Power Systems-III Ditital Notes
Power Systems-III Ditital Notes
Power Systems-III Ditital Notes
(R20- R20A0209)
LECTURE NOTES
B.TECH
(III YEAR – II
SEM)(2022-2023)
Assistant Professor
ENGINEERING
COURSE OBJECTIVES:
• To understand and develop Y bus matrices
• To give the knowledge on per unit system.
• To understand and develop Z bus matrices
• To give the knowledge on faults analysis.
• Give the knowledge of iterative method in power systems.
• To understand the concepts load flow studies.
UNIT I:
PER UNIT REPRESENTATION OF POWER SYSTEMS: The one-line diagram, impedance
and reactance diagrams, per unit quantities, changing the base of per unit quantities, advantages of
per unit system.
POWER SYSTEM NETWORK MATRICES: Bus Incidence Matrix, Y‐bus formation by Direct
andSingular Transformation Methods, Numerical Problems.
UNIT II:
FORMATION OF Z‐BUS: Partial network, Algorithm for the Modification of Z Bus Matrix for
addition element for the following cases: Addition of element from a new bus to reference,
Addition of element from a new bus to an old bus, Addition of element between an old bus to
reference and addition of element between two old buses
UNIT–III
SYMMETRICAL COMPONENTS AND FAULT CALCULATIONS: Significance of positive,
negative and zero sequence components, sequence impedances and sequence networks, fault
calculations, sequence network equations, single line to ground fault, line to line fault, double line
to ground fault, three phase faults, faults with fault impedance.
UNIT–IV
LOAD FLOW STUDIES I: Derivation of Static load flow equations. Load Flow Solutions Using
Gauss Seidel Method: Acceleration Factor, Load flow solution with and without P‐V buses,
Algorithm and Flowchart. Numerical Load flow Solution for Simple Power Systems (Max.
3‐Buses): Determination of Bus Voltages, Injected Active and Reactive Powers (Sample One
Iteration only) and finding Line Flows/Losses for the given Bus Voltages.
UNIT–V
LOAD FLOW STUDIES II: Numerical Load flow Solution for Simple Power Systems (Max. 3-
Buses): Determination of Bus Voltages, Injected Active and Reactive Powers (One Iteration only)
and finding Line Flows/Losses for the given Bus Voltages, Newton Raphson Method (Polar
coordinates only): Load Flow Solution with and without P-V Buses, Derivation of Jacobian
Elements, Fast Decoupled Method.
TEXT BOOKS:
1. C.L.Wadhwa, Electrical Power Systems, 3rd Edn, New Age International
Publishing Co., 2001.
2. D.P.Kothari and I.J.Nagrath, Modern Power System Analysis, 4th Edn, Tata
McGraw Hill Education Private Limited2011.
REFERENCEBOOKS:
1. D. P. Kothari: Modern Power System Analysis-Tata McGraw Hill Pub. Co. 2003
2. Hadi Scadat: Power System Analysis – Tata McGraw Hill Pub. Co.2002
3. W.D. Stevenson: Elements of Power system Analysis – McGraw Hill
International Student Edition.
COURSE OUTCOMES:
At the end of the course the student will be able to:
• Understand the concept of per unit system and faults in power systems.
• Evaluate the admittance matrix of a given power systems.
• Analyze the power system using iterative methods.
• Understand the concept of load flow studies in power system.
• Understand the PF and computer control in power system.
UNIT-I
In practice, electric power systems are very complex and their size is
unwieldy. It is very difficult to represent all the components of the system on
a single frame. The complexities could be in terms of various types of
protective devices, machines (transformers, generators, motors, etc.), their
connections (star, delta, etc.), etc. Hence, for the purpose of power system
analysis, a simple single phase equivalent circuit is developed called, the
one line diagram (OLD) or the single line diagram (SLD). An SLD is thus,
the concise form of representing a given power system. It is to be noted that a
given SLD will contain only such data that are relevant to the system
analysis/study under consideration. For example, the details of protective
devices need not be shown for load flow analysis nor it is necessary to show
the details of shunt values for stability studies.
Impedance Diagram
The impedance diagram on single-phase basis for use under balanced conditions
can be easily drawn from the SLD. The following assumptions are made in
obtaining the impedance diagrams.
Assumptions:
1. The single phase transformer equivalents are shown as ideals with impedances on
appropriate side (LV/HV),
2. The magnetizing reactances of transformers are negligible,
3. The generators are represented as constant voltage sources with series resistance or
reactance,
4. The transmission lines are approximated by their equivalent -Models,
5. The loads are assumed to be passive and are represented by a series branch of
resistance or reactance and
6. Since the balanced conditions are assumed, the neutral grounding impedances do not
appear in the impedance diagram.
Example system
As per the list of assumptions as above and with reference to the system of
figure 2, the impedance diagram can be obtained as shown in figure 3.
Reactance Diagram
Example system
as per the assumptions given above and with reference to the system of figure 2
and figure 3, the reactance diagram can be obtained as shown in figure 4.
Note: These impedance & reactance diagrams are also refered as the Positive Sequence
Diagrams/ Networks.
On the other hand, the change of base can also be done by first converting the
given pu impedance to its ohmic value and then calculating its pu value on the
new set of base values.
Merits
➢ The pu value is the same for both 1-phase and & 3-phase systems
➢ The pu value once expressed on a proper base, will be the same when refereed
to either side of the transformer. Thus the presence of transformer is totally
eliminated
➢ The variation of values is in a smaller range 9nearby unity). Hence the errors
involved in pu computations are very less.
➢ Usually the nameplate ratings will be marked in pu on the base of the name
plate ratings, etc.
Demerits:
➢ If proper bases are not chosen, then the resulting pu values may be highly
absurd (such as 5.8 pu, -18.9 pu, etc.). This may cause confusion to the user.
However, this problem can be avoided by selecting the base MVA near the
high-rated equipment and a convenient base KV in any section of the system.
The bus admittance matrix, YBUS plays a very important role in computer aided power
system analysis. It can be formed in practice by either of the methods as under:
1. Rule of Inspection
2. Singular Transformation
3. Non-Singular Transformation
4. ZBUS Building Algorithms, etc.
The performance equations of a given power system can be considered in three different
frames of reference as discussed below:
Frames of Reference:
Bus Frame of Reference: There are b independent equations (b = no. of buses) relating the
bus vectors of currents and voltages through the bus impedance matrix and bus admittance
1
POWER SYSTEMS - III R20A0209
matrix:
Of the various network matrices refered above, the bus admittance matrix (YBUS) and the
bus impedance matrix (ZBUS) are determined for a given power system by the rule of
inspection as explained next.
Rule of Inspection
Consider the 3-node admittance network as shown in figure5. Using the basic branch
relation: I = (YV), for all the elemental currents and applying Kirchhoff‟s Current
Law principle at the nodal points, we get the relations as under:
2
POWER SYSTEMS - III R20A0209
These are the performance equations of the given network in admittance form and
they can be represented in matrix form as:
In other words, the relation of equation (9) can be represented in the form
IBUS = YBUS EBUS (14)
Where, YBUS is the bus admittance matrix, IBUS & EBUS are the bus current and bus
voltage vectors respectively. By observing the elements of the bus admittance matrix,
YBUS of equation (13), it is observed that the matrix elements can as well be obtained by
a simple inspection of the given system diagram:
Diagonal elements: A diagonal element (Yii) of the bus admittance matrix, YBUS, is
equal to the sum total of the admittance values of all the elements incident at the bus/node
i,
Off Diagonal elements: An off-diagonal element (Yij) of the bus admittance matrix,
YBUS, is equal to the negative of the admittance value of the connecting element present
between the buses I and j, if any. This is the principle of the rule of inspection. Thus the
algorithmic equations for the rule of inspection are obtained as:
For i = 1,2,….n, n = no. of buses of the given system, yij is the admittance of element
connected between buses i and j and yii is the admittance of element connected between
bus i and ground (reference bus).
3
POWER SYSTEMS - III R20A0209
In cases where, the bus impedance matrix is also required, it cannot be formed by direct
inspection of the given system diagram. However, the bus admittance matrix determined
by the rule of inspection following the steps explained above, can be inverted to obtain the
bus impedance matrix, since the two matrices are interinvertible.
Note: It is to be noted that the rule of inspection can be applied only to those power
systems that do not have any mutually coupled elements.
Example 6: Obtain the bus admittance matrix for the admittance network shown aside by
the rule of inspection
Example 7: Obtain YBUS for the impedance network shown aside by the rule of
inspection. Also, determine YBUS for the reduced network after eliminating the eligible
unwanted node. Draw the resulting reduced system diagram.
4
POWER SYSTEMS - III R20A0209
SINGULAR TRANSFORMATIONS
The primitive network matrices are the most basic matrices and depend purely on the
impedance or admittance of the individual elements. However, they do not contain any
information about the behaviour of the interconnected network variables. Hence, it is
necessary to transform the primitive matrices into more meaningful matrices which can
relate variables of the interconnected network.
5
POWER SYSTEMS - III R20A0209
In the bus frame of reference, the performance of the interconnected network is described
by n independent nodal equations, where n is the total number of buses (n+1nodes are
present, out of which one of them is designated as the reference node).
For example a 5-bus system will have 5 external buses and 1 ground/ ref. bus). The
performance equation relating the bus voltages to bus current injections in bus frame of
reference in admittance form is given by
At i =0,
since it indicates a vector whose elements are the algebraic sum of element currents
incident at a bus, which by Kirchhoff‟s law is zero. Similarly, At j gives the algebraic sum
of all source currents incident at each bus and this is nothing but the total current injected
at the bus. Hence,
At j = IBUS (19)
Thus from (18) we have, IBUS = At [y] v (20)
However, from (5), we have
v =A EBUS
And hence substituting in (20) we get,
6
POWER SYSTEMS - III R20A0209
Example 8: For the network of Fig E8, form the primitive matrices [z] & [y] and obtain
the bus admittance matrix by singular transformation. Choose a Tree T(1,2,3). The data is
given in Table E8.
7
POWER SYSTEMS - III R20A0209
Solution:
The bus incidence matrix is formed taking node 1 as the reference bus.
8
POWER SYSTEMS - III R20A0209
SUMMARY
The formulation of the mathematical model is the first step in obtaining the solution of any
electrical network. The independent variables can be either currents or voltages.
Correspondingly, the elements of the coefficient matrix will be impedances or
admittances.
Network equations can be formulated for solution of the network using graph theory,
independent of the nature of elements. In the graph of a network, the tree-branches and
links are distinctly identified. The complete information about the interconnection of the
network, with the directions of the currents is contained in the bus incidence matrix.
The information on the nature of the elements which form the interconnected network is
contained in the primitive impedance matrix. A primitive element can be represented in
impedance form or admittance form. In the bus frame of reference, the performance of the
interconnected system is described by (n-1) nodal equations, where n is the number of
nodes. The bus admittance matrix and the bus impedance matrix relate the bus voltages
and currents. These matrices can be obtained from the primitive impedance and
admittance matrices.
Nodes can be eliminated by the matrix manipulation of the standard node equations.
However, only those nodes at which current does not enter or leave the network can be
considered for such elimination. Such nodes can be eliminated either in one group or by
taking the eligible nodes one after the other for elimination, as discussed next.
Consider the performance equation of the given network in bus frame of reference in
admittance form for a n-bus system, given by:
Where IBUS and EBUS are n-vectors of injected bus current and bus voltages and YBUS
is the square, symmetric, coefficient bus admittance matrix of order n. Now, of the n buses
present in the system, let p buses be considered for node elimination so that the reduced
system after elimination of p nodes would be retained with m (= n-p) nodes only. Hence
the corresponding performance equation would be similar to (1) except that the coefficient
matrix would be of order m now, i.e.,
Where YBUSnew is the bus admittance matrix of the reduced network and the vectors
9
POWER SYSTEMS - III R20A0209
IBUS and EBUS are of order m. It is assumed in (1) that IBUS and EBUS are obtained
with their elements arranged such that the elements associated with p nodes to be
eliminated are in the lower portion of the vectors. Then the elements of YBUS also get
located accordingly so that (1) after matrix partitioning yields,
Where the self and mutual values of YA and YD are those identified only with the nodes
to be retained and removed respectively and YC=YBt is composed of only the
corresponding mutual admittance values, that are common to the nodes m and p.
Now, for the p nodes to be eliminated, it is necessary that, each element of the vector
IBUS-p should be zero. Thus we have from (3):
Solving,
EBUS-p = - YD-1YC EBUS-m
(5)
Thus, by simplification, we obtain an expression similar to (2) as,
IBUS-m = {YA - YBYD-1YC} EBUS-m
(6)
Thus by comparing (2) and (6), we get an expression for the new bus admittance matrix in
terms of the sub-matrices of the original bus admittance matrix as:
YBUSnew = {YA – YBYD -1YC}
(7)
This expression enables us to construct the given network with only the necessary nodes
retained and all the unwanted nodes/buses eliminated. However, it can be observed from
(7) that the expression involves finding the inverse of the sub-matrix YD (of order p). This
would be computationally very tedious if p, the nodes to be eliminated is very large,
especially for real practical systems. In such cases, it is more advantageous to eliminate
the unwanted nodes from the given network by considering one node only at a time for
elimination, as discussed next.
Yij new = Yij old – Yin Ynj / Ynn " i,j = 1,2,…… n. (8)
10
POWER SYSTEMS - III R20A0209
Each element of the original matrix must therefore be modified as per (7). Further, this
procedure of eliminating the last numbered node from the given system of n nodes is to be
iteratively repeated p times, so as to eliminate all the unnecessary p nodes from the
original system.
Example-1: Obtain YBUS for the impedance network shown below by the rule of
inspection. Also, determine YBUS for the reduced network after eliminating the eligible
unwanted node. Draw the resulting reduced system diagram.
The reduced matrix after elimination of node 3 from the given system is determined as per the
equation:
11
POWER SYSTEMS - III R20A0209
Alternatively,
Thus the reduced network can be obtained again by the rule of inspection as shown below.
Example-2: Obtain YBUS for the admittance network shown below by the rule of
inspection. Also, determine YBUS for the reduced network after eliminating the eligible
unwanted node. Draw the resulting reduced system diagram.
12
Power System -III R20A0209
Thus the reduced system of two nodes can be drawn by the rule of inspection as under:
Power System -III R20A0209
Power System -III R20A0209
UNIT II
FORMATION OF Z‐BUS
ZBUS building
The bus impedance matrix is the inverse of the bus admittance matrix. An alternative
method is possible, based on an algorithm to form the bus impedance matrix directly from
system parameters and the coded bus numbers. The bus impedance matrix is formed
adding one element at a time to a partial network of the given system. The performance
equation of the network in bus frame of reference in impedance form using the currents as
independent variables is given in matrix form by
Now assume that the bus impedance matrix Zbus is known for a partial network of m
buses and a known reference bus. Thus, Zbus of the partial network is of dimension mxm.
If now a new element is added between buses p and q we have the following two
possibilities:
(i) p is an existing bus in the partial network and q is a new bus; in this case p-q is a
branch added to the p-network as shown in Fig 1a, and
Power System -III R20A0209
(ii) both p and q are buses existing in the partial network; in this case p-q is a link
added to the p-network as shown in Fig 1b.
Power System -III R20A0209
If the added element ia a branch, p-q, then the new bus impedance matrix would be of
order m+1, and the analysis is confined to finding only the elements of the new row and
column (corresponding to bus-q) introduced into the original matrix. If the added element
ia a link, p-q, then the new bus impedance matrix will remain unaltered with regard to its
order. However, all the elements of the original matrix are updated to take account of the
effect of the link added.
ADDITION OF A BRANCH
Consider now the performance equation of the network in impedance form with the added
branch p-q, given by
It is assumed that the added branch p-q is mutually coupled with some elements of the
partial network and since the network has bilateral passive elements only, we have
Vector ypq-rs is not equal to zero and Zij= Zji " i,j=1,2,…m,q
(12)
To find Zqi:
The elements of last row-q and last column-q are determined by injecting a current of 1.0
pu at the bus-i and measuring the voltage of the bus-q with respect to the reference bus-0,
as shown in Fig.2. Since all other bus currents are zero, we have from (11) that
Also, Eq=Ep -vpq ; so that Zqi = Zpi - vpq " i =1, 2,…i.…...p,….m, _q
(14)
To find vpq:
In terms of the primitive admittances and voltages across the elements, the current through
the elements is given by
Power System -III R20A0209
Special Cases
The following special cases of analysis concerning ZBUS building can be considered with
respect to the addition of branch to a p-network.
Power System -III R20A0209
ADDITION OF A LINK
Consider now the performance equation of the network in impedance form with the added
link p-l, (p-l being a fictitious branch and l being a fictitious node) given by
It is assumed that the added branch p-q is mutually coupled with some elements of the
partial network and since the network has bilateral passive elements only, we have
To find Zli:
The elements of last row-l and last column-l are determined by injecting a current of 1.0
pu at the bus-i and measuring the voltage of the bus-q with respect to the reference bus-0,
as shown in Fig.3. Further, the current in the added element is made zero by connecting a
voltage source, el in series with element p-q, as shown. Since all other bus currents are
zero, we have from (25) that
Power System III R20A0209
To find vpq:
In terms of the primitive admittances and voltages across the elements, the current through
the elements is given by
Power System -III R20A0209
Power System -III R20A0209
From (39), it is thus observed that, when a link is added to a ref. bus, then the situation is
similar to adding a branch to a fictitious bus and hence the following steps are followed:
Power System -III R20A0209
1. The element is added similar to addition of a branch (case-b) to obtain the new matrix
of order m+1.
2. The extra fictitious node, l is eliminated using the node elimination algorithm.
Case (d): If there is no mutual coupling, then elements of pq rs y , are zero. Further, if p is
not the reference node, then
An element which is not coupled to any other element can be removed easily. The Zbus is
modified as explained in sections above, by adding in parallel with the element (to be
removed), a link whose impedance is equal to the negative of the impedance of the
element to be removed. Similarly, the impedance value of an element which is not coupled
to any other element can be changed easily. The Zbus is modified again as explained in
sections above, by adding in parallel with the element (whose impedance is to be
changed), a link element of impedance value chosen such that the parallel equivalent
impedance is equal to the desired value of impedance. When mutually coupled elements
are removed, the Zbus is modified by introducing appropriate changes in the bus currents
of the original network to reflect the changes introduced due to the removal of the
elements.
Example 1: For the positive sequence network data shown in table below, obtain ZBUS
by building procedure.
Solution:
The given network is as shown below with the data marked on it. Assume the elements to
be added as per the given sequence: 0-1, 0-3, 1-2, and 2-3.
Power System -III R20A0209
Step-2: Add element–2 of impedance 0.2 pu from the external node-3 (q=3) to internal ref.
node-0 (p=0). (Case-a), as shown in the partial network;
Power System -III R20A0209
Step-3: Add element–3 of impedance 0.08 pu from the external node-2 (q=2) to internal node-
1 (p=1). (Case-b), as shown in the partial network;
Step-4: Add element–4 of impedance 0.06 pu between the two internal nodes, node-2
(p=2) to node-3 (q=3). (Case-d), as shown in the partial network;
Power System -III R20A0209
The fictitious node l is eliminated further to arrive at the final impedance matrix as under:
Power System -III R20A0209
Power System -III R20A0209
Power System -III R20A0209
Solution: The specified system is considered with the reference node denoted by node-0.
By its inspection, we can obtain the bus impedance matrix by building procedure by
following the steps through the p-networks as under:
Step1: Add branch 1 between node 1 and reference node. (q =1, p = 0)
Now the extra node-l has to be eliminated to obtain the new matrix of step-4, using the
algorithmic relation:
32
UNIT III
FAULT ANALYSIS
INTRODUCTION
A fault is any abnormal condition in a power system. The steady state operating mode of a
power system is balanced 3-phase a.c. .However, due to sudden external or internal
changes in the system, this condition is disrupted.
When the insulation of the system fails at one or more points or a conducting object
comes into contact with a live point, a short circuit or a fault occurs.
• Lightning
• Heavy winds
• Trees falling across lines
• Vehicles colliding with towers or poles
• Birds shorting lines
• Aircraft colliding with lines
• Vandalism
• Small animals entering switchgear
• Line breaks due to excessive loading
All the above results into retarded development due to low gross domestic product realised.
It is important therefore to determine the values of system voltages and currents during
faulted conditions, so that protective devices may be set to detect and minimize the harmful
effects of such contingencies
The emf is the open circuit voltage as seen from the terminals under consideration and the
impedance is the network impedance as seen from these terminals.
This circuit consisting of a single emf and impedance is known as Thevenin’s equivalent
circuit.
The calculation of fault current can then be very easily done by applying this theorem after
obtaining the open circuit emf and network impedance as seen from the fault point.
SYMMETRICAL COMPONENTS
The majority of faults in power systems are asymmetrical. To analyse an asymmetrical fault,
an unbalanced 3- phase circuit has to be solved. Since the direct solution of such a circuit is
very difficult, the solution can be more easily obtained by using symmetrical components
since this yields three (fictitious) single phase networks, only one of which contains a driving
emf.
Since the system reactances are balanced the thee fictitious networks have no mutual coupling
between them, a fact that is making this method of analysis quite simple.
1. A positive sequence set of three symmetrical voltages (i.e. all numerically equal
and all displaced from each other by 1200) having the same phase sequence abc as the
original set and denoted by Va1,Vb1,Vc1 as shown in the fig(1a)
Vc1 Va1
Vb1
Fig. (a)
2. A negative sequence set of three symmetrical voltages having the phase sequence
opposite to that of the original set and denoted by Va2, Vb2, Vc2 as shown in fig(1b)
Va2
Vb2
Vc2
Fig. 1 (b)
3. A zero sequence set of three voltages, all equal in magnitude and in phase with each other
and denoted by Va0, Vb0, Vc0 as shown in fig (1c) below:
Va0
Vb0
Vc0
Fig. 1 (c )
The positive, negative and zero sequence sets above are known as symmetrical components.
Thus we have,
Generally the subscripts 1, 2 and 0 are used to indicate positive sequence, negative sequence
and zero sequence respectively.
The symmetrical components do not have separate existence; they are just mathematical
components of unbalanced currents (or voltages) which actually flow in the system.
1.2.2 The “a” operator
The operator “a” as used in symmetrical components is one in which when multiplied to a
vector, rotates the vector through 1200 in a positive (anticlockwise) direction without
changing the magnitude.
In any part of the circuit, the voltage drop caused by current of a certain sequence depends on
the impedance of that part of the circuit to current of that sequence.
The impedance of any section of a balanced network to current of one sequence may be
different from impedance to current of another sequence.
The impedance of a circuit when positive sequence currents are flowing is called impedance,
When only negative sequence currents are flowing the impedance is termed as negative
sequence impedance.
With only zero sequence currents flowing the impedance is termed as zero sequence
impedance.
The analysis of unsymmetrical faults in power systems is carried out by finding the
symmetrical components of the unbalanced currents. Since each sequence current causes a
voltage drop of that sequence only, each sequence current can be considered to flow in an
independent network composed of impedances to current of that sequence only.
The single phase equivalent circuit composed of the impedances to current of any one
sequence only is called the sequence network of that particular sequence.
The sequence networks contain the generated emfs and impedances of like sequence.
Therefore for every power system we can form three- sequence network s. These sequence
networks, carrying current Ia1, Ia2 and Ia0 are then inter-connected to represent the different
fault conditions.
It is noted that for this condition, the relative phase positions of the voltages applied to the
motor are the same as for the negative sequence set.
Hence, a negative sequence set of voltages produces a rotating field rotating in an opposite
direction to that of positive sequence.
For both positive and negative sequence components, the standard convention of counter
clockwise rotation is followed.
The application of zero sequence voltages does not produce any field because these voltages
are in phase and the three -phase windings are displaced by 1200.The positive and the
negative sequence set are the balanced one. Thus, if only positive and negative sequence
currents are flowing, the phasor sum of each will be zero and there will be no residual current.
However, the zero sequence components of currents in the three phases are in phase and the
residual current will be three times the zero sequence current of one phase. In the case of a
fault involving ground, the positive and negative sequence currents are in equilibrium while
the zero sequence currents flow through the ground and overhead ground wires.
SEQUENCE NETWORKS OF SYNCHRONOUS MACHINES
An unloaded synchronous machine having its neutral earthed through impedance, zn, is shown
in fig. 2(a) below.
A fault at its terminals causes currents Ia, Ib and Ic to flow in the lines. If fault involves earth, a
current In flows into the neutral from the earth. This current flows through the neutral
impedance Zn.
Thus depending on the type of fault, one or more of the line currents may be zero.
Ia1
a
Ea +
-
In Zn
n
- Eb +
- Ib1
Ec
+ b
c
Ic1
Fig.2 (a)
Positive sequence network
The generated voltages of a synchronous machine are of positive sequence only since the
windings of a synchronous machine are symmetrical.
The positive sequence network consists of an emf equal to no load terminal voltages and is in
series with the positive sequence impedance Z1 of the machine. Fig.2 (b) and fig.2(c) shows
the paths for positive sequence currents and positive sequence network respectively on a
single phase basis in the synchronous machine. The neutral impedance Zn does not appear in
the circuit because the phasor sum of Ia1, Ib1 and Ic1 is zero and no positive sequence current
can flow through Zn. Since its a balanced circuit, the positive sequence N
The reference bus for the positive sequence network is the neutral of the generator.
The positive sequence impedance Z1 consists of winding resistance and direct axis reactance.
The reactance is the sub-transient reactance X”d or transient reactance X’d or synchronous
reactance Xd depending on whether sub-transient, transient or steady state conditions are
being studied.
From fig.2 (b) , the positive sequence voltage of terminal a with respect to the reference bus is
given by:
Z1 +
-
- Eb +
Ib1
Z1
-
Ec
+ b
Ic1
Fig.2 (b)
Reference bus
-
Ea
Z1
a
Ia1
Fig.2(c)
Thus the negative sequence mmf alternates past the direct and quadrature axis and sets up a
varying armature reaction effect. Thus, the negative sequence reactance is taken as the
average of direct axis and quadrature axis sub-transient reactance, i.e.,
It not necessary to consider any time variation of X2 during transient conditions because there
is no normal constant armature reaction to be effected. For more accurate calculations, the
negative sequence resistance should be considered to account for power dissipated in the rotor
poles or damper winding by double supply frequency induced currents.
The fig.2 (d) and fig.2 (e) shows the negative sequence currents paths and the negative
sequence network respectively on a single phase basis of a synchronous machine.
The reference bus for the negative sequence network is the neutral of the machine. Thus, the
negative sequence voltage of terminal a with respect to the reference bus is given by:
Va2= -Z2Ia2
Ia2
Z2
Z2
Z2
Ib2
b
Ic2
Fig.2 (d)
Reference bus
Z2
a
Ia2
Fig.2 (e)
2.0.3 Zero sequence network
No zero sequence voltage is induced in a synchronous machine. The flow of zero sequence
currents in the stator windings produces three mmf which are in time phase. If each phase
winding produced a sinusoidal space mmf, then with the rotor removed, the flux at a point on
the axis of the stator due to zero sequence current would be zero at every instant.
When the flux in the air gap or the leakage flux around slots or end connections is considered,
no point in these regions is equidistant from all the three –phase windings of the stator.
The mmf produced by a phase winding departs from a sine wave, by amounts which depend
upon the arrangement of the winding.
The zero sequence currents flow through the neutral impedance Zn and the current flowing
through this impedance is 3Ia0.
Fig.2(f) and fig.2(g) shows the zero sequence current paths and zero sequence network
respectively, and as can be seen, the zero sequence voltage drop from point a to ground is -
3Ia0Zn –Ia0Zg0 where Zg0 is the zero sequence impedance per phase of the generator.
Since the current in the zero sequence network is Ia0 this network must have an impedance of
3Zn +Zg0. Thus,
Z0 =3Zn +Zg0
The zero sequence voltage of terminal a with respect to the reference bus is thus:
Va0 = -Ia0Z0
Ia0
a
Zg0
Ea
Ia0+ Ib0+ Ic0
n Zg0
Zn Ib0
Zg0
b
c
Ic0
Fig.2 (f)
Reference bus
3Zn
Z0
Zg0
Ia0
Fig.2 (g)
SEQUENCE IMPEDANCES OF TRANSMISSION LINE
The positive and negative sequence impedances of linear symmetrical static circuits do not
depend on the phase sequence and are, therefore equal. When only zero sequence currents
flow in the lines, the currents in all the phases are identical. These currents return partly
through the ground and partly through overhead ground wires.
The magnetic field due to the flow of zero sequence currents through line, ground and round
wires is very different from the magnetic field due to positive sequence currents. The zero
sequence reactance of lines is about 2 to 4 times the positive sequence reactance.
A transformer for a 3-phase circuit may consist of three single phase transformers with
windings suitably connected in star or delta or it may be a 3-phase unit.
Modern transformers are invariably three-phase units because of their lower cost, lesser space
requirements and higher efficiency. The positive sequence impedance of a transformer equals
its leakage impedance. The resistance of the windings is usually small as compared to leakage
reactance.
For transformers above 1 MVA rating, the reactance and impedance are almost equal. Since
the transformer is a static device, the negative sequence impedance is equal to the positive
sequence impedance.
The zero sequence impedance of 3-phase units is slightly different from positive sequence
impedance. However the difference is very slight and the zero sequence impedance is also
assumed to be the same as the positive sequence impedance.
The flow of zero sequence currents through a transformer and hence in the system depends
greatly on the winding connections. The zero sequence currents can flow through the winding
connected in star only if the star point is grounded. If the star point isolated zero sequence
currents cannot flow in the winding.
The zero sequence currents cannot flow in the lines connected to a delta connected winding
because no return path is available for these zero sequence currents. However, the zero
sequence currents caused by the presence of zero sequence voltages can circulate through the
delta connected windings.
The positive sequence network is the same as the single line reactance diagram used for the
calculation of symmetrical fault current. The reference bus for positive sequence network is
the system neutral.
The negative sequence network is similar to the positive sequence network except that the
negative sequence network does not contain any voltage source. The negative sequence
impedances for transmission line and transformers are the same as the positive sequence
impedances. But the negative sequence impedance of a synchronous machine may be
different from its positive sequence impedance.
Any impedance connected between a neutral and ground is not included in the positive and
negative sequence networks because the positive and the negative sequence currents cannot
flow through such impedance.
The zero sequence network also does not contain any voltage source. Any impedance
included between neutral and ground becomes three times its value in a zero sequence
network.
The following are the summary of the rules for the formation of sequence networks:-
• The positive sequence network is the same as single line impedance or reactance
diagram used in symmetrical fault analysis. The reference bus for this network is the
system neutral.
• The generators in power system produce balanced voltages. Therefore only positive
sequence network has voltage source. There are no voltage sources in negative and
zero sequence networks.
• The positive sequence current can cause only positive sequence voltage drop.
Similarly negative sequence current can cause only negative sequence voltage drop
and zero sequence current can cause only zero sequence voltage drop.
• The reference for negative sequence network is the system neutral. However, the
reference for zero sequence network is the ground. Zero sequence current can flow
only if the neutral is grounded.
• The neutral grounding impedance Zn appears as 3Zn in the zero sequence network.
• The three sequence networks are independent and are interconnected suitably
depending on the type of fault.
UNSYMMETRICAL FAULTS
The basic approach to the analysis of unsymmetrical faults is to consider the general situation
shown in the fig.3.0 which shows the three lines of the three- phase power system at the point
of fault.
The general terminals brought out are for purposes of external connections which simulate the
fault. Appropriate connections of the three stubs represent the different faults, e.g., connecting
stub `a’ to ground produces a single line to ground fault, through zero impedance, on phase
`a’. The currents in stubs b and c are then zero and Ia is the fault current.
Similarly, the connection of stubs b and c produces a line to line fault, through zero
impedance, between phases b and c, the current in stub a is then zero and Ib is equal to Ic.The
positive assignment of phase quantities is important. It is seen that the currents flow out of
the system.
The three general sequence circuits are shown in fig.3.1 (a). The ports indicated correspond to
the general 3- phase entry port of fig.3.1. A suitable inter- connection of the three- sequence
networks depending on the type fault yields the solution to the problem.
The sequence networks of fig.3.1 (a) can be replaced by equivalent sequence networks of
fig.3.1 (b) . Z0, Z1 and Z2 indicate the sequence impedances of the network looking into the
fault
Ia Ib Ic
+ + +
n Va Vb Vc
Z0 Ia0
Zero Ia0 +
sequence +
network Va0 Va0
- -
Ia1 Z1 Ia1
Positive + +
sequence +
Va1 E
network - Va1
-
-
Ia2 Z2 Ia2
Negative +
+
sequence
network Va2
Va2
-
-
Ib = 0
Ic = 0
Va = IaZf
Ia + Ib Ic
Zf
Va + Vb + Vc
n
Fig. 3.2
Connections of sequence networks for a single line to ground fault and its simplified
equivalent circuit are shown in the fig. 3.3(a) and fig. 3.3 (b) below:
Equivalent sequence networks
General sequence networks
Ia0 Ia1
Ia0
Zero Z0
Va0
+
Sequence
Va0
network
-
Ia1
Ia1
Z1
Positive
+ Va1 3Zf
Sequence +
3Zf
Va1 E0
network
-
-
Sequence
The Z2
+ Va2
network Va2
-
Fig.3.3 (b)
Fig.3.3 (a)
LINE TO LINE FAULT
The termination of the three- phase access port as in the fig.3.4 below simulates a line to line
fault through a fault impedance Zf .
Ia Ib Ic
+ +
Zf
Va Vb Vc
n
Fig. 3.4
The terminal conditions at the fault point give the following equations,
Ia = 0
Ib = -Ic
Vb = Vc + Zf Ib
Connection of sequence networks for a line to line fault and its simplified equivalent circuit
are shown in the fig.3.5 (a) and fig.(b) below.
Equivalent sequence networks
General sequence networks
Ia0
Zero
+
Sequence
network
Ia1
Ia1
Positive
Z1
Sequence + +
network Zf E0 Zf
Va1
+- -
Ia2 Ia2
Negative
Sequence
+
Network Z2
Va2
The terminal conditions at the fault point give the following equations,
Ia = 0
Vb = Vc = ( Ib + Ic ) Zf
Ia Ib Ic
+ +
Zf
Va Vb Vc
n
Fig. 3.6
The sequence networks and the equivalent circuit are shown by the Fig.3.7 (a) and Fig. 3.7 (b)
below
Equivalent sequence networks
General sequencenetworks
Ia0 +
Zero 3Zf Ia0 3Zf
Sequence Va0
network Z0 Va0
-
Ia1
Ia1
Positive +
Z1
Sequence +
Va1
network E0 Va1
- -
Ia2
Ia2
Negative +
Sequence
Network Va2 Z2
Va2
-
Fig. 3.7(a) Fig.3.7 (b)
Power System -III R20A0209
It is an important type of fault in that it results in an easy calculation and generally, a pessimistic
answer.
The circuit breaker rated MVA breaking capacity is based on 3- phase fault MVA. Since circuit
breakers are manufactured in preferred standard sizes e.g. 250, 500, 750 MVA high precision is not
necessary when calculating the 3- phase fault level at a point in a power system.
The system impedances are also never known accurately in three phase faults.
Power System -III R20A0209
UNIT-IV
The numerical analysis involving the solution of algebraic simultaneous equations forms
the basis for solution of the performance equations in computer aided electrical power
system analyses, such as during linear graph analysis, load flow analysis (nonlinear
equations), transient stability studies (differential equations), etc. Hence, it is necessary to
review the general forms of the various solution methods with respect to all forms of
equations, as under:
* Iterative methods:
- Gauss Method
- Gauss-Siedel Method (for diagonally dominant systems)
It is to be observed that the nonlinear and differential equations can be solved only by the
iterative methods. The iterative methods are characterized by the various performance
features as under:
_ Selection of initial solution/ estimates
_ Determination of fresh/ new estimates during each iteration
_ Selection of number of iterations as per tolerance limit
_ Time per iteration and total time of solution as per the solution method selected
_ Convergence and divergence criteria of the iterative solution
_ Choice of the Acceleration factor of convergence, etc.
Power System -III R20A0209
Introduction: Load flow studies are important in planning and designing future expansion
of power systems. The study gives steady state solutions of the voltages at all the buses,
for a particular load condition. Different steady state solutions can be obtained, for
different operating conditions, to help in planning, design and operation of the power
system. Generally, load flow studies are limited to the transmission system, which
involves bulk power transmission. The load at the buses is assumed to be known. Load
flow studies throw light on some of the important aspects of the system operation, such as:
violation of voltage magnitudes at the buses, overloading of lines, overloading of
generators, stability margin reduction, indicated by power angle differences between buses
linked by a line, effect of contingencies like line voltages, emergency shutdown of
generators, etc. Load flow studies are required for deciding the economic operation of the
power system. They are also required in transient stability studies. Hence, load flow
studies play a vital role in power system studies. Thus the load flow problem consists of
finding the power flows (real and reactive) and voltages of a network for given bus
conditions. At each bus, there are four quantities of interest to be known for further
analysis: the real and reactive power, the voltage magnitude and its phase angle. Because
of the nonlinearity of the algebraic equations, describing the given power system, their
solutions are obviously, based on the iterative methods only. The constraints placed on the
load flow solutions could be:
_ The Kirchhoff‟s relations holding good,
_ Capability limits of reactive power sources,
_ Tap-setting range of tap-changing transformers,
_ Specified power interchange between interconnected systems,
_ Selection of initial values, acceleration factor, convergence limit, etc.
Classification of buses for LFA: Different types of buses are present based on the
specified and unspecified variables at a given bus as presented in the table below:
Power System -III R20A0209
Importance of swing bus: The slack or swing bus is usually a PV-bus with the largest
capacity generator of the given system connected to it. The generator at the swing bus
supplies the power difference between the “specified power into the system at the other
buses” and the “total system output plus losses”. Thus swing bus is needed to supply the
additional real and reactive power to meet the losses. Both the magnitude and phase angle
of voltage are specified at the swing bus, or otherwise, they are assumed to be equal to 1.0
p.u. and 00 , as per flat-start procedure of iterative
solutions. The real and reactive powers at the swing bus are found by the computer routine
as part of the load flow solution process. It is to be noted that the source at the swing bus is
a perfect one, called the swing machine, or slack machine. It is voltage regulated, i.e., the
magnitude of voltage fixed. The phase angle is the system reference phase and hence is
fixed. The generator at the swing bus has a torque angle and excitation which vary or
swing as the demand changes. This variation is such as to produce fixed voltage.
coefficient matrices. This is due to the fact that only the non-zero elements YBUS can be
stored during the computer based implementation of the schemes, by adopting the suitable
optimal storage schemes. While YBUS is thus highly sparse, it‟s inverse, ZBUS, the bus
impedance matrix is not so. It is a FULL matrix, unless the optimal bus ordering schemes
are followed before proceeding for load flow analysis.
Here, the analysis is restricted to a balanced three-phase power system, so that the analysis
can be carried out on a single phase basis. The per unit quantities are used for all
quantities. The first step in the analysis is the formulation of suitable equations for the
power flows in the system. The power system is a large interconnected system, where
various buses are connected by transmission lines. At any bus, complex power is injected
into the bus by the generators and complex power is drawn by the loads. Of course at any
bus, either one of them may not be present. The power is transported from one bus to other
via the transmission lines. At any bus i, the complex power Si (injected), shown in figure
1, is defined as
where Si = net complex power injected into bus i, SGi = complex power injected by the
generator at bus i, and SDi = complex power drawn by the load at bus i. According to
conservation of complex power, at any bus i, the complex power injected into the bus must
be equal to the sum of complex power flows out of the bus via the transmission lines.
Hence,
where IGi is the current injected by the generator at the bus and IDi is the current drawn
by the load (demand) at that bus. In the bus frame of reference
Equations (9)-(10) and (13)-(14) are the „power flow equations‟ or the „load flow
equations‟ in two alternative forms, corresponding to the n-bus system, where each bus-i is
characterized by four variables, Pi, Qi, |Vi|, and di. Thus a total of 4n variables are
Power System -III R20A0209
involved in these equations. The load flow equations can be solved for any 2n unknowns,
if the other 2n variables are specified. This establishes the need for classification of buses
of the system for load flow analysis into: PV bus, PQ bus, etc.
Irrespective of the method used for the solution, the data required is common for any load
flow. All data is normally in pu. The bus admittance matrix is formulated from these data.
The various data required are as under:
Generator bus data: For every PV bus i, the data required includes the bus number,
active power generation PGi, the specified voltage magnitude i sp V , , minimum reactive
power limit Qi,min, and maximum reactive power limit Qi,max.
Load data: For all loads the data required includes the the bus number, active power
demand PDi, and the reactive power demand QDi.
Transmission line data: For every transmission line connected between buses i and k the
data includes the starting bus number i, ending bus number k,.resistance of the line,
reactance of the line and the half line charging admittance.
Transformer data:
For every transformer connected between buses i and k the data to be given includes: the
starting bus number i, ending bus number k, resistance of the transformer, reactance of the
transformer, and the off nominal turns-ratio a.
Shunt element data: The data needed for the shunt element includes the bus number
where element is connected, and the shunt admittance (Gsh + j Bsh).
Equation (17) is an implicit equation since the unknown variable, appears on both sides of
the equation. Hence, it needs to be solved by an iterative technique. Starting from an initial
estimate of all bus voltages, in the RHS of (17) the most recent values of the bus voltages
is substituted. One iteration of the method involves computation of all the bus voltages. In
Gauss–Seidel method, the value of the updated voltages are used in the computation of
subsequent voltages in the same iteration, thus speeding up convergence. Iterations are
carried out till the magnitudes of all bus voltages do not change by more than the tolerance
value. Thus the algorithm for GS method is as under:
Here note that when computation is carried out for bus-i, updated values are already
available for buses 2,3….(i-1) in the current (k+1)st iteration. Hence these values are used.
For buses (i+1)…..n, values from previous, kth iteration are used.
Where,e is the tolerance value. Generally it is customary to use a value of 0.0001 pu.
Compute slack bus power after voltages have converged using (15) [assuming bus 1 is
slack bus].
Case (c): Systems with PV buses with reactive power generation limits specified:
In the previous algorithm if the Q limit at the voltage controlled bus is violated during any
iteration, i.e (k +1) i Q computed using (21) is either less than Qi, min or greater than
Qi,max, it means that the voltage cannot be maintained at the specified value due to lack
of reactive power support. This bus is then treated as a PQ bus in the (k+1)st iteration and
the voltage is calculated with the value of Qi set as follows:
If in the subsequent iteration, if Qi falls within the limits, then the bus can be switched
back to PV status.
Acceleration of convergence
It is found that in GS method of load flow, the number of iterations increase with increase
in the size of the system. The number of iterations required can be reduced if the
correction in voltage at each bus is accelerated, by multiplying with a constant α, called
the acceleration factor. In the (k+1)st iteration we can let
where is a real number. When =1, the value of (k +1) is the computed value. If 1<
<2 then the value computed is extrapolated. Generally _ is taken between 1.2 to 1.6, for
GS load flow procedure. At PQ buses (pure load buses) if the voltage magnitude violates
Power System -III R20A0209
the limit, it simply means that the specified reactive power demand cannot be supplied,
with the voltage maintained within acceptable limits.
Since the difference in the voltage magnitudes is less than 10-6 pu, the iterations can be
stopped. To compute line flow
Power System -III R20A0209
The total loss in the line is given by S12 + S21 = j 0.133329 pu Obviously, it is observed
that there is no real power loss, since the line has no resistance.
Power System -III R20A0209
Example-2:
For the power system shown in fig. below, with the data as given in tables below, obtain
the bus voltages at the end of first iteration, by applying GS method.
Power System -III R20A0209
Power System -III R20A0209
Power System III R20A0215
Example-3:
Obtain the load flow solution at the end of first iteration of the system with data as given
below. The solution is to be obtained for the following cases
(i) All buses except bus 1 are PQ Buses
(ii) Bus 2 is a PV bus whose voltage magnitude is specified as 1.04 pu
Power System III R20A0209
(iii) Bus 2 is PV bus, with voltage magnitude specified as 1.04 and 0.25_Q2_1.0 pu.
Power System -III R20A0209
Power System -III
s
Power System -III R20A0209
Power System -III R20A0209
Power System -III R20A0209
GS method is very useful for very small systems. It is easily adoptable, it can be
generalized and it is very efficient for systems having less number of buses. However, GS
LFA fails to converge in systems with one or more of the features as under:
• Systems having large number of radial lines
• Systems with short and long lines terminating on the same bus
• Systems having negative values of transfer admittances
• Systems with heavily loaded lines, etc.
UNIT–V
LOAD FLOW STUDIES II:
Power System -III R20A0215
Here, the matrix [J] is called the Jacobian matrix. The vector of unknown variables is
updated using (30). The process is continued till the difference between two successive
iterations is less than the tolerance value.
24
Power System -III R20A0209
Power System -III R20A0209
Power System -III R20A0209
Power System -III R20A0209
Power System -III
Power System -III
28
Power System -III R20A0209
Power System -III R20A0209
Power System -III R20A0209
Power System Analysis R17A0215
FINAL WORD
In this chapter, the load flow problem, also called as the power flow problem, has
been considered in detail. The load flow solution gives the complex voltages at all the
buses and the complex power flows in the lines. Though, algorithms are available
using the impedance form of the equations, the sparsity of the bus admittance matrix
and the ease of building the bus admittance matrix, have made algorithms using the
admittance form of equations more popular. The most popular methods are the Gauss-
Seidel method, the Newton-Raphson method and the Fast Decoupled Load Flow
method. These methods have been discussed in detail with illustrative examples. In
smaller systems, the ease of programming and the memory requirements, make GS
method attractive. However, the computation time increases with increase in the size
of the system. Hence, in large systems NR and FDLF methods are more popular.
There is a trade off between various requirements like speed, storage, reliability,
computation time, convergence characteristics etc. No single method has all the
desirable features. However, NR method is most popular because of its versatility,
reliability and accuracy.