Performance - 2212kW YVAA0523@39C - Primary Variable

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Page 1 of 4

Performance Report
Performance Specification
Project Name: Ascenty DC Unit Tag: CH-1 Qty.: 1 Model: YVAA0523

Full Load - Design

PIN
YVAA0523JP K46CAVMXXX SAXLXXXX60 63RDFXXH18 1X1SVGA2BM XKXR1XXXXX MXXSXX???? ?????????? ??????????

....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Unit

Model No. YVAA0523

Number of Compressors 2

Compressor Type VSD Screw - Semi Hermetic

Number of Compressor Circuits 2

Capacity Control 10% - 100%

Refrigerant R-134a

Performance Data

Net Cooling Capacity [kW] 2212

Total Power Input [kW] 689.8

EER [kW/kW] 3.206

IPLV.SI [kW/kW] 5.369

A-Weighted Sound Power [dB(A)] 110.0

Sound Pressure (Hemispherical Method)


79.0
[dB(A)]
Performance Impacting Options
Sound Pressure Measured at [m] 10.0
End User Application Data Center / Process Duty
Electrical Data
High Capacity Optimized Part Load
Compressor Style
Nominal Voltage / Voltage Limits 460-3-60.0 / 414V - 508V Efficiency

Compressor kW (each circuit) 310.1 / 310.3 Condenser Coil Microchannel Coils

Compressor RLA (each circuit) [A] 410.2 / 410.5 High Airflow Fans With Variable Speed
Fan
Control
Fan QTY (each circuit) 13 / 13
Additional Compressor Enclosure Sound Kit
Sound Attenuation
(Level 1 Reduction)
Fan FLA (each circuit) [A] 3.8 / 3.8

Min. Circuit Ampacity (each system) [A] 567.8 / 562.5 Weight & Dimensional Data

Max. Fuse / CB Rating (each system) [A] 800.0 / 800.0 Shipping Weight [kg] 13917

Unit Short Circuit Withstand [kA] 65 kA Operating Weight [kg] 14533

Wires Per Phase (each system) 2/2 Refrigerant Charge [kg] Value / 135

Wire Range (Lug Size) (each system) #1 - 500 kcmil / #1 -500 kcmil Length [mm] 15222

Displacement Power Factor 0.95 Width [mm] 2242

Control kVA 3.000 Height [mm] 2403

Project Name: Ascenty DC


Rating Engine Version: REV.v9_18a.idd Version: SN23.12a Generated: 2024/02/13 at 08:07
Unit Name: 2280kW YVAA0523@39C CHL.2024-02.001 Page 1 of 4
Page 2 of 4
Performance Report
Performance Specification
Project Name: Ascenty DC Unit Tag: CH-1 Qty.: 1 Model: YVAA0523

Heat Exchanger Performance

Evaporator Condenser (Air Cooled)

Heat Exchanger Type Hybrid Falling Film Ambient Air Temperature* [ºC] 39.0

Entering Fluid Temperature* [ºC] 27.00 Altitude* [m] 600

Leaving Fluid Temperature* [ºC] 17.00 Condensing Temperature [ºC] 60.06 / 60.09

Flow Rate [L/s] 53.08 Number of Fans (Circuit 1 / Circuit 2) 13 / 13

Fouling Factor* [m2 K/kW] 0.0176 Total Air Flow [m3/s] 194

Fluid Type* Water Total Fan Power [kW] 69.45

Passes* 2

Pressure Drop [kPa] 30.1

Fluid Volume [L] 556.0

Evaporating Temperature [ºC] 14.75

Partload Minimum Flow Rate w/VPF [L/s] 17.35

Minimum Flow Rate [L/s] 34.70

Maximum Flow Rate [L/s] 136.3

* Designates user specified input

Outside the scope of AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and
AHRI Standard 551/591 (SI). Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power

Part Load Performance (Based on Variable Primary Flow)

Unit Efficiency
Percent Load Ambient [ºC] Capacity [kW] Power Input [kW] EFT [ºC] LFT [ºC] Flow Rate [L/s] Evap. PD [kPa]
[kW/kW]

100.0 39.0 2212 689.8 3.206 27.00 17.00 53.08 30.1

90.0 35.1 1991 533.3 3.733 27.00 17.00 47.78 25.0

80.0 31.2 1770 405.7 4.361 27.00 17.00 42.47 20.2

70.0 27.4 1548 292.4 5.296 27.00 17.00 37.16 16.0

60.0 23.5 1327 208.6 6.361 27.00 17.00 31.85 12.1

50.0 19.6 1106 135.5 8.162 27.00 17.00 26.54 8.77

40.0 15.7 884.8 87.02 10.17 27.00 17.00 21.23 5.81

30.0 13.0 663.6 81.32 8.160 26.17 17.00 17.35 3.75

20.0 13.0 442.4 43.92 10.07 23.11 17.00 17.35 3.71

15.4 13.0 339.6 29.52 11.51 21.69 17.00 17.35 3.70

Project Name: Ascenty DC


Rating Engine Version: REV.v9_18a.idd Version: SN23.12a Generated: 2024/02/13 at 08:07
Unit Name: 2280kW YVAA0523@39C CHL.2024-02.001 Page 2 of 4
Page 3 of 4
Performance Report
Performance Specification
Project Name: Ascenty DC Unit Tag: CH-1 Qty.: 1 Model: YVAA0523

Sound Power Levels (In Accordance with AHRI 370)

Octave Band Center Frequency [Hz]


Percent Load Ambient [ºC] LWA
63 125 250 500 1000 2000 4000 8000

100.0 39.0 99.0 112.0 109.0 108.0 107.0 100.0 94.0 86.0 110.0

90.0 35.1 99.0 111.0 109.0 107.0 102.0 98.0 92.0 85.0 108.0

80.0 31.2 94.0 106.0 108.0 113.0 106.0 97.0 91.0 82.0 112.0

70.0 27.4 92.0 104.0 101.0 102.0 96.0 93.0 87.0 79.0 103.0

60.0 23.5 91.0 102.0 100.0 99.0 101.0 90.0 85.0 77.0 103.0

50.0 19.6 88.0 101.0 98.0 101.0 95.0 86.0 80.0 74.0 100.0

40.0 15.7 88.0 102.0 93.0 106.0 92.0 82.0 76.0 67.0 103.0

30.0 13.0 85.0 98.0 94.0 106.0 92.0 82.0 76.0 67.0 103.0

20.0 13.0 80.0 92.0 90.0 91.0 88.0 76.0 70.0 62.0 92.0

15.4 13.0 83.0 104.0 89.0 92.0 89.0 77.0 72.0 61.0 94.0

Note:Unit is equipped with Additional Compressor Enclosure Sound Kit (Level 1 Reduction) and High Airflow Fans With Variable Speed Control.

Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.

Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the
rating metric.

For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation
model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given distance
from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models pertaining to air-
cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.

Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band, +/-
4dB in all other octave bands and +/- 3dB for the overall dBA.

Tolerance limits are based on uncertainties associated with:

1. Measurement Test Procedure

2. Repeatability

3. Production / Manufacturing Variability

Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels. Note
that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.

Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.

Estimated Sound Pressure Levels at 10.0 m (Derived from AHRI 370 Sound Power using Hemispherical Method)

Octave Band Center Frequency [Hz]


Percent Load Ambient [ºC] LpA
63 125 250 500 1000 2000 4000 8000

100.0 39.0 67.0 80.0 78.0 76.0 75.0 68.0 62.0 55.0 79.0

90.0 35.1 67.0 80.0 77.0 75.0 71.0 66.0 60.0 54.0 76.0

80.0 31.2 63.0 74.0 76.0 81.0 74.0 65.0 59.0 50.0 80.0

70.0 27.4 60.0 72.0 69.0 71.0 65.0 61.0 55.0 47.0 71.0

60.0 23.5 59.0 71.0 68.0 67.0 69.0 59.0 53.0 45.0 71.0

50.0 19.6 56.0 69.0 66.0 69.0 63.0 55.0 49.0 42.0 68.0

40.0 15.7 56.0 71.0 61.0 74.0 60.0 50.0 44.0 36.0 71.0

30.0 13.0 53.0 66.0 63.0 74.0 61.0 50.0 45.0 36.0 71.0

20.0 13.0 48.0 60.0 58.0 59.0 57.0 45.0 39.0 30.0 60.0

15.4 13.0 52.0 72.0 58.0 61.0 57.0 46.0 40.0 29.0 62.0

Project Name: Ascenty DC


Rating Engine Version: REV.v9_18a.idd Version: SN23.12a Generated: 2024/02/13 at 08:07
Unit Name: 2280kW YVAA0523@39C CHL.2024-02.001 Page 3 of 4
Page 4 of 4
Performance Report
Performance Specification
Project Name: Ascenty DC Unit Tag: CH-1 Qty.: 1 Model: YVAA0523

Performance at AHRI Conditions

Evaporator Condenser

EFT [ºC] 12.00 Ambient Temp. [ºC] 35.0

LFT [ºC] 7.00 Altitude [m] 0.00

Flow Rate [L/s] 83.96 Performance

Pressure Drop [kPa] 73.4 EER [kW/kW] 3.000

Fluid Type Water IPLV.SI [kW/kW] 5.369

Fouling Factor [m2 K/kW] 0.0180 Net Cooling Capacity [kW] 1760

Fluid Volume [L] 556.0

Note:Unit rated at design condition capacity.

Part Load Performance (Based on AHRI 551/591 - 2018 (SI))

Percent Load Ambient [ºC] Capacity [kW] Power Input [kW] Unit Efficiency [kW/kW]

100.0 35.0 1760 586.6 3.000

75.0 27.0 1320 322.0 4.099

50.0 19.0 880.0 144.6 6.087

25.0 13.0 440.0 60.15 7.315

Notes:

Country of Origin:Mexico

Min DSD (Factory Purpose/Use Only):150.1 psig

Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option selected. Calculated value is available by request.

Use Copper Conductors only

The unit does not have a coil coating selected.

Minimum and maximum evaporator flow information are for full load ratings with Water.

Evaporator Passes:2, Condenser Type:M, Fan Type:K

Compliant with ASHRAE 90.1 - 2010,2013,2016,2019,2022.

Part load minimum flow rate with variable primary flow is based on the fluid being Water.

The product image shown is for illustrative purposes only and is not representative of selected options.

Project Name: Ascenty DC


Rating Engine Version: REV.v9_18a.idd Version: SN23.12a Generated: 2024/02/13 at 08:07
Unit Name: 2280kW YVAA0523@39C CHL.2024-02.001 Page 4 of 4