1 Core CU/PVC 450/750V
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
02
03
1 Core CU/PVC/PVC 600/1000V 3 Core CU/PVC/PVC 600/1000V
Nominal Approx. Approx. Test Voltage Max. Current Current Volt drop for Nominal Shaped Approx. Approx. Test Max. Current Current Volt drop
rating cross- Overall Cable Voltage conductor rating rating
cross- Overall Cable conductor rating based 3 phase for 3
based on a DC based on
sectional Diameter Weight based on a
sectional Diameter Weight DC perforated on laid in air resistance enclosed phase
cable tray area in conduit perforated
at
area resistance horizontal in trefoil at on a wall / cable tray
20°C ceiling / in
at 20°C / vertical at 40°C / free air at
25°C trunking at
2
30°C 40°C
(mm ) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
0.82 (mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
50 13.6 553 3.5 0.387 177 145
70 15.0 754 3.5 0.268 230 188 0.57
1.5 C 11.9 233 3.5 12.1 15 18.5 25
95 17.2 1030 3.5 0.193 281 230 0.42
120 18.6 1266 3.5 0.153 328 268 0.35
2.5 C 12.8 286 3.5 7.41 20 25 15
150 20.6 1558 3.5 0.124 380 310 0.29
185 22.7 1937 3.5 0.0991 437 356 0.25
4 C 14.8 395 3.5 4.61 27 34 9.5
240 25.5 2515 3.5 0.0754 519 422 0.21
300 28.1 3130 3.5 0.0601 602 488 0.19
400 31.8 3976 3.5 0.0470 699 571 0.17 6 C 16.1 491 3.5 3.08 34 43 6.4
500 35.0 5044 3.5 0.0366 801 652 0.16
630 38.3 6411 3.5 0.0283 919 744 0.15 10 CC 18.1 672 3.5 1.83 46 60 3.8
800 42.1 8096 3.5 0.0221 1051 845 0.14
16 CC 20.3 916 3.5 1.15 62 80 2.4
2 Core CU/PVC/PVC 600/1000V
25 CC 24.1 1331 3.5 0.727 80 101 1.5
Nominal Shaped Approx. Approx. Test Max. Current Current Volt drop
cross- Overall Cable Voltage conductor rating rating for single
based on based on a phase a.c 35 SC 23.7 1370 3.5 0.524 99 126 1.1
sectional Diameter Weight DC perforated
clipped
area resistance cable tray
direct at / free air at 50 SC 27.2 1799 3.5 0.387 118 153 0.81
at 20°C 30°C 30°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
70 SC 30.3 2457 3.5 0.268 149 196 0.57
1.5 C 11.4 184 3.5 12.1 19.5 22 29
2.5 C 12.2 225 3.5 7.41 27 30 18
4 C 14.1 308 3.5 4.61 36 40 11 95 SC 34.7 3339 3.5 0.193 179 238 0.43
6 C 15.2 380 3.5 3.08 46 51 7.3
10 CC 17.1 514 3.5 1.83 63 70 4.4 120 SC 37.7 4110 3.5 0.153 206 276 0.35
16 CC 19.2 679 3.5 1.15 85 94 2.8
25 CC 22.6 997 3.5 0.727 112 119 1.75 150 SC 41.7 5014 3.5 0.124 225 319 0.29
35 SC 20.8 969 3.5 0.524 138 148 1.25
50 SC 23.8 1269 3.5 0.387 168 180 0.94
185 SC 45.9 6218 3.5 0.0991 255 364 0.25
70 SC 26.2 1698 3.5 0.268 213 232 0.65
95 SC 29.7 2285 3.5 0.193 258 282 0.50
120 SC 32.2 2806 3.5 0.153 299 328 0.41 240 SC 51.4 8062 3.5 0.0754 297 430 0.21
150 SC 35.6 3420 3.5 0.124 344 379 0.34
185 SC 39.1 4233 3.5 0.0991 392 434 0.29 300 SC 56.9 10024 3.5 0.0601 339 497 0.185
240 SC 43.8 5480 3.5 0.0754 461 514 0.24
300 SC 48.2 6784 3.5 0.0601 530 593 0.21
400 SC 64.2 12694 3.5 0.0470 402 597 0.16
400 SC 54.4 8584 3.5 0.0470 634 715 0.185
C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
04
05
4 Core CU/PVC/PVC 600/1000V 1 Core CU/PVC/AWA/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop Nominal Approx. Approx. Test Voltage Max. con- Current Current Volt drop for
cross- Overall Cable Voltage ductor DC rating rating for 3 cross- Overall Cable ductor DC rating based rating based 3 phase
Diameter Weight based on a sectional Diameter Weight resistance
sectional resistance based on phase on clipped on laid in air
perforated area at 20°C
area at 20°C clipped
cable tray direct at trefoil at
direct at / free air
30°C 30°C 40°C
at 30°C
2
(mm ) 2
(mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) (mm ) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
16 15.9 432 3.5 1.15 84 79 2.39
1.5 C 12.7 275 3.5 12.1 17.5 18.5 25 25 17.4 566 3.5 0.727 117 107 1.51
35 18.5 668 3.5 0.524 145 134 1.09
2.5 C 13.7 341 3.5 7.41 24 25 15 50 20.2 836 3.5 0.387 179 157 0.82
70 21.6 1057 3.5 0.268 225 201 0.57
95 23.9 1385 3.5 0.193 269 244 0.42
4 C 16.0 470 3.5 4.61 32 34 9.5 120 25.3 1649 3.5 0.153 309 282 0.35
150 27.1 1963 3.5 0.124 320 339 0.29
6 C 17.4 591 3.5 3.08 41 43 6.4 185 29.2 2374 3.5 0.0991 399 370 0.24
240 32.0 3003 3.5 0.0754 465 436 0.21
300 35.3 3738 3.5 0.0601 515 493 0.18
10 CC 19.6 815 3.5 1.83 57 60 3.8 400 39.4 4685 3.5 0.0470 575 572 0.16
500 42.6 5822 3.5 0.0366 622 636 0.15
16 CC 22.2 1136 3.5 1.15 76 80 2.4 630 47.0 7421 3.5 0.0283 669 704 0.14
C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
06
07
3 Core CU/PVC/SWA/PVC 600/1000V 4 Core CU/PVC/SWA/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop
cross- Overall Cable Voltage ductor DC rating rating for 3 cross- Overall Cable Voltage ductor DC rating rating for 3
sectional Diameter Weight resistance based on based on a phase sectional Diameter Weight resistance based on based on a phase
perforated perforated
area at 20°C clipped area at 20°C clipped
cable tray cable tray
direct at / free air direct at / free air
30°C at 30°C 30°C at 30°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) (mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
1.5 C 16.0 477 3.5 12.1 18 19 25 1.5 C 17.5 594 3.5 12.1 18 19 25
2.5 C 17.6 637 3.5 7.41 25 26 15 2.5 C 18.5 688 3.5 7.41 25 26 15
4 C 19.6 800 3.5 4.61 33 35 9.5 4 C 20.8 891 3.5 4.61 33 35 9.5
6 C 20.9 929 3.5 3.08 42 45 6.4 6 C 22.2 1040 3.5 3.08 42 45 6.4
10 CC 23.6 1282 3.5 1.83 58 62 3.8 10 CC 25.1 1467 3.5 1.83 58 62 3.8
16 CC 25.8 1607 3.5 1.15 77 83 2.4 16 CC 27.7 1880 3.5 1.15 77 83 2.4
25 CC 29.8 2159 3.5 0.727 102 110 1.50 25 CC 32.2 2575 3.5 0.727 102 110 1.50
35 SC 29.4 2231 3.5 0.524 125 135 1.10 35 SC 32.3 2702 3.5 0.524 125 135 1.10
50 SC 33.1 2809 3.5 0.387 151 163 0.81 50 SC 37.9 3745 3.5 0.387 151 163 0.81
70 SC 37.6 3872 3.5 0.268 192 207 0.57 70 SC 41.6 4764 3.5 0.268 192 207 0.57
95 SC 41.8 4946 3.5 0.193 231 251 0.43 95 SC 47.6 6548 3.5 0.193 231 251 0.43
120 SC 44.8 5842 3.5 0.153 267 290 0.35 120 SC 51.4 7829 3.5 0.153 267 290 0.35
150 SC 50.4 7410 3.5 0.124 306 332 0.29 150 SC 56.2 9283 3.5 0.124 306 332 0.29
185 SC 54.6 8848 3.5 0.0991 348 378 0.25 185 SC 61.3 11230 3.5 0.0991 348 378 0.25
240 SC 60.5 11071 3.5 0.0754 409 445 0.21 240 SC 67.9 14059 3.5 0.0754 409 445 0.21
300 SC 66.0 13325 3.5 0.0601 469 510 0.185 300 SC 75.3 17868 3.5 0.0601 469 510 0.185
400 SC 74.8 17256 3.5 0.0470 540 590 0.160 400 SC 84.4 22148 3.5 0.0470 540 590 0.160
C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED C : CIRCULAR STRANDED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
08
09
1 Core CU/XLPE/PVC 600/1000V
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
10
11
2 core CU/XLPE/PVC 600/1000V 3 Core CU/XLPE/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. con-
Current Current Volt drop Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop
cross- Overall Cable Voltage rating rating cross- Overall Cable Voltage ductor DC rating rating for 3
ductor DC for single
based on Diameter Weight based on a
sectional Diameter Weight based on a sectional resistance based on phase
resistance enclosed perforated
area in conduit perforated phase area at 20°C clipped
at 20°C cable tray
on a wall / cable tray direct at / free air
a.c
ceiling / in 30°C at 40°C
/ free air at
trunking at (mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
30°C 40°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) 16 CC 19.0 826 3.5 1.15 96 91 2.55
25 CC 22.8 1213 3.5 0.727 119 116 1.65
16 CC 18.0 611 3.5 1.15 91 105 2.90 35 SC 22.4 1275 3.5 0.524 147 144 1.15
50 SC 25.4 1666 3.5 0.387 179 175 0.87
70 SC 29.0 2320 3.5 0.268 229 224 0.60
25 CC 21.4 908 3.5 0.727 119 136 1.90
95 SC 32.4 3110 3.5 0.193 278 271 0.45
120 SC 35.8 3878 3.5 0.153 322 315 0.37
35 SC 19.6 902 3.5 0.524 146 168 1.35 150 SC 39.8 4740 3.5 0.124 371 363 0.30
185 SC 44.1 5914 3.5 0.0991 424 415 0.26
240 SC 49.1 7641 3.5 0.0754 500 490 0.21
50 SC 22.2 1170 3.5 0.387 175 205 1.00
300 SC 54.1 9499 3.5 0.0601 576 565 0.185
400 SC 61.4 12075 3.5 0.0470 667 674 0.165
70 SC 25.0 1603 3.5 0.268 221 263 0.69
95 SC 27.5 2125 3.5 0.193 265 320 0.52 Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop
cross- Overall Cable Voltage ductor DC rating rating for 3
sectional Diameter Weight resistance based on based on a phase
perforated
area at 20°C clipped
120 SC 30.4 2645 3.5 0.153 305 373 0.42 cable tray
direct at / free air
30°C at 40°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
150 SC 33.8 3229 3.5 0.124 334 430 0.35 16 CC 20.7 1023 3.5 1.15 96 91 2.55
25 CC 24.9 1511 3.5 0.727 119 116 1.65
35 SC 25.0 1605 3.5 0.524 147 144 1.15
185 SC 37.5 4026 3.5 0.0991 384 493 0.29
50 SC 28.7 2128 3.5 0.387 179 175 0.87
70 SC 32.8 2986 3.5 0.268 229 224 0.60
240 SC 41.6 5189 3.5 0.0754 459 583 0.24 95 SC 36.7 4036 3.5 0.193 278 271 0.45
120 SC 40.7 5065 3.5 0.153 322 315 0.37
150 SC 45.3 6200 3.5 0.124 371 363 0.30
300 SC 45.6 6423 3.5 0.0601 532 674 0.21
185 SC 50.3 7772 3.5 0.0991 424 415 0.26
240 SC 56.1 10106 3.5 0.0754 500 490 0.21
400 SC 51.8 8160 3.5 0.0470 625 787 0.19 300 SC 61.8 12579 3.5 0.0601 576 565 0.185
400 SC 70.3 16036 3.5 0.0470 667 674 0.165
CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED CC : COMPACTED CIRCULAR STRANDED SC : SECTORAL STRANDED COMPACTED
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
12
13
1 Core CU/XLPE/AWA/PVC 600/1000V 3 Core CU/XLPE/SWA/PVC 600/1000V
Nominal Approx. Approx. Test Voltage Max. Current Current Volt drop for Nominal Shaped Approx. Approx. Test Max. con- Current Current Volt drop
cross- sec- Overall Cable conductor rating based rating based 3 phase cross- sec- Overall Cable Voltage ductor DC rating rating for 3
Diameter Weight DC resis- on clipped on laid in air tional area Diameter Weight resistance based on based on a phase
tional area
tance at direct at in trefoil at perforated
at 20°C clipped
20°C 30°C 40°C cable tray
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) direct at / free air
2.55 30°C at 40°C
16 15.3 401 3.5 1.15 99 -
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
25 16.8 521 3.5 0.727 130 127 1.61
16 CC 24.5 1242 3.5 1.15 94 90 2.55
35 17.9 632 3.5 0.524 161 160 1.16
25 CC 28.5 1682 3.5 0.727 124 119 1.61
50 19.4 782 3.5 0.387 220 202 0.87
35 SC 27.9 1899 3.5 0.524 154 147 1.16
70 21.0 1009 3.5 0.268 277 259 0.61
50 SC 31.3 2392 3.5 0.387 187 179 0.87
95 22.9 1306 3.5 0.193 333 315 0.45
70 SC 35.7 3338 3.5 0.268 238 228 0.61
120 24.5 1572 3.5 0.153 383 366 0.36
0.30 95 SC 39.5 4258 3.5 0.193 289 277 0.45
150 26.3 1874 3.5 0.124 437 421
0.25 120 SC 42.9 5139 3.5 0.153 335 321 0.36
185 28.4 2279 3.5 0.0991 496 481
0.21 150 SC 48.1 6513 3.5 0.124 386 369 0.30
240 30.8 2861 3.5 0.0754 579 569
0.18 185 SC 52.8 7890 3.5 0.0991 441 421 0.25
300 33.9 3560 3.5 0.0601 662 655
400 38.2 4503 3.5 0.0470 717 742 0.16 240 SC 57.8 9850 3.5 0.0754 520 497 0.21
500 41.4 5606 3.5 0.0366 791 835 0.15 300 SC 63.2 11977 3.5 0.0601 599 571 0.18
630 46.0 7193 3.5 0.0283 861 935 0.14 400 SC 70.5 14896 3.5 0.0470 673 662 0.16
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
14