Building Systems Design MidTerm Lesson Rev.
Building Systems Design MidTerm Lesson Rev.
___________________
Lesson 1: The National Building Code of the Philippines
The National Building Code is a set of
Learning Outcomes:
rules and regulations pertaining to the
At the end of the lesson, you are
construction of all residential projects
expected to: and buildings here in the Philippines.
1. know some important provisions Building codes are intended to further
of the code; and secure safety, welfare and health of the
2. apply the code to building design residents of a building.
GENERAL PROVISIONS
Section 101. Title. This Decree shall be known as the "National Building Code of the
Philippines" and shall hereinafter be referred to as the "Code".
1
Code shall not be affected thereby except when alterations, additions, conversions or
repairs are to be made therein in which case, this Code maintenance.
Section 103. Scope and Application. (a) The provisions of this Code shall apply to
the design, location, sitting, construction, alteration, repair, conversion, use,
occupancy, maintenance, moving, demolition of, and addition to public and private
buildings and structures, except traditional indigenous family dwellings as defined
herein. (b) Building and/or structures constructed before shall apply only to portions
to be altered, added, converted or repaired.
Section 105.Site Requirements. The land or site upon which will be constructed any
building or structure, or any ancillary or auxiliary facility thereto, shall be sanitary,
hygienic or safe. In case of sites or buildings intended for use as human habitation or
abode, the same shall be at a safe distance, as determined by competent authorities,
from streams or bodies of water and/or sources of air considered to be polluted; from
a volcano or volcanic site and/or any other building considered to be a potential
source of fire or explosion.
TYPES OF CONSTRUCTION
Section 401. Types of Construction. For purposes of this Code, all buildings proposed
for construction shall be classified or identified according to the following types:
Type II. Type II buildings shall be of wood construction with protective fire-
resistant materials and one-hour fire resistive throughout: Except, that permanent
non-bearing partitions may use fire-retardant treated wood within the framing
assembly.
Type III. Type III buildings shall be of masonry and wood construction.
Structural elements may be any of the materials permitted by this Code: Provided,
that the building shall be one-hour fire-resistive throughout. Exterior walls shall be of
incombustible fire-resistive construction.
2
Type V. Type V buildings shall be fire-resistive. The structural elements shall
be of steel, iron, concrete, or masonry construction. Walls, ceilings, and permanent
partitions shall be of incombustible fire-resistive construction.
Section 501. Fire Zones Defined. Fire zones are areas within which only certain types
of buildings are permitted to be constructed based on their use or occupancy, type of
construction, and resistance to fire.
Section 502. Buildings located in more than One Fire Zone. A building or structure
which is located partly in one fire zone and partly in another shall be considered to be
in the more highly restrictive fire zone, when more than one-third of its total floor area
is located in such zone.
OTHER PROVISIONS
The allowable floor areas for one-storey building and buildings over one-storey shall
not exceed the limits prescribed by the Secretary for each occupancy groups and/or
types of construction. For purposes of this Section, each portion of a building
separation by one or more area separation walls may be considered a separate
building provided the area separation walls meet the requirements prescribed
therefor by the Secretary.
The floor areas hereinabove provided may be increased in certain specific instances
and under appropriate conditions, based on the existence of public space, streets or
yards extending along and adjoining two or more sides of the building or structure
subject to the approval of the Building Official.
The maximum height and number of storeys of every building shall be dependent
upon the character of occupancy and the type of construction as determined by the
Secretary considering population density, building bulk, widths of streets and car
parking requirements.
The height shall be measured from the highest adjoining sidewalk or ground surface:
Provided, that the height measured from the lowest adjoining surface shall not
exceed such maximum height by more than 3.00 meters: Except, that towers, spires,
and steeples, erected as part of a building and not used for habitation or storage are
limited as to height only by structural design if completely of incombustible materials,
or may extend not to exceed 6.00 meters above the height limits for each occupancy
group if of combustible materials.
(a) Dwelling Location and Lot Occupancy. The dwelling shall occupy not more
than ninety percent of a corner lot and eighty percent of an inside lot, and
subject to the provisions on Easement on Light and View of the Civil Code of
the Philippines, shall be at least 2 meters from the property line.
3
(b) Light and Ventilation. Every dwelling shall be so constructed and arranged
as to provide adequate light and ventilation as provided under Section 805, of
this Code.
(c) Sanitation. Every dwelling shall be provided with at least one sanitary toilet
and adequate washing and drainage facilities.
(d) Foundation. Footing shall be of sufficient size and strength to support the
load of the dwelling and shall be at least 250 millimeters thick and 600
millimeters below the surface of the ground.
(e) Post. The dimensions of wooden post shall be those found in Table 708-A
Dimensions of Wooden Posts (Annex B-1). Each post shall be anchored to
such footing by strap and bolts of adequate size.
(f) Floor. The live load of the first floor shall be at least 200 kilograms per
square meter and for the second floor, at least 150 kilograms per square
meter.
(g) Roof . The wind load for roofs shall be at least 120 kilograms per square
meter for vertical projection.
(h) Stairs. Stairs shall be at least 750 millimeters in clear width, with a rise of
200 millimeters and a minimum run of 200 millimeters.
(i) Entrance and Exit. There shall be at least one entrance and another one for
exit. (j) Electrical Requirements. All electrical installation shall conform to the
requirements
(a) Subject to the provisions of the Civil Code of the Philippines on Basement
of Light and View and to the provisions of this part of the Code, every building
shall be designed, constructed, and equipped to provide adequate light and
ventilation.
(b) All buildings shall face a street or public alley or a private street which has
been duly approved.
(c) No building shall be altered nor arranged so as to reduce the size of any
room or the relative area of windows to less than that provided for buildings
under this Code, or to create an additional room, unless such additional room
conforms to the requirements of this Code.
(d) No building shall be enlarged so that the dimensions of the required court
or yard would be less than that prescribed for such building.
4
Section 805. Ceiling Heights.
(a) Habitable rooms provided with artificial ventilation have ceiling heights not
less than 2.40 meters measured from the floor to the ceiling; Provided that for
buildings of more than one-storey, the minimum ceiling height of the first
storey shall be 2.70 meters and that for the second storey 2.40 meters and
succeeding storeys shall have an unobstructed typical head-room clearance
of not less than 2.10 meters above the finished floor. Above stated rooms with
a natural ventilation shall have ceiling height not less than 2.70 meters.
(b) Mezzanine floors shall have a clear ceiling height not less than 1.80
meters above and below it.
(a) Minimum sizes of rooms and their least horizontal dimensions shall be as
follows: 1. Rooms for Human Habitations. 6.00 square meters with at least
dimensions of 2.00 2. Kitchens. 3.00 square meters with at least
dimension of 1.50 meters; 3. Bath and toilet. 1.20 square meters with at
least dimension of 0.90 meters.
(a) Minimum space shall be provided as follows: 1. School Rooms. 3.00 cubic
meters with 1.00 square meter of floor area per person; 2. Workshops,
Factories, and Offices. 12.00 cubic meters of space per person; 3.
Habitable rooms. 14.00 cubic meters of space per person.
(a) Every room intended for any use, not provided with artificial ventilation
system as herein specified in this Code, shall be provided with a window or
windows with a total free area of openings equal to at least ten percent of the
floor area of room, and such window shall open directly to a court, yard, public
street or alley, or open water courses.
(a) Skylights shall have glass area not less than that required for the windows
that are replaced. They shall be equipped with movable sashes or louvers
with an aggregate net free area not less than that required for openable parts
in the window that are replaced or provided with approved artificial ventilation
of equivalent effectiveness.
5
(a) No part of any building or structure or any of its appendages shall project
beyond the property line of the building site, except as provided in this Code.
(b) The projection of any structure or appendage over a public property shall
be the distance measured horizontally from the property line to the outermost
point of the projection.
(a) No part of any structure or its appendage shall project into any alley or
street, national road or public highway except as provided in this Code.
(b) Footings located at least 2.40 meters below grade along national roads or
public highway may project not more than 300 millimeters beyond the
property line.
(a) The extent of any projection over an alley or street shall be uniform within
a block and shall conform to the limitations set forth in Table 1003-A of the
code; Projection of Balconies and Appendages (Annex B-2);
(b) The clearance between the established grade of the street and/or sidewalk
and the lowest under surface of any part of the balcony shall not be less than
3.00 meters.
6
(c) Construction. A marquee shall be constructed of incombustible material or
materials of not less than twohours fire-resistive construction. It shall be
provided with necessary drainage facility.
(d) Location. Every marquee shall be so located as not to interfere with the
operation of any exterior standpipe connection or to obstruct the clear
passage from stairway exits from the building or the installation or
maintenance of electroliers.
(b) Clearance. The horizontal clearance between the awning and the curb line
shall not be less than 300 millimeters. The vertical clearance between the
undermost surface of the awning and the pavement or ground line shall be not
less than 2.40 meters. Collapsible awnings shall be so designated that they
shall not block a required exit when collapsed or folded. Section 1007. Doors,
Windows, and the like. Doors, windows and the like less than 2.40 meters
above the pavement or ground line shall not, when fully opened or upon
opening, project beyond the property line except fire exit doors.
(a) Every corner building or solid fence on a public street or alley less than
3.60 meter in width shall be truncated at the corner. The face of the triangle
so formed shall be at right angles to the bisector of the angle of the
intersection of the street lines; provided, that in no case, the Secretary shall
determine the size and form of the chaflan.
Note: For other provisions of the code please refer to this link:
1. http://www.humanitarianlibrary.org National Building Code of the Philippines
2. http://www.academia.edu The National Building Code of the Philippines
7
to periodic changes without legislative flat to be in accordance with universal
advancements in science and technology. It prescribes rules and regulatory
measures to ascertain good building design and construction with inherent
considerations and provisions for the safety and protection of limb, health, life,
property and general public welfare, within a sound/wholesome environmental set-up.
GENERAL
The following considerations should guide the architect in the total design of the
building and other structures in accordance with the Declaration of Policy of this
code.
8
efficiently serve its purpose while protecting life, health, property and general
public welfare and concomitant resource of civic pride and aspirations.
2. Buildings and other structures intended to be used for the manufacture and
production of any kind of article or product shall comply with adequate
environmental safeguards as provided by all government agencies
concerned.
3. Buildings and structures together with all parts thereof as well as their adjunct
facilities, utilities and equipment therein shall be maintained in good repair,
safe, sanitary, and good working condition as originally approved for
occupancy.
1. The land or site upon which the building or structure or any adjunct or
ancillary facility thereof shall be the concern of the architect. He shall verify,
survey, and ascertain safe design determinants such as geodetically and
geophysical characteristics, the potential chronological or periodic flooding,
soil conditions of the site, and other potentials hazard such as volcanic
eruption, pollution, landslides, tsunami. Other environmental factors shall also
be considered such as: solar angles, prevailing, typhoon winds and
orientation to significant views.
2. Siting of the building shall be governed by NBC-IRR as to allowable buildable
area on lots actual characteristics of physical boundaries.
DEFINITIONS
ALLEY An alley is a narrow lane for pedestrians or service that runs between or
behind buildings. Alleys used to be planned into cities for trash access, deliveries,
electrical, plumbing, and mechanical services, fire engines, and for parking.
9
ARCADE A roofed passageway of a building, covered pedestrian passage or
covered sidewalk built as protection for pedestrians against rain or sun.
ATTIC STOREY Any storey situated wholly or partly in a roof, so designed, arranged
or built as to be used for any occupancy or habitation.
BALCONY A platform projecting from a wall protective railing around its periphery.
Also, an elevated tier of seats over an assembly hall, the lowest part of which is
raised 1.20 m. or more above the level of the main floor.
BALCONY EXTERIOR EXIT A landing or porch projecting from the wall of a building
which serves as a means of egress. The open area above the guardrail shall remain
open so as to prevent the accumulation of smoke or toxic gas.
BAY OR PANEL The intervals or spaces between two adjacent pillars, columns, or
buttresses into which the building front is divided.
BOARDING HOUSE are buildings containing several similarly furnished and fully
equipped apartments. They differ from apartment hotels in that they can often be
rented for a longer period of time. Boarding houses offer residents a washing
machine in the apartments or the building, as well as a fully equipped kitchen.
BUIDABLE AREA The remaining space in a lot after deducting the required
minimum open spaces for light and ventilation.
BUILDING a structure (such as a house, hospital, school, etc.) with a roof and walls
that is used as a place for people to live, work, do activities, store things, etc. : the act
or process of making structures by putting together materials.
10
BUILDING LENGTH a building means a building's greatest horizontal distance or
dimension.
BUILDING WIDTH Lot width means the distance on a horizontal plane between the
side lot lines of a lot, measured at right angles to the line establishing the lot depth at
the established building setback line. Lot width categories are determined by a range
of plus or minus 1.0m.
CASING a wood, metal or plastic covering or trim around the door or window frame.
COPING the material or units to form or serve as a cop or finish on top of a wall, pier,
parapet or pilaster.
COURT an unoccupied space enclosed by buildings and lot lines other than a yard;
free, open, and unobstructed clear area of any appendages from the ground upward.
EXIT, FIRE a means of exiting a building in the event of fire. You're not allowed to put
anything in front of this door as it is a fire exit.
EASEMENT An easement is a no possessory right to use and/or enter onto the real
property of another without possessing it. It is "best typified in the right of way which
one landowner, A, may enjoy over the land of another, B".
EXIT COURTS a yard or court providing safe egress to a public way for one or more
exits.
11
EXIT (HORIZONTAL) WAY In essence, the horizontal exit is an exit that allows
occupants to egress from one side of a building to another side through a fire-
resistance-rated assembly, such as a fire wall or fire barrier.
FACING any masonry, forming an integral part of a wall used as a finished surface to
veneer or wainscot.
FIRECLAY clay capable of withstanding high temperatures, chiefly used for making
firebricks.
FIRE SEPARATION (WALL) is the method for protecting buildings from the spread
of fire into adjoining areas for designated time periods by the introduction
of fire resisting walls, floors, doors, ducts and so on. These constructions divide the
building into distinct fire zones called 'fire compartments'.
FIREWALL is a network security device that monitors incoming and outgoing network
traffic and permits or blocks data packets based on a set of security rules.
ROW HOUSE one of a row of houses having uniform, or nearly uniform, plans and
fenestration and usually having a uniform architectural treatment, as in
certain housing developments. a house having at least one side wall in common with
a neighboring dwelling.
12
FIRE-RESISTIVE STANDARDS
All materials of construction and type of materials and assemblies or combinations
thereof shall conform to the following fire-resistive ratings:
Chapter I - General Requirements. The following changes are made in this code:
Section 103 - Classification of Buildings School buildings of more than one storey,
hospitals and designated evacuation centers are added under the essential
facilities category.
Section 104 - Design Requirements
Deflection of any structural member under the serviceability requirement is
deleted. For concrete and steel materials see Chapter 4 and 5 respectively;
new requirements are added to the design review section.
3Section 105 - Posting and Instrumentation
The provision of installed recording accelerograph is adjusted.
Chapter 2 - Minimum Design Loads. The changes made in this code arc as follows:
Sect ion 203 - Combination of Loads
The load factor values on wind 10"d5 are adjusted together with the inclusion
of rain loads.
Section 205 - Live Loads
Additional loads are incorporated in the table for minimum uniform and
concentrated loads.
Section 207 - Wind Loads
Wind load provisions, which were previously based on ASCE7-95. are
updated by the introduction of the Wind Directionality Factor, Kd , based on
ASCE7-05. The ANSI ElAfTIA-222-G is also referenced for wind loads on
antennas.
Equations for the gust effect factors for both rigid and flexible structures are
introduced. These include the gust effect factor for antennas. transmission
and latticed towers. poles/posts. masts and transmission lines based on
13
ASCE Manual of Practice No.74 (Guidelines for Electrical Transmission Line
Structural Loading).
New formulas are also introduced for the natural frequency and damping ratio.
Section 208 _ . Earthquake Loads
Basically , there are no major changes on the earth quake provisions due to
the availability of Phivolcs-issued spectral acceleration maps for all areas in
the Philippines. However, ASCE/SEI7-05 is recognized as an alternative
procedure in the determination of the earthquake loads.
Section 210 and Section 211 - Environmental Loads
New sections on rain loads and flood loads are added.
Chapter 3: Specification for Excavations and Geo materials. The revisions made in
this updated code arc as follows:
Section 3.I Provisions pertaining to the conduct and interpretation of foundation
investigations for cases involving liquefiable. expansive or questionable soils
arc adopted;
Section 3.2 The section on footings is amended 10 incorporate provisions for
differential settlement. design loads and vibratory loads;
Section 3.3 The section on pile foundations is amended to incorporate new provisions
on splicing of concrete piles; and
Section 3.4 The section on special foundations, slope stabilization and materials of
construction arc added.
Chapter 4: Structural Concrete. The revisions made in this updated code are as
follows:
Section 40 I - Genera l Requirements: Design requirements for earthquake-resistant
structures are updated based on ACI 318-08M which mentions the "Seismic
Design Categories (SDCs)" of ASCEISEI 7-05. However. in the absence of
Phlvolcs-issued spectral acceleration maps for all areas in the Philippines, the
seismic loading procedures based on ASCE/SEI 7-05 is adopted as an
alternative procedure (see Section 208- 11). Therefore. based on the
Commentary of ACI 318·08. Seismic Zone 2 (lIB ( 7) was adopted in lieu 0 1"
SDC C (ASCE/SEI 7-()5). Similarly, Seismic ZOIlC 4 is adopted in lieu 0 1"
SDC, D, '" and F;
Section 403 - Materials: New requirements for headed shear stud reinforcement,
headed deformed bars, and stainless steel bars are given with appropriate
references to ASTM standards;
Section 404 ~ Durability Requirement: Exposure categories and classes,
requirements or concrete by exposure class arc adopted to replace the many
tables of durability requirements in Section 404, making it easier to clearly
specify the intended application;
Section 405 - Concrete Quality, Mixing, and Placing: The use of three 100 mm x 200
mm cylinders is adopted as equivalent to the usc of two 150 mill x 300 mm
cylinders for determining concrete compressive strength. Due to concern that
material properties may change with time, a 12-11l0nth limit is set on historical
data used to qualify mixture proportions and flexural test performance criteria
are added to qualify the use of steel fiber - reinforced concrete as a
replacement for minimum shear reinforcement;
Section 407 - Details of Reinforcement: To avoid the misconception that there is no
minus tolerance on cover values given in the code, "minimum cover" is
14
replaced with "specified cover" throughout Section 407; Class B lap splices
are now required for structural integrity reinforcement; continuous top and
bottom structural integrity reinforcement are required to pass through the
column core; and requirements for transverse reinforcement confining
structural integrity reinforcement in perimeter beams are clarified;
Section 408 - Analysis and Design - General Considerations: Provisions arc modified
10 allow redistribution of positive moments; and a simple modeling procedure
for evaluation of lateral displacements is added;
Section 409 ~ Strength and Serviceability Requirements: Strength reduction factors
for compression-controlled sections (other structural members) is reduced
from 0.70 to 0.65, and shear and torsion for shear walls and frames in Seismic
Zone 4 is reduced from 0.85 to 0.75, bearing on concrete (except for post-
tensioning anchorage zones) is reduced from 0.70 to 0.65. Strength reduction
factors for strut-and-tie models, flexural sections in pretensioned members,
are also added;
Section 410 - Flexure and Axial Loads: The section on slenderness effects is
reorganized to recognize computer analysis techniques as the primary
method of evaluating second order effects:
Section 411 ~ Shear and Torsion: Code requirements are added to permit the list of
headed stud assemblies as shear reinforcement for slabs and footings. The
nominal shear strength is permitted (0 be larger for headed stud assemblies
than for other forms of slab and footing shear reinforcement; more stringent
limits are placed on the depths of beams that are exempted from the
requirement for minimum shear reinforcement; a new limit 011 the depth of
hollow core units for which minimum shear reinforcement could be waived is
established; steel fiber-reinforced concrete is added as an alternative to
minimum shear reinforcement: and the upper limit on shear friction strength is
significantly increased for monolithically placed concrete and concrete placed
against intentionally roughened concrete;
Section 412 - Development and Splices of Reinforcement: Provisions are added for
the development length of headed deformed bars; splice length when splicing
bars with different sizes is addressed; and a coating factor of 1.0 for
galvanized reinforcement is added;
Section 413 - Two-Way Slab Systems: Dimension limits are added for the use of
shear caps; and alternative corner reinforcement arrangement is added for
two-way slabs supported of edge beams or walls;
Section 414 . - Walls: Design provisions for slender wall panels are modified to be
more
consistent with the methods used in design practice;
Section 418 - Prestressed Concrete: The allowable concrete compression stress
immediately after prestress transfer is increased; and requirements for
structural integrity steel in two-way unbondcd post-tensioned slab systems are
modified;
Section 4.20 - Strength Evaluation of Existing Structures: Load factors for
determining
the required test load are modified to reflect typical modern load
combinations;
15
Section 421 - Earthquake-Resistant Structures: This section presents the
requirements for Seismic Resistant Design from ASCEISEI 7-05, but instead
of using the Seismic Design Categories of ASCESEI 7-05, the equivalent
Seismic Zones as per UBC 1997 are specified. Also, new design
requirements are added for such seismic zones; newdetailing option is added
for diagonally reinforced coupling beams; design yield strength for
confinement reinforcement is raised to 690 MPa to help reduce congestion;
and boundary element confinement requirements is relaxed;
Section 423 - Anchoring to Concrete: Use of reinforcement in the vicinity of anchors
and ductility requirements for anchors in seismic zones arc clarified.
Section 425 - Alternative Provisions for Reinforced and Prestressed Concrete
Flexural
and Compression Members: Revisions in Appendix B of ACI 318-08M is
adopted;
Section 426 - Alternative Load and Strength Reduction Factors: Revisions in
Appendix
C of ACI 318-08M is adopted; and
Section 427 - Strut-and-tie Models: Appendix A of ACI 318-08M is adopted in its
entirety.
Chapter 5: Structural Steel. The revisions made in this updated code are as follows:
Section 5.1 Adopted is an integrated treatment of the Allowable Stress Design (ASD)
and the Load and Resistance Factor Design (L...RFD) such that the earlier
Specification that treated only the ASD method is retained;
c.2 In lieu of the previous method of analysis, a new method (Direct Analysis
Method) is adopted: and
Section 5.2 The cold formed steel design for building systems and structural
members are included. The chapter on steel design from NSCP 2001 which
covered Allowable Working Stress Design (ASD) is fully updated (0 address
usage, advances in the state of knowledge, and changes in design practice.
Chapter 6: Wood
Section 6.I The provisions in this chapter arc refined to incorporate local practices
and
corrections in the previous version of the code (NSCP 2(01). Referrals arc
made to the NSCP 2010 Vol. III on Housing for relevant provisions concerning
single-family dwellings / low-cost housing;
Section 6.2 Tables from the previous version of NSCP 2001 including the Table
containing specie design information are amended to incorporate the latest
updated information/ list of wood species as provided by the Forest Products
Research and Development Institute (FPRDl);
Section 6.3 A provision that limit the use of wood shear walls and diaphragms is
added;
and
Section 6.4 A section for Machine Graded Lumber (MGL) is included.
Chapter 7: Masonry
Section 7.1 The provisions in this chapter are refined to include local practices and
16
corrections from the previous version of the code (NSCP 2001); referrals are
made to the NSCP 2010 Vol. III on Housing for relevant provisions concerning
single-family dwellings / low-cost housing;
Section 7.2 Recycled aggregates are defined and provided;
Section 7.3 A section for Seismic Design is added; and
Section 7.4 Additional sections each for Masonry Fireplaces and Masonry Chimneys
are included.
Note: Visit this link for more readings www.scribd.com national structural code of the philippines
C. Apartment Buildings – includes buildings containing three (3) or more living units
independent cooking and bathroom facilities, whether designated as condominium,
row house, apartment house, tenement, garden apartment, or by any other name.
17
persons, on either a transient or permanent basis; with or without meals, but without
separate cooking facilities for individual occupants.
1. No door in any means of egress shall be locked against egress when the
building is occupied.
2. No residential occupancy shall have its means of egress pass through any
non-residential occupancy in the same building, except in buildings provided with
approved, supervised sprinkler system provided that the means of egress shall not
pass through a high hazard content 171 area as determined by the City/Municipal
Fire Marshal having jurisdiction and the means of egress shall be separated by a
construction of not less than 1 hour.
A. Requirements
1. Any ballroom assembly or exhibition hall, and other space used for purposes of
public assembly shall be in accordance, with Division 7 of this Chapter.
Restaurant having a capacity of fifty (50) or more persons shall be treated as
places of assembly.
2. Any dormitory divided into suites of rooms, with one or more bedrooms opening
into a living room or study that has a door opening into a common corridor
serving number of suites, shall be classified as an apartment building.
B. Exit Details
1. Requirements
a. Any room having a capacity of less than fifty (50) persons with an outside
door at street or ground level may have such outside door as a single exit
18
provided that no part of the room or area is more than fifteen and one-fourth
meters (15.25 m) from the door measured along the natural path of travel.
b. Any floor below the floor of exit discharge occupied for public purposes
shall have exits arranged in accordance with the subsequent paragraph of this
Section, with access thereto in accordance with Section 10.2.5.2 of this IRR.
c. Any floor below the floor of exit discharge not open to the public and used
only for mechanical equipment, storage, and service operations (other than
kitchens which are considered part of the hotel occupancy) shall have exits
appropriate to its actual occupancy in accordance with applicable sections of
this Chapter. 172
d. The same stairway or other exit required to serve any one upper floor may
also serve other upper floor, except that no inside open stairway, escalator, or
ramp may serve as a required egress from more than one floor.
2. Types of Exits, arranged in accordance with Division 5 of this Chapter, shall be one
or more of the following types:
a. Doors, provided that doors in any means of egress shall not be locked
against egress when the building is occupied. Delayed egress locks may be
permitted, provided that not more than one such is located in any one egress
path.
4. Number of Exits Not less than two (2) exits shall be accessible from every floor,
including floors below the floor of exit discharge and occupied for public
purposes.
5. Travel Distance to Exits a. Any exit shall be such that it will not be necessary to
travel more than thirty meters (30 m) from the door of any room to reach the
nearest exit. b. Travel distance within a guest room or guest suite to a corridor
door shall not exceed twenty three meters (23 m) in buildings not protected by
an approved, supervised automatic sprinkler system. c. Travel distance within
a guest room or guest suite to a corridor door shall not exceed thirty eight
meters (38 m) in buildings protected by an approved, supervised sprinkler
system. 173
19
b. Means of egress shall be so arranged that, from every point in any open
area or from any room door, exits will be accessible in at least two (2) different
directions.
a. At least half of the required number of units of exit from upper floors,
exclusive of horizontal exits, shall load directly to the street or through a yard,
court, or passageway with protected openings and separated from all parts of
the interior of the buildings.
b. A maximum of fifty percent (50%) of the exits may discharge through areas
on the floor of exit discharge provided:
ii. The floor of discharge into which the exit discharge is provided with
automatic fire suppression system and any other portion of the level of
discharge with access to the discharge area is provided with automatic
fire suppression system or separated from it in accordance with the
requirements for the enclosure of exit. (See Section 10.2.5.2 of this
IRR),
iii. The entire area on the floor of discharge is separated from areas
below by construction having a minimum fire-resistance rating of two
(2) hours.
a. Each public space, hallway, stairway, or other means of egress shall have
illumination in accordance with Section 10.2.5.11 of this IRR. Access to exit
shall be continuously illuminated at all times. Any hotel and dormitory shall
have emergency lighting installed in individual guest rooms or guest suites,
hallways, landings of stairways and other appropriate areas as determined by
the C/MFM having jurisdiction. 174
b. Every exit access door from public hallways or from corridors on floors with
sleeping accommodations shall have an illuminated sign in accordance with
Section 10.2.5.12 of this IRR. Where exits are not visible in a hallway or
corridor, illuminated directional signs shall be provided to indicate the direction
C. Protection
a. Every stairway, elevator shaft and other vertical openings shall be enclosed
or protected in accordance with Section 10.2.6.2 of this IRR.
20
b. Any required exit stair which is so located that it is necessary to pass
through the lobby or other open space to reach the outside of the building
shall be continuously enclosed down to the lobby level.
c. No floor below the floor of exit discharge, used only for storage, heating
requirements, or other than hotel occupancy open to guest or the public, shall
have unprotected openings to floors used for hotel purposes.
a. In any new hotel building every corridor shall be separated from guest
rooms by partitions having at least a one (1) hour fire resistance rating.
b. Each guest room shall be provided with a door having a fire protection
rating
at least twenty (20) minutes.
c. Openings in corridor partitions other than door openings shall be prohibited.
d. Doors that open directly onto exit access corridors shall be self-closing and
self-latching.
3. Interior Finish Interior finish, in accordance with Section 10.2.6.3 of this IRR and
subject to the limitations and modifications therein specified, shall be as follows:
i. Exits – Class A or B;
ii. Lobbies and Corridors;
ii.a. Used as exit access – Class A or B
ii.b. Not used as required exit access – Class A, B or C
iii. Places of Assembly – See Section 10.2.8.16 of this IRR;
iv. Individual guest rooms – Class A, B or C; and v. Other rooms –
Class
A, B or C.
4. Fire Detection and Alarm System
21
f. Hotels and dormitories including its guest rooms and guests suites shall be
required to be equipped with both audible and visible notification appliance.
g. In hotels and dormitories not equipped with automatic fire detection and
alarm system, guest rooms, living area and sleeping rooms within a guest
suite shall be installed with single-station smoke detectors.
5. Extinguishing Requirements
b. Every hazardous area shall be separated from other parts of the building by
construction having a fire-resistance rating of at least one (1) hour and
communicating openings shall be protected by approved automatic or self-
closing fire doors, or such area shall be equipped with automatic fire
suppression system. Where a hazard is high as determined by the
City/Municipal Fire Marshal having jurisdiction, both fire-resistive construction
and automatic fire suppression system shall be used. Hazardous areas
include, but are not limited to:
22
D. Building Service Equipment
1. All premises intended for human use or habitation shall be provided with a supply
of pure and wholesome water, neither connected to unsafe water supply nor subject
to backflow or back- siphonage.
2. Plumbing fixtures, devices and appurtenances shall be supplied with water in
sufficient volume and pressure adequate to function satisfactorily and without undue
noise.
3. Plumbing shall be designed and adjusted to use the minimum quantity of water
consistent with proper performance and cleaning.
4. Devices for heating and storing water shall be so designed and installed as to
prevent dangers from explosion through overheating.
5. Every building abutting on a street, alley or easement with a public sewer shall
connect its plumbing fixtures to the sewer system.
6. Each family dwelling unit shall have at least one water closet, one kitchen type
sink, a lavatory and a bathtub or shower to meet the basic requirements of sanitation
and personal hygiene.
7. Plumbing fixtures shall be made of smooth non-absorbent material, free from
concealed fouling surfaces and shall be located in ventilated enclosures.
8. The drainage system shall be designed, constructed and maintained to safeguard
against fouling, deposit of solids, clogging and with adequate cleanouts so arranged
that the pipes may be readily cleaned.
9. All piping shall be of durable NAMPAP-approved materials, free from defective
workmanship, designed and constructed by Registered Master Plumbers to ensure
satisfactory service.
23
10. Each fixture directly connected to the drainage system shall be equipped with a
water-sealed trap.
11.The drainage pipes piping system shall be designed to provide adequate
circulation of air free from siphonage, aspiration or forcing of trap seals under
ordinary use.
12. Vent terminals shall extend to the outer air and installed to prevent clogging and
the return of foul air to the building.
13. Plumbing systems shall be subjected to such tests to effectively disclose all leaks
and defects in the workmanship.
14. Substance which will clog the pipes, produce explosive mixtures, destroy the
pipes or their joints or interfere unduly with the sewage-disposal process shall not be
allowed to enter the building drainage system.
15. Proper protection shall be provided to prevent contamination of food, water,
sterile goods and similar materials by backflow of sewage. When necessary, the
fixture, device or appliance shall be connected indirectly with the building drainage
system.
16. No water closet shall be located in a room or compartment which is not properly
lighted and ventilated.
17. If there is no sewer system in the area, suitable provision shall be made for the
disposal of building sewage by some accepted method of sewage treatment and
disposal, such as a septic tank.
18. Where a plumbing drainage system may be subject to backflow of sewage,
suitable provision shall be made to prevent its overflow in the building.
19. Plumbing systems shall be maintained in serviceable condition by Registered
Master Plumbers.
20. All plumbing fixtures shall be installed properly spaced, to be accessible for their
intended use.
21. Plumbing shall be installed with due regard to the preservation of the strength of
structural members and the prevention of damage to walls and other surfaces
through fixture usage.
22. Sewage or other waste from plumbing systems, which may be deleterious to
surface or sub-surface waters shall not be discharged into the ground or into any
waterway, unless first rendered innocuous through subjection to some acceptable
form of treatment.
Exercise No. 1
Draw a plan and apply the most important provisions of the code to your design. Limit
your design to a 3-storey commercial building with floor dimensions of 12 meters by
20 meters. The plan will include the following:
1. Floor plan
2. Elevations
24
schedule. Number of these documents is produced for the owner whereas others are
utilized by contractor for bidding and construction.
_____________________________________________________
Lesson 1: Structural Engineering and Architectural Documents
Learning Outcome: Structural Engineering Documents
At the end of the lesson, you are shall identify the project and specify
expected to formulate a technical design criteria both for the overall
documents for Architectural and structure and for structural components
Structural Engineering of a certain and structural systems. The drawings
project. shall identify the nature, magnitude and
location of all design loads to be imposed
on the structure. The structural
engineering documents shall provide construction requirements to indicate the nature
and character of the work and to describe, detail, label and define the structure’s
components, systems, materials, assemblies, and equipment.
a. LOCATION PLAN
A Location or Site Location Plan is a map drawn to a suitable
metric scale which shows the location of a development or
proposed development. Most Site Location plans are based on
Ordnance Survey Master map.
25
b. SITE DEVELOPMENT PLAN
A Site Development Plan depicts the general layout and
configuration of a site, including building footprints, parking and
street layout, conceptual landscaping and lighting, site cross
section drawings, and building elevations. A Site Development
Plan must be approved prior to the issuance of building permits.
Site Development Plan at scale of 1:200 m.
c. PERSPECTIVE
The art of drawing solid objects on a two-dimensional surface so
as to give the right impression of their height, width, depth, and
position in relation to each other when viewed from a particular
point.
Perspective is the way that one looks at something. It is also an
art technique that changes the distance or depth of an object on
paper.
26
d. FLOOR PLAN
In architecture and building engineering, a floor plan is a drawing
to scale, showing a view from above, of the relationships between
rooms, spaces, traffic patterns, and other physical features at one
level of a structure.
Dimensions are usually drawn between the walls to specify room
sizes and wall lengths.
e. ELEVATION
On a building plan there are normally four or five elevations,
showing a front, rear and end elevation, these would include any
basement or attic rooms. The plan elevation would show the
upper and lower floor room layouts.
The front elevation is a straight-on view of the house as if you
were looking at it from a spot on the front yard. Also called an
"entry elevation," the front elevation shows home features such
as entry doors, windows, the front porch and any items that
protrude from the home.
27
f. SECTION
The term longitudinal section pertains to a section done by a plane
along the long axis of a structure in contrast to the other term,
cross section, which is a section that is cut
transversely. Longitudinal sections would therefore pertain to any
vertical section such as median, sagittal, and coronal sections.
h. FOUNDATION PLAN
The foundation plan is a plan view drawing, in section, showing
the location and size of footings, piers, columns, foundation walls,
and supporting beams. A foundation plan ordinarily includes the
following:
28
Crawlspace Foundations. Homes with crawl space foundation
are elevated a few feet off the ground.
Basement Foundations.
i. FRAMING PLAN
A plan of each floor of a building showing the makeup of beams
and girders on that floor, and their connections, using a simplified
system of symbols and drafting line work.
29
either similar member for distributing concentrated load in the form
of uniformly loads on the soil below. The footing may be square,
rectangular or circular in plan.
l. DETAIL OF STAIRS
A stairway, staircase, stairwell, flight of stairs, or simply stairs, is a
construction designed to bridge a large vertical distance by dividing
it into smaller vertical distances, called steps. Stairs may be
straight, round, or may consist of two or more straight pieces
connected at angles.
SANITARY/PLUMBING
30
accompanied by sanitary plans and specifications signed and
sealed by a duly licensed Sanitary Engineer.
1. Sanitary Plan, layouts and details.
2. Isometric drawings of roughing-ins of sanitary drainage,
ventilation lines, hot and cold water distribution/supplies to
plumbing fixtures and equipment.
3. Detail drawings of Imhoff tanks/septic tanks in the absence
of disposal to the street sanitary sewer.
4. Riser diagram of drainage including details of
miscellaneous appurtenances such as manholes, junction
boxes catch basins, water/sewer/storm drainage
connections.
5. Design Analysis, technical specifications.
6. Estimate of Cost (for statistical purposes only)
7. Detail drawing of deep well water source and water
treatment device in the absence of municipal water system.
MECHANICAL
31
b. Make and catalog number, size, model serial
number, capacity.
c. Revolution per minute (RPM) and drive (direct, V-
belt or flat-belt, gear reducer hydraulic, magnetic,
chain or line shafting).
d. Motor or Prime Mover Showing a.)ICE (International
Combustion Engine), RPM (revolution per minute),
Total horsepower, Fuel and Use. b.)ELECTRIC
MOTOR: Horsepower (HP) rating, RPM (revolution
per minute), Voltage, Chase, Cycle Current,
Kilowatt (kw) and Use
10. Flow sheets for processing plant, manufacturing plant or
Assembly plant
ELECTRICAL
For new electrical installation with more than twenty outlets or a capacity of more
than a 4 kw, of any voltage, application shall be accompanied by electrical plans and
specifications signed and sealed by a duly licensed Professional Electrical Engineer,
containing the following:
Exercise No. 2
From Exercise No. 1 you have to continue the inclusion of the different codes
and prepare the technical documents (details, specifications) of the following:
1. Foundation/Footing
2. Column
3. Beam
4. Wall
5. Flooring
6. Roofing
32
Lesson 2: Quantity Survey and Cost Estimates
The key differences between estimators and quantity surveyors include: The
projects they take on.
a. Quantity surveyors are frequently engaged with larger and more complex
projects. While this isn't necessarily always the case.
b. Estimators are more frequently engaged with residential and smaller
commercial projects.
WHAT IS AN ESTIMATE?
Webster defines an estimate as arriving “at an often accurate but usually only
approximate statement of the cost of a job to be done.” The Means Illustrated
Construction Dictionary defines it more closely for our purposes; “The anticipated
cost of materials, labor, equipment, or any combination of these for a proposed
construction project.” In real-world terms, a construction estimate is simply a
projection of the likely cost of a project based on an assumption of scope and cost
data.
33
estimate should average out closely to the final aggregate bids.
Some line items will be high, and others low.
34
level a reasonable estimate can be developed. (However, no
amount of time can improve an estimate if the project design
steps aren’t properly developed.)
35
Essential to business success – If we overstate an estimate, we
could force the Owner not to complete other important projects. If we
understate an estimate, we could miss a critical ROI (Return on
Investment.) It is simply essential to the health of a business that
capital management be effective. In addition, yearly depreciation
charges must be considered, which go directly against P&L (Profit and
Loss.)
Histories – This is the best and most reliable source of costs for early-
stage estimating. Keep track of what projects cost by major
subcategories. These will be helpful later. Remember to increase for
inflation. We will cover how to do this later.
METHODS OF ESTIMATING
36
Now that we have learned the sources of estimating data, how do we actually
perform the estimate? The following are the primary methods of estimating (often
called by different names but include similar approaches):
FORGOTTEN COSTS
Leaving things out of an estimate is obviously problematic. Although scope is
commonly forgotten, omissions often are the intangibles associated with a project.
First, we need to understand Direct versus Indirect costs. Direct Costs are tangible
37
costs associated with vendors, equipment, and sub-contractors. Examples include
actual equipment costs, subcontracts, etc. Indirect costs are associated with other
requirements necessary to complete the work. These can include construction
management/construction fees and overhead/general conditions, design, pre-
operating costs, permits, etc. Unfortunately, people often forget about indirect costs,
which can be 10-50% of the Direct Costs! This most often occurs when the “phone
call engineering” approach is employed.
Delivery
Rigging
Equipment Installation
Insurance
Utility/Infrastructure
Sitework
Data/Telephone
38
Building permit is a written
Learning Outcomes: authorization granted by
At the end of the lesson, you are Building Officials to an applicant
expected to know some important allowing them to proceed with
provisions of acquiring a building the construction of a specific
permit and its processes. project after plans,
specifications, and other
pertinent documents have been
found to be in conformity with the National Building Code (PD 1096) and its
implementing rules and regulations. It includes any or all of the Permits
enumerated under Section 1 of Rule 111.
FILING OF APPLICATION
a. When satisfied that all documents, plans and specifications
accompanying an application are in order. The Building Official gives due
course to the application.
b. Upon receipt of application the Building Official refers one set of plans
and specifications to the chief of the Local Fire Service (CLFS) for his
evaluation, review and recommendation with respect to fire safety and
control requirements. The CLFS is given five days to act and submit this
report to the Building Official.
PROCESSING OF APPLICATION
Corresponding Technical Staff evaluates bidding documents as to technical
requirements.
a. ARCHITECTURAL
Types of construction
39
Requirements of Fire Zone
Light and Ventilation
Building Projections over public streets
General Design and Construction requirements
Classification and General requirements by use or occupancy
Signs
b. STRUCTURAL
Structural design requirements
Fire resistive requirements on construction
Excavation, foundation and retaining walls
The use of computers
Pre-fabricated construction
c. SANITARY/PLUMBING
Sanitation
d. ELETRICAL
Electrical regulations
e. MECHANICAL
Mechanical regulations
f. FIRE SAFETY AND CONTROL
Fire extinguishing systems
In addition, if you are get caught of building a house without securing a permit,
the building officials will forcefully stop the construction until your permit has
been issued or released. You will receive a notice to apply for the mandatory
building permit.
40
Structural Design Analysis — signed and sealed by Civil Engineer
at every page
3. For construction of more than two-storey building:
Boring and Plate Load Test
Seismic Analysis
4. Proof of Property
Photocopy of Transfer Certificate if Title (TCT)
Photocopy of tax Declaration of Property-lot (Certified True Copy)
Photocopy of Current Tax Receipt
5. If property is not registered under the name of the applicant:
Submit 5 copies of any of the following:
Contract of Lease
Contract of Sale
Affidavit of Consent of the Lot Owner for the construction of
building/house
Deed of Absolute Sale
6. Permit Billboard (0.60 X 0.90 Plywood with the following contents):
7. Bill of Materials and Specification (5 copies) — signed and sealed by an
engineer or an architect at every page
8. Locational Clearance
9. Photocopy of PTR # and PRC license of all concerned engineers and
architects
10. Clearance from the DPWH if the construction is located along National
Highway
11. DOLE Clearance
41
Notice of non- issuance, suspension or revocation of building permits shall
always be made in writing, stating the reason or grounds thereof.
APPEAL
Within fifteen (15) days from the date of receipt of advice of the non- issuance,
suspension or revocation of permits, the applicant/permitted may file an
appeal with the Secretary who shall render his decision within fifteen days
from date of receipt of notice of appeal. The decision of the Secretary shall be
final subject only to review by the Office of the President.
1. The owner of the Building who is issued or granted a building permit under
the Code shall engage the services of a duly licensed architect or civil
engineer to undertake the full time inspection and supervision of the
construction work.
2. Such architect or civil engineer may or may not be the same architect or
civil engineer who is responsible for the design of the building.
3. It is understood however that in either case, the designing architect or civil
engineer is not precluded from conducting inspection of the construction
work to check and determine compliance with the plans and specifications
of the building submitted.
4. There shall be kept at the jobsite at all times a logbook wherein the actual
progress of construction including tests conducted, weather conditions and
other pertinent data are to be recorded.
5. Upon completion of the construction, the said licensed architect or civil
engineer shall submit the logbook, duly signed and sealed, to the Building
Official. He shall also prepare and submit a Certificate of Completion of the
project stating that the construction of building conforms to the provisions
of the Code as well as with the approved plans and specifications.
CERTIFICATE OF OCCUPANCY
42
2. A notification to conduct final inspection shall be endorsed by the OBO to
the C/MFM, BFP, who shall issue a Fire Safety Inspection Certificate within
five (5) workings days if the Fire Safety requirement shall have been
complied. If, after the prescribed period no action is taken by the C/MFM,
the Building Official may issue the Certificate of Occupancy with the
condition that the Fire Safety requirements shall be complied with, within
the prescribed period set forth in the Fire Code of the Philippines (PD
1185).
3. The OBO undertakes the final inspection, verification and/or review of the
building/structure based on the Certificate of Completion, construction
logbook, building inspection sheets, original and as-built plans and
specifications, as the case may be and specifications on the prescribed
standard form according to the requirements set forth under Section 303.
4. Prior to the issuance of the Certificate of Occupancy, the OBO shall
prepare the corresponding fees and order of payment. The Building Official
then issues the Certificate of Occupancy in the form prescribed therefor
after all fees are paid.
a. A partial Certificate of Occupancy may be issued for the use or
occupancy of a portion or portions of a building or structure prior to the
completion of the entire building or structure, through the proper
phasing of its major independent portions without posing hazards to its
occupants, the adjacent building residents and general public.
b. A building for which a Certificate of Occupancy has been issued may
further be issued other Certificates of Occupancy due to changes in
use, whether partly or wholly, provided, that the new use/s or
character/s of occupancy conforms with the requirement of the Code
and its IRR.
Exercise No. 3:
Prepare a material and cost estimate for the footing, column, beam, wall, flooring and
roofing of your design drawing in Exercise No 1 & 2.
43
REFERENCES
44