The fault is thus cleared within the first half-cycle of the fault within 10 ms. Thus current-
limiting fuses also protect systems from voltage sag in the event of a fault in one part of the
system.
The current limiting fuses contains elements made of copper or silver. The elements are
designed to have constrictions at a number of places which will heat up in the event of a
fault. This enables quick operation. The arcing is also made to occur in a pre-determined
number. The arcing which occurs in many streams enables easy quenching instead of one
single arc. The quenching medium is usually compacted quartz sand.
Current limiting fuses also reduce hazards of arc-flashing, since they are extremely fast
acting and also able to restrict the currents.
Arc flashing occurs when different conductors accidentally come into contact. The resulting
arc can cause flashovers which generate tremendous amounts of heat causing danger to
personnel nearby.
147
Q- Why is Gravel used to pave substation surfaces?
Gravel has many qualities which make it a preferred material for layering surfaces inside
substations. Its high resistivity helps ensure that the step and touch potentials remain
within limits.
It also prevents growth of weeds and small plants. It mitigates the chances of a fire in the
event of oil spillage. It can be easily excavated. Besides, it also prevents the entry and
movement of small animals and reptiles inside the substation. Gravel also prevents the
accumulation of water and the formation of puddles inside the substation. All these features
ensure that gravel is the material of choice for use in substations.
However, the hipot test carries with it the potential failure of the insulation during the
testing process itself. Weak insulation can fail during the test. Hence, many equipment
owners avoid conducting this test. The hipot test certifies that the insulation is sufficient to
withstand excess voltage during
The Hipot test is alternatively known as Dielectric Withstand test. The test involves the
application of a high voltage usually about two times the
operating voltage. Thus a 6.6kV equipment will be tested at a voltage of 13kV.
The test is conducted for 1 minute or five minute. If the hipot test is conducted on a
transformer winding or an alternator winding, the test is conducted on individual phases.
The phases are separated and those phases which are not subjected to the hipot voltage are
grounded.
Test Procedure
Prior to commencing the hipot test, it is necessary to get the Insulation Resistance and the
Polarization Index values for the insulation. This ensures that the windings are free of any
moisture or contamination. A wet or contaminated winding is more vulnerable to fail during
the test.
The hipot test voltage is applied to the winding terminals to be tested. The voltage is
148
sustained for one minute or five minute and then reduced. The current during the test
period is also studied. Should there be a failure during the testing. There wil be a surge in
the current which will cause the MCBs in the hipot test kit to trip.
There are two methods of raising the voltage to the value of the test voltage. They are
Step Test
In this method, the test voltage is raised gradually in small incremental steps. This enables
the tester to abandon the test if he suspects that any current increase which may indicate a
weak winding.
Ramp test
In this method, the test voltage is raised gradually or ramped up at a specific rate. The
voltage can be increased to the rated voltage along with constant monitoring of the current.
The ramp method is the most effective test as it can avoid any insulation failure during the
test by identifying potential weaknesses in the winding early on.
The Hipot test does not offer scope for analysis such as the Insulation Resistance or the
Polarization Test. It is simple a pass-fail kind of test. It is significant in that it gives
operators the confidence that the equipment is strong enough to withstand the operating
voltage and transient overvoltages in the system.
The high voltage used during the test calls for high standards of safety. The area around the
test location should be cleared of all items not related to the test(clutter). The area needs to
be cordoned off to prevent the entry of unauthorized persons. Personnel should be stationed
at the main power switch so that the switch can be turned at the first sign of any
abnormality. The personnel conducting the test should be properly trained with awareness
of emergency first-aid procedures in the event of an electric shock. The device which is
being tested should be grounded after the test to discharge the capacitance.
XLPE has many qualities which make it extremely useful for cable insulation. It is flexible
permitting smaller bending radius for the cables. It is light weight and water proof. It is also
tough which minimizes the need for armouring.
149
XLPE cables are available for a wide range of voltage ranges from 600V to 154kV.
It is easier to handle and store compared to cables with paper insulation or lead insulation.
They are relatively maintenance free and have simple terminating and jointing procedures.
However, XLPE does have some disadvantages such as high cost, and the formation of
water trees in the insulation due to ageing which result in partial discharge. Hence, recently,
another polymer known as XLVLDPE(Cross linked Very Low Density PolyEthylene) is being
used for cable insulation
Aluminium is a good conductor of electricity besides being cheap. However, its mechanical
properties are not desirable. It is soft and cannot be hardened. It also has low tensile
strength
This problem is resolved by providing a core of steel stranded cables inside an outer layer of
aluminium stranded cables. The steel imparts excellent mechanical properties. Due to the
skin effect, the bulk of the power is transmitted through the outer aluminium layer of the
The amount of aluminium and steel strandings can be adjusted depending on the
requirement for mechanical strength vis-a-vis electrical conductivity.
The conductors are sometimes impregnated with grease to protect against corrosion.
The strength of ACSR conductors is greater than that of copper conductors. The ACSR
conductors also have a higher corona limit as they have a higer diameter.
Q- Losses in a Transformer
The Efficiency of the transformer is the given by
150
(Power output/Power Input)*100
The Efficiency of the transformer is affected by the losses inside the transformer.
These losses can be categorized into three types
Iron Losses
These are losses caused by the heating of the conductor when current is passes through it.
They are also known as I2R losses as the heat generated is proportional to the formula
H=I2R
Core Losses
Core losses are the losses which occur in the core of the transformer. There are two kinds of
core losses, They are Hysteresis Loss and Eddy Current Losses
Hysteresis losses occur when the magnetic orientation of the molecules inside the core
are reversed when the magnetic field changes. This reversal of orientation of the molecules
results in the generation of heat.
Eddy current losses occur due to circulating currents in the form of eddies which are
generated in the core. These eddy currents generate heat.
Stray losses
These are losses which occur due to the leakage of the magnetic flux of the transformer.
This leakage can cause eddy currents in the fitments of the transformer such as the tank,
channels, bolts, etc.
However, there is one issue to be considered when designing a protection for a generator.
In the event of a short circuit, the fault current is very high for a few milliseconds after a
fault. This heavy current causes the generator voltage to drop. This drop in voltage causes
the current to decay. Therefore, a high overcurrent setting may not operate in the event of
a short-circuit.
To solve this problem, voltage dependent overcurrent relays bias the overcurrent setting
with the measured voltage. That is, at normal voltage, the overcurrent relay operates if the
current exceeds the setpoint. However, if there is a voltage drop, the overcurrent setting
151
also progressive
decreases according to the biasing. Thus, at lower voltages, the current required to operate
the relay is very low.
A variation of the voltage-dependent relay is the voltage controlled. This relay has an
undervoltage setting and a overcurrent setting. The overcurrent setting is set at a value less
than the rated current of the generator. For the relay to operate, both the undervoltage and
the overcurrent need to occur at the same time. This can occur only at the instant of a short
circuit.
Q- Transients - An Overview
A Transient can be defined as a momentary change in a parameter such as voltage, current
or frequency that occurs when a system changes from one steady state operating condition
to another. Transients occur during switching on and switching off loads, during starting
motors, etc.
Impulsive Transients
They are usually caused by lightning. These transients do not have any impact on the
system frequency. They cause a very sharp change in either the voltage or the current.
However, the change is in only one direction, the positive or the negative side i.e. they are
unidirectional.
They are characterized by a sharp rise followed by a decay. For instance a 1.5 x 60
microsecond, 2500V surge cause the voltage to rise to 2500V in a period of 1.5
microseconds. This will be followed by a decay to 50% of the voltage value in 60
microseconds.
The impulsive transient may appear differently in the waveform from different points in the
system as it is a fast-changing phenomenon. This is because the transient can be modified
by various components of the power system.
152
Oscillatory Transients
They differ from impulsive transients in that they are bi-directional, they occur on both the
positive and negative sides of the waveform. Oscillatory transients can be classified into
High, Medium, and Low Frequency Transients depending on the primary frequency of the
transient.
High frequencies, with a primary frequency greater than 500 kHz, are caused by a reaction
of the system to an impulsive transient. Impulsive transient can excite the natural
frequency of the power system which can cause oscillations.
Medium Frequency Transients, with a primary frequency ranging from 5 to 500 kHz, are
known as Medium frequency transients. They are generally caused by switching capacitor
banks or charging large cables.
Low frequency transients have a primary frequency less than 5 kHz. They are usually
caused by transformer energization and Ferro resonance.
Q- Reclosers - An Introduction
Reclosers are useful in distribution lines, where some of the overcurrent conditions are
temporary in nature and clear quickly. They ensure that the system is normalized quickly.
After isolating a system, the recloser closes again after a preset time to see if the fault has
been cleared. If the fault persists, the recloser trips again. It closes again for a few more
times to see if the fault has cleared. Then it locks the system and permanently isolates it.
153
medium for arc extinction. They also contain coils for opening and closing, besides sensing
transformers.
The tripping coils of reclosers are powered by the fault current which flows through the
system. Unlike circuit breakers, where the closing coil is powered by an auxiliary supply, the
reclosers are powered by a transformer which is located on the source side.
In the case of an undervoltage, the low voltage causes the torque developed to reduce. This
results in an increase of slip and a reduction in speed. The motor tries to reduce the slip by
drawing more current. This overloads the motor and can cause overheating.
Principle
The Tan Delta test works on the principle that any insulation in its pure state acts as a
capacitor. The test involves applying a very low frequency AC voltage. The voltage is
generally double the rated voltage of the cable or winding.
A low frequency causes a higher value of capacitive reactance which leads to lesser power
requirement during the test. Besides, the currents will be limited
In a pure capacitor, the current is ahead of the voltage by 90 degrees. The insulation, in a
pure condition, will behave similarly. However, if the insulation has deteriorated due to the
entry of dirt and moisture. The current which flows through the insulation will also have a
resistive component.
This will cause the angle of the current to be less than 90 degrees. This difference in the
angle is known as the loss angle. The tangent of the angle which is Ir/Ic (opposite/adjacent)
gives us an indication of the condition of the insulation. A higher value for the loss angle
indicates a high degree of contamination of the insulation.
Method of Testing
154
The cable or winding whose insulation is to be tested is first disconnected and isolated. The
test voltage is applied from the Very Low Frequency power source and the Tan delta
controller takes the measurements. The test voltage is increased in steps upto the rated
voltage of the cable. The readings are plotted in a graph against the applied voltage and the
trend is studied. A healthy insulation would produce a straight line.
The test should be continued only if the graph is a straight line. A rising trend would indicate
weak insulation which may fail if the test voltage is increased beyond the rated voltage of
the cable.
There are not standard formulae or benchmarks to ascertain the success of a tan delta test.
The health of the insulation which is measured is obtained by observing the nature of the
trend which is plotted. A steady, straight trend would indicate a healthy insulation, while a
rising trend would indicate an insulation that has been contaminated with water and other
impurities.
155
“Fall of Potential” Method:
The Earth resistance is measured using the “Fall of Potential” Method. The method works by
injecting a constant current between two spikes which are inserted into the ground and
measuring the voltage at points between them (as shown in the figure)
The “Fall of Potential” Method is a three terminal test. The electrode whose earth resistance
is to be measured is disconnected from the system or earthing grid. The earth meggar has a
current terminal, a voltage terminal and a common terminal. The common terminal is
connected to the electrode,
Equal lines of potential
When an electrode is inserted into the ground and current flows through it, the potential
around the electrode takes the form of concentric circles of equal potential.
It is essential that the equal lines of the common terminal and the current terminal do not
overlap. Therefore distance between the ground electrode to be tested and the current
terminal is vital. The distance should be sufficient so that the equal lines of potential of the
common terminal and the current terminal do not overlap.
Method of Measurement:
The readings are taken at points close to the ground electrode and then gradually away
from it. The resistance readings in ohms are plotted against the distance in a graph. The
graph should take the form as below. At around 62% of the distance between the ground
electrode and the current terminal, the graph levels off. This reading is taken as the value of
the earth resistance. This point should be outside the equipotential zones of both the
current terminal and the ground electrode
Q- Polarization Index
Polarization Index is an indicator which gives an idea of the cleanliness of the windings. It is
a ratio of the Insulation Resistance Measured for 10 minutes to the insulation resistance
value measured after 1 minute. Since it is a ratio; it does not have any units.
The Polarization Index should be above 2.0 to be permissible. Machines having PI below 2.0
cannot be operated. The Polarization Index does not have any significant relation with
temperature upto 50 deg. C. However, the Polarization Index test should not be conducted
at a temperature beyond 50 deg. C
In the normal operation of machinery, the insulation is subjected to moisture, oil, dust,
electrostatic stress due to machine operation and a host of other elements. Hence,
insulation ages and deteriorates. It is vital that the health of the insulation be monitored
continually to avoid sudden, catastrophic failure of machines.
Principle of Insulation Resistance Measurement
156
The method used to measure insulation resistance is based on Ohm’s law. A high voltage is
applied across the resistance; the current that flows through the insulation is measured. The
ratio of voltage and current gives the resistance. The value of the insulation resistance is
usually in the order of mega ohms
The instrument used to measure Insulation Resistance is known as the Megger. It is similar
in principle to the ohmmeter except for the fact that a higher voltage is used. The typical
meggars have a test voltage of 500V, 2500V or 5000V. The Meggar has a high internal
resistance hence, there it is safe to use despite the high voltage generated. The meggar has
The test voltage appears on the “Line” Terminal. This terminal is connected to the winding
whose insulation needs to be checked. The “Earth” Terminal is connected to the ground. The
“Guard” Terminal is connected to the surface of the insulation to measure the surface
currents which tends to flow along the surface of the insulation.
The winding to be tested should first be isolated. The other windings of the machine which
are not being tested should be connected to the ground. The voltage is applied to the
winding and the reading is taken after about 60 seconds. The reading is noted. After the
test is over, the winding needs to be “discharged”. This is because the insulation acts as a
dielectric forming a capacitor between the winding and the earth. This can store charge and
can deliver a shock if not discharged. Discharging can be done by connecting to the ground.
The Insulation Resistance thus measured is usually in the order of mega ohms. A general
rule of the thumb is that the minimum value should be greater than 1 mega ohm for every
1kV rating of the machine. Thus, for a machine rated for 11kV, the minimum acceptable
value would be 11 mega ohms. Temperature has a direct impact on the value of the
Insulation Resistance. The Insulation Resistance decreases with increase in temperature.
Thus the values should be normalized for a standard temperature.
That is, a value measured at 20 deg. C cannot be compared with a value measured at 30
deg. C. The value at 30 deg. C needs to be corrected. A general rule of thumb is that the
insulation resistance decreases by a factor of 2 for every 10 degree rise in temperature.
Hence, the value taken at 30 deg. C needs to be multiplied by a 2 to get a value corrected
to 20 degrees.
157
The Insulation Resistance of a machine depends chiefly on the dryness of the windings. The
entry of moisture into the windings lowers the Insulation Resistance. The ingress of
moisture can be prevented by ensuring that the windings are kept dry. Special heaters
known as anti-condensation heaters are provided in machines to keep them dry. It must be
ensured that these heaters are kept on.
If machines are found with low Insulation Resistance values below the permissible limits,
heating the windings by connecting lamps around them is an effective method of driving
moisture from the windings. If no improvement is seen even after heating, other reasons
such as insulation wear or deterioration can be suspected.
Other parameters related to the health of the Insulation are the Polarization Index(PI), tan
delta, hipot test, step test, etc
The net resultant flux being zero does not induce any current in the secondary of the
transformer. Thus the secondary current of the core balance current transformerwhen all
the three phases are healthy is zero.
When an earth fault occurs in one of the phases, the zero-sequence fault current which
flows is not cancelled by the flux of the other two phases and hence induces a current in the
secondary.
The core balance current transformer can be connected to an earth fault relay which can be
used to generate the tripping signal.
158
Q- Checking the Polarity of Current Transformers
The Polarity of current transformers is extremely important. Just like a battery, a current
transformer too has a polarity. The polarity determines the direction of the secondary
current in relation to the primary current.
Wrong connection of the current transformers can cause false operation of the protection
relays. Hence, it is vital to ensure that the current transformers are connected with the
correct polarity.
A DC source is connected with the positive terminal to P1 and the negative terminal to P2.
An analog voltmeter is connected to the secondary terminal of the CT. The positive terminal
of the meter is connected to terminal S1 of the CT while the negative is connected to
terminal S2.
A contact is momentarily made through the switch. The contact is made for a second and
broken. This is important as continuous contact can short-circuit the battery. The
momentary make-break contact causes a deflection in the analog multimeter in the positive
direction, if the polarity is correct.
If the deflection is negative, it indicates that the polarity of the current transformer is
reversed. The terminals S1 and S2 need to be reversed and the test can be carried out.
When batteries of different ampere hour ratings are connected in series, it is necessary to
ensure that none of the batteries is discharged beyond its capacity. This is because if a
battery connected in series in a battery bank is discharged to its maximum, the voltage of
this battery will become zero. This will cause a voltage from the other batteries to be
applied across the battery in the wrong direction. This can cause damage to the battery
159
Q- Dissolved Gas Analysis
Dissolved Gas Analysis is an extremely useful testing procedure that is used to give
information about the condition of the windings inside a transformer. It is also an effective
tool in diagnosing abnormal conditions that may arise during normal operation
During a fault inside the transformer, gases are created as the polymeric compounds of the
oil and the winding insulation, usually cellulose, are broken down to form simpler gases
such as ethylene, methane, carbon monoxide, nitrogen, etc.
The type and the quantity of the gas evolved is dependent on the nature of the fault inside
the transformer.
The reasons for the evolution of fault gases can be classified into three types ,
The type and quantity of the gas evolved is dependent on the nature of the fault.
Pyrolysis,
Pyrolysis refers to the splitting of large organic compounds in oil and the insulating cellulose
due high temperature.The pyrolysis of oil leads to the generation of gases such as methane,
ethane, ethylene and hydrogen. When cellulose is pyrolysed, it results in carbon-di-oxide or
carbon monoxide.
Arcing
Arcing is caused due to electrical faults in the alternator such as short-circuits or earth
faults. Hydrogen and Acetylene are the gases which are generally evolved during faults of
this nature.
Corona
Corona or Partial discharge is caused by the ionization of gas or oil around a high voltage
conductor. Corona in transformers causes the creation of gases such as hydrogen, carbon
monoxide and carbon di-oxide.
Dissolved Gas Analysis (DGA), as the name suggests, refers to the analysis of the various
gases which are created during a fault conditions and are present in a dissolved form in the
oil used for cooling inside the transformer. A sample is extracted from the oil of the
transformer. The gases dissolved are extracted for analysis. The nature and quantity of each
gas is analysed.
By identifying the type of the gas and the quantity, it is possible to identify the nature of the
fault which could have led to that particular gas.
A periodic or continual analysis of the evolved gas helps in the monitoring of the health of
the transformer. Hence, gas analysis occupies an important place in the maintenance
schedule of the transformer.
Q- Ripples in dc systems
Ripples are the constantly varying voltages found in the output of rectifiers. The output of a
rectifier produces a pulsating voltage, which rises from zero to maximum Vp and then to
minimum. This voltage is not suitable to be used in electronics as it contains ripples. The
160
ripples need to be filtered by a filter circuit which is usually a capacitor connected in parallel
Ripple factor
The amount of ripples in a dc source is indicated by the ripple factor which is defined as the
ratio of the rms value of the ripple voltage to the absolute value of the dc voltage.
Thus if we have 10V dc supply with a variation between 9.5 to 10.5 volts, the ripple factor
would be (.5/5)*100 which indicates a ripple factor of 5%.
The peak-to-peak value of the ripples at the output of a full wave rectifier is given by
Vpp=I/2fC
Vpp=I/fC
where I is the current in the circuit, f is the frequency and C is the value of capacitance that
is connected in parallel to filter the ripples
Measuring Ripples
Ripples can be measured in the field by an ordinary multimeter. Set the multimeter to
measure AC voltage, and check the voltage at the output of the power supply. Any ripples
would reflect as an AC voltage. Now, set the multimeter to dc voltage and measure the
actual dc output. The Ripple factor is the ratio of the ac voltage to the dc voltage.
Effects of Ripples
Ripples can cause failure of components such as capacitors and can cause heating and
failure in certain electronic components.
In audio circuits, the ripples can be reflected as noise, as the frequency of the ripples is
within the audio band.
Ripples can also interfere in TV displays
161
Q- Using Broken Delta Protection for Earth Faults
The Broken Delta configuration is used to protect against earth faults. It is a configuration
that works by monitoring the vector sum of the phase voltages.
In the event of a ground fault in one phase, the phase-to-ground voltage in the remaining
two phases is now equal to the phase-to-phase voltage with a displacement of 60 degrees.
The voltage at the broken delta becomes 3Vo or three times the phase-to-ground voltage.
This voltage can be measured by a relay and can be used to trip the power system. A
resistor is usually connected across the broken delta connection to prevent Ferro resonance,
a condition that occurs when the line capacitance and the inductance in the potential
transformers reach a state of resonance.
Broken delta transformers are usually marked as 11kV/√3:110 volts. It means that the
transformer is designed that in the event of a ground fault in the primary side, the
secondary output will be 110 V.
Hence, it is imperative that the choice of CT is made with full knowledge of the application
and the number of relays and meters which are to be connected to it. A current transformer
with a wrong burden rating or a wrong accuracy class will seriously compromise the
effectiveness of the measuring or protection system.
The burden of a current transformer is indicated in its nameplate. The burden is rated in VA.
such as 15VA or 25 VA. The rated VA indicates the load the transformer can take.
162
The burden of a current transformer can increase over time as the resistance of the
connecting wires may slightly increase due to age, change in temperature and loosening of
connections. Hence, the current transformer should never be loaded to 100% of its
capacity.
Depending on their application, current transformers can be classified into measuring and
protection current transformers.
Measuring transformers have high accuracy. However, they have a low saturation point.
They are deliberately designed this way, so that the measuring instruments are not
damaged by the high currents during a fault. During a fault, the measuring transformers get
saturated and the output stays within the range of the measuring instruments.
Measuring transformers are classified into 0.1,0.3, 0.5, 1. The values indicate the
percentage error at the rated primary current. Thus a 100/5 transformer with 0.3 accuracy
will have a maximum error of 0.3 when a current of 100 A passes through the primary.
The current transformers used for protection have lesser accuracy as compared to
measuring current transformers. They have a very high saturation limit. This is necessary as
they need to continue sensing the current even at high fault values.
Protection Transformers are classified as 5P10,10P10, etc. The first letter in the notation
indicates the maximum percentage error. The last number indicates the number of times
the rated current. Thus a 5P10 transformer would indicate a maximum error of 5 % at 10
times the rated current.
Application:
When a phase to earth fault occurs in ungrounded 3 phase systems, the phase voltage of
the faulty phase is reduced to the ground potential. This causes the phase voltage in the
other two phases to rise by √3 times. This increase in voltage causes a charging current, Ic
between the phase-to-earth capacitances. The current Ic, which
163
increases to three times the normal capacitive charging current, needs to complete its
circuit. This causes a series of restrikes at the fault locations known as arcing grounds. This
can also lead to overvoltages in the system.
A Petersen coil consists of an iron-cored reactor connected at the star point of a three phase
system. In the event of a fault, the capacitive charging current is neutralized by the current
across the reactor which is equal in magnitude but 180 degrees out of phase. This
compensates for the leading current drawn by the line capacitances.
Where IC is the resultant charging current that is three times the charging current of each
phase to ground.
Consider a Petersen coil connected between the star-point and the ground with inductive
reactance ωL, then
The current flowing through it is given by IL =Vp/ωL
The value of the inductance in the Petersen coil needs to match the value of the line
capacitance which may vary as and when modifications in the transmission lines are carried
out. Hence, the Petersen coil comes with a provision to vary the inductance.
Following is the list of the functions. The codes are sometimes followed by an alphabet
which gives some additional information for instance, the code 51G may indicate an
overcurrent ground relay. 50N may indicate a ground sensitive overcurrent relay based on
neutral current measurement. 87T may indicate that a differential relay may be used for
Transformer protection.
164
ANSI codes for Protection Functions
1 - Master Element
2 - Time Delay Starting or Closing Relay
3 - Checking or Interlocking Relay
4 - Master Contactor
5 - Stopping Device
6 - Starting Circuit Breaker
7 - Anode Circuit Breaker
8 - Control Power Disconnecting Device
9 - Reversing Device
10 - Unit Sequence Switch
11 - Reserved for future application
12 - Overspeed Device
13 - Synchronous-speed Device
14 - Underspeed Device
15 - Speed - or Frequency, Matching Device
16 - Reserved for future application
17 - Shunting or Discharge Switch
18 - Accelerating or Decelerating Device
19 - Starting to Running Transition Contactor
20 - Electrically Operated Valve
21 - Distance Relay
22 - Equalizer Circuit Breaker
23 - Temperature Control Device
24 - Over-Excitation Relay (V/Hz)
25 - Synchronizing or Synchronism-Check Device
26 - Apparatus Thermal Device
27 - Undervoltage Relay
28 - Flame Detector
29 - Isolating Contactor
30 - Annunciator Relay
31 - Separate Excitation Device
32 - Directional Power Relay
33 - Position Switch
34 - Master Sequence Device
35 - Brush-Operating or Slip-Ring Short-Circuiting, Device
36 - Polarity or Polarizing Voltage Devices
37 - Undercurrent or Underpower Relay
38 - Bearing Protective Device
39 - Mechanical Conduction Monitor
40 - Field Relay
41 - Field Circuit Breaker
42 - Running Circuit Breaker
43 - Manual Transfer or Selector Device
44 - Unit Sequence Starting Relay
45 - Atmospheric Condition Monitor
46 - Reverse-phase or Phase-Balance Current Relay
47 - Phase-Sequence Voltage Relay
48 - Incomplete Sequence Relay
165
49 - Machine or Transformer, Thermal Relay
50 - Instantaneous Overcurrent or Rate of Rise, Relay
51 - AC Time Overcurrent Relay
52 - AC Circuit Breaker
53 - Exciter or DC Generator Relay
54 - High-Speed DC Circuit Breaker
55 - Power Factor Relay
56 - Field Application Relay
57 - Short-Circuiting or Grounding (Earthing) Device
58 - Rectification Failure Relay
59 - Overvoltage Relay
60 - Voltage or Current Balance Relay
61 - Machine Split Phase Current Balance
62 - Time-Delay Stopping or Opening Relay
63 - Pressure Switch
64 - Ground (Earth) Detector Relay
65 - Governor
66 - Notching or Jogging Device
67 - AC Directional Overcurrent Relay
68 - Blocking Relay
69 - Permissive Control Device
70 - Rheostat
71 - Level Switch
72 - DC Circuit Breaker
73 - Load-Resistor Contactor
74 - Alarm Relay
75 - Position Changing Mechanism
76 - DC Overcurrent Relay
77 - Pulse Transmitter
78 - Phase-Angle Measuring or Out-of-Step Protective Relay
79 - AC Reclosing Relay
80 - Flow Switch
81 - Frequency Relay
82 - DC Reclosing Relay
83 - Automatic Selective Control or Transfer Relay
84 - Operating Mechanism
85 - Carrier or Pilot-Wire Receiver Relay
86 - Lockout Relay
87 - Differential Protective Relay
88 - Auxiliary Motor or Motor Generator
89 - Line Switch
90 - Regulating Device
91 - Voltage Directional Relay
92 - Voltage and Power Directional Relay
93 - Field Changing Contactor
94 - Tripping or Trip-Free Relay
95 - Reluctance Torque Synchrocheck
96 - Autoloading Relay
166
Q- Zig Zag Transformers
Ungrounded systems that need protection against earth faults usually need a grounding
transformer. This is usually a delta-star transformer whose neutral can be earthed. An
alternative way of grounding the system is by using a zig-zag transformer.
The Zig-zag Transformer generally has a ratio of 1:1. It consists of six windings, two for
each phase – . The two windings for each phase(outer and inner windings) are wound on
the same core but in opposite directions.
The windings are connected in a zig-zag fashion. For instance, the primary winding of R
phase may be connected to the secondary of Y, the primary of Y phase would be connected
to the secondary of B. In a perfectly balanced condition, the magnetic fluxes in the primary
and the secondary are able to cancel each other; therefore, their magnetic fluxes cancel
each other out. However, in a fault condition, the magnetic fluxes may not be equal and
hence a fault current may flow through the neutral of the secondary
winding.
Zig-zag Transformers are used to provide earthing for ungrounded systems. They are
advantageous over delta-wye systems due to their low internal impedance and lower cost.
Apart from providing earthing to ungrounded systems, zig-zag transformers can be used to
filter harmonic currents. Zig-zag transformers are connected close the loads that cause
heavy harmonics. Since the transformer has opposing windings, the harmonic currents get
cancelled.
Q- Ingress Protection
Electrical enclosures such as panels,switch boxes and appliances need to be protected
against the entry of foreign objects and water for healthy operation and safety of the
operating personnel. The European Commitee for Electro-technical Standardization has
developed IP(Ingress Protection) ratings which specify the degree of protection the panels
provide.
The IP codes are defined in the IEC standard 60529. The ingress protection of each panel is
in the form of a code such as IP65. The first number indicates the protection against dust
167
and other particles while the second numbers denotes the protection against water.
Object size
Level Effective against
protected against
0 — No protection against contact and ingress of objects
Any large surface of the body, such as the back of a hand,
1 >50 mm
but no protection against deliberate contact with a body part
2 >12.5 mm Fingers or similar objects
3 >2.5 mm Tools, thick wires, etc.
4 >1 mm Most wires, screws, etc.
Ingress of dust is not entirely prevented, but it must not
enter in sufficient quantity to interfere with the satisfactory
5 dust protected
operation of the equipment; complete protection against
contact
6 dust tight No ingress of dust; complete protection against contact
The Second letter indicates the degree of protection of the panel against the entry of water.
168
Q- Neutral Grounding Resistors
Function: NGRs or Neutral Grounding Resistors are used to limit the fault current in a
generator or a transformer during earth faults.
In star connected 3 phase equipment such as a generator or a transformer, the star point is
grounded. In systems where the star point is directly grounded, known as solid earthing,
there is a chance of heavy currents in the windings during an earth fault as the net
resistance is only the soil resistance.
This heavy current, in the order of hundreds of amperes, can damage the windings. Hence,
a series resistance is introduced in the star point. This increases the net resistance in the
event of an earth fault and limits the current. This resistor is known as the Neutral
Grounding Resistor(NGR).
The current flowing in the Neutral Grounding resistor can be monitored. This can be used to
activate the Earth Fault Relay. It is generally mounted with a Current Transformer.
Types:
NGRs can be broadly classified into two types.
Low Resistance Grounding, which limits current to more than 100A and
High Resistance Grounding, which limits current to generally 5 to 10 amperes.
The Choice of the rating of the NGR is made taking into account different factors such as the
rating of the machine, overall fault level of the system and the system capacitance.
The rating of the machine should be kept in mind while deciding on the NGR value. Fault
current should be limited to a value that can be safely handled by the machine. It is also
essential that the fault feeds enough current which can be sensed by the earth fault
protection. Too high a value of the NGR would the limit the current to a very low value
which will not be able to activate the earth fault protection.
The system capacitance is another factor which should be kept in mind. A 3 phase star
connected system forms capacitances with the ground. In the event of an earth fault, this
capacitance can get charged with the line voltage and can cause transient overvoltages. The
value NGR should be chosen in a manner which will permit a let-through current and enable
the capacitances to discharge.
169
Q- Why are the advantages of a three phase system over a single phase power
system?
The three phase power system has been adopted universally for transmission of AC power.
The advantages of a three phase system over a single phase system are:-
Higher power/weight ratio of alternators. A three phase alternator is smaller and lighter that
a single phase alternator of the same power output. Hence, it is also cheaper.
A three phase transmission system requires less copper or aluminium to transmit the same
quantity of power of a specific distance than a single phase system.
Three phase motors are self-starting due to the rotating magnetic field induced by the three
phases. On the other hand, a single phase motor is not self starting, it requires a capacitor
and an auxilliary winding.
In Single phase systems, the instanteous power(power delivered at any instant) is not
constant and is sinusoidal. This results in vibrations in single phase motors.
In a three phase power system, though, the instanteous power is always the same.
Three phase motors have better power factor compared to single phase motors.
Three phase supply can be rectified into dc supply with a lesser ripple factor.
Softstarters are equipment which limit the initial start current of the motors by controlling
the voltage. This is done by means of thyristors. This "soft" starting prevents the
occurence of the high inrush currents. The downside of using softstarters is that the
reduced voltage applied on the stator windings can result in increased slip causing heating
of the rotor.
Another advantage of the softstarter is that it can be used to gradually increase the
torque. In loads such as conveyor belts involving chains and other transmission gear, this
avoids jerks which over time can cause wear on the machinery. The voltage and the torque
are gradually increased to the rated value.
While stopping a motor, the softstarter usually provides the "softstop" function which
involves doing the starting process in reverse. The voltage is gradually reduced to zero this
gradually stops the system avoiding sudden jerky motions due to system inertia.
170
Q- Adding water to the electrolyte level of unsealed batteries.
The electrolyte in the battery is a mixture of sulphuric acid and water. The amount of water
in a battery can fall due to electrolysis or evaporation. This may cause in a drop in the level
of the electrolyte and consequently a drop in the battery output.
Hence, it is necessary to periodically inspect the level of electrolyte in the battery. If the
level of the electrolyte falls below the minimum level, it can be topped up by adding
water. Only distilled water should be added as ordinary water may contain a lot of
impurities and ions which may contaminate the electrolyte.
The level of electrolyte in the battery tends to fall as the battery gets discharged and tends
to rise as the battery gets charged. Hence, water should be added to the electrolyte only
when the battery is fully charged. If the water is added to the battery when it is in the
discharged condition, the level can increase beyond the limit when the battery is fully
charged and may overflow
The acid used as the electrolyte is extremely corrosive and should be handled with extreme
care. Proper protective outfits should be worn while handling them. Water can be added to
a container of acid. However, acid can never be added to container of water as the heat
generated can cause splashing.
Lightning strokes have the ability to discharge thousands of amperes of current in very
short time. This high current needs to be discharged quickly into the earth to prevent the
potential of the tower from rising.
When a tower is struck by lightning, a travelling voltage is induced which moves many times
between the top and the bottom of the tower , the potential of the tower is thus raised. The
elevated voltage also appears on the cross arms of the towers. This can cause back
flashovers if the insulators are unable to withstand the voltage surge.
Back flashovers can be avoided by improving the impulse resistance of the earth point of
the transmission towers and improving critical flashover limits of the insulators.
Back flashovers are identified as line to earth faults.
171
Short Circuit Breaking Current of Circuit Breaker
This is the maximum short circuit current which a circuit breaker can
withstand before it. Finally cleared by opening its contacts. When a short
circuit flows through a circuit breaker, there would be thermal and
mechanical stresses in the current carrying parts of the breaker. If the
contact area and cross-section of the conducting parts of the circuit breaker
are not sufficiently large, there may be a chance of permanent damage in
insulation as well as conducting parts of the CB. As per Joule’s law of
heating, the rising temperature is directly proportional to square of short
circuit current, contact resistance and duration of short circuit current. The
short circuit current continuous to flow through circuit breaker until the short
circuit is cleared by opening operation of the circuit breaker. As the thermal
stress in the circuit breaker is proportional to the period of short circuit, the
breaking capacity of electrical circuit breaker, depends upon the operating
time. At 160°C aluminum becomes soft and losses its mechanical strength,
this temperature may be taken as limit of temperature rise of breaker
contacts during short circuit. Hence short circuit breaking capacity or short
circuit breaking current of circuit breaker is defined as maximum
current can flow through the breaker from time of occurring short circuit to
the time of clearing the short circuit without any permanent damage in the
CB. The value of short circuit breaking current is expressed in RMS. During
short circuit, the CB is not only subjected to thermal stress, it also suffers
seriously from mechanical stresses. So during determining short circuit
capacity, the mechanical strength of the CB is also considered. So for
choosing suitable circuit breaker it is obvious to determine the fault level at
that point of the system where CB to be installed. Once the fault level of any
part of electrical transmission is determined it is easy to choose the correct
rated circuit breaker for this part of network.
172
making capacity. As the rated short circuit making current of circuit
breaker is expressed in maximum peak value, it is always more than rated
short circuit breaking current of circuit breaker. Normally value of short circuit
making current is 2.5 times more than short circuit breaking current.
173
short period of time. The short circuit current may have two major affects
inside a circuit breaker.
1. Because of the high electric current, there may be high thermal stress in
the insulation and conducting parts of CB.
2. The high short circuit current, produces significant mechanical stresses in
different current carrying parts of the circuit breaker. A circuit breaker is
designed to withstand these stresses. But no circuit breaker has to carry a
short circuit current not more than a short period depending upon the
coordination of protection. So it is sufficient to make CB capable of
withstanding affects of short circuit current for a specified short period. The
rated short time current of a circuit breaker is at least equal to rated short
circuit breaking current of the circuit breaker.
174
2) Like other apparatuses connected to power system, a circuit breaker may
have also to face lighting impulse and switching impulses during its life span.
The insulation system of CB and contact gap of an open CB have to withstand
these impulse voltage waveform amplitude of this disturbance is very very
high but extremely transient in nature. So a circuit breaker is designed to
withstand this impulse peaky voltage for microsecond range only
11 KV 12 KV - -
33 KV 36 KV 70 KV 170 KV
400 KV 420 KV - -
175