Set Point Comparator Am-215A Instruction Manual: Before Using The Product
Set Point Comparator Am-215A Instruction Manual: Before Using The Product
24.0
▲
▲
E M
AL1 AL2
48.0
E M
! Caution
34.2
22.0
(1) The equipment may be damaged if the input current or voltage exceeds
the maximum allowed value.
(2) Only use a supply voltage which is in the usable voltage range. Using a
3.5 84.3
voltage outside this range may result in fire, electric shock, or damage to
the equipment.
(3) Please note that the contents of this manual may be changed without 2.3. Panel attachment procedure
notice due to product modifications.
(4) In preparing this manual, we made every effort to provide the best manual After removing the attachment bands from the main unit, insert the unit
possible. Please contact your dealer or Watanabe if you notice any
deficiencies, errors, omissions, etc. through the front of the panel, and fasten it from the rear side of the panel
(5) After you finish reading the manual, keep it handy for future access. using the attachment bands.
Input range
11:11Range(+-99.99mV)
12:12Range(+-999.9mV)
13:13Range(+-9.999V) POWER !
1V:1VRange(1-5V)
2A:2ARange(4-20mA)
1 2 3 4 5 6 7 8 9
HI LO + - DZ 0V +V
1.2. Standard accessories check INPUT ANALOG TERMINA POWER
OUT TOR
The AM-215A package includes an operating manual (this document) and one unit or
RS485
5-6mm
Follow the dimensions shown in the diagram below in cutting the panel in order
to install the AM-215A Series. Dimensions of terminal
block opening
1.8
+0.5
45.0 -0 M2.5 Phillips screwdriver
Recommended
2.2
+0.3
-0
torque: 0.4 Nm
22.2
* Recommended panel
thickness: 1-8 mm • Make the input signal lines as short as possible. Keep them away from other
signal lines.
• If there is a lot of external noise, use a two-wire shielded cable and form
MIN a single connection between the outer sheath and the LO side at the signal
57
source.
(1) Apply the rated voltage at once (gradually increasing the applied voltage may not turn the machine The smallest digit is 0 or
ON). Normal.
5
(Step wide) The smallest digit is an
(2) The time interval for turning the power ON/OFF should be at least 10 seconds (turning the power The smallest digit is 0
ON/OFF within 10 seconds may not turn the machine ON). even numder.
(3) T h e I N P U T L O , E X C 0 V , a n d C O M t e r m i n a l s a r e a t t h e s a m e p o t e n t i a l , b u t t h e y s h o u l d b e w i r e d
s e p a r a t e l y . (When using a 2-wire sensor, terminals 2-11 should be externally connected.) Brightest Dim Turned off
(4) When no terminals are selected for outputting, do not connect anything to vacant terminals. (Display blanking)
Bright Dimmest
E M 7bit
(Data length)
8bit
*A menu is displayed only the option output form 4.
③ ④ ⑤ ⑥
Even parity No parity
① Main display area: Displays measured values, as well as menus and (Parity bit)
Odd parity
their contents for parameter setting. *A menu is displayed only the option output form 4.
② Check results display area: Displays the check results (when using the
1bit
GO output, neither the AL1 nor the AL2 is (Stop bit)
2bit
flashing). *A menu is displayed only the option output form 4.
③ ENTER switch: Move from the measurement mode to the parameter
CR+LF
setting mode (“ENTER” + “Mode”). (Delimiter)
CR
④ Mode switch: In the parameter setting mode, switch from one item *A menu is displayed only the option output form 4.
to another.
Move to the shift data setting mode (Equipment ID) ~ The ID of RS-485 equipment is set (00 not permitted).
*The default value is 00.
(“Mode” + “Shift”). *A menu is displayed only the option output form 4.
Turn the DZ terminal ON/OFF on the front panel
The digital zero value is stored when the power is turned OFF.
(“Mode” + “Increment”). (DZ Backup)
The digital zero value is not stored when the power is turned
⑤ Shift switch: In the parameter setting mode, switch from one OFF.
If M key is pushed in the state of each menu name or there is no key operation
during 1 second, it will shift to contents selection of a parameter. Moreover,
If M key is pushed in the state of each menu name or there is no key operation when there is no key operation during 8 seconds at the time of selection of the
during 1 second, it will shift to contents selection of a parameter. Moreover, when contents of a parameter, it returns to a menu.
Press twice
there is no key operation during 8 seconds at the time of selection of the contents
of a parameter, it returns to a menu. Numerical value or option
Digit shift
change
Numerical value or option Back to measurement
Digit shift Default value
change operasion
Back to measurement
Default value
operasion
Menu name The contents of a parameter
Menu name The contents of a parameter
(Displayedfull-scale The value to be displayed at the time of FIN signal
~
value) input is set.
(Comparative HI-LO check operation (HI/GO/LO comparative output)
*The default value is 9999.
outputtypr) HH check operation (HH/HI/GO comparative output)
LL check operation (GO/LO/LL comparative output)
F S C : 5000 5000
●Comparative operation type F I N : 9999
OFS : 0
In the AM-215A, use the comparator data to select one type of O I N 0
3000
Input
comparative operation from the three types below: voltage
HI / GO / LO mode 0 10 V
Comparator condition
Output ●Analog output setting
OUT1 OUT2 OUT3
Measurement value > HI limit value OFF OFF ON
The range of displayed values of the AM-215A’s analog output can
LO limit value ≦ Measurement value ≦ HI limit value OFF ON OFF be arbitrarily set, such that it corresponds to the range of 4-20
LO limit value > Measurement value ON OFF OFF mA or 0-10 V. Analog output scaling sets a displayed value to the
HH / HI / GO mode analog output HI that corresponds to 20 mA or 10 V. Likewise, it
Output
sets a displayed value to the analog output LO that corresponds
Comparator condition to 4 mA or 0 V.
OUT1 OUT2 OUT3
Measurement value > HH limit value OFF ON ON The scaling concept is presented below:
Measurement value > HI limit value OFF ON OFF The operation for scaling is the same as that for the displayed
HI limit value ≧ Measurement value ON OFF OFF
value setting.
GO / LO / LL mode :Displayed value when the analog output is 20 mA or 10 V
Output :Displayed value when the analog output is 4 mA or 0 V
Comparator condition
OUT1 OUT2 OUT3
Measurement value ≧ LO limit value OFF OFF ON
O u t p u t : 4-20 mA Output
current current
LO limit value > Measurement value OFF ON OFF
Displayed 20 mA
LL limit value > Measurement value ON ON OFF v a l u e : 0-5000
r a n g e
4.1.3 Scaling Data Setting
●Displayed value setting
The concept of the scaling data and an example setting of a
full-scale value are presented below: A O H I : 5000
AOLO : 0
Displayed value = (a×X) + b 4 mA
a = (Displayed full-scale value - Displayed offset value) / (Input
full-scale value - Input offset value) Displayed
0 5000
b = Displayed offset value - (Input offset value×a) value
range
where
X: Input value; a: Gain; b: Offset ! Caution
When the equipment input range is used, the full scale input values are initially set to 1 V → 5.000
and 2 A → 20.00. The offset input value is 0, so 1 V → 1.000 and 2 A → 4.00 are set.
Instruction Manual for MODEL AM-215A UL 4/4
5. Error messages Comparator unit
Control method : Microcomputer computation
The error message of AM-215A and the solution at the time of an error Setting range : -9999 to +9999
are as follow. Comparator operation : Depends on sampling speed.
Comparator conditions : AL1 and AL2 judging monitor can be turned on at the time of arbitrary
Error Display Details Recovery Response judgment results.
When an input or displayed Use the relay so that input and displayed values HI / GO / LO mode
value is out of the measured are in the measured value range.
value range Output
Comparator condition
When the micro-computer is Make sure that the averaging frequency is not set OUT1 OUT2 OUT3
waiting for data input too high. Measurement value > HI limit value OFF OFF ON
LO limit value ≦ Measurement value ≦ HI limit value
Error in the internal memory of Turn the power of the relay OFF and turn it ON OFF ON OFF
the relay again. If the relay still does not recover, contact LO limit value > Measurement value ON OFF OFF
our dealer or office.
Reset the condition data. HH / HI / GO mode
Condition data error * Change at least one of the data in a parameter
and cycle through all of the other parameters. Output
Comparator condition
Reset the comparator data. OUT1 OUT2 OUT3
Comparator data error * Change at least one of the data in a parameter Measurement value > HH limit value OFF ON ON
and cycle through all of the other parameters.
Measurement value > HI limit value OFF ON OFF
Reset the scaling data. HI limit value ≧ Measurement value ON OFF OFF
Scaling data error * Change at least one of the data in a parameter
and cycle through all of the other parameters. GO / LO / LL mode
Reset the linearize data. Output
Linearize data error * Change at least one of the data in a parameter Comparator condition
and cycle through all of the other parameters. OUT1 OUT2 OUT3
Measurement value ≧ LO limit value OFF OFF ON
Shift data error Reset the shift data. LO limit value > Measurement value OFF ON OFF
LL limit value > Measurement value ON ON OFF
Digital zero value backup data Perform a writing operation for the digital zero
error value. Setting condition : HI / GO / LO mode HI limit value > LO limit value
HH / HI / GO mode HH limit value > HI limit value
GO / LO / LL mode LO limit value > LL limit value
6. Specifications Hysterisis : For each comparator all limit value can be set as 1 to 999 digits.
Input specifications
DC voltage measurements Relay output unit
Output ratings : DC 24 V, 1 A (resistance load)
Range Measurement range Display Input impedance Maximum allowed input
11 ±99.99mV 100 M or greater ±50V Photocoupler output
12 ±999.9mV or greater
100 M ±50V
Offset ±9999 Output ratings : MAX.30V 50mA
13 ±9.999V Full scale ±9999
Approximately 1 M ±50V Output saturation voltage : 1.2V max. at 50mA
1V 1-5 V Approximately 1 M ±50V
Accuracy: ±(0.03% of rdg + 2 digits) (at 23°C± 5°C) Optional unit
Analog output unit(can not be installed together with RS-485)
DC current measurements Output function : 4 to 20mA(AM-215A-XX-6X) or 0 to 10V(AM-215A-XX-7X)
Range Measurement range Display Input impedance Maximum allowed input Output specifications : Mode Load Resistance Accuracy Ripple
4 to 20mA 0 to 250 ±(0.5 % of FS) 25mVp-p max.
2A 4-20mA
Offset ±9999
Full scale ±9999
Approximately 50 ±50 mA 0 to 10V 10k min. ±(0.5 % of FS) 50mVp-p max.
Note) The ripple current for the 4 to 20mA output mode is specified for
Accuracy: ±(0.1% of rdg + 2 digits) (at 23°C ± 5°C)
a load resistance of 250 and an output current of 20mA.
*1
* This accuracy is for (FSC - OFS) / (FIN - OIN) 1
RS-485 unit
* 1: 1V [(FIN-OIN)×2], 2A [(FIN-OIN)×5]
Synchronization method : Start - stop synchronization
Communication method : 2 - wire half-duplex (polling selecting)
General specifications Transfer rates : 38400 / 19200 / 9600 / 4800 / 2400
Measurement function : Select either DC voltage or DC current (single range) Start bit : 1bit
Input circuit : Single ended Data length : 7bits / 8bits
Operation type : Sigma-Delta conversion Parity bit : Even / Odd / None
Sampling speed : Maximum 25 per second Error check : Block check character (BCC) checksum
Display : Red 7-segment LED display (character height: approximately 8 mm) Stop bit : 1bit / 2bits
Polarity display : A minus sign is displayed if the operation result is negative. Character code : ASCII code
Out-of-range warning : "oL" or "-oL" is displayed with respect to the input signal when the value is Delimiter : CR + LF / CR
outside the display range. Transmission control protocol : None
Maximum display : ±9999 (full 4 digits) Used signal name : Non - inverted (+), inverted(-)
Decimal point : Can be set at any position using the front-panel flat switches. Maximum connected units : Maximum 31 meters
Zero display : Leading zero suppress Maximum line length : 500 meters(total) *In EN conformity, it is unber 30m.
Backup : Settings are held in EEPROM (guaranteed for 100,000 writes)
Operating temperature and humidity ranges : 0 to 50°C, 35 to 85% RH (no condensation) 7 Warranty and after-sales service
Storage temperature and humidity ranges : -20 to 70°C, 60% or lower RH (no condensation)
Supply voltage : DC 24 V ±20% 7.1 Warranty
Consumed power : Approximately 2.2 W
External dimensions : 48 24 87.8 The warranty lasts one year from the date of delivery. If
Weight : Weight: Approximately 100 g
Withstand voltage : DC 500 V for one minute across power terminals/input terminals and each
an equipment failure which is considered to be clearly at
output terminal the fault of Watanabe occurs during this period, we will
DC 500 V for one minute across input terminals/each output terminal
AC 1500 V for one minute across case/power terminals, input terminals, and repair the equipment at no charge.
each output terminal
Insulating resistance : 100 M or higher with DC 500 V across the terminals listed above 7.2 After-sales service
Standard accessories : Operating manual, unit seal
Conformity standard : EN61326-1:2006 This product was manufactured, tested, and inspected according
E247481
External control unit
to rigorous quality control procedures before it was shipped from
Digital zero : Digital Zero is turned ON when the DZ terminal and terminal are shorted or the factory. If an equipment failure should occur, please contact
at the same potential.
your dealer or Watanabe(send the product to us). (Along with the
External power supply unit
Rating : DC 24 V ±5% failed product, please include a description with as much
Maximum load : 25mA information as possible.)
6-16-19,
6-16-19,Jingumae,
Jingumae,Shibuya-ku,
Shibuya-ku,Tokyo
Tokyo150-0001,
150-0001,Japan
Japan
WATANABE ELECTRIC INDUSTRY CO., LTD. Phone:
Phone:(81)3-3400-6140
(81)3-3400-6141
WATANABE ELECTRIC INDUSTRY CO., LTD. Homepage
Homepage http://en.watanabe-electric.co.jp/
http://www.watanabe-electric.co.jp/en/
ASAHI KEIKI DIVISION
(UX-34106j)
Digital panel meter 2. Shift function
MODEL AM-215A Series
Linearize function 2.1 View
/Shift functional handling description
This shift function is a function which shifts display value
compulsorily (offset), and the uncontrollable numerical
1. Linearize compensation function specification of it is attained in digital zero.
1.1 View 2.2 The operation method
This linearize function depends the linearity between (Measurement
operation)
compensation mark on input value (display value before (3 times)
compensation), and output value (display value after
compensation).
Displa About 1 second
y -9999~+9999 The display value offset is inputted.
The rectifying point
3 *The default value is 0.
9999 Digit shift Numerical value or option
change
*When there is no key operation during about 8 seconds, it returns
to "SHF" display. Furthermore, when there is no key operation
After [ compensation ] during about 8 seconds in the state of "SHF" display, it returns to
straight line
measurement operation.
Front
6000 [ compensation ] The value set up by M key is memorized and it checks that it is the display
straight line which contained shift operation to the display value equivalent to the
5000 present input.
The rectifying
point 2 Cautions :
The display will return to the setting of a shift value if M key has
pressed more than twice.
Then please set a shift value again.
If you return to measurement operation without resetting,
the shift value will affect the display value,
but please note that set value will not be backed up.
Input
0 The rectifying *When there is no key operation during about 8 seconds, it returns
5[V] 10[V]
point 2
to "SHF" display. Furthermore, when there is no key operation
① A rectifying point is set up with 3. (Measurement during about 8 seconds in the state of "SHF" display, it returns to
②The input value (0) and the output value (0) of the rectifying point 1 are set up. operation) measurement operation.
③Since the value (scaling is an initial state) when inputting the rectifying point 2 5V to 13 ranges turns into However, the memorized offset value (shift value) is reflected in
input value, input value is set up with 5000 and output value is set up with 6000. display value.
④The input value (9999) and the output value (9999) of the rectifying point 3 are set up.
Wish
1.2 The operation method
Setting range of a shift function Although it becomes the range of -9999 to 9999,
(Measurement operation)
if a shift setup is carried out after setting up comparator data,
the setting range of a shift may turn into the range of 0 to 9999,
In the state of the input value / output value of rectifying point X, when and it may not be able to perform a setup by the side of minus.
there is no key operation during about 8 seconds (0 etc.), it returns to
3 times
the display of n-XX.
Numerical value or option
Digit shift
change
Back to measurement
Default value
operasion
(Rectifying point
1 setup)
(Rectifying point -9999~+9999 The input value (display value before linearity
1 input value) compensation) of the rectifying point 1 is inputted.
*Setting condition (rectifying point n input value) >
(rectifying point n-1 input value)
(Rectifying point
2 setup)
(Rectifying point -9999~+9999 The input value (display value before linearity
2 input value) compensation) of the rectifying point 2 is inputted.
*Setting condition (rectifying point n input value) >
(rectifying point n-1 input value)
(Rectifying point -9999~+9999 The output value (display value before linearity
2 output value) compensation) of the rectifying point 2 is inputted.
(Rectifying point
16 setup)
(Measurement operation)
2014.04
WATANABE ELECTRIC INDUSTRY CO., LTD UX-48894c
User’s Manual AM-215A Series RS-485 1/8
AM-215A Series
RS-485 User’s Manual
1. Overview
This manual explains the specifications of the communication functions provided by the AM -215A series of digital
panelmeters. It also explains how to handle the AM -215A series.
2. Specifications
Synchronization : Start-stop
Communication method : Two-wire half-duplex (polling/selecting)
Transmission rate : 2400, 4800, 9600, 19200, 38400 bps
Number of start bits : 1bit
Data length : 7bits, 8bits
Parity bit : Even parity, odd parity, or no parity
Error detection : Block check character (BCC) checksum
Number of stop bits : 1bit, 2bits
Character code : ASCII
Delimiter : CR+LF, CR
Transmission control procedure : Non-procedural
Signal name used : Non-inverting (+), inverting (-)
Number of units that can be connected : 31 for meters
Transmission line length : 500 m max. (overall length)
*In EN conformity, it is under 30m.
POWER !
1 2 3 4 5 6 7 8 9
HI LO + - DZ 0V +V
Note: A terminator will be set to being turned on if No. 5 and No. 6 are short-circuited.
UX-34109f
WATANABE ELECTRIC INDUSTRY CO., LTD. 2017.02
User’s Manual AM-215A Series RS-485 2/8
+ +
AL1 AL2
RS-485/ - E M
RS-232C
converter -
SG
+
AL1 AL2
+ AL1 AL2
E M
Note: If the panelmeter is an end station, set the terminator to ON. -
As a means of error detection, a block check character (BCC) checksum is added to the RS -485 communication function
of the AM-215A panelmeter. See the following illustrations for details on the transmission and reception formats.
6. Communication Commands
Function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Char. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Char.
Length Length
Measured value and comparison D S P CR LF 3 5 0 0 0 H I CR LF 10
results response (+ reading, w/o decimal point)
- 5 0 0 0 H I CR LF 10
(- reading, w/o decimal point)
5 0 0 . 0 H I CR LF 11
(+ reading, w/ decimal point)
< = 9 8 0 0 H I CR LF 10
(+ overrange reading, w/o decimal point)
< = - 9 8 0 . 0 H I CR LF 11
(- overrange reading, w/ decimal point)
Trigger input T CR LF 1 5 0 0 . 0 H I CR LF 11
(+ reading, w/ decimal point)
Note: The response is the same as that of “DSP”.
Hold remote control cancellation E S M CR LF 3 Y E S CR LF 5
User’s Manual AM-215A Series RS-485 4/8
Digital zero remote control response D Z R CR LF 3 D Z R O F F CR LF 7
(Response with the status of the digital zero function being set to OFF by
remote control)
D Z R 1 0 0 0 CR LF 9
(Response with the status of the digital zero function being set to ON by
remote control)
Note: The main unit responds with the reading when the digital zero function is
set to ON.
Device ID response A D R CR LF 3 A D R 0 1 CR LF 6
(Response with the status of the device ID being 01)
A D R 9 9 CR LF 6
(Response with the status of the device ID being 99)
Device ID setting A D R 0 1 CR LF 6 Y E S CR LF 5
(Sets the device ID to 01.)
A D R 9 9 CR LF 6 Y E S CR LF 5
(Sets the device ID to 99.)
N O ? CR LF 5
(Response with the status of digital zero backup being OFF.)
8 0 0 0 CR LF 4 S - H I 8 0 0 0 CR LF 10
(Sets the HH-side judgment value to 8000.)
N CR LF 1 S - L O 5 0 0 CR LF 10
4 0 0 0 CR LF 4 S - L O 4 0 0 0 CR LF 10
(Sets the HI-side judgment value to 4000.)
N CR LF 1 H - H H 0 CR LF 10
N CR LF 1 H - H I 0 CR LF 10
N CR LF 1 L - H H N . O CR LF 8
N . C CR LF 3 L - H H N . C CR LF 8
R CR LF 1 Y E S CR LF 5
Note: If an R command is sent after setting required data, the main unit saves data provided
up to that moment and then returns to measurement operation. E r r o r CR LF 6
(Response when a value that does not meet the setting conditions is input.)
User’s Manual AM-215A Series RS-485 7/8
Scaling data response M E T CR LF 3 F S C 9 9 9 9 CR LF 10
Note: The reading of the main unit changes to MET the moment it receives an MET command. (Response with a full-scale reading.)
N CR LF 1 F I N 9 9 9 9 CR LF 10
(Response with a full-scale input value.)
N CR LF 1 O F S 0 CR LF 10
(Response with an offset reading.)
N CR LF 1 O I N 0 CR LF 10
(Response with an offset input value.)
N CR LF 1 D L H I 9 9 9 9 CR LF 10
(Response with the HI value of the digital limiter.)
N CR LF 1 D L L O - 9 9 9 9 CR LF 10
(Response with the LO value of the digital limiter.)
N CR LF 1 D E P 4 CR LF 6
(Response with the position of the decimal point.)
R CR LF 1 Y E S CR LF 5
Note: The main unit returns to measurement operation upon an R command (or returns to
the response with the full-scale reading if an N command is sent.)
N CR LF 1 O F S 0 CR LF 10
2 0 CR LF 2 O F S 2 0 CR LF 10
(Sets the offset reading to 20.)
R CR LF 1 Y E S CR LF 5
Note: If an R command is sent after setting required data, the main unit saves data provided
up to that moment and then returns to measurement operation. E r r o r CR LF 6
(Response when a value outside the setpoint range is input.)
- 9 0 0 CR LF 4 L N D 0 1 O = - 9 0 0 CR LF 14
(Sets the output value of linearization data N-01 to -900.)
N CR LF 1 L N D 0 2 I = 0 CR LF 14
- 5 0 0 CR LF 4 L N D 0 2 I = - 5 0 0 CR LF 14
(Sets the input value of linearization data N-02 to -500.)
N CR LF 1 L N D 0 2 O = 0 CR LF 14
- 6 0 0 CR LF 4 L N D 0 2 O = - 6 0 0 CR LF 14
(Sets the output value of linearization data N-01 to -600.)
・
・
・
R CR LF 1 Y E S CR LF 5
Note: If an R command is sent after setting required data, the main unit saves data provided
up to that point and then returns to measurement operation. E r r o r CR LF 6
(Response when a value outside the setpoint range is input.)
User’s Manual AM-215A Series RS-485 8/8
Common response Y E S CR LF 5
(Normal response)
N O ? CR LF 5
(Response to, e.g., undefined commands.)
E r r o r CR LF 6
(Response to out-of-range data or data that do not meet setting conditions.)
E R R O R A CR LF 7
(Response when there is any communication parameter failure.)
Note: Under normal conditions, this response is made only once.
Note: ERROR B to ERROR F are available as the response commands for
acknowledgment.
Note: If a response to the ERROR X command is received, execute the same
processing once again. If the panelmeter still does not recover, turn off the
panelmeter once and then turn it on again.
Response in case of data failure in the D A T A L O S T C O N D CR LF 14
internal memory (Response in case of condition data failure.)
Note: Under normal conditions, this Note: Set the condition data again.
response is made only once. D A T A L O S T C O M CR LF 13
(Response in case of comparator data failure.)
Note: Set the comparator data again.
D A T A L O S T M E T CR LF 13
(Response in case of scaling data failure.)
Note: Set the scaling data again.
6-16-19,
6-16-19,Jingumae,
Jingumae,Shibuya-ku,
Shibuya-ku,Tokyo
Tokyo150-0001,
150-0001,Japan
Japan
WATANABE ELECTRIC INDUSTRY CO., LTD. Phone:
Phone:(81)3-3400-6140
(81)3-3400-6141
WATANABE ELECTRIC INDUSTRY CO., LTD. Homepage
Homepage http://en.watanabe-electric.co.jp/
http://www.watanabe-electric.co.jp/en/
ASAHI KEIKI DIVISION
(UX-34108f)