Medium Voltage Circuit Breaker Switchgear Projects, ANSI vs. IEC. What's The Difference in Construction
Medium Voltage Circuit Breaker Switchgear Projects, ANSI vs. IEC. What's The Difference in Construction
Medium Voltage Circuit Breaker Switchgear Projects, ANSI vs. IEC. What's The Difference in Construction
114
In today’s marketplace it is becoming more and more common to see both ANSI/IEEE and IEC standards
in specifications for a project. In the case of medium-voltage (MV) circuit breaker switchgear projects
IEEE C37.20.2, IEEE Standard for Metal-Clad Switchgear and IEC 62271, High-voltage switchgear and
controlgear–Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and
up to and including 52 kV, are commonly cited in the same specification.
Until 2003 both ANSI/IEEE and the IEC standards contained a type of MV switchgear that was termed
Metal-Clad (MC) Switchgear. The 2003 edition of IEC 62271-200, which superseded IEC 60298,
discontinued use of the term Metal Clad and instead introduced a new classification of switchgear
assemblies based upon Loss of Service Continuity (LSC) categories. There were numerous valid technical
reasons for the IEC to discontinue the use of the term Metal Clad and Annex C of the 2003 edition of
62271-200 describes the reasons for the changes in some detail. The last sentence of Annex C.1
summarizes by stating “Differences between IEC and IEEE definitions made harmonization difficult.”
This Tech Brief will focus only on the major differences in the construction requirements contained in the
two standards. There are numerous other differences in Ratings, Tests, Internal Arc Classifications, etc.
that will not be described in this Brief. Those differences will be the topics of future Tech Briefs.
Metal-Clad Switchgear as defined in ANSI/IEEE meets the requirements of IEC class LSC2B-PM metal-
enclosed switchgear and controlgear. However, ANSI/IEEE also requires several additional features in
order to be classified MC switchgear that are not required in class LSC2B-PM switchgear. These
differences are summarized below.
• The main circuit switching and interrupting devices (i.e. circuit breakers) must be withdrawable,
equipped with self-aligning and self-coupling primary disconnecting devices, and disconnectable
control and auxiliary circuits. Manual secondary disconnecting devices must also be interlocked with
the switching device such that the switching device control connections are always made and
maintained when the circuit breaker is in the connected position. Stationary, or non-withdrawable,
switching devices are allowed in IEC providing the requirements of LSC2B-PM are still met.
• Voltage transformers and control power transformers must be contained in separate metal enclosed
compartments. The primary circuits of all voltage transformers must include current-limiting fuses for
protecting transformers and shall be mounted in such a way that they must be disconnected from the
high voltage circuit before access can be obtained. There must also be provisions for disconnecting or
automatically grounding the low voltage circuit of voltage transformers when the high voltage circuit is
disconnected. Additionally, a method for grounding the high voltage winding and/or fuses during the
disconnecting operation to dissipate static charges shall be provided. Fixed-mounted and unfused
transformers are allowed in IEC providing the requirements of LSC2B-PM are still met.
• All the live parts must be enclosed within grounded metal compartments. Metallic barriers between
primary compartments must be a minimum of 11 gauge steel. Barriers not made of 11 gauge steel,
such as aluminium, must be increased in thickness or reinforced to provide a strength equivalent to
steel. Although IEC LSC2B-PM requires metallic barriers, there is no thickness or strength
requirement stated.
• A metal barrier in front of, or a part of, the switching device to ensure that when the device is in the
connected position no high-voltage parts are exposed by the opening of a door must be provided. The
IEC standard does not require this barrier, but rather addresses high-voltage part access by
means of interlock controlled or procedure based compartment access requirements.
So, what’s the difference? As you can see above, there are many. This is not meant to presume that
manufacturers of IEC MV switchgear can not or will not supply equipment that will meet the additional
ANSI/IEEE requirments for the “same” switchgear. Rather, it is simply to point out that equipment that
meets only the basic requirements of IEC 62271-200 is definitely not the same. It is definitely worth
considering the above when both ANS/IEEE C37.20.2 and IEC 62271-200 are requirements of the same
RFQ or specification for MV circuit breaker switchgear projects.
Ted A. Burse
Director, Research and Development