IBTS Solar PV System Inspection Checklist 4
IBTS Solar PV System Inspection Checklist 4
INSPECTION CHECKLIST
GENERAL INFORMATION: Please complete this form.
Customer Name Customer Case Number
SCORECARD:
Total Points Available
REPORT SUMMARY:
Passing Score = > 70% and 0 priority criteria missed Failing Score(s) = < 70% score
> 70% and 1 or more priority criteria missed
How long did the process take from sale to installation? Total Days:
Are there signs of damage or wear to the home stemming from installation of
Yes No N/A
the PV system?
Comments:
Number of Stories
POINT OF INTERCONNECTION
2.1 Method of Interconnection Supply Side Load Side N/A
2.6 Subpanel Breaker Size (current feeding the subpanel busbar) Amps
What is the sum of the rated AC output current from inverter(s)
2.7 Amps
X 1.25?
Is the PV system AC output overcurrent device properly sized? Pass Fail Missing N/A
2.8
NEC 705.12
Is the PV system overcurrent protection installed in the correct
2.9 Pass Fail Missing N/A
location within the panelboard? NEC 705.12(D)(2)(3)(a)
The ampere rating of the overcurrent device protecting the panelboard
busbar, plus 125% of the inverter output current ratings must not
2.10 Pass Fail Missing N/A
exceed 120% of the ampere rating of the panelboard busbar.
NEC 690.8(3), 705.12(D)(2)(3)(b) *
Where the PV system is connected to the supply side of the service
disconnecting means, the sum of the ratings of the inverter AC
2.11 overcurrent protection device(s) must not exceed the rating of the Pass Fail Missing N/A
utility service.
NEC 705.12(A) *
INVERTER
3.1 Type of inverter technology used?
INVERTER
4.1 System Output (kW)
4.3 Manufacturer
4.4 Model
4.23 Are modules UL listed for use? IBC 1505.9 Pass Fail Missing N/A
Are modules spaced according to manufacturer’s
4.24 Pass Fail Missing N/A
recommendations?
4.25 Total Number of Strings or Branch Circuits in System?
Height from the roof surface to the bottom of the module
4.26
frame (in.)
4.27 Tilt and Azimuth measured by?
ELECTRICAL
Are standard building conductors used and was
5.1 appropriate care taken when wiring or completing Pass Fail Missing N/A
terminations? NEC 110.14(A), 690.31
Are conductors on the rooftop properly sized and rated for
5.2 90 degrees C and wet service: THWN-2, THHW, THW, RHW, Pass Fail Missing N/A
XHHW, or ZW? NEC 310.15 *
Do PV Source Circuit free-air conductors have 900 C,
sunlight, and wet service ratings? Single-conductor cable
5.3 type specifically listed and labeled PV-Wire required for Pass Fail Missing N/A
use in ungrounded systems. Grounded systems may use
USE-2 or PV wire. NEC 690.31(D)
Nonmetallic-sheathed conductors and cables are secured
5.4 within 12 inches of each box, cabinet, conduit body or Pass Fail Missing N/A
other termination? NEC 334.30
Are splices suitable for the location in which they are
5.5 made? Wet- location wire nuts shall be used even when Pass Fail Missing N/A
installed in a waterproof junction box. NEC 110.14(B)
Are disconnects rated for their locations and properly Pass Fail Missing N/A
5.6
installed? NEC 690 section III, 705.22
Are disconnects located such that fuses can be isolated for
5.7 Pass Fail Missing N/A
service, where applicable? NEC 690.16
Are module connectors rated for use and are connections
5.8 Pass Fail Missing N/A
properly made? NEC 690.32, 690.33
Is a strain relief fitting appropriate for the installation at
5.9 the junction box or the transition into conduit? Pass Fail Missing N/A
NEC 300.16(B)
Are all zip ties and wire ties rated for use with exposure
5.13 Pass Fail Missing N/A
to UV?
5.14 Are any dissimilar metals being combined? NEC 110.14 Pass Fail Missing N/A
Are conductors loose or not properly managed beneath
5.15 Pass Fail Missing N/A
the array? NEC 110.7
Are Conductors touching roof surface or in contact with Pass Fail Missing N/A
5.16
sharp or abrasive surfaces? NEC 300.4, 334 *
Conductor bend radius: The radius of the curve of the
inner edge of any bend during or after installation shall not Pass Fail Missing N/A
5.17
be less than five times the diameter of the cable.
NEC 334.24
Junction, pull, and outlet boxes are installed so that the
wiring contained in them can be rendered accessible
5.18 directly or by displacement of components secured by Pass Fail Missing N/A
removable fasteners and connected by a flexible wiring
system. NEC 690.34
5.19 Does the system have arc fault protection? NEC 690.11 Pass Fail Missing N/A
STRUCTURAL / MECHANICAL
Are modules and racking equipment mounted securely,
6.1 Pass Fail Missing N/A
neatly, and level? NEC 110.12, 110.13
All junction boxes, combiners, or switchgear are listed,
6.2 rated for exterior application, and securely installed? Pass Fail Missing N/A
NEC 110.3, 110.12, 110.13, 300.6 *
Are there any objects or hardware in contact with module Pass Fail Missing N/A
6.3
backsheet? *
Any sign of damage to modules or system components?
6.4 Pass Fail Missing N/A
NEC 110.12 *
Are modules installed over top of any mechanical or Pass Fail Missing N/A
6.5
plumbing vents? IRC P3103.1
Is conduit rated for its location, with supports properly
6.6 spaced for the size and type of conduit? Pass Fail Missing N/A
NEC 352, 350.22, 358
Are conduit supports rated for use and properly installed? Pass Fail Missing N/A
6.7
NEC 110.13
Is module racking installed to manufacturers’
6.8 Pass Fail Missing N/A
specifications? IBC 1505.9
Are footings, support structure, and all penetrations
6.9 Pass Fail Missing N/A
sufficiently flashed and waterproofed? IBC R903, R905.2.8*
All conduit transitions to conditioned space properly
6.10 Pass Fail Missing N/A
sealed with exterior grade sealant? NEC 300.7
Where applicable, ballast type support systems are
properly installed where roof pitch does not exceed one (1) Pass Fail Missing N/A
6.11
unit vertical in twelve (12) units horizontal, or 4.5°?
IBC 1613.6
Contact
Rudolph Saporite III, Sr. Program Manager
[email protected] | 703.481.2011
Locations: District of Columbia • Louisiana • Missouri • New York • Puerto Rico • Texas • Virginia