PE - Gas Sizing - Guide
PE - Gas Sizing - Guide
Featuring the Con-Stab I.D. Seal® Fittings from Continental Industries, Inc.
and Medium Density Polyethylene (MDPE) Pipe
Jan 2019
TECHNICAL DATA
Part Number Tubing Size Average OD (in.) SDR Min. Wall (in.)
PE-8 1/2" CTS .625 7.0 0.090
PE-12 3/4" IPS 1.050 11.0 0.095
PE-16 1" CTS 1.125 11.5 0.099
PE-16-IPS 1" IPS 1.315 11.0 0.120
PE-20 1-1/4" IPS 1.660 10.0 0.166
PE-24 1-1/2" IPS 1.900 11.0 0.173
PE-32 2" IPS 2.375 11.0 0.216
Normal Pipe Size and SDR must be used to match fittings and IPS PE pipe.
Nominal Pipe Size and Min. Wall must be used to match fittings and CTS PE pipe.
MDPE pipe complies with ASTM D2513.
STEP 1 STEP 5
Verify the polyethylene Mark the stab depth by
(P.E.) pipe being inserting the pipe into
assembled is the the chamfer tool and
correct size. marking the pipe at the
entrance as shown.
STEP 2 STEP 6
Cut pipe ends square. If using chamfer tool
with ID gauge, check
for proper chamfer by
inserting pipe over
gauge.
STEP 3 STEP 7
Clean piping thoroughly Stab pipe completely
to assure there is no into fitting entrance.
dirt, grease or oil in
assembly area.
STEP 4 STEP 8
Chamfer end of pipe Stab pipe completely
using Continental’s into fitting so that the
chamfering tool with mark on the pipe is
I.D. gauge. within 1/8" from the
fitting entrance.
STEP 9
Repeat steps 1 though 4 for all Con-Stab joints.
STEP 10
To assure proper assembly and to comply with 49
CFR 192 Subpart J-Test requirements, the joint shall
be leak tested.
Rev. 1/2019