PRS - Theory Distance Protection Complete - ENU
PRS - Theory Distance Protection Complete - ENU
© OMICRON Page 3
Contents
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 4
Agenda
© OMICRON Page 5
Introduction
Why can‘t we only
use overcurrent
protection relays?
Why do we have to
protect against
short circuits? What does a
distance protection
relay do?
When do short
circuits occur?
© OMICRON Page 6
When do short circuit currents occur?
© OMICRON Page 7
Kite vs. Overhead Line
>
© OMICRON Page 8
Why can't we only use overcurrent protection relays?
A B
100% Isc
? ?
50% Isc
? ?
50% Isc
Overcurrent relay
© OMICRON Page 9
Why can't we only use overcurrent protection relays?
A 1 B
0,6s 0,3s
0,6s 0,3s
2
directional overcurrent protection relay short circuit current (Isc) = passed = failed
© OMICRON Page 10
What does a distance protection relay do?
criterion
operating faulty
condition condition
Z<
Definition:
The distance protection relay trips, if the impedance
falls below a predetermined value.
© OMICRON Page 11
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 12
Short circuit impedance
Zsc
Rsc Xsc
Isc Vsc
= Distance protection device Isc = short circuit current Rsc = short circuit resistance metallic fault
= short circuit impedance ( Zsc ) Vsc = short circuit voltage Xsc = short circuit reactance
© OMICRON Page 13
Short circuit angle (impedance)
Im Im Im
VR sc VX sc Vsc
1
+ 2
= 3 ϕsc
IR sc Re Re
1
Re
IXsc
Isc
current area for
forward fault
VR sc VX sc
Isc
Rsc Xsc
VPh-E
IR sc = active componet of the short circuit current Isc = short circuit current Rsc = short circuit resistance metallic fault
IX sc = reactive componet of the short circuit current Vsc = short circuit voltage Xsc = short circuit reactance ϕsc short circuit angle
© OMICRON Page 14
Determination of fault direction (only with Isc and Vsc)
current area for
reverse fault Im
2
Isc 2 Isc
Vsc
Re
Isc Vsc
Isc
1
1 current area for
forward fault
ϕsc Re
V sc V sc 1V
Zsc = = (ϕV − ϕI ) = ( 0° − [ −45°]) = 1 Ω ( 0° + 45° ) = 1 Ω∠45°
Isc Isc 1 A
Isc
current area for
forward fault X
current area for
forward fault
Zsc
Vsc = short circuit voltage Isc = short circuit current Zsc short circuit impedance
© OMICRON Page 16
Distance protection principle (physical background)
Vsc
Vsc = 0
Ohm‘s law:
Isc
V sc
Z sc =
A B I sc
© OMICRON Page 17
Distance protection principle (physical background)
For this example: Zline A−B= 1 Ω Isc = 1 A Vsc = 0,5 V ϕsc =ϕline =ϕi =−45° ϕv = 0°
V V
Vr= 100% Vr= 100%
Vsc = 50% of Vr
1 3
Isc Isc
Vsc = 0
ct ct
A vt B A vt B
V sc V sc 0.5 V
Zsc=
V sc
=
V sc 0V
(ϕV − ϕI )= ( 0° + 45° )= 0 Ω∠45° 2
Z=
sc =
Isc Isc
(ϕV − ϕ=
I) 1 A ( 0° + 45=
° ) 0.5 Ω∠45° 4
Isc Isc 1A
X X
Zone 2 Zone 2
1 tZ2 = 350ms 1 tZ2 = 350ms
Zone 1 Zone 1
tZ1 = 0s tZ1 = 0s
ϕline ϕline
R R
forward forward
reverse reverse
directional characteristic directional characteristic
© OMICRON Page 18
Distance protection principle (physical background)
Vsc
C A B
Zsc
distance 100%
= Zline
© OMICRON Page 19
Distance protection principle (phase-to-phase fault)
1
0.5Ω
0.5Ω
Zsc
IA
VA R
e IB Zsc M Vsc = Zsc ● 2 Isc
l
0.5Ω
VB a
y
IC Zsc
Vsc 1 0.5Ω
Zsc = ● =
VC Isc 2
IE ZE (0.5Ω) + (0.5Ω)
M = fault loop
© OMICRON Page 20
Distance protection principle (phase-to-phase fault)
Short circuit calculation:
Vsc = VA - VB
+
Vsc = ( IB ● Zsc ) + ( IB ● Zsc )
Vsc = Zsc ● ( IB + IB )
© OMICRON Page 21
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 22
Distance protection principle (phase-to-earth fault)
1
0.5Ω
For this example:
A Zsc B
Zline AB = 1Ω
distance 50%
distance 100% = Zline
Zsc
IA Vsc = ( Zsc + ZE ) ● IC
VA R
e Zsc
IB
l
VB a
y
IC Zsc
(0.5Ω)
Vsc
Zsc + ZE =
VC Isc
M
IE ZE
Zsc fault loop = 0.5Ω + 0.3Ω = 0.8Ω !
(0.3Ω)
M = fault loop
© OMICRON Page 23
Distance protection principle (phase-to-earth fault)
Short circuit calculation:
Vsc = VC
Vsc = ( Zsc ● IE ) - ( ZE ● IC )
IE = - IC Vsc = ( Zsc + ZE ) ● IC
Vsc
IC = Isc Zsc + ZE =
Isc
© OMICRON Page 24
Distance protection principle (zero sequence comp.)
0.5Ω
A Zsc nom B
Without a special mathematical
distance 50% zero sequence compensation
Zsc fault loop method the relay cannot detect
the correct fault distance in case
distance 80% of phase-to-earth short circuits!
= Result of the earth impedance with phase-to-earth faults (Zsc fault loop) Zsc nom = 0.5Ω Zsc fault loop = 0.8Ω
© OMICRON Page 25
Distance protection principle (summary)
Ohm‘s law: V sc
Z sc =
I sc
For phase-to-earth short circuits the distance relay works with a zero
sequence compensation method for the correct distance calculation.
With the directional function the distance relay can detect „forward fault“ or
„reverse fault“.
© OMICRON Page 26
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 27
Field of application (overview)
A B
C
G 2
1
main protection
backup protection
© OMICRON Page 28
Distance protection concept for overhead lines (basics)
distance
50% 50%
1 2
A B
3 4
distance 100%
metallic fault
= passed
© OMICRON Page 29
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 30
Connection example of a distance relay
relay connected via feeder vt: relay connected via busbar vt:
vt
V
Trip
signal Trip
I signal
I
ct 21
ct 21
Start
signal
Start
vt signal
a) b)
© OMICRON Page 31
Connection example 3ph
A
B
C 21
A
CT
B
VT B
© OMICRON Page 32
Monitoring function of a distance relay (MCB tripped)
vt
„MCB tripped“
V
è The distance protection function is
MCB
blocked instantaneously!
MCB = Micro Circuit Breaker Distance protection device Binary Input (BI)
© OMICRON Page 33
Monitoring function of a distance relay (MCB tripped)
Situation: Short circuit on the secondary side of the VT è ANSI 21 blocked.
Dangerous situation !
A OVL not protected ! B
distance protection (21)
is blocked
I
21
(-) substation
auxiliary voltage
ct
(+)
MCB = Micro Circuit Breaker Binary Input (BI) = Distance relay blocked
© OMICRON Page 34
Monitoring function of a distance relay (FFM)
Situation: fuse-protected voltage transformer
ct 21
optional
© OMICRON Page 35
Monitoring function of a distance Relay (FFM)
Situation: Short circuit on the secondary side of the VT
phase-to-earth voltage
Van Vbn Vcn
1 Im
Vcn
phase currents
Ia Ib Ic
Van = 0
I = 1A n
I = 300A Re
2 Im
Ic
300A/1A ct 21
Vbn
Ia
Re
vt
Ib
Vn V=0
© OMICRON Page 36
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 37
Measured trip time (response time)
Situation: Testing protection relays è different trip times for the same fault
!
Test report of the secondary test set:
!
© OMICRON Page 38
Measured trip time (trip log)
fault inception
faulty area
operating area
pickup
trip drop-off
response time Trip time stored in the Trip Log file
© OMICRON Page 39
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 40
Internal logic diagram of a distance relay (overview)
1
Starter
I>
V<; I>
Z<
2 3
Impedance zones 2 Timer Directional function 2 Additional features
X Im
t1 reverse fault Autoreclosure
t2 Isc Powerswingblocking
. Sensitive earth fault
R
. Vsc protection
Re
Teleprotection
shemes
Isc Backup overcurrent
4 forward fault
protection
Binary Input
5
Internal relay Logic
© OMICRON Page 41
Starter logics
Starter Logic
V/I Pickup
Overcurrent Pickup Impedance Pickup
(voltage controlled overcurrent pickup)
X
V/Vr
operating faulty
area area
Vph>
0 Ioc max Isc min I
Trip area R
Idrop-off Ipickup
Iph> Iph>>
I/Ir
Ir
© OMICRON Page 42
Starter logics (overcurrent pickup)
operating
area faulty area
Idrop-off Ipickup
© OMICRON Page 43
Starter logics (V/I pickup)
V/Vr
Vr 1
Vph>
A 1 B
Vph> = 0.8 Vr
●
© OMICRON Page 44
Starter logics (impedance pickup)
A 1 B C
X
Zload 2
1
1
rea
pa
R
Tri
A 2 B C
Zload
= Load area è System is healthy = Load current = line impedance ( Zline ) = metallic fault
= Trip area è System is not healthy = short circuit current = distance protection device
© OMICRON Page 45
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 46
Zone reaches and time grading
Zone reach:
1 Zone 3
Zone 2
Zone 1 ∆Ζ
A B C
Zone 1 = 85%
distance 100%
Zone 2
Zone 3
Time grading: t
Zone 3
700ms
2 Zone 2
350ms
∆t
Zone 1
0s
A B C
© OMICRON Page 47
Calculation of fault resistance (selection)
phase-to-phase fault (ph-ph): phase-to-earth fault (ph-e):
Zline = Rline + Xline Zline = Rline + Xline
VA VA
R R
e e
l l
VB a VB a
y y
VC VC
ZE = RE + XE X ZE = RE + XE
X 1
1
2 3
2
ϕline
ϕline Rline + Rarc RE
R
R
Rline + Rarc
© OMICRON Page 48
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 49
Structure of the impedance characteristic (Quadrilateral)
t
Zone 3
700ms
Zone 2
350ms
∆t
Zone 1
0s
A B C
X
Zone reaches:
Zone 2
tZ2 = 350ms
= for phase-to-earth fault
Zone 1 = for phase-to-phase fault
tZ1 = 0s
= reverse zone (optional)
ϕline
R
forward
reverse
directional characteristic
© OMICRON Page 50
Impedance characteristics (zone characteristics)
A zone characteristic can consist of any number and combination of line,
circle or arc elements.
1 X 2 X 3
R R R
© OMICRON Page 51
Impedance characteristics
A zone characteristic can consist of any number and
combination of line, circle or arc elements.
X X
1 2
© OMICRON Page 52
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 53
MHO characteristic or quadrilateral characteristic?
A B
X
Zone 2
14
Zone 1
12
Zsc 1 Zsc 2 10
VA R
P
8
e
l 6
VB a
y
VC
4
2
P
ϕline
Zone 1 = 85% = 8,5Ω R
2 4 6 8
Fault 1 Fault 2 10
= (1,04+i3,86)Ω = (2,07+i7,73)Ω 4
P
2
ϕline
= metallic faults (Rf =0Ω)
R
2 4 6 8
© OMICRON Page 54
MHO characteristic or quadrilateral characteristic?
A B
Zone 2 X
Zone 1 14
12
Zsc 1 Zsc 2
10
VA 8
R
e 6
RF
P For short circuits with fault resistance (Rf ),
l
e.g. arc resistance, the quadrilateral
VB a
characteristic measured the short circuit in
y
4
RF P the correct zone.
2
VC ϕline
R
Zone 1 = 85% = 8,5Ω 2 4 6 8
10
Fault 1 Fault 2 1
8
RF For short circuits with fault resistance (Rf ),
e.g. arc resistance, the MHO characteristic
6 can‘t measured the short circuit in the
= short circuit with Rf =3Ω correct zone.
4
RF P
2
ϕline
R
2 4 6 8
© OMICRON Page 55
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 56
Synchronism-check (wiring example)
L1
L2
L3
CB Close
L1 Distance L1
Protection Device
L2 L2
with Synchronism
L3 Check 1
N
1 L1-L2 is only a wiring example. All variants possible (e.g. L1L3, L1N, etc.).
© OMICRON Page 57
Synchronism-Check (voltage test)
© OMICRON Page 58
Synchronism-Check (dead line / live bus)
CB on command side A:
VA VB
1 VCB
Vr switched on 2
A B
Iload C
V>
CB on command side B:
undefined
VA VB
2 VCB
V<
de-energized 1
0 A B
Iload C
© OMICRON Page 59
Synchronism-check (starting conditions)
VA VB
VCB
A B
Iload C
Standard values:
Maximum amplitude difference (∆Vmax) ≈ 10 %
Maximum angular difference(∆ϕmax) ≈ 10° ... 20°
Maximum frequency difference (∆fmax) ≈ 0 Hz (0.01 ... 0.04 Hz)
© OMICRON Page 60
Synchronism-check (frequencies)
The frequencies on both sides of the circuit breaker must be the same.
© OMICRON Page 61
Synchronism-Check (voltages)
The amplitudes of the voltages must NOT deviate significantly from one another.
© OMICRON Page 62
Synchronism-check (phase angles)
The phase angles must NOT deviate significantly from one another.
© OMICRON Page 63
Synchronism-check (parameters)
If these conditions are met for a minimum time tmin = 0…5 ... 10 s,
the CB close command release is issued.
© OMICRON Page 64
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 65
Autoreclosure (principle)
Note: The Autoreclosure (AR) function is not for cables!
t Trip time = 0 s
Zone 3
700ms
Zone 2
350ms Trip time = 350 ms
Zone 1 ≈15%
0s
A B C
1 2
Trip times formally OK but not the optimal behavior. Practical experience has shown that approx. 80%
of short circuits, mostly transient single-phase ground faults, are caused by lightning strokes on
overhead lines.
The principle of auto-reclosing is clearing a fault by momentarily de-energizing the line and fast
reclosing of the circuit breakers (CBs) in order to maintain system stability and continuity of service.
© OMICRON Page 66
Autoreclosure (principle) t
Zone 3
700ms
Zone 2
350ms
Zone 1
0s
A B C
Zone 1
tZ1 = 0s
ϕline
R
© OMICRON Page 67
Autoreclosure function ready (AR-cycle allowed)
A
Distance relay
CB ready for 1
blocked by
O-C-O cycle external signal
CB position 2
no blocked by
external signal P
CB ready
P
CB position „closed“
P
AR function „READY“
© OMICRON Page 68
Autoreclosure “AR” (operation modes)
© OMICRON Page 69
Autoreclosure (short time AR /successful)
t
Zone 3
700ms
Zone 2
350ms
Zone 1
0s ≈120% of ZAB = Overreach zone
A B C
Trip time ≈ 35 ms
1 2 3 4
short circuit
pick up
action time
Trip
dead time 500ms
CB-ON
reclaim time
AR running
1
0s 35ms 140ms 640ms t
30ms
© OMICRON Page 70
Autoreclosure (parameters / action time)
short circuit
pick up
action time
P The relay has activated the trip command
Trip
dead time
P at the action time and has initiated the
AR-cycle.
200ms
© OMICRON Page 71
Autoreclosure (parameters / dead time)
Deionizing time and dead time depending on the voltage level:
t/s
0,6
0,5
0,4
0,3
0,2
Deionizing time
0,1 Dead time
0
0 100 200 300 400 500 V/kV
The deionizing time for an arc in free air depends on the circuit voltage, conductor
spacing, fault circuit current, fault duration, wind speed and capacitive coupling
particularly for single phase AR. The times on the right are valid for a three-phase
AR.
© OMICRON Page 72
Autoreclosure (parameters / reclaim time)
3s
short circuit
pick up
action time
Trip
dead time 500ms
P
CB-ON
reclaim time
AR running
P The short circuit occurs at the end of the reclaim time. The next AR-cycle is started. Trip time 0s!
3s
short circuit
pick up
action time
Trip
dead time
CB-ON
500ms
reclaim time
AR running
The short circuit occurs during the reclaim time. The AR function is blocked!
Trip time = 350ms (Zone 2)!
© OMICRON Page 73
Autoreclosure (short time AR / unsuccessful)
t
Zone 3
700ms
Zone 2
350ms ≈120% of ZAB = Overreach zone
Zone 1
0s
A B C
1 3
short circuit
pick up 4
action time
Trip 2
dead time 500ms
CB-ON
reclaim time
AR running
© OMICRON Page 74
Autoreclosure (short time / long time AR)
t
Zone 3
700ms
Zone 2
350ms
A B C
1 2 3 4 5 6
short circuit
pick up
action time
Trip
dead time 1st-cycle / 500ms 2nd-cycle / 30 ... 60... 120s
1 SynchoCheck Passed
CB-ON
reclaim time
AR running
0s 35ms t
Trip time = Overreach zone
30ms
1st-cycle 2nd-cycle
© OMICRON Page 75
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 76
Switch-on-to-Fault (SOTF / backround)
t
Zone 2
A 350ms
B
Zone 1
0s Initial situation:
© OMICRON Page 77
Switch-on-to-Fault (theory of operation)
Switch-on to fault (SOTF) is a protection function providing fast tripping if the line
breaker is closed on to a faulty line.
t
Zone 2
A 350ms
Zone 1 B
0s
1 2 3
CB-ON command CB-on command
Relay received
1 „CB-ON“ command
action time
2 overreach zone
activated
short circuit
pick up
Trip
0s 0.5 ... 3s t
0s 35ms
t
30ms
© OMICRON Page 78
Switch-on-to-Fault (short circuit out of range)
t
Zone 2
A 350ms
Zone 1 B
0s
CB-ON command
CB-on command
Relay received
„CB-ON“ command
action time 1
short circuit
pick up
Trip
0s 0.5 ... 3s t
0s 350ms
t
30ms
2
© OMICRON Page 79
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOTF)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 80
Teleprotection (technical backround)
a) Overhead line with AR function:
t
Zone 3
700ms
Zone 2
350ms
Zone 1
0s
≈120% of ZAB = Overreach zone
A B 1 C
Zone 2
350ms
Zone 1
0s
c) Very short Overhead line or
cable without AR function:
A 2 B C
Zone 1 ?
Teleprotection guarantees for 100% distance
A 3 B (ZAB) selectivity with a trip time of 0s
© OMICRON Page 81
Teleprotection (basic principle)
t
Zone 3
700ms
Zone 2
350ms
= SEND / RECElVE signal
Zone 1
0s
A B C
1
Both protection relays of the section (AB) are connected via communication channels (fiber optic, copper wiring,
etc.)
Connection Example:
B
A
Copper wiring
2 4 2
© OMICRON Page 82
Teleprotection (summarization of schemes)
The teleprotection schemes worldwide are called differently by their
manufacturer. This table shows some equivalent names.
© OMICRON Page 83
Teleprotection (only overview / selection)
Short circuit between A-B:
t
Zone 2
A 350ms
P Zone 1 PB 0s
A B C ≈120% of ZAB = Overreach zone
Zone 1
Zone 2
= SEND / RECElVE signal
P
Zone 1 B 0s
A B C ≈120% of ZAB = Overreach zone
Zone 1
Zone 2
no SEND / RECElVE signal
© OMICRON Page 84
Teleprotection (overview / theory of operation)
Short circuit between A-B:
t
Zone 2
A 350ms
Zone 1 B
0s
A B C
Zone 1
1 2 4
Zone 2
short circuit
3 pick up
© OMICRON Page 86
Agenda
> Introduction to Distance Protection
> Protection Criterion Impedance
> Impedance – Zero sequence compensation
> Field of Application
> Connection Example Monitoring function
> Measured Trip Time and analog signals
> Basic structure of distance relays
> Zone reaches, time grading and Calculation of the resistance settings
> Structure of the Impedance characteristic
> MHO / Quadrilateral characteristic
> Synchronism-Check (Synchro-Check)
> Autoreclosure (AR)
> Switch-on-to-Fault (SOFT)
> Teleprotection (overview)
> Protection testing principle
© OMICRON Page 87
Protective functions and test modules
© OMICRON Page 88
Front view of the CMC 356
© OMICRON Page 89
Wiring scheme of the CMC (distance)
A B
Z< Z<
Standard:
outputs
binary
analog inputs
Test currents
I 1 „Pickup“ signal
binary
inputs
2 „Trip“ signal
V
Test voltages
Optional:
4
3 „CB-ON“ signal
4 „CB-ON“ signal
1
2
3
© OMICRON Page 90
Wiring scheme of the CMC analog outputs (synchro-check)
L1
L2
L3
CB Close
Distance
L1 Protection Device with L1
L2 L2
Synchronism Check
L3
N
outputs
binary
analog inputs
V feeder
analog inputs
V busbar
Test voltages
Test voltages
1
2
© OMICRON Page 91
Wiring scheme of the CMC (teleprotection)
A B
outputs
outputs
binary
binary
analog inputs
analog inputs
I
I
Test currents Test currents
binary binary
inputs inputs
V
V
Test voltages Test voltages
1 2 1 2
© OMICRON Page 92
© OMICRON Page 93