Construction Issue Binder - 10-436 - 26-06-23

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

© COPYRIGHT : THE CONTENTS OF THIS DRAWING MAY

NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT


THE WRITTEN PERMISSION OF CSE Consulting.

GENERAL NOTES

1. These drawings are to be read in conjunction with all


relevant Survey and Engineers drawings.
Do not scale this drawing.

2. All dimensions to be obtained by site measurement


Extent of existing retaining wall to be fully prior to the commencement of works or ordering of
removed, including foundations to allow for the materials.
construction of the replacement retaining wall.
3. Where discrepancy occurs between specification and
drawing the Engineer must be notified.

Existing ground level to far side Existing retaining wall across 4. The Contractor is responsible for the overall stability of
(No. 7). No. 7 garden. the structure from the commencement of work,
Approximate outline of original Extent of damage & rotation of existing remaining
including the design and provision of all necessary
wall (assumed). boundary retaining wall to be assessed at the
temporary works. The Contractor is to submit full details
commencement of works.
of his temporary works proposals to the Engineer for
Wall to be carefully taken down to four courses
his consideration at least two full weeks prior to the
below traces of damage and rebuilt to existing
commencement of works.
width.
5. All DPMs, DPCs, waterproofing and weathering details
to be in accordance with current regulations.

6. Concrete to be Grade C32/40 with 20mm max. size of


aggregate. Mass concrete padstones and tie bars to be
Grade C25/30 with 10mm max. size of aggregate. All
concrete to be in accordance with BS 8110.

7. All mortar and concrete below DPC level to use sulphate


resisting cement.

8. Concrete dry pack to consist of 3:1 sharp sand : OPC with


Combex admixtures, with only sufficient water to bind
Existing ground level to near together the mix when well rammed into place. Ensuring
side (No. 5). Outline of existing additional full load transfer where necessary.
retaining structure to far side
of existing wall (No. 7). 9. This scheme assumes a min. compressive strength of
existing brickwork to be 15N/mm² in mortar designation
IV. This is to be agreed with the Local Authority prior to
the commencement of works.
Note - Details shown on CSE Consulting Ltd
Existing ground level to far side
drawings are based on a Topographical survey of 10. All structural works are to be carried out strictly in
(No. 7).
the wall and surrounding ground levels accordance with the details given by CSEconsulting. The
undertaken by 'Twickenham Surveys' . Contractor Engineer is to be advised of any significant variation
to make reference to the Topographical Survey
for existing wall heights and site ground levels.
EXISTING ELEVATION prior to its implementation.

scale 1:50 11. The contractor is responsible for the location of all
underground services that may exist and to divert them if
necessary prior to the commencement of works.

12. All foundations to be cast on an approved formation level


to the satisfaction of the Local Building Control Officer.
Foundations have been designed for an allowable ground
bearing pressure of 150kN/m². This is to be agreed with
the Local Building Control Officer on site prior to the
commencement of works or ordering of materials.

13. In the absence of a site investigation the design and


details shown on these drawings are based on the
assumption that the prevalent site conditions are
suitable for conventional foundation formation.
Final formation level to suit site conditions and to be
taken down a further 150mm locally below any tree roots
Existing additional 9" thick encountered - Typical.
retaining structure to side of This is to be agreed with the Local Building Control
existing wall. Officer following an inspection of the ground conditions
at the commencement of works prior to the ordering of
materials.
No. 7 Frognal Way Existing retaining wall.
14. In addition to details shown on CSE Consulting drawings
No. 7 Frognal Way Existing retaining wall. Contractor is to ensure full compliance with all statutory
requirements including current Building Regulations.

No. 5 Frognal Way

0 26.06.23 Construction
Extent of fully dilapidated existing retaining wall to No. 5 Frognal Way Extent of partially dilapidated wall.
be fully removed, including foundations to allow Damage & rotation of existing remaining boundary rev. date description chk.
for the construction of the replacement retaining retaining wall to be assessed at the
Devonshire House

engineers
civil
structural
wall. commencement of works.
Wall to be carefully taken down to four courses Cliveden Office Village
below traces of damage. Lancaster Road
EXISTING PLAN High Wycombe
Bucks HP12 3YZ
scale 1:50 tel: 01494 923307

construction
email: [email protected]
client:

Mr. Wilson Lee

job title:

5 Frognal Way,
London
NW3 6XE

drawing title:

Garden Boundary Retaining Wall


Existing Plan and Elevation

scale: date: drawn by: checked by:


1:50@A1 June 2024 MRH
job number: drawing number: revision:
0 1m 2m 5m
1:50
10-436 100 0
© COPYRIGHT : THE CONTENTS OF THIS DRAWING MAY
NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT
THE WRITTEN PERMISSION OF CSE Consulting.

For General Notes refer to drawing No. 10-436 100.

Contractor to allow, in their price, for the taking


New retaining wall: down and rebuilding of wall to ground level on
Stepoc reinforced blockwork by Anderton No. 5 side.
Concrete with 215mm solid brickwork garden
boundary wall off top to a max height of 1925mm to In practice extent of damage & rotation to be
1 high side and brick facing to low side (No. 5) assessed at the commencement of works and
110 existing wall to be carefully taken down to four
courses below traces of damage and rebuilt to
match existing off sound construction.
2 Care to be taken to ensure that adjoining
110
neighbour's retaining wall is left intact and
undisturbed.
1000

225
Existing ground level to near
side (No. 5).

225
New retaining wall built off
reinforced concrete footing, TYPICAL FOUNDATION
1025 mm wide x 450mm min
deep taken down to a formation STEP DETAIL
level as approved by the Local scale 1:20
Building Control Office

Note - Brickwork: Red dotted line indicates


All brickwork to be frost resistant quality (type FN) existing ground level to far side
minimum class (3) laid in mortar class (ii) (No. 7).
Ensure provision of adequate movement joints in
accordance with brick manufacturer's PROPOSED ELEVATION Note:
Wall elevation has been developed using the
recommendations and Architect's specification. scale 1:50 survey information provided.
Actual 'stepping' of foundation and height of
reinforced blockwork to be determined on site by
the Contractor at the commencement of works,
prior to the ordering of materials.

Note - Care to betaken to ensure all existing retaining walls and garden
structures within the rear garden of the adjoining property are left intact
and undisturbed during the course of the boundary wall remedial and
reconstruction works.

Trees and vegetation which require to removal along the boundary line,
New retaining wall built off within the rear garden of the adjoining property, to facilitate the boundary
reinforced concrete footing, 900 wall remedial and reconstruction works are to be identified and agreed
wide x 450mm min deep taken
1 with the property owner.
2
110 110
down to a formation level as
approved by the Local Building
Control Office No. 7 Frognal Way 7.74
t/s wall

10.07 7.18
11.57 7.36 t/s wall
t/s wall t/s wall 8.52 t/s wall
7.74
t/s wall t/s wall
9.52 8.75 8.07
t/s wall t/s wall t/s wall
9.40
t/s wall
11.29 10.47 9.69 8.59 0 26.06.23 Construction
t/s wall t/s wall t/s wall t/s wall
STP

7.68
rev. date description chk.
t/s wall
8.05
Devonshire House

engineers
civil
structural
t/s wall
8.62
t/s wall Cliveden Office Village
Lancaster Road
High Wycombe
Bucks HP12 3YZ
Extent of existing retaining fully removed and No. 5 Frognal Way Contractor to allow, in their price, for the taking tel: 01494 923307

construction
replaced using Stepoc reinforced blockwork by down and rebuilding of wall to ground level on email: [email protected]
Anderton Concrete with 215mm solid brickwork No. 5 side.
garden boundary wall off top to a max height of client:
1925mm to high side and brick facing to low side In practice extent of damage & rotation to be
(No. 5) assessed at the commencement of works and Mr. Wilson Lee
PROPOSED PLAN existing wall to be carefully taken down to four
courses below traces of damage and rebuilt to
scale 1:50 match existing off sound construction.
job title:

5 Frognal Way,
London
NW3 6XE

drawing title:

Garden Boundary Retaining Wall


Proposed Plan and Elevation

scale: date: drawn by: checked by:


0 500mm 1m 2m 1:50,1:20@A1 June 2024 MRH
1:20 job number: drawing number: revision:
0 1m 2m 5m
1:50
10-436 101 0
© COPYRIGHT : THE CONTENTS OF THIS DRAWING MAY
NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT
THE WRITTEN PERMISSION OF CSE Consulting.

For General Notes refer to drawing No. 10-436 100.

Brick on edge course.


No. 5 Frognal Way No. 7 Frognal Way No. 5 Frognal Way No. 7 Frognal Way

Double tile creasing with concrete fillets


(to match existing)

Varies - 1925mm max.


Brick wall - Flemish bond.

215mm thick solid brickwork garden Existing garden boundary wall to be


boundary wall built off top of carefully taken down to min 4
reinforced blockwork wall. courses below the level of damaged
Top of wall 'stepped' down in a brickwork and rebuilt off the sound
similar manner to pre-existing construction to match existing.
condition.
TOP OF WALL SECTION
Lowest level of cracking/rotational
"Stepoc" 256mm thick reinforced damage to existing wall. scale 1:10
blockwork retaining wall by
Brickwork facing to reinforced Anderton Concrete.
blockwork retaining wall.
Waterproofing to rear of wall -
Weep holes: bituminous membrane or 2 layers of 4 No. brick courses (min.)
Min 50mm dia. at max. 1000mm bituminous emulsion.
centres along wall.
Free draining granular material -
Min. cover to foundation 200mm well compacted in min 150mm max.
layers.
325
Mass concrete fill:
Concrete specification to match that
Existing garden boundary wall to be
used for main foundation.
retained intact from 4 brick courses Existing retaining structure to No. 7
450

below lowest level of side - foundation detail unknown.


cracking/rotational damage.
Existing foundation detail to be
Paving
determined on site by trial hole
1025mm wide x 450mm deep investigation.
foundation to reinforced blockwork
retaining wall taken down in lean
mix concrete to a formation level as
approved by the Local Building 1025
Control Officer. - TYPICAL
0 26.06.23 Construction
SECTION 2 - 2
SECTION 1 - 1 scale 1:20 rev. date description chk.

Devonshire House

engineers
scale 1:20

civil
structural
Cliveden Office Village
Lancaster Road
High Wycombe
Bucks HP12 3YZ
tel: 01494 923307

construction
email: [email protected]
client:

Mr. Wilson Lee

job title:

5 Frognal Way,
London
NW3 6XE

drawing title:

Garden Boundary Retaining Wall


Proposed Sections

scale: date: drawn by: checked by:


0 500mm 1m 1:20,1:10@A1 June 2024 MRH
1:10 job number: drawing number: revision:
0 500mm 1m 2m
1:20
10-436 110 0
© COPYRIGHT : THE CONTENTS OF THIS DRAWING MAY
NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT
THE WRITTEN PERMISSION OF CSE Consulting.

For General Notes refer to drawing No. 10-436 100.

3
200

4
200

14 H16-02-150
in pairs 7T, 7B
05 03 04 05 7 H12-04 14 H16-02-150
L bars - T in pairs 7T, 7B H16-06-266
640 wall bars
04 05 7 H12-04 14 H16-02-150
L bars - T in pairs 7T, 7B
7 H16-03-150 640
u bars 04 05 7 H12-04 14 H16-02-150
L bars - T in pairs 7T, 7B
640
04 05 7 H12-04 14 H16-02-150
L bars - T in pairs 7T, 7B
640
05 03 04 05 7 H12-04 14 H16-02-150
14 H12-05 L bars - T
7T, 7B in pairs 7T, 7B
640 640
H16-01-150 05 04 04 05 7 H12-04
7 H12-04 L bars - T
in pairs T & B L bars - B 640 640
14 H12-05
7 H12-04 05 04 03 05
7T, 7B
H16-01-150 L bars - B 640
14 H12-05
in pairs T & B 7 H12-04 05 04
7T, 7B
H16-01-150 L bars - B 640 7 H16-03-150
14 H12-05
in pairs T & B 7 H12-04 05 04 u bars
7T, 7B
H16-01-150 L bars - B 640
14 H12-05
in pairs T & B 7 H12-04 05 04
7T, 7B
WALL ELEVATION H16-01-150 L bars - B
14 H12-05
640
in pairs T & B 05 04 03 05
scale 1:20 7T, 7B
H16-01-150
7 H12-04
L bars - B
14 H12-05
in pairs T & B 7T, 7B
BENDING SCHEDULE H16-01-150
in pairs T & B
Number
Bar Type Length of
Shape A* B* C* D* E/R*
Member Mark and of in in bar+ Revision
Code mm mm mm mm mm
Size mbrs each total mm
Note: Note:
01 H16 1 1500 21 300 970 [300] Wall elevation has been developed using the All reinforcement qunatities to be determined by
blockwork retaining

survey information provided. the Contractor based on prevalent site conditions.


No. off all bars to be

02 H16 1 1950 21 525 970 [525]


determined by the
Contractor on site

Actual 'stepping' of foundation and height of


wall and base
Reinforced

03 H12 1 1325 21 500 370 [500] reinforced blockwork to be determined on site by


the Contractor at the commencement of works,
04 H12 1 1350 11 550 825 prior to the ordering of materials.
05 H12 1 varies 00 cut & lapped to suit on site
06 H16 1 varies 11 400 varies cut to suit on site
07 H12 1 varies 00 cut & lapped to suit on site

This schedule complies with BS8666:2005 * Specified to nearest 5mm + Specified to nearest 25mm

0 26.06.23 Construction

rev. date description chk.

Devonshire House

engineers
civil
structural
04 07
Cliveden Office Village
Lancaster Road
04 07 High Wycombe
Bucks HP12 3YZ
tel: 01494 923307
varies

construction
04 07
email: [email protected]

varies
client:
04 07

Mr. Wilson Lee


04 07

05 05 04,05 04,05 job title:

H16-01 @ 150 H16-06 @ 266


5 Frognal Way,
05 05
u bars in pairs wall bars H16-02 @ 150 H16-06 @ 266 London
u bars in pairs wall bars
05 05
05 05 NW3 6XE
14 H12-05 @ 150
04,05 04,05
7T & 7B
drawing title:
14 H12-04 & 05 @ 150
7T & 7B Garden Boundary Retaining Wall
SECTION 3 - 3 RC Details
scale 1:20 SECTION 4 - 4
scale 1:20 scale: date: drawn by: checked by:
1:20@A1 June 2024 MRH
job number: drawing number: revision:
0 500mm 1m 2m
1:20
10-436 200 0

You might also like