Instruction For STZ-P80C Pressure Switch
Instruction For STZ-P80C Pressure Switch
1, Technical Parameters
Pressure Range -1bar...0-1bar...6bar...600bar
Accuracy 1%FS
Power Supply 12VDC;24VDC;220VAC;380VAC(Optional)
Alarm Point Setting Can set any point in the full scale
Output Signal Relay output
Overload Capacity 380V 3A; 220V 5A; 24V 5A
Using Temperature -20℃~ 80℃
Measurement Medium Which is compatible with 316L stainless steel
WireConnection Portection Protection for reversed polarity and short circuit
Installation Connection M20*1.5; G1/2; G1/4;NPT1/4(Optional)
Connection Wires Power line:red and blue; output line:black and white
2, Button Description
1.(ON/OFF)Run Button:run button for system,should close this button when you
want to do the parameter setting,if not,it won't save the setting;
2.(SET)Setting Button:press SET button shortly to be into the upper and lower
limit value setting,press SET button for 3 seconds to be into the system setting;
3.(▲)Increase Value Button:press one time the value will increase into
0.01Mpa,press for 2 seconds will increase into 0.1Mpa;
4.(▼)Decrease Value Button:press one time the value will decrease into
0.01Mpa,press for 2 seconds will decrease into 0.1Mpa;
3, Using Method
1.The method for setting the controlled pressure
(1)press ON/OFF run button shortly,and then the run light and the pressure
control system will be closed;
(2)Setting for the upper and lower limit value
Press SET button shortly,then be into the lower limit value setting(right now the
light of the DOWN is open),and then through (▲)(▼) button to increase or decrease
the value,after done the setting,press SET button again to be into the upper limit value
setting(right now the light of the UP is open),and then through (▲)(▼) button to
increase or decrease the value;
(3)Done all setting,press SET button to save it(after setting some value,the system
will save it automatically if have not any button operation for 5 seconds)
(4)Press ON/OFF run button again(the run light is on),the switch will work.
2.Change the Unit: press ON/OFF run button to close the run light,you press ▲
to choose your unit(MPa; kgf/cm2; PSI), press for one time the unit will be MPa, press
for two times the unit will be kgf/ cm2, press for three times the unit will be PSI,after
setting,start the run light;
3.The function for zero clearing: press ON/OFF run button to close the run
light,and then press (▼) button for 5 seconds to change the current value into zero
point,after done the setting,press ON/OFF run button.(when you do this setting,the
pressure switch should not under any press condition)