Tyco
Tyco
DATASHEET
MINERVA® MX
MX1000/MX4000/ZX1/ZX4
MX Panel Range
Features:
Long term service and support
Reliable, modular fire controllers
LPCB, BV, VdS approved controllers, network,
detectors and ancillaries
Expandable from one 1 zone controller to multiple 240
zone, 1000 point controllers
Easy to use with flexible and powerful configuration
functions
MINERVA® MX
What should you expect of your fire detection Modular in design, MINERVA® MX provides economical fire
detection for small buildings but is also flexible enough to
system? implement the complex event procedures required in larger ones.
In broad terms: cost effective reliability and flexibility. In today's Detectors are controlled in groups of up to 240 zones all software
buildings, under today's conditions, you should also be looking for configurable, so avoiding the expensive need to hardwire each zone
ease of operation, flexible programming, precise fire source pin- back to the control panel. Further savings are made possible by
pointing and the kind of circuitry and sensitivity which ensures harnessing the power of the latest micro-processing technology to
rapid activation in the event of a fire. enable a single loop of two-core cabling to carry both detection and
command signals.
MINERVA® MX meets all these expectations as a
matter of course. Backwards compatibility is also achieved by using an ancillary
MINERVA MX is a comprehensive range of fire controllers
® module which allows existing fire systems to be updated and
designed and built to BSEN ISO9001/2 by the UK’s leading fire extended cost effectively, utilising existing wiring where possible
and security company. The 4 similar models are:- and with minimal disruption. Other ancillary modules offer even
MX1000/MX4000/ZX1 & ZX4. The MX1000/MX4000 may be greater system flexibility: short circuit sensing isolation ensures the
installed to BS5839 Part 1 and have been approved by LPCB and MINERVA® MX continues in operation, even if a wiring fault occurs.
the ZX1/ZX4, have been approved by VdS. Local sounder activation further reduces wiring costs and switch
monitoring allows easy interface to a building's plant and control
An advanced proven micro-processor based system, MINERVA® systems.
MX provides conventional as well as digital addressable
detection at the price of today's conventional systems. The Further flexibility and installation savings can be made using the
decision to sound the alarm is made at the controller allowing loop power MINERVA® MX options. Loop powered MINERVA® MX
adjustments and compensations to be made for changes in envi- panels allow sounders to be powered from the same loop wires that
ronmental conditions. In short, maximum security whilst minimis- carry communications and power to the detectors and other
ing the risk of false alarms. ancillaries.
PSF126TFIS.qxp 08/05/2007 09:49 Page 3
MINERVA® MX
MINERVA® MX Key Functions MINERVA® MX1000 & MX4000
Thanks to powerful software each zone can be given a tailor-made The MINERVA® MX panels are intelligent LPCB EN54 approved
response text message to help locate the source of a fire. Software panels, which can be networked to provide up to 792 detection
configuration and reconfiguration can be carried out on site, with loops and installed to BS5839:Pt.1.
minimum disruption and the avoidance of system down time.
Correct execution of the software is ensured by twin micro-proces- The MX1000 supports one MX DIGITAL detection loop with up to
sors that perform watchdog functions on each other. MINERVA® MX 250 addressable devices.
sounders can be set for either continuous, pulse, or a The MX4000 supports two MX DIGITAL detection loops and can
combination of two tones via the system software. The pattern of be expanded to eight loops supporting up to 1000
signals is programmable, allowing phased, controlled evacuation of addressable devices.
buildings. To aid the rapid location of fire, remote repeater panels or
geographical mimics can be connected to the controllers for greater Both panels consist of a strong steel enclosure incorporating a
monitoring convenience, as can visual display units. removable chassis plate. The chassis plate holds:
MINERVA® MX
MINERVA® MX Repeaters The panel has a strong cast aluminium front door, which
The MINERVA® MX full function repeater is an EN54 LPCB approved incorporates a modular user interface that fully complies with
repeater with optional addressable EN54:Pt.4 power supply. The EN54:pt.2. The user interface incorporates the ODM800 operator
repeater consists of a steel backbox and cast aluminium front door display module with a 16 x 40-character backlit LCD display, simple
which incorporates the ODM800 operator display module with a 16 alphanumeric keypad, 5 softkeys and a fast access key. The
x 40-character backlit LCD display, simple alphanumeric keypad and OCM800 operator control module provides all mandatory operator
5 softkeys. The OCM800 operator control module provides all control keys and LED functions including Day/Night switching. Four
mandatory operator control keys and LED functions including control keys and 4 indication LEDs are provided for site-specific
Day/Night switching. Two control keys and 2 indication LEDs are functions.
provided for site-specific functions.
Control keys and LEDs are labelled in German according to the
Control keys and LEDs are labelled in English according to the default VdS functionality. The slide in decals can be reversed and
default LPCB functionality. The slide in decals can be reversed and alternative text added.
alternative text added.
The batteries and any additional zone LED’s or operator controls are
The back box has a removable chassis plate with the PSM800 mounted in a separate housing which can be mounted below the
power supply, APM800 addressable PSU monitor module and main panel or behind the panel. This expansion battery box is
space for 2 x 7 Ah batteries to provide 72 h backup. supplied with the panel as a deep box to take 38Ah batteries. The
chassis plate in the battery box also has space for up to 2 x IOB800
The MINERVA® MX repeater with Power Supply is connected to the input/output expansion modules (maximum 24 I/O) or a TUD800
Panel via the remote bus (RS485, 1200 m distance). A German Fire Brigade transmission unit.
maximum of 7 repeaters (including one MX REMOTE repeater) can
be linked to each MINERVA® MX panel and can provide full repeater The battery box can have one or two 40 way zone indicators
functions for all panels on the system. (ANN840) mounted in the front door.
MINERVA® MX
ZETTLER Expert 1000 & 4000 ZETTLER Expert Repeaters
The ZETTLER EXPERT panels are intelligent LPCB & VdS certified The ZETTLER EXPERT full function repeater is an EN54 LPCB & VdS
EN54 panels, which can be networked to provide up to 512 certified repeater with optional addressable EN54:Pt.4 power supply.
detection loops. The repeater consists of a steel backbox and cast aluminium front
door which incorporates the ODM800 operator display module with
The ZX1 supports one Tyco MX DIGITAL detection loop with up to a 16 x 40-character backlit LCD display, simple alphanumeric
250 addressable devices or 128 for VdS certified installations. keypad, 5 softkeys and a fast access key. The OCM800 operator
The ZX4 supports two Tyco MX DIGITAL detection loops and can control module provides all mandatory operator control keys and
be expanded to eight loops supporting up to 1000 LED functions including Day/Night switching. Four control keys and
addressable devices or 512 devices for VdS certified 4 indication LEDs are provided for site-specific functions.
installations.
Control keys and LEDs are labelled in German according to the
Both panels consist of a strong deep steel enclosure incorporating a default VdS functionality. The slide in decals can be reversed and
removable chassis plate. The chassis plate holds: alternative text added.
PSB800 5A 24V DC battery backed power supply and loop
booster to EN54:pt.4 The back box has a removable chassis plate with the PSM800
FIM800 field interface PCB incorporating one or two MX DIGITAL power supply, APM800 addressable PSU monitor and space for 2 x
loops 7 Ah batteries to provide 72 h backup.
CPU800 32 bit processor and memory card The ZETTLER EXPERT Repeater with Power Supply is connected to
Optional network card, additional loop card (s) and remote the Panel via the remote bus (RS485, 1200 m distance). A
diagnostic modem maximum of 7 repeaters (including one MX REMOTE repeater) can
be linked to each ZETTLER EXPERT panel and can provide full
The panel has a strong cast aluminium front door, which repeater functions for all panels on the system.
incorporates a modular user interface that fully complies with
EN54:pt.2. The user interface incorporates the ODM800 operator The operator control module (OCM800) can support up to 80 inputs
display module with a 16 x 40-character backlit LCD display, simple and outputs in the form of LED annunciators and IOB800 in/output
alphanumeric keypad, 5 softkeys and a fast access key. The modules
OCM800 operator control module provides all mandatory operator
control keys and LED functions including Day/Night switching. Four
control keys and 4 indication LEDs are provided for site-specific
functions.
The batteries and any additional zone LED’s or operator controls are
mounted in a separate housing which can be mounted below the
main panel or behind the panel. This expansion battery box is
supplied with the panel as a deep box to take 38Ah batteries. The
chassis plate in the battery box also has space for up to 2 x IOB800
input/output expansion modules (maximum 24 I/O) or a TUD800
German Fire Brigade transmission unit.
The battery box can have one or two 40 way zone indicators
(ANN840) mounted in the front door.
PSF126TFIS.qxp 08/05/2007 09:49 Page 6
SPECIFICATIONS
Output
Display 240 Zone (all panels above)
16 x 40 Character (all panels above)
Sounder There are two separate monitored
sounder outputs each rated at 2A.
Alarm Fire _ Relay output rated at 30V d.c.
at 1.0A volt free c/o.
Fault _ Relay output rated at 30V
d.c. at 1.0A volt free c/o.
For further information on how we can help you please visit our website at www.tycofis.com or e-mail us on [email protected]. The right is reserved to modify or withdraw any
product or service without notice. PSF126TFIS Issue 2 May 2007 © 2007