Foxboro DCS: FBM232 Field Device System Integrator Module, 10/ 100 Mbps Ethernet, Single
Foxboro DCS: FBM232 Field Device System Integrator Module, 10/ 100 Mbps Ethernet, Single
PSS 41H-2S232
Product Specification
May 2023
https://www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished
for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or
otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
FBM232 Field Device System Integrator Module, 10/100 Mbps
Overview Ethernet, Single
Overview
The FBM232 Field Device System Integrator (FDSI) module provides a single
Ethernet interface between single-ported field I/O devices and the EcoStruxure™
Foxboro™ DCS system.
The FBM232 connects to a single 10 Mbps or 100 Mbps copper Ethernet network to
communicate with devices. The FBM232 is connected to Ethernet switches or hubs in
order to communicate with one external device or up to 64 external devices.
The general network configuration is shown in Figure 1, page 4.
Features
Key features of the FBM232 are:
• 10 Mbps or 100 Mbps Ethernet network transmission rate to/from field device
• Communicates with up to 64 field devices
• I/O software driver is downloadable from a library of available protocols
• Up to 2000 DCI block connections
• Integrates field device data into a Foxboro DCS control database using Ethernet
connectivity
• Field mounted
• Class G3 (harsh) environments.
I/O Drivers
This fieldbus module (FBM) is a generic Ethernet hardware module in which different
software drivers can be loaded. These drivers configure the FBM to recognize a
particular protocol used by the device. Several of the software drivers are standard
product offerings. Other custom drivers can be developed to meet specific needs.
These drivers are dynamically downloaded to the FBM232 with software code
specifically designed to interface with the third party device’s protocol. The
configuration procedures and the software requirements for each driver are unique to
the device(s) being integrated into the system.
Configurator
The FDSI configurator sets up the FBM232 XML based port and device configuration
files. The port configurator allows for easy setup of the communication parameters for
each port (such as, Dynamic Host Configuration Protocol (DHCP), IP addresses). The
device configurator is not needed for all devices, but when needed it configures
device specific and point specific considerations (such as, scan rate, address of the
data to be transferred, and the amount of data to be transferred in one transaction).
Operations
The FBM232 can access up to 64 devices to read or write data. From the Foxboro
DCS control station to which the FBM232 is connected, up to 2000 Distributed Control
Interface (DCI) data connections can be made to read or write data. Supported data
types are determined by the particular driver loaded on the FBM232, which converts
the data to the DCI data types listed below:
• An analog input or output value (integer or IEEE single-precision floating point)
• A single digital input or output value
• Multiple (packed) digital input or output values (packed in groups of up to 32
digital points per connection).
Thus the FBM232 can access up to 2000 analog I/O values, or up to 64000 digital I/O
values, or a combination of digital and analog values up to the maximum capacity a
user allows within the sizing guidelines of the control processor. The frequency of
access to the FBM232 data by a control station can be as fast as 500 ms. The
performance depends on each device type and the layout of data in the device.
The FBM232 collects the required data from the devices, performs the necessary
conversions, and then stores the converted data in its database for incorporation into
the Foxboro DCS plant management functions and operator displays. Data may also
be written out to the individual devices from the Foxboro DCS system.
Fieldbus Communications
The Fieldbus Communications Module (FCM100Et or FCM100E) or the Field Control
Processor (FCP270 or FCP280) interface the redundant 2 Mbps module Fieldbus
used by the FBMs. The FBM232 accepts communication from either path of the
redundant 2 Mbps module Fieldbus - should one path fail or be switched at the system
level, the module continues communication over the active path.
The DCI blocks are configured just like other Foxboro DCS control blocks. The DCI
blocks address and read/write data from/to the addressed field device.
Easy Removal/Replacement
The module can be removed or replaced without removing power.
Visual Indicators
Light-emitting diodes (LEDs) incorporated into the front of the module provide visual
indication of the module’s operational status, and the communication activity
(transmit/receive) of the Ethernet port.
Functional Specifications
Communications Bus Characteristics
• Communication Type
Ethernet
• Communication Transmission Rate
10 or 100 Mbps
• Communication Protocol
UDP/IP or TCP/IP
• IP Address
Fixed or DHCP
NOTE: For driver specific limitations on I/O Capacity and Data Types Transferred,
refer to the corresponding driver PSS or User’s Guide.
I/O Capacity
• Up to 64 devices per FBM232 maximum (number of actual devices is performance
dependent) with up to 2000 DCI connections.
Data Types Transferred
• 2-byte or 4-byte signed or unsigned integers, 4-byte IEEE single-precision floating
values, or binary values. Automatic conversion for other types as implemented in
the downloadable driver.
Fastest Allowed ECB Block Period
• 500 msec
Module Fieldbus Communicates with its associated FCM100Et, FCM100E, FCP280, or FCP270 via the
Communication redundant 2 Mbps module Fieldbus.
FBM232 Power
• Input Voltage Range (Redundant)
Requirements
24 V DC +5%, -10%
• Consumption
7 W (maximum)
• Heat Dissipation
7 W (maximum)
Regulatory Compliance, European EMC Directive 2014/30/EU
Electromagnetic
Compatibility (EMC) Meets: EN61326-1:2013 Class A Emissions and Industrial Immunity Levels
Regulatory Compliance,
• Underwriters Laboratories (UL) for U.S. and Canada
Product Safety
UL/UL-C listed as suitable for use in UL/UL-C listed Class I, Groups A-D; Division
2; temperature code T4 enclosure based systems when connected to specified
Foxboro DCS processor modules as described in the Standard and Compact 200
Series Subsystem User's Guide (B0400FA).
Communications circuits also meet the requirements for Class 2 as defined in
Article 725 of the National Electrical Code (NFPA No.70) and Section 16 of the
Canadian Electrical Code (CSA C22.1). Conditions for use are as specified in the
Standard and Compact 200 Series Subsystem User's Guide (B0400FA).
• European Low Voltage Directive 2014/35/EU and Explosive Atmospheres (ATEX)
Directive 2014/34/EU
DEMKO certified as Ex nA IIC T4 for use in certified Zone 2 enclosure when
connected to specified processor modules as described in the Standard and
Compact 200 Series Subsystem User's Guide (B0400FA).
• Marine Certification
ABS Type Approved and Bureau Veritas Marine certified for Environmental
Category EC31.
Calibration Calibration of the module is not required.
Requirements
Environmental Specifications
Operating Storage
Temperature Rev A to J: -20 to +70°C (-4 to +158°F) -40 to +70°C (-40 to +158°F)
Rev K and later: 0 to +70°C (32 to +158°F)
Relative Humidity 5 to 95% (noncondensing) 5 to 95% (noncondensing)
Contamination Suitable for use in Class G3 (Harsh) environments as defined in ISA Standard S71.04, based
on exposure testing according to EIA Standard 364-65, Class III.
Physical Specifications
Mounting The FBM232 mounts on a Modular Baseplate. The Modular Baseplate can
be mounted horizontally or vertically on a DIN rail, or mounted horizontally in
a 19-inch rack using a mounting kit. Refer to PSS 31H-2SBASPLT for
details.
Weight 284 g (10 oz) approximate
Part Number P0926GW
Dimensions
• Height: 102 mm (4 in)
114 mm (4.5 in) including mounting lugs
• Width: 45 mm (1.75 in)
• Depth: 104 mm (4.11 in)
Cables • From Module to Hub/Switch/Device
1 m (3.3 ft) to 100 m (330 ft)
• Connectors
RJ-45
• Null Hub Adapter Cable
P0971PK
Figure 2. 5-Port 10/100 Base TX DIN Rail Mounted Ethernet Switch (P0972WE)