Performance - 2212kW YVAA0523@39C - Primary Variable
Performance - 2212kW YVAA0523@39C - Primary Variable
Performance - 2212kW YVAA0523@39C - Primary Variable
Performance Report
Performance Specification
Project Name: Ascenty DC Unit Tag: CH-1 Qty.: 1 Model: YVAA0523
PIN
YVAA0523JP K46CAVMXXX SAXLXXXX60 63RDFXXH18 1X1SVGA2BM XKXR1XXXXX MXXSXX???? ?????????? ??????????
Unit
Number of Compressors 2
Refrigerant R-134a
Performance Data
Compressor RLA (each circuit) [A] 410.2 / 410.5 High Airflow Fans With Variable Speed
Fan
Control
Fan QTY (each circuit) 13 / 13
Additional Compressor Enclosure Sound Kit
Sound Attenuation
(Level 1 Reduction)
Fan FLA (each circuit) [A] 3.8 / 3.8
Min. Circuit Ampacity (each system) [A] 567.8 / 562.5 Weight & Dimensional Data
Max. Fuse / CB Rating (each system) [A] 800.0 / 800.0 Shipping Weight [kg] 13917
Wires Per Phase (each system) 2/2 Refrigerant Charge [kg] Value / 135
Wire Range (Lug Size) (each system) #1 - 500 kcmil / #1 -500 kcmil Length [mm] 15222
Heat Exchanger Type Hybrid Falling Film Ambient Air Temperature* [ºC] 39.0
Leaving Fluid Temperature* [ºC] 17.00 Condensing Temperature [ºC] 60.06 / 60.09
Fouling Factor* [m2 K/kW] 0.0176 Total Air Flow [m3/s] 194
Passes* 2
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and
AHRI Standard 551/591 (SI). Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power
Unit Efficiency
Percent Load Ambient [ºC] Capacity [kW] Power Input [kW] EFT [ºC] LFT [ºC] Flow Rate [L/s] Evap. PD [kPa]
[kW/kW]
100.0 39.0 99.0 112.0 109.0 108.0 107.0 100.0 94.0 86.0 110.0
90.0 35.1 99.0 111.0 109.0 107.0 102.0 98.0 92.0 85.0 108.0
80.0 31.2 94.0 106.0 108.0 113.0 106.0 97.0 91.0 82.0 112.0
70.0 27.4 92.0 104.0 101.0 102.0 96.0 93.0 87.0 79.0 103.0
60.0 23.5 91.0 102.0 100.0 99.0 101.0 90.0 85.0 77.0 103.0
50.0 19.6 88.0 101.0 98.0 101.0 95.0 86.0 80.0 74.0 100.0
40.0 15.7 88.0 102.0 93.0 106.0 92.0 82.0 76.0 67.0 103.0
30.0 13.0 85.0 98.0 94.0 106.0 92.0 82.0 76.0 67.0 103.0
20.0 13.0 80.0 92.0 90.0 91.0 88.0 76.0 70.0 62.0 92.0
15.4 13.0 83.0 104.0 89.0 92.0 89.0 77.0 72.0 61.0 94.0
Note:Unit is equipped with Additional Compressor Enclosure Sound Kit (Level 1 Reduction) and High Airflow Fans With Variable Speed Control.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the
rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation
model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given distance
from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models pertaining to air-
cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band, +/-
4dB in all other octave bands and +/- 3dB for the overall dBA.
2. Repeatability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels. Note
that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.
Estimated Sound Pressure Levels at 10.0 m (Derived from AHRI 370 Sound Power using Hemispherical Method)
100.0 39.0 67.0 80.0 78.0 76.0 75.0 68.0 62.0 55.0 79.0
90.0 35.1 67.0 80.0 77.0 75.0 71.0 66.0 60.0 54.0 76.0
80.0 31.2 63.0 74.0 76.0 81.0 74.0 65.0 59.0 50.0 80.0
70.0 27.4 60.0 72.0 69.0 71.0 65.0 61.0 55.0 47.0 71.0
60.0 23.5 59.0 71.0 68.0 67.0 69.0 59.0 53.0 45.0 71.0
50.0 19.6 56.0 69.0 66.0 69.0 63.0 55.0 49.0 42.0 68.0
40.0 15.7 56.0 71.0 61.0 74.0 60.0 50.0 44.0 36.0 71.0
30.0 13.0 53.0 66.0 63.0 74.0 61.0 50.0 45.0 36.0 71.0
20.0 13.0 48.0 60.0 58.0 59.0 57.0 45.0 39.0 30.0 60.0
15.4 13.0 52.0 72.0 58.0 61.0 57.0 46.0 40.0 29.0 62.0
Evaporator Condenser
Fouling Factor [m2 K/kW] 0.0180 Net Cooling Capacity [kW] 1760
Percent Load Ambient [ºC] Capacity [kW] Power Input [kW] Unit Efficiency [kW/kW]
Notes:
Country of Origin:Mexico
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option selected. Calculated value is available by request.
Minimum and maximum evaporator flow information are for full load ratings with Water.
Part load minimum flow rate with variable primary flow is based on the fluid being Water.
The product image shown is for illustrative purposes only and is not representative of selected options.