Experimental Investigation and Numerical Modeling of Rocking Cross Laminated Timber Walls On A Flexible Foundation

This paper presents a numerical modeling procedure for mass timber rocking wall lateral systems that was validated using results from a full-scale two-story shake table test. The test structure performed better than expected due to the flexibility of its foundation, which limited damage to the rocking walls. The numerical model was adjusted to represent a rigid foundation, and it was determined that the walls would have experienced more damage but still met design objectives on a rigid foundation. A distributed spring modeling technique is presented that captures component-level behavior like damage to wood at wall bases and can provide insight into how foundation flexibility impacts seismic performance.

Uploaded by

navid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views21 pages

Experimental Investigation and Numerical Modeling of Rocking Cross Laminated Timber Walls On A Flexible Foundation

This paper presents a numerical modeling procedure for mass timber rocking wall lateral systems that was validated using results from a full-scale two-story shake table test. The test structure performed better than expected due to the flexibility of its foundation, which limited damage to the rocking walls. The numerical model was adjusted to represent a rigid foundation, and it was determined that the walls would have experienced more damage but still met design objectives on a rigid foundation. A distributed spring modeling technique is presented that captures component-level behavior like damage to wood at wall bases and can provide insight into how foundation flexibility impacts seismic performance.

Uploaded by

navid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

Received: 18 August 2021 Revised: 4 January 2022 Accepted: 25 February 2022

DOI: 10.1002/eqe.3634

RESEARCH ARTICLE

Experimental investigation and numerical modeling of


rocking cross laminated timber walls on a flexible
foundation

Sarah Wichman1 Jeffrey W. Berman1 Shiling Pei2

1 Department of Civil and Environmental


Engineering, University of Washington, Abstract
Seattle, Washington, USA With recent developments of engineered wood products such as cross laminated
2 Department of Civil and Environmental timber, mass timber buildings in areas of high seismicity are becoming feasible
Engineering, Colorado School of Mines,
Golden, Colorado, USA
and offer benefits such as faster construction and unique architectural features. It
has also opened the door to creating seismically resilient lateral systems that sus-
Correspondence tain minor and reparable damage during large earthquakes. This paper presents
Sarah Wichman, Department of Civil and
Environmental Engineering, University of a numerical modeling procedure for mass timber rocking wall lateral system with
Washington, Seattle, WA 98195, USA. distributed spring elements to model base rocking. This modeling technique was
Email: [email protected]
validated by comparing the behavior with results from the full-scale two-story
shake table test on a mass timber building with coupled CLT rocking walls com-
pleted as part of the NHERI TallWood Project. Although the lateral system per-
formed better than expected during testing, it was determined that the flexibility
of the foundation actually limited damage to the rocking wall panels. By adjust-
ing the numerical model to represent a rigid foundation boundary condition, it
was determined that the wall system would have experienced more damage, but
would have still met design performance objectives had it been tested on a rigid
foundation.

KEYWORDS
cross laminated timber (CLT), numerical modeling, rocking walls, seismic performance, shake
table testing

1 INTRODUCTION

Using mass timber rocking walls as the main lateral force resisting system in buildings located in areas of high seismicity is
gaining interest with the increase in popularity of mass timber products. In mass timber rocking wall systems, unbonded
post-tension (PT) connections are used for recentering purposes while energy dissipation devices (such as U-shaped flex-
ural plates [UFP]) provide energy dissipation for the system. This results in an efficient structural system that can undergo
large inelastic deformations while also recentering following large earthquakes. The design of the replaceable UFP com-
ponents allows for predictable and localized yielding that can be easily repaired after large earthquake events. While this
study focuses on CLT rocking walls, similar concepts and modeling approaches can be applied for other mass timber panel
products such as mass plywood panels.
Mass timber rocking walls may be designed as seismically resilient systems that sustain minor, but easily repairable,
damage during frequent earthquakes and achieve collapse prevention for maximum considered earthquake intensity.

Earthquake Engng Struct Dyn. 2022;51:1697–1717. wileyonlinelibrary.com/journal/eqe © 2022 John Wiley & Sons Ltd. 1697
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1698 WICHMAN et al.

FIGURE 1 Coupled post-tensioned rocking wall schematic

These multiple performance goals are achieved by designing for rigorous performance objectives for different earthquake
intensity levels and ensuring critical force and deformation limits are not exceeded for important components in the
system such as the PT bars, the UFPs, and the mass timber walls themselves.
Various numerical modeling approaches have been proposed for post-tensioned rocking wall systems. For lumped plas-
ticity models, such as those developed by Iqbal1 and Sarti2 for laminated veneer lumber (LVL) rocking walls and Pei et al.3
for CLT walls, a nonlinear rotational spring at the base of the wall panels model base rocking. While these models are effi-
cient and can capture global behavior of the system well, they lack the ability to assess detailed behavior of the components
such as damage to the wood at the base of the wall. Alternatively, distributed plasticity models utilize distributed springs in
parallel at the base of the wall to model base rocking and compressive behavior of the wood at the base. While these mod-
els are typically less computationally efficient, they can provide detailed information about individual wall components.
The distributed plasticity models proposed by Sarti2 and Ganey4 were compared to experimental results on LVL and CLT
rocking walls, respectively. Both models accurately captured system force-deformation behavior and provided valuable
information about the compression neutral axis depth at the base of the wall and wall uplift that cannot be determined
from lumped plasticity models.
To better understand the performance and behavior of using rocking mass timber walls as a seismic force resisting
system, a full-scale two-story mass timber building with cross laminated timber (CLT) rocking walls was tested on the
NHERI@UCSD (Natural Hazards Engineering Research Infrastructure) shake table at the University of California, San
Diego as part of the NHERI TallWood Project.5,6 Figure 1 illustrates the post-tensioned coupled rocking wall system uti-
lized in the test. As will be discussed, the specimen performed better than expected and the rocking walls met all design
performance objectives. However, the foundation supporting the rocking walls was unexpectedly flexible and permanent
deformations in the flange of the steel foundation beam were observed during even small hazard level earthquakes, alter-
ing the behavior of the structure, and resulting in less damage to the CLT wall than expected. Extending the results of
these shake table tests thus requires numerical modeling to remove the foundation flexibility. While pervious publica-
tions have focused on the design and performance of the overall structure,5,7 this paper focuses specifically on the design
and performance of the CLT walls and will address the impact of the flexible foundation and predict the performance of
the structure had the foundation been rigid.
A detailed numerical modeling technique using distributed springs to simulate the rocking interface is presented and
validated using the results from the two-story shake table test. This model provides valuable information about individual
wall components during dynamic response including the PT bars, UFPs, and damage to the base of the rocking wall at the
corners. With this level of detail, the model is well suited to investigate the impact of the flexible foundation beam observed
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1699

F I G U R E 2 Rocking wall equilibrium: (A) CLT stress strain at base of wall at decompression, (B) CLT stress strain at base of wall after
significant uplift, and (C) full rocking wall system behavior under lateral load

during the test. When comparing the numerical model with the experimental results, the contribution of the foundation
flexibility was included in the model with additional springs at the foundation level. With modeling techniques validated,
the foundation flexibility was removed from the model to predict how the test structure would have behaved with a rigid
foundation since that is more likely to represent a realistic building. The response of the numerical model under rigid
foundation boundary conditions was compared to design performance objectives and used to further determine the impact
of the flexible foundation.

2 BEHAVIOR OF ROCKING CLT WALLS

2.1 Post-tensioned connections

In the rocking CLT wall considered here, the wall panels are precompressed against the foundation using unbonded steel
post-tensioning bars, which are fixed to the foundation at the base of the wall and anchored to the top of the wall. Apart
from the post-tensioned bars, the wall is not otherwise attached directly to the foundation; however, some form of shear
transfer is needed at the base to prevent sliding. Once lateral loads produce a moment that exceeds the decompression
moment, a gap opens at the base of the wall. Prior to decompression, the overturning moment is resisted by the initial PT
force, To,pt , and gravity loads, W, and behaves as a cantilever such that displacements are a result of shear and flexural
deformations, and not rigid body rotation. Assuming a linear distribution of the CLT compression stress along the base of
the wall, as shown in Figure 2A, the decompression moment can be approximated as:
( )
𝑀𝑑𝑒𝑐 = 𝑇𝑜,𝑝𝑡 + 𝑊 𝑑 (1)

where d is the distance between the resisting CLT panel compression force, Cclt , and the resultant of the initial PT force
and the gravity load. The resultant of the CLT compression stress acts at the centroid of its triangular distribution. If the
resultant of the initial PT force and gravity load acts through the wall’s centroid at Lw /2, where Lw is the length of the wall,
then the moment arm, d, is Lw /6 at the decompression moment.
After decompression, a gap, 𝜃𝑔𝑎𝑝 , opens between the wall base and the foundation. However, the lateral-load response
is essentially linear-elastic until the portion of the wall base in compression and in contact with the foundation, c, is at
least less than Lw /2 and the PT bars begin to elongate. Figure 2B shows the stress distribution at the base of the wall when
the contact length is less than Lw /2. Akbas et al.8 defines an effective linear limit (ELL) which corresponds to a visible gap
and reduced contact length such that the lateral stiffness of the wall is reduced enough to exhibit significant nonlinear
behavior. This point is assumed to occur when the contact length, c, is approximately 3Lw /8 and the elongation of the PT
is assumed negligible. The contact length is based on fit to experimental results from Ganey4 and was proposed by Akbas
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1700 WICHMAN et al.

FIGURE 3 Idealized compressive stress strain relationship for CLT material

et al.8 Similar to Equation (1), Mell can be calculated assuming initial PT force, To,pt , and a linear stress distribution along
the contact length, resulting in a moment arm, d, also equal to 3Lw /8.
UFPs are assumed to remain elastic and do not contribute significantly to moment resistance until after the decompres-
sion moment, but before the ELL. Once the UFPs experience significant deformations, they will yield and produce a shear
force, Vufp , along the vertical edge of the wall. Figure 2C shows a free body diagram of coupled post-tensioned rocking
walls at a point beyond decompression, with the contribution of the UFPs.
Although, the moment in the two walls will differ because of the UFP forces, the difference is assumed negligible
because the force in the PT bars is much greater than the vertical force provided by the UFPs. Thus, equal base moment
in each wall panel is assumed. As a result, the total moment at the base of the wall system, after UFP yielding, can be
calculated as:
𝑛𝑠
∑ ( ) ( )
𝑀= 𝑉𝑖 ℎ𝑖 = 𝑛𝑝 𝑇𝑝𝑡 + 𝑊 𝑑 + 𝑛𝑢𝑓𝑝 𝑉𝑢𝑓𝑝 𝐿𝑤 (2)
1

where ns is the total number of stories, np is the total number of panels in the wall, Tpt is the total force in the bars after
elongation, and nupf is the number of UFPs. As the panels rock and the CLT deforms, the portion of the wall base in
compression changes constantly. As long as the peak stress at the base of the CLT wall remains below yield, the stress
distribution will be linear. During uplift, as the lateral load increases, the PT bars stretch, increasing their tension force
and the resisting moment. The UFPs also deform, further increasing the resisting moment. As long as the PT bars remain
elastic, they will shorten upon unloading and the initial PT force will fully recenter the walls.

2.2 UFP energy dissipating devices

UFPs can be used as the primary source of energy dissipation when mounted between two rocking CLT wall panels as
shown in Figure 1. The UFP dissipates energy when one end of the UFP moves relative to the other end, yielding the steel
back and forth along the plate.9 Bolted saddle connections, like the one shown in Figure 1 make for easy replacement of
damaged UFPs after large seismic events. Figure 1 also shows a schematic of a typical UFP, where 𝑡𝑢 is the thickness of
the plate, 𝑏𝑢 is the width of the UFP, and 𝐷𝑢 is the diameter of the UFP.

2.3 CLT wall panel behavior

For this study, the stress-strain behavior of CLT is based on compression tests completed on 5-ply, E2-M1, DR Johnson CLT
at Oregon State University.10 As shown in Figure 3, in compression, the behavior can be approximated as elastic, with an
elastic modulus of Ew , until the yield stress, fy,clt is reached. After yielding, the behavior can be approximated with a zero
strain-hardening plateau until CLT splitting begins at the splitting strain, ɛs,clt . After splitting, the strength deteriorates
until crushing occurs at approximately 25% of the yield stress and at the crushing strain, ɛcr,clt .
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1701

FIGURE 4 Hysteretic behavior of rocking CLT wall systems

2.4 Cyclic behavior

The PT bars, in combination with gap opening at the base of the wall, provide a nonlinear elastic response with zero
residual rotation after unloading. However, with only PT bars, the system lacks damping. The hysteretic behavior of the
steel yielding energy dissipaters provides the needed energy dissipation. The combination of the unbonded PT bars and
the energy dissipaters produces a hybrid system that can undergo large inelastic deformations while assuring recentering
and minimized damage. The resulting flag shaped hysteresis is shown in Figure 4.
Figure 4 also shows structural limit states defined in previous research by Akbas et al.8 and Ganey et al.11 Under small
lateral forces, prior to decompression, the wall remains linear and elastic with a stiffness equal to the elastic shear and
flexural stiffness of the CLT panels alone. After the decompression point, the stiffness decreases slightly. Notable nonlin-
earity occurs after significant uplift occurs; this point is defined as the ELL. The UPFs will yield in the region between
the decompression point and the ELL or just after the ELL depending on their strength and stiffness. With increasing
lateral displacement, significant uplift and nonlinear behavior begins. The system is designed such that the base of the
CLT panels will yield, split, and crush (as shown in Figure 3) prior to PT yielding.

3 SUMMARY OF TEST SPECIMEN DESIGN

To better understand the seismic performance and behavior of mass timber rocking wall lateral systems, such as the ones
described above, a full-scale two-story mass timber building was tested on the NHERI@UCSD shake table. Figure 5 shows
a photo and schematic of the test specimen. To extend the usable width of the shake table and study diaphragm action,
the gravity columns sat atop four steel gravity frame extender beams that cantilevered off the shake table (perpendicular
to the direction of shaking). The seismic force resisting system, comprised of two coupled rocking CLT walls, was also
placed atop steel foundation beams to make the entire structure start at the same elevation. This section will discuss the
post-tensioned rocking walls in detail and presents the information pertinent to the design of the CLT wall system and the
details necessary for the numerical models presented later. The design of the remaining structure will only be discussed
briefly; more details on other aspects of the design can be found in Pei et al.5 and Barbosa et al.7

3.1 Design loads

The building was designed assuming typical office loading with a dead load of 321 and 386 kg/m2 on the floor and roof
levels, respectively. Because nonstructural elements were not included on the test structure and because concrete was
only added on the roof level, additional mass was added in the form of large steel trench plates to achieve the intended
design seismic mass. Although the final weight of the structure was intended to be equivalent to the design dead load
(329 kN on the floor level and 409 kN on the roof level), the actual seismic weight, not including the weight of the CLT
walls themselves, was estimated as 391 and 400 kN for the floor and roof, respectively.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1702 WICHMAN et al.

F I G U R E 5 Two-story test building: (A) photo, (B) CLT rocking wall elevation view, (C) building elevation view, (D) roof plan view, and
(E) floor plan view

3.2 Gravity framing and diaphragm

The gravity frame, designed in accordance with the US 2015 National Design Specification for Wood Construction,12 con-
sisted of glulam beams and eight glulam columns. The four inner columns (columns C1 in Figure 5C) were continuous
through the diaphragm, demonstrating balloon framing. The outer columns (columns C2 in Figure 5C) were separated by
the floor diaphragm, demonstrating platform framing. The connections between the beams and columns and at column
bases utilized vertically slotted details to allow free rotation and minimize damage to columns, beams, and joints under
large lateral drifts.
Also shown in Figure 5, the more flexible first-floor diaphragm was 3-ply CLT, while the roof diaphragm was 5-ply CLT
with a 57 mm concrete composite deck. The spans between the beams supporting the diaphragm were designed to satisfy
deflection and vibration requirements for the design office occupancy. The floor and roof diaphragms were designed to
be damage-free under the planned seismic excitations and the differing stiffness of each level was intentionally a study
parameter as discussed in Barbosa et al.7 Figure 5D and E show the plan views for the roof and floor diaphragms and show
the orientations of the beams and CLT diaphragm panels tested on each level.

3.3 Post-tensioned rocking CLT walls

The seismic force resisting system was designed to meet the seismic demands computed per ASCE 7–1013 for a class B soil
site in San Francisco, California. A seismic force reduction factor (R) of 6, an importance factor of 1.0, and an approximate
period per ASCE 7–10 were used to compute equivalent lateral force demands used in the design. The design spectral
response acceleration parameter at short periods (SDS ) and at a period of 1 second (SD1 ) were 1.06 and 0.34 g, respectively,
and the approximate fundamental period (Ta ) was 0.20 s.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1703

TA B L E 1 CLT wall panel dimensions and assumed material properties for design and modeling
bw (m) Lw (m) hw (m) Ew (MPa) Gw (MPa) fy,clt (MPa) εs,clt (m/m) εcr,clt (m/m)
0.17 1.52 7.32 8536 552 25 0.0056 0.0375

The walls were designed such that the ELL moment, Mell , could resist the design moment corresponding to seismic
demands. Mell was calculated using Equation (2), assuming a compression contact length, c, equal to 3Lw /8 with a linear
stress distribution in the CLT, initial PT bar forces, and fully yielded UFPs.
The full moment-rotation behavior of the coupled wall was also approximated to check a series of performance objec-
tives. This behavior was approximated using the cross-section analysis procedure and the monolithic beam analogy, ini-
tially developed by Pampanin et al.14 for precast concrete frames and adapted by Newcombe et al.15 and Ganey4 for mass
timber. The performance objectives used for the design of this test specimen were based on the performance objectives
developed by Ganey4 with some modifications. They were as follows:

1. Immediate Occupancy: no required repair of the system after a service level earthquake (SLE), defined as earthquake
intensity with 50% probability of exceedance in 30 years (43-year return period). Limited UFP yielding is allowed,
however, PT bars and CLT walls should remain elastic. System reaches peak drifts of around 1%.
2. Limited Repair: allows significant yielding of the UFPs with potential replacement and full system recentering after a
design based earthquake (DBE), defined as earthquake intensity with 10% probability of exceedance in 50 years (475-
year return-period). While UFPs can be heavily damaged and thus replaced, PT bars should not yield and CLT panels
should see minimal damage. Story drifts should be limited to 2%.
3. Collapse Prevention: limited overall damage to the system to prevent collapse after a maximum considered earthquake
intensity (MCER ), defined here as the MCER earthquake intensity from ASCE 7–10. PT bars can experience minor
yielding and wall corners can reach strains that indicate localized crushing, but damage should be limited to prevent
any major loss of strength or stiffness. Story drifts should be limited to 4%.

The four CLT wall panels were 5-ply, grade E2-M1 CLT. Each panel was balloon framed, such that the top of the walls
extended 0.61 m above the roof. The material properties and compression behavior used for the CLT panels in design
were approximated as shown in Figure 3, based on test results from previous CLT testing.10 Table 1 summarizes the wall
dimensions and the assumed CLT compression properties based on the test results.
Each wall panel was post-tensioned with four bars that spanned the entire height of the wall. The bars were Simpson
Strong-Tie, ATS high-strength, fully threaded, 19-mm diameter rods (with a net tensile area, Anet,pt , of 215 mm2 and an
elastic modulus, Ept , of 2×105 MPa). The listed yield and ultimate stresses were 634 and 827 MPa, respectively. As shown
in Figure 6B, PT bars were anchored to the top of each CLT wall panel with a fabricated steel saddle. While recording the
applied force using load cells, each bar was manually tightened to an initial force, To,pt , of 53 kN, about 40% of the yield
force. At the base of the wall, a steel post-tensioning hold down plate was welded to the steel foundation beam anchoring
the PT bars to the foundation, as seen in Figure 6C.
Also seen in Figure 6C, shear transfer angles were welded to the foundation beam at either end of the wall to transfer
shear forces from the wall panels to the foundation beam. To prevent out-of-plane movement at the wall bases, a series of
out-of-plane restraint angles were also welded to the foundation beam, against the faces of the walls.
The UFP energy dissipaters were designed to provide a minimum energy dissipation ratio, β, of 0.3 per the recommen-
dations of Christopoulous et al.16 The ratio, β, is approximated as the ratio of the idealized flag-shape damping hysteresis
area to the area of the idealized full elastic-plastic hysteresis, calculated as:
( )
𝑀𝑢𝑓𝑝 𝑛𝑢𝑓𝑝 𝑉𝑢𝑓𝑝 𝐿𝑤
𝛽= = [ ( ) ] (3)
2𝑀𝑦 2 𝑛𝑝 𝑇𝑜,𝑝𝑡 + 𝑊 𝑑

where Mufp , is the moment due to the UFPs in the system and My is the idealized yield moment in the system.17 For this
design, My was taken as the ELL moment, Mell , ignoring the contribution of the UFPs. Figure 6D shows one of the UFPs
used to couple two CLT panels to form each wall. After initial post-tensioning of the walls, bolts were used to attach the
UPFs to steel saddles that were anchored to the wall panels. The UFP properties, including dimensions and the elastic
modulus, 𝐸𝑢𝑓𝑝 , and yield stress, 𝑓𝑦,𝑢𝑓𝑝 , of the steel used are summarized in Table 2.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1704 WICHMAN et al.

F I G U R E 6 CLT rocking wall


connection details: (A) wall-to-diaphragm
shear transfer connection and out-of-plane
bracing; (B) top of wall PT wall saddle
connection; (C) base of wall shear transfer,
bracing, and PT hold down connection; and
(D) UFP energy dissipater connection

TA B L E 2 UFP dimension and material properties


bu (mm) tu (mm) Du (mm) Eufp (MPa) fy,ufp (MPa)
5
114 9.5 92.1 2×10 414

TA B L E 3 Dimensions and properties of diaphragm-to-wall shear key transfer connection


Level wkey (mm) tkey (mm) Lkey (mm) Ekey (MPa)
Roof 67.5 44.5 416 2×105
Floor 73.0 22.2 416 2×105

The rocking wall lateral system connected to the diaphragm using the vertically slotted shear key connection detail
shown in Figure 6A. Originally, developed for the Framework project in Portland, OR,18 the connection transferred shear
forces between the diaphragm and the rocking shear walls while keeping the diaphragm level by allowing uplift of the wall
panels relative to the diaphragm. As seen in Figure 6A, a rounded cantilevered steel shear key (width, wkey and thickness,
tkey ) was inserted into a vertically slotted hole to create a slotted pin connection allowing vertical and rotational movement
to decouple the diaphragm from the rocking walls. To reduce resistance at the interface in the vertical direction, the shear
key was wrapped in a thin Teflon sheet. One end of the shear key was bolted to a steel wing plate to transfer load from
the shear key to the diaphragm. The shear key cantilevered a length, Lkey , measured from the centroid of the wall to the
edge of the wing plate. A 45-degree timber screws and washers anchored the wing plate to the CLT diaphragm. Also seen
in Figure 6A, collector plates, welded to the wing plate, ran along the width of the diaphragm (parallel to the wall faces).
Timber screws anchored the collector plates to the diaphragm. The connection was designed based on the estimated
rocking wall capacity at 4% drift with an additional safety factor of 1.5. Table 3 summarizes the properties of the shear
keys used on the roof and floor level. In addition, adjacent to the shear-transfer connection, a series of angles provided
out-of-plane bracing as shown in Figure 6A.

4 TESTING PROGRAM

Prior to testing, a white noise excitation was run to obtain the approximate first mode elastic period of 0.9 s.5,24 Four
ground motion records from the NGA West PEER ground motion database19 were then scaled to represent the three
hazard levels (SLE, DBE, and MCER ) used to establish the performance objectives described previously. For each hazard
level, the ground motion records were scaled such that the average of the spectra did not fall below the uniform hazard
spectra or response spectra at 0.9 s, the approximate first mode fundamental period.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1705

TA B L E 4 Ground motion testing sequence


PEER-NGA Ground Motion Record
Information
Station RSN- Hazard Target Effective Effective Effective Sa
Test Event Name Name Component Level SF SF PGA (g) @ 0.9 sec (g)
1 Loma Prieta Capitola 752-2 SLE 0.42 0.36 0.16 0.15
2 Loma Prieta Capitola 752-2 SLE 0.44 0.38 0.18 0.16
3 Northridge Canoga Park 959-2 SLE 0.28 0.25 0.19 0.18
4 Superstition Hills Poe Road 725-2 SLE 0.40 0.37 0.13 0.12
5 Northridge Canoga Park 959-2 DBE 1.00 0.99 0.53 0.69
6 Northridge Canoga Park 959-2 DBE+ 1.06 1.13 0.52 0.74
7 Imperial Valley Delta 169-1 SLE 0.50 0.42 0.13 0.21
8 Northridge Canoga Park 959-2 DBE+ 1.06 1.13 0.53 0.74
9 Loma Prieta Capitola 752-2 DBE 1.21 1.16 0.52 0.49
10 Superstition Hills Poe Road 725-2 DBE 1.42 1.41 0.44 0.42
11 Loma Prieta Capitola 752-2 MCER 1.37 1.32 0.62 0.57
12 Northridge Canoga Park 959-2 MCER 1.32 1.31 0.73 0.91
13 Superstition Hills Poe Road 725-2 MCER 1.98 2.06 0.63 0.63
14 Northridge Canoga Park 959-2 MCER ×1.2 1.60 1.57 0.85 1.11

FIGURE 7 Effective spectral acceleration spectra of (A) SLE, (B) DBE, and (C) MCER level ground motions

Summarized in Table 4, the specimen was subjected to fourteen ground motion records, selected from the group of
scaled motions. The target scale factor is the intended scale factor for the ground motion file, while the effective scale
factor is the average ratio of the output response spectra to the unscaled input response spectra between the periods of
0.4 and 2 s. The difference in these two factors results from inherent error in the shake table. The effective peak ground
acceleration (PGA) and the spectral acceleration at a period of 0.9 s are taken from the output ground motion files. Note
that tests 6 and 8 used the Northridge motion scaled to be slightly larger than DBE and was repeated back-to-back to
demonstrate the ability of the building to withstand multiple strong motions without the need for repair between motions.
The PT bars did not yield during any MCER level motions, so the Northridge MCER level motion was scaled by a factor of
1.2 for test 14 to study the response of the building with yielded PT bars.
Figure 7A and B show the target uniform hazard spectra for the SLE and DBE hazard levels respectively, and Figure 7C
shows the MCER response spectra. Each figure also includes the response spectra for the effective ground motions and
their average response spectra. In Figure 7B, tests 6 and 8 are not included in the calculation of the average DBE hazard
level because they are slightly larger than DBE. Similarly, test 14 was not included in the calculation of the average spec-
trum for motions scale to the MCER hazard level because it was scaled to be 1.2 times the MCER spectrum at the building’s
period. As shown, the average spectral acceleration of each ground motion set at the building’s approximate period (0.9
s) exceeds the target hazard level spectral accelerations. This is because the effective ground motions recorded from the
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1706 WICHMAN et al.

F I G U R E 8 Wall base and foundation beam, (A) photo of gap at base of the wall panel and the foundation beam at the end of testing, (B)
yielded foundation beam schematic elevation view, and (C) cross-section view

shake table were slightly larger than the input motions and because the smallest ground motion in the scaled set was not
run.

4.1 Experimental observations

The overall response of the structure was symmetric, both coupled walls performed almost identically, and displacements
across the diaphragm indicated little torsion, as intended in the design. In general, minimal damage to the structure was
observed and the walls met all design performance objectives with respect to drift, PT bar yielding, UFP yielding, and
damage to the CLT at the base of the wall.5,24 The walls performed better than expected, with no PT bar yielding observed
until larger than MCER level ground motions were run. There was no major structural damage or crushing at the rocking
corners of the walls during any of the tests.
Figure 8A shows an image of one wall panel corner; a gap is notable between the wall toe and the foundation beam. After
removing the walls at the end of testing, it was determined that this gap was a result of both foundation beam deformation
and CLT deformation, with the former contributing more substantially. Figure 8B shows an exaggerated elevation view
schematic of the yielded foundation beam and Figure 8C shows the corresponding section view of the foundation beam.
The permanent vertical deformation at the corners of the panels, 𝑑𝑓 , ranged from 6.9 to 12.2 mm, and the length over which
this deformation occurred, 𝑙𝑓 , ranged from 203 to 356 mm. Welding the thick PT anchorage plates to the foundation beam
at the centerline of each wall panel effectively stiffened the foundation beam in these locations. As a result, this portion of
the foundation beam saw no permanent deformations and elastic deformations were not observed in video footage. It is
assumed that these portions of the foundation beam remained essentially rigid while the corners were flexible as shown
in Figure 8B.
Although the permanent deformation after every test was not measured, the gaps observed in Figure 8A appeared early
on during the testing sequence and gradually increased in size throughout testing. The flexibility of the foundation beams
is believed to have altered the behavior of the specimen from the designed case with a rigid foundation. The foundation
flexibility observed is unique to this test and a more rigid foundation would be expected in actual buildings.

5 NUMERICAL MODEL

Two numerical models were developed using OpenSees20 and built upon techniques presented in Ganey.4 While the tech-
niques presented in Ganey4 have been previously validated using cyclic loading test results, this study aims to also validate
them for nonlinear dynamic time history analyses. The first model included the flexibility of the foundation beam and is
intended to replicate the test results and verify the modeling techniques. The second model replaces flexible foundation
beam with a rigid foundation boundary condition and is intended to predict the response of the specimen had it been
tested with a more rigid foundation. Both models were two dimensional, representing one of the coupled walls in the test
specimen, with half the gravity system included and half the mass. Figure 9 shows a schematic of the numerical model
including foundation flexibility and conceptual behaviors of various component models used within the model.
The PT bars were modeled using corotatinal truss elements that connected to a fixed node at the base and to the end
of a cantilevered rigid element at the top of the wall representing the PT offset from the centerline of the wall. A bilinear
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1707

FIGURE 9 Numerical model schematic and material models used to model the two-story specimen

hysteretic material model with damage (ElasticPPGap material in OpenSees) limited the element behavior to tension only
and allowed for damage accumulation after yielding (shown in Figure 9B). An initial strain wrapper (InitStrainMaterial in
OpenSees) was applied to simulate prestressing in the elements. To correct for elastic wall shortening with application of

the initial PT stress, a higher initial PT force (𝑇𝑜,𝑝𝑡 ) is applied in the model to ensure the target PT force (𝑇𝑜,𝑝𝑡 ) is achieved.
The larger applied PT force is calculated as:
( )
∗ 𝑘𝑤
𝑇𝑜,𝑝𝑡 = 𝑇𝑜,𝑝𝑡 (4)
𝑘𝑤 − 𝑘𝑝𝑡

where 𝑘𝑤 is the elastic stiffness of the wall calculated as 𝐴𝑤 𝐸𝑤 ∕ℎ𝑤 and 𝑘𝑝𝑡 is the elastic stiffness of the PT bars calculated
as 𝐴𝑝𝑡 𝐸𝑝𝑡 ∕ℎ𝑤 .
Each UFP was modeled using a vertically orientated zero-length spring with a uniaxial Giuffrè-Menegotto-Pinto steel
material model with isotropic strain hardening (Steel02 in OpenSees) as shown in Figure 9C. A yield force of 23.3 kN and
a stiffness of 4.8 kN/mm were used, calculated using equations from Kelly et al.21 and Baird et al.,9 with properties from
Table 2. The UFPs were located at the midpoint between the two wall panels and rigid elements connected each end of
the UFP spring to each of the wall element at the same vertical position.
A series of elastic beam-column frame elements (ElasticTimoshenkoBeam element in OpenSees) that included axial,
flexure, and shear deformations modeled the elastic portion of the CLT rocking walls. The CLT properties from Table 1
were used for these elements.
The inelastic compressive deformation of the CLT and the rocking behavior at the base of the panels was modeled using
a multispring contact element, initially developed by Spieth et al.22 for prestressed concrete structures. The wall base
multispring element consisted of 40 parallel zero-length springs distributed along the length of the wall using a Labatto
Integration method. The top of each spring connected to the base of the wall beam-column element with a horizontal
rigid element. For the rigid foundation model, the bottom of each spring was fixed. For the flexible foundation model,
the bottom of each spring within a distance of 𝑙𝑓 from the corners of each wall panel was connected to an additional
zero length spring modeling the foundation beam flexibility. The base of the remaining springs near the centers of each
wall panel were fixed, modeling the portion of the foundation that was assumed to be rigid. Additionally, two stiff shear
transfer springs were attached diagonally to the outer multispring and foundation beam springs to transfer shear without
significantly inhibiting rocking action.
Each zero-length spring at the wall base is assigned the compression-only hysteretic material model shown in Figure 9D.
The compression-only portion of the material model simulated the rocking behavior while the hysteretic properties sim-
ulated the CLT compression behavior. To transform the CLT stress-strain compression behavior shown in Figure 3 to
a force-deformation behavior needed for zero-length springs (Figure 9D), a plastic hinge length, lp , was chosen. In this
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1708 WICHMAN et al.

TA B L E 5 Initial gap included in the model


Test numbers 𝒅𝒇,𝒊 (mm)
1–2 0.0
3–5 1.3
6–11 2.5
12–14 5.1

model, a plastic hinge length of 2bw was assumed in accordance with Akbas et al.8 An overall contact stiffness, Ks , was
determined for the entire wall base (all multispring elements representing the CLT) as:

𝐴𝑤 𝐸𝑤
𝐾𝑠 = (5)
𝑙𝑝

where Aw is the cross-sectional area of the wall panel equal to the product of 𝑏𝑤 and 𝐿𝑤 . Wall dimensions and material
properties can be referenced in Table 1. Referring to Figure 9D, each individual spring stiffness, ks , was a weighted portion
of the overall contact stiffness, Ks , based on the Labatto Integration method. The product of the CLT panel yield stress and
the Labbatto weighted area of each spring determined the yield strength of each spring, Fy,s . Similarly, the product of the
respective strains, ∈s and ∈cr , and the plastic hinge length, 𝑙𝑝 , determined the splitting deformation, Δs , and the crushing
deformation, Δcr .
The addition of the wall base multispring elements increases the axial flexibility of the wall. Although small and unlikely
to affect the performance dramatically, a simple truss element, spanning the length of the CLT beam-column wall ele-
ments, can be added to increase the area of the wall and compensate for the reduced stiffness. The truss element has an

elastic material model, with elastic modulus 𝐸𝑤 and an area, 𝐴𝑤 calculated as:


𝑙𝑝
𝐴𝑤 = (6)
ℎ𝑤 − 𝑙 𝑝

In the flexible foundation model, the foundation beam was assumed to be undamaged at the beginning of the first two
ground motions. Subsequently, an initial permanent deformation of the foundation beam was assumed at the beginning
of the tests from accumulated foundation beam damage. Thus, a compression gap was introduced to the CLT wall base
springs in the model. The size of the gap decreased linearly along the flexible foundation portions of the beam with the
corner springs having an initial gap length of 𝑑𝑓,𝑖 and the springs located at a distance of 𝑙𝑓 from the corners having no
initial gap. A flexible foundation length (𝑙𝑓 ) of 0.61 m was used for all tests. The gap values (𝑑𝑓,𝑖 ) used for each test are
shown in Table 5 and are based on observations made during the testing. As shown in Figure 9D, for the flexible foundation
model, a compression only elastic-perfectly plastic material with a gap (ElasticPPGap in OpenSees) was used to achieve the
initial stiffness of the CLT and account for the initial gap. Although this material model cannot capture the deterioration,
the CLT remained elastic, so it did not affect the behavior.
A multilinear material model (Steel01 in OpenSees) modeled the foundation beam flexibility, as shown in Figure 9E.
The approximated stiffness of the foundation beam springs was calculated assuming the top flange of the double webbed
beam shown in Figure 8C acted as a fixed-fixed beam between the two webs and the base of the wall imposed a uniformly
distributed load (along a length equal to the panel thickness, bw ) at the center of the beam. The thickness of the top flange
(𝑡𝑓 ) was 15.9 mm and the webs were spaced at a distance (𝑑𝑓 ) of 138 mm. The elastic stiffness of the beam was calculated
for the flange dimensions and loading, and the yield force was approximated using plastic analysis. The stiffness (kb ) and
yield force (Fy,b ) of each spring was calculated as a weighted portion of the total stiffness and yield force using the same
Labatto Integration distribution as the rocking wall base multispring element. A yield stress of 414 MPa was assumed for
the steel beam. Note, the methods used to justify the flexible foundation beam material are custom for this test, however,
the multispring approach could be used for other forms of flexible foundations.
The gravity columns were modeled with two continuous elastic beam column elements with cross-sectional areas repre-
sentative of the continuous and platform columns and moment of inertias corresponding to only the continuous, balloon
framed columns. Equivalent gravity loads and seismic masses were applied to each gravity column at each floor level.
Rigid elements connected the gravity columns to the wall panels at each floor level simulating a rigid diaphragm. As dis-
cussed by Hasani et al.,23 the rigid diaphragm model assumption can predict the fundamental mode behavior and peak
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1709

F I G U R E 1 0 Comparison of the roof


drift time history response from experimental
results, the flexible foundation numerical
model, and the rigid foundation numerical
model for (A) Test 1, SLE Loma Prieta, (B)
Test 10, DBE Superstition Hills, and (C) Test
12, MCER Northridge

story drifts well, but the flexibility in the diaphragm should be included to predict the higher frequency motion and floor
accelerations.
The connection between the diaphragm and walls was modeled with a zero-length spring. To model the elastic flexibility
of the wall-to-diaphragm connection, the material properties assigned to the horizontal degree of freedom of the zero-
length spring were that of a cantilever beam with the dimensions of the shear key listed in Table 3. The spring had zero
stiffness in the vertical and rotational degrees of freedom to allow for uplift and rocking.

6 DISCUSSION OF EXPERIMENTAL AND ANALYTICAL RESULTS

The following section presents results from the flexible foundation model and rigid foundation model with the exper-
imental results. The flexible foundation model is intended to match the experimental results and verify the modeling
techniques as it more correctly models experimental boundary conditions. The intention of also presenting the results of
the rigid foundation model is not to match the experimental results, but to predict how the specimen would have behaved
with the as designed rigid foundation boundary condition. First, a discussion comparing the experimental results to the
numerical model including foundation flexibility will be presented. Then, the experimental results will be compared to
the rigid foundation model to study how the structure’s behavior would have changed had it been tested with a rigid
foundation boundary condition. Finally, the results from the rigid foundation model were assessed to determine if the
structure would have met all design performance objectives.

6.1 Comparison of numerical model including foundation flexibility with


experimental results

Experimental drift results were determined by averaging and double integrating recordings from seven accelerometers
located on each diaphragm level. As discussed in Pei et al.,5 first-mode response dominated such that all interstory drifts
were similar. The numerical model showed similar results, thus only the roof drifts are presented and discussed. Figure 10
compares the time history roof drift response from the experimental results with the flexible foundation numerical model
for three of the tests, each at a different intensity level. As shown, the numerical model very accurately replicated the period
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1710 WICHMAN et al.

F I G U R E 1 1 Comparison of peak roof drift values from the experimental results, the flexible foundation numerical model, and the rigid
foundation numerical model

F I G U R E 1 2 Comparison of the hysteretic response from experimental results, the flexible foundation numerical model, and the rigid
foundation numerical model for (A) Test 1, SLE Loma Prieta, (B) Test 10, DBE Superstition Hills, and (C) Test 12, MCER Northridge

and overall behavior, but under predicted the peak drift values. The maximum absolute roof drift for the experimental and
numerical results for all 14 tests are summarized in Figure 11 which plots the spectral acceleration of each ground motion
at the approximate period of the building (0.9 s) versus the peak roof drift value. The figure shows a clear positive trend
between the increasing spectral acceleration and increasing drift ratios. It also shows that the numerical model with
foundation flexibility underestimates the peak drifts.
Assuming a rigid diaphragm, experimental base shear results were approximated by calculating the inertial force at
each floor by multiplying the average of the accelerometer readings on each story by the estimated mass on each story.
Figure 12 shows the base shear versus roof drift hysteretic response for the experimental and numerical results for the
same three tests shown in Figure 11. Relatively good agreement of the overall structure stiffness is shown, but the base
shear values are slightly underestimated with the numerical model. Again, Figure 13 summarizes the peak base shear
values obtained from each test plotted against the spectral acceleration from the recorded table motion at the building’s
measured first natural period. Here, the experimental values are consistently larger than the numerical results. Note that
results for a single coupled wall are shown in Figures 12 and 13.
The PT bar forces were measured using load cells. Figure 14 shows the PT bar force normalized by the bar yield force
(taken as the manufactures specified yield stress times the tensile area) versus roof drift for an SLE, DBE, and MCER level
ground motion. For each test, the figure shows the four PT bar locations along the face of the coupled wall, as denoted
by the graphics on each plot. A plot of the peak PT force for each test versus the ground motions spectral acceleration
at the building’s period is plotted in Figure 15. As seen in Figure 14, the general behavior of the PT bars is well predicted
by the numerical model, but also underestimates peak PT force values. The underestimated peak PT force values with
the numerical model is expected because the roof drift values are also underestimated, meaning the walls do not lift as
much and the PT bars elongate less than in the tests. Further, the flexibility of the foundation beam resulted in downward
sinking movement of the walls when rocking, decreasing bar elongation.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1711

F I G U R E 1 3 Comparison of peak base shear values for a single wall from the experimental results, the flexible foundation numerical
model, and the rigid foundation numerical model

F I G U R E 1 4 Comparison of PT force yield ratio versus roof drift response for the experimental results, the flexible foundation numerical
model, and the rigid foundation numerical model for (A) Test 1, SLE Loma Prieta, (B) Test 10, DBE Superstition Hills, and (C) Test 12, MCER
Northridge

String potentiometers measured UFP deformation, as shown in Figure 6D. A ratio of peak to yield displacement was
used to quantify a measure of UFP ductility demand. Figure 16 shows the spectral acceleration at the building’s period
versus peak UFP yield displacement ratio for all tests. As shown in the figure, the UFPs yielded in almost every test and
the energy dissipation increased with increasing ground motion intensity, as expected. Because the numerical model with
foundation flexibility under predicts roof drift, it also under predicts the UFP yield displacement ratio.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1712 WICHMAN et al.

F I G U R E 1 5 Comparison of peak PT force yield ratios from the experimental results, the flexible foundation numerical model, and the
rigid foundation numerical model

F I G U R E 1 6 Comparison of peak UFP yield displacement ratios from the experimental results, the flexible foundation numerical model,
and the rigid foundation numerical model

Linear potentiometers installed at the corners of the wall panels (Figure 6C) were used to investigate positive uplift
rotations and negative compression rotations at the wall base. The vertically orientated potentiometers were anchored to
the portion of the foundation beam flanges outside of the webs (the portion of the foundation beam that did not deform).
The downward deformation recorded by these potentiometers was intended to measure compression deformations of
CLT. However, because the deformations from foundation beam flange flexibility were substantially larger, the recorded
deformations were assumed to be fully attributed to foundation beam deformations. The base rotation was approximated
by dividing the recordings by the CLT wall panel length (𝐿𝑤 ). Figure 17 plots a time history calculated from one of the
potentiometers. Similarly, the numerical results are calculated by dividing the displacement recorded by the top node of
the outermost spring in the wall base multispring element by the length of the CLT wall panel (𝐿𝑤 ). Because the springs
at the base of the numerical model are all zero-length, this recorded deformation includes the uplift and deformations of
the CLT wall panel and foundation beam.
Because the numerical model underestimates the peak drift values it is logical that the rotations in Figure 17 are
also underestimated, however, there is good agreement in the general shape of the response. While uplift rotations
are underestimated by the model, the negative or compressive deformation are slightly overestimated, indicating that
the material model used for the foundation beam flange behavior in the numerical model may have been too flexible.
Figure 18 summarizes the peak uplift rotations and peak compressive rotations observed in each test. Again, this
figure shows that the numerical model with foundation flexibility underestimates uplift rotations and overestimates
compressive rotations. The overestimation of the compressive rotations could partially explain the underestimation of the
uplift rotations (and similarly the drifts and PT forces) since the wall is settling into the foundation beam more instead
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1713

F I G U R E 1 7 Comparison of CLT wall panel base rotation from experimental results, the flexible foundation numerical model, and the
rigid foundation numerical model for (a) Test 1, SLE Loma Prieta, (b) Test 10, DBE Superstition Hills, and (c) Test 12, MCER Northridge

F I G U R E 1 8 Comparison of peak wall base (a) uplift and (b) compressive rotations from the experimental results, the flexible
foundation numerical model, and the rigid foundation numerical model

of lifting and rocking up. However, apart from peak values, the overestimation of the downward rotations appears to be
smaller than the overestimation of the uplift rotations, thus only partially explaining the differences.
Due to the unforeseen flexibility in the foundation beam, instrumentation during testing did not accurately measure
axial deformations in the CLT at the wall base. However, there was no visual damage to the base of the walls after demoli-
tion of the structure; the bases of the walls were largely square. Similarly, in the numerical model with foundation flexibil-
ity, the deformations of the wall base multispring element springs remained below the yield deformation (Δ𝑦 ), calculated
by dividing the yield force of each spring (𝐹𝑦,𝑠 ) by the stiffness of each spring (𝑘𝑠 ).
Overall, the presented numerical model including foundation flexibility does a good job of predicting the response of the
tested structure and thus similar modeling techniques can be used to predict the response of structures with comparable
rocking wall systems with confidence.

6.2 Comparison of numerical model without foundation flexibility with experimental


results

Because the foundation flexibility was unexpected, it is important to quantify impact of the foundation flexibility on the
overall behavior and to explore if the design would still meet performance objectives with the intended rigid foundation
behavior. Thus, the rigid foundation numerical model was created as discussed above.
Figure 10 includes results from the numerical model with the rigid foundation. In comparison to the flexible foundation
model that was intended to replicate test results, the change in foundation boundary condition does have a significant
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1714 WICHMAN et al.

F I G U R E 1 9 Rigid foundation numerical model results only; spectral acceleration at the building’s period for all tests versus the
percentage of the panel length exceeding the CLT damage state of yielding, splitting, and crushing

effect on the overall response. The period appears to be shorter with the rigid foundation as a result of the increased
system stiffness. The increased stiffness also results in smaller roof drifts, as seen in Figure 11.
The impact of the increased stiffness with the rigid foundation model is also clearly shown in the hysteretic response
shown in Figure 12. It is also interesting that the idealized flag shape response of rocking systems is more apparent in the
response for the rigid foundation model. With a rigid foundation, major hysteretic damping does not occur until after the
ELL when the wall begins to uplift, and the UFPs experience large deformations. However, with the flexible foundation
beam, nonlinearity in the foundation occurs prior to the ELL, resulting in increased damping. This is clear from Figure 12A,
an example of an SLE test. For the rigid foundation model, the response is bilinear, the peak response has just exceeded
the ELL, and there is minimal damping. In comparison, for the flexible foundation model, while the response is more
linear than the comparable DBE and MCER response (Figure 12B and C, respectively) there is an increase in damping
from the foundation beam deformation. Additionally, the increased system stiffness in the rigid foundation model results
in increased peak base shear values as shown in Figure 13.
Because the rigid foundation model has smaller drifts, a decrease in peak PT forces may be expected, however, the rigid
foundation model resulted in increased peak PT bar forces as shown in Figure 15 because the point of uplift shifts toward
the compression toe of the wall panels, resulting in more elongation of the PT bars for a given roof drift when compared
to the flexible foundation model. In the flexible foundation model, as the walls rocked the base of the wall sunk into the
beam, flattening the response such that PT bar forces remained constant at low drifts, despite increasing drifts, as shown
in Figure 15.
With the rigid foundation model, the UFPs still yielded during smaller hazard level earthquakes, as shown in Figure 16.
However, because the drifts were smaller for the rigid foundation model, the peak UFP deformations were also slightly
smaller. This resulted in slightly less damping as a result of UFP behavior in the rigid foundation model.
The base rotation response histories shown in Figure 17 and the peak uplift rotations summarized in Figure 18A indicate
that the rigid foundation model had slightly higher uplift rotations than the flexible foundation model. The decrease in
drifts with the rigid foundation model would typically result in decreased uplift rotations, however, since the point of uplift
of the wall shifted toward the compression toe of the wall panels in the rigid foundation model instead of sinking into the
foundation beam uplift rotations increased. The summarized compression rotations in Figure 18B show a major decrease
in compressive base rotations in the rigid foundation model. While the compressive rotations were almost entirely a result
of foundation beam deformations in the flexible foundation model, the compression rotations in the rigid foundation
model are solely the result of deformations in the CLT.
The CLT deformations observed in the rigid foundation model resulted in predicted damage to the CLT base. Because
no CLT damage was observed in the experiments or in the numerical model with the flexible foundation, Figure 19 only
summarizes CLT damage results for the rigid foundation model. Figure 19 plots the spectral acceleration at the building’s
approximate period versus the percentage of damaged panel length. For each damage state, the length of the panel base
over which spring deformations exceed the respective deformation limit (Δ𝑦 for yielding, Δ𝑠 for splitting, and Δ𝑐𝑟 for
crushing), was recorded. Of the four wall panel corners, Figure 19 summarizes the maximum length as a percentage of
the total wall panel length (𝐿𝑤 ). While the strongest motions experienced some CLT yielding and splitting, CLT crushing
was not observed in the simulations of any of the tests with the rigid foundation model.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1715

6.3 Performance of the numerical model without foundation flexibility with respect to
design criteria

The CLT rocking wall system met all design performance objectives during testing.24 However, it is clear that the flexibility
in the foundation beams altered the performance of the specimen. Because the specimen was designed to rock on a rigid
foundation and because realistic buildings would have rigid foundations, it is important to assess if performance objectives
would have still been met had it been tested with a rigid foundation. The building was designed to meet three performance
objectives: (1) immediate occupancy after SLE earthquakes, (2) limited repair after DBE earthquakes, and (3) collapse
prevention after MCER earthquakes. To meet each of these three performance objectives, target drifts and damage criteria
had to be met for the UFPs, the PT bars, and the CLT at the wall base.
Because many of the motions exceeded the target spectral acceleration of the intended hazard level at the building’s
period of 0.9 s, performance objectives were assessed by looking at the general trends instead of performance at each
individual ground motion. For example, ground motions 6 and 8 were scaled to be DBE level earthquakes; however, with
a spectral acceleration of 0.74 g at the building’s 0.9 s period, they are most likely more representative of an MCER ground
motion which has a target spectral acceleration of 0.60 g at 0.9 s.
To meet the drift criteria of the performance objectives, SLE, DBE, and MCER level earthquake should remain under
1%, 2%, and 4%, respectively. As seen in Figure 11, the drifts for the numerical model with the rigid foundation satisfy these
criteria for all ground motions. Interestingly, the largest ground motion (that had a spectral acceleration 85% larger than
the target MCER ground motion) only had a peak roof drift of 3.2%, using the rigid foundation model.
The design performance objectives allow for initial UFP yielding under SLE earthquakes and the UFPs can undergo
large deformations beyond yield during DBE and MCER level earthquakes. The intent is to replace the damaged UFPs
after DBE and MCER level earthquakes but should not need replacement after SLE level earthquakes. The peak UFP yield
displacement ratios summarized in Figure 16 show that UFP criteria is met for all ground motions for the rigid foundation
numerical model. Only one earthquake within the SLE region caused UFP yielding.
With target performance objectives, the PT bars were designed to remain elastic during SLE and DBE earthquakes and
were allowed to yield during MCER earthquakes. The rigid foundation numerical results in Figure 15 show that PT bar
yield criteria was met for all performance objectives. Note that while both the rigid foundation numerical model results
and the experimental results met PT bar performance objectives, the rigid foundation results are closer to the limits of
these performance objectives, but also are much closer to the intended design performance.
Finally, to meet performance objectives, the CLT at the base of the wall has to remain elastic during SLE earthquakes,
should only have some damage during DBE earthquakes, and can have repairable damage under MCER level earthquakes.
For the rigid foundation numerical model, Figure 19 shows that ground motions at the SLE hazard level resulted in no
CLT yielding, ground motions at the DBE hazard level resulted in some yielding and a small amount of splitting, and
the ground motions in the MCER region saw significant yielding and minor splitting. However, no CLT crushing was
observed in any of the ground motions in the simulations with the rigid foundation model. These would all be considered
to meet performance objectives. Again, note that while performance objectives are met for both the flexible foundation
and rigid foundation case, the flexible foundation model predicted zero damage and the rigid foundation model predicted
significantly more CLT damage.

7 RECOMMENDATIONS FOR FUTURE RESEARCH

The design procedure and modeling methodology presented have limitations that should be addressed in future research.
Future research is needed to determine the effects of three-dimensional rocking to determine how these rocking walls
perform when rocking on their corners and if the base rocking multispring methodology accurately predicts the response.
Additionally, future testing is needed to determine if adjustments need to be made during the design of modeling of rock-
ing timber shear walls in tall buildings. The plastic hinge length used to estimate CLT crushing at the base of the wall
is based on limited testing, and should also be considered in future research, specifically when instrumenting for future
testing. Finally, it is recommended that modeling simplifications be explored and their impact on accurately predicting
performance be assessed. This would consist of investigating the use of software common in design practice and is neces-
sary for wider adoption of the system.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
1716 WICHMAN et al.

8 SUMMARY AND CONCLUSIONS

Results from the two-story NHERI TallWood Project showed that post-tensioned CLT rocking walls can provide great seis-
mic performance while remaining essentially damage-free. The walls were designed to meet three performance objectives:
(1) immediate occupancy after SLE earthquakes, (2) limited repair after DBE earthquakes, and (3) collapse prevention after
MCER earthquakes. To meet each of these three performance objectives, target drifts and damage criteria had to be met for
the UFPs, the PT bars, and the CLT at the base of the rocking wall. The CLT walls met all design performance objectives
while testing the building with fourteen ground motions, scaled to range from SLE hazard levels to 1.2 times the MCER
level hazard. Although the wall system was essentially undamaged after testing, the foundation beams supporting the
CLT wall panels experienced unexpected flexibility and permanent deformations.
This paper presented a numerical model for the CLT rocking walls in the two-story test specimen. Base rocking was
modeled through distributed springs at the wall base and the contribution of foundation flexibility was included through
additional springs below the base rocking springs. Overall, the model showed good agreement with the test results and
offered a good prediction of the overall behavior and period. The numerical model underestimated drifts, resulting in
lower PT bar forces, lower UFP deformations, and lower base uplift rotations. Additionally, the numerical model slightly
overestimated compressive base rotations, indicating that the assumed foundation model was slightly too flexible. Like
test results, the numerical model indicated no damage to the base of the CLT rocking walls.
Because the test structure was not designed to have a flexible foundation and because a typical building would be
designed with a rigid foundation, an additional numerical model was created with a rigid foundation. A comparison of
the rigid foundation numerical model and the flexible foundation numerical model showed that the differing boundary
conditions had significant effects on overall specimen behavior. As expected, the rigid foundation greatly increased system
stiffness, decreased the first mode period, and decreased drifts. Although drifts decreased, the increased stiffness due to
movement of the uplift point closer to the compression toe of the wall panels resulted in larger PT bar forces relative to
those observed in the test and predicted using the flexible foundation model. Most importantly, the compressive rotations
at the base of the wall panels decreased significantly without the foundation beam flexibility, resulting in much higher CLT
strains at the base of the wall. Under the rigid foundation boundary condition, the CLT experienced permanent yielding
and damage. Thus, it is concluded that even though the flexible foundation beam produced larger peak drifts relative to
the rigid foundation beam model, in general, that deformation protected the base of the wall from damage and resulted
in better overall performance in terms of CLT damage.
The test specimen easily met all performance objectives and performed much better than expected. Apart from reduced
roof drifts, the numerical model with the rigid foundation did not perform quite as well as it predicted considerable CLT
damage in the DBE and MCER ground motions; however, it still predicted the system would meet all design performance
objectives and the predicted performance was closer to the design intent. Because of the accurate prediction of overall
building performance between test results and the flexible foundation model results, the modeling approaches presented
here can be used as a good prediction for mass timber rocking wall systems.

AC K N OW L E D G E M E N T S
Financial support for this study was provided by the National Science Foundation through grant CMMI 1635227, 1634628
and 1634204. Any opinions, findings, conclusions, and recommendations presented in this paper are those of the authors
and do not necessarily reflect the views of the sponsors.

D A T A AVA I L A B I L I T Y S T A T E M E N T
The data that support the findings of this study are openly available in DesignSafe at https://doi.org//10.17603/ds2-zcb9-
ry11, reference number PRJ-1717

ORCID
Sarah Wichman https://orcid.org/0000-0003-0393-379X
Shiling Pei https://orcid.org/0000-0002-6458-3124

REFERENCES
1. Iqbal A. Seismic Response of Subassemblies for Multi-Storey Prestressed Timber buildings. Phd. Thesis. University of Canterbury,
Christchurch, New Zealand; 2011.
10969845, 2022, 7, Downloaded from https://onlinelibrary.wiley.com/doi/10.1002/eqe.3634 by University Of British Columbia, Wiley Online Library on [02/12/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
WICHMAN et al. 1717

2. Sarti F. Seismic Design of Low-Damage Post-Tensioned Timber Wall Systems. Phd. Thesis. University of Canterbury, Christchurch, New
Zealand; 2015.
3. Pei S, Huang D, Berman J, Wichman S. A simplified model for dynamic response prediction of post-tensioned cross laminated timber
rocking walls. Earthquake Eng Struct Dyn. 2020;50:845-862.
4. Ganey R. Seismic design and testing of rocking cross laminated timber walls. M.S. thesis. University of Washington, Seattle, WA; 2015.
5. Pei S, van de Lindt JW, Barbosa AR, et al. Experimental seismic response of a resilient 2-story mass-timber building with post-tensioned
rocking walls. J Struct Eng. 2019. http://doi.org/10.1061/(ASCE)ST.1943-541X.0002382.
6. Van Den Einde L, Conte JP, Restrepo JI, et al. NHERI@UC San Diego 6-DOF large high-performance outdoor shake table facility. Front
Built Environ. 2021;6:580333. http://doi.org/10.3389/fbuil.2020.580333.
7. Barbosa AR, Rodrigues LG, Arijit S, et al. Shake-table experimental testing and performance of topped and untopped cross-laminated
timber diaphragms. J Struct Eng. 2021;147(4):04021211.
8. Akbas T, Sause R, Ricles JM, et al. Analytical and experimental lateral-load response of self-centering posttensioned clt walls. J Struct Eng.
2017;143(6):04017019.
9. Baird A, Smith T, Palermo A, Pampanin S, (2014). Experimental and numerical Study of U-shape Flexural Plate (UFP) dissipaters. NZSEE
Conference.
10. Barbosa AR, Sinha A, Higgins C, Soti R, (2018). Structural Testing for the DR Johnson’s CLT Panels. Report No. 17-03, Oregon State Uni-
versity.
11. Ganey R, Berman J, Akbas T, et al. Experimental investigation of self-centering cross laminated timber walls. J Struct Eng.
2017;143(10):04017135.
12. AWC. National Design Specification for Wood Construction. American Wood Council; 2015.
13. ASCE. Minimum design loads for buildings and other structures, ASCE/SEI 7–10, American Society of Civil Engineers; 2010.
14. Pampanin S, Priestley MJN, Sritharan S. Analytical modeling of the seismic behavior of precast concrete frames designed with ductile
connections. J Earthquake Eng. 2001;5(3):329-367.
15. Newcombe MP, Pampanin S, Buchanan A, Palermo A. Section analysis and cyclic behavior of post-tensioned jointed ductile connections
for multi-story timber buildings. J Earthquake Eng. 2008;12(1):83-110.
16. Christopoulos C, Filiatrault A, Folz B. Seismic response of self-centering hysteretic SDOF systems. Earthquake Eng Struct Dyn. 2002;31:1131-
1150.
17. Seo CY, Sause R. Ductility demands on self-centering systems under earthquake loading. ACI Struc J. 2005;102(2):275-285.
18. Zimmerman R, McDonnel E. Framework – innovation in re-centering mass timber wall buildings. Proceedings of the 11th National Con-
ference in Earthquake Engineering. Earthquake Engineering Research Institute, Los Angeles, CA; 2018.
19. PEER. PEER NGA Database. Pacific Earthquake Engineering Research Center, University of California, Berkeley, California; 2006.
20. Mazzoni S, McKenna F, Scott M, Fenves G. Open Systems for Earthquake Engineering Simulation User Command-Language Manual –
OpenSees version 2.0. Pacific Earthquake Engineering Research Center, University of California, Berkeley, CA; 2009.
21. Kelly JM, Skiner RI, Heine AJ. Mechanisms of energy absorption in special devices for use in earthquake resistant structures. Bull N Z Soc
Earthq Eng. 1972;5(3):63-88.
22. Spieth HA, Carr AJ, Pampanin S, Murahidy AG, Mander J. Modeling of precast prestressed concrete from structures with rocking beam-
column connections. Report No. 2004-01, University of Canterbury, Christchurch, New Zealand; 2004.
23. Hasani H, Ryan KL, Wichman S, Berman J. Dynamic behavior of mass timber building with cross-laminated timber rocking walls. Earthq
Eng Struct Dyn. 2021. In Press.
24. Wichman S. Large-scale dynamic testing of rocking cross laminated timber walls. M.S. thesis. University of Washington, Seattle, WA; 2018.

How to cite this article: Wichman S, Berman JW, Pei S. Experimental investigation and numerical modeling of
rocking cross laminated timber walls on a flexible foudndation. Earthquake Engng Struct Dyn. 2022;51:1697–1717.
https://doi.org/10.1002/eqe.3634