509ta Eng Um
509ta Eng Um
DESCRIPTION COMMUNICATIONS
The TJ-509T is a next generation genset SM-GPRS
control unit combining multi-functionality and Web monitoring
wide communication possibilities together Web programming
with a reliable and low cost design. GSM-SMS
The unit complies and mostly exceeds e-mail
world’s tightest safety, EMC, vibration and USB Device
environmental standards for the industrial RS-232
category. Software features are complete J1939-CANBUS
with easy firmware upgrade process through
USB port. The Windows based PC software
allows monitoring and programming through
USB, RS-485, Ethernet and GPRS. The PC and
server based Rainbow Scada software allows
monitoring and control of an unlimited number
of gensets from a single central location.
FUNCTIONALITIES TOPOLOGIES
AMF unit with uninterrupted transfer 2 phases 3 wires, L1-L2
ATS unit with uninterrupted transfer 2 phases 3 wires, L1-L3
Remote start controller 3 phases 3 wires, 3 CTs
Manual start controller 3 phases 3 wires, 2 CTs (L1-L2)
Engine controller 3 phases 3 wires, 2 CTs (L1-L3)
Remote display & control unit 3 phases 4 wires, star
Waveform display of V & I 3 phases 4 wires, delta
Harmonic analysis of V & I 1 phase 2 wires
CTs at genset or load side
TJ 509T-V.112013 1
COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part of this document is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
RELATED DOCUMENTS
FILENAME DESCRIPTION
REVISION HISTORY
REVISION DATE AUTHOR DESCRIPTION
02 15.08.2012 MH Remote Monitoring and SNMP functionality added
03 01.10.2012 MH Revised for firmware version 3.2
03 01.10.2012 MH Revised for firmware version 3.3
2 TJ 509T-V.112013
04 18.04.2013 MH Revised for firmware
version 3.9
TERMINOLOGY
SPARE PARTS
The 509T family units are available in various options and peripheral features. Please use below infor-
mation for ordering the correct version:
TJ 509T-V.112013 3
SAFETY NOTICE
Failure to follow below instructions
will result in death or serious injury
Check the unit for cracks and damages due to transportation. Do not install dam-
aged equipment.
Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
Any electrical parameter applied to the device must be in the range specified
in the user manual. Although the unit is designed with a wide safety margin,
over-range parameters may reduce lifetime, alter operational precision or even
damage the unit.
Do not try to clean the device with solvent or the like. Only clean with a dump
cloth.
4 TJ 509T-V.112013
TABLE OF CONTENTS
1. INSTALLATION INSTRUCTIONS
2. MOUNTING
2.1 DIMENSIONS
2.2 SEALING, GASKET
2.3 ELECTRICAL INSTALLATION
3. TERMINAL DESCRIPTIONS
3.1. BATTERY VOLTAGE INPUT
3.2. AC VOLTAGE INPUTS
3.3. AC CURRENT INPUTS
3.4. DIGITAL INPUTS
3.5. ANALOG SENDER INPUTS AND SENDER GROUND
3.6. CHARGE INPUT TERMINAL
3.7. MAGNETIC PICKUP INPUT
3.8. MAINS CONTACTOR OUTPUT
3.9. GENERATOR CONTACTOR OUTPUT
3.10. DIGITAL OUTPUTS
3.11. INPUT/OUTPUT EXTENSION
3.12. -
3.13. J1939-CANBUS PORT
3.14. -
3.15. USB DEVICE PORT
3.16. -
3.17. RS-232 PORT
3.18. –
3.19. EXTERNAL GSM MODEM
4. TOPOLOGIES
4.1. SELECTING THE TOPOLOGY
4.2. 3 PHASE, 4 WIRE, STAR
4.3. 3 PHASE, 3 WIRE, DELTA
4.4. 3 PHASE, 4 WIRE, DELTA
4.5. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L2)
4.6. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L3)
4.7. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L2)
4.8. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L3)
4.9. 1 PHASE, 2 WIRE
5. FUNCTIONALITIES
5.1. CT LOCATION SELECTION
5.2. AMF FUNCTIONALITY
5.3. ATS FUNCTIONALITY
5.4. REMOTE START FUNCTIONALITY
5.5 ENGINE CONTROLLER FUNCTIONALITY
5.6. REMOTE DISPLAY UNIT FUNCTIONALITY
5.7. 400HZ OPERATION
TJ 509T-V.112013 5
6. CONNECTION DIAGRAMS
6.1. AMF FUNCTIONALITY, CTs AT LOAD SIDE
6.2. AMF FUNCTIONALITY, CTs AT ALTERNATOR SIDE
6.3. ATS FUNCTIONALITY
6.4. REMOTE START FUNCTIONALITY
6.5. ENGINE CONTROL FUNCTIONALITY
6.6. REMOTE DISPLAY PANEL FUNCTIONALITY
7. TERMINAL DESCRIPTION
8. TECHNICAL SPECIFICATIONS
9. DESCRIPTION OF CONTROLS
9.1. FRONT PANEL FUNCTIONALITY
9.2. PUSHBUTTON FUNCTIONS
9.3. DISPLAY SCREEN ORGANIZATION
9.4. AUTOMATIC DISPLAY SCROLL
9.5. MEASURED PARAMETERS
9.6. LED LAMPS
10. WAVEFORM DISPLAY & HARMONIC ANALYSIS
11. DISPLAYING EVENT LOGS
12. STATISTICAL COUNTERS
12.1. FUEL FILLING COUNTER
13. OPERATION OF THE UNIT
13.1. QUICK START GUIDE
13.2. STOP MODE
13.3. AUTO MODE
13.4. RUN MODE, MANUAL CONTROL
13.5. TEST MODE
14. PROTECTIONS AND ALARMS
14.1. DISABLING ALL PROTECTIONS
14.2. SERVICE REQUEST ALARM
14.3. SHUTDOWN ALARMS
14.4. LOADDUMP ALARMS
14.5. WARNINGS
14.6. NON-VISUAL WARNINGS
15. PROGRAMMING
15.1. RESETTING TO FACTORY DEFAULTS
15.2. ENTERING THE PROGRAMMING MODE
15.3. NAVIGATING BETWEEN MENUS
15.4. MODIFYING PARAMETER VALUE
15.5. PROGRAMMING MODE EXIT
16. PROGRAM PARAMETER LIST
16.12. MODEM1-2/SMS1-2-3-4 TELEPHONE NUMBERS
16.13. GSM MODEM PARAMETERS
16.14. -
16.15. SYNCHRONIZATION PARAMETERS
17. CRANK CUTTING
18. OVERCURRENT PROTECTION (IDMT)
19. MOTORIZED CIRCUIT BREAKER CONTROL
20. J1939 CANBUS ENGINE SUPPORT
6 TJ 509T-V.112013
21. -
22. GSM CONFIGURATION
23. -
24. -
25. -
26. CENTRAL MONITORING OF GENSETS
27. E-MAIL SENDING
28. -
29. SMS COMMANDS
30. LOAD TRANSFER MODES
30.1. TRANSFER WITH INTERRUPTION
30.2. UNINTERRUPTED TRANSFER
31. -
32. SOFTWARE FEATURES
32.1. LOAD SHEDDING / DUMMY LOAD
32.2. LOAD ADD / SUBSTRACT
32.3. FIVE STEP LOAD MANAGEMENT
32.4. REMOTE START OPERATION
32.5. DISABLE AUTO START, SIMULATE MAINS
32.6. BATTERY CHARGING OPERATION, DELAYED SIMULATE MAINS
32.7. DUAL GENSET MUTUAL STANDBY OPERATION
32.8. MULTIPLE VOLTAGE AND FREQUENCY
37.9. SINGLE PHASE OPERATION
37.10. EXTERNAL CONTROL OF THE UNIT
37.11. AUTOMATIC EXERCISER
37.12. WEEKLY OPERATION SCHEDULER
37.13. ENGINE HEATING OPERATION
37.14. ENGİNE IDLE SPEED OPERATİON
37.15. ENGINE BLOCK HEATER
37.16. FUEL PUMP CONTROL
37.17. GAS ENGINE FUEL SOLENOID CONTROL
37.18. PRE-TRANSFER SIGNAL
37.19. CHARGING THE ENGINE BATTERY
37.20. EXTERNALLY CONTROLLED DIGITAL OUTPUTS
37.21. COMBAT MODE
38. -
39. -
40. DECLARATION OF CONFORMITY
41. MAINTENANCE
42. DISPOSAL OF THE UNIT
43. ROHS COMPLIANCE
44. TROUBLESHOOTING GUIDE
TJ 509T-V.112013 7
1. INSTALLATION INSTRUCTIONS
Before installation:
• Read the user manual carefully, determine the correct connection diagram.
• Remove all connectors and mounting brackets from the unit, then pass the unit through the
mounting opening.
• Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
• Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
• Be sure that adequate cooling is provided.
• Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
Below conditions may damage the device:
• Incorrect connections.
• Incorrect power supply voltage.
• Voltage at measuring terminals beyond specified range.
• Voltage applied to digital inputs over specified range.
• Current at measuring terminals beyond specified range.
• Overload or short circuit at relay outputs
• Connecting or removing data terminals when the unit is powered-up.
• High voltage applied to communication ports.
• Ground potential differences at non-isolated communication ports.
• Excessive vibration, direct installation on vibrating parts.
8 TJ 509T-V.112013
2. MOUNTING
2.1. DIMENSIONS
TJ 509T-V.112013 9
The unit is designed for panel mounting. The user should not be able to access parts of the unit other
than the front panel.
Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and con-
nectors from the unit, then pass the unit through the mounting opening.
121mm
176mm
Panel Cutout
WALL
10 TJ 509T-V.112013
Two different types of brackets are provided:
TJ 509T-V.112013 11
2.2. SEALING, GASKET
PANEL
GASKET
GASKET
The rubber gasket provides a watertight means of mounting the module to the genset panel. Together
with the gasket, IEC 60529-IP65 protection can be reached from the front panel. A short definition of
IP protection levels is given below.
12 TJ 509T-V.112013
2.3. ELECTRICAL INSTALLATION
Although the unit is protected against electromagnetic disturbance, excessive disturbance can
affect the operation, measurement precision and data communication quality.
Fuses must be connected to the power supply and phase voltage inputs, in close proximity
of the unit.
For current transformer inputs, use at least 1.5mm2 section (AWG15) cable.
The current transformer cable length should not exceed 1.5 meters. If longer cable is used,
increase the cable section proportionally.
TJ 509T-V.112013 13
3. TERMINAL DESCRIPTIONS
14 TJ 509T-V.112013
3.2. AC VOLTAGE INPUTS
TJ 509T-V.112013 15
3.3. AC CURRENT INPUTS
16 TJ 509T-V.112013
Current Transformers must be used for current
measurement. No direct connection allowed.
No common terminals or grounding allowed.
CONNECTING CTs:
Be sure of connecting each CT to the related phase input with the correct polarity. Mixing CTs
between phases will cause faulty power and pf readings.
Many combinations of incorrect CTs connections are possible, so check both order of CTs and their
polarity. Reactive power measurement is affected by incorrect CTs connection in similar way as
active power measurement.
CORRECT CT CONNECTIONS
MAINS or LOAD
ALTERNATOR
Let’s suppose that the genset is loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 100.0 0.0 100 1.00
Phase L3 100.0 0.0 100 1.00
Total 300.0 0.0 300 1.00
TJ 509T-V.112013 17
EFFECT OF POLARITY REVERSAL
MAINS or
LOAD
ALTERNATOR
The generator is still loaded with 100 kW On each phase. The load Power Factor (PF) is 1.
PF in phase L2 will show -1,00 due to reverse CT polarity. The result is that total generator power
displayed by the controller is 100 kW.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 -100.0 0.0 100 -1.00
Phase L3 100.0 0.0 100 1.00
Total 100.0 0.0 300 0.33
MAINS or
LOAD
ALTERNATOR
The generator is still loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
PF in phases L2 and L3 will show -0,50 due to phase shift between voltages and currents which is
caused by CT swapping. The result is that total generator power displayed by controller is 0 kW.
Measured values are as follows:
kW kVAr kVA pf
Phase L1 100.0 0.0 100 1.00
Phase L2 -50.0 86.6 100 -0.50
Phase L3 -50.0 -86.6 100 -0.50
Total 0.0 0.0 300 0.0
18 TJ 509T-V.112013
3.4. DIGITAL INPUTS
Number of inputs: 8 inputs, all configurable
Function selection: from list
Contact type: Normally open or normally closed (programmable)
Switching: Battery negative or battery positive (programmable)
Structure: 47 k-ohms resistor to battery positive, 110k-ohms to battery negative.
Measurement: Analog voltage measurement.
Open circuit voltage: 70% of battery voltage
Low level threshold: 35% of battery voltage
High level threshold: 85% of battery voltage
Maximum input voltage: +100VDC with respect to battery negative
Minimum input voltage: -70VDC with respect to battery negative
Noise filtering: yes
TJ 509T-V.112013 19
3.6. CHARGE INPUT TERMINAL
The Charge terminal is both an input and output.
When the engine is ready to run, this terminal supplies the excitation current to the charge alternator.
The excitation circuit is equivalent to a 2W lamp.
The threshold voltages for warning and shutdown alarm are adjustable through program parameter.
20 TJ 509T-V.112013
3.8. MAINS CONTACTOR OUTPUT
Structure: Relay output, normally closed contact. One terminal is internally
connected to mains phase L1 input.
Max switching current: 16A @250VAC
Max switching voltage: 440VAC
Max switching power: 3000VA
TJ 509T-V.112013 21
3.11. INPUT/OUTPUT EXTENSION
The module provides resources for 32 additional
digital inputs and 32 additional digital outputs.
22 TJ 509T-V.112013
3.13. J1939-CANBUS PORT
The USB-Device port is designed to connect the module to a PC. Using the RainbowPlus software,
programming, control of the genset and monitoring of measured parameters are achieved.
The RainbowPlus software can be downloaded from www.datakom.com.tr website.
The connector on the module is of USB-B type. Thus A to B type USB cable should be used. This is
the same cable used for USB printers.
For more details about programming, control and monitoring please refer to RainbowPlus user
manual.
TJ 509T-V.112013 23
3.17. RS-232 PORT
The 1800/1900 MHz magnetic antenna together with its 2 meter cable is supplied with the modem.
The antenna is intended to be placed outside of the genset panel for the best signal reception.
The module requires a GPRS enabled SIM card for full functionality. Voice-only type SIM cards will
usually not function properly.
Please refer to GSM Modem Configuration Guide for more details.
24 TJ 509T-V.112013
SIM CARD EXTRACTION SIM CARD EXTRACTION /
INSERTION
TJ 509T-V.112013 25
4. TOPOLOGIES
Various topologies are selectable through program parameter.
The topology is independently selectable for both genset and mains sections.
In following drawings the connections are shown for the alternator. Current transformers are sup-
posed connected to the alternator side.
26 TJ 509T-V.112013
4.2 3 PHASE, 4 WIRE, STAR
TJ 509T-V.112013 27
4.4. 3 PHASE, 4 WIRE, DELTA
28 TJ 509T-V.112013
4.6. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L3)
TJ 509T-V.112013 29
4.8. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L3)
30 TJ 509T-V.112013
5. FUNCTIONALITIES
The same unit provides different functionalities through parameter setting. Thus a single stock item
will fulfill various duties, minimizing stock cost.
When CTs are located at the alternator side, them mains current and power parameters will not be
displayed.
When CTs are located at load side, then both mains and genset currents and power parameters will
be displayed, based on contactor positions.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
The unit provides control outputs for both contactors and motorized circuit breakers.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
TJ 509T-V.112013 31
5.5. ENGINE CONTROLLER FUNCTIONALITY
When the Engine Controller functionality is selected, genset electrical measurements and protections
will be disabled. The unit is supposed to control an engine without alternator.
-the unit will not display genset AC parameters (volts, amps, kW and pf).
-genset voltage and frequency protections are disabled. However engine rpm protections
will be active.
Note that the engine controller functionality is compatible with both AMF and Remote Start modes.
When AMF and Engine controller modes are selected, the unit will monitor the mains and will run the
engine upon mains failure. This functionality is useful for the backup electric motor driven systems
during mains failures, like fire pump or irrigation systems.
When Remote Start and Engine controller modes are selected, the unit will start and stop the engine
with external signal only.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
32 TJ 509T-V.112013
5.6. REMOTE DISPLAY UNIT FUNCTIONALITY
The unit is able to become the remote display and control panel of another identical module.
The connection between two modules is done through RS-485 ports. For the best results, a 120 ohms
balanced, low capacitance cable should be used.
The data rate between modules is selectable between 2400 and 115200 bauds.
A high data rate offers better synchronization between modules, but the distance will be limited.
Typically at 115200 bauds and with adequate cable, the distance will be 200m maximum.
The measurement system of the unit allows frequencies up to 1000Hz to be measured precisely.
However the display is limited to 650Hz. Frequencies over 650Hz will be displayed as 650Hz.
The bandwidth of the harmonic analyzer is limited to 1800Hz. Thus in case of a 400Hz system, only
the 3rd harmonic will be displayed.
The waveform display of a 400Hz signal will be represented with 10 points. It will not be as accurate
as 50/60Hz signals.
For more details please read chapter: “Waveform Display & Harmonic Analysis”.
TJ 509T-V.112013 33
6. CONNECTION DIAGRAMS
34 TJ 509T-V.112013
6.2. AMF FUNCTIONALITY, CTs AT LOAD SIDE
TJ 509T-V.112013 35
6.3. ATS FUNCTIONALITY
36 TJ 509T-V.112013
6.4. REMOTE START FUNCTIONALITY
TJ 509T-V.112013 37
6.5. ENGINE CONTROL FUNCTIONALITY
38 TJ 509T-V.112013
6.6. REMOTE DISPLAY PANEL FUNCTIONALITY
TJ 509T-V.112013 39
7. TERMINAL DESCRIPTION
Term Function Technical data Description
1 GENERATOR CON- Relay output, This output provides energy to the genera-
TACTOR 16A-AC tor contactor. If the generator phases do not
have acceptable voltage or frequency values,
the generator contactor will be de-energized.
In order to provide extra security, the nor-
mally closed contact of the mains contactor
should be serially connected to this output.
2 GEN-L1 Generator phase Connect the generator phases to these
3 GEN-L2 inputs, 0-330V- inputs. The generator phase voltages upper
AC and lower limits are programmable.
4 GEN-L3
5 BATTERY NEGATIVE Input, 0-330V-AC Neutral terminal for the generator phases.
40 TJ 509T-V.112013
Term Function Technical data Description
11 BATTERY POSITIVE +12 or 24VDC The positive terminal of the DC Supply.
12 BATTERY NEGATIVE O VDC Power supply negative connection.
13 ANALOG SENDER 3 Resistor measuring Connect to the fuel level sender.
(FUEL LEVEL inputs, Do not connect the sender to other
SENDER) 0-5000 ohms devices.
14 ANALOG SENDER 1 Connect to the oil pressure sender.
(OIL PRESSURE Do not connect the sender to other
SENDER) devices.
15 ANALOG SENDER 2 Connect to the coolant temperature
(COOLANT TEMP. sender. Do not connect the sender to
SENDER) other devices.
16 CHARGE Input and output Connect the charge alternator’s WL/D+
terminal to this terminal. This terminal
will supply the excitation current and
measure the voltage of the charge
alternator.
17 DIGITAL OUTPUT 1 Relay Outputs This relay has programmable function,
10A/33VDC selectable from a list. Factory set as
ALARM output.
18 DIGITAL OUTPUT 2 This relay has programmable function,
selectable from a list. Factory set as
STOP output.
19 DIGITAL OUTPUT 3 This relay has programmable function,
selectable from a list. Factory set as
CRANK output.
20 DIGITAL OUTPUT 4 This relay has programmable function,
selectable from a list. Factory set as
FUEL output.
TJ 509T-V.112013 41
Term Function Technical Description
data
21 DIGITAL INPUT 1 Digital Inputs, The input has programmable function.
0-30Vdc Factory set as EMERGENCY STOP.
22 DIGITAL INPUT 2 The input has programmable function.
Factory set as SPARE INPUT-2.
23 DIGITAL INPUT 3 The input has programmable function.
Factory set as PROGRAM LOCK input.
24 DIGITAL INPUT 4 The input has programmable function.
Factory set as SPARE INPUT-1.
25 DIGITAL INPUT 5 The input has programmable function.
Factory set as LOW COOLANT LEVEL
SWITCH.
26 DIGITAL INPUT 6 The input has programmable function.
Factory set as HIGH TEMP SWITCH.
27 DIGITAL INPUT 7 The input has programmable function.
Factory set as LOW OIL PRESSURE
SWITCH.
28 DIGITAL INPUT 8 The input has programmable function.
Factory set as RECTIFIER FAIL input.
35 ANALOG SENDER 4 Connect to the oil temperature sender.
(OIL TEMP SENDER) Do not connect the sender to other
devices.
42 TJ 509T-V.112013
Term Function Technical data Description
41 CAN GROUND Output 0Vdc Connect the protective shield of the
MPU and CANBUS-J1939 cables to this
terminal, from one end only.
36 CANBUS-H Digital communication Connect the J1939 port of an electronic
37 CANBUS-L port engine to these terminals.
The 120 ohm terminating resistors are
inside the unit. Please do not connect
external resistors.
Use a twisted cable pair or coaxial
cable for best results.
42 MPU - Analog input, 0.5 to Connect the MPU unit to these inputs
43 MPU + 30V-AC Use a twisted cable pair or coaxial
cable for best results.
TJ 509T-V.112013 43
TECHNICAL SPECIFICATIONS
DC Supply Range: 9.0 to 33.0 V-DC.
DC power consumption:
250 mA-DC typical @12V-DC
125 mA-DC typical @24V-DC
500 mA-DC max. @12V-DC
250 mA-DC max. @24V-DC
Alternator voltage: 0 to 300 V-AC (Ph-N), 0 to 520V Ph-Ph
Alternator frequency: 0-500 Hz.
Mains voltage: 0 to 300 V-AC (Ph-N) , 0 to 520V Ph-Ph
Mains frequency: 0-500 Hz.
Current Inputs: from current transformers. ../5A.
CT Range: 5/5A to 5000/5A
VT Range: 0.1/1 to 6500 / 1
kW Range: 0.1kW to 65000 kW
Accuracy:
Voltage: 0.5%+1digit
Current: 0.5%+1 digit
Frequency: 0.5%+1 digit
Power(kW,kVAr): 1.0%+2digit
Power factor: 0.5 %+1digit
Digital inputs: input voltage 0 to 36 V-DC.
Analog input range: 0-5000 ohms.
Mains and genset contactor outputs: 16Amps@250V
DC Outputs (1,2,3,4): Relay outputs, positive switching, rated 10Amp@33V-DC
Cranking dropouts: survives 0V for 100ms.
Magnetic pickup voltage: 0.5 to 30V-RMS.
Magnetic pickup frequency: 10 to 10000 Hz.
Charge Alternator Excitation: 160mA @12VDC, 80mA @24VDC
USB Device: USB 2.0 Full speed
RS-232 Port: selectable baud rate
Operating temperature: -20°C to 70°C (-4 to +158 °F).
Storage temperature: -40°C to 80°C (-40 to +176°F).
Maximum humidity: 95% non-condensing.
IP Protection: IP54 from front panel, IP30 from the rear.
Dimensions: 200 x 148 x 46mm (WxHxD)
Panel Cut-out Dimensions: 176 x 121 mm minimum.
Weight: 450 g (approx.)
Case Material: High Temperature, non-flammable, ROHS compliant ABS/PC
Mounting: Flush mounted with rear retaining plastic brackets.
EU Directives Conformity
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL Compatibility: UL 508 - Industrial Control Equipment
CSA Compatibility: CAN/CSA C22.2 No. 14-2005 – Industrial Control Equipment
44 TJ 509T-V.112013
9. DESCRIPTION OF CONTROLS
9.1. FRONT PANEL FUNCTIONALITY
When the engine hours OR the time limit is over, the SERVICE REQUEST led (red) will start to flash
and the service request output function will be active. The service request can also create a fault
condition of any level following parameter setting.
The service request output function may be assigned to any digital output using Relay Definition
program parameters. Also relays on an extension module may be assigned to this function.
To turn off the SERVICE REQUEST led, and reset the service
period, press together the ALARM MUTE and LAMP TEST keys
for 5 seconds.
TJ 509T-V.112013 45
9.2. PUSHBUTTON FUNCTIONS
BUTTON FUNCTION
Selects TEST mode. The genset runs and takes the load.
Selects AUTO mode. The genset runs when necessary and takes the load.
46 TJ 509T-V.112013
9.3. DISPLAY SCREEN ORGANIZATION
The unit measures a large number of electrical and engine parameters. The display of the parameters
is organized as PARAMETER GROUPS and items in a group.
Each depression of the button will cause the display to switch to the next group of parameters.
Afterthe last group the display will switch to the first group.
Each depression of the button will cause the display to switch to the previous group of param-
eters. After the first group the display will switch to the last group.
Navigation inside a groups is made with and buttons.
Each depression of the button will cause the display to switch to the next parameter in the same
group. After the last parameter the display will switch to the first parameter.
Each depression of the button will cause the display to switch to the previous parameter in the
same group. After the first parameter the display will switch to the last parameter.
Below is a basic list of parameter groups:
TJ 509T-V.112013 47
9.4. AUTOMATIC DISPLAY SCROLL
The unit will automatically scroll all Mains, Genset and Engine measurements with programmable
interval. The scroll period setting can be performed using the RainbowPlus program through Module
> Screen options.
Eventually the same parameter can be modified through the front panel programming menu. The
related parameter is Controller Configuration > Screen Scroll Timer.
48 TJ 509T-V.112013
TJ 509T-V.112013 49
9.5. MEASURED PARAMETERS
The unit performs a detailed set of AC measurements.
Mains currents and power parameters (listed in blue color) are measured and displayed only if CTs
are placed at load side. please see connection diagrams section for more details.
The list of measured AC parameters is below:
Mains voltage phase L1 to neutral Gen voltage phase L1 to neutral
Mains voltage phase L2 to neutral Gen voltage phase L2 to neutral
Mains voltage phase L3 to neutral Gen voltage phase L3 to neutral
Mains average voltage phase to neutral Gen average voltage phase to neutral
Mains voltage phase L1-L2 Gen voltage phase L1-L2
Mains voltage phase L2-L3 Gen voltage phase L2-L3
Mains voltage phase L3-L1 Gen voltage phase L3-L1
Mains frequency Gen frequency
Mains current phase L1 Gen current phase L1
Mains current phase L2 Gen current phase L2
Mains current phase L3 Gen current phase L3
Mains average current Gen average current
Mains kW phase L1 Gen kW phase L1
Mains kW phase L2 Gen kW phase L2
Mains kW phase L3 Gen kW phase L3
Mains total kW Gen total kW
Mains kVA phase L1 Gen kVA phase L1
Mains kVA phase L2 Gen kVA phase L2
Mains kVA phase L3 Gen kVA phase L3
Mains kVAr phase L1 Gen kVAr phase L1
Mains kVAr phase L2 Gen kVAr phase L2
Mains kVAr phase L3 Gen kVAr phase L3
Mains pf phase L1 Gen pf phase L1
Mains pf phase L2 Gen pf phase L2
Mains pf phase L3 Gen pf phase L3
Mains total pf Gen total pf
Mains neutral current Gen Neutral current
Below engine parameters are always measured:
Engine speed (rpm)
Battery voltage,
The unit features 4 analog senders, fully configurable for the name and function.
50 TJ 509T-V.112013
9.6. LED LAMPS
STATUS LEDS:
AUTO READY: Turns on when the AUTO mode is selected and there is no condition pre
venting engine start.
ALARM: Turns on when a shutdown alarm or loaddump condition exists.
WARNING: Turns on when a warning condition exists
SERVICE REQUEST: Turns on when at least one of the service counters has expired.
MODE LEDS: Each led turns on when the related mode is selected, either locally or remotely.
MIMIC DIAGRAM LEDS:
MAINS AVAILABLE: This led turns on when all mains phase voltages and the mains
frequency are within limits. If enabled, the mains phase rotation order must be also right.
When any digital input is defined as Remote Start, this led will reflect the status of the
input. When a Simulate Mains signal is present, then mains status will become “available”.
When a Force to Start signal is present, then the mains status will become “not available”.
MAINS CONTACTOR ON: Turns on when the mains contactor is activated.
GENSET CONTACTOR ON: Turns on when the genset contactor is activated.
GENSET AVAILABLE: This led turns on when all genset phase voltages and the genset
frequency are within limits. If enabled, the genset phase rotation order must be also right.
TJ 509T-V.112013 51
10. WAVEFORM DISPLAY & HARMONIC ANALYSIS
The unit features waveform display together with a precision harmonic analyzer for both mains and
genset voltages and currents. Both phase to neutral and phase to phase voltages are available for
analysis, thus 18 channels in total are possible.
Scopemeter Display
The waveform display memory is of 100 samples length and 13 bit resolution, with a sampling rate
of 4096 s/s. Thus one cycle of a a 50Hz signal is represented with 82 points. The vertical scale is
automatically adjusted in order to avoid clipping of the signal.
The waveform is displayed on the device screen, and with more resolution on PC screen through the
RainbowPlus program.
The display memory is also available in the Modbus register area for third party applications. For more
details please check chapter “MODBUS Communications”.
The waveform display is updated twice a second. All channels may be scrolled using buttons.
52 TJ 509T-V.112013
The harmonic analyzer consists on a Fast Fourier Transform (FFT) algorithm which is run twice a
second on the selected channel.
The sample memory is 1024 samples length and 13 bits resolution with a sampling rate of 4096 s/s.
The theory says that a periodic signal may have only odd multiples of the main frequency. Thus in a
50Hz network, harmonics will be found only at 150, 250, 350, 450 Hz etc...
The unit is able to analyze up to 1800Hz and up to 31th harmonic, whichever is
smaller. Thus in a 50Hz system all 31 harmonics will be displayed, but in a 60Hz system only 29
harmonics will come to the screen.
In case of a 400Hz system, only the 3rd harmonic will be displayed.
The second display is alphanumeric, thus all harmonics are displayed with 0.1% resolution in order to
provide more detailed information.
On RainbowPlus program, harmonics and waveform are displayed on a single screen with more
resolution.
TJ 509T-V.112013 53
11. DISPLAYING EVENT LOGS
The unit features more than 400 event logs with date-time stamp and full snapshot of measured
values at the moment that the event has occurred.
Possible event sources are various. Every source can be individually enabled or disabled:
Program mode entrance event: recorded with the password level when program mode is entered.
Periodic event: recorded every 30 minutes when the engine is running, and every 60 minutes any-
way.
Mode change event: recorded when the operation mode is changed.
Shutdown/loaddump/warning events: recorded when the related fault condition occurs.
Mains fail/restore events: recorded when mains status is changed
Engine started/stopped events: recorded when engine status is changed
Genset on_load/off_load events: recorded when the genset loading status is changed
54 TJ 509T-V.112013
Event logs are displayed within the program mode menu. This is designed in order to reduce the
interference of event logs with other measurement screens.
To enter the event display, press together and buttons for 5 seconds.
When the program mode is entered, below password entry screen will be displayed.
Skip the password entry screen by pressing the button 4 times. The screen below left will come.
Press again the button. The last stored event will open, as in the below-right picture.
The first page will display the event number, event type, fault type and date-time information/
TJ 509T-V.112013 55
12. STATISTICAL COUNTERS
The unit provides a set of non resettable incremental counters for statistical purposes.
These counters are kept in a non-volatile memory and are not affected from power failures.
The quantity of the fuel filled in the tank is read from pulses generated by a flowmeter installed at
the tank filling hose. Flowmeter pulse outputs will be connected to the MPU input of the controller.
The controller will count pulses and convert them in liters (or gallons) then increment the fuel filling
counter by the calculated amount.
The fuel filling counter is visible through Scada and Central Monitoring. Thus the genset operator can
confirm fuel invoices with the real amount of fuel filled in the tank, preventing corruption.
56 TJ 509T-V.112013
13. OPERATION OF THE UNIT
13.1. QUICK START GUIDE
STOPPING THE ENGINE: Press STOP button
LOAD TEST: Press TEST button. The genset will run and take the load.
AUTOMATIC OPERATION: Press AUTO button. Check that AUTO READY led is illuminated.
If the STOP button is pressed again, then the engine will immediately stop.
If the engine fails to stop after the expiration of Stop Timer then a Fail to Stop warning will occur.
In this mode, the mains contactor will be energized only if mains phase voltages and frequency are
within the programmed limits. If enabled, the mains phase order is also checked.
If a Remote Start or Force to Start signal arrives in STOP mode, the genset will not start until AUTO
mode is selected
TJ 509T-V.112013 57
13.3. AUTO MODE
The AUTO mode is entered by pressing the button.
The AUTO mode is used for the automatic transfer between genset and mains. The controller will
constantly monitor the mains availability. It will run the engine and transfer the load when a mains
failure occurs.
When mains are evaluated as “unavailable” then an engine start sequence begins:
• The unit waits during Engine Start Delay for skipping short mains failures. If the mains is restored
before the end of this timer, the genset will not start.
• The unit turns on the fuel and preheat glow plugs (if any) and waits for preheat timer.
• The engine will be cranked for programmed times during crank timer. When the engine fires, the
crank relay will be immediately deactivated. See section Crank Cutting for more details.
• The engine will run at idle speed during Idle Speed Timer.
• The engine will run unloaded during engine heating timer.
• If alternator phase voltages, frequency and phase order are correct, the unit will wait for the
generator contactor period and the generator contactor will be energized.
When mains are evaluated as “available” again then an engine stop sequence begins:
• The engine will continue to run for the mains waiting period to allow mains voltages to stabilize.
• Then the generator contactor is deactivated and the mains contactor will be energized after
mains contactor timer.
• If a cooldown period is given, the generator will continue to run during the cooldown period.
• Before the end of cooldown, the unit will reduce the engine speed to idle speed.
• At the end of cooldown, the fuel solenoid will be de-energized, the stop solenoid will be
energized for Stop Solenoid timer and the diesel will stop.
• The unit will be ready for the next mains failure.
58 TJ 509T-V.112013
13.4. RUN MODE, MANUAL CONTROL
The RUN mode is entered by pressing the button.
When the RUN mode is selected, the engine will be started regardless of the mains availability.
• The unit turns on the fuel and preheat glow plugs (if any) and waits for preheat timer.
• The engine will be cranked for programmed times during crank timer. When the engine fires, the
crank relay will be immediately deactivated. See section Crank Cutting for more details.
• The engine will run at idle speed during Idle Speed Timer.
• The engine will run unloaded until another mode is selected..
The RUN mode allows also manual contactor control through MC and GC buttons.
When a contactor button is pressed, the related contactor will change position. Thus if it was on, then
it will turn off. If it was off then it will turn on.
If the other contactor was on, then it will turn off, the controller will wait for the related contactor
timer and the contactor will turn on. This will prevent manual closure of both contactors.
In order to stop the engine press button or select another mode of operation.
TJ 509T-V.112013 59
13.5. TEST MODE
The TEST mode is entered by pressing the button.
The TEST mode is used in order to test the genset under load.
Once this mode is selected, the engine will run as described in the AUTO mode, regardless of the
mains availability and the load will be transferred to the genset.
The genset will feed the load indefinitely unless another mode is selected.
Most of the alarms have programmable trip levels. See the programming chapter for adjustable alarm
limits.
60 TJ 509T-V.112013
14.1. DISABLING ALL PROTECTIONS
The unit allows any digital input to be configured as “Disable Protections”.
This input configuration is used in cases where the engine is required to run until destruction. This
may be the case under critical conditions like fire fighting or other emergency cases.
This input should be configured as a “Warning”. Thus when protections are disabled, a warning mes-
sage will immediately appear on the screen.
When protections are disabled, all shutdown alarms and loaddumps will become warnings. They will
appear on the screen, but will not affect genset operation.
The input may be constantly activated, or preferably it may be activated by an external key activated
switch in order to prevent unauthorized activation.
Disabling protections will allow the genset run until destruction. Place
written warnings about this situation in the genset room.
To turn off the SERVICE REQUEST led, and reset the service
period, press together the ALARM MUTE and LAMP TEST keys for 5 seconds.
The remaining engine hours and the remaining time limits are kept stored in a non-volatile memory
and are not affected from power supply failures.
The time and engine hours to service are displayed in the GENSET STATUS menu group.
TJ 509T-V.112013 61
14.3. SHUTDOWN ALARMS
Digital input and analog sender alarms are fully
programmable for the alarm name, sampling and
action. Only internal alarms are explained in this section.
GENSET Set if the generator frequency is outside programmed limits. These faults will be moni-
LOW / HIGH tored with Fault Holdoff Timer delay after the engine is running. Low and high limits
FREQUENCY are separately programmable. The detection delay is also programmable. Another high
frequency shutdown limit which is 12% above the high limit is always monitored and
stops the engine immediately.
GENSET Set if the generator rpm is outside programmed limits. These faults will be monitored
LOW / HIGH with Fault Holdoff Timer delay after the engine is running. Low and high limits are
RPM separately programmable. The detection delay is also programmable. The high rpm
overshoot limit is always monitored and stops the engine immediately.
GENSET Set if any of the generator phase voltages goes outside programmed limits for Voltage
LOW / HIGH Fail Timer. This fault will be monitored with Fault Holdoff Timer delay after the engine
VOLTAGE is running.
LOW / HIGH Set if the genset battery voltage is outside programmed limits. Low and high limits are
BATTERY separately programmable. The detection delay is also programmable.
VOLTAGE
FAIL TO Set if the engine is not running after programmed number of start attempts.
START
LOW Set if the charge alternator voltage is below the programmed limit. This fault will be
CHARGE monitored with Fault Holdoff Timer delay after the engine is running.
VOLTAGE
J1939 ECU Set if no information has been received during 3 seconds from the ECU of the elec-
FAIL tronic engine. This fault condition is only controlled when fuel is on.
VOLTAGE Set if any of the generator phase voltages differs from the average by more than Volt-
UNBAL- age Unbalance Limit for Voltage Fail Timer. This fault will be monitored with Fault
ANCE Holdoff Timer delay after the engine is running.
CURRENT Set if any of the generator phase currents differs from the average by more than Volt-
UNBAL- age Unbalance Limit for Voltage Fail Timer. This fault will be monitored with Fault
ANCE Holdoff Timer delay after the engine is running. The action taken at fault condition is
programmable.
OVERCUR- Set if at least one of the genset phase currents goes over the Overcurrent Limit for
RENT the period allowed by the IDMT curve setting. The allowed timer is dependent of the
overcurrent level. If currents go below the limit before expiration of the timer then no
alarm will be set. Please check chapter Overcurrent Protection (IDMT) for more details.
The action taken at fault condition is programmable.
PICKUP SIG- Set if the rpm measured from the magnetic pickup input falls below the Crank Cut
NAL LOST RPM level during Loss of Speed Signal Timer. The action of signal loss is program-
mable.
SERVICE Set if at least one of the service counters has expired. In order to reset the service
REQUEST counters please hold pressed both with and buttons during 5 seconds. The screen
will display “Completed!”
62 TJ 509T-V.112013
14.4. LOADDUMP ALARMS
VOLTAGE UNBALANCE Set if any of the generator phase voltages differs from the average
by more than Voltage Unbalance Limit for Voltage Fail Timer.
This fault will be monitored with Fault Holdoff Timer delay after the
engine is running.
CURRENT UNBALANCE Set if any of the generator phase currents differs from the average
by more than Voltage Unbalance Limit for Voltage Fail Timer. This
fault will be monitored with Fault Holdoff Timer delay after the en-
gine is running. The action taken at fault condition is programmable.
OVERCURRENT Set if any of the generator phase voltages goes outside programmed
limits for Voltage Fail Timer. This fault will be monitored with Fault
Holdoff Timer delay after the engine is running.
OVERLOAD Set if the genset power (kW) supplied to the load goes over the Over-
load Load Dump limit for Overload Timer. If the power goes below
the limit before expiration of the timer then no alarm will be set.
REVERSE POWER Set if the genset power (kW) is negative and goes over the Reverse
Power limit for Reverse Power Timer. If the power goes below the
limit before expiration of the timer then no alarm will be set.
REVERSE POWER Set if the genset power (kW) is negative and goes over the Reverse
Power limit for Reverse Power Timer. If the power goes below the
limit before expiration of the timer then no alarm will be set.
GENSET PHASE ORDER Set if the fault is enabled and the genset phase order is reverse.
FAIL
MAINS CB FAIL TO OPEN Set if the feedback input is defined and the related contactor block
feedback signal is not detected after the expiration of Contactor
Open/Close Fail Timer.
PICKUP SIGNAL LOST Set if the rpm measured from the magnetic pickup input falls below
the Crank Cut RPM level during Loss of Speed Signal Timer. The
action of signal loss is programmable.
SERVICE REQUEST Set if at least one of the service counters has expired. In order to
reset the service counters please hold pressed both with and
buttons during 5 seconds. The screen will display “Completed!”
UNIT LOCKED Set if the controller is remotely locked.
TJ 509T-V.112013 63
14.5. WARNINGS
GENSET LOW / HIGH Set if the generator frequency is outside programmed limits. These
FREQUENCY faults will be monitored with Fault Holdoff Timer delay after the
engine is running. Low and high limits are separately programmable.
The detection delay is also programmable. Another high frequency
shutdown limit which is 12% above the high limit is always monitored
and stops the engine immediately.
GENSET LOW / HIGH Set if the generator rpm is outside programmed limits. These faults will
RPM be monitored with Fault Holdoff Timer delay after the engine is run-
ning. Low and high limits are separately programmable. The detection
delay is also programmable. The high rpm overshoot limit is always
monitored and stops the engine immediately.
GENSET LOW / HIGH Set if any of the generator phase voltages goes outside programmed
VOLTAGE limits for Voltage Fail Timer. This fault will be monitored with Fault
Holdoff Timer delay after the engine is running.
LOW / HIGH BATTERY Set if the genset battery voltage is outside programmed limits. Low
VOLTAGE and high limits are separately programmable. The detection delay is
also programmable.
FAIL TO STOP Set if the engine has not stopped before the expiration of the Stop
Timer.
LOW CHARGE VOLTAGE Set if the charge alternator voltage is below the programmed limit. This
fault will be monitored with Fault Holdoff Timer delay after the engine
is running.
64 TJ 509T-V.112013
J1939 ECU FAIL Set when an engine fault code is received from the ECU of the electronic
engine. This fault will not cause an engine stop. If necessary, the engine will
be stopped by the ECU.
VOLTAGE Set if any of the generator phase voltages differs from the average by more
UNBALANCE than Voltage Unbalance Limit for Voltage Fail Timer. This fault will be moni-
tored with Fault Holdoff Timer delay after the engine is running.
CURRENT Set if any of the generator phase currents differs from the average by more
UNBALANCE than Voltage Unbalance Limit for Voltage Fail Timer. This fault will be
monitored with Fault Holdoff Timer delay after the engine is running. The
action taken at fault condition is programmable.
OVERCURRENT Set if at least one of the genset phase currents goes over the Overcurrent
Limit for the period allowed by the IDMT curve setting. The allowed timer
is dependent of the overcurrent level. If currents go below the limit before
expiration of the timer then no alarm will be set. Please check chapter Over-
current Protection (IDMT) for more details. The action taken at fault condition
is programmable.
OVERCURRENT Set if at least one of the genset phase currents goes over the Overcurrent
Limit .
REVERSE POWER Set if the genset power (kW) is negative and goes over the Reverse Power
limit for Reverse Power Timer. If the power goes below the limit before
expiration of the timer then no alarm will be set.
MAINS PHASE Set if the mains phase order checking is enabled, mains phases are present
ORDER FAIL and mains phase order is reversed. This fault prevents the Mains Contactor
to close.
GENSET CB FAIL Set if the feedback input is defined and the related contactor block feedback
TO CLOSE / OPEN signal is not detected after the expiration of Contactor Open/Close Fail Timer.
MAINS CB FAIL Set if the feedback input is defined and the related contactor block feedback
TO CLOSE signal is not detected after the expiration of Contactor Open/Close Fail Timer.
SYNCHRONIZA- Set if the uninterrupted transfer is enabled and voltage, frequency and phase
TION FAIL matching is not found before the expiration of the Synchronization Fail
Timer
PICKUP SIGNAL Set if the rpm measured from the magnetic pickup input falls below the
LOST Crank Cut RPM level during Loss of Speed Signal Timer. The action of
signal loss is programmable.
SERVICE Set if at least one of the service counters has expired. In order to reset the
REQUEST service counters please hold pressed both with and buttons during 5
seconds. The screen will display “Completed!”
EEPROM WRITE Set if the internal non-volatile memory cannot be written.
FAULT
ENGINE RUNNING Set if the engine is running while the fuel output is not energized.
AUTO NOT READY Set if the genset is not in AUTO mode or a fault condition or the weekly
schedule prevents the automatic starting of the genset.
TJ 509T-V.112013 65
14.6. NON-VISUAL WARNINGS
66 TJ 509T-V.112013
15. PROGRAMMING
15.1. RESETTING TO FACTORY DEFAULTS
In order to resume to the factory set parameter values:
-hold pressed the OFF, LAMP TEST and ALARM MUTE buttons for 5 seconds,
-“RETURN TO FACTORY SET” will be displayed
-immediately press and hold pressed the ALARM MUTE button for 5 seconds
-factory set values will be reprogrammed to the parameter memory.
TJ 509T-V.112013 67
The program mode is used to adjust timers, operational limits and the configuration of the unit.
Although a free PC program is provided for programming, every parameter may be modified through
the front panel, regardless of the operating mode.
When modified, program parameters are automatically recorded into a non-erasable memory and take
effect immediately.
The program mode will not affect the operation of the unit. Thus programs may be modified anytime,
even while the genset is running.
The , buttons modify the value of the current digit. The MENU ► , MENU buttons navigate
►
►
►
between digits.
The unit supports 3 password levels. The level_1 is designed for field adjustable parameters. The
level_2 is designed for factory adjustable parameters. The level_3 is reserved. It allows recalibration
of the unit.
The password level-1 is factory set to ‘1234’ and the password level-2 is factory set to ‘9876’.
If a wrong password is entered, the unit will still allow access to the program parameters, but in read-
only mode.
If password “0000” is entered, only EVENT LOG file will be available.
68 TJ 509T-V.112013
15.3. NAVIGATING BETWEEN MENUS
The program mode is driven with a two level menu system. The top menu consists on program
groups and each group consists on various program parameters.
When program mode is entered, a list of available groups will be displayed. Navigation between
different groups are made with and buttons. Selected group is shown in reverse video (blue on
►
white). In order to enter inside a group, please press MENU ► button. In order to exit from the group
►
to the main list please press MENU button.
Navigation inside a group is made also with and buttons. A list of available parameters will be
►
displayed. Selected parameter is shown in reverse video (blue on white). In order display/change
the value of this parameter, please press MENU ► button. Parameter value may be increased and
decreased with and buttons. If these keys are hold pressed, the program value will be in-
►
TJ 509T-V.112013 69
15.4. ENTERING THE PROGRAMMING MODE
70 TJ 509T-V.112013
16. PROGRAM PARAMETER LIST
16.1. CONTROLLER CONFIGURATION GROUP
Parameter Definition Unit Min Max Factory Set Description
LCD Contrast - 30 50 39 This parameter is used to set LCD
contrast. Adjust for the best viewing
angle.
Screen Scroll Timer sec 0 250 0 The screen will scroll between differ-
ent measurements with this interval.
If set to zero, the screen scroll will be
disabled.
Language - 0 1 0 0: English language selected.
1: Local language selected. This
language may depend on the country
where the unit is intended to be used.
Genset Default Display - 0 4 0 This parameter selects the screen
which is displayed during genset on
load operation.
0: genset voltages table
1: genset currents and freq. table
2: genset kW and pf table
3: genset kVA and kVAr table
4: genset average measurements
Status Prompt Window - 0 1 0 0: Status prompts disabled
Enable 1: Status prompts enabled
Fault Holdoff Timer sec 0 120 12 This parameter defines the delay after
the engine runs and before the fault
monitoring is enabled.
Alarm Relay Timer sec 0 120 60 This is the period during which the
ALARM relay is active. If the period is
set to 0, this will mean that the period
is unlimited.
Intermittent Alarm - 0 1 0 0: continuous
Relay 1: intermittent (turns on and off every
second)
Emergency Backup - 0 1 0 0: In RUN mode, the load will not be
Operation transferred to the genset even if the
mains fails.
1: In RUN mode, the load will be
transferred to the genset if the mains
fails.
Exerciser Enable - 0 1 0 0: automatic exerciser disabled
1: automatic exerciser enabled
TJ 509T-V.112013 71
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Parameter Defini- Unit Min Max Factory Description
tion Set
Exercise Period - 0 1 0 0: exercise once per week
1: exercise once per month
The exact exerciser day and time is ad-
justed within the EXERCISE SCHEDULE
section.
Exercise Off/On Load - 0 1 1 0: Exercise at RUN mode
1: Exercise at TEST mode
Delayed Simulate - 0 1 0 0: delayed simulate mains disabled
Mains 1: delayed simulate mains enabled
Modem Selection - 0 4 0 0: not used
1: Internal GSM modem
2: external GSM Datakom modem
3: external GSM generic modem
4: external PSTN (land) modem
External Modem bns 2400 115200 115200 This is the data rate for accessing the
Baud Rate external modem.
GSM Sim Card Pin - 0000 9999 0 If the GSM SIM card uses pin number,
enter the pin number here. If incorrect
pin number is entered, then the SIM
card will not operate.
SMS Enable - 0 1 0 0: SMS messages disabled
1: SMS messages enabled
GPRS Connection - 0 1 0 0: GPRS disabled
Enable 1: GPRS enabled
Web Programming - 0 1 0 0: Web programming disabled
Enable 1: Web programming enabled
Web Control Enable - 0 1 0 0: Web control disabled
1: Web control enabled
Web Refresh Rate sec 0 240 5 The unit will refresh the web page with
this interval.
Ping Period sec 30 900 120 The unit will check the availability
of the internet connection with this
interval.
Rainbow Scada sec 0 65535 5 The unit will update the distant moni-
Refresh Rate toring terminal with this rate.
72 TJ 509T-V.112013
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Rainbow Scada - 0 65535 0 This is the port number of the
Address-1 Port first monitoring terminal address.
Rainbow Scada - 0 65535 0 This is the port number of the
Address-2 Port second monitoring terminal
address.
Web Server Port - 0 65535 80 This is the port number of the
internal web server. The unit will
answer queries to this port only.
Modbus TCP/IP Port - 0 65535 502 Internal Modbus TCP/IP server’s
port number. The unit answers
Modbus requests to this port
only.
SMTP Port - 0 65535 587 This is the port number used for
e-mail sending.
Ethernet to RS-485 - 0 1 0 0: ethernet-modbus gateway
Modbus Gateway function disabled.
Enable 1: ethernet-modbus gateway
function enabled. The unit will
redirect Modbus requests from
ethernet to the RS-485 port.
GPRS to RS-485 Mod- - 0 1 0 0: gprs-modbus gateway function
bus Gateway Enable disabled.
1: gprs-modbus gateway function
enabled. The unit will redirect
Modbus requests from GPRS to
the RS-485 port.
RS-485 Enable - 0 1 1 0: RS-485 port disabled
1: RS-485 port enabled
Modbus Address - 0 240 1 This is the modbus controller
identity used in Modbus com-
munication.
RS-485 Baud Rate bps 2400 115200 9600 This is the data rate of the RS-
485 Modbus port.
Ethernet Enable - 0 1 1 0: ethernet port disabled
1: ethernet port enabled
Oil Pressure Switch - 0 1 0 0: crank cut is performed through
Priority oil pressure switch and oil pres-
sure sender reading
1: crank cut is performed only
through oil pressure switch
TJ 509T-V.112013 73
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Flashing Relay ON min 0 1200 0 Delayed Simulate Mains Opera-
Timer tion: max genset running time after
Simulate Mains signal disappears.
Dual Genset Systems: flashing
relay ON state duration timer.
Flashing Relay OFF min 0 1200 0 Dual Genset Systems: flashing
Timer relay OFF state duration.
Real Time Clock Adjust - 0 255 117 This parameter trims precisely the
real time clock circuit. Values from
0 to 63 speed up the clock with
0.25sec/day steps. Values from
127 to 64 slow down the clock with
0.25sec/day steps.
Hysteresis Voltage V-AC 0 30 8 This parameter provides the mains
and genset voltage limits with
a hysteresis feature in order to
prevent faulty decisions.
For example, when the mains are
present, the mains voltage low limit
will be used as the programmed
low limit. When the mains fail, the
low limit will be incremented by
this value. It is advised to set this
value to 8 volts.
Engine Control Only - 0 1 0 0: Genset control
1: Engine control (no alternator)
Alternator Pole Pairs - 1 8 2 This parameter is used for frquency
to rpm conversion. For a 1500/1800
rpm engine select 2. For a
3000/3600 rpm engine select 1.
RPM from genset - 0 1 1 0: read rpm from the MPU input
frequency 1: convert frequency to rpm (using
Alternator Pole Pairs)
Crank Teeth Count - 1 244 30 This is the number of pulses gener-
ated by the magnetic pickup sens-
ing unit in one turn of the flywheel.
74 TJ 509T-V.112013
CONTROLLER CONFIGURATION GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
SMS on Mains Change - 0 1 0 This parameter controls SMS
sending when mains voltages
status is changed. No warnings
generated.
0: no SMS on mains failed or
restored
1: SMS sent on mains failed or
restored
SMS on IP Change - 0 1 0 This parameter controls SMS
sending when IP address of GPRS
connection is changed. No warn-
ings generated.
0: no SMS on IP change
1: SMS sent on IP change
E-mail on IP Change - 0 1 0 This parameter controls e-mail
sending when IP address of
GPRS or ethernet connection is
changed. No warnings generated.
0: no e-mail on IP change
1: e-mail sent on IP change
Fuel Pump Low Limit % 0 100 20 If the fuel level measured from
the sender input falls below this
level, then the FUEL PUMP func-
tion will become active.
Fuel Pump High Limit % 0 100 80 If the fuel level measured from
the sender input goes above this
level, then the FUEL PUMP func-
tion will become passive.
Warning Before Start - 0 1 1 This parameter controls the
activation of the ALARM output
during “Engine Start Delay” timer
before engine run.
0: no warning before start
1: warning before start
Latch all Warnings - 0 1 0 0: warnings are latching/non-
latching on parameter control
1: all warnings are latched. Even
if the fault source is removed,
warnings will persist until manu-
ally reset.
TJ 509T-V.112013 75
CONTROLLER CONFIGURATION GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Remote Control Enable - 0 1 1 This parameter controls remote
control of the unit through Rainbow,
Modbus and Modbus-IP.
0: remote control disabled
1: remote control enabled
Annunciator Mode - 0 1 0 0: normal operation
1: the unit becomes an annunciator
of the remote unit. Engine/genset
control functions are disabled.
CT Location - Gen Load Gen 0: CTs are at the genset side.
Mains currents are not measured.
1: CTs are at load side. Both mains
and genset currents are monitored
following contactor status.
Reverse CT Direction - 0 1 0 This parameter is useful to invert all
CT polarities at the same time.
0: normal CT polarity assumed.
1: reverse CT polarity assumed.
Buzzer Enable - 0 1 1 Internal buzzer control (not func-
tional in D-500)
0: buzzer disabled
1: buzzer enabled
Unit Functionality - 0 3 AMF 0: AMF functionality. The unit con-
trols both engine and load transfer.
The genset starts based on mains
status.
1: ATS functionality. The unit con-
trols the load transfer and issues
genset start signal based on mains
status.
2: REMOTE START functional-
ity. The unit controls engine and
alternator. The genset starts with
external signal.
3: RESERVED. Not used.
76 TJ 509T-V.112013
CONTROLLER CONFIGURATION GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Data Logging Period sec 2 3600 2 This parameter adjusts the data
logging frequency to micro-
SD or USB Flash memories.
Frequent recording will require
more memory capacity.
With a period of 2 seconds,
4GB per year of memory is
necessary.
With a period of 1 minute,
133MB is consumed per year.
LCD Backlight Dimming min 0 1440 60 If no button is pressed during
Delay this period, then the unit will re-
duce the LCD screen backlight
intensity in for economy.
Fuel Filling Timer sec 0 36000 0 After activation of the fuel
pump function, if the Fuel Pump
High Limit level is not reached,
then the fuel pump will stop for
safety.
If this parameter is set to zero,
then the timer is unlimited.
SMS Commands - 0 1 0 0: SMS commands not ac-
Enabled cepted
1: SMS commands are accept-
ed but from listed telephone
numbers only.
Open with Last Mode - 0 1 0 0: The unit powers up in STOP
mode
1: The unit powers up in the
same operating mode before
power down.
Pre-Transfer Delay sec 0 60 0 If this parameter is not zero,
the unit will activate the Wait
Before Transfer output function
during this timer, before initiat-
ing a load transfer.
This function is designed for
elevator systems, in order to
bring the cabin to a floor and
open doors before transfer.
TJ 509T-V.112013 77
CONTROLLER CONFIGURATION GROUP (continued)
Parameter Unit Min Max Factory Set Description
Definition
E-mail - 0 1 0 0: No e-mail at mains status changes
on mains 1: E-mails sent at mains status change
change
Enable Auto - 0 1 0 0: Auto not Ready Warning disabled
not Ready 1: Auto not Ready Warning enabled
Warning
78 TJ 509T-V.112013
16.2. ELECTRICAL PARAMETERS GROUP
Parameter Unit Min Max Factory Description
Definition Set
Current Trans- Amp 1 5000 500 This is the rated value of current trans-
former Primary formers. All transformers must have
the same rating. The secondary of the
transformer will be 5 Amps.
Voltage Trans- - 0 5000 1.0 This is the voltage transformer ratio. This
former Ratio value will multiply all voltage and power
readings. If transformers are not used, the
ratio should be set to 1.0
Nominal Voltage V-AC 0 300 230 The nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
Nominal Fre- Hz 0 500 50 The nominal value of genset and mains
quency frequency. Frequency limits are defined by
reference to this value.
Nominal Volt- V-AC 0 300 120 When secondary voltage is selected, this
age-2 is the nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
Nominal Fre- Hz 0 500 60 When secondary frequency is selected,
quency-2 this is nominal value of genset and mains
frequency. Frequency limits are defined by
reference to this value.
Nominal Volt- V-AC 0 300 120 When tertiaryy voltage is selected, this
age-3 is the nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
Nominal Fre- Hz 0 500 60 When tertiary frequency is selected, this
quency-3 is nominal value of genset and mains
frequency. Frequency limits are defined by
reference to this value.
Mains Voltage % V-100 V+100 V-20% If one of the mains phases goes under this
Low Limit limit, it means that the mains are off and
starts the transfer to the genset in AUTO
mode. The value is defined with reference
to Nominal Voltage.
Mains Voltage % V-100 V+100 V-20% If one of the mains phases goes over this
High Limit limit, it means that the mains are off and
starts the transfer to the genset in AUTO
mode. The value is defined with reference
to Nominal Voltage.
TJ 509T-V.112013 79
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Mains Voltage Fail sec 0 10 1 If at least one of the mains
Timer phase voltages goes outside
of the limits during this timer,
it means that the mains are off
and it starts the transfer to the
genset in AUTO mode.
Instant Mains Dropout % 0 50 0 If the mains phase voltages are
outside limits, but not more
than this parameter (with
reference to nominal voltage),
then the genset will run without
releasing the mains contactor.
When the genset is ready to
take the load, the load will be
transferred.
If this parameter is set to zero
then the mains contactor is
immediately released at mains
failure.
Mains Frequency Low % F-100 F+100 F-10% If the mains frequency goes
Limit under this limit, it means that
the mains are off and starts the
transfer to the genset in AUTO
mode. The value is defined
with reference to Nominal
Frequency.
Mains Frequency High % F-100 F+100 F+10% If the mains frequency goes
Limit over this limit, it means that
the mains are off and starts the
transfer to the genset in AUTO
mode. The value is defined
with reference to Nominal
Frequency.
80 TJ 509T-V.112013
ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Mains Frequency Fail sec 0 10 1 If the mains frequency goes
Timer outside of the limits during this
timer, it means that the mains
are off and starts the transfer
to the genset in AUTO mode.
Genset Low Voltage % V-100 V+100 V-15% If one of the genset phase
Warning Limit voltages goes under this limit
when feeding the load, this
will generate a GENSET LOW
VOLTAGE warning.
Genset Low Voltage % V-100 V+100 V-20% If one of the genset phase
Shutdown Limit voltages goes under this limit
when feeding the load, this
will generate a GENSET LOW
VOLTAGE shutdown alarm
and the engine will stop.
Genset High Voltage % V-100 V+100 V+15% If one of the genset phase
Warning Limit voltages goes over this limit
when feeding the load, this
will generate a GENSET HIGH
VOLTAGE warning.
Genset High Voltage % V-100 V+100 V+20% If one of the genset phase
Shutdown Limit voltages goes over this limit
when feeding the load, this
will generate a GENSET HIGH
VOLTAGE shutdown alarm
and the engine will stop.
Genset Voltage Fail sec 0 10 1 If at least one of the genset
Timer phase voltages goes outside of
the limits during this timer, a
genset voltage fault will occur.
Genset Low Frequency % F-100 F+100 V-15% If the genset frequency goes
Warning Limit under this limit when feeding
the load, this will generate a
GENSET LOW FREQUENCY
warning.
Genset Low Frequency % F-100 F+100 F-20% If the genset frequency goes
Shutdown Limit under this limit when feeding
the load, this will generate a
GENSET LOW FREQUENCY
shutdown alarm and the
engine will stop.
TJ 509T-V.112013 81
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Genset High Fre- % F-100 F+100 F+15% If the genset frequency goes over
quency Warning Limit this limit when feeding the load,
this will generate a GENSET
HIGH FREQUENCY warning.
Genset High Fre- % F-100 F+100 F+20% If the genset frequency goes over
quency Shutdown this limit when feeding the load,
Limit this will generate a GENSET
HIGH FREQUENCY shutdown
alarm and the engine will stop.
Genset Frequency sec 0 10 1 If the genset frequency goes
Fail Timer outside of the limits during this
timer, a genset frequency fault
will occur.
Low Battery Voltage V-DC 5.0 35.0 12.0 If the battery voltage falls below
Warning Limit this limit, this will generate a
LOW BATTERY warning.
Low Battery Voltage V-DC 5.0 35.0 9.0 If the battery voltage falls below
Shutdown Limit this limit, this will generate a
LOW BATTERY shutdown alarm
and the engine will stop.
High Battery Voltage V-DC 5.0 35.0 29.0 If the battery voltage goes over
Warning Limit this limit, this will generate a
HIGH BATTERY warning.
High Battery Voltage V-DC 5.0 35.0 30.0 If the battery voltage goes over
Shutdown Limit this limit, this will generate a
HIGH BATTERY shutdown alarm
and the engine will stop.
Battery Voltage Fail sec 0 10 3 If the battery voltage goes
Timer outside of the limits during this
timer, a battery voltage fault will
occur.
Genset Voltage % 0 100 0.0 If any genset phase voltage
Unbalance Limit differs from the average more
than this limit, it will generate a
Voltage Unbalance fault condi-
tion. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0
then voltage unbalance is not
monitored
82 TJ 509T-V.112013
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Genset Voltage - 0 3 0 0: no action
Unbalance Action 1: shutdown alarm
2: loaddump alarm
3: warning
Genset Current Unbal- % 0 100 0.0 If any genset phase current
ance Limit differs from the average more
than this limit, it will gener-
ate a Current Unbalance fault
condition. The action taken
upon fault condition is program-
mable.
If this parameter is set to 0.0
then voltage unbalance is not
monitored
Genset Current Unbal- - 0 3 0 0: no action
ance Action 1: shutdown alarm
2: loaddump alarm
3: warning
Genset Reverse kW 0 50000 0 If the genset power is negative
Power Warning Limit and goes above this limit then a
REVERSE POWER warning will
be generated. If this parameter
is set to 0 then reverse power
fault is not monitored.
Genset Reverse kW 0 50000 0 If the genset power is negative
Power Loaddumpg and goes above this limit then
Limit a REVERSE POWER loaddump
will be generated.
Genset Reverse sec 0 120 5 If the genset power is negative
Power Fail Timer and over limits during this
timer, a reverse power fault will
occur.
Genset Overcurrent Amp 0 50000 0 If one of the genset phase cur-
Limit rents goes over this limit when
feeding the load, this will gen-
erate a genset overcurrent fault
condition. The action taken
upon fault condition is program-
mable. If this parameter is set
to 0 then overcurrent fault is
not monitored.
TJ 509T-V.112013 83
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Parameter Unit Min Max Factory Description
Definition Set
Genset Overcur- Amp 0 50000 0 When secondary voltage is selected, if one
rent Limit-2 of the genset phase currents goes over this
limit when feeding the load, this will gener-
ate a genset overcurrent fault condition.
The action taken upon fault condition is
programmable. If this parameter is set to 0
then overcurrent fault is not monitored.
Genset Overcur- Amp 0 5000 0 When tertiary voltage is selected, if one of
rent Limit-3 the genset phase currents goes over this
limit when feeding the load, this will gener-
ate a genset overcurrent fault condition.
The action taken upon fault condition is
programmable. If this parameter is set to 0
then overcurrent fault is not monitored.
Genset Overcur- - 0 3 0 0: shutdown alarm
rent Limit-2 1: loaddump alarm
Overcurrent Time 0 1 64 16 This parameter defines the reaction speed of
Multiplier the overcurrent detector. A higher number
means higher sensitivity.
Detailed explanation is given at chapter:
“Overcurrent Protection”
Genset Overload kW 0 50000 0 If the total genset active power goes over
Limit this limit when feeding the load, this will
generate a genset overload loaddump alarm.
If this parameter is set to 0 then overload
fault is not monitored.
Genset Overload sec 0 120 3 If the genset active power is over the limit
Fail Timer during this timer, an overload fault will oc-
cur.
Load Shedding kW 0 50000 0 If the genset power goes below this limit
Low Limit then the load shedding relay will be deacti-
vated. Review chapter “Load Shedding” for
more details.
Load Shedding kW 0 50000 0 If the genset power goes above this limit
High Limit then the load shedding relay will be acti-
vated. Review chapter “Load Shedding” for
more details.
Load Add Delay sec 0 240 0 This is the minimum delay between 2
load_add pulses. Review chapter “Load
Shedding” for more details.
84 TJ 509T-V.112013
ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Load Subtract-Add min 0 120 0 This is the minimum delay
Delay required for a load_add pulse
after a load_substract pulse.
Review chapter “Load Shed-
ding” for more details.
Mains Waiting Timer sec 0 50000 30 This is the time between the
mains voltages and frequency
entered within the limits and
the generator contactor is
deactivated.
Mains Connection - 0 7 5 This is the connection topology
Topology of mains voltages and CTs.
Detailed explanations are given
in the chapter: “TOPOLOGIES”.
0: 2 phase, 3 wire L1-L2
1: 2 phase, 3 wire L1-L3
2: 3 phase, 3 wire
3: 3 phase, 3 wire, 2CTs L1-L2
4: 3 phase, 3 wire, 2CTs L1-L3
5: 3 phase, 4 wire star
6: 3 phase, 4 wire delta
7: single phase, 2 wire
Genset Connection - 0 7 5 This is the connection topology
Topology of genset voltages and CTs.
Detailed explanations are given
in the chapter: TOPOLOGIES.
0: 2 phase, 3 wire L1-L2
1: 2 phase, 3 wire L1-L3
2: 3 phase, 3 wire
3: 3 phase, 3 wire, 2CTs L1-L2
4: 3 phase, 3 wire, 2CTs L1-L3
5: 3 phase, 4 wire star
6: 3 phase, 4 wire delta
7: single phase, 2 wire
Mains Contactor sec 0 600 0.5 This is the period after the
Timer generator contactor has been
deactivated and before the
mains contactor has been
activated.
TJ 509T-V.112013 85
ELECTRICAL PARAMETERS GROUP (continued)
Parameter Defini- Unit Min Max Factory Description
tion Set
Mains MCB Close sec 0 10 0.5 After the mains MCB_undervoltage
Pulse coil is energized and mains MCB_un-
dervoltage coil timer is elapsed,
the mains MCB_close relay will be
activated during this period.Review
chapter “Motorized Circuit Breaker
Control” for more details.
Mains MCB Open sec 0 10 0.5 The mains MCB_open relay will be
Pulse activated during this period.
Review chapter “Motorized Circuit
Breaker Control” for more details.
Mains MCB sec 0 10 0.5 The mains MCB_undervoltage coil is
Undervoltage energized during this period before the
Coil Timer mains MCB_close relay is activated.
Review chapter “Motorized Circuit
Breaker Control” for more details.
Mains MCB Fail sec 0 600 2.0 If a mains MCB feedback input is
Timer defined and if the mains MCB fails to
change position before the expiration
of this timer, then a fault condition
occurs.
Mains Phase Order - 0 1 0 0: mains phase order checking
Check Enable disabled
1: if mains phase order is faulty, then a
warning is given and mains contactor
deenergized.
Genset Contactor sec 0 600 0.5 This is the period after the mains-
Timer contactor has been deactivated and
before the genset contactor has been
activated.
Genset MCB Close sec 0 10 0.5 After the genset MCB_undervoltage
Pulse coil is energised and genset MCB_un-
dervoltage coil timer is elapsed,
the genset MCB_close relay will be
activated during this period.
Review chapter “Motorized Circuit
Breaker Control” for more details.
86 TJ 509T-V.112013
ELECTRICAL PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Genset MCB Open sec 0 10 0.5 The genset MCB_open relay
Pulse will be activated during this
period.
Review chapter “Motorized
Circuit Breaker Control” for
more details.
Genset MCB Under- sec 0 10 0.5 The genset MCB_undervoltage
voltage Coil Timer coil is energised during this
period before the genset MCB_
close relay is activated.
Review chapter “Motorized
Circuit Breaker Control” for
more details.
GCB Alarm Level - 0 1 0 0: shutdown alarm
1: loaddump alarm
Genset MCB Fail sec 0 600 2.0 If a genset MCB feedback input
Timer is defined and if the genset
MCB fails to change position
before the expiration of this
timer, then a fault condition
occurs.
Genset Phase Order - 0 1 0 0: genset phase order checking
Check Enable disabled
1: if genset phase order is
faulty, then a genset phase
order fail loaddump alarm is
given.
TJ 509T-V.112013 87
ELECTRICAL PARAMETERS GROUP (continued)
Parameter Unit Min Max Factory Set Description
Definition
Busbar Fail sec 0 30 2.0 When a genset closes to the Busbar, if
Timer the mater genset controller does detect
the Busbar voltage at the expiration of this
period, a “BUSBAR FAIL” fault condition will
occur.
Busbar Ready sec 0 30 2.0 This is the delay after all generators close
Timer to the busbar and before the master genset
controller acknowledges “Busbar ready”
signal.
Multi Load kW 0 65000 0 When the genset active power goes below
Subtract this limit, the controller will start adding
Power Level load as described in chapter Five Step Load
Management.
Multi Load kW 0 65000 0 When the genset active power goes below
Add Power this limit, the controller will start adding
Level load as described in chapter Five Step Load
Management.
Multi Load sec 0 36000 0 If the load stays over the Multi Load Sub-
Substract stract Power Level parameter during this
Start Delay timer, then 1 step of load is substracted.
Multi Load sec 0 36000 0 If the load stays over the Multi Load Sub-
Substract stract Power Level parameter during this
Wait Delay timer, then 1 step of load is substracted.
Multi Load sec 0 36000 0 This is the minimum period between two
Add Start load subtract operations.
Delay
Multi Load sec 0 36000 0 If the load stays below the Multi Load Add
Add Start Power Level parameter during this timer,
Delay then 1 step of load is added.
Multi Load sec 0 36000 0 This is the minimum period between two
Add Wait load add operations.
Delay
88 TJ 509T-V.112013
16.3. ENGINE PARAMETERS GROUP
Parameter Unit Min Max Factory Description
Definition Set
Nominal rpm 0 50000 1500 The nominal value of engine rpm. Low-high
RPM rpm limits are defined by reference to this
value.
Nominal rpm 0 50000 1800 When secondary frequency is selected, this
RPM-2 is the nominal value of engine rpm. Low-high
rpm limits are defined by reference to this
value.
Nominal rpm 0 50000 1800 When tertiary frequency is selected, this is
RPM-3 the nominal value of engine rpm. Low-high
rpm limits are defined by reference to this
value.
Low RPM % R-100 R+100 R-10% If the engine rpm goes under this limit when
Warning feeding the load, this will generate a GEN-
Limit SET LOW RPM warning.
Low RPM % R-100 R+100 R-15% If the engine rpm goes under this limit
Shutdown when feeding the load, this will generate a
Limit GENSET LOW RPM shutdown alarm and the
engine will stop.
High RPM % R-100 R+100 R+10% If the engine rpm goes over this limit when
Warning feeding the load, this will generate a GEN-
Limit SET HIGH RPM warning.
High RPM % R-100 R+100 R+15% If the engine rpm goes over this limit when
Shutdown feeding the load, this will generate a GEN-
Limit SET HIGH RPM shutdown alarm and the
engine will stop.
RPM Fail sec 0 10 3 If the engine rpm goes outside of the limits
Timer during this timer, an engine speed fault will
occur.
Overspeed % HRSL- HRSL HRSL If the engine rpm goes over the “High RPM
Overshoot 100 +100 +10% Shutdown Limit” by this quantity, this will
Limit generate immediately a GENSET HIGH RPM
shutdown alarm and the engine will stop.
Loss of Sig- - 0 1 0 0: speed signal existency not checked
nal Check 1:If the speed signal is lost, it will generate a
Speed Signal Lost fault condition. The action
taken upon fault condition is programmable.
TJ 509T-V.112013 89
ENGINE PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Set Description
Loss of Speed Signal - 0 2 0 0: shutdown alarm
Action 1: loaddump alarm
2: warning
Loss of Speed Signal sec 0 240 0 If the speed signal is lost during
Timer this timer, a Speed Signal Lost
fault will occur.
Low Charge Voltage V-DC 0 40 6.0 If the charge alternator voltage
Warning Limit goes under this limit, a charge
alternator voltage warning will
occur.
Low Charge Voltage V-DC 0 40 4.0 If the charge alternator voltage
Shutdown Limit goes under this limit, a charge
alternator voltage shutdown
will occur and the engine will
stop.
Charge Voltage Fail sec 0 120 1 If the charge alternator voltage
Timer goes under limits during this
timer, a charge alternator volt-
age fault will occur.
Engine Heating Tem- °C 0 80 0 If it is requested that the
perature engine runs without load until
reaching a certain temperature,
this parameter defines the
temperature.
Engine Start Delay min 0 720 1 This is the time between
the mains fails and the fuel
solenoid turns on before start-
ing the genset. It prevents
unwanted genset operation in
battery backed-up loads.
Preheat Timer sec 0 30 0 This is the time after the fuel
solenoid is energized and be-
fore the genset is started. Dur-
ing this period the PREHEAT
relay output is energized (if
assigned by Relay Definitions)
Crank Timer sec 1 15 6 This is the maximum start pe-
riod. Starting will be automati-
cally cancelled if the genset
fires before the timer.
90 TJ 509T-V.112013
ENGINE PARAMETERS GROUP
Parameter Definition Unit Min Max Factory Set Description
Wait Between Starts sec 1 240 10 This is the waiting period be-
tween two start attempts.
Engine Heating Timer sec 0 240 4 This is the period used for en-
gine heating before load transfer.
Engine Heating - 0 1 0 The genset will not take the
Method load before engine heating is
completed.
0: engine is heated during
Engine Heating Timer.
1: engine is heated until the
coolant temperature reaches the
Engine Heating Temperature
and at least during the Engine
Heating Timer.
Cooldown Timer sec 0 600 120 This is the period that the gen-
erator runs for cooling purpose
after the load is transferred to
mains.
Stop Solenoid Timer sec 0 90 10 This is the maximum time
duration for the engine to stop.
During this period the STOP
relay output is energized (if
assigned by Relay Definitions). If
the genset has not stopped after
this period, a FAIL TO STOP
warning occurs.
Number of Starts - 1 6 3 Number of Starts
Choke Timer sec 0 240 5 This is the control delay of
CHOKE output.
The choke output is activated
together with the crank output.
It is released after this delay or
when engine runs (whichever
occurs first).
Idle Speed Timer sec 0 240 0 When the engine runs, the Idle
output relay function will be
active during this timer. While
the IDLE output is active, low
voltage, low frequency and low
rpm checks are disabled.
TJ 509T-V.112013 91
ENGINE PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Description
Set
Idle Holdoff Timer sec 0 30 10 While the IDLE periode is over, low
voltage, low frequency and low
speed checks are enabled after the
expiration of this timer.
Gas Solenoid Delay sec 0 240 5 The gas solenoid of the gas engine
(if assigned by Relay Definitions)
will be opened after this delay dur-
ing cranking.
Crank Cut Voltage V-AC 0 65000 100 The crank relay output is deener-
gized when the genset phase L1
voltage reaches this limit.
Crank Cut Frequency Hz 0 100 10 The crank relay output is deener-
gized when the genset frequency
reaches this limit.
Crank Cut RPM rpm 0 65000 500 The crank relay output is deen-
ergized when the engine rpm
reaches this limit.
Crank Cut Charge V-DC 0 40 6 The crank relay output is deener-
Voltage gized when the charge alternator
voltage reaches this limit.
Crank Cut with Oil - 0 1 0 0: no crank cut with oil pressure
Pressure 1: cranking is cut when oil pres-
sure switch is open or the oil pres-
sure measured is above shutdown
limit.
Crank Cut with Oil sec 0 30 2 If crank cutting with oil pressure is
Pressure Delay enabled, cranking is cut after this
delay when oil pressure switch is
open or the oil pressure measured
is above shutdown limit.
92 TJ 509T-V.112013
ENGINE PARAMETERS GROUP
Parameter Definition Unit Min Max Factory Description
Set
Fuel Consumption per % 0 100 0.0 This parameter is the threshold for
Hour sending FUEL THEFT and FUELLING
sms messages.
If this parameter is set to 0, then no
Fuel Theft and Fuelling sms mes-
sages will be sent.
If SMS is required, set this param-
eter to a value above the hourly fuel
consumption of the genset.
Coolant Cooler On °C 0 250 90 If the coolant temp is above this
limit then the cooler relay function
will become active.
Coolant Cooler Off °C 0 250 80 If the coolant temp is below this
limit then the cooler relay function
will become inactive.
Coolant Heater On °C 0 250 50 If the coolant temp is below this
limit then the heater relay function
will become active.
Coolant Heater Off °C 0 250 60 If the coolant temp is above this
limit then the heater relay function
will become inactive.
Fan Overrun Timer sec 0 240 0 The cooler relay will stay active dur-
ing this timer after the coolant temp
is below “Coolant Cooler Off” limit.
Canopy Fan Turn-On °C 0 250 90 If the canopy temp is above this
limit then the canopy fan relay func-
tion will become active.
Canopy Fan Turn-Off °C 0 250 80 If the canopy temp is below this
limit then the canopy fan relay func-
tion will become inactive.
Ambient Fan Turn-On °C 0 250 90 If the ambient temp is above this
limit then the ambient fan relay
function will become active.
Ambient Fan Turn-Off °C 0 250 80 If the ambient temp is below this
limit then the ambient fan relay
function will become inactive.
TJ 509T-V.112013 93
16.3. ENGINE PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Description
Set
Service-1 Engine hours 0 5000 250 The SERVICE REQUEST led indicator
Hours will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-1
engine hours.
Service-1 Period month 0 24 6 The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be indi-
cated depending on Service-1 Period.
Service-1 Alarm Level - 0 3 3 0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
Service-2 Engine hours 0 5000 250 The SERVICE REQUEST led indicator
Hours will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-2
engine hours.
Service-2 Period month 0 24 6 The SERVICE REQUEST led indicator
will turn on after this amount of time
from the last service. If the period is set
to ‘0’ no SERVICE REQUEST will be indi-
cated depending on Service-2 Period.
Service-2 Alarm Level - 0 3 0 0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
Service-3 Engine hours 0 5000 250 The SERVICE REQUEST led indicator
Hours will turn on after this quantity of engine
hours from the last service. If the period
is set to ‘0’ no SERVICE REQUEST will
be generated depending on service-3
engine hours.
94 TJ 509T-V.112013
16.3. ENGINE PARAMETERS GROUP
Parameter Definition Unit Min Max Factory Description
Set
Service-3 Period month 0 24 6 The SERVICE REQUEST led indica-
tor will turn on after this amount
of time from the last service. If the
period is set to ‘0’ no SERVICE
REQUEST will be indicated depend-
ing on Service-3 Period.
Service-3 Alarm Level - 0 3 0 0: no action
1: shutdown alarm
2: loaddump alarm
3: warning
J1939 Enable - 0 1 0 0: The J1939 port is inoperative.
1: The analog measurements (oil,
temp, rpm) are picked_up from
the ECU. If the ECU communica-
tion is lost, then the engine will be
stopped.
J1939 Engine Brand - 0 15 0 0: GENERIC
1: CUMMINS
2: DETROIT DIESEL
3: DEUTZ
4: JOHN DEERE
5: PERKINS
6: VOLVO
7: CATERPILLAR
8: SCANIA
9: IVECO
10: MTU-MDEC
11: BOSCH
Other values: Reserved. Do not
use.
TJ 509T-V.112013 95
ENGINE PARAMETERS GROUP (continued)
Parameter Definition Unit Min Max Factory Description
Set
J1939 ECU Type - 0 7 0 GENERIC ENGINE BRAND
0: Generic
CUMMINS ENGINE
0: CM850
1: CM570
DETROIT DIESEL ENGINE
0: Generic
DEUTZ ENGINE
0: Generic
1: EMR2
2: EMR3
JOHN DEERE ENGINE
0: Generic
PERKINS ENGINE
0: Generic
1: ADEM3
2: ADEM 1.3
VOLVO ENGINE
0: Generic
1: without CIU unit
2: EDC4
CATERPILLAR ENGINE
0: Generic
SCANIA ENGINE
0: Generic
1: Single Speed
2: All Speed
IVECO ENGINE
0: Generic
MTU-MDEC ENGINE
0: MDEC 302
1: MDEC 201
2: MDEC 303
3: MDEC 304
4: MDEC 506
BOSCH INJECTION SYSTEM
0: Generic
1: EDC 731
2: EDC 9.3
J1939 Speed Adjust % -100 +100 0.0 This parameter adjusts the speed of an
ECU controlled engine by +/- 8%.
96 TJ 509T-V.112013
16.3. ENGINE PARAMETERS GROUP
Parameter Definition Unit Min Max Factory Description
Set
High Air Inlet Temperature °C 0 200 0 If the air inlet temperature
Warning Limit measured through ECU is
over this limit, then a high air
inlet temperature warning will
occur.
High Air Inlet Temperature °C 0 200 0 If the air inlet temperature
Alarm Limit measured through ECU is over
this limit, then a high air inlet
temperature shutdown/load-
dump alarm will occur.
High Air Inlet Temperature - 0 1 0: shutdown alarm
Alarm Action 1: loaddump alarm
Low Coolant Level % 0 100 0 If the coolant level measured
Warning Limit through ECU is below this
limit, then a low coolant level
warning will occur.
Low Coolant Level Alarm % 0 100 0 If the coolant level measured
Limit through ECU is below this
limit, then a low coolant level
shutdown/loaddump alarm will
occur.
Low Coolant Level Alarm - 0 1 0 0: shutdown alarm
Action 1: loaddump alarm
Battery Charge Run V-DC 0 35.0 0 If the battery voltage goes
Voltage below this limit the engine
will be automatically started
in order to charge the battery
using the charge alternator.
Battery Charge Run Timer min 0 1200 0 If the battery voltage goes
below the Battery Charge Run
Voltage limit, the engine will
be automatically run during
this period in order to charge
the battery using the charge
alternator.
TJ 509T-V.112013 97
16.4. ADJUST DATE AND TIME
These parameters allow adjusting the battery backup real time clock of the module. Once set,
the clock will continue to run even if DC power is removed from the unit.
In AUTO mode, it is possible to define the periods where automatic operation is desired. It
may be required that the genset does not start at night or weekends.
Weekly schedule programs allow an hourly setting of automatic operation of the unit during
one week.
There are 7days x 24hours =144 parameters. Each hour of the week can be independently
defined as AUTO or OFF period.
98 TJ 509T-V.112013
16.6. EXERCISER SCHEDULE
The unit provides 7 independent automatic exerciser programs. Automatic exercise may be done in
weekly or monthly basis.
If monthly exercise is selected, the week, day and hour is adjustable for each exercise item.
If weekly exercise is selected, the day and hour is adjustable for each exercise item.
Thus the genset can be instructed to run automatically in given days and times of a week and take
the load.
TJ 509T-V.112013 99
16.7. SENDER CONFIGURATION
The unit has 4 analog sender inputs. Only parameters of one sender are explained below. Other
senders have identical parameter set.
Each sender has 16 step programmable curves. The sender name and reading unit is freely program-
mable, thus the sender can be adapted to any type through programming.
100 TJ 509T-V.112013
EXERCISER SCHEDULE
Parameter Definition Unit Min Max Factory Description
Set
Low Alarm Level x 0 10000 If enabled, defines the low alarm
limit. The low alarm may be
selected as shutdown or loaddump
with “alarm level” parameter.
Low Warning Level x 0 10000 If defined, defines the low warning.
High Alarm Level x 0 10000 If enabled, defines the high alarm
limit. The high alarm may be
selected as shutdown or loaddump
with “alarm level” parameter.
High Warning Level x 0 10000 If defined, defines the high warn-
ing.
Sender Curve-1 ohm ohms 0 5000 Point-1 ohm value
Sender Curve-1 value x 0 10000 Point-1 reading
Sender Curve-2 ohm ohms 0 5000 Point-2 ohm value
Sender Curve-2 value x 0 10000 Point-2 reading
Sender Curve-3 ohm ohms 0 5000 Point-3 ohm value
Sender Curve-3 value x 0 10000 Point-3 reading
Sender Curve-4 ohm ohms 0 5000 Point-4 ohm value
Sender Curve-4 value x 0 10000 Point-4 reading
Sender Curve-5 ohm ohms 0 5000 Point-5 ohm value
Sender Curve-5 value x 0 10000 Point-5 reading
Sender Curve-6 ohm ohms 0 5000 Point-6 ohm value
Sender Curve-6 value x 0 10000 Point-6 reading
Sender Curve-7 ohm ohms 0 5000 Point-7 ohm value
Sender Curve-7 value x 0 10000 Point-7 reading
Sender Curve-8 ohm ohms 0 5000 Point-8 ohm value
Sender Curve-8 value x 0 10000 Point-8 reading
Sender Curve-9 ohm ohms 0 5000 Point-9 ohm value
Sender Curve-9 value x 0 10000 Point-9 reading
Sender Curve-10 ohm ohms 0 5000 Point-10 ohm value
Sender Curve-10 value x 0 10000 Point-10 reading
TJ 509T-V.112013 101
SENDER CONFIGURATION
Parameter Definition Unit Min Max Factory Description
Set
Sender Curve-11 ohm ohms 0 5000 Point-11 ohm value
Sender Curve-11 value x 0 10000 Point-11 reading
Sender Curve-12 ohm ohms 0 5000 Point-12 ohm value
Sender Curve-12 value x 0 10000 Point-12 reading
Sender Curve-13 ohm ohms 0 5000 Point-13 ohm value
Sender Curve-13 value x 0 10000 Point-13 reading
Sender Curve-14 ohm ohms 0 5000 Point-14 ohm value
Sender Curve-14 value x 0 10000 Point-14 reading
Sender Curve-15 ohm ohms 0 5000 Point-15 ohm value
Sender Curve-15 value x 0 10000 Point-15 reading
Sender Curve-16 ohm ohms 0 5000 Point-16 ohm value
Sender Curve-16 value x 0 10000 Point-16 reading
Sender Name - - - If the sender type parameter is
set to zero (not used), this string
is used as sender name while
displaying the sender reading.
Sender Low Fault String - - - If the sender type parameter is
set to zero (not used), this string
is used as sender low value fault
in the alarm display.
Sender High Fault String - - - If the sender type parameter is
set to zero (not used), this string
is used as sender high value fault
in the alarm display.
102 TJ 509T-V.112013
16.8. DIGITAL INPUT CONFIGURATION
The unit has 8 digital inputs. By using external input extension modules, up to 40 inputs in total are
available.
Only parameters of one input are explained below. Other inputs have identical parameter set.
The input name is freely programmable, thus the input can be adapted to any functionality through
programming.
TJ 509T-V.112013 103
INPUT FUNCTION LIST
No Description No Description No Description
104 TJ 509T-V.112013
16.9. OUTPUT CONFIGURATION
The parameters below define the functions of relay outputs. The unit has 8 relay outputs. All relays
have programmable functions, selected from a list.
TJ 509T-V.112013 105
Relay-25 1 Relay extension module – 3
Relay-26 1 Relay extension module – 3
Relay-27 1 Relay extension module – 3
Relay-28 1 Relay extension module – 3
Relay-29 1 Relay extension module – 3
Relay-30 1 Relay extension module – 3
Relay-31 1 Relay extension module – 3
Relay-32 1 Relay extension module – 3
106 TJ 509T-V.112013
Below is a short list for reference purposes. Please use
the RainbowPlus program for complete selection list.
TJ 509T-V.112013 107
No Description
This is the site Id string sent at the beginning of SMS messages, e-mails and web page headers for
the identification of the genset sending the message. Any 20 character long string may be entered.
If Modem Selection= External PSTN Modem: First 2 numbers are used for modem calls.
Other selections: all numbers are used for SMS sending.
108 TJ 509T-V.112013
16.13. GSM MODEM PARAMETERS
Parameter Definition Description
APN User Name The APN (access point name) username may be required by the GSM
operator. However some GSM operators may allow access without
username.
The exact information should be obtained from the GSM operator.
Please search the GSM operator’s website with “APN” string.
APN Password If the APN (access point name) username is required by the GSM opera-
tor, most probably the APN password will also be required. However
some GSM operators may allow access without password.
The exact information should be obtained from the GSM operator.
Please search the GSM operator’s website with “APN” string.
APN Name The APN (access point name) is always required by the GSM operator.
The exact information should be obtained from the GSM operator.
Please search the GSM operator’s website with “APN” string.
SMS Service Center The SMS service center number may be required by the GSM operator.
Number However some GSM operators may allow SMS sending without SMS
service center number.
The exact information should be obtained from the GSM operator.
Please search the GSM operator’s website with “sms service center”
string.
TJ 509T-V.112013 109
16.15. SYNCHRONIZATION PARAMETERS
Parameter Definition Unit Min Max Factory Set Description
No Break Transfer - 0 1 0 0: only interrupted transfer enabled
Enable 1: no break transfer enabled
Synchronization Fail sec 0 240 30 If the phase and voltage synchronization
Timeout is not successful before the expiration of
this timer, then a Synchronization Fail
warning is given and the transfer will be
performed with interruption.
Synchronization Contac- sec 0 25 0.5 When synchronization is detected, both
tor Timeout contactors will stay closed during this
timer.
Max Freq Difference Hz 0.1 2.0 0.5 This is the maximum difference between
mains and genset frequencies to close
both contactors.
Phase to Phase Voltage - 0 1 0 0: Phase to neutral voltage check
Check 1: Phase to phase voltage check
110 TJ 509T-V.112013
17. CRANK CUTTING
In order to insure fast and reliable crank cutting, the unit uses various resources for engine running
condition detection.
The crank timer is adjusted through Engine Parameters > Crank Timer. The maximum allowed
timer is 15 seconds.
If the genset phase L1 AC voltage reaches Engine Parameters > Crank Cut Voltage, then cranking
is immediately stopped.
If the genset phase L1 frequency reaches Engine Parameters > Crank Cut Frequency, then crank-
ing is immediately stopped.
If the genset rpm reaches Engine Parameters > Crank Cut RPM, then cranking is immediately
stopped.
Following setting is necessary: Engine Parameters > Crank Cut with Oil Pressure = 1
The crank cutting with oil pressure offers a programmable delay through Engine Parameters >
Crank Cut with Oil Pressure Delay. The parameter is factory set to 2 seconds.
Both low oil pressure switch and oil pressure sender readings may be used for crank cutting. The oil
pressure switch is always used. The sender may be disabled through Controller Configuration > Oil
Pressure Switch Priority parameter.
If enabled, when oil pressure is detected, cranking is stopped after adjustable timer delay.
TJ 509T-V.112013 111
18. OVERCURRENT PROTECTION (IDMT)
The unit offers a programmable IDMT protection function in order to protect the alternator against
excessive currents.
The IDMT (Inverse Definite Minimum Time) protection function has such tripping characteristics that
the
tripping time varies inversely with the value of current. Beyond a certain current limit the tripping time
becomes constant (definite) and causes tripping in minimum time.
The tripping formula is defined as below:
Where:
TMS is the IDMT time multiplier setting. This is also the tripping time at 100% overload.
I is the current of the most loaded phase
Iset is the programmed overcurrent limit
t is the tripping time in seconds
Currents below the overcurrent limit are allowed to flow for unlimited time. Currents above the limit
will
cause the IDMT protection to trigger with a delay depending on the strength of the overcurrent.
Higher the
current, faster the protection will trip.
When a non-tripping overcurrent condition occurs, the unit will keep trace of it. In case of a consecu-
tive
overcurrent, the controller will take into account the residual heat caused by the previous overcurrent
and
will trip faster than usual.
The IDMT multiplier adjusts the sensitivity of the IDMT detector. When the multiplier is low, then
tripping
will be faster for the same current.
The unit provides separate Overcurrent limits for primary and secondary volt/speed/amp settings.
Switching from primary volt/freq/amps to secondary values will also switch the IDMT detector to the
secondary setting.
The action of the tripping may be selected as a Loaddump (stop after cooldown) or shutdown alarm
(immediate stop).
112 TJ 509T-V.112013
Below is a table showing the tripping delay in function of the percent load level (with MS=36):
TJ 509T-V.112013 113
19. MOTORIZED CIRCUIT BREAKER CONTROL
The unit offers full control for any brand and model of motorized circuit breakers (MCB).
The MCB control is performed through 3 digital output functions, namely Open, Close and Undervolt-
age
coil controls. Only 2 of these outputs are used in a single application.
Any digital output can be assigned to MCB control signals through programming menu.
114 TJ 509T-V.112013
MCB modules can be operated by 2 different ways. The unit supports both configurations.
Below is the terminology used:
M: gear motor
PF: ready to close contact
XF: close coil
MX: open coil
MN: undervoltage trip (release)
AUX: auxiliary contacts
TJ 509T-V.112013 115
20. J1939 CANBUS ENGINE SUPPORT
The unit offers a special J1939 port in order to communicate with electronic engines controlled by an ECU (elec-
tronic control unit). The J1939 port consists of 2 terminals which are J1939+ and J1939-.
The connection between the unit and the engine should be made with an appropriate balanced 120 ohms low
capacitance coaxial cable. The external conductor should be grounded at one end only.
A 120 ohms termination resistor is installed inside the unit. Please do not connect external resistor.
The J1939 port is activated by setting the program parameter J1939 Enable to 1. The J1939 Engine Type param-
eter should be set accordingly. The list of available engines is given at the programming section. Please contact
TEKSAN GENERATOR for the most current list of engines.
If the J1939 port is enabled then the oil pressure, coolant temperature and the engine rpm information are
picked up from the ECU unit. If connected, the MPU unit and related analog senders are discarded.
The controller is able to read and display all below parameters, under condition that the engine sends these infor-
mation. Most engines send only some of them. If the engine does not send a parameter, the unit will simply skip
it. Thus only available information are displayed.
The J1939 measurements are also available for Modbus operation. Please check chapter Modbus Communica-
tions for more details.
When the fuel output is active, if no information is received from the ECU during last 3 seconds, then the unit will
give a ECU FAIL alarm and stop the engine. This feature prevents uncontrolled engine operation.
The fault conditions of an electronic engine are considered by the unit as warnings and do not cause engine
stop. The engine is supposed protected by the ECU which will stop it when necessary.
The electronic engine fault codes are displayed in text within the alarm list table, together with their SPN-FMI
codes. The complete list of fault codes is given in the engine manufacturer’s user manual.
116 TJ 509T-V.112013
Below is a basic list of fault conditions (x denotes any FMI)
TJ 509T-V.112013 117
Below is a basic list of FMI codes.
Please be aware that these codes may differ slightly depending on the engine brand and model.
FMI DESCRIPTION
0 Value too high” Valid data, but above the normal working range
1 “Value too low” Valid data, but below the normal working range
2 “Faulty data” Intermittent or faulty data or
Short circuit to battery voltage, injector high voltage side
3 “Electrical fault” Abnormally high voltage or short circuit to battery voltage, injector low voltage side
4 “Electrical fault” Abnormally low voltage or short circuit to battery negative, injector low voltage or high
voltage side
5 “Electrical fault” Abnormally low current or open circuit
6 “Electrical fault” Abnormally high current or short circuit to battery negative
7 “Mechanical fault” Faulty response from mechanical system
8 “Mechanical or electrical fault” Abnormal frequency
9 “Communication fault” Abnormal updating rate or
Open circuit in injector circuit
10 “Mechanical or electrical fault” Abnormally large variations
11 “Unknown fault” Unidentified fault
12 “Component fault” Faulty unit or component
13 “Faulty calibration” Calibration values outside the limits
14 “Unknown fault” Special instructions
15 Data valid but above normal operating range - least severe level
16 Data valid but above normal operating range - moderately severe level
17 Data valid but below normal operating range - least severe level
18 Data valid but below normal operating range - moderately severe level
19 Received network data in error
20 not used (reserved)
21 not used (reserved)
22 not used (reserved)
23 not used (reserved)
24 not used (reserved)
25 not used (reserved)
26 not used (reserved)
27 not used (reserved)
28 not used (reserved)
29 not used (reserved)
30 not used (reserved)
31 Condition exist
118 TJ 509T-V.112013
21. -
23. -
24. -
25. -
TJ 509T-V.112013 119
29. SMS COMMANDS
SMS messages are accepted only from phone numbers re-
corded in the Communication>GSM>Message Numbers tab.
Answers to SMS messages will be sent to all phone numbers
in the list.
120 TJ 509T-V.112013
COMMAND DESCRIPTION ANSWER
MODE STOP Puts the controller into STOP Unit forced to STOP!
mode. Alarms are also cleared.
MODE AUTO Puts the controller into AUTO Unit forced to AUTO!
mode. Alarms are also cleared.
MODE MAN- Puts the controller into Unit forced to RUN!
UAL MANUAL (RUN) mode. Alarms
are also cleared.
MODE TEST Puts the controller into TEST Unit forced to TEST!
mode. Alarms are also cleared.
OUT1 ON Sets remote controlled output OUT 1 = ON
#1 to active state
OUT1 OFF Sets remote controlled output OUT 1 = OFF
#1 to passive state
OUTxx ON Sets remote controlled output OUT xx = ON
#xx to active state (xx denotes
any number between 1 and
16).
OUTxx OFF Sets remote controlled output OUT xx = OFF
#xx to passive state (xx
denotes any number between
1 and 16).
TJ 509T-V.112013 121
30. LOAD TRANSFER MODES
The unit offers 2 ways of transferring the load from genset to mains and vice versa:
-transfer with interruption,
-no break transfer, (with or without synchronization)
122 TJ 509T-V.112013
30.2. UNINTERRUPTED TRANSFER
In this mode, the transfer will be made without power interruption. This implies that both of the
mains and generator contactors will be active during transfer.
The maximum duration that both contactors will be active is programmable. However this pro-
cess may be quicker with the use of one auxiliary feedback contact from each contactor. Thus the
changeover will be quite instantaneous, preventing any excess or reverse power condition.
When an uninterrupted transfer cycle is started, the unit will wait until the expiration of the
Synchronization Fail Timer, to find a matching frequency, phase and voltage.
Usually, with frequencies matching at +/- 2Hz and voltages matching at +/-10 volts an
Uninterrupted Transfer is expected to successful.
If matching is found before the expiration of the Synchronization Fail Timer, then both contactors
will be activated. If contactor auxiliary contacts are used, the other contactor will release immedi-
ately. If contactor auxiliary contacts are not used, the other contactor will release after contactor
timeout .
The unit offers below parameters for the setup of the Uninterrupted transfer feature.
Parameter Definition Description
No Break Transfer 0: only interrupted transfer enabled
Enable 1: no break transfer enabled
Synchronization Fail If the phase and voltage synchronization is not successful before the expiration of
Timeout this timer, then a Synchronization Fail warning is given and the transfer will be
performed with interruption.
Synchronization When synchronization is detected, both contactors will stay closed during this timer.
Contactor Timeout
Max Freq Difference This is the maximum difference between mains and genset frequencies to close both
contactors.
Max Volt Difference This is the maximum difference between the mains phase-L1 and the genset phase-
L1 voltages to close both contactors. If voltage transformer is used, this quantity is
multiplied with voltage transformer ratio.
Max Phase Difference This is the maximum phase angle between the mains phase-L1 and the genset phase-
L1 voltages to close both contactors.
TJ 509T-V.112013 123
31. -
32. SOFTWARE FEATURES
32.1. Load Shedding / Dummy Load
The load shedding feature consists on the disconnection of the least crucial loads when the genset
power approaches to its limits. These loads will be supplied again when the genset power falls below
the programmed limit. The internal Load Shedding function is always active. Any digital output may
be used as the load shedding output.
The dummy load function consists on the connection of a dummy load if the total genset load is
below a limit and to disconnection of the dummy load when the total power exceeds another limit.
The dummy load function is the inverse of the load shedding function, thus the same output may be
used for both purposes.
It is also possible to control more complex external systems with multiple steps, using LOAD_ADD
and LOAD_SUBSTRACT output functions. Any digital output may be assigned to these signals.
When the load is above the Load Shedding High Limit, the controller will activate the Load Substract
output.
When the load is below the Load Shedding Low Limit, the controller will activate the Load Add output.
The external system will decrease the load until it goes below the high limit, where the
Load Substract output will become inactive.
There are protection delays between two pulses.
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Load Shedding Low Limit: If the genset power goes below this limit then the load shedding relay will
be deactivated.
Load Shedding High Limit: If the genset power goes above this limit then the load shedding relay will
be activated.
t1: the load goes below the Load Shedding Low Limit, thus the Load Shedding output becomes inactive.
t2: the load goes above the Load Shedding High Limit, thus the Load Shedding output becomes active.
t3: the load goes below the Load Shedding Low Limit, thus the Load Shedding output becomes inactive.
124 TJ 509T-V.112013
32.2. LOAD ADD / SUBSTRACT
The load add/substract output functions are designed to provide control signals for an external, multi-
step load adding/substracting system.
This external system will add either linearly or by small steps a dummy load that will prevent the genset
from running below the minimum required load level.
The same function may be used in order to supply loads of different priority levels following the available
genset capacity.
When the load is below the Load Shedding Low Limit, the controller will activate the Load Add output.
The external system will increase the load until it goes over the low limit, where the Load Add output
will become inactive.
When the load is above the Load Shedding High Limit, the controller will activate the Load Substract
output. The external system will decrease the load until it goes below the high limit, where the Load
Substract output will become inactive.
There are protection delays between two pulses.
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Load Shedding Low Limit: If the genset power goes below this limit then the load shedding relay will
be deactivated.
Load Shedding High Limit: If the genset power goes above this limit then the load shedding relay will
be activated.
Load Add Delay: This is the minimum delay between 2 load_add pulses. This is also the minimum
delay between 2 load_substract pulses.
Load Subtract-Add Delay: This is the minimum delay between load_add and load_substract pulses.
t1: the load goes below the Load Shedding Low Limit, thus the Load Add output becomes active.
t2: the load goes above the Load Shedding Low Limit, thus the Load Add output becomes inactive.
t3: the load goes above the Load Shedding High Limit, thus the Load Substract output becomes active.
t4: the load goes below the Load Shedding High Limit, thus the Load Substract output becomes
inactive.
t5: the load goes below the Load Shedding Low Limit, but the Load Substract-Add delay is not expired.
The controller waits until expiration of the timer.
t6: the timer is expired and the load is still below the Load Shedding Low Limit, the Load Add output
becomes active.
t7: the load goes above the Load Shedding Low Limit, thus the Load Add output becomes inactive.
TJ 509T-V.112013 125
Protection timers help to stabilizing the decision algorithm and preventing unwanted multiple opera-
tions.
When the load is below the Multi Load Add Power Level during Multi Load Add Start Delay, then 1
step of load is added. The minimum wait period between two load_adds is Multi Load Add Wait
Delay.
When the load is above the Multi Load Substract Power Level during Multi Load Substract Start
Delay, then 1 step of load is unloaded. The minimum wait period between two load_substracts is
Multi Load Substract Wait Delay.
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Multi Load Substract Power Level: When the genset active power goes over this limit, the control-
ler will start substracting load as described in chapter Five Step Load Management.
Multi Load Add Power Level: When the genset active power goes below this limit, the controller will
start adding load as described in chapter Five Step Load Management.
Multi Load Substract Start Delay: If the load stays over the Multi Load Substract Power Level
parameter during this timer, then 1 step of load is substracted.
Multi Load Substract Wait Delay: This is the minimum period between two load subtract opera-
tions.
Multi Load Add Start Delay: If the load stays below the Multi Load Add Power Level parameter
during this timer, then 1 step of load is added.
Multi Load Add Wait Delay: This is the minimum period between two load addt operations.
t1: the load goes below the Multi Load Add Power Level.
t2: after Multi Load Add Start Delay the load is still below Multi Load Add Power Level, the Load_
Add_1 becomes active.
t3: after Multi Load Add Start Delay and Multi Load Add Wait Delay, the load is still below Multi Load
Add Power Level, thus Load_Add_2 becomes active.
t4: the load goes above the Multi Load Substract Power Level.
t5: after Multi Load Substract Start Delay, the load is still above Multi Load Substract Power Level,
thus the Load_Add_2 becomes inactive and the Load_Substract_2 becomes active for 3 seconds
(fixed delay).
t6: the load goes above the Multi Load Substract Power Level.
t7: after Multi Load Substract Start Delay, the load is still above Multi Load Substract Power Level,
thus the Load_Add_2 becomes inactive and the Load_Substract_1 becomes active for 3 seconds
(fixed delay).
126 TJ 509T-V.112013
negative. These selections are made using programming menu.
It is also necessary to set the ACTION program parameter of the related input to 3 in order to prevent
any alarm from this input.
When a Remote Start input is defined, the mains phases are not monitored. When the Remote Start
signal is present then the mains will be supposed to fail, inversely when the Remote Start signal is
absent then mains voltages will be supposed to be present.
The front panels mimic diagram’s mains LEDs will always reflect the status of the Remote Start input.
The unit offers an optional Disable Auto Start signal input. Any digital input may be assigned as
Simulate Mains using Input Function Select program parameters.
It is also necessary to set the ACTION program parameter of the related input to 3 in order to prevent
any alarms generated from this input.
The Disable Auto Start signal may be a NO or NC contact, switching to either battery positive or
battery negative. These selections are made using the programming menu.
If the Delayed Simulate Mains program parameter is set to 1 and the input signal is active when
the genset is not feeding the load, the mains phases are not monitored and supposed to be inside
limits. This will prevent the genset from starting when the simulate mains signal is present (batteries
TJ 509T-V.112013 127
charged). The genset will start when mains voltages are out of limits and the simulate mains signal
not present. If the genset is running when the signal is applied, then MAINS SIMULATION will be
prevented during Flashing Relay On Timer program parameter. After this, usual Mains Waiting and
Cooldown cycles will be performed before engine stop. When the SIMULATE MAINS signal is present,
the front panels mimic diagram’s mains LEDs will reflect the mains voltages as present.
When the signal is passive, the unit will revert to normal operation and monitor the mains
voltage status.
128 TJ 509T-V.112013
32.8. MULTIPLE VOLTAGE AND FREQUENCY
The unit offers 3 sets of voltage and frequency protection limit values. The user is allowed to switch
between these 3 sets anytime.
This feature is especially useful in dual voltage or frequency gensets for easy switching between 2
operating conditions.
The switching to the second or third set of limit values can be done via digital input signal.
If switching is done with digital input signal, one of digital inputs has to be defined as “2nd Volt-Freq
Select” using “INPUT FUNCTION SELECT“program group.
External mode select signals have priority on mode buttons of the unit. If the mode is selected by
external signal, it is impossible to change this mode with front panel pushbuttons. However if the
external mode select signal is removed, the unit will revert to the last selected mode via pushbuttons.
It is also possible to lock the front panel completely for remote command.
TJ 509T-V.112013 129
37.11. AUTOMATIC EXERCISER
The unit offers 7 independent automatic exercisers. The exercise operation may be done on a weekly
or monthly basis.
The start day and time of the exercise is programmable as well as its duration. The exercise may be
done with or without load following programming.
Please refer to the programming section for a more detailed description of the above parameters.
When the start day and hour of exercise has come, the unit will automatically switch to either RUN
or TEST mode. The engine will run. If the on_load exercise is selected then the load will be trans-
ferred to the genset.
If a mains failure occurs during the off-load exercise, the load will not be transferred to the genset
unless the Emergency Backup Operation is allowed by setting the related program parameter to 1.
Thus it is highly recommended that the Emergency Backup mode enabled with off-load exerciser.
At the end of the exercise duration, the unit will switch back to the initial mode of operation.
If any of the mode selection keys are pressed during exercise, then the exercise will be immediately
terminated.
Using the weekly exercise mode and with suitable parameter setting, the unit may feed the load from
the genset during predefined hours of each day. This operation may be used in high tariff periods of
the day.
The scheduler consists of 144 programmable parameters, one for each hour in a week. Thus every
hour of the week may be independently selected as ON or OFF times.
These programmable parameters allow the genset to operate automatically only in allowed time
limits.
The unit has a battery backed-up precision real time clock circuit. The real time clock circuit will
continue its operation even in power failures. The real time clock is precisely trimmed using the Real
Time Clock Adjust program parameter. For more details check the programming section.
130 TJ 509T-V.112013
37.13. ENGINE HEATING OPERATION
Especially on engines without a body heater, or with a failing one, it may be desired that the genset
should not take the load before reaching a suitable temperature. The unit offers 2 different ways of
engine heating.
This operation mode is selected when the Engine Heating Method parameter is set to 0. In this
mode, the engine will run during parameter Engine Heating Timer, and then the genset will take the
load.
This operation mode is selected when the Engine Heating Method parameter is set to 1. In this
mode, at first the engine will run during parameter Engine Heating Timer, then it will continue to
run until the measured coolant temperature reaches the limit defined in parameter Engine Heating
Temperature. When the requested temperature is reached, the load will be transferred to the genset.
This operation mode may be used as a backup to the engine body heater. If the engine body is warm
the heating will be skipped.
Any digital output may be assigned as IDLE output using Relay Definition program parameters.
The Idle speed operation is performed both in engine start-up and cool-down sequences. Low speed
and low voltage protections are disabled during idle speed operation.
TJ 509T-V.112013 131
37.16. FUEL PUMP CONTROL
The unit is able to provide a digital output function in order to drive the fuel pump motor. The fuel
pump is used in order to transfer fuel from the large capacity main tank (if exists), to the genset daily
tank which is generally integrated in the chassis and has a limited capacity.
The fuel level reference is measured through the analog fuel level sender. When the measured fuel
level falls below Fuel Pump Low Limit parameter, the fuel pump output function will become active.
When the fuel level reaches Fuel Pump High Limit parameter, the output function will become pas-
sive. Thus the chassis fuel tank level will be always kept between Fuel Pump Low Limit and Fuel
Pump High Limit parameters.
The fuel pump relay function may be assigned to any digital output using Relay Definition program
parameters.
The fuel solenoid of a gas engine is different from a diesel engine. It should be opened after the crank-
ing has been started and should be closed between crank cycles. The delay between the crank start
and solenoid opening is adjusted using the Gas Solenoid Delay program parameter.
The gas engine fuel solenoid relay function may be assigned to any digital output using Relay Definition
program parameters.
132 TJ 509T-V.112013
37.19. CHARGING THE ENGINE BATTERY
The controller offers an automatic charge cycle for the engine battery.
When the engine battery weakens, the genset will run automatically during programmed period in
an unloaded state in order to charge the engine battery, protecting it from total discharge when the
genset has not run for a long time.
Related parameters:
Battery Charge Run Voltage: If this parameter is different from zero and the engine battery voltage
falls below this limit then the controller will run the engine unloaded, in order to charge engine battery.
The running duration is determined by the Battery Charge Run Timer parameter.
Battery Charge Run Timer: This parameter determines the engine battery charge running duration.
The minimum run time is 2 minutes.
Emergency Backup: If this parameter if activated and the mains fails during engine battery charging
run, then the genset will take the load.
TJ 509T-V.112013 133
40. DECLARATION OF CONFORMITY
The unit conforms to the EU directives
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
The CE mark indicates that this product complies with the European requirements for safety, health
environmental and customer protection.
UL / CSA Conformity:
certification teting in progress
UL 508, Edition 17
UL 2200, 1st Edition.
UL 840 Edition 3
CSA C22.2 NO. 14 - Edition 10
41. MAINTENANCE
DO NOT OPEN THE UNIT !
There are NO serviceable parts inside the unit.
Wipe the unit, if necessary with a soft damp cloth. Do not use chemical agents
Following the “DIRECTIVE 2011/65/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL
of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical and
electronic equipment”, this product is listed in annex-I under category: “Monitoring and control
instruments including industrial monitoring and control instruments” and exempted from ROHS
directive.
However Teksan Generator is not using any ROHS uncompliant electronic components in the produc-
tion. Only the solder contains lead. The switching to unleaded solderin is in progress.
134 TJ 509T-V.112013
44. TROUBLESHOOTING GUIDE
The genset operates while AC mains are OK or continues to operate after AC mains are OK:
-Check engine body grounding.
-AC mains voltages may be outside programmed limits, measure the phase voltages.
-Check the AC voltage readings on the screen.
-Upper and lower limits of the mains voltages may be too tight. Check the parameters Mains Volt-
age Low Limit and Mains Voltage High Limit. Standard values are 170/270 volts.
-The hysteresis voltage may be given to excessive. The standard value is 8 volts.
AC voltages or frequency displayed on the unit are not correct:
-Check engine body grounding, it is necessary.
-The error margin of the unit is +/- 2 volts.
-If there are faulty measurements only when the engine is running, there may be a faulty charging
alternator or voltage regulator on the engine. Disconnect the charging alternator connection of the
engine and check if the error is removed.
-If there are faulty measurements only when mains are present, then the battery charger may be
failed. Turn off the rectifier fuse and check again.
KW and cos Φ readings are faulty although the Amp readings are correct:
-Current transformers are not connected to the correct inputs or some of the CTs are connected
with reverse polarity. Determine the correct connections of each individual CT in order to obtain
correct KW and cosΦ for the related phase, and then connect all CTs. Please review chapter “AC
CURRENT INPUTS”
When the AC mains fails the unit energizes the fuel solenoid, but does not start and OIL
PRESSURE EXISTS ! message is displayed:
The unit is not supplied with battery (-) voltage at the oil pressure input.
-Oil pressure switch not connected.
-Oil pressure switch connection wire cut.
-Oil pressure switch faulty.
-Oil pressure switch closes too lately. If oil pressure switch closes, the unit will start. Optionally oil
pressure switch may be replaced.
TJ 509T-V.112013 135
The engine does not run after the first start attempt, then the unit does not start again and
OIL PRESSURE EXISTS ! message is displayed:
-The oil pressure switch closes very lately. As the unit senses an oil pressure, it does not start.
When oil pressure switch closes the unit will start. Optionally the oil pressure switch may be
replaced.
When the AC mains fails, the engine starts to run but the unit gives START FAIL alarm and
then the engine stops:
-The generator phase voltages are not connected to the unit. Measure the AC voltage between
terminals GEN L1-L2-L3 and Generator Neutral at the rear of the unit while the engine is running.
A fuse protecting the generator phases may be failed. A misconnection may be occurred. If every-
thing is OK, turn all the fuses off, and then turn all the fuses on, starting from the DC supply fuse.
Then test the unit again.
The unit is late to remove engine cranking:
-The generator voltage rises lately. Also the generator remnant voltage is below 15 volts. The
unit removes starting with the generator frequency, and needs at least 15 volts to measure the
frequency.
-The unit is also able to cut cranking from charge alternator voltage and oil pressure input. Please
read chapter “CRANK CUTTING”
The unit is inoperative:
Measure the DC-supply voltage between terminals BAT+ and BAT- at the rear of the unit. If OK,
turn all fuses off, then turn all the fuses on, starting from the DC supply fuse. Then test the unit
again.
Programming mode can not be entered:
The program lock input disables programming mode entry. Disconnect the program lock input
from battery negative before modification. Do not forget to make this connection again to prevent
unauthorized program modifications.
Some program parameters are skipped:
These parameters are reserved for factory setting and cannot be modified.
AUTO led flashes and the genset does not run when mains fail:
The unit is in Weekly Schedule OFF time. Please check date and time setting of the unit. Please
check also Weekly Schedule program parameters.
The genset runs but does not take the load:
Check that the genset Yellow led is on steadily. Adjust genset voltage and frequency limits if
necessary.
Check that the digital output-8 is configured as “Genset Contactor”
Check “Genset Contactor Timer” program parameter.
Check that a Genset Loading Inhibit input signal is not active. Check input functions. If an input is
configured as “Genset Loading Inhibit” then check the signal is not present at this input.
136 TJ 509T-V.112013
Yenidogan Mah. Edebali Cad. No:12
Sancaktepe 34791 ISTANBUL / TURKEY
Tel: +90 (216) 312 05 50 Pbx
Fax: +90 (216) 312 69 09
e-Mail: [email protected]
www.teksanjenerator.com