Update Firmware and Parameter Set Released en US
Update Firmware and Parameter Set Released en US
General 1
Importing and Managing Device Drivers 2
SIPROTEC 5
Features When Handling Protocols 3
Update Firmware and
Configuration Upgrading the Configuration Version 4
Manual
C53000-G5040-C003-8B
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
1 General......................................................................................................................................................... 4
You can use DIGSI 5 for updating both the configuration and the firmware. No additional tool is necessary for
updating the firmware of the device or the firmware of the communication module. In order to carry out an
update, you must first import the new DIGSI device driver (DDD) into DIGSI 5. You can then update the device
firmware and the configuration. When updating the firmware, use a connection with at least 1 Mbit/s.
If you wish to use new functions or if the manufacturer provides an improved version of the firmware, a firm-
ware update is necessary. The files for the firmware update are digitally signed. This prevents you from
loading the device with any faulty files or firmware that is not suitable for the device.
If you have installed new communication modules in the SIPROTEC 5 device, check the firmware version of the
individual components. You can find up-to-date device drivers and communication protocols (*.DDD, DIGSI
Device Driver) in the Siemens download pool.
DIGSI 5 device drivers contain both the firmware and the configuration data.
Siemens recommends performing the firmware update on the device locally. If you wish to start the firmware
update remotely, use a data circuit with a transmission rate of at least 1 Mbit/s.
Step 1
• Download the device driver or protocol drivers necessary for updating your SIPROTEC 5 device from the
Siemens download pool.
http://www.siemens.com/siprotec
• Open the overview of download products with the > Enter link.
Step 2
• In the SIPROTEC 5 and DIGSI 5 Downloads download pool, select the device (for example: 7SL87).
• Save the file to any location on your DIGSI 5 PC, for example, C:\temp.
• Save the file to any location on your DIGSI 5 PC, for example, C:\temp.
Step 3
• Select the previously saved device driver file (DDD for device and protocol) in DIGSI 5 via the menu item
Tools → Import device drivers.
[scdddcom-260716-01, 1, en_US]
If the process has been completed without errors, the following dialog will appear:
[scsucddd-260716-01, 1, en_US]
[scgetrvw-250716-01, 1, en_US]
NOTE
i Before doing a firmware update of your SIPROTEC 5 device or the communication modules, back up the
data and the configuration of the device using DIGSI 5 via Connect to device and retrieve data!
NOTE
i The device will not carry out any functions during the update.
The update can take several minutes and the device can reboot several times. Do not shut off the device
under any conditions during the update.
[scausfiw-011116-01, 1, en_US]
As an alternative, you can update the firmware for all the devices on the network at the same time.
• To do this, double-click the menu item Load firmware to device in the project tree.
[scmulaus-260716-01, 1, en_US]
The following dialog allows you to select the devices to be updated and their firmware components.
[scfwupsd-280716-01, 1, en_US]
[scfwdvlo-280716-01, 1, en_US]
After the firmware update of the device and the communication modules, all firmware components of the
device have been updated.
The firmware for the communication modules consists of the basic firmware and all available protocols. The
communication drivers depend on the device firmware and must be updated together with this firmware.
When you set parameters for a protocol in DIGSI 5 and when you load the configuration into the device, the
protocol firmware is loaded automatically in the device if necessary.
To be able to use the extended functionality after a firmware update, you must perform an upgrade of the
configuration. Proceed as follows:
NOTE
i Before doing an update, back up the configuration of your SIPROTEC 5 device using DIGSI 5 via Connect to
device and retrieve data!
[scupgpar-041016-01, 1, en_US]
• Select the desired device configuration and the corresponding communication configuration by selecting
the available version:
[scupgcnf-290716-01, 1, en_US]
[scaktolf-290716-01, 1, en_US]
[scupginf-260716-01, 1, en_US]
The 2nd tab shows information, possible errors and warnings regarding the upgrade procedure.
[scupgwrn-260716-01, 1, en_US]
[scupgpa2-130913-01, 2, en_US]