Eastron SDM72D-M-2 User Manual V1.1.
1 2023
SDM72D-M-2
Three Phase Four Wire Energy Meter
Multi-parameter measurment
Resettable partial energy
Bi-directional measurement IMP & EXP
Pulse Output
RS485 Modbus
Din rail mounting 35mm
Direct connection, up to 100A
Better than Class 1/ B accuracy
User Manual V1.1.1 2023
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -1-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Introduction
The SDM72D-M-2 is digital 3 phase 4 wires energy meter with white back-lighted LCD screen for perfect reading.
The unit measures and displays voltage, current, frequency, power factor, active power, reactive power, active
energy and reactive energy, etc. A resettable partial energy is provided, so the user can easily check the active
energy imported and active energy exported during a certain period. SDM72D-M-2 supports max.100A direct
connection, saving the cost and avoiding the trouble to connect external CTs, giving the unit a cost-effective and
east operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password
protected.
PART 1 Specification
General Specifications
Voltage AC (Un) 3x230(400)V
Voltage Range 80~120% Un
Base Current (Ib) 10A AC
Max. Current (Imax) 100A AC
Mini Current (Imin) 5% of Ib AC
Starting current 0.4% of Ib
Power consumption ≤ 2W/10VA for the voltage measuring circuit
≤ 4VA for the current measuring circuit
Frequency 50/60Hz (non-MID); 50Hz(MID)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30 Imax for 0.01s
Power supply self-power supply
Display LCD with backlit
Max. Reading 999999.9kWh
Active energy Class 1 IEC62053-21 (non-MID)
Class B EN50470-1/3 (MID)
Reactive energy Class 2 IEC62053-23
Unit Characteristics
Characteristics: Accuracy: Resolution:
Voltage 0.5% ≤ 0.1V
Current 0.5% ≤ 0.1A
Frequency 0.2% ≤ 0.2%
Power factor 1% ≤ 0.1
Active power 1% ≤ 0.1kW
Reactive Power 1% ≤ 0.1 kVAr
Active energy imported and exported 1% ≤ 0.1kWh
Reactive energy 2% ≤ 0.1 kVArh
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -2-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
RS485 Serial – Modbus RTU
This unit uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and
controlling the Unit.
Set-up screens are provided for setting up the RS485 port.
Pulse output
The unit provides pulse output for active kWh. The Pulse output is passive type.
Pulse constant: 1000imp/kWh
Pulse width: 35mS
Direction for Pulse: Import
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Baud rate 1200,2400, 4800, 9600, 19200 bps
Parity none (default)/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from
the set-up menu.
Environment
Operating temperature 3K6 (-25℃ to +55℃)(default)
3K7 (-40℃ to + 70℃) (optional)
Storage and transportation temperature -40℃ to +70℃
Reference temperature 23℃±2℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 2000m
Warm up time 3s
Installation category CAT III
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2
Mechanics
Din rail dimensions 72x100x66 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Protection against penetration of dust and water IP51 (indoor)
Material self-extinguishing UL94V-0
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -3-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
PART 2 Operation
Initialization Display
When it is powered on, the meter will initialize and do self-checking.
Full Screen
Software Version
Pulse constant
Total active energy(kWh)
Total=Import+ Export
5+2 -> 6+1
Max. reading: 999999.9 kWh
Buttons function
There are two buttons on the front panel.
>Scroll the display for data-check.
>Change option at Set-up mode
>Exit the Set-up mode
>Set-up mode entry
>Confirmation
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -4-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Scroll display
After initialization and self-checking program, the meter displays the measured values. The default page is total
kWh. If the user wants to check other information, please press the scroll button on the front panel.
Total active energy
Total=Import+ Export
Resettable partial kWh
Total=Import+ Export
Import energy
Export energy
Total reactive energy
Resettable reactive energy
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -5-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Voltage L1-N
Voltage L2-N
Voltage L3-N
L1 current
L2 current
L3 current
L1 active power
L2 active power
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -6-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
L3 active power
Total active power
L1 reactive power
L2 reactive power
L3 reactive power
Total reactive power
L1 Power factor
L2 power factor
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -7-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
L3 power factor
Total Power factor
Frequency
Pulse output type:
Default: kWh
Pulse constant: 1000imp
Modbus Address
Baud Rate
Parity
Software version
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -8-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Set-up Mode
To get into Set-up Mode, the user need to press the “Enter” button for 3 seconds.
Setting interface Setting status Option:
Password
Default: 1000
Modbus address
Rane:001~247
default:001
Buad rate
Option:
1200,2400,4800,9600,
19200 bps
default:9600 bps
Parity:
Option:NONE,EVEN,ODD
default:NONE
Stop bit
Option:1,2
default:1
Automatic Scroll display set
Range:0~60,unit:second
default:05, 0 means do not
scroll
Backlit time setting
Option:
on,5,10,30,60,120,off
unit:minute
default:60 minute
System:
Option: 3P4W,1P2W
default: 3P4W
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH -9-
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Password:
default:1000
Resettable partial energy
Keep pressing button to exit the set-up mold.
Wiring diagram
Terminals
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 10
Eastron SDM72D-M-2 User Manual V1.1.1 2023
3 phase 4 wire
1 phase 2 wire
NOTE:
Maximum Wire Size for Mainload: 25mm²
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 11
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Dimensions
Installation
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 12
Eastron SDM72D-M-2 User Manual V1.1.1 2023
PART 3 Modbus Protocol
Input Registers
Input registers are used to indicate the present values of the measured and calculated electrical quantities. Each
parameter is held in two consecutive 16 big register. The following table details the 3X register address, and the
values of the the address bytes within the message. A (*) in the column indicated the parameter is valid for the
particular wiring system, Any parameter with a cross (X) will return the value zero. Each parameter is held in the 3X
registers. Modbus Protocol function code 04 is used to access all parameters.
For example, to request: Amps 1 Start address = 0006
No.of registers = 0002
Amps 2 Start address = 0008
No. Of register = 0002
Each request for data must be restricted to 30 parameters or less. Exceeding the 30 parameter limit will cause a
Modbus Protocol exception code to be returned.
Modbus
Protocol
Input Register Parameter Start
Address Address
(Register) Hex
Length Data Hi Lo
Description Units
(bytes) Format Byte Byte
30001 Phase 1 line to neutral volts. 4 Float V 00 00
30003 Phase 2 line to neutral volts. 4 Float V 00 02
30007 Phase 1 current. 4 Float A 00 06
30009 Phase 2 current. 4 Float A 00 08
30011 Phase 3 current. 4 Float A 00 0A
30013 Phase 1 active power. 4 Float W 00 0C
30015 Phase 2 active power. 4 Float W 00 0E
30017 Phase 3 active power. 4 Float W 00 10
30019 Phase 1 apparent power. 4 Float VA 00 12
30021 Phase 2 apparent power. 4 Float VA 00 14
30023 Phase 3 apparent power. 4 Float VA 00 16
30025 Phase 1 reactive power. 4 Float VAr 00 18
30027 Phase 2 reactive power. 4 Float VAr 00 1A
30029 Phase 3 reactive power. 4 Float VAr 00 1C
30031 Phase 1 power factor (1). 4 Float None 00 1E
30033 Phase 2 power factor (1). 4 Float None 00 20
30035 Phase 3 power factor (1). 4 Float None 00 22
30043 Average line to neutral volts. 4 Float V 00 2A
30047 Average line current. 4 Float A 00 2E
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 13
Eastron SDM72D-M-2 User Manual V1.1.1 2023
30049 Sum of line currents. 4 Float A 00 30
30053 Total system power. 4 Float W 00 34
30057 Total system volt amps. 4 Float VA 00 38
30061 Total system VAr. 4 Float VAr 00 3C
30063 Total system power factor (1). 4 Float None 00 3E
30071 Frequency of supply voltages. 4 Float Hz 00 46
30073 Import active energy 4 Float kWh 00 48
30075 Export active energy 4 Float kWh 00 4A
30201 Line 1 to Line 2 volts. 4 Float V 00 C8
30203 Line 2 to Line 3 volts. 4 Float V 00 CA
30205 Line 3 to Line 1 volts. 4 Float V 00 CC
30207 Average line to line volts. 4 Float V 00 CE
30225 Neutral current. 4 Float A 00 E0
30343 Total active Energy (2) 4 Float kWh 01 56
30345 Total reactive energy 4 Float kVArh 01 58
30385 resettable total active energy 4 Float kWh 01 80
30387 Resettable total reactive energy 4 Float kVarh 01 82
30389 resettable import active energy 4 Float kWh 01 84
30391 resettable export active energy 4 Float kWh 01 86
30397 Net kWh (Import - Export) 4 Float kWh 01 8C
31281 Total import active power 4 Float W 05 00
31283 Total export active power 4 Float W 05 02
Instruction:
1: The power factor has its sign adjusted to indicate the direction of the current. Positive refers to forward current,
negative refers to reverse current.
2: Total active energy equals to import + export.
Holding Registers
Holding register are used to store and display instrument configuration settings. All holding registers not listed
in the table below should be considered as reserved for manufacturer use and no attempt should be made to
modify their values.
The holding register parameters may be viewed or changed using the Modbus Protocol. Each parameter is held
in two consecutive 4X registers. Modbus Protocol Function Code 03 is used to read the parameter and Function
code 10 is used to write. Write only to one parameter per massage.
Modbus
Address Protocol
Parameter Valid range Mode
Register Start Address
Hex
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 14
Eastron SDM72D-M-2 User Manual V1.1.1 2023
High High
Byte Byte
Write system type:
1 = 1P2W;
3 = 3P4W,(default);
40011 System Type 00 0A r/w
Length : 4 byte
Data Format : Float
(KPPA is asked)
Range:60, 100, 200,unit: ms,
default 100.
Note: If pulse output
=1000imp/kWh,then pulse
40013 Pulse width 00 OC r/w
width is fixed at 35ms,and
cannot be adjusted.
Length : 4 byte
Data Format : Float
Read: to get the status of the KPPA
0 = not authorized;1 = authorized
Key Parameter
Write the correct password to get
Programming
40015 00 0E KPPA, enable to program key r/w
Authorization
parameters.
(KPPA)
Length : 4 byte
Data Format : Float
Write the network port
parity/stop bits for MODBUS
Protocol, where: 0 = One stop bit
and no parity, default. 1 = One
Parity and stop
40019 00 12 stop bit and even parity. 2 = One r/w
bit
stop bit and odd parity.3 = Two
stop bits and no parity.
Length : 4 byte
Data Format : Float
Write the network port node
Address: 1 to 247
Modbus
40021 00 14 default 1. r/w
address
Length : 4 byte
Data Format : Float
Option: 0~3, default 0
0 :1000 imp/kWh
1 : 100 imp/kWh
40023 Pulse constant 00 16 2: 10 imp/kWh r/w
3: 1 imp/kWh
Note: If pulse output
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 15
Eastron SDM72D-M-2 User Manual V1.1.1 2023
=1000imp/kWh,then pulse
width is fixed at 35ms,and
cannot be adjusted.
Length : 4 byte
Data Format : Float
Read: to get the password of the
meter
Write: to program the new
40025 Password 00 18 password of the meter r/w
Default 1000
Length : 4 byte
Data Format : Float
Write the network port baud rate
for MODBUS Protocol, where:
0 = 2400 baud. 1 = 4800 baud.
Network Baud 2 = 9600 baud(default).
40029 00 1C r/w
Rate 3 = 19200 baud
5 = 1200 band
Length : 4 byte
Data Format : Float
Default 0,second
Automatic
Range 0~60
40059 Scroll Display 00 3A r/w
Length : 4 byte
Time
Data Format : Float
Default 60, min
Range 0~121, 0 means backlit
always on, 121 means backlit
40061 Backlit time 00 3C r/w
always off
Length : 4byte
Data Format : Float
Pulse 1 Energy Type:
1: import active energy
Pulse 1 Energy 2: total active energy (default)
40087 00 56 r/w
Type 4: export active energy
Length : 4 byte
Data Format : Float
00 03 = reset energy info
Reset historical
461457 F0 10 Length : 2 byte wo
data
Data Format: Hex
Zhejiang Eastron Electronic Co.,Ltd. in distribution of B+G e-tech GmbH - 16
Eastron SDM72D-M-2 User Manual V1.1.1 2023
Serial number
Length : 4 byte
464513 Serial number FC 00 ro
Data Format : unsigned int32
Note: Only read
Meter code
SDM72D-M-2= 00 89
464515 Meter code FC 02 Length : 2 byte ro
Data Format : Hex
Note: Only read
The software showed on display
XX.YY
Format: XX= first byte; YY= ro
Software
464645 FC 84 second byte
version
Length: 2 byte
Data Format: Hex
Note: Read only