Manual Og200c (S)
Manual Og200c (S)
Manual Og200c (S)
Instruction Manual
TeamTec Incinerator
OG200C/OG200CS
TG5.2
1
OG200C(S)
2
OG200C(S)
3
ADDENDUMS, CORRECTIONS AND NOTES
All Teamtec incinerators are made according to EC Type-Examination Certificate MED-B, and
are found to comply with the requirements in the following regulations/standards:
Annex A.1, item NO. A1/2.7 and Annex B, Module B in the Directive. Marpol 73/78 as amended,
Annex VI Regulation 16(2)(a), IMO Res. MEPC. 244(66), adopted April 4th, 2014 (Replacing
MEPC.76(40)).
4
LIST OF CONTENTS
Table of contents
ADDENDUMS, CORRECTIONS AND NOTES..................................................................................... 4
TABLE OF CONTENTS............................................................................................................................ 5
PART I: OPERATOR MANUAL...............................................................................................................9
INTRODUCTION.......................................................................................................................................10
INSTRUCTION MANUAL, PURPOSE AND SCOPE...........................................................................................10
SERVICE NETWORK FOR TEAMTEC INCINERATORS................................................................................... 10
SAFETY MARKINGS...............................................................................................................................11
GENERAL USE AND SAFETY INSTRUCTIONS.............................................................................. 11
ACRONYMS AND TERMS..................................................................................................................... 12
TECHNICAL DESCRIPTION AND MAIN DATA................................................................................ 13
OVERALL SYSTEM FUNCTION DESCRIPTION...............................................................................................13
Combustion chamber...........................................................................................................................13
Main data/Performance data: Incinerator (combustion chamber)............................................................... 14
Burner (fixed on combustion chamber).............................................................................................................14
Sludge dosage pump (fixed on combustion chamber).................................................................................. 15
Sludge filling pump (if dual sludge tank system).............................................................................................15
Diesel oil preheater (fixed on combustion chamber)......................................................................................15
Diesel oil booster pump (optional)..................................................................................................................... 15
Electrical control panel incinerator (normally fixed on combustion chamber)........................................... 15
Operator panel (User terminal/display fixed to control panel), description................................................ 16
Operator panel, main data...................................................................................................................................17
Flue gas fan (bulkhead or deck mounted)........................................................................................18
Main data/Performance data: Flue gas fan......................................................................................................18
Flue gas damper...................................................................................................................................18
Main data/Performance data: Flue gas damper..............................................................................................18
Sludge service tank..............................................................................................................................19
Sludge settling tank with heater (optional)....................................................................................... 19
Sludge burning capacity.......................................................................................................................................20
Sludge burning control......................................................................................................................................... 20
Main data/Performance data: Sludge tank.......................................................................................................21
Sludge circulating pump. (installed on sludge tank).......................................................................................21
CONTROL PROGRAM DESCRIPTION AND OPERATOR INSTRUCTIONS.............................. 22
GENERAL PROGRAM OVERVIEW................................................................................................................. 22
INCINERATOR CONTROL CABINET, OPERATOR PANEL DESCRIPTION........................................................ 23
General overview of the touch screen...............................................................................................23
Screens seen in the incinerator control panel display.................................................................... 24
Structure..................................................................................................................................................................24
Pop-up menu Start -Stop..................................................................................................................................... 25
Information pop-up................................................................................................................................................25
Burner screen.........................................................................................................................................................26
Settings tanks.........................................................................................................................................................26
Hour counters.........................................................................................................................................................27
Setup menu............................................................................................................................................................ 27
Backlight menu...................................................................................................................................................... 28
Time and date menu.............................................................................................................................................28
Program information............................................................................................................................................. 28
Consumption.......................................................................................................................................................... 29
Consumption setup............................................................................................................................................... 29
Alarm system......................................................................................................................................................... 29
The alarm Screen..................................................................................................................................................30
GENERAL OPERATOR INSTRUCTIONS......................................................................................................... 31
Garbage management.........................................................................................................................31
Types of waste that can be burned................................................................................................... 31
Solid and liquid waste that is prohibited to burn.............................................................................. 31
General use- and safety instructions.................................................................................................32
5
INTRODUCTION
Emergency stops..................................................................................................................................32
In the incinerator room......................................................................................................................................... 32
Outside the incinerator room...............................................................................................................................32
Important to know, before you start using the incinerator: When emergency stop is used, or at black
out.............................................................................................................................................................................32
THE SLUDGE BURNING PROGRAM.............................................................................................................. 33
Description.............................................................................................................................................33
General sludge burning use- and safety instructions..................................................................... 33
Operator procedure..............................................................................................................................34
THE SOLID WASTE BURNING PROGRAM......................................................................................................35
Description.............................................................................................................................................35
Batch loading......................................................................................................................................................... 35
Sluice feeding.........................................................................................................................................................35
General solid waste burning use- and safety instructions............................................................. 35
Operator procedure..............................................................................................................................36
THE COMBINED SOLID WASTE AND SLUDGE BURNING PROGRAM............................................................. 37
Description.............................................................................................................................................37
Operator procedure..............................................................................................................................37
THE SLAGGING PROGRAM...........................................................................................................................37
Description.............................................................................................................................................37
Operator procedure..............................................................................................................................37
PART II: MAINTENANCE MANUAL.....................................................................................................39
MAINTENANCE INSTRUCTIONS.................................................................................................................... 40
Preventive maintenance system........................................................................................................ 40
REGULAR MAINTENANCE CHECK LIST.......................................................................................41
Recommended Minimum spare parts............................................................................................................... 45
One year wear and tear parts OG200/400C, TG5.2...................................................................................... 45
Recommended on board repair parts, OG200/400C, TG5.2....................................................................... 46
MAINTENANCE, REPAIR TASKS AND PROCEDURES....................................................................................47
General tool list..................................................................................................................................... 47
Incinerator..............................................................................................................................................47
Chamber................................................................................................................................................................. 47
Refractory cracks where bricks have split in two or more pieces...........................................................47
Bad looking refractory surface?.....................................................................................................................47
Slag is building up on the refectory surface................................................................................................47
Parts of bricks have fallen out........................................................................................................................48
Instructions for use of repair substance for refractory.............................................................................. 48
Combustion chamber refractory exchange................................................................................................. 48
In doubt?............................................................................................................................................................ 49
Restriction bricks replacement...................................................................................................................... 49
Door gasket replacement................................................................................................................................50
Safety door interlock switch replacement....................................................................................................51
Greasing of door hinges..................................................................................................................................51
Greasing of sluice bearings............................................................................................................................51
Burner maintenance and repair..........................................................................................................................52
General information......................................................................................................................................... 52
Burner diesel nozzle assembly and repair.................................................................................................. 53
Reassembly of burner nozzle assembly......................................................................................................55
Burner Blast tube Replacement.................................................................................................................... 58
Ignition cables replacement........................................................................................................................... 60
Reassembly of ignition cables....................................................................................................................... 61
Photo Resistor replacement...........................................................................................................................62
Ignition transformer replacement.................................................................................................................. 63
Oil burner damper motor replacement......................................................................................................... 64
Diesel oil pump maintenance and repair..................................................................................................... 68
Diesel oil pressure adjustment...................................................................................................................... 71
Burner pump shaft seal replacement........................................................................................................... 75
Burner diesel pressure regulation kit replacement.................................................................................... 77
Spline coupling replacement..........................................................................................................................80
Sludge dosage pump maintenance and repair............................................................................................... 82
Sludge dosage pump maintenance and repair procedures....................................................................86
Sludge valve...........................................................................................................................................................93
Control cabinet.......................................................................................................................................................94
PLC repair or replacement............................................................................................................................. 94
6
LIST OF CONTENTS
7
8
OPERATOR MANUAL
9
INTRODUCTION
Introduction
Instruction manual, purpose and scope
The manual will guide the reader/user gradually to an understanding required for safe operation
(Part I) and maintenance (Part II) of the incinerator system.
It is important for the user to have a good understanding of the incinerator function, to avoid
malfunction caused by operational errors. The user/operator should therefore always familiarize
themselves with both parts of the manual, before starting to use the equipment.
The guarantee will be invalid if problems and/or caused by operational errors or mistreatment.
Tel.: +(47) 37 19 98 00
Email: [email protected]
[email protected]
General office email: [email protected]
China
Manufacturer: CSSC NanJing Luzhou Environment Protect Co.,Ltd
Address: LISHUI STREET,BINJIANG ECONOMIC DEVELOPMENT ZONE,JIANGNING
DISTRICT,NANJING
Postal Code: 211162
Tel: +86-(0)25-86723713
Fax: +86-(0)25-86723747
E-Mail: [email protected]
Please note that our main strategy is to offer our customers the best service and quality
spare parts wherever and whenever they need them. To reach this goal we have
established a stock of spare parts and trained service personnel in major ports
throughout the world.
10
GENERAL SAFETY INSTRUCTION
Safety markings
The contents of this manual use marking based on ISO 3864-1, with the following differentiation:
• Never turn off the main power before the chamber temperature is down below 170°C.
• Never load glass, lithium batteries or spray cans in the incinerator – nor
large quantities of oily rags or filter cartridges. This may damage the flue gas stack and
refractory.
• Inspect the cooling jacket every 6 months (open the cover plates) and clean as required
with steam or hot water.
• When doing maintenance on any of the incinerator components always make sure that
the power is switched off.
11
ACRONYMS AND TERMS
12
TECHNICAL DESCRIPTION AND MAIN DATA
• Combustion chamber with diesel oil burner, sludge burner, pilot fuel heater and electric
control panel.
• Flue gas damper.
• Sludge service tank with circulating pump and heater.
• Sludge settling tank with filling pump and heater. (Optional)
Combustion chamber
The combustion chamber consists of a cylindrical chamber. The trash is ignited by burner in the
chamber. The combustion chamber is equipped with an inspection/ash door, which can be
opened only while the incinerator is not burning. The control system will prevent the door from
being opened before the set temperature for cooling is reached.
The flue gas outlet is located at the top of the chamber. The flames from the burners follow a
corkscrew pattern towards the bottom and continue rotation upwards in the center of the
combustion chamber. Remnants of particulate matters in the gas flow are neutralized by the
burner, making the combustion ecologically safe. As the fumes exits the chamber, cooling air
drawn from the lower part of the casing is mixed with the flue gas to bring the temperature down
to approx. 330°C before it pulled out by the flue gas fan and blown out the stack to atmosphere.
The burning process is monitored by the PLC and scanned by a photo resistor in the burner.
The temperatures are also monitored/regulated automatically by the PLC control system.
Two sight glasses are equipped, for the operator to be able to inspect the amount of trash in the
chamber and the function of the system.
The combustion chamber is of steel construction, lined with specially designed refractory blocks.
Between the steel and refraction there is a 50mm layer of insulation. The refractory material is
made of a low cement/high alumina quality being slag resistant and having very good thermal
shock resistance. A double steel casing with a cooling air jacket forms the outside of the
combustion chamber.
The combustion chamber is equipped with a, three-stage diesel oil burner and a steam/air
atomizing nozzle for sludge burning. Under the burner assembly, a bracket/drip tray for sludge
burning equipment is mounted.
The diesel oil burner has 3 stages, automatically controlled by the PLC. In addition, there are
four stages for sludge burning, using steam or compressed air for atomizing. The sludge burner
allows particles up to 4 mm to pass through. The D.O. burner is monitored by the PLC and has
a built-in primary air fan and diesel oil pump.
The main electrical control panel is normally fitted on the incinerator and it contains circuit
breakers, starters, frequency inverters, PLC and operator panel. The electric panels are built
according to international standards for marine equipment. The operator panel, which is located
at the side of the control panel, has a LCD display touch screen for selecting burner program
modes and for monitoring the burning process.
13
TECHNICAL DESCRIPTIAND MAIN DATA
53 l/h IMO sludge oil (without water IMO sludge (20% water)
injection)
Corresponding to:
Solid waste max. 400 litre per charge or
IMO class 02 waste
55 l/charge continuous feeding
Max. 1200 °C
Combustion chamber
temperature: Working. 870-1150 °C
Flue gas temperature: Max. 350°C
Working. 250 - 340 °C
Surface temperature:
15°C above ambient temperature.
1
USCG Capacity
2
USCG Capacity
14
TECHNICAL DESCRIPTION AND MAIN DATA
Connections: 1/4"
Weight: 12 kg.
Enclosure rating IP 55
15
TECHNICAL DESCRIPTION AND MAIN DATA
• Display running condition, temperature, pressure, alarm, oil consumption, timer etc.
16
TECHNICAL DESCRIPTION AND MAIN DATA
USB
The operator panel is an Ethernet only display with 2 USB port, and consist of a color (640X480)
graphics display. Color terminals support a fixed palette of 256 standard VGA colors. All colors
in an application is defined when the application is created, and not selectable at the terminal.
The SD flash slot is used to program the display. Normally, this will be done by Teamtec
personnel.
The operator panel is connected to the PLC with Ethernet communication.
The terminal requires 24VDC.
Display temperature should be less than 55°C. The CPU temperature should be less than 95°C.
The terminal has one LED indicator that shows listed operations:
Color Indication Description
Green On Offline
In Operation
17
TECHNICAL DESCRIPTION AND MAIN DATA
Size:
DN400/DN300
Actuator motor: Drive force 20Nm. Travel
time for 90° is 150/125sec
50/60Hz.
18
TECHNICAL DESCRIPTION AND MAIN DATA
19
TECHNICAL DESCRIPTION AND MAIN DATA
A water content higher than 50% requires a pilot burner (support burner). This reduces the
available capacity for burning of sludge, thus the sudden drop in the below curve.
20
TECHNICAL DESCRIPTION AND MAIN DATA
Flange rating: PN 16
21
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
• “Sludge”
• “Solid Waste”
• “Slagging”
The different programs will be explained in detail in later chapters, as well as a number of
different menus and available information, including user guidance.
22
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
10
(The appearance of the screen may differ, depending on model and configuration.)
23
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
Main
Start/stop
Water tank
pumps and
heating
Select/start
programs
Setup Burner
Sludge I/O
Solid waste
Information
The control system Pop-up SW Sludge
will activate these
screens. Service Sludge and
Pop-up Water
Load/slag &
stop
Display
backlight
Date time
Prog. info
Water tank
Hour
General: From all screens it is possible to stop the incinerator by pressing “Stop” It is also
possible to access “Main”, Setup” and “Alarm from all screens.
24
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
Pop-up menu to select
program
This appears after pressing Start in the
Main menu. Select program to start. The
pop-up will close after selection of
program. Select “Cancel” to close pop-
up if you do not want to start or change
program.
Description of the program selection
alternatives are given in chapter
program description.
Information pop-up
An information pop-up gives information to
the user about irregularities between user
actions and incinerator status. Read the
message and press “Ack”.
The following messages may appear as
information messages:
25
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
transfer pump high level in sludge settling tank
• Not possible to start sludge filling pump high level in sludge service tank
• Not possible to start sludge filling pump when sludge program is running
• Not possible to start sludge circulation pump low level in sludge service tank
• Not possible to start sludge program - low level sludge service tank
• Not possible to start solid waste - sludge program - low level sludge service tank
• Not possible to start program - Door not closed - please close door
• Heating of refractory is finished. Let the incinerator cool down for 10 Hours
Burner screen
Appears when touching the burner.
The menu displays actual values and
status on motors, actuators and sensors
No adjustments or settings on this
screen – view only.
Settings tanks
Displays tanks physical attributes and
sludge mass for correct sludge
consumption.
26
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
Hour counters
Displays last run and total hours. Press
“Next” button to access screen “Hour
counters 2”
Setup menu
Some functions require the operator to
login to access a screen or to alter a
value in the setup. This normally
indicates that the operator needs
training to be aware of the
consequences of his actions.
Select the setup screen you want to
access. If not logged in as user “usr”,
values on the different setup screens are
“view only”.
For further information on login and
settings, refer to Appendix B on “User
login and changing of settings in
operator display”.
27
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
Backlight menu
No user name and password required.
Program information
Values are view only. If assistance from
Teamtec is required, you might be
asked for the type and version listed on
the screen.
28
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
Consumption
Displays consumption for last run and
total. Press “Setup consumption” to
access setup screen.
Consumption setup
If not logged in as user “usr”, values on
different setup screens are “view only”.
29
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
Alarm system
If the control system encounters any irregularities, the system will give an alarm and shut down
the incinerator. When an alarm occurs, the internal audible alarm activates, and the alarm signal
is given to ships alarm system. The "ALARM" screen will pop-up at the operator panel display
and the most recent alarm(s) will be displayed at the top of the list. The “ALARM” screen will
display active alarms as well as the alarm history. A total of 128 alarms (active and history) can
be displayed. When additional alarms occur, the oldest alarms will be deleted from the alarm
history list.
30
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
Waste incineration on board sea going ships and offshore platforms is worldwide regulated by
IMO MARPOL 73/78, RESOLUTION MEPC 244(66) adopted April 4th, 2014 (Replacing
MEPC.76(40)), STANDARD SPECIFICATION FOR SHIPBOARD INCINERATORS, adopted on
25. September 1997, and IMO MARPOL ANNEX VI REGULATION 16 and APPENDIX IV
adopted on 26. September 1997.
MERCURY
LEAD
NICKEL
VANADIUM
ZINC
IMO Annex VI regulation 16 prohibits incineration on ship of certain products, such as
contaminated packaging materials and polychlorinated biphenyls (PCBs).
31
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
General use- and safety instructions
• Never turn off the main power before the chamber temperature is down below 170°C.
• Read the operator- and maintenance manual, and never change any settings. Know the
regular maintenance tasks in the maintenance manual under part II as a minimum. It is
recommended to know it completely.
• Main switch on the control panel is switched to position "ON". The operator panel is
energized, and the Process picture will show in the display.
Emergency stops
In the incinerator room.
Turn the main switch at the control panel "OFF".
Safety warning: If smoke exits the incinerator to the incinerator room, evacuate the room
immediately. Risk of loss of health and life.
32
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
The sludge burning program
Description
The incinerator is designed and approved to burn sludge according to IMO specifications.
The incinerator starts heating up using the diesel oil burner. The diesel oil burner goes through
different steps. See maintenance description of burner for details.
When the combustion chamber temperature (CCT) has reached set point “min CCT for run
Sludge” (680°C), the steam line will flush for 10 seconds to drain out condensate water before
starting up the sludge burner. The frequency-controlled sludge dosage pump (SDP) starts. As
the temperature increases and temperature set-points are reached, the diesel oil burner will
adjust to other burner steps to save diesel and increasing sludge oil. At 870 degrees the sludge
program requires burner step 7 from the burner program, and diesel oil will be cut off completely
to run sludge only.
Sludge dosage pump (SDP) will increase sludge dozing until combustion chamber temperature
(CCT) has reached set point” Max CCT run Sludge” (1150°C) or flue gas temperature (FGT)
raises above “Max FGT – start adjust SDP RPM (340°C). The control system will then adjust
sludge dosage pump (SDP) to keep combustion temperature (CCT) steady.
The low sludge tank level will activate the low-level switch and result in a normal stop of the
program. When sludge burner stops, the sludge solenoid valve closes the sludge while the
steam/air solenoid flushes the sludge nozzle until the temperature in the combustion chamber is
lower than 300°C in order to avoid building up of coal on the burner tip.
• Know the regular maintenance tasks in the maintenance manual under part II as a
minimum. It is recommended to know it completely.
• As a minimum, heat the sludge overnight, without starting the circulating pump. Next
morning, drain off the free water and start the sludge programs.
• If experiencing any problem with high temperature in combustion chamber, flue gas or
control of sludge dosing, replace the dosing pump stator.
• Inspect the cooling jacket every 6 months (open the cover plates) and clean as required
with steam or hot water. Any sign of oily sludge here, is a notification of lack of
maintenance, and represents a fire hazard.
• Never transfer sludge to the service tank during sludge burning (can damage the
refractory).
33
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
Operator procedure
1. Fill up the sludge tank and activate the heater. This is done by the pressing the heater
symbol on the operator panel. Choose start heater and the heater symbol will change
color to indicate that the heater is on and the temperature is controlled locally by the
thermostat
2. Start the filling pump by pressing the pump symbol and choose start pump. The symbol
will change color to green to indicate that the pump is running. The pump will stop
automatically if the service tank level is high or the settling tank level is low.
3. Activate the heater on the service tank. This is done by pressing the heater symbol on
the operator panel. Choose start heater and the heater symbol will change color to
indicate that the heater is on and the temperature is controlled locally by the thermostat
4. Drain off water from the service tank. (The sludge should be settled overnight before
water is drained off). Remember, longer settling time = better settling!
5. Start the service tank circulation pump by pressing the pump symbol and choose start
pump. The symbol will change color to green to indicate that the pump is running.
Check the sludge pressure on the pressure indicator to be in the range of 0.2 bar,
adjust if required, using the bypass valve. Run the circulation pump for at least 1 hour
prior to burning sludge!
6. Check the atomizing -air supply pressure to be 6 - 8 bar. (The manual regulating valve
for air atomizing located at sludge equipment drip tray should be from ¾ to 1 turn open.
The pressure should be shown in the upper half of the green area (3.3 bar or 48 PSI)
when the sludge burner/nozzle is clean. If pressure rises, do NOT adjust the valve, but
clean the sludge burner before starting the incinerator!)
7. Push the key "START" and choose "SLUDGE" from the menu. The flue gas fan will
start and automatically control the pressure in the chamber. If there are conditions not
met required for starting the incinerator, the operator panel will display a message
explaining the condition.
8. When the low level in sludge tank, or the key "STOP" is pushed, the burner will stop,
and the cooling down sequence starts.
When the temperature in the combustion chamber has decreased to 170°C, the flue gas fan will
stop, and door locks will be energized.
34
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
The solid waste burning program
Description
The program is based on a regular daily routine, where a batch of solid waste is loaded directly
into the chamber before start of the program. From here, waste is loaded through the sluice.
The incinerator PLC will detect how much heat is released from the waste itself, and adjust
accordingly:
1 – Flue gas damper opening (FGD).
2 – Diesel oil burner steps
The program will urge to save diesel, when possible.
Batch loading
Each morning, providing that the combustion chamber temperature is lower than 170°C, slag
and ashes should be removed.
Partly burnt garbage shall remain in the chamber. This garbage will be fully incinerated at the
next sequence of incineration.
The air inlet openings in the bottom of the combustion chamber must be open. Clean, if
necessary.
Load the combustion chamber to maximum 2/3 height with garbage of mixed waste. This is
approximately 500 liters.
If high calorific garbage is loaded, a smaller quantity must be loaded per charge. Make sure to
mix higher calorific waste, like plastics and cardboard, with food waste. This will make
incineration more efficient.
Sluice feeding
If a sluice is installed, solid waste can be fed into the 55-liter sluice at temperatures between
850°C and 1050°C. Fill the trash in a garbage paper bag, open the sluice lid/sluice door and put
the bag into the sluice. Do not jam the trash bag into the sluice or overfill it. Close the lid / sluice
door and rotate the sluice by the handle on the sluice. The recommended waiting time between
each time the sluice can be operated is 210 seconds. After the waiting time has elapsed, the
sluice is ready for a new load.
Never load glass, lithium batteries or spray cans in the incinerator, nor large
quantities of oily rags or filter cartridges. This may damage the flue gas stack and refractory.
Do not incinerate metals as soda and food can plates, flatware, serving
spoons/tray, hardware (nuts & bolts), structural pieces, wire rope, chains etc, glass such
as bottles, jars, drinking glasses etc., flammable materials such as bottles or cans
containing flammable liquids or gasses and aerosol cans. Do not incinerate heavy load
with plastics or bulk food waste.
35
CONTROL PROGRAM DESCRIPTION AND
OPERATOR INSTRUCTIONS
Be aware that plastics has high calorific value, about 36 000 kJ/kg and must
only be incinerated in small amounts at the same time.
Class 2 refuse consists of approximately even mixture of rubbish and garbage by weight. This
type of waste is common to passenger ships occupancy, consisting of up to 50% moisture, 7%
incombustible solids and has a heating value of about 10 000 kJ/kg as fired.
Know the regular maintenance tasks in the maintenance manual under part II as a minimum. It
is recommended to know it completely.
Operator procedure
1. Fill the combustion chamber 2/3 full of waste (approx. 500 L).
NOTE: The Solid waste program start up sequence assumes a batch load. If the
incinerator is to be heated up without a batch load, choose the sludge program.
2. Close the door.
3. Push the key "START" and choose "SOLID WASTE" from the menu. The flue gas fan
will start and automatically control the pressure in the chamber. If there are conditions
not met required for starting the incinerator, the operator panel will display a message
explaining the condition. If an exact burning time is wanted, it can be activated from the
“Settings Solid Waste” menu. After the time has elapsed the incinerator stops, and the
cooling down sequence starts.
4. When the key "STOP" is pushed, the burner will stop, and the cooling down sequence
starts.
5. When the temperature in the combustion chamber has decreased to 170°C, the flue
gas fan will stop, and door locks energized.
36
CONTROL PROGRAM DESCRIPTION AND
PERATOR INSTRUCTIONS
The combined solid waste and sludge burning program
Description
The Solid waste and sludge program heat up the combustion chamber according to the solid
waste program, and switches to burn sludge from the service tank when ready. However, the
maximum combustion chamber temperature kept lower than approximately 950°C to enable the
operator to feed solid waste continuously.
Operator procedure
1. Perform settling and sludge preparation in the service tank according to the routine
described in the sludge program.
2. Follow the Solid waste procedure but choose “Solid Waste Sludge” program instead of
“Solid Waste” program.
Operator procedure
1. Check that there are no flames in the incinerator.
2. Push the "SLAG" key, the flue gas fan will run at a fixed speed (even when the
temperature is below 170°C).
3. Open the ash door and remove ashes and slag/Inspect the chamber from the inside.
Partly burned cans, can remain in the chamber. These will disappear eventually.
NOTE! Combustion air inlet openings at "floor" level must be opened, if
blocked.
37
38
MAINTENANCE MANUAL
39
MAINTENANCE MANUAL
Maintenance instructions
Preventive maintenance system
Preventive maintenance periods are
programmed in the control system based on
running hours of the diesel oil burner, apart
from the regular checks found below. The
preventive maintenance tasks groups are:
If not logged in as user “usr” (Ref appendix), values on different setup screens are “view only”.
Also, the “Done” buttons are only visible if user “usr” has logged in.
Following the preventive maintenance
tasks will as a minimum consume
parts according to below list of “One-
year wear and tear parts”.
Make sure the incinerator has finished the cooling down procedure before the main
power is turned off.
40
MAINTENANCE MANUAL
41
MAINTENANCE MANUAL
42
MAINTENANCE MANUAL
43
MAINTENANCE MANUAL
44
MAINTENANCE MANUAL
Remember: Following the preventive maintenance tasks will as a minimum consume parts
according to below list of “One-year wear and tear parts”.
Typical repair and maintenance tasks and procedures are described in detail elsewhere in the
manual.
It is advised to keep the following kit of parts on board to be prepared for unwanted downtime.
45
MAINTENANCE MANUAL
46
MAINTENANCE MANUAL
For most maintenance and repair tasks, it is enough with the following tools:
For detailed instructions of all maintenance tasks, please see the “Teamtec incinerator
service video” supplied by Teamtec
Incinerator
Chamber
Parts of refractory can chip off, for example if air at room temperature is leaking in to the
chamber from the door gasket or if sludge containing water is transferred to the sludge service
tank during sludge burning. In the latter case, water in the sludge will then become steam at
100°C. Both room air and steam are very chilly for 1100°C refractory, cooling the refractory
surface very rapidly, but not the core. The huge temperature difference between surface and
core of refractory will then create a lot of tension forces, for which concrete has little strength to
withstand, and the result in these scenarios is chipping.
Refractory is very slowly wearing down from day one of operation (faster if handbook
procedures and instructions are not followed to the point), but the look of the surface can be
disregarded. The important parameter is if 30% of the thickness or more of the brick dimension
is lost, repair material should be added in order to rebuild the brick to original dimension.
The first is a glass-like, hard slag, looking like the surface of the moon. This type of slag is
normally building up in a thin layer and should not be removed.
47
MAINTENANCE MANUAL
The second type of slag is the soft ash type of slag that builds up in a heavy layer and should
be gently removed during the daily ash removal routine.
The main power switch must be turned off before starting this maintenance task. Check that the
incinerator combustion chamber is cold.
1. The surface should be clean(ed) and all loose material should be removed to secure a
firm binding between the repair substance and the bricks.
2. The bricks should be padded individually, meaning no substance should cement two
bricks together.
3. Do not fill the gaps between the bricks with Calde Patch. The bricks need the space for
heat expansion. Preferably, use cardboard between the bricks when padding the brick
edges.
4. If there is some OLD repair substance left on the area that is to be fixed, it is important
to add some water to this part of the area and make it wet BEFORE new repair
substance is added to the spot.
5. The substance consists of proximately 20% water to obtain a plastic substance that can
easily be worked with. The material is VERY sensitive to additional water content.
(Additional water should not be added without consulting to TeamTec AS first).
6. The substance shall be added to the bricks by means of a stopping knife until the right
thickness has been reached. The thickness should be at least 10mm, but not so much it
causes sagging. The material will have to dry for some hours before the next layer, if
necessary.
We advise to dry the material over night by means of an electrical heater (max 50 degrees)
before the incinerator is started up again. I your incinerator have a burn in program; please use
this for 5 to 6 hours the day after padding, before reverting to normal incineration.
48
MAINTENANCE MANUAL
Contact [email protected] for a new refractory kit. A certified Teamtec service engineer will
be required for the replacement. The after sales department will assist in providing global
support.
In doubt?
Feel free to ask Teamtec main office to give an opinion. Good quality digital photos, taken from
different distances and angels are required ( [email protected] or [email protected] or
[email protected] or [email protected]).
The main power switch must be turned off before starting this maintenance task. Check that the
incinerator combustion chamber is cold.
1. There are 4 bricks located at the outlet of the combustion chamber. The 4 bricks are
forming a circle and are self-locking.
2. Push one brick up and then the three others are loose.
49
MAINTENANCE MANUAL
4. Insert the new gasket. Start and end in the middle in the lower part of the door and cut
the gasket to exact length.
5. Give the gasket a series of gentle and even punches all the way around the door
perimeter to settle it in the sealing compound, for example using the handle of a mallet.
6. Remove any excess sealing compound, close the door, and leave it closed until the
compound has settled.
50
MAINTENANCE MANUAL
Tools needed:
- Flathead screw driver.
- Torx screw driver set
- Allen key set
Disassembly
Repair
It is not possible to repair a damaged safety interlock switch to reliable state.
Replacement
1. Install the new switch on the chamber.
2. Thread and re-attach the wires according to reference pictures.
3. Replace the lid.
Use ordinary ball bearing grease. Consult service video for execution.
51
MAINTENANCE MANUAL
0 X X X
1 1 X X X
2 2 X X X
3 1+2 X X X
4 1 Yes X X N/A
5 2 Yes X X N/A
6 1+2 Yes X X N/A
7 Yes X X N/A
The complete (red) burner housing should never be dismantled from the incinerator for
any maintenance or replacement!
52
MAINTENANCE MANUAL
(Demo pictures only. The (red) burner housing should never be dismantled from the incinerator
for any maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
53
MAINTENANCE MANUAL
4. Loosen the two screws marked at the picture to dismantle the electrodes and the flame
scrod and then unscrew the D.O. nozzles!
7842
12329
5. Clean or replace as parts as needed. This can be cleaned with Kerosene, White Spirit or
Marine Diesel Oil and a brush. The electrodes should be wiped off with a cloth dipped in
one of the above mentioned agents.
54
MAINTENANCE MANUAL
DO nozzles data
Incinerator Nozzle 1 Nozzle 2 Std. pressure DO temp.
OG120C 2.5 GPH 60° - 16 bar 50°C
OG 200C 2.5 GPH 60° 4.5 GPH 45° 16 bar 50°C
OG 400C 2.5 GPH 60° 4.5 GPH 45° 16 bar 50°C
GS 500C 3.5 GPH 60° 5.5 GPH 45° 16 bar 50°C
GS900CX 4.5 GPH 45° 6.5 GPH 45° 16 bar 50 °C
GS1000CX 4.5 GPH 45° 6.5 GPH 45° 16 bar 50 °C
For special cases other nozzles may be used.
Maintenance
Burner nozzle cannot be repaired.
55
MAINTENANCE MANUAL
56
MAINTENANCE MANUAL
1. Loosen nut (A) and pull out the external pipe (B)
2. Clean the external (B) and internal (C) pipes
3. Re‐assemble the sludge burner in reverse order
57
MAINTENANCE MANUAL
(Demo pictures only. The complete burner should never be dismantled from the incinerator for
any maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
- Hammer and chisel
58
MAINTENANCE MANUAL
3. Unscrew the two screws shown at the picture. Use a hammer and chisel gently to
loosen the blast tube if stuck. Do not hit the red casting, as this is made of brittle
material.
4. The blast tube is now loose and can be pushed into the combustion chamber.
Note: Due to soot deposits, the blast tube might be stuck. Use a hammer and chisel
carefully to get loosen the blast tube.
Note: The blast tube should be adjusted for the two screws mentioned in point 3 to be in
the middle of the sliding track.
59
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
60
MAINTENANCE MANUAL
61
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Screwdriver set
- Allen key set, metric
62
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Allen key set, metric
1. Mount the ignition transformer on the burner by fastening the two screws.
2. Reattach the two cables into the ignition transformer.
3. Put the inspection cover back on and tighten the screws to keep it in place.
4. Turn main power back on.
63
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or
replacement.)
Tools needed:
- Screwdriver set
- Allen key set, metric
64
MAINTENANCE MANUAL
PS! Make sure that the shaft is in approx. mid position when assembling, and that the damper
flap is in closed position.
65
MAINTENANCE MANUAL
Air adjustment
The Burner damper motor is analogue and will open the damper proportionally to the control
voltage applied by the control system. The only two checks necessary is Closed position and
that it operates freely.
To check that the damper is closed make sure that the damper blade is vertical to the opening
when the control system shows 0% opening (after power up, flue gas fan not running).
To check that the damper operates freely, wind up the actuator by using a 4mm hex key on the
top of the damper motor, then release and observe that the damper closed by the spring action.
66
MAINTENANCE MANUAL
Capacities
Oil burner nozzle capacities in l/h at various pressures.3
Rated flow 4 Pressure in bar
G.P.H. l/h 10 11 12 13 14 15 16
1,50 5,68 6,82 7,12 7,41 7,71 8,00 8,24 8,47
1,65 6,25 7,41 7,82 8,24 8,53 8,82 9,29 9,76
1,75 6,62 7,88 8,29 8,71 9,06 9,41 9,71 10,00
2,00 7,57 9,06 9,47 9,88 10,29 10,71 11,06 11,41
2,25 8,52 10,24 10,71 11,18 11,59 12,00 12,41 12,82
2,50 9,46 11,29 11,82 12,35 12,88 13,41 13,88 14,35
3,00 11,36 13,53 14,18 14,82 15,47 16,12 16,65 17,18
3,50 13,25 15,88 16,65 17,41 18,06 18,71 19,35 20,00
4,00 15,14 18,12 19,00 19,88 20,65 21,41 22,18 22,94
4,50 17,03 20,35 21,35 22,35 23,24 24,12 24,94 25,76
5,00 18,93 22,59 23,71 24,82 25,82 26,82 27,71 28,59
5,50 20,82 24,82 26,06 27,29 28,35 29,41 30,47 31,53
6,00 22,71 27,18 28,47 29,76 30,94 32,12 33,24 34,35
6,50 24,61 29,41 30,59 31,76 33,53 35,29 36,47 37,65
7,00 26,50 31,76 33,53 35,29 36,47 37,65 38,82 40,00
7,50 28,39 34,12 35,88 37,65 38,82 40,00 41,76 43,53
8,00 30,28 36,47 38,24 40,00 41,18 42,35 44,12 45,88
3
Sp gr 0,85 @ 25°C and viscosity 1,3°E @ 20°C
4
Pressure = 100 P.S.I.
67
MAINTENANCE MANUAL
68
MAINTENANCE MANUAL
Hydraulic data
Nozzle pressure range. 10 to 21 bar.
Delivery pressure setting. 16 bar
Viscosity range. 2.8 to 200 cSt
Inlet and return pressure. 1.5 bar max.
Suction height. 0.45 bar max. vacuum to prevent air separation
from oil.
Rated speed. 3600 rpm max.
Oil temperature. Max. 90°C in the pump.
Starting torque. 0.4 Nm
Bar Bar
69
MAINTENANCE MANUAL
Pipe dimensions
The tables below give the maximum length (in meters) of suction line as function of 3 variables:
Q (l/h) 150
d (mm)
H (m) 10 12 14 16
0 11 24 46 80
0.5 12 27 51 90
1 14 30 57 99
2 17 36 68 118
3 20 42 79 136
4 22 48 90 155
Q (l/h) 150
d (mm)
H (m) 10 12 14 16
0 11 24 46 80
0.5 9 21 41 71
1 8 18 35 61
2 5 12 24 42
3 2 6 13 24
4 0 0 2 5
70
MAINTENANCE MANUAL
Installation
The pump is ready for use with 2 pipe systems (i.e. with by-pass plug fitted, in the return port.)
The inlet and return pressures must not exceed 1.5 bar.
The vacuum must not be more than 0.45 bar to prevent air separation from oil.
It is recommended to use a separate filter upstream of the pump.
The pump is to be used with cylindrical fitting or conical fittings as appropriate and sealing
washers. Other sealants are not recommended.
Start up
Check that the sense of rotation for pump and motor are the same (an arrow is stamped on the
pump body).
In order to purge pumps used on 1 pipe systems, loosen one of the high-pressure connections.
On 2 pipe systems, purging is automatic.
Pressure regulation
Remove end cap nut from pump for access to pressure stetting screw. Turning the regulator
screw clockwise increases the pressure.
Systematic maintenance
1. Check the stop valve and in line filters.
1. Check the pump filter.
This filter should be cleaned with a soft brush and fuel oil.
Each time, the cover gasket should be changed.
2. Check the tightness of all couplings and unused plugs.
3. Check the shaft coupling.
4. Check the pump pressure.
Fit a pressure gauge in the fitting provided and run the pump in normal manner.
If the pressure required cannot be obtained, check that the pump is completely purged.
If air bubbles are found in the fuel, check all connections for tightness.
5. Check the pump vacuum.
Fit a vacuum gauge in fitting provided and run the pump in the normal manner, making
sure to fully purge the pump.
The vacuum should not exceed 0.45 bar. If this is the case, check condition of all
components (non-return valve, stop valves, filters....).
If the pump does not suck correctly, check for any leaks in the line by retightening all
fittings.
71
MAINTENANCE MANUAL
Parts list
72
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
3. Measure the distance shown at the below picture before removing the spline coupling
from the old pump. Should be 10mm.
73
MAINTENANCE MANUAL
4. Untighten the set screw and move the spline coupling to the new pump. Distance
between spline coupling and pump as measured in point 3.
74
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
- Lug spanner
3. Measure the distance shown at the below picture to positioning the spline coupling
correctly when reassembling. Should be 10mm
75
MAINTENANCE MANUAL
5. Use a felt pen to mark position of the nut with a line from nut to housing. Unscrew the
nut with the lug spanner by turning it anticlockwise.
6. Pick out all the parts and replace it with the new ones. Picture below shows in which
order!
Reassembly
1. Put all the parts back in the pump in the order shown on the picture above
2. Put the lock nut back and tighten by turning it clockwise, tighten with 20Nm force
3. Mount the spline coupling on the pump, distance should be 10mm
4. Put the pump back on the burner, and tighten the 2 bolts to keep it in place
5. Reconnect the 3 D.O, pipes to the pump
6. Turn main power back on
76
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Screwdriver set
1. Disconnect the D.O. pipe from the pump. Unscrew the two large hexagon nuts.
2. Use a pipe or similar to knock out the cylindered part that remain inside the pump.
77
MAINTENANCE MANUAL
4. Add item 6 and 7 to item 5, as shown at the picture below, and slide the complete unit
back in position in the pump.
5. Enter the nut item 10 to the pump. Notice the direction of the spring washer item 8.
6. Enter the item 1, 2, 3 and 4 to the pump. Notice the direction of item 3.
78
MAINTENANCE MANUAL
7. When starting the incinerator again, the pressure must be regulated to 16 bar by
adjusting at the screw as shown at picture below.
79
MAINTENANCE MANUAL
(Demo pictures only. The burner should never be dismantled from the incinerator for any
maintenance or replacement.)
Tools needed:
- Wrench set, metric
- Allen key set, metric
80
MAINTENANCE MANUAL
4. Measure the distance shown at the below picture before removing the spline coupling.
Should be 10mm
1. Put the inner spline coupling back into the fan wheel and tighten the set screws.
2. Put the outer spline coupling on the pump and adjust the distance between them,
should be 10mm. tighten the set screw to keep it in place
3. Put the motor with the fan wheel back on the burner and tighten the 4 bolts.
4. Put the pump back on the burner, and tighten the 2 bolts to keep it in place
5. Reconnect the 3 D.O, pipes to the pump
6. Turn main power back on
81
MAINTENANCE MANUAL
Dimensions
82
MAINTENANCE MANUAL
83
MAINTENANCE MANUAL
84
MAINTENANCE MANUAL
General recommendations
Dry running
Never run the pump in a dry condition even for a few revolutions, the stator will be
damaged immediately. Continual dry running could produce some harmful or damaging
effects.
If, the pump has been left standing for an appreciable time, or has been dismantled and re-
assembled, it must be refilled with liquid and given a few turns before starting. The pump is
normally somewhat stiff to turn by hand owing to the dose rotor/stator fit. However, this stiffness
disappears when the pump is running normally against pressure.
Rotor and stator
The wear rate on these components is dependent on many factors, such as product abrasives,
speed, pressure etc.
When pump performance has reduced to an unacceptable level one or possibly both items will
need replacing.
85
MAINTENANCE MANUAL
This procedure covers replacement of bonded rubber stator, rotor for dosage pump, universal
joint, mechanical seal, seal plate gasket, stuffing box gasket
Tools needed:
- Wrench set, metric
- Allen key set, metric
- Flat screw driver
- Pin punch tool
1. Cover the area under the dosage pump with plastic and cover the plastic with rags to
collect oil.
2. Close sludge valves.
3. Unscrew the sludge supply line on the pressure side.
86
MAINTENANCE MANUAL
6. Unscrew and remove the sludge supply AND return pipes connected to the dosage
pump.
8. Loosen the two hex socket bolts to loosen the pump shaft from the motor shaft. There is
a third hex socket grub bolt between the two tightening bolts. This will loosen the clamp
from the shafts when tightened.
87
MAINTENANCE MANUAL
11. At this stage of changing the mechanical seal, it is recommended to change both the
universal joint, the rotor and all gaskets.
12. Remove the retaining pin on the stub shaft side with a pin punch tool and remove the
universal joint.
13. Split the mechanical seal housing by unscrewing the two hex nuts.
88
MAINTENANCE MANUAL
14. Unscrew the three hex socket set screws and dismantle the shaft parts.
15. Carefully remove the seal plate, and gently push out the mechanical seal.
89
MAINTENANCE MANUAL
16. Reassemble in reverse order with a bit of oil for lubrication. The shiny side of the white
mechanical seal shall face outwards.
17. Fix assembly with the three hex socket screws with 120 mm as shown in below
picture.
90
MAINTENANCE MANUAL
18. Reconnect the shaft to the universal joint with the retaining pin. Grease the universal
joint and reassemble the remaining parts in reverse order.
19. Reassemble the shaft assembly and the housing with a new seal plate
gasket.
pump.
91
MAINTENANCE MANUAL
21. Install the pump on the motor. Reattach all pipes and tighten all nuts before fixing the
stub shaft to the motor. Notice how the two axles are positioned.
Loosen the grub hex socket bolt once in correct position. Tighten the two fixing hex
socket bolts, and finally remember to slightly tighten the grub hex socket bolt to keep it
from vibrating loose.
23. To prime the pump before starting the incinerator, start the sludge circulation pump in
the incinerator control display. Failure to prime the pump will cause damage.
92
MAINTENANCE MANUAL
Sludge valve
Article 12560, 0-1 bar, 3/4": Two of these valves are in the drip tray in the sludge dosage
assembly. It ensures that sludge is not injected through the sludge burner, without
atomizing air or atomizing steam present.
Repair kit for sludge valve article no. 12806 consists of:
3 (306) 1 Seal
4 (309) 1 Bolt
5 (310) 1 O-ring
6 (311) 2 Ring
7 (312) 1 O-ring
8 (313) 1 O-ring
9 (316) 1 Deflector
11 (318) 1 Spring
93
MAINTENANCE MANUAL
Control cabinet
PLC repair or replacement
General information
The Standard PLC contain of 4 units. See below figures.
1 2 3 4
94
MAINTENANCE MANUAL
Base Unit
1. Status LEDs
2. Output removable screw terminal block
3. Clip-on lock for 35 mm (1.38in.)
4. Ethernet port
5. 220Vac 50/60 Hz Power supply
6. USB mini-B programming port
7. Serial line port 1
8. SD Card slot
9. 2 analogue inputs
10. Run/Stop switch
11. Input removable screw terminal block
12. I/O Expansion connector
13. Cartridge slot 1
14. Cartridge slot 2
95
MAINTENANCE MANUAL
Inserting SD card
When new program is received from Teamtec, this must be installed from the SD Card slot.
Follow the steps listed to reprogram the PLC.
3. Check the Status LED on the PLC, when the SD label is activated the SD card program is
being downloaded to the PLC.
4. When the LED switches off and the PLC Run indication is activated, remove the SD card
from the PLC.
96
MAINTENANCE MANUAL
Replacing the battery when the controller is powered down will lose all user
application memory. Always replace the battery when the controller is powered on!
Follow the procedure 1-3 below to connect the new battery to the PLC.
A
C
Dimension:
A – 90 mm (3.5 in.)
B – 29.4 mm (1.157 in.)
C – 27.4 mm (1.07 in.)
97
MAINTENANCE MANUAL
Troubleshooting
98
MAINTENANCE MANUAL
1. Use a flat head screw driver to pull out the locking device in the lower base of the module,
shown on the picture above.
2. Move wiring from old to new module, one wire at the time to identical location.
3. Insert new module on the rail.
99
MAINTENANCE MANUAL
Control
terminals
Power
terminals
Power Terminals
The power terminals must be connected before connecting the control terminals!
Maximum connection
AWG 10 / 5 mm2
capacity:
Tightening torque: 1.2 Nm
100
MAINTENANCE MANUAL
• The Assignment of the “Fast stop” or “Freewheel stop” functions will prevent the drive
from starting if the corresponding logic inputs are nor powered up. The ATV320 then
displays “nSt” in freewheel stop mode and “FSt” in stop mode. This is normal since
these functions are active at zero so that the drive will be stopped safely if there is a
wire break.
• Check that the run command input(s) have been actuated in accordance with the
chosen control mode (tCC parameter in the I-O menu).
• If an input is assigned to the limit switch function and this input is zero, the drive can
only be started up by sending a command for the opposite direction, see ATV 320
programming manual.
• If the reference channel or the control channel is assigned to Modbus or CANopen, the
drive displays nSt on power-up and remains at stop until the communication bus sends
a command.
• If the LED on the DC bus is lit and nothing appears on the display, check that there is
no short-circuit on the 10 V power supply.
• If the drive displays “rdY” and refuses to start, check that there is not short circuit on the
10 V power supply and check the wiring of inputs AI1 and AI2 and the connection to the
RJ45 connector.
101
MAINTENANCE MANUAL
102
MAINTENANCE MANUAL
Tools needed:
- adjustable spanner.
- flathead screw driver
Disassembly
Repair
It is not possible to repair a damaged thermocouple or temperature transmitter to reliable state.
Replacement
1. Adjust the length of the thermocouple going into the fan housing to match the removed
103
MAINTENANCE MANUAL
Disassembly
1. Switch off the power and make sure it cannot be switched on again while the unit is under
repair. If unit is switched on during repair, it may cause serious damage and injuries.
2. Unscrew the four bolts holding the protective cover over the V-belts and remove the cover.
3. Use the wide screw driver to force the outer belt out of the track while rotating the pulley.
4. Use the screw driver to move the inner belt to the outer track and beyond to remove it. ONE
track at each pulley at the time!
Repair
It is not advisable to repair V-belts.
Replacement
Install new belts in reverse order of disassembly.
Reassembly
Check the tensioning of the belt’s mid-way between pulleys. It should be 10 mm deflection at 3
kg pressure. If the tensioning needs adjustment, follow the next items 2-5 before replacing the
cover.
1. Use a marker to draw a line where the upper edge of the motor base is located. This is used
as a reference.
2. Loosen the four bolts securing the motor.
3. Adjust the two positioning bolts counter clockwise to tighten the belts to above specification.
Make sure the motor base stays parallel to the marked line. Double check that the two
pulleys are parallel by using a ruler.
4. Once tension is acceptable, tighten the 4 bolts securing the motor.
5. Replace the cover and tighten the cover bolts.
6. Power to the unit can now be restored.
104
MAINTENANCE MANUAL
For mounting after re-greasing, the tightening torque for the cup bolts for the incinerator size
OG200C, housing type SNL 513 are torque 80Nm.
The bearings are mounted with an adaptor sleeve. The bearings have a small internal clearance
and an accurate mounting is very important. When the bearing is properly mounted, the outer
ring can be easily turned, but there should be a slight resistance when the ring is swiveled out.
When mounting a new bearing to the fan’s shaft, the following procedure should be followed:
Before mounting the threads of the nut and the side face of the nut which is about the bearing
should be greased and the outside diameter of the sleeve should be lightly oiled. The bearing is
then pushed on to the sleeve and the nut screwed on by hand.
Check that the bearing is correctly located on the shaft. Use a hook spanner and turn the nut an
angle of 90°. By turning the nut through this given angle of 90° the bearing will be pressed up
on the tapered seating of the sleeve. Re-position the hook spanner and apply a light hammer
blow to the spanner. The bearing will straighten up on its seating and is correctly fastened to the
shaft. Lock the nut but bending down one of the tabs on the locking washer. The residual
clearance of the bearing should be checked.
105
MAINTENANCE MANUAL
Disassembly
1. Switch off the power and make sure it cannot be switched on again while the unit is under
repair.
2. Disconnect the electrical cables to the motor.
3. Remove the 16 bolts pos. 30 on the cover (motor end of the fan housing).
4. Remove the 4 bolts for the bearing stand (fan base).
5. Slide the bearing stand assembly backwards from the fan housing till the impeller is clear of
the housing.
6. Carefully turn the bearing stand assembly to get access to the impeller.
7. The impeller is attached to the shaft with a taper lock hub. On the hub, unscrew the two
hexagon screws. By inserting one of the screws in the third hole (the one not in use), the
impeller will come off the hub when the screw is screwed in.
Repair
It is not advisable to repair an impeller unless one has access to balancing equipment.
106
MAINTENANCE MANUAL
Replacement
No special procedure is required except for cleaning the shaft and the hub before the hub is
placed on the shaft.
Reassembly
1. Remove the hexagon screws from the third hole. Insert the taper lock hub in the
impeller and put the two hexagon screws back to their original position and tighten.
2. Carefully slide the bearing stand assembly back into the fan house.
3. Put the 4 bolts for the bearing stand back and tighten
4. But back the 16 bolts for fastening the bearing base to the fan housing and tighten.
5. Reconnect all electrical cables to the motor
6. Main power can now be turned back on again
Performance verification
1. Run the fan in cold and hot condition and listen for noise.
2. Inspect that the fan is able to provide at least 100 mm WC negative pressure in the
combustion chamber. (Cold gas.)
107
MAINTENANCE MANUAL
(Demo pictures only. The motor can be replaced without dismantling the damper unit from the
stack)
Tools needed:
- Wrench set, metric
1. Disconnect the cables from the junction box (remember the color combination) and
loosen the lock bolt shown at the picture.
108
MAINTENANCE MANUAL
4. Unscrew one of the bolts for the bracket shown at the picture below to turn the bracket
and free the motor.
5. Picture below is showing all parts in the new damper motor kit. The marked parts will
not be needed, as they are excessive part! Use the previously dismantled original parts!
6. Enter the marked unit into the motor and lock it with shaft lock shown at point 2.
7. Make sure that the motor can turn 90° by pressing the button marked at the picture and
turn the shaft.
109
MAINTENANCE MANUAL
8. Assemble the motor to the damper. The damper flap position is marked with a cut in the
shaft end. Remember to tighten the bolt shown in point 1 and the bracket shown in
point 4.
Connect the wires. Test that the motor is turning correctly. Ex. If the motor turns the flap open
when it is supposed to close, you should change wires in junction box +6, terminal clamps X1-
1 and X1-3.
110
MAINTENANCE MANUAL
1.General information
Model 40WYXH-6-20 marine sludge oil circulation pump is a motor-driven horizontal sludge
Pumps of this series are suitable for delivering heavy oil and sludge oil with temperature up
to 90℃. This is a piece of equipment optimal for completion of incinerator in water treatment
plant.
1.1Type designation
40 WY XH ─ 6 ─ 20
Circulation pump
A. Pump of this series is composed of casing, impeller, locking bolts, sealing device,
B. Pump of this series is a horizontal pump with the motor at rear and pump in front
coupled together. The pump uses semi-open impeller which is directly connected to
C. Inlet and outlet of the pump shall be connected to external with standard four-step four-
hole flanges.
2.2 Features
Pumps of this series feature high discharge power, good sealing performance, thermal
a. Pump casing, rear pump casing and impeller are made of ductile cast iron.
111
MAINTENANCE MANUAL
Type
40WYXH-6-20
Item Unit
Flow m3/h 6
Weight kg
Outline(L×W×H) mm 454×225×240
5. Installation Instructions (See Fig. For dimension
The pump is a non-self-suction type and media is sludge oil with solid granulates or heavy oil.
Therefore, centerline of pump casing must be below medium level and suction and discharge
pipes must have size larger than inlet and outlet with minimal bends. Otherwise, pumping
Pump base plate shall be secured with bolts. There shall have four pump casing fixing bolts at
Prior to initial start, pump motor shall be checked for conformance of power supply to be
Open valves in suction and discharge pipelines and start the motor. At start up direction of
pump rotation shall be checked to see if it is in line with that indicated on pump casing, or it shall
be changed.
If there is any leakage with the pump, stop the pump immediately to make checks and close
valves so as not to burn the motor. When necessary, seal ring shall be replaced. Normal leakage
The pump shall not be run empty so as not burn seal ring.
When the pump is not to be operated for al long time, it shall be dismantled for cleaning.
Special attention shall be paid when disassembling that both faces of mechanical seal shall not be
damaged. A suitable amount of lubricant shall be applied at assembling for proper storage
7.1Disassembling
a. Removal the four securing nuts(15) and take off pump casing(1).
112
MAINTENANCE MANUAL
b. Undone lock nuts (2) and pull out impeller (4). Take out flat key (5).
c. Remove three fixing screws (14) for rear pump casing (14) and pull out rear casing (13) together
with mechanical seal ring(7). And remove the mechanical seal ring from rear pump casing for
replacement or repair.
d. Remove 3 screws (9) fixing the gland and take off the gland (10) and you will be able to fill
e. Remove the retainer from motor shaft (11) by means of circlip pliers. Remove 3 fixing screws on
motor enclosure and pull out the enclosure with bearing for replacement and cleaning.
7.2. Assembling
b. Both faces of the mechanical seal ring shall be cleaned up before being installed. Never strike
8. Spare Parts Delivered with the pump (see packing list for details)
4 Document
Inspection:____________ Packing:____________Date:____________
113
MAINTENANCE MANUAL
114
MAINTENANCE MANUAL
60Hz
50Hz
115
MAINTENANCE MANUAL
5. Temperature raising 1. Loaded too much waste Stop loading, and tray to block
"uncontrolled" with high calorific value. lower four corner ventilation
slots.
2. Damaged sludge dosing Change stator.
pump stator.
3. Sludge speed control not Check sludge speed.
working.
4. Leaking diesel oil Change the valve.
solenoid valve.
116
MAINTENANCE MANUAL
117
MAINTENANCE MANUAL
10. DRAUGHT FAILURE 1. Leaking sensor tube. Check sensor tube for
(low under pressure) damage and fixing.
12. LOW CAPACITY 1. Blocked air-cooling inlet. Clean inlet. (Bottom grating)
5. Damaged or blocked
sludge nozzle. Check the nozzle and if
necessary clean and adjust it.
118
APPENDIX A: STORAGE, PRESERVATION AND INSTALLATION
119
APPENDIX A: STORAGE, PRESERVATION AND INSTALLATION
Diesel oil.
Diesel oil supply line Equipped with a closing
valve. DN 15 flange, max
Connection: pressure 1.5 bar
Recommended filter, mesh
40µm
Max. suction lift 3500 mm
Diesel oil return line Connection. DN 15 flange, max
pressure 1.5 bar
120
APPENDIX A: STORAGE, PRESERVATION AND INSTALLATION
Detailed information regarding the system found on the Piping & Instrument Diagram as given in
the Drawings section. A detailed installation instruction is given in approval drawings, as well as
the drawing package towards the end of this manual.
121
APPENDIX A: STORAGE, PRESERVATION AND INSTALLATION
Pre-commissioning
Mechanical completion check list.
Prior to function testing at first start up, the following mechanical completion must be checked.
1. Check that the foundation support and the deck strength are adequate for the
incinerator unit. (5. ton)
2. Check that flue gas fan foundation is of a sturdy design for fan to run without vibration.
3. Check that the air inlet to the incinerator room has enough capacity.
4. Check that the necessary drainpipe is installed and connected.
5. Check that the incinerator door can be fully opened and locked in the installed locking
mechanism.
6. Check that the insulation, flue gas duct and flue gas fan is installed and fixed.
7. Check that the flue gas duct is not welded direct into painted wall penetration. (fire
hazard)
8. Check that the refractory brickwork has been dried out with a portable heater for 48
hours at approximately 100°C.
9. Check that the “Burn In” program has been run for 10 hours. The “Burn In” program
starts with a combustion chamber temperature at 200°C and runs for 10 hours. The
Burn In Program is available from the set up menu in the operator panel when logged in
as user.
10. Check the diesel oil line for correct hook up, and make sure that no valve is closed on
the return line. (A blocked return line will result in a leak in the diesel oil pump shaft seal)
11. Check the electrical power supply for correct rated protection at the ship distribution
board.
12. Check that all pipes, ducts and cables hooked up have been correctly completed
according to arrangement drawings.
After having checked out the above items, a function test according to this manual can take
place.
122
APPENDIX B: USER LOGIN
123
APPENDIX B: USER LOGIN
Change values
Plot the value that should be changed. A numeric pop-up will appear:
The present value is displayed on the line. Type in a new value
and press return to accept, or press “ESC” to cancel.
Settings burner
If not logged in as user “usr”, values on
different setup screens are “view only”.
Buttons “Prev.” and “Next” is used in a
circular shift function between several
setting screens.
Text Description
Burner damper Burner damper opening. Adjusts the amount of air supplied to the
burner step x combustion process by the burner motor fan.
Factor SDP burner Correction of burner damper opening in related to sludge dosage
damper reg. pump (SDP) speed. Used internally by the control system.
124
APPENDIX B: USER LOGIN
Settings alarms
If not logged in as user “usr”, values on
different setup screens are “view only”.
Text Description
Alarm max time The maximum time the diesel heater is activated the first time
diesel heater start after start incinerator. The diesel heater requires extra time at
start-up.
Alarm max time The maximum time the diesel heater is activated during
diesel heater run incinerating.
125
APPENDIX B: USER LOGIN
Text Description
Min. CCP run Minimum combustion chamber pressure (CCP). Used internally
sludge as a limit in the control system
Max. CCP run Maximum combustion chamber pressure (CCP). Used internally
sludge as a limit in the control system
Min. CCT for run Minimum combustion chamber temperature (CCT) before starting
sludge sludge.
126
APPENDIX B: USER LOGIN
Text Description
Time start sludge Time after start sludge dosage pump (SDP) before making
before adjust adjustments – to ensure a stable process before adjusting
sludge.
Time check CCT Time between reading combustion chamber temperature (CCT)
after adjust and adjusting the process
CCT stop burner Minimum combustion chamber temperature (CCT) before stop
diesel oil diesel oil and further increase sludge.
Hys restart burner Maximum drop combustion chamber temperature (CCT) before
diesel oil restart burner diesel oil and decrease sludge.
Hys max. CCT – Maximum drop combustion chamber temperature (CCT) before
stop dec sludge stop reducing sludge.
Set CCP running Set point for Combustion Chamber Pressure (CCP) is -15mmWC
Step 4 & 5 during burner stage 4 & 5 if the Combustion Chamber
Temperature is below 800°C
Set min CCP for Minimum set point for Combustion Chamber Pressure (CCP) as
temp.regulating long as the Combustion Chamber Temperature is above 800°C
127
APPENDIX B: USER LOGIN
Text Description
Max. FGT – start Maximum flue gas temperature (FGT) before decreasing
adjust CCP combustion chamber pressure (CCP)
Hys max. FGT – Maximum drop flue gas temperature (FGT) before stop
stop adjust CCP decreasing combustion chamber pressure (CCP)
Time check FGT Time between check flue gas temperature (FGT) before making
adjust CCP further increase in combustion chamber pressure (CCP)
FGT max. inc. CCP Maximum flue gas temperature (FGT), increase combustion
chamber pressure(CCP).
Max. FGT – start Maximum flue gas temperature (FGT) decrease sludge dosage
adjust SDP RPM pump (SDP) RPM.
Hys FGT – stop Minimum drop flue gas temperature (FGT) before stop
adjust SDP RPM decreasing sludge dosage pump (SDP) RPM.
CCP running Set point combustion chamber pressure (CCP) running burner
burner step 6 step 6
128
APPENDIX B: USER LOGIN
Text Description
SDP RPM increase Increasing SDP RPM every 30 second if combustion temperature
CCT increases or equal.
Min. RPM SDP Minimum RPM for sludge dosage pump (SDP).
Max. RPM SDP Maximum RPM for sludge dosage pump (SDP).
Manual set point Adjust sludge dosage pump manually.
SDP RPM
Purging start Time for purging sludge nozzle before opening sludge.
sludge
Alarm low level Activate if alarm is needed when sludge service tank low level
Sludge service tank switch is activated.
129
APPENDIX B: USER LOGIN
Text Description
Alarm set point Adjust set point for minimum steam/air pressure
minimum steam/air
pressure
Alarm set point Adjust set point for maximum steam/air pressure
maximum steam/air
pressure
Alarm set point Adjust set point for minimum sludge pressure
minimum sludge
pressure
Alarm set point Adjust set point for maximum sludge pressure
maximum sludge
pressure
130
APPENDIX B: USER LOGIN
Text Description
Set burning time On, makes it possible to program a fixed burning time
CCP start-up solid Minimum combustion chamber pressure (CCP) before start
waste program burner at start solid waste program
CCP max. solid Maximum combustion chamber pressure (CCP) when running
waste program solid waste
CCP min. solid Minimum combustion chamber pressure (CCP) when running
waste program solid waste
131
APPENDIX B: USER LOGIN
Text Description
Max. FGT start Maximum flue gas temperature (FGT) before start adjusting
adjustment CCP combustion chamber pressure (CCP).
Hysteresis FGT Minimum drop flus gas temperature (FGT) before stop adjusting
stop adjusting CCP combustion chamber pressure (CCP)
CCP inc when FGT Value for increasing combustion chamber pressure (CCP) when
above set point flue gas temperature (FGT) is above set point
CCP dec when Value for decrease combustion chamber pressure (CCP) when
FGT below set flue gas temperature (FGT) is below set point
point
Time check FGT Time between reading flue gas temperature (FGT) before
adjust CCP adjusting combustion chamber pressure (CCP).
Max. FGT start Maximum flue gas temperature (FGT) before start adjusting
adjust burner step burner step.
Hysteresis FGT Minimum drop flue gas temperature (FGT) before stop adjusting
stop adjust burner burner step.
step
Time check FGT Time between reading flue gas temperature (FGT) before making
adjust burner step adjustment to burner step.
132
APPENDIX B: USER LOGIN
Text Description
Settings loading/slagging
and stop
If not logged in as user “usr”, values on
different setup screens are “view only”.
Buttons “Prev.” and “Next” is used in a
circular shift function between several
setting screens.
Text Description
CCP running Set point for combustion chamber pressure (CCP) when running
cooling “Stop” program (cooling).
Auto start of FGF The flue gas fan atomically starts after the emergency stop is
after emergency released, if CCT above 220°C.
stop
133
APPENDIX B: USER LOGIN
Burn-in
If not logged in as user “usr”, values on
different setup screens are “view only”.
Burn-in program is used for burning in
refractory after long storage periods or
refractory replacement. It runs
automatically for 10 hours, increasing
CCT from 100°C to 600°C. A message
will appear when refractory is ready.
Text Description
Temperature set Set point for combustion chamber temperature CCT, running
point (view only) Burn-in program
Hys. chang. burner Hysteresis for temperature set point, when changing burner step.
step
Incinerator configuration
The button “Restore factory settings”
can be used to restore settings to
factory specifications.
If assistance from Teamtec is required,
you may be asked for the incinerator
configuration listed on the screen
134
APPENDIX B: USER LOGIN
135
APPENDIX B: USER LOGIN
5
Visible if heat tracing installed
6
Visible if heat tracing installed
136
APPENDIX B: USER LOGIN
Settings Tanks
Volume below low
Max tank level Tank Area Sludge density
level
435 L 500000 mm2 0,96 kg/L
703 L 217,9 L 750000 mm2 0,96 kg/L
1107 L 219,5 L 1020703 mm2 0,96 kg/L
1692 L 277,0 L 1517468 mm2 0,96 kg/L
2071 L 277,0 L 1517468 mm2 0,96 kg/L
2938 L 277,0 L 1517468 mm2 0,96 kg/L
3812 L 622,0 L 1985565 mm2 0,96 kg/L
4945 L 550,0 L 1985565 mm2 0,96 kg/L
137
APPENDIX B: USER LOGIN
138
APPENDIX C: ALARM LIST
Sludge pressure high 1.00 bar Sl. prog -U11 Sludge pressure high.
50°C Sl. prog. -F16 Sludge temperature low.
Sludge temperature low
Sludge service tank temp. 110°C Sl. Prog. +3A-S4 Safety thermostat released.
high8 (require manual reset)
7
See motor rating
8
sludge tank w/el. heater
139
APPENDIX C: ALARM LIST
140
APPENDIX D: TEST OF SAFETY AND ALARMS
2. FLUE GAS TEMP. HIGH At flue gas temperature above alarm set point,
Adjust alarm set point the alarm will activate, and the burner stops.
[Alarm max. FGT]
below operating temp. Flue gas temp. FGT high
5. MOTOR OVERLOAD The motor stops, the alarm will activate, and the
Activate test button, one by burner stops.
one, at front of the motor
circuit breaker.
Thermal failure - motor overload
141
APPENDIX D: TEST OF SAFETY AND ALARMS
8. DIESEL OIL TEMP HIGH At release of safety thermostat-S3 the alarm will
Start a burner program. activate, and the burner stops
Adjust down the safety
thermostat -S3 to below set Diesel oil temp. high
point for working thermostat -
S4. The safety thermostat requires manual reset.
9. DIESEL OIL TEMP LOW At start of heating the alarm activates and the
Start a burner program. burner stops.
Adjust alarm set point
[Alarm max. time dieselheater
start] Diesel oil temp. low
to "0".
10. DIESEL OIL PRESSURE At pressure below setting [Alarm minimum Diesel
LOW oil pressure] (11 Bar), the alarm activates, and
Start a burner program. the burner stops.
Reduce the fuel oil pressure
Diesel oil press. low
by adjusting the pump.
142
APPENDIX D: TEST OF SAFETY AND ALARMS
13. STEAM/AIR PRESSURE After 10 sec. alarm activates and the burner
SLUDGE LOW stops.
Adjust [Alarm setpoint
minimum steam/air pressure]
setting to 3.5 bar. Steam/air press. - sludge low
14. STEAM/AIR PRESSURE After 10 sec. alarm activates and the burner
SLUDGE HIGH stops.
Adjust [Alarm setpoint
maximum steam/air pressure] Steam/air press. - sludge high
setting to 1 bar.
Start a sludge program.
15. SLUDGE PRESSURE LOW After 10 sec. alarm activates and the burner
Adjust [Alarm setpoint stops.
minimum sludge pressure]
setting to 1 bar. Sludge pressure low
143
APPENDIX D: TEST OF SAFETY AND ALARMS
18. SLUDGE TEMP HIGH Alarm activates, and the burner stops.
Start a sludge program.
Adjust set point
[Min. sludge temp run sludge]
below actual temperature and Sludge temperature high
adjust alarm set point to 0.
[Alarm sludge temp high]
20. ERROR MODBUS COMM. Alarm activates, and the burner stops.
SLAVE 2 SDP
Withdraw the modbus plug on Error Modbus comm. slave 2 SDP
the inverter –U4, wait for
alarm modbus comm.
144
APPENDIX D: TEST OF SAFETY AND ALARMS
22. LOW LEVEL SLUDGE After 5 sec. delay the Alarm/Warning activates
SERVICE TANK and burner stops
Activate test lever if
mounted or disconnect cable. Low level sludge service tank
Start a sludge program.
23. CIRCUIT FAILURE FGT Alarm activates and the burner stops
Disconnect wire terminal
Circuit failure FGT
+1-X1-114
24. CIRCUIT FAILURE CCT Alarm activates, and the burner stops.
Disconnect wire from A2
Cartrige AI0 Circuit failure CCT
25. CIRCUIT FAILURE SDP Alarm activates, and the burner stops.
TEMP
Disconnect wire from A2
Circuit failure SDP Temp
Cartrige AI1
9
Sludge tank with el. heater.
145
APPENDIX D: TEST OF SAFETY AND ALARMS
146
DRAWINGS
DRAWINGS
147
DRAWINGS
List of drawings
Incinerator
Dwg. No Name of drawing
1011242 Piping & Instrument Diagram OG200C/CS, Steam Heating
116711 Combustion Chamber Assy. OG200/400C
116740 Combustion Chamber Assy. OG200/400CS
1008973 Combustion Chamber Mounting Drawing OG200/400C
116711M Combustion Chamber Main Dimension. OG200/400C
116740M Combustion Chamber Main Dimension. OG200/400CS
119827 Oil Burner F-50-45-T, 220V With Analog Motor
119512 Oil Burner F-50-45-T, 220V with Sludge Burner, Sub Assy.
1008970 Refractory and Insulation OG200C/CS
119640 Sludge Oil Dosage Valve Assembly,
116726 Garbage Door Assembly
116742 Door Assy.CO1310×510 with Sluice
3010075 Running Instructions OG200/400C
3010073 Running Instructions OG200/400CS
Flue gas
Dwg. No Name of drawing
1011015 Flue Gas Damper Assembly DN400/300
1006998 Flue Gas Damper, Sub. Assy DN400/300
1008644 Flue Gas Fan, Sub. Assy. DN 300 H2
4009251 Main dimensions Flue Gas Fan DN 300 H2
AS300-5 Expansion Compensator DN 300
Sludge Tank
Dwg. no Name of drawing
116831 Sludge Tank Assembly1100 L Net Steam Heating
116831M Main Dimension Sludge Tank 1100L Net Stem heating
Electrical diagrams
Dwg. no Name of drawing
2009906 Cable Arrangement for OG200C/CS
1011269 Control Panel 380/440V - 220V for OG400C/CS
1010728 Mounting Plate with El.Components 380/440V-220V, OG200C/CS
3010840 Electric Diagram 380/440V-220V Teamtec Incinerator OG200C/CS
3011031 Terminal Diagram Diesel Oil Burner F-50-45-T with Analog Motor
1010920 Control Panel Sludge Tank w/Steam Heating
2009668 Mounting Plate w/El.Components Sludge Tank w/Steam Heating
3010933 Electric Diagram Sludge Tank w/Steam Heating
14 8