Maintenance Manual For Power Lead 2 3 P Series 10-20KVA: in February 2019
Maintenance Manual For Power Lead 2 3 P Series 10-20KVA: in February 2019
Maintenance Manual For Power Lead 2 3 P Series 10-20KVA: in February 2019
com
Version 1.0
In February 2019
-1-
www.everexceed.com
WARNING OF BATTERY
The battery can present a risk of electrical shook and high short circuit current.
Following precautions should be observed before replace the battery or maintain
standard UPS.
Wear rubber gloves and boots.
Remove rings, watches and other metal objects.
Use tools with insulated handles.
Do not lay tools or other metal objects on the batteries.
If the battery is damaged in any way or shows signs of leakage, contact your
local representative immediately.
Do not dispose batteries in a fire. The batteries may explode.
Handle, transport and recycle batteries in accordance with local representative.
WARNING
Although UPS has been designed and manufactured to ensure personal safety,
improper use also can result in electrical shock or fire. To ensure safety, observe the
following precautions:
Turn off and unplug the UPS before cleaning it.
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of
the UPS.
Do not place the UPS power cord where it might be damaged.
If there is a fire, please use the dry powder extinguisher. If you use
liquid extinguisher, there may get an electric shock risk.
Before turning on the ups, please check that whether the cable and the polarity
of the batteries are correct.
Important Tips:
When you need to replace board, please turn off ups, disconnect the main switch
and battery switch (built-in battery, please unplug at least one battery cable), wait for
10 minutes.
-2-
www.everexceed.com
Contents
1. Product Structure ............................................................... 4
1.1 Outlook ................................................................................... 4
1.2 Panel instruction ........................................................................ 6
2. Topology and System Description ............................................ 10
2.1 Topology ................................................................................10
2.2 System description ....................................................................11
3. Alarm Code ...................................................................... 13
4. Hardware Detection ............................................................ 15
4.1 Inner structure .........................................................................15
4.2 Rectifier failure ........................................................................20
4.3 Inverter failure and inverter protection ............................................21
4.4 Bypass failure ..........................................................................22
4.5 Charger failure and battery issue ...................................................22
4.6 Utility abnormal........................................................................23
4.7 Bypass voltage abnormal .............................................................23
4.8 Output overload or overload timeout...............................................24
-3-
www.everexceed.com
1. Product Structure
1.1 Outlook
Available models are shown as Table1-1:
Table 1- 1: Models
Model Nominal Power Model Nominal Power
10K long backup 10000VA/10000W 15K long backup 15000VA/15000W
20K long backup 20000VA/20000W
10KVA 15K/20KVA
-4-
www.everexceed.com
EPO
USB(option )
Parallel
(option)
RS232
Cold
start
Intelligent
button
slot
Fan
Reserved
Ground
Bypass
breaker
Input
breaker
Terminal
cover
Cable
protector
10KVA
EPO
Parallel
RS232 (option)
Cold
USB(option) start
button
Intelligent
slot
Fan
Reserved
Bypass
breaker
Input
Ground
breaker
Terminal
cover
Cable
protector
15/20KVA
Fig 1.2 Rear view
-5-
www.everexceed.com
OUT_ BYP_
PE OUT_L BAT+ BAT- IN_L1 IN_L2 IN_L3 IN_N
N L
10KVA
BYP_
IN_L1 IN_L2 IN_L3 IN_N
L
OUT_
PE BAT+ BAT- OUT_L
N
15/20KVA
Fig 1.3 Connection terminals
As shown in Fig 1.2, the rear panel provides the following components and function:
⚫ USB: B type, used to connect monitoring software
⚫ EPO: NC
⚫ Parallel port: option
⚫ Reserved: reserved for customer function, such as manual bypass, battery breaker, socket and
so on
⚫ Terminal cover
⚫ Input breaker: surge protection
⚫ Bypass breaker: surge protection
⚫ Cable protector: cable entry, fix cables, safety
⚫ Cold start: start UPS from battery
⚫ Fans: intelligent fan speed control
-6-
www.everexceed.com
LCD
Table 1-1 showing the descriptions of controls on the control and display panel.
Table 1-1 Descriptions of controls
Controls Description
1. Press ON/OFF to start inverter when rectifier is OK
NOTE:
Not available when UPS is set in automatically start mode
ON/OFF 2. Press ON/OFF to shutdown inverter and transfer to bypass
3.Press ON/OFF to shutdown UPS completely when UPS is in
battery mode
4.Press ON/OFF to confirm setting when in setting mode
Functional button:
1. Press FUNC to page down to see LCD menu
2. Press FUNC for 2.5s at the page 1 to mute off, press again to mute
FUNC
on
3. Press FUNC and ON/OFF together for 2.5s to enter in setting mode
4.Press FUNC for 2.5s at the page 4 to clear fault
Indicators Description
Rectifier indicator: green--rectifier is normal, green flicker--rectifier is
REC
starting, dark--rectifier is not working
Inverter indicator: green--inverter is normal, green flicker--inverter is
INV starting or tracking with bypass(ECO), dark--inverter is not working
Bypass indicator: yellow—bypass is normal, yellow flicker--bypass
BYP
alarm ,dark--UPS is in normal mode and bypass is normal
Battery indicator: yellow--battery discharged, yellow flicker--No
BAT
battery or battery alarm, dark--battery is connected
-7-
www.everexceed.com
-8-
www.everexceed.com
Page 3:
Input current: 0.8A
Output current: 0.1A
Battery current: 0.0A (downward arrow—charge, upward
arrow—discharge, no arrow—no battery)
Firmware version: V0.17(17.0)
Page 4:
“B”: flicks, bypass input menu now
Bypass input voltage: 220VAC
Alarm code: 07
Press “FUNC” for 2.5s to manually clear fault
Parameters setting:
If you want to set rated parameters, press ON/OFF and FUNC buttons together for 2.5s to enter
in setting mode, “SETTING” on the bottom of LCD present and all LEDs flicks. Press the
FUNC to change the parameters, and press the ON/OFF to transfer to another parameter setting.
-9-
www.everexceed.com
2.1 Topology
The topology is shown in following figures.
-10-
www.everexceed.com
-11-
www.everexceed.com
(3) Inverter
In normal operation, the inverter utilize the DC output of the power factor correction circuit and
inverters it into precise, regulated sine wave AC power. Upon a utility power failure, the inverter
receives its required energy from the battery through the DC-to-DC converter. In both modes of
operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC
output power.
(6) Battery
If input power is failure when in normal mode, UPS will transfer to battery mode. In this mode, the
battery provide power to inverter.
-12-
www.everexceed.com
3. Alarm Code
This chapter describes how to check the UPS’s status. This section also indicates various UPS
symptoms a user may encounter and provides a trouble shooting guide in the event when the
UPS appear a problem. Use following information to determine whether external factors caused
the problem and how to solve the situation.
If the UPS alarm and buzzer sound, please press “FUCC” to get alarm code on the menu of
alarm code ) on LCD. And press “FUNC” for 2.5s when at page 4 to manually clear fault.
If alarm is still existing, please refer to the Table 3-1 to solve the problem.
-13-
www.everexceed.com
-14-
www.everexceed.com
4. Hardware Detection
4.1 Inner structure
The Power Lead 2 3P Series10KL/S and the Power Lead 2 3P Series 20KL/S are similar in
structure. Consisting of following parts: control board, power board, charger board, bus
capacitor board, battery fuse board and EMI board, SCR board and so on. The aux power
board is welded to the power board or power transfer board. The inner structure is shown in
following figures.
-16-
www.everexceed.com
-17-
www.everexceed.com
-18-
www.everexceed.com
-19-
www.everexceed.com
Fig 4.8 Power Lead 2 3P 10KL Sampling resistors for bus voltages
D59,D60,D65,D66,D67,D68
-20-
www.everexceed.com
Fig 4.10 Power Lead 2 3P 10KL Sampling resistors for inverter voltage
Check if the sampling resistors for bypass input voltage are ok.
The following figure shows the sampling resistors for bypass input voltage.
Fig 4.11 Power Lead 2 3P 10KL Sampling resistors for bypass input voltage
Fig 4.12 Power Lead 2 3P 10KL Sampling resistors for battery voltage
Fig 4.13 Power Lead 2 3P 10KL Sampling resistors for main input voltage
-22-
www.everexceed.com
Fig 4.14 Power Lead 2 3P 10KL Sampling resistors for bypass input voltage
Fig 4.15 Power Lead 2 3P 10KL Sampling resistors for output voltage
-23-