KYP5110 Modbus Protocol (Add Modbus Address) v1 0
KYP5110 Modbus Protocol (Add Modbus Address) v1 0
0
Measuring class parameter [Floating point format data]
Register
Input Register Parameter
Address
[ Function code : 04H ]
[Hex]
30165 Maximum total system reactive power demand (3). 4 Float var 00 A4
33353 The total active energy consumption of the current days 20 Float kWh 0D 18
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 1 days
33363 20 Float kWh 0D 22
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 2 days kWh
33373 20 Float 0D 2C
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 3 days kWh
33383 20 Float 0D 36
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 4 days kWh
33393 20 Float 0D 40
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 5 days
33403 20 Float kWh 0D 4A
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 6 days
33413 20 Float kWh 0D 54
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 7 days
33423 20 Float kWh 0D 5E
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 8 days
33433 20 Float kWh 0D 68
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 9 days
33443 20 Float kWh 0D 72
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 10 days
33453 20 Float kWh 0D 7C
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 11 days
33463 20 Float kWh 0D 86
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 12 days
33473 20 Float kWh 0D 90
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 13 days kWh
33483 20 Float 0D 9A
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 14 days kWh
33493 20 Float 0D A4
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 15 days
33503 20 Float kWh 0D AE
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 16 days
33513 20 Float kWh 0D B8
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 17 days
33523 20 Float kWh 0D C2
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 18 days
33533 20 Float kWh 0D CC
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 19 days
33543 20 Float kWh 0D D6
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 20 days
33553 20 Float kWh 0D E0
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 21 days
33563 20 Float kWh 0D EA
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 22 days
33573 20 Float kWh 0D F4
(Total、Rate1、Rate2、Rate3、Rate4)
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
The total active energy consumption of the last 23 days kWh
33583 20 Float 0D FE
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 24 days kWh
33593 20 Float 0E 08
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 25 days
33603 20 Float kWh 0E 12
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 26 days
33613 20 Float kWh 0E 1C
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 27 days
33623 20 Float kWh 0E 26
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 28 days
33633 20 Float kWh 0E 30
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 29 days
33643 20 Float kWh 0E 3A
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 30 days
33653 20 Float kWh 0E 44
(Total、Rate1、Rate2、Rate3、Rate4)
The total active energy consumption of the last 31 days
33663 20 Float kWh 0E 4E
(Total、Rate1、Rate2、Rate3、Rate4)
Import active energy category
(Each set of data includes the energy of all rate segments, the energy of rate 1, the energy of rate 2, the energy of rate 3 and the
energy of rate 4 respectively)
YY.MM
The occurrence time of the maximum total system active power DD
36671 6 BCD 1A 0E
demand HH:mm:
SS
36674 Maximum total system reactive power demand (3). 4 Float var 1A 11
YY.MM
The occurrence time of the maximum total system reactive DD
36676 6 BCD 1A 13
power demand HH:mm:
SS
YY.MM
The occurrence time of the maximum total system apparent DD
36681 6 BCD 1A 18
power demand HH:mm:
SS
YY.MM
DD
36731 The occurrence time of the maximum phase 1 current demand 6 BCD 1A 4A
HH:mm:
SS
YY.MM
DD
36736 The occurrence time of the maximum phase 2 current demand 6 BCD 1A 4F
HH:mm:
SS
36741 The occurrence time of the maximum phase 3 current demand 6 BCD YY.MM 1A 54
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
DD
HH:mm:
SS
YY.MM
DD
36746 The occurrence time of the maximum neutral current demand 6 BCD 1A 59
HH:mm:
SS
YY.MM
The occurrence time of the maximum import active power DD
36781 6 BCD 1A 7C
demand HH:mm:
SS
YY.MM
The occurrence time of the maximum export active power DD
36786 6 BCD 1A 81
demand HH:mm:
SS
YY.MM
DD
36931 The occurrence time of the total active power maximum value 6 BCD 1B 12
HH:mm:
SS
YY.MM
The occurrence time of the total reactive power maximum DD
36936 6 BCD 1B 17
value HH:mm:
SS
YY.MM
The occurrence time of the total apparent power maximum DD
36941 6 BCD 1B 1C
value HH:mm:
SS
YY.MM
DD
36946 The occurrence time of the total power factor maximum value 6 BCD 1B 21
HH:mm:
SS
YY.MM
DD
36951 The occurrence time of the L1 active power maximum value 6 BCD 1B 26
HH:mm:
SS
YY.MM
DD
36961 The occurrence time of the L3 active power maximum value 6 BCD 1B 30
HH:mm:
SS
YY.MM
DD
36966 The occurrence time of the L1 reactive power maximum value 6 BCD 1B 35
HH:mm:
SS
YY.MM
DD
36971 The occurrence time of the L2 reactive power maximum value 6 BCD 1B 3A
HH:mm:
SS
YY.MM
DD
36976 The occurrence time of the L3 reactive power maximum value 6 BCD 1B 3F
HH:mm:
SS
YY.MM
DD
36981 The occurrence time of the L1 apparent power maximum value 6 BCD 1B 44
HH:mm:
SS
YY.MM
DD
36986 The occurrence time of the L2 apparent power maximum value 6 BCD 1B 49
HH:mm:
SS
YY.MM
DD
36991 The occurrence time of the L3 apparent power maximum value 6 BCD 1B 4E
HH:mm:
SS
YY.MM
DD
36996 The occurrence time of the L1 power factor maximum value 6 BCD 1B 53
HH:mm:
SS
YY.MM
DD
37006 The occurrence time of the L3 power factor maximum value 6 BCD 1B 5D
HH:mm:
SS
YY.MM
DD
37011 The occurrence time of the L1 current maximum value 6 BCD 1B 62
HH:mm:
SS
YY.MM
DD
37016 The occurrence time of the L2 current maximum value 6 BCD 1B 67
HH:mm:
SS
YY.MM
DD
37021 The occurrence time of the L3 current maximum value 6 BCD 1B 6C
HH:mm:
SS
YY.MM
DD
37026 The occurrence time of the neutral current maximum value 6 BCD 1B 71
HH:mm:
SS
YY.MM
DD
37031 The occurrence time of the total current maximum value 6 BCD 1B 76
HH:mm:
SS
YY.MM
DD
37036 The occurrence time of the L1 voltage maximum value 6 BCD 1B 7B
HH:mm:
SS
YY.MM
DD
37041 The occurrence time of the L2 voltage maximum value 6 BCD 1B 80
HH:mm:
SS
YY.MM
DD
37051 The occurrence time of the L1-2 voltage maximum value 6 BCD 1B 8A
HH:mm:
SS
YY.MM
DD
37056 The occurrence time of the L2-3 voltage maximum value 6 BCD 1B 8F
HH:mm:
SS
YY.MM
DD
37061 The occurrence time of the L3-1 voltage maximum value 6 BCD 1B 94
HH:mm:
SS
YY.MM
The occurrence time of the L1 voltage total harmonic maximum DD
37066 6 BCD 1B 99
value HH:mm:
SS
YY.MM
The occurrence time of the L2 voltage total harmonic maximum DD
37071 6 BCD 1B 9E
value HH:mm:
SS
YY.MM
The occurrence time of the L3 voltage total harmonic maximum DD
37076 6 BCD 1B A3
value HH:mm:
SS
YY.MM
The occurrence time of the L1 current total harmonic maximum DD
37081 6 BCD 1B A8
value HH:mm:
SS
YY.MM
The occurrence time of the L2 current total harmonic maximum DD
37086 6 BCD 1B AD
value HH:mm:
SS
YY.MM
DD
37096 The occurrence time of the total active power Minimum value 6 BCD 1B B7
HH:mm:
SS
YY.MM
DD
37101 The occurrence time of the total reactive power Minimum value 6 BCD 1B BC
HH:mm:
SS
YY.MM
The occurrence time of the total apparent power Minimum DD
37106 6 BCD 1B C1
value HH:mm:
SS
YY.MM
DD
37111 The occurrence time of the total power factor Minimum value 6 BCD 1B C6
HH:mm:
SS
YY.MM
DD
37116 The occurrence time of the L1 active power Minimum value 6 BCD 1B CB
HH:mm:
SS
YY.MM
DD
37121 The occurrence time of the L2 active power Minimum value 6 BCD 1B D0
HH:mm:
SS
YY.MM
DD
37126 The occurrence time of the L3 active power Minimum value 6 BCD 1B D5
HH:mm:
SS
YY.MM
DD
37131 The occurrence time of the L1 reactive power Minimum value 6 BCD 1B DA
HH:mm:
SS
YY.MM
DD
37141 The occurrence time of the L3 reactive power Minimum value 6 BCD 1B E4
HH:mm:
SS
YY.MM
DD
37146 The occurrence time of the L1 apparent power Minimum value 6 BCD 1B E9
HH:mm:
SS
YY.MM
DD
37151 The occurrence time of the L2 apparent power Minimum value 6 BCD 1B EE
HH:mm:
SS
YY.MM
DD
37156 The occurrence time of the L3 apparent power Minimum value 6 BCD 1B F3
HH:mm:
SS
YY.MM
DD
37161 The occurrence time of the L1 power factor Minimum value 6 BCD 1B F8
HH:mm:
SS
YY.MM
DD
37166 The occurrence time of the L2 power factor Minimum value 6 BCD 1B FD
HH:mm:
SS
YY.MM
DD
37171 The occurrence time of the L3 power factor Minimum value 6 BCD 1C 02
HH:mm:
SS
YY.MM
DD
37176 The occurrence time of the L1 current Minimum value 6 BCD 1C 07
HH:mm:
SS
YY.MM
DD
37186 The occurrence time of the L3 current Minimum value 6 BCD 1C 11
HH:mm:
SS
YY.MM
DD
37191 The occurrence time of the neutral current Minimum value 6 BCD 1C 16
HH:mm:
SS
YY.MM
DD
37196 The occurrence time of the total current Minimum value 6 BCD 1C 1B
HH:mm:
SS
YY.MM
DD
37201 The occurrence time of the L1 voltage Minimum value 6 BCD 1C 20
HH:mm:
SS
YY.MM
DD
37206 The occurrence time of the L2 voltage Minimum value 6 BCD 1C 25
HH:mm:
SS
YY.MM
DD
37211 The occurrence time of the L3 voltage Minimum value 6 BCD 1C 2A
HH:mm:
SS
YY.MM
DD
37216 The occurrence time of the L1-2 voltage Minimum value 6 BCD 1C 2F
HH:mm:
SS
YY.MM
DD
37221 The occurrence time of the L2-3 voltage Minimum value 6 BCD 1C 34
HH:mm:
SS
YY.MM
The occurrence time of the L1 voltage total harmonic Minimum DD
37231 6 BCD 1C 3E
value HH:mm:
SS
YY.MM
The occurrence time of the L2 voltage total harmonic Minimum DD
37236 6 BCD 1C 43
value HH:mm:
SS
YY.MM
The occurrence time of the L3 voltage total harmonic Minimum DD
37241 6 BCD 1C 48
value HH:mm:
SS
YY.MM
The occurrence time of the L1 current total harmonic Minimum DD
37246 6 BCD 1C 4D
value HH:mm:
SS
YY.MM
The occurrence time of the L2 current total harmonic Minimum DD
37251 6 BCD 1C 52
value HH:mm:
SS
YY.MM
The occurrence time of the L3 current total harmonic Minimum DD
37256 6 BCD 1C 57
value HH:mm:
SS
Notes:
1. The power factor has its sign adjusted to indicate the direction of the current. Positive refers to forward
current, negative refers to reverse current.
2. In 3P3W mode, L1 represents the line voltage THD of L1-2, L2 represents the line voltage harmonic
content of L2-3, and L3 represents the Line voltage THD of L3-1. In 3P4W, 1P2W, 1P3W and other modes,
L1, L2 and L3 respectively represent the corresponding phase voltage harmonic content
3. The power sum demand calculation is for import – export.
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
Measuring class parameter [Integer format data]
Register
Holding Register Parameter
Address
[ Read : Function code : 03H ]
[Hex]
Default 1, min.
420484 Slide time 2 UINT 50 03 R/W
Range:1 ~ (Demand Period -1).
Demand Default 0,
420485 calculation 0 = sliding block 2 UINT 50 04 R/W
method 1 = fixed block
420489 Password Read: to get the password of the meter 2 UINT 50 08 R/W
Write: to program the new password of the
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
meter
Default : 0000
(KPPA is asked)
Data definition:
420507 System time 20-Year-Month-Date-Week-Hour-Minute- 8 BCD 50 1A R/W
Second
Data definition:
Tariff number-Min-Hour
Tariff number : 00 , 01 , 02 , 03 , 04 ; 00
420511 Tariff 30 BCD 50 1E R/W
mean invalid tariff number
Min:00-59
Hour:00-23
Running time.
Data definition:
Day-hour-minute,
day=2byte; hour=1byte; minute=1byte
Explame:
420526 Running time 04 23 21 57 mean : 4 BCD 50 2D R/W
Running time=423 day + 21 hour + 57 min
Write 0 to reset the running time. No
response if write other value.
Note: The meter starts timing when it's
powered on
AL-2 Status
0 = No alarm
AL-2
421026 1 = HC alarm (High threshold alarm) 2 UINT 52 21 R
Status
2 = LC alarm (Low threshold alarm)
3 = Both HC and LC alarms exist
Fault code
422024 Fault code 0 mean No fault. 2 UINT 56 07 R
1 mean Battery low voltage fault.
422029 Rated voltage of Rated voltage of the system, default:230V。 4 ULONG 56 0C R/W
the system Represents the voltage that is connected to
the voltage measuring interface.
If a voltage transformer is used, it represents
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
the voltage on the secondary side of the
voltage transformer.
425089 SOE-01 (3) SOE information; the format is: 12 Custom 62 00 R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
425119 SOE-06 (3) SOE information; the format is: 12 Custom 62 1E R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
425149 SOE-11 (3) SOE information; the format is: 12 Custom 62 3C R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
425179 SOE-16 (3) SOE information; the format is: 12 Custom 62 5A R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
425209 SOE-21 (3) SOE information; the format is: 12 Custom 62 78 R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
425239 SOE-26 (3) SOE information; the format is: 12 Custom 62 96 R/W
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
type-event cause-alarm value-year-month-
date -hour-min-second
Note:
Type : 1 byte, BCD.
event cause : 1 byte, BCD.
alarm value : 4 byte, Float.
year-month-date -hour-min-second : 6 byte,
BCD.
Note:
(1) Table-1 Alarm Parameter
2 Phase 3 line to neutral 15 Phase 3 active power. 28 Total system power factor.
volts.
7 Average line to line volts. 20 Total system reactive 33 Active power of per phase
power.
Note: Alarm objects with number in the range of 30-36 represent that when the parameters of any one of the three phases detected by
the electricity meter exceed the alarm threshold, the alarm action will be triggered.
(2) Please make sure during the setting: HC>HO >LO >LC
Table-2 A unit of alarm parameter.
Phase 2 line to neutral V Average line current. A Phase 1 apparent power. kVA
volts.
Average line to neutral V Phase 1 active power. kW Phase 3 apparent power. kVA
volts.
Line 2 to Line 3 volts. V Phase 3 active power. kW Phase 1 power factor. None
Phase 1 current. A Phase 2 reactive power. kvar Total system power factor. None
Lengt Hig
Data Low Mod
Parameter Description h h
Format Byte e
(bits) Byte
Lengt Hig
Data Low Mod
Parameter Description h h
Format Byte e
(bits) Byte
Lengt
Hig
h Data Low Mod
Parameter Description h
(bytes Format Byte e
Byte
)
Request: 01 04 00 00 00 02 71 CB
04 = Function code
71 = CRC Low
CB = CRC High
Response: 01 04 04 43 66 33 34 1B 38
04 = Function code
1B = CRC Low
38 = CRC High
Request: 01 03 00 00 00 02 C4 B0
03 = Function code
C4 = CRC Low
B0 = CRC High
Response: 01 03 04 00 00 61 AA 53 DC
04 = Function code
53 = CRC Low
DC = CRC High
Request: 01 03 50 03 00 01 65 0A
03 = Function code
65 = CRC Low
0A = CRC High
Response: 01 03 02 00 05 78 47
03 = Function code
78 = CRC Low
47 = CRC High
10 = Function code
02 = Byte Count
77 = CRC Low
BF = CRC High
Response: 01 10 50 02 00 01 B1 09
10 = Function code
B1 = CRC Low
09 = CRC High
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
4, Read Input Status
Example: Read DI1~4 status
Request: 01 02 00 00 00 04 79 C9
02 = Function code
79 = CRC Low
C9 = CRC High
Response: 01 02 01 03 E1 89
02 = Function code
01 = Byte Count
03 =Data,( DI status)
E1 = CRC Low
89 = CRC High
Bit 0 refers to the status of DI-1. The value is 1, which means DI-1 is on.
Bit 1 refers to the status of DI-2. The value is 1, which means DI-2 is on
Bit 2 refers to the status of DI-3. The value is 0, which means DI-3 is off
Bit 3 refers to the status of DI-4. The value is 0, which means DI-4 is off
01 = Function code
BD = CRC Low
CB = CRC High
Response: 01 01 01 02 D0 49
01 = Function code
01 = Byte Count
02 =Data,( DO status)
D0 = CRC Low
49 = CRC High
Bit 0 refers to DO-1 status. The value is 0, which means DO-1 is open
Bit 1 refers to DO-2 status. The value is 1, which means DO-1 is close
Yuyao KY smart equipments factory KYP5110 Protocol V1.0
6, Force Single Coil
Example: Control DO1=ON
Request: 01 05 00 00 FF 00 8C 3A
05 = Function code
8C = CRC Low
3A = CRC High
Response: 01 05 00 00 FF 00 8C 3A
05 = Function code
8C = CRC Low
3A = CRC High