CTR FIRE SYSTEMS DIVISION
POONA
DETAILS OF DRAWINGS FOR APPROVAL OF FIRE PREVENTION AND EXTINGUISHING
SYSTEM BY NITROGEN INJECTION METHOD FOR 2 x 315MVA, 400/138/34.5 kV
AUTO TRANSFORMER FOR CROMPTON GREAVES LIMITED, MUMBAI
A/C TATA STEEL LTD.JAMSHEDPUR (W.O.NO. T09849)
(CONSULTANT: TATA CONSULTING ENGINEERS LIMITED)
SR. DRAWING
TITLE REMARKS
NR. NUMBER
DETAILS OF INTERCONNECTION DIAGRAM OF
1 FS 3743 A3 01 PNT FIRE SYSTEM 220 VDC FOR CGL A/C
TATA STEEL LIMITED
DETAILS OF CONTROL BOX OF PNT FIRE
2 FS 1940 A4 01
SYSTEM 220 VDC
DETAILS OF FIRE EXTINGUISHING CUBICLE OF
3 FS 1935 A4 01
PNTMXXXC20 FIRE SYSTEM
DETAILS OF CUBICLE OF PNTMXXXC20 FIRE
4 FS 1936 A4 01
SYSTEM
DETAILS OF VALVE POSITION WITH PRESSURE
5 FS 1957 A4 00
SWITCH IN F.E.C. OF PNT FIRE SYSTEM
DETAILS OF PNRV (TCIV)AND MOUNTING
6 FS 1960 A4 04 FLANGES FOR PNRV (TCIV)OF PNT FIRE
SYSTEM
DETAILS OF WORKING OF PRE-STRESSED NON
7 FS 1961 A4 00
RETURN VALVE OF PNT FIRE SYSTEM
DETAILS OF `T’ TYPE FIRE DETECTOR OF PNT
8 FS 1939 A4 02
FIRE SYSTEM
DETAILS OF PLINTH FOR FIRE EXTINGUISHING
9 FS 1934 A4 01
CUBICLE OF PNTMXXXC20 FIRE SYSTEM
DETAILS OF LOGIC DIAGRAM FOR OPERATION
10 FS 1966 A3 02
OF PNT FIRE SYSTEM
11 FS 1946 A3 02 DETAILS OF OIL PIT FOR PNT FIRE SYSTEM
DETAILS OF SCHEMATIC CONTROL DIAGRAM OF
12 FS 2527 A4 01 PNT FIRE SYSTEM FOR PNT FIRE SYSTEM FOR
220 VDC
13 --- GUARANTEED TECHNICAL PARTICULARS
14 --- FUNCTIONAL DISCRIPTION
15 --- BILL OF MATERIAL FOR SYSTEM
DETAILS OF WIRING DIAGRAM FOR CONTROL
16 FS 3791 A3 00 BOX OF PNT FIRE SYSTEM 220 VDC FOR CGL
A/C TATA
DETAILS OF ELECTRICAL WIRING CONNECTION,
17 FS 3792 A4 00
220 VDC FOR CGL A/C TATA
TURNOVER
FOR REFERENCE :
1 --- SEQUENTIAL OPERATION OF PNT FIRE SYSTEM
PREPARED CHECKED APPROVED CC:MKM(FS) —- 1 SET +
BY:OFA (FS4) BY:SAPM(FS) BY:VP3 1 SOFT COPY FOR CUSTOMER
Initials DMJ:dmj DMJ VKW :DEA(FS3) --- 1 SET
Date 31.01.2011 31.01.2011 31.01.2011
GUARANTEED TECHNICAL PARTICULARS
FOR NITROGEN INJECTION FIRE PREVENTION AND EXTINGUISHING SYSTEM FOR
2 X 315 MVA,400/138/34.5 kV AURO TRANSFORMER FOR CROMPTON GREAVES LIMITED,
MUMBAI A/C TATA STEEL LTD, JAMSHEDPUR (W.O.NO. T09849)
Sr.
No. Description Guaranteed Particulars
1 Name of Manufacture and country of CTR Manufacturing Industries Ltd. Pune
origin transformer INDIA
2 Reference standards Manufacturer's relevant IS, BS
3 Details of system equipments FEC, CB, TCIV,DETECTORS
4 FEC(Fire Extinguishing Cubicle)
4.1 Dimensions (LXBXH) mm 1600X600X1800+100(Base)
4.2 Weight 550 kg Maximum
4.3 Capacity of Nitrogen cylinder 2X10 Cubic Meter 150 kg/ sq.cm. Pressure
4.4 Number of cylinders 2
4.5 Pressure of Nitrogen filing 150kg/cm2 Maximum
4.6 Minimum distance of FE cubicle from 5 meters or place next to fire wall if fire
the transformer fighting wall exists.
4.7 Method of mounting Floor
4.8 Whether the following items are
provided in FE cubicle. If so
furnish make, type & other details.
4.9 Contact manometer GIC/FIEGBIG/ GAUGES BOURDEN,Falling
pressure, Electrical contact
4.10 Pressure Regulator VANAZ/PAARTH/MESSER/EQUIVALENT
4.11 Oil Release Unit CTR
4.12 Gas release unit CTR
4.13 Oil drain assembly CTR
4.14 Pressure /limit switches Pressure switch (Back up) : ORION/ INDFOS/
EQUIVALENT
Limit switch: TECKNIC/ SCHMERSAL/
EQUIVALENT
4.15 No of contacts & spare contacts Limit switches G02=2 NO, G03= 2NO,
(NO&NC) G04=1NO+1NC, G05=2NO/ 1NC+1NO,
G06=2NO/1NC+1NO
4.16 Oil drain valve (ABOVE FEC)
4.17 Make PETSON/SUNRISE/EQUIVALENT
4.18 Type Butterfly valve
4.19 Size 125NB
4.20 Type of metal Mild steel
4.21 Nitrogen Injection Valve (ABOVE
FEC)
4.22 Make OSWAL/LEADER/MANIXON/NEO/EQUIVALENT
4.23 Type Gun metal, Lockable, Stem rising
4.24 Size 25NB
4.25 Oil drain pipe Yes
..2..
..2..
4.26 Size 125NB
4.27 Length As per site location, Transformer to FEC &
FEC to Oil Pit.
4.28 Number of openings in the 1
transformer tank
4.29 Material MS,ERW, Heavy duty for TRS to FEC & GI,
Medium for FEC to Oil pit.
5 Control Box
5.1 Dimensions (LXBXH) mm 500x270x700
5.2 Weight 45 Kg Maximum
5.3 Type & Thickness of sheet steel CRCA, 16/14 SWG
5.4 Details of components provided in MCB, Relays, Hooters, Contactors,
the control box Indicating lamps, Operating switches, Latch
contactactos, Rotary switches.
5.5 Control voltage 220 VDC
5.6 Method of mounting Wall
5.7 Whether audio and visual alarms Yes with different volume (dB) levels
provided?
6 Transformer Conservator Isolation Valve (TCIV)
6.1 Make CTR
6.2 Type Operating mechanically of Transformer oil
flow rate with visual position indicator.
6.3 Location In the conservator pipe line between
Conservator and Buchholz relay.
6.4 Whether suitable for pipe of size Yes
80mm dia
6.5 No of contacts & spare contacts 1NO
(NO&NC)
6.6 Padlocking provision YES
7 Fire Detectors
7.1 Make CTR
7.2 Type Quartz bulb, Heat sensing.
7.3 Quantity required Depending upon transformner top cover area.
7.4 Method of fixing Bolting on bracket on transformer top
cover.
7.5 Effective heat sensing area Circular 2.01 sq. meter (800mm Radius)
7.6 Temperature recommended for 141°C
effective heat sensing
7.7 Number of contacts NO/NC 2 NO
7.8 Necessity and Condition of After operation
Refilling
8 Whether approved by Tariff Advisory Yes
Committee of India
..3..
..3..
9 TECHNICAL PARTICUARS FOR NITROGEN INJECTION SYSTEM FOR PREVENTION OF
TRANSFORMER EXPLOSION
10 Power Supply
10.1 Control box 220 VDC and 230VAC for DC fail alarm
10.2 FEC (lighting) 230VAC
10.3 Extinction period Maximum 3 minutes
10.4 On system activation Maximum 3 minutes
10.5 Oncommencement of Nitrogen Maximum 30 Seconds
injection
11 FEC suitable for capacity Transformer : 315 MVA
11.1 Dimensions (LXBXH) mm 1600X600X1800+100(Base)
11.2 Weight 550 kg Maximum
11.3 Nitrogen cylinder capacity 2X10 Cubic Meter 150 kg/ sq.cm. Pressure,
68 Litre water capacity
12 Control Box
12.1 Dimensions (LXBXH) mm 500x270x700
12.2 Weight 45 kg Maximum
13 Fire Detectors
13.1 Heat sensing temperature 141°C
13.2 Time of operation
Transformer Tank Fire Extinction
Explosion Prevention
a. For system activation Maximum 50 Maximum 100
Milliseconds Milliseconds
b. For reduction of pressure in Maximum 730 Maximum 730
Tank by Nitrogen release Milliseconds Milliseconds
13.3 Any other technical details not On line supervision of required signals, DC
covered above supply monitoring, Test facility (excluding
PNRV(TCIV), FD) on live transformer,
Anticondensation heater for FEC.
DMJ:smp
16.11.2010
CTR FIRE SYSTEMS DIVISION 1/2
POONA
FUNCTIONAL DESCRIPTION OF NITROGEN INJECTION FIRE PROTECTION SYSTEM
FOR OIL FILLED TRANSFORMER
GENERAL :
Nitrogen Injection Fire Prevention and extinguishing System designed
for oil filled transformers, shall prevent tank explosion and the fire
during internal faults resulting in an arc where tank explosion will
normally take few seconds after arc generation and also extinguish the
external oil fires on transformer top cover due to tank explosion
and/or external failures like bushing fires, due to OLTC fires and
fire from surrounding equipments.
The system shall work on the principle of DRAIN AND STIR and on
activation, shall drain a pre-determined quantity of oil from the tank
top through outlet valve, to reduce the tank pressure and inject
nitrogen gas at high pressure from the lower side of the tank through
inlet valves to create stirring action and reduce the temperature of
top oil surface below flash point to extinguish the fire.
Conservator tank oil shall be isolated during tank explosion and oil
fire, to prevent aggravation of oil fire.
Transformer isolation shall be an essential pre-condition for
activating the system
The system shall be designed to operate manually, in case of failure
of power source.
OPERATIONAL CONTROLS
The system is provided with automatic control for fire Prevention and
fire extinction besides remote electrical switch control on control
box and local manual control in the fire extinguishing cubicle.
Transformer isolation through Master trip relay, or circuit breaker
(HV and LV in series) shall be an essential requirement for the system
activation in automatic or remote electrical control.
(Drawing Nr. FS 1966 A3 01)
A. Automatic control:
A.1 Operation under prevention mode :
Due to internal arcing gases are generated, resulting into
pressurizing the transformer tank. These leads to operation of
differential relay, pressure relief valve and / or buchholz
relay. On sensing these faults, which is the first stage of
transformer being under fire, a predetermined quantity of oil
from tank top is drained, which reduces the pressure in tank.
Simultaneously conservator oil is isolated through Pre-stressed
non return valve and nitrogen gas starts injecting at
predetermined flow and pressure from lower side of the
transformer tank to reduce temperature of top oil surface.
2/2
A.2 Operation under extinction mode:
During transformer fire, Pre-stressed non return valve operates
and isolates the conservator oil to prevent further aggravation
and spreading of fire. Before rupture of tank, Pressure relief
valve and / or buchholz relay operates due to pressurization of
transformer tank. Due to fire on transformer, Fire detector will
operate. After receipt of these signals predetermined quantity of
oil will be drained. Simultaneously nitrogen gas starts injecting
at predetermined flow and pressure from lower side of the
transformer tank to reduce temperature of top oil below flash
point and extinguishes the fire.
B. Remote manual
In case system failed to operate in Auto mode due to non
availability any one signal, operator shall operate system
manually by breaking window glass and operating extinction
release switch.
C. Local Manual
In case system failed to operate in Auto mode / remote manual
mode due to non availability of either signal or failure of
power source, operator shall operate system manually from fire
extinguishing cubicle and extinguishes the fire.
VKE:dmj
20.04.2003
CTR FIRE SYSTEMS DIVISION
LOCATION:POONA
BOM FOR NITROGEN INJECTION FIRE PROTECTION SYSTEM
SR. QTY PER
ITEM DESCRIPTION REMARKS
NO. SYSTEM
1 FIRE EXTINGUISHING CUBICLE 1 NO
2 CONTROL BOX 1 NO
3 TRANSFORMER CONSERVATOR ISOLATION VALVE 1 NO
(TCIV)
4 FIRE DETECTORS 15 NOS
5 FIRE SURVIVAL CABLE 60 MTRS
6 FIRE RETARDANT LOW SMOKE (FRLS), 12CORE X 1.5 1200 MTR APPROXIMATE LENGTH *
SQ.MM, ARMOURED, COPPER
7 FIRE RETARDANT LOW SMOKE (FRLS), 4CORE X 1.5 200 MTR
SQ.MM, ARMOURED, COPPER
8 PIPES AND CONNECTION FITTINGS (TRANSFORMER- 1 SET
FEC-OIL PIT)
9 PLINTH FOR FIRE EXTINGUISHING CUBICLE 1 NO NOT IN CTR SCOPE OF SUPPLY
10 OIL PIT 1 NO NOT IN CTR SCOPE OF SUPPLY
11 SPARES FOR EACH SUBSTATION
11.1 FILLED NITROGEN CYLINDER (68 LITRE WATER 2 Nos.
CAPACITY)
11.2 HOSE PIPES WITH FITTINGS 1 set
11.3 HEAT SENSOR ASSEMBLY 3 Nos
11.4 PRESSURE REGULATOR ASSEMBLY 1 set
* Cable length through trench between 1. FEC near transformer and Control room 2. CGL
Marshalling box near transformer and control room 3. Control room and control room. May
be calculated on receipt on cable trench layout in autocad 2004/2005 format.
CUSTOMER CROMPTON GREEVES LIMITED MUMBAI (W.O. NR. 9849)
CONSULTANT TATA CONSULTING ENGINEERS LIMTTED, MUMBAI
END USER TATA STEEL LIMITED, JAMSHEDPUR
RATING 2 X 315 MVA, 400/138/34.5 kV AUTO TRANSFORMER
Prepared Checked Approved
by : DEA(FS3) by : SAPM(FS) by : VP3
Initials DMJ:dmj DMJ VKW
Date 05.01.2011 05.01.2011 05.01.2011
CTR FIRE SYSTEMS DIVISION
LOCATION:POONA
SEQUENTIAL OPERATIONS OF OIL DRAIN AND NITROGEN INJECTION
FIRE PROTECTION SYSTEM FOR OIL FILLED TRANSFORMERS.
On receipt of required operating inputs signals, 220
VDC/110VDC supply is extended through terminal Nr 22 (+ve)
and terminal Nr 23(-ve) (Terminal trip (TS1) of control box
to Terminal Nr 3 and Terminal Nr 4 (TS3) of Fire
Extinguishing cubicle respectively.
• Operation and monitoring of oil release unit and gas
release unit.
Y01 Lifting Magnet
Y01 is energized for initiation of
oil release unit i.e. depressurization
of transformer tank
G02 Limit Switch
Resets Y01 Lifting magnet
(Indicates oil drain valve closed
position, prior to initiation of oil
release unit)
NC OPEN
CONTACT CONTACT
G03 Limit Switch PO4 Pressure switch
Indicates oil drain Back-up for energizing
valve open, energizing Lifting magnet Y02
Lifting magnet Y02
NO CLOSE NO CLOSE
CONTACT CONTACT CONTACT CONTACT
Y02 Lifting Magnet
Y02 is energized for initiation of
Nitrogen gas release unit i.e.
starting of nitrogen injection
G04 Limit Switch
Indicates extinction in progress
(NO CLOSE) and resets gas
inlet valve closed indication
NC OPEN
CONTACT CONTACT
..2..
• Monitoring of Nitrogen cylinder pressure
P01 Contact Manometer
Indication of cylinder pressure low
incase pressure drops below the set
required minimum cylinder pressure
NO CLOSE
CONTACT CONTACT
• Mechanical lockings for oil release unit and gas release
unit.
G05 Limit Switch G06 Limit Switch
Indicates ‘Out of service’ Indicates ‘Out of service’
on mechanical locking of on mechanical locking of
oil release unit gas release unit
NO CLOSE NO CLOSE
CONTACT CONTACT CONTACT CONTACT
• Interlocks
a) Interlock is provided for starting draining of oil
(Depressurization) from transformer tank through
limit switch G02.
b) Interlock is provided for starting injection of
nitrogen gas into the transformer tank (after
depressurization of transformer tank) through
limit switch G03/ Pressure switch (P04)
•Spare Contacts for operation
Spare contacts are available in control box for operation
of Fire Protection system through relay K03.
•Pressure switch (P04)
Operating on differential pressure principle. Electrical
contact remain open (NO) under static pressure due to
transformer oil head. During draining of oil through oil
drain located in the fire Extinguishing Cubicle`NO’
contact get closed and energize Lifting Magnet Y02.
VKW:dmj
02.06.2006