Manual Módulo Acromag
Manual Módulo Acromag
USER’S MANUAL
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 3
TB4 TB3
MOUNTING AND
Ac romag
46 45 44 43 42 41 36 35 34 33 32 31
DIMENSIONS
TB4
TB3
RUN
G ND
ST
IN5+
IN4+
IN5-
IN4-
DC+
DC-
(118.9)
4.68
IN P U TS 4, 5 PWR
rails (35mm, type EN50022).
(95.3)
3.75
CL
A CT
LIN K
Model 961E N-4006
Model 962E N-4006 Units may be mounted side-
D FT R S T by-side on 1-inch centers.
IN P U TS 0, 1 IN P U TS 2, 3
IN1+
IN3+
IN0+
IN2+
IN0-
IN2-
IN1-
IN3-
(59.4)
2.34
TB1
TB2
E TH E R N E T
11 12 13 14 15 16 21 22 23 24 25 26
Standards may require that
this device be mounted within
TB1 TB2
an approved metal enclosure
1.05 "T" RAIL DIN MOUNTING 3.90 or sub-system, particularly for
(26.7) DIN EN 50022, 35mm (99.1) 4.35
NOTE: Dimensions Are INCHES (MILLIMETERS). (110.5) applications with exposure to
voltages greater than or equal
MODEL 961/962EN ENCLOSURE DIMENSIONS
to 75VDC or 50VAC.
TB4 TB3
TB3
46 45 44 43 42 41 33 32 31
RUN
GND
DC+
IN5+
IN4+
DC-
IN5-
IN4-
ST
IN3+
IN0+
IN2+
IN0-
IN2-
IN1-
IN3-
RJ45 ETHERNET
TB1
TB2
E THE RNE T
CONNECTOR 11 12 13 14 15 16 21 22 23 24 25 26
and stays ON if an input is out
of range.
REMOVABLE
(PLUG-IN TYPE)
TERMINAL BLOCKS TB1 TB2 Green LINK LED ON if auto-
negotiation has successfully
The toggle switch is used to toggle the module into or out of Default Mode established a connection.
(toggle left), or to reset the module (toggle right). In Default Communication
Mode, the yellow ST LED blinks slowly and the module assumes a fixed Yellow ACT LED signals PHY
static IP address of “128.1.1.100”, a default subnet mask of “255.255.255.0”, network Activity (busy).
a default username of “User”, and a default password of “password00”.
DC
ANALOG I/O PWR ISOLATION BARRIERS
TB4 TB3
TB3
G ND
IN5+
IN4+
IN5-
IN4-
DC+
DC-
RX
DIAGRAM
IN P U TS 0, 1 IN P U TS 2, 3
IN1+
IN3+
IN0+
IN2+
IN0-
IN2-
IN1-
IN3-
TB1
TB2
11 12 13 14 15 16 21 22 23 24 25 26
TB1 TB2
ANALOG I/O ANALOG I/O
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
4 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
PUSH
TB4
TB3
46 45 44 43 42 41 33 32 31
unit towards the rail until it snaps into
GND
DC+
DC-
place. To remove, first separate the PWR
TB1
TB2
11 12 13 14 15 16 21 22 23 24 25 26
DIN rail connector and use it as a
lever to force the connector down Remove Terminal Blocks On This
until the unit disengages from the rail Side To Provide Clearance
PRY WITH SCREWDRIVER
INSERTED IN SLOT HERE
(do not twist the screwdriver to avoid (DO NOT TWIST TO AVOID
DAMAGING PLASTIC TAB)
damaging plastic). PUSH SCREWDRIVER AS SHOWN
TO TILT AND LIFT MODULE OFF RAIL
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 5
Refer to the section “Cable Accessories” at the back of this manual for more CONNECTIONS
information on accessory cables including patch and crossover cables
available from Acromag and other vendors.
Network
TIP: You can significantly enhance the EMI/RFI performance of your
network connections by using Category 5E STP cable (Shielded Twisted
Pair) with shielded RJ45 plug connectors. This will also help to protect your
installation from damage due to ESD (Electro-Static Discharge). The use of
shielded cable is strongly recommended for installations in harsh industrial
environments and/or in the presence of strong electrical fields.
S1 S2
P1
PUSH
or equivalent.
G ND
RUN
DC+
DC+
DC-
TO
DI P SW S1/ S2 PG M
generally not automatic MDI/MDI-X X1
CFG O PTI O NS PO RT
PO W ER
/
ACT
LK
Acromag 9xxEN-4012
ETHERNET
Because the Acromag ethernet switch SWI TCH
X1 X2 X3 X4 Ac ro m a g
Ethernet Modules.
900EN-S005 is automatic MDI/MDI-X RUN ST
01 23
01 23
(Straight-Through or Crossover Cable) ETHERNET
THE ACROMAG ETHERNETSWITCH IS AUTOMATIC MDI/MDI-X AND Order Acromag Cable Model 5035-355 8 9 10 11
THE USE OFSTRAIGHT-THROUGH (MDI) AND CROSSOVER (MDI-X) CAT-5 UTP CABLE LI NK
01 23
(Straight-Through or Crossover Cable) ETHERNET
Acromag offers a straight-through patch cable (Model 5035-355), or a 4 567
crossover cable (Model 5035-360) for use with Series 9xxEN modules. 8 9 10 11
ACT
UP TO 100 METERS RS DA
Ac ro m a g
RUN ST
CH. I / O STATUS
01 23
(Straight-Through or Crossover Cable) ETHERNET
4 567
8 9 10 11
ACT
UP TO 100 METERS RS DA
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
6 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
CONNECTIONS
Connect 15-36V DC to the power terminals labeled DC+ & DC-.
Power Observe proper polarity. For supply connections, use No. 14 AWG
wires rated for at least 75 C. CAUTION: Do not exceed 36VDC peak.
Voltage Current
15VDC 113mA
18VDC 95mA 15 TO 36VDC
TB3 TB3
33 32 31
24VDC 74mA DC+
PWR
+ INPUT POWER
DC- IS ISOLATED
36VDC 55mA GND
EARTH
GROUND
CAUTION: Risk of Electric Shock – More than one disconnect switch may
be required to de-energize equipment before servicing.
IMPORTANT – External Fuse: If unit is powered from a supply capable of
delivering more than 1A to the unit, it is recommended that this current be
limited via a high surge tolerant fuse rated for a maximum current of 1A or
less (for example, see Bel Fuse MJS1).
Analog Inputs Connect analog input signals to the input terminals as shown below
according to your model.
Input is DC current (961EN),
or DC voltage (962EN), Ranges: 0-20mA, 4-20mA,
0-11.17mA, 0-1mA DC.
16 15 14 13 12 11
according to model number. SHIELDED
CABLE
DC I
IN0+
INPUTS 0, 1
Inputs are not isolated CURRENT IN0-
channel-to-channel, except for (961EN) IN1+
small common mode voltage IN1-
SHIELDED
CABLE
+ +
DC IN0+
V
INPUTS 0, 1
VOLTAGE IN0-
(962EN) - -
IN1+
IN1-
N OTE 1
TB1
AC CURRENT
SENSOR INPUT (961EN) 2-WIRE TRANSMITTER (961EN)
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 7
S
E
N Temperature
INP OUT DCS/PLC CONNECTIONS
S Pressure + +
FIELD +24V DC
O Level
XMTR
R Flow - -
+
Analog Inputs
S Speed - +
IN0+
IN1+
IN0-
IN1-
EXCEPT FOR COMMON MODE low level voltages in the range
VOLTAGES LESS THAN +/-5V. AS INPUTS 0, 1 of ±12V (962EN), and ±5V
SUCH, A 4-20mA ISOLATOR MAY BE
REQUIRED FOR CURRENT LOOPS
(961EN). This makes these
WITH LOADS GREATER THAN 250 OHMS. models useful for differential
current and voltage monitoring
S applications similar to the
E INP OUT
N Temperature DCS/PLC examples shown here.
S Pressure + +
FIELD +24V DC
O Level
XMTR
R Flow - -
+
S Speed
250 OHMS
DIFFERENTIAL -
CHART RECORDER
VOLTAGE MONITORING DATA LOGGER
OR TRANSMITTER
NOTE: 962EN INPUTS ARE NOT
962EN
ISOLATED CHANNEL-TO-CHANNEL,
EXCEPT FOR COMMON MODE
16 15 14 13 12 11
+ +
VOLTAGES LESS THAN +/-12V. AS 250
SUCH, A V/V ISOLATOR MAY BE OHMS IN0+
INPUTS 0, 1
962EN
10V
16 15 14 13 12 11
+
IN0+
INPUTS 0, 1
- IN0-
IN1+
IN1-
TB1
Connect Earth Ground as shown in the connection drawings above. Earth Ground
Additionally, connect the GND terminal (TB3-33) to earth ground.
Warning: To comply with
The ground connections noted are recommended for best results. If safety and performance
sensors are already grounded, use caution and avoid making additional standards, use shielded cable
ground connections which could create ground loops. and connect earth ground as
noted. Failure to use good
The plastic module housing does not require earth ground. wiring and grounding practices
may be unsafe and hurt
performance.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
8 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
WEB BROWSER This module supports Modbus over TCP/IP. You may use your own
software to issue Modbus command to this module (see Modbus Registers),
or you may use a standard web browser, as these modules have built-in web
Home Page pages that allow you to setup, control, and calibrate the module. Simply
execute your web browser, type the IP address assigned to your module in
the “Address” window (http://128.1.1.100/ for our example), click [Go], and
you will be presented with a Home Page window similar to that shown below:
The Home Page provides buttons to access the other web pages of this
module that are used to configure the network parameters, change the user
name and password, map inputs to calibrate the module, and operate/test
the module.
For each new browser session that accesses the Home Page of this
module, you will be presented with a window prompting you to enter the
current User Name and Password as shown below. This information is
required before the program will allow you to make any other selections.
The default user name and password is “User” and “password00”
respectively. After entering these defaults, you may wish to invoke the
Password Configuration Page to change these parameters to something
more meaningful to you.
IMPORTANT: If you forget your
installed user name & password,
you can always toggle the module
into default mode via the default
mode toggle switch at the front of
the module. Then the password
and username will revert to the
original defaults noted above,
allowing you to re-invoke the
Password Configuration Page and
change the username and
password settings as required.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 9
Password
Configuration Page
Use up to 20 alphanumeric
characters (case sensitive) to
specify your username, and 10
alphanumeric characters (case
sensitive) to specify a
password. You will have to
type in these entries twice to
help prevent errors (yes, I
know this is annoying).
You can click the “Network Configuration Page” button to set the network Network Configuration
configuration parameters for the module. You may have to consult your
network administrator for help to complete the contents of this page.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
10 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
WEB BROWSER An IP Address is a unique identification number for any host (this module)
on any TCP/IP network (including the internet). The IP address is made up
of four octets (8 bits), each octet having a value between 0-255 (00H-FFH).
Network Configuration It is expressed here in decimal form, with a period placed between octets.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 11
By default, the module is setup to use Static IP Addressing and a Static IP WEB BROWSER
Address of 128.1.1.100. You can optionally choose to have the IP address
assigned dynamically via DHCP/BOOTP or DHCP/BOOTP w/Fallback. This
will also require that you specify a valid Host Name. Note that Network Configuration
DHCP/BOOTP w/Fallback will revert to the static IP address if your DHCP or
BOOTP server cannot be found at the address specified.
The unit includes a default address toggle switch to cause the module to The Default Communication
assume a preset default factory address. This switch is at the front of the Mode uses a static IP address
module and is used to toggle the module into, or out of Default Mode. If you of “128.1.1.100”, a default
use the toggle switch at the front of the module to place the module in subnet mask of
default mode, then “Default Communications Mode” will be indicated at the “255.255.255.0”, a default
bottom of this screen. username of “User”, and a
default password of
Click the Submit button to complete any changes made on this page. “password00”.
Click the Wink On/Off button to toggle the module in/out of “wink” ID mode.
In this mode, the module’s green RUN LED will blink to confirm identification
as an aide to locating a specific module on a network.
Refer to the Technical Reference section of this manual to learn more about
IP Addressing terms and concepts.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
12 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
WEB BROWSER This module includes special messaging functionality (i2o, input-to-output
communication) that allows it to send its input level to an output channel on
an Acromag 972EN-400x or 973EN-400x analog output module. The I/O
I/O Mapping Page Mapping page is used to specify the static IP address of the 972/973EN
(Optional i2o Function) module to send an input channel’s data to, the specific Holding Register
address of that module, and an update rate.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 13
WEB BROWSER
Test Page
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
14 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
WEB BROWSER
Use the scroll bar on the right to scroll down the page as shown below:
Test Page
You can also use the Configuration Control of this page to change the input
range for each channel group (0, 1, & 2 or 3, 4, & 5). For the 961EN shown,
you may select from 0-20mA, 4-20mA, 0-11.17mA, and 0-1mA DC current
ranges. For the 962EN, you may select ±10V, ±5V, ±2.5V, ±1.25V, ±625mV,
±313mV, ±156mV, or ±78mV DC voltage ranges. Note that your range
selection will apply to all channels of the group. Click on “submit” to execute
your range change.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 15
The Calibration Page will allow you to recalibrate each channel’s zero and Calibration Page
span signal as required. Simply select the channel to be calibrated, choose
zero or span, apply the zero or full-scale signal to the input, then click
calibrate. For best results, always calibrate zero before span.
You can choose to use the web browser calibration page above to
accomplish calibration (Method 1, easiest), or via direct register access as
described in Method 2 of the following page.
Your success in recalibrating the input will strongly depend upon the
accuracy and precision of your signal source.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
16 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 17
Upon power-up, the green “Run” LED should light. A continuous blinking TROUBLE-
Run LED indicates “wink” ID mode. If the Run LED remains OFF and
correct power has been applied, then either the internal power supply has SHOOTING
failed or a fatal processor error (firmware) has occurred.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
18 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
TROUBLE- Please refer Acromag Application Note 8500-734 for help in setting up
network communication with your module (located on the CDROM shipped
SHOOTING with your module or via download from our web site at www.acromag.com).
This document gives details for changing your PC’s TCP/IP configuration in
order to communicate with your module (see TCP/IP Properties of Network
Configuration in Windows). For additional information, you may also wish to
download whitepaper 8500-765, Introduction To Modbus TCP/IP.
Trouble Browsing Your If you have carefully followed this procedure and you still cannot browse your
Module? module, you may have the web browser of your laptop or PC setup to use a
proxy server when browsing the web. If you are using Internet Explorer,
Refer to the “Tools” pulldown menu, select “Internet options…”, click the
“Connections” tab, then click the “LAN Settings” button. Locate the Proxy
server information and uncheck the box next to the statement “Use a proxy
server for your LAN”. Then click [OK] to return to the “Connections” screen,
and click [OK] again to save your settings.
You should now be able to use Internet Explorer to browse the module as
required. However, to later restore your PC’s connection to your company
network, you may have to re-enable the use of a proxy server for your LAN.
Getting Out Of Trouble There is no built-in error detection to prevent you from writing invalid values
to a configuration register. As such, if you inadvertently write an invalid value
to an internal register, you could cause the module to become inoperable
under certain conditions. If this happens, in order to regain control of the
module, the module can either be re-downloaded at the factory, or you can
try restoring the module to its initial configuration by following this procedure:
So, your module’s “gone wild”, Procedure For Restoring any 9xxEN Module to its Initial Configuration
follow this procedure to restore
it to its initial configuration and 1. While module power is OFF, press and hold the front-panel toggle
regain control. switch in the default (DFT left) position.
2. While continuing to hold the toggle switch in the default position, apply
power to the module.
3. After a few seconds, the Status LED will begin to blink quickly and you
can release the default switch at this point. The module will continue to
boot itself as it normally does. That is, the green RUN LED will blink for
1-10 seconds as the unit acquires its address, then remain ON for
normal operation.
4. If the STATUS LED fails to blink rapidly after a few seconds and the
RUN LED just blinks for a few moments as it normally does, then
reinitializing the module has failed and you should try it again. This
time, make sure that the DFT switch is completely depressed and held
while powering the unit. Also make sure that you are pressing the DFT
toggle in the DFT direction (left), rather than the RST direction (right).
Note that if you perform the procedure for restoring a module to its original
configuration as outlined above, all of the I/O mapping variables are returned
to their default values and mapping may have to be reconfigured.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 19
TECHNICAL REFERENCE
Safety Agency Approvals – CE, UL, & cUL listed, plus Class I; Division KEY FEATURES
2; Groups A, B, C, D approval.
Fully Isolated – Input channels (as a group), network, and power are all
isolated from each other for safety and increased noise immunity.
Modbus TCP/IP Protocol Support – Supports up to 10 master sockets
(the maximum number of sockets is user-selectable) using the Modbus
TCP default port number 502.
I/O Mapping (i2o) Feature – I/O Mapping feature allows the inputs of
this device to control the outputs of an Acromag 972EN-400x or
973EN-400x analog output module.
Built-In Web Pages - Allows unit to optionally be configured, controlled,
calibrated, and monitored with a standard web browser over ethernet.
Convenient “Wink” ID Mode Support – Blinks green RUN LED in wink
mode as a visual tool to help identify specific remote units on a network.
Fully Independent w/ Direct I/O Connection – Self-contained with no
special bus couplers, power supply, or rack mount required to operate.
Isolated Network Interface – Immune to noise & can operate over long
distances. Allows many modules to network together.
Network Port is Transient Protected – Shielded RJ45 port includes
transient protection from ESD, EFT, and other transients.
10Base-T and 100Base-TX Support – Integrated IEEE 802.3/802.3u
100Base-TX/10Base-T.
Auto-Negotiated 10/100Mbps, Half or Full Duplex.
Flexible Multi-Range Analog Inputs - Accepts either DC current or DC
voltage, according to model number.
Range Variability – The first 3 channels must share the same range,
but this can be different than the range of the last 3 channels.
Optional AC Current Input (961EN Only) - An optional AC current
sensor can be purchased separately to support AC current inputs.
Precise High-Resolution A/D Conversion – Modules use high-
resolution, low noise, sigma-delta analog-to-digital conversion for high
accuracy and reliability.
Plug-In Terminal Blocks & DIN-Rail Mount - Make mounting, removal,
and replacement easy.
Nonvolatile Reprogrammable Memory – Allows the functionality of this
device to be reliably reprogrammed thousands of times.
Operation/Diagnostic LED Indicators Aide Troubleshooting – Yellow
ACT LED indicates port activity (busy). Green LNK LED indicates link
(auto-negotiation complete & connection established). Green RUN LED
indicates power/wink ID mode. Yellow ST LED indicates module status.
Self-Diagnostics & Built In Watchdog - For easy maintenance and
troubleshooting. Includes a hardware watchdog timer built into the
microcontroller that causes it to initiate a self reset if the controller ever
“locks up” or fails to return from an operation in a timely manner.
Wide-Range DC-Power – Wide range diode-coupled for use with
redundant supplies, and/or battery back-up.
Hardened For Harsh Environments - For protection from RFI, EMI,
ESD, EFT, & surges. Has low radiated emissions per CE requirements.
Wide Ambient Operation – Reliable over a wide temperature range.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
20 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
HOW IT WORKS These input modules provide up to six process current (961EN), or six
differential DC voltage (962EN) input channels, and provide an isolated
10/100 Ethernet interface for configuration, monitoring, and control of the
input module. The current input model (961EN) uses precision 24.9Ω
current sink resistors across the inputs. Voltage input models use 10:1
precision resistor voltage dividers at the input. A multiplexer is used to
connect each input voltage to an A/D converter (separate A/D channels
serve 3 input channels each). The A/D converter then applies appropriate
gain to the signals, performs analog-to-digital conversion, and digitally filters
the signals. The microcontroller completes the transfer function according to
the input type and its embedded program. Configuration and calibration
parameters are stored in non-volatile memory integrated within the
microcontroller. A dedicated Ethernet controller handles Ethernet
communication. The I/O terminals and the Ethernet port terminals also
include transient suppression. A wide input switching regulator (isolated
flyback) provides isolated power to the I/O circuits and the Ethernet
controller. Refer to the simplified schematic shown below to help gain a
better understanding of the circuit.
+6V
IN P U TS 0, 1, & 2 MU S T
IN0+ B E S A ME TY P E
IN P U TS 3, 4, & 5 MU S T
IN1+ B E S A ME TY P E
MUX +1.6V
+ 3 .3 V
S RA M
B IA S
(512K x8)
+ 3 .3 V
-6V FLA S H GN D
+6V (512K x8) E A R TH GR OU N D
IN3-
TOGGLE S W ITC H
IN4-
IS OLA TE D IN P U T P OW E R
IN5- 15-36V D C P
M I/O LOGIC 3.3V
D C +O
P OW E R IS OLA TE D
U + FLY B A C K W
IN3+ X S W ITC H E R
A IN 2
I/O P OW E R 5V DC- E
IN4+ -
R
+6V
IN5+
N E G V OLTA GE
-6V
-6V C ON V E R TE R
Note that input types may vary between the two channel groups—channel 0,
1, and 2 may be configured differently from channel 3, 4, and 5. Inputs are
not isolated channel-to-channel, except for small common mode voltage
differences in the range of ±5V (961EN), or ±12V (962EN).
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 21
TCP/IP is the foundation for the World Wide Web and refers to ABOUT MODBUS
Transmission Control Protocol and Internet Protocol. TCP/IP allows blocks
of binary data to be exchanged between computers. The primary function of TCP/IP
TCP is to ensure that all packets of data are received correctly. IP makes
sure that messages are correctly addressed and routed. Note that the
TCP/IP combination does not define what the data means or how the data is
to be interpreted, it is merely a transport protocol.
Modbus is an application protocol. It defines rules for organizing and You can find more information
interpreting data and is essentially a messaging structure that is independent on Modbus TCP/IP by visiting
of the underlying physical layer. It is freely available and accessible to our web site and down-loading
anyone, easy to understand, and widely supported by many manufacturers. whitepaper 8500-765,
Introduction To Modbus
Modbus TCP/IP uses TCP/IP and Ethernet to carry the data of the Modbus TCP/IP.
message structure between devices. That is, Modbus TCP/IP combines a
physical network (Ethernet), with a networking standard (TCP/IP), and a
standard method of representing data (Modbus). A Modbus TCP/IP
message is simply a Modbus communication encapsulated in an Ethernet
TCP/IP wrapper.
In practice, Modbus TCP embeds a Modbus data frame into a TCP frame,
without the Modbus checksum, as shown in the following diagram. The
Modbus checksum is not used, as the standard ethernet TCP/IP link layer
checksum methods are instead used to guaranty data integrity.
TCP FRAME
Modbus Checksum
Not Included
Address Function Code Data Checksum
MODBUS FRAME
Note that the Modbus address field is referred to as the Unit Identifier in
Modbus TCP. In a typical slave application, the Unit ID is ignored and just
echoed back in the response.
A host is any device on any network. On TCP/IP networks, each host has IP Addressing
one or more unique IP addresses. This module connected to an ethernet
network is a host.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
22 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Subnets are further broken down into three size classes based on the 4
octets that make up the IP address. A Class A subnet is any subnet that
shares the first octet of the IP address. The remaining 3 octets of a Class A
24
subnet will define up to 16,777,214 possible IP addresses (2 – 2). A Class
16
B subnet shares the first two octets of an IP address (providing 2 – 2, or
65534 possible IP addresses). Class C subnets share the first 3 octets of an
IP address, giving 254 possible IP addresses. Recall that the first and last
IP addresses are always used as a network number and broadcast address
respectively, and this is why we subtract 2 from the total possible unique
addresses that are defined via the remaining octet(s).
Note that the first node For our Example, if we wish to further divide this network into 14 subnets,
address (0) and node 10 are then the first 4 bits of the host address will be required to identify the
typically reserved for servers subnetwork (0110), then we would use “11111111.11111111.11111111.
and should not be used. The 11110000” as our subnet mask. This would effectively subdivide our Class
last node (255) is a broadcast C network into 14 subnetworks of up to 14 possible nodes each.
address. Node 100 is the
default address of this module. With respect to the default settings of this module:
Use of these node addresses Subnet Mask 255.255.255.0 (11111111.11111111.11111111.00000000)
for any other purpose may IP Address: 128.1.1.100 (10000000.00000001.00000001.01100100)
yield poor performance. Subnet Address: 128.1.1.0 (1000000.00000001.00000001.00000000)
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 23
DHCP refers to Dynamic Host Configuration Protocol and is a method used Dynamic Host
to dynamically assign temporary numeric IP addresses as required. A
Configuration Protocol
DHCP server maintains a pool of shared IP addresses which are recycled.
When a DHCP device wants to use a TCP/IP application, it must request an (DHCP)
IP address from the DHCP server. The DHCP server will check the shared
supply, and if all addresses are in use, the server will send a busy signal to
the client which tells it to try again later. Static addresses will ensure a
connection every time, but dynamic addresses do not.
DNS refers to the Domain Name System or Domain Name Server and refers Domain Name System
to the system used to associate an alphanumeric character string with a
(DNS)
numeric IP address. The DNS is actually a distributed database of domain
names and corresponding IP addresses. The DNS allows us to use
Acromag.com as an IP address rather than a complicated string of numbers.
Note that name servers contain information on some segment of the domain
name space and make this information available to clients called resolvers.
Modbus registers are organized into reference types identified by the leading MODBUS
number of the reference address:
REGISTERS
Reference Description
0xxxx Read/Write Discrete Outputs or Coils. A 0x reference The “x” following the leading
address is used to drive output data to a digital output character represents a four-
channel. digit address location in user
1xxxx Read Discrete Inputs. The ON/OFF status of a 1x data memory.
reference address is controlled by the corresponding
digital input channel.
3xxxx Read Input Registers. A 3x reference register contains a The leading character is
16-bit number received from an external source—e.g. an generally implied by the
analog signal. function code and omitted from
4xxxx Read/Write Output or Holding Registers. A 4x register is the address specifier for a
used to store 16-bits of numerical data (binary or decimal), given function. The leading
or to send the data from the CPU to an output channel. character also identifies the
Note: The ON/OFF state of discrete inputs and outputs is represented by a I/O data type.
1 or 0 value assigned to an individual bit in a 16-bit data word. This is
sixteen 0x or 1x references per data word. With respect to mapping,
the LSB of the word maps to the lowest numbered channel of a group
and channel numbers increase sequentially as you move towards the
MSB. Unused bit positions are set to zero.
All I/O values are accessed via the 16-bit Input or Holding Registers given in
the Register Map. Input registers contain read-only information. For
example, the current input value read from a channel, or the states of a
group of digital inputs. Holding registers contain read/write information that
may be configuration data or output data. For example, the high limit value
of an alarm operating at an input, or an output value for an output channel.
Each module has a default factory configuration as noted in the Register Functions
SPECIFICATIONS section. Your application will likely differ from the default
configuration and the module will need to be reconfigured. You may
reconfigure this module by issuing the appropriate Modbus functions to
Register Map registers, as required by your application. You may also use a
standard web browser to access the built-in web pages of the module to
perform basic operations.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
24 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Register Functions Below is a subset of standard Modbus functions that are supported by this
module along with the reference register addresses that the function
operates on. Use these functions to access these registers as outlined in
the Register Map for sending and retrieving data.
IMPORTANT: When using The following Modbus functions operate on register map registers to
your own software to monitor, configure, and control module I/O:
manipulate the module, please
note that the maximum query CODE FUNCTION REFERENCE
through the Modbus TCP 01 (01H) Read Coil (Output) Status 0xxxx
interface is only 50 registers, 02 (02H) Read Input Status 1xxxx
due to the maximum buffer 03 (03H) Read Holding Registers 4xxxx
size limitations of the TCP/IP 04 (04H) Read Input Registers 3xxxx
stack. As such, you can only 05 (05H) Force Single Coil (Output) 0xxxx
request data from 50 registers 06 (06H) Preset Single Register 4xxxx
at one time for commands that 15 (0FH) Force Multiple Coils (Outputs) 0xxxx
access multiple registers. For 16 (10H) Preset Multiple Registers 4xxxx
example, the Read Holding 17 (11H) Report Slave ID (See Below) Hidden
Registers command may only
retrieve the contents of
If an unsupported function code is sent to a module, exception code 01
registers 40001 to 40051 in
(Illegal Function) will be returned in the response. If a holding register is
one read.
written with an invalid value, exception code 03 (Illegal Data Value) will be
returned in the response message. You may refer to the Modbus
specification for a complete list of possible error codes.
1
961EN-4006 Report Slave ID Example Response
FIELD DESCRIPTION
Unit ID Echo Unit ID Sent In Query
Function Code 11
Byte Count 42
Slave ID (Model No.) 00=961EN-4006 (6 Diff Current In w/Modbus)
01=962EN-4006 (6 Diff Voltage In w/Modbus)
Run Indicator Status FFH (ON)
Firmware Number 41 43 52 4F 4D 41 47 2C 39 33 30 30 2D
String (Additional 31 32 31 2C 39 36 31 45 4E 2D 34 30 30 36 2C
Data Field) 30 31 32 33 34 35 41 2C 30 31 32 33 34 35
(“ACROMAG,9300-118,961EN-4006,serial
number&rev,six-byteMACID”)
1
Note: For Model 962EN-4006, the slave ID is “01” and the firmware
number is “9300-119”.
Register Mirroring For your convenience, 9xxEN Ethernet modules mirror the contents and
operation of registers 0xxxx, 1xxxx, & 3xxxx (as applicable) into holding
register space for systems and controllers that cannot directly access
registers 0xxxx, 1xxxx, & 3xxxx.
All Modbus registers of this model can now be written to, or read from, using
either the standard methods described in the Modbus specification, or
through mapping (mirroring) to the Holding Registers. The registers are
mapped as follows and specifics follow the mapping:
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 25
0xxxx Coil Registers are mapped to 42xxx Holding Registers Register Mirroring
1xxxx Input Status Registers are mapped to 41xxx Holding Registers
3xxxx Input Registers are mapped to 43xxx Holding Registers
For 3xxxx Input Registers, the format of the registers are identical and you
only need to offset your address by 43000. For example: if you want to read
Input Register 1 through the Holding Registers, you would use the “Read
Holding Registers” function with an address of 43001.
For the 1xxxx Input Status Registers (where supported), the return data is
reformatted to match the Holding Register format. For example: if you
request the Input Status for 12 digital inputs, instead of getting 2 bytes
returned with the first 12 bits representing the 12 digital inputs, you will get
12 separate words, each set to either 0000H (OFF), or FFFFH (ON).
For the 0xxxx Coil Registers (where supported), reads are handled in the
same way as the 1xxxx Input Status Registers. You can also write to the coil
registers by using the “Preset Single Register” function with an address
offset of 42000. Setting the data to 0000H will turn the coil OFF, while setting
the data to FF00H will turn the coil ON. Writing to multiple coils is not
supported via register mirroring, you must use the “Write Multiple Coils”
function for that.
Note that with respect to Acromag 9xxMB Modbus RTU modules, only 3xxxx
Input Registers are mirrored into 4xxxx space, not Coil or Input Status
registers as noted here for 9xxEN models.
I/O values for Series 900EN modules are represented by the following Data Types
simple data types for temperature, percentage, and discrete on/off.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
26 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Register Map The following table outlines the register map for the Model 961EN-4006 and
962EN-4006 network input modules. The Modbus functions operate on
these registers using the data types noted above (except for the Reset Slave
Model 961EN-4006 and Report Slave ID functions). Unless otherwise noted, Holding Register
Model 962EN-4006 values are maintained in flash memory and are non-volatile.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 27
Ref Addr. Description Data Type/Format Register Map
Input Registers (3x References, Read-Only)
30007 0006 CH03 Status Bits 15-2: 0 (Not Used)
Model 961EN-4006
Bits 1,0: Input Signal Status
Model 962EN-4006
00 In Range
01 Over-Range
10 Under-Range
11 Not Used
30008 0007 CH04 Status Bits 15-2: 0 (Not Used)
Bits 1,0: Input Signal Status
00 In Range
01 Over-Range
10 Under-Range
11 Not Used
30009 0008 CH05 Status Bits 15-2: 0 (Not Used)
Bits 1,0: Input Signal Status
00 In Range
01 Over-Range
10 Under-Range
11 Not Used
30010 0009 CH00 Value Percentage (%)
30011 000A CH01 Value Percentage (%)
30012 000B CH02 Value Percentage (%)
30013 000C CH03 Value Percentage (%)
30014 000D CH04 Value Percentage (%)
30015 000E CH05 Value Percentage (%)
30016 000F CH00 Count Raw A/D Count Value (See Note 2)
30017 0010 CH01 Count Raw A/D Count Value (See Note 2)
30018 0011 CH02 Count Raw A/D Count Value (See Note 2)
30019 0012 CH03 Count Raw A/D Count Value (See Note 2)
30020 0013 CH04 Count Raw A/D Count Value (See Note 2)
30021 0014 CH05 Count Raw A/D Count Value (See Note 2)
Holding Registers (4x References, Read/Write)
40001 0000 Input Range Bits 15-4: 0 (Not Used) Note: Changes to Holding
(CH 0,1,2 ) Bits Registers take effect
3,2,1,0: 961EN 962EN immediately.
0000 0=0-20mA 0=±10V
0001 1=4-20mA 1=±5V
0010 2=0-11.17mA 2=±2.5V
0011 3=0-1mA 3=±1.25V
0100 Reserved 4=±625mV
0101 Reserved 5=±313mV
0110 Reserved 6=±156mV
0111 Reserved 7=±78mV
1000-1111 Reserved
40002 0001 Input Range Format is same as Above.
(CH 3,4,5 )
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
28 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Register Map
Ref Addr. Description Data Type/Format
Model 961EN-4006 Holding Registers (4x References, Read/Write)
Model 962EN-4006 40003 0002 Reserved Do Not Use
40004 0003 Reserved Do Not Use
Note: Changes to Holding 40005 0004 Reserved Do Not Use
Registers take effect 40006 0005 Reserved Do Not Use
immediately. 40007 0006 Reserved Do Not Use
40008 0007 Port 0 Reserved For Factory Use - Do Not Use
Scaling Low
40009 0008 Reserved Do Not Use
40010 0009 Port 0 Reserved For Factory Use - Do Not Use
Scaling High
40011 000A Reserved Do Not Use
40012 000B Port 1 Reserved For Factory Use - Do Not Use
Scaling Low
40013 000C Reserved Do Not Use
40014 000D Port 1 Reserved For Factory Use - Do Not Use
Scaling High
40015 000E Reserved Do Not Use
40016 000F Reserved Do Not Use
40017 0010 Reserved Do Not Use
40018 0011 Reserved Do Not Use
40019 0012 Reserved Do Not Use
40020 0013 Reserved Do Not Use
40021 0014 Calibration Writing 24106 (5E2AH) here immediately
Access removes write protection from the
calibration registers that follow. All other
values apply write protection to the
calibration registers (except 21845,
And 44718, and 43981--See Below).
Wink Mode Writing 21845 (5555H) to this register will
Toggle cause the module to “Wink” its Run LED.
Writing this value a second time will stop
And “Wink” (Toggles Wink ON/OFF).
Restore Writing 44718 (AEAEH) will cause the
Factory module to restore its factory calibration.
Calibration This can only be done after “Save
Factory Calibration” has been done at the
And factory.
Factory Writing 43981 (ABCDH) is reserved for
Use Only factory use. This should not be
performed by anyone else or
This register operation will be degraded.
is not
This register always reads back 0.
maintained
After a reset, this register is set back to 0
in flash.
(write protection enabled and no wink).
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 29
Ref Addr. Description Data Type/Format Register Map
Holding Registers (4x References, Read/Write)
40022 0015 CH0 Cal Hi Raw A/D Count Value (See Note 2). Model 961EN-4006
Range 0 0-20mA (961EN) or ±10V (962EN)
Model 962EN-4006
40023 0016 CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 0 0-20mA (961EN) or ±10V (962EN)
40024 0017 CH0 Cal Hi Raw A/D Count Value (See Note 2). Shaded 4xxxx register entries
Range 1 4-20mA (961EN) or ±5V (962EN) are Read Only
40025 0018 CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 1 4-20mA (961EN) or ±5V (962EN)
40026 0019 CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40027 001A CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40028 001B CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40029 001C CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40030 001D CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
40031 001E CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
40032 001F CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 5 ±313mV (962EN)
40033 0020 CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 5 ±313mV (962EN)
40034 0021 CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 6 ±156mV (962EN)
40035 0022 CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 6 ±156mV (962EN)
40036 0023 CH0 Cal Hi Raw A/D Count Value (See Note 2).
Range 7 ±78mV (962EN)
40037 0024 CH0 Cal Lo Raw A/D Count Value (See Note 2).
Range 7 ±78mV (962EN)
40038 0025 CH1 Cal Hi Raw A/D Count Value (See Note 2).
Range 0 0-20mA (961EN) or ±10V (962EN)
40039 0026 CH1 Cal Lo Raw A/D Count Value (See Note 2).
Range 0 0-20mA (961EN) or ±10V (962EN)
40040 0027 CH1 Cal Hi Raw A/D Count Value (See Note 2).
Range 1 4-20mA (961EN) or ±5V (962EN)
40041 0028 CH1 Cal Lo Raw A/D Count Value (See Note 2).
Range 1 4-20mA (961EN) or ±5V (962EN)
40042 0029 CH1 Cal Hi Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40043 002A CH1 Cal Lo Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40044 002B CH1 Cal Hi Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40045 002C CH1 Cal Lo Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40046 002D CH1 Cal Hi Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
30 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 31
Ref Addr. Description Data Type/Format Register Map
Holding Registers (4x References, Read/Write)
40072 0047 CH3 Cal Hi Raw A/D Count Value (See Note 2). Model 961EN-4006
Range 1 4-20mA (961EN) or ±5V (962EN)
40073 0048 CH3 Cal Lo Raw A/D Count Value (See Note 2). Model 962EN-4006
Range 1 4-20mA (961EN) or ±5V (962EN)
40074 0049 CH3 Cal Hi Raw A/D Count Value (See Note 2). Shaded 4xxxx register entries
Range 2 0-11.17mA (961EN) or ±2.5V (962EN) are Read-Only.
40075 004A CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40076 004B CH3 Cal Hi Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40077 004C CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40078 004D CH3 Cal Hi Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
40079 004E CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
40080 004F CH3 Cal Hi Raw A/D Count Value (See Note 2).
Range 5 ±313mV (962EN)
40081 0050 CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 5 ±313mV (962EN)
40082 0051 CH3 Cal Hi Raw A/D Count Value (See Note 2).
Range 6 ±156mV (962EN)
40083 0052 CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 6 ±156mV (962EN)
40084 0053 CH3 Cal Hi Raw A/D Count Value (See Note 2).
Range 7 ±78mV (962EN)
40085 0054 CH3 Cal Lo Raw A/D Count Value (See Note 2).
Range 7 ±78mV (962EN)
40086 0055 CH4 Cal Hi Raw A/D Count Value (See Note 2).
Range 0 0-20mA (961EN) or ±10V (962EN)
40087 0056 CH4 Cal Lo Raw A/D Count Value (See Note 2).
Range 0 0-20mA (961EN) or ±10V (962EN)
40088 0057 CH4 Cal Hi Raw A/D Count Value (See Note 2).
Range 1 4-20mA (961EN) or ±5V (962EN)
40089 0058 CH4 Cal Lo Raw A/D Count Value (See Note 2).
Range 1 4-20mA (961EN) or ±5V (962EN)
40090 0059 CH4 Cal Hi Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40091 005A CH4 Cal Lo Raw A/D Count Value (See Note 2).
Range 2 0-11.17mA (961EN) or ±2.5V (962EN)
40092 005B CH4 Cal Hi Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40093 005C CH4 Cal Lo Raw A/D Count Value (See Note 2).
Range 3 0-1mA (961EN) or ±1.25V (962EN)
40094 005D CH4 Cal Hi Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
40095 005E CH4 Cal Lo Raw A/D Count Value (See Note 2).
Range 4 ±625mV (962EN)
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
32 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 33
Ref Addr. Description Data Type/Format Register Map
Holding Registers (4x References, Read/Write)
40121 0078 Ideal Ideal A/D Count Value (See Note 2). Model 961EN-4006
Range 1 Lo 4-20mA (961EN) or ±5V (962EN)
40122 0079 Ideal Ideal A/D Count Value (See Note 2). Model 962EN-4006
Range 2 Hi 0-11.17mA (961EN) or ±2.5V (962EN)
40123 007A Ideal Ideal A/D Count Value (See Note 2). Shaded 4xxxx registers are
Range 2 Lo 0-11.17mA (961EN) or ±2.5V (962EN) Read-Only.
40124 007B Ideal Ideal A/D Count Value (See Note 2).
Range 3 Hi 0-1mA (961EN) or ±1.25V (962EN)
40125 007C Ideal Ideal A/D Count Value (See Note 2).
Range 3 Lo 0-1mA (961EN) or ±1.25V (962EN)
40126 007D Ideal Ideal A/D Count Value (See Note 2).
Range 4 Hi ±625mV (962EN)
40127 007E Ideal Ideal A/D Count Value (See Note 2).
Range 4 Lo ±625mV (962EN)
40128 007F Ideal Ideal A/D Count Value (See Note 2).
Range 5 Hi ±313mV (962EN)
40129 0080 Ideal Ideal A/D Count Value (See Note 2).
Range 5 Lo ±313mV (962EN)
40130 0081 Ideal Ideal A/D Count Value (See Note 2).
Range 6 Hi ±156mV (962EN)
40131 0082 Ideal Ideal A/D Count Value (See Note 2).
Range 6 Lo ±156mV (962EN)
40132 0083 Ideal Ideal A/D Count Value (See Note 2).
Range 7 Hi ±78mV (962EN)
40133 0084 Ideal Ideal A/D Count Value (See Note 2).
Range 7 Lo ±78mV (962EN)
40134 0085 Reserved Do Not Use
40135 0086 Reserved Do Not Use
40136 0087 Span Cal A 16-Bit value whose bit position when
Register set indicates the channel to be calibrated
for span. For example: to calibrate span
of channel 0, write 0001H to this register.
To calibrate span of channel 5, write
0020H to this register.
IMPORTANT: You must FIRST write
5E2AH into the Calibration Access
Register (Register 40021) before
attempting calibration.
40137 0088 Zero Cal A 16-Bit value whose bit position when
Register set indicates the channel to be calibrated
for zero. For example: to calibrate zero
of channel 0, write 0001H to this register.
To calibrate zero of channel 5, write
0020H to this register.
IMPORTANT: You must FIRST write
5E2AH into the Calibration Access
Register (Register 40021) before
attempting calibration.
43001 This block Refer to Register Mirroring. 3xxxx Input
. Mirrors Registers are mapped to the 43xxx
. 3xxxx Holding Register space using an address
Registers. offset of 43000.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
34 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
SPECIFICATIONS These DIN-rail mount, industrial Ethernet, analog input modules will
condition up to six differential DC current (961EN), or voltage (962EN) input
signals, and provide an isolated 10/100BaseT Ethernet port for monitoring
and control. Units are DC-powered and include reverse polarity protection.
Analog inputs (as a group), network, and power are isolated from each
other. Non-volatile reprogrammable memory in the module stores
configuration and calibration information.
Model Numbers The BusWorks model prefix “900” denotes the Series 900 network I/O
family. The “EN” suffix denotes EtherNet. Select 961EN for current input,
961EN-4006 (6 DC Current) and 962EN for voltage input. The four digit suffix of this model number
962EN-4006 (6 DC Voltage)
represents the following options, respectively: “4” = Ethernet; “0” = Default;
“06” = 6 Channels.
Analog Inputs Up to six process current or voltage input channels, according to model
number. The unit can be configured to accept one of several input ranges at
each group of 3 channels as described below. The unit must be wired and
configured for the intended input type and range (see Connections section
for details). The following paragraphs summarize this model’s input types,
ranges, and applicable specifications.
DC Current (961EN Only): Configurable for 0 to 20mA, 4-20mA,
0-11.17mA, and 0-1mA DC nominal input ranges. A precision 24.9
current sink resistor converts the input current to a voltage that is
processed by the A/D converter. An optional external sensor is
required to monitor AC current signals (Acromag Model 5020-350).
This sensor generates a DC milliampere signal of 0 to 11.17mA for the
module (see Table 1 below for scaling to AC current).
Current Input Reference Test Conditions: 4 to 20mA current input;
ambient temperature = 25 C; 24VDC supply.
Input Overvoltage Protection: Bipolar Transient Voltage Suppressers
(TVS), 5.2V clamp level typical.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 35
AC Current Sensor (Model 5020-350, For Use With 961EN): This SPECIFICATIONS
sensor is a toroidal instrument transformer that converts a sinusoidal
50-60Hz AC current signal into a low level DC milliampere signal of 0 to
11.17mA. The input AC current range is a function of the number of Analog Inputs
turns placed through the toroid as shown in Table 1 below. This sensor
is isolated and requires no calibration or adjustment. When used with a
961EN module, it provides redundant input isolation and may facilitate
input-to-input isolation of this six channel unit.
The output wires of this sensor are polarized with red as (+) plus and
black as (-) minus. Normally these output wires are attached to one
end of a user supplied cable while the other end connects to the
961EN’s process current input terminals.
Input Burden: A function of the wire gauge resistance used for primary
turns (the current carrying wire being monitored).
AC Current Sensor to Transmitter Wiring Distance: 400 feet
maximum for 18 gauge wire. Other wire gauges can be used as long
as the resistance of both wires is less than 5 .
Input Overload: The AC current sensor will withstand overload
conditions as follows:
20 times full scale for 0.01 seconds.
10 times full scale for 0.1 seconds.
5 times full scale for 1.0 second.
Accuracy: Better than 0.05% of span, typical for nominal input ranges General Specifications
(except 0-1mA). This includes the effects of repeatability, terminal
point conformity, and linearization, but does not include sensor
error.
Measurement Temperature Drift: Better than 50ppm/ C
(±0.005%/ C).
Analog to Digital Converter (A/D): A 16-bit - converter.
Resolution: 0.005% or 1 part in 20000 (961EN), 0.0025% or 1 part in
40000 (962EN, full bipolar range).
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
36 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
General Specifications Input Conversion Rate: 80ms per channel, or 480ms for six input
channels.
Input Filter: Normal mode filtering, plus digital filtering optimized and
fixed per input range within the - ADC.
Input Filter Bandwidth: -3dB at 3Hz, typical.
Noise Rejection (Normal Mode): 40dB @ 60Hz, typical with 100
input unbalance.
Noise Rejection (Common Mode): 140dB @ 60Hz, typical with 100
input unbalance.
Data Types: Percentage - A 16-bit signed integer value with resolution
of 0.005%/lsb. 20000 is used to represent 100%. For example,
-100%, 0%, and +100% are represented by decimal values –
20000, 0, and 20000, respectively. The full range is –163.84% (-
32768 decimal) to +163.835% (+32767 decimal).
Enclosure & Physical Dimensions: 1.05 inches wide, 4.68 inches tall, 4.35 inches deep. Refer to
the dimensions drawing at the front of this manual.
DIN Rail Mount: Type EN50022; “T” rail (35mm).
I/O Connectors: Removable plug-in type terminal blocks rated for
15A/300V; AWG #12-24 stranded or solid copper wire.
Network Connector: 8-pin RJ-45 connector socket with metal shield
(shield is bypassed to earth ground at the GND terminal via an isolation
capacitor and TVS). Connections are wired MDI, as opposed to MDI-X.
You must use a CAT-5 crossover cable to connect this module to a PC.
Otherwise you may use an auto-crossing Ethernet switch, such as the
Acromag 900EN-S005 to make connections.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 37
Operating Temperature: -25 C to +70 C (-13 F to +158 F). Environmental
Storage Temperature: -40 C to +85 C (-40 F to +185 F).
Relative Humidity: 5 to 95%, non-condensing.
Power Requirements: 15-36V DC SELV (Safety Extra Low Voltage), 2W.
Observe proper polarity. See table for current.
Isolation: Input channels (as a group), power, and network circuits are CAUTION: Risk of Electric
isolated from each other for common-mode voltages up to 250VAC, or Shock – More than one
354V DC off DC power ground, on a continuous basis (will withstand disconnect switch may be
1500VAC dielectric strength test for one minute without breakdown). required to de-energize the
Complies with test requirements of ANSI/ISA-82.01-1988 for voltage equipment before servicing.
rating specified.
Installation Category: Designed to operate in an installation in a Pollution
Degree 2 environment with an installation category (over-voltage
category) II rating.
Electromagnetic Interference Immunity (EMI): Unit has demonstrated
measurement shift less than 0.25% of input span with interference
from switching solenoids, commutator motors, and drill motors.
Electromagnetic Compatibility (EMC) -
Immunity Per European Norm BS EN 61000-6-2:2005: These limits represent the
Electrostatic Discharge (ESD) Immunity: 4KV direct contact and minimum requirements of the
8KV air-discharge to the enclosure port per IEC61000-4-2. standard, but product has
Radiated Field Immunity (RFI): 10V/M, 80 to 1000MHz AM, 1.4 to typically been tested to comply
2GHz 3V/M, and 2 to 2.7GHz 1V/M, per IEC61000-4-3. with higher standards in some
Electrical Fast Transient Immunity (EFT): 2KV to power, and 1KV to cases.
signal I/O per IEC61000-4-4.
Conducted RF Immunity (CRFI): 10V rms, 150KHz to 80MHz, per
IEC61000-4-6.
Surge Immunity: 0.5KV per IEC61000-4-5.
Emissions Per European Norm BS EN 61000-6-4:2007
Radiated Frequency Emissions: 30 to 1000MHz per CISPR16 Class A
WARNING: This is a Class A product. In a domestic environment, this
product may cause radio interference in which the user may be required to
take adequate measures.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
38 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Environmental IMPORTANT: Power, input, and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods of Article 501-4(b) of the National
Electrical Code, NFPA 70 for installations in the US, or as specified in
section 18-1J2 of the Canadian Electrical Code for installations within
Canada and in accordance with the authority having jurisdiction.
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, and D, or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Substitution of components may
impair suitability for Class I, Division 2.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless
power has been switched off or the area is known to be non-hazardous.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________ 39
LED Indicators: Controls & Indicators
RUN (Green) - Constant ON if power is on. Continuous flashing ON/OFF
indicates unit is in “wink” ID mode.
ST (Yellow) – Blinks ON/OFF in default communication mode. Stays ON
if an input is out of range.
LINK (Green) – Indicates Ethernet link status (ON if auto-negotiation has
successfully established a connection).
ACT (Yellow) – Indicates Ethernet activity (Ethernet connection is
busy/traffic is present).
Controls:
Reset/Default Address Switch: This momentary toggle switch is
located on the front panel and is used to either reset the module
(toggle right), or cause the module to assume a default IP address
(toggle left). Module address is initially set to 128.1.1.100 at the
factory, or may be preset by the user. This switch can also be used to
restore the module to its initial factory configuration by holding this
switch in its default position while powering up the unit (see “Getting
Out Of Trouble” in the Troubleshooting section for more information).
The minimum cable required for full operation of this device is Category 5. ACCESSORY
The term “Category” refers to classifications of UTP (Unshielded Twisted
Pair) and STP (Shielded Twisted Pair) cables. There are 3 main categories CABLES
of cable – Category 3, Category 4, and Category 5. The differences in
classification is found in their electrical performance and this is documented
in the TIA/EIA 568-A standard.
There are two types of cable conductors: solid cable and stranded cable.
Stranded cables are more flexible than solid cables. But since attenuation is
higher for stranded cables than solid conductor cables, these are generally
reserved for short runs and patch applications less than 6 meters.
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com
40 BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
__________________________________________________________________
Patch Cable & Acromag offers the following cable accessories for use with this module:
Crossover Cable
Cable Model 5035-355 – A yellow, 3 foot long, single-shielded Category 5e
STP patch cable with drain wire and an RJ45 plug at both ends. Use this
cable to connect an Acromag 9xxEN I/O module to the Acromag 900EN-
S005 switch.
Cable Model 5035-360 – A green, 5 foot long, single-shielded Category 5e
STP crossover cable with a drain wire and an RJ45 plug at both ends. This
cable performs the Ethernet crossover function and is used to connect a PC
directly to an Acromag Series 9xxEN I/O module.
Note that you do not need to use a crossover cable to connect your PC to
this module if the Acromag 900EN-S005 switch is used between the PC and
module, as the switch is auto-crossing. However, you must use a crossover
cable when directly connecting your PC to a Series 9xxEN I/O Module
without the use of an auto-crossing switch or hub.
You may obtain cable in other lengths and colors as required for your
application from other vendors. For example, shielded CAT-5e cable is
available from the following vendors:
For very noisy environments or in the presence of strong electrical fields, you
can obtain double-shielded CAT-5e cable and shielded RJ45 plugs from the
following vendors:
_______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:[email protected] http://www.acromag.com