R4875S5 PSU User Manual V1.1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

R4875S5 PSU User Manual V1.

Operating Environment
Item Specifications
Operating temperature
–40°C to +75°C
range

Storage temperature –40°C to +75°C

Relative humidity 5% RH–95% RH (non-condensing)

≤ 5000 m. When the altitude ranges


Peak efficiency: 97.8% from 2000 m to 5000 m, the operating
Altitude
Efficiency temperature decreases by 1°C for
> 96% (230 V AC, 30%–80% load) each additional 200 m.
Dimensions 40.8 mm×105 mm×269 mm
(H x W x D) .8 mm x 105 mm x 269 mm Electrical Features
Weight ≤ 2.5 kg
Item Specifications
Cooling mode Built-in fan (speed adjustable)
Input

Product Overview Operating voltage


rangeange
85–300 V AC
The R4875S5 is a digital power supply unit (PSU) 45–66 Hz
with super high efficiency and high power density. Input frequency
Rated frequency: 50 Hz/60 Hz
It supports a wide range of input voltage and Rated input
≤ 21 A
provides 53.5 V DC/57.0 V DC output voltage by current
default. It supports soft start and comprehensive Power factor ≥ 0.99 (50%–100% load)
protection, and boasts low noise. Multiple PSUs THD ≤ 5% (50%–100% load)
can be connected in parallel. The status of loads Output
and PSUs can be monitored in real time and the
42–58 V DC
output voltage can be adjusted by power Output voltage
Rated voltage: 53.5 V DC/57.0 V DC
monitoring. 4000 W (176–300 V AC)
Output power
4000–1608 W (176–85 V AC)
Peak efficiency 97.8%
Key Features
• Wide input voltage range Regulated
≤ ±0.6% x Vo
voltage precision
• Wide operating temperature range
Ripple and noise ≤ 200 mVp-p (bandwidth ≤ 20 MHz)
• Low total harmonic distortion (THD)
• Fully digital control • 25%–50%, 50%–75% load:
− Overshoot: ±5%
• Supports hot swapping. Dynamic − Recovery time: ≤ 200 μs (±0.6% x Vo)
response • 10%–90% load:
• Supports a smart electricity meter. − Overshoot: ±5%
• CAN bus communication − Recovery time: ≤ 1 ms (±1% x Vo)

• LED alarm display Standby power ≤5W

• Voltage adjustment, current adjustment, and Startup time 3 s–10 s


current balancing Output hold-up > 10 ms

• Disconnects at 320 V AC. Psophometrically


weighted noise ≤ 2 mV
• RoHS compliance voltage
• Passed the TUV, NRTL, RCM, and CE Wide-band noise ≤ 50 mV (3.4 kHz–150 kHz)
certification and obtained the CB certificate. voltage ≤ 20 mV (0.15 Mhz–30 MHz)

1 Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.


R4875S5 PSU User Manual V1.1
Other Characteristics
Output Feature Curves
Item Specifications Figure 1 Output feature curve
Protection Characteristics 60
55
Input AC protection threshold: > 300 V AC 50
overvoltage 45
protection AC recovery range: 290 V AC–300 V AC 40

Output Voltage (V)


35
Input AC protection threshold: < 80 V AC
30
undervoltage
protection AC recovery threshold: 80–90 V AC 25
20
Protection range: 56–60 V DC 15
(configurable on the monitoring module) 10
Output 5
overvoltage 1.If overvoltage occurs due to an internal fault,
protection the PSU locks out. 0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
2.If the external voltage is greater than 63 V DC
Output Current(A)
for more than 500 ms, the PSU locks out.

Output
current Figure
Figure22Output
Outputefficiency curve
efficiency (230(230
curves V AC,V25℃)
AC,
See Figure 1.
limiting 25° C)
98.00%
protection
97.50%
97.00%
Output short- A long term short circuit is allowed. After the
circuit fault disappears, the PSU is restored to the 96.50%
protection normal state automatically. 96.00%
95.50%
Efficiency

Overtempera
95.00%
ture Supported
protection 94.50%
94.00%
Safety/EMC/Surge protection 93.50%
93.00% Vout=53.5V
Certification 92.50%
• Complies with IEC 62368-1, IEC 60950-1, Vout=57.0V
Safety UL62368 and UL 60950-1. 92.00%
compliance 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80

Output Current (A)


EN 55032, EN 55024, EN 61000-3-2,
EN 61000-3-3; ETSI EN 300 386, Figure 3 Output power derating curve
EMC
ETSI EN201 468; ETSI EN 301489;
ITU-T K.20 Figure 3 Output power derating curve
4500
Surge
5 kA (8/20 µs) 4000
protection 4000
4000
3500
Reliability 3206
Output Power (W)

3000

Mean time 2500


2400
between
≥ 500,000 hours (at 40°C) 2000
failures
(MTBF) 1500

1000 1000
Acoustic noise
500
Specifications ≤ 55 dB(A) (40°C) 0 0
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80

Ta (℃)

2
R4875S5 PSU User Manual V1.1

Connector Description
Figure 4 Edge connector of the module • To prevent burns, wear protective gloves and exercise caution when
removing the module because it may be hot as a result of
continuous operation.
• If the red indicator is on or the green indicator is off, check the PSU
first and then power it on. (Shake the PSU to check whether there is
abnormal sound, check whether the PSU has an odor, whether the
edge connector is clean and intact, and whether the L/N and PE pins
of the edge connector are short-circuited.) Do not directly power on
the PSU. Otherwise, it may arc or become faulty.

Replacing a Module
Figure 5 Removing a PSU

Step 1: Push the locking latch leftward.


Step 2: Pull out the handle and remove the module
from the subrack.

Figure 6 Installing a PSU


Table 1 Edge connector pin definition

Pins Definitions Function


1–2 DC- Output 48 V–
Step 1: Place a new PSU in the correct slot, push the
3–5 PRE-CHARGE Pre-charge locking latch left, and pull out the handle.
6 PRESENT PSU in-position detection Step 2: Gently push the module along the guide rails
into the subrack, close the handle, and flip the locking
7–8 DC+ Output 48 V+
latch rightward to secure the handle.
9 P_ADJ Power identifying signal 1
Transportation
10 N_ADJ Power identifying signal 2 During transportation, the product must be securely
11 AC_D2 Slot detection signal 2 placed in a packing case. The packing case must
comply with related international standards and be
12 AC_D1 Slot detection signal 1 printed with marks such as "Handle with care" and
13 CANL Low-level CAN bus "Keep dry." The packing case containing the product
can be transported by any means. The packing case
14 CANH High-level CAN bus must be protected against rains, snows, and
15–16 PE Protective earthing mechanical impact during transportation.
Storage
17–18 N AC input neutral wire Unused products must be stored in packing cases and
19–20 L AC input live wire placed in a dry, well-ventilated warehouse where the
temperature ranges from –40°C to +75°C, the
21 AC-PRECHAR Input pre-charge relative humidity is not greater than 80%, and no
corrosive gas exists.
• Only trained and qualified personnel are allowed to install or
maintain the module.
• A fuse is equipped for both the input terminals L and N of the • If this product is installed in an indoor cabinet, you are advised to
module. power the product on within seven days after unpacking. If the
• The operating environment of this product should meet related product cannot be powered on in time, place it in a dry indoor
specifications in the user manual. environment without corrosive gas.
• If the product is used with abnormal grid input or exposed to salt • If this product is installed in an outdoor cabinet, you are advised to
mist, dust, or water mist, the product may become faulty, and the power the product on within 24 hours after unpacking. If the product
resulting product exceptions or component damage are beyond cannot be powered on in time, place it in a dry indoor environment
the warranty scope. without corrosive gas.

3
R4875S5 PSU User Manual V1.1

Maintenance

• The high voltage power supply provides power for the equipment operation. Direct or indirect contact (especially with
a damp object) with the high voltage power supply may result in fatal injury.
• Non-standard and improper high-voltage operations may result in accidents such as fire or electric shock.

To rectify common faults, refer to Table 2.


Table 2 Indicator status and troubleshooting

Indicator Color Status Description Suggestion


Steady on The PSU has an AC input. Normal
Checking whether the ac input is normal.
Power The PSU has no AC input.
Off If the AC input is normal, replace the PSU.
indicator
Green The PSU is damaged. Replace the PSU.
Blinking at 0.5
Querying is in progress. Normal
Hz
Blinking at 4 The PSU is loading the application The PSU automatically recovers after the
Hz program. loading is finished, and no action is required.
The PSU does not generate any
Off Normal
protection alarm.
Alarm A warning is generated due to ambient
indicator overtemperature. Check that the air vent is not blocked and
A shutdown protection alarm is the ambient temperature is within the
generated due to ambient normal range.
Steady on overtemperature or undertemperature.

Yellow AC input overvoltage or undervoltage


Check the power grid voltage.
protection is triggered.
The PSU is hibernating. Normal
The communication between the PSU
and the monitoring module is Replace the PSU or monitoring module.
Blinking at 0.5 interrupted.
Hz
The PSU is being registered for the anti-
Wait until the registration to finish.
theft function.
Off The PSU is normal. Normal
The PSU locks out due to output Remove the PSU and then insert it 1 minute
Fault indicator overvoltage or it is not properly inserted. later.
Steady on
Red The PSU has no output due to an
Replace the PSU.
internal fault.
Blinking at 0.5 Contact the local network administrator to
The PSU locks out to prevent theft.
Hz unlock the module.

Suggestion
1.Rectify faults by referring to the table.
2.If the faults persist, replace the PSU.
3.Return the faulty PSU to Huawei for repair.

Huawei technical support website: Huawei Technologies Co., Ltd.


http://support.huawei.com Huawei Industrial Base, Bantian, Longgang
Tel: +86-755-400-830-2118 Shenzhen 518129 People's Republic of China
www.huawei.com
4

You might also like