CONTROL MODULE WITH CONTINUOUS MONITORING AND CAPACITOR CLOSE 110/125V - DV19450
ECLIPSE
CONTROL MODULE WITH CONTINUOUS MONITORING AND CAPACITOR CLOSE 110/125V
DV19450
In all communications please quote the contract and serial numbers of the equipment to allow a prompt response to queries. Designs are constantly subject to improvement and consequently there may be small differences in detail between the equipment supplied and that described in the manual. Instructions in this manual are given for information and guidance of appropriately qualified engineers, and where applicable must be considered in relation to the relevant National or International Health and Safety requirements / legislation and subsequent amendments. Should the user have any doubt regarding the interpretation of the information contained therein, our Customer Services Department will be pleased to advise accordingly. For contact details see page 18.
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE
NOTES
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ii
ECLIPSE RANGE
TABLE OF CONTENTS HEALTH AND SAFETY ......................................................................................................................... IV 1 FEATURES ........................................................................................................................................ 1 2 APPLICATION ................................................................................................................................... 1 3 GENERAL DESCRIPTION ................................................................................................................ 2 3.1 DESCRIPTION ...................................................................................................................... 2 3.2 INTRODUCTION ................................................................................................................... 2 3.3 TRIP CIRCUIT SUPERVISION ............................................................................................. 2 3.4 CLOSE CONTROL................................................................................................................ 2 3.5 TRIP CONTROL.................................................................................................................... 3 3.6 DISCONNECTOR POSITION MONITORING....................................................................... 3 3.7 CIRCUIT BREAKER (CB) MONITORING ............................................................................ 3 3.8 OPERATIONS COUNTER .................................................................................................... 3 3.9 PIC MICRO-CONTROLLER ................................................................................................. 4 3.10 ALARMS AND DISCONNECTOR POSITION INDICATION................................................ 4 4 LED FUNCTION & HEALTHY / ALARM STATES TABLE............................................................... 5 5 REMOTE TRIP/CLOSE UNIT ............................................................................................................ 6 6 TECHNICAL DATA............................................................................................................................ 6 6.1 VOLTAGE RATING (VX) ...................................................................................................... 6 6.2 BURDEN................................................................................................................................ 6 6.3 CONTACT RATING .............................................................................................................. 6 6.4 TYPE TESTING ..................................................................................................................... 6 7 TERMINAL FUNCTIONS ................................................................................................................... 7 7.1.1 Key........................................................................................................................... 7 7.1.2 Supply & Control Inputs........................................................................................... 8 7.1.3 Disconnector & Alarm Outputs ................................................................................ 8 7.1.4 Actuator Inputs ........................................................................................................ 8 7.1.5 Local/Remote Switch & Secondary Close Inhibit Contact Inputs............................ 8 7.1.6 Close Supply Input/Output....................................................................................... 9 7.2 FAULT FINDING ................................................................................................................... 9 7.3 FAULT FINDING AIDE.......................................................................................................... 9 7.3.1 Module has NO indication. ...................................................................................... 9 7.3.2 8.1.2 Circuit Breaker will not Close ..................................................................... 9 7.3.3 Circuit Breaker will not Trip. .................................................................................. 10 7.3.4 Trip Circuit Healthy (TCS) LED Flashing............................................................... 10 7.3.5 Circuit Breaker Healthy LED Flashing................................................................... 10 7.3.6 Aux. Wiring Healthy LED Flashing ........................................................................ 10 7.4 TRIP CIRCUIT SUPERVISION (TCS) FAIL FAULT FINDING........................................... 10 8 110/125VDC MODULE DV19450 .................................................................................................... 11 8.1 FEEDER INCOMER ARRANGEMENT............................................................................... 11 8.2 Bus Section Arrangement DV19450 ................................................................................ 12 9 ACTUATOR MONITORING CIRCUIT DV19450 ............................................................................. 13 10 BLOCK DIAGRAM DV19450 .......................................................................................................... 14 11 GENERAL ASSEMBLY ................................................................................................................... 15 12 CONTACT DETAILS........................................................................................................................ 15
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
iii
ECLIPSE RANGE
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
iv
ECLIPSE RANGE
1
-
FEATURES
Continuous Trip Circuit Supervision of actuator and control circuit. Circuit Breaker (CB) monitoring. Disconnector Position Monitoring. Control of maximum close pulse duration. Direct tripping. Built-in power relays for actuator trip and close control. Integral Local Indication showing the following: CB Position Selector In Use Trip Circuit Supervision CB Healthy Aux. Wiring Healthy
Operations Counter. Remote test connection for trip and close operation of the Eclipse. Fast close less than 70mS for UPS applications.
APPLICATION
The module is designed to control and monitor the Eclipse circuit breaker manufactured by Hawker Siddeley Switchgear Ltd. The module provides the following supervision: Continuous Trip Circuit Supervision of actuator and control circuit. CB Monitoring. Disconnector Position Monitoring.
The module provides the following control: CB trip, close and auto reclose control. Controls the maximum pulse length of a close signal to the actuator. Co-ordinates the correct operation of the actuator when trip and close signals occur simultaneously. Anti-pump close control.
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE
3 3.1
3.2
INTRODUCTION
The module comprises of three PCBs a Processor/Indication board, PSU/ I/O Board, a Control board with Capacitor Close circuitry. The Processor/Indication board is mounted at the top of the module, containing the control logic to initiate and control the close signal. A PIC micro-controller monitors the Disconnector and Circuit Breaker, and six LEDs for CB Position, Selector In Use, Trip Circuit Supervision, Circuit Breaker Healthy, Aux. Wiring Healthy, CB Close counter and the remote test connection for CB operation/indication of the Eclipse. The second PSU/I/O board contains the Power supply, monitoring components and remote alarm relay drives. The third Control board contains the four power relays for actuator control with an optocoupler for actuator Trip Circuit Supervision (TCS) along with the capacitor charging circuits and switching relays for the fast close operation.
3.3
The module uses a quad and a dual optocoupler to monitor the Trip Circuit. The quad optocoupler is used to monitor the trip control circuit and a dual to monitor the actuator circuit. As illustrated on the General Block Diagram, monitoring current is continually flowing in the two branches of the trip circuit. If any part of the two branches becomes open circuit then one or more of the optocoupler transistor outputs will go low, causing the TCS LED to flash, initiate a Remote TCS Alarm and prevent CB closing after a 500mS delay. This would also occur if the actuator or trip relay coil became open circuit. Circuit breaker position indication is deactivated when the trip circuit is unhealthy, to prevent incorrect position indication. Position indication is reactivated when the trip circuit is returned to its healthy state. The alarm condition can only be reset when the trip circuit is returned to its healthy state. NOTE: The Trip Circuit Supervision feature is not designed to be used as a supply voltage monitor.
3.4
CLOSE CONTROL
The substation battery is used to supply the charging energy for the close capacitors mounted external to the module, as well as energy for a close operation. This is because it acts as the bottom stage of a capacitor divider network. These close capacitors are charged in parallel to the battery, as illustrated on the block diagram. With the Disconnector Access cover closed, the close supply is connected to J2-12. When the Close handle is operated, it connects this supply to J2-7, which initiates a close operation. This close signal is fed into an electronic anti-pump circuit which checks that the circuit breaker is open and that no trip signal is present before outputting the close signal.
The Electronic Anti-pump circuit contains the following features: a) Limits the closing pulse to 300mS if CB fails to Close. b) The close pulse is cut off by a successful CB Close. c) Close signal must be removed before next close operation is attempted.
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08 2
ECLIPSE RANGE This output then energises relay RLY6 on the Control board 2802588-9, which switches the external close capacitors in series with the battery. This effectively gives a nominal closing supply of 2xthe battery voltage. At the same time the two power relays connected in series operate on the control board to close the CB and interrupt the close actuator current. A minimum close pulse of 50mS must be applied to the module for a successful close operation After the close operation relay RLY6 used to switch the capacitors in series de-energise. This effectively switches the capacitors in parallel with the battery. The capacitors then start to recharge through the current limiting resistor. The close pulse MUST NOT exceed 100mS for autoreclose operation.
3.5
TRIP CONTROL
When a trip signal is applied across terminals J2-4 & J2-5 it energises two power relays on the control board to trip the CB and interrupt the trip actuator current. This relay is not controlled by logic, so CB operation or the removal of the trip signal, which ever is the shortest, determines the relay ON time. In the unlikely event of the Eclipse failing to trip the cause of the problem needs to be identified before attempting to send another trip signal to the control module. NOTES: 1) The CB cannot be electrically tripped when the Disconnector is in the Earth Position. 2) ONLY VOLT FREE contacts are to be wired in parallel across J2-4 & J2-5
3.6
The modules again use optocouplers to monitor the position of the disconnector. transistor outputs from these are: -
a) Fed into the PIC microcontroller for monitoring b) Used to drive the base of open collector transistor outputs via another optocoupler used for isolation. These transistors drive the remote relay contacts. The PIC then uses these signals to monitor the position of the disconnector and if an invalid sequence is detected (e.g. change of disconnector position without the Selector In Use being detected) the Aux. Wiring Healthy LED will flash and a Remote General alarm signal is triggered.
3.7
Each CB operation is timed and compared to pre-set timing by the PIC. The timer is started when the PIC receives a valid Close or Trip command depending on the position of the CB and stops when the Aux. Switch changes state. If the time falls outside the pre-set time the Circuit Breaker Healthy flashes and a General Alarm signal is triggered. A subsequent operation of the CB within the pre-set timings will clear the alarm. The operating supply voltage and charge state should be checked to ensure full charge and further CB operations should be performed (with the disconnector in the OFF position).
3.8
OPERATIONS COUNTER
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE
3.9
PIC MICRO-CONTROLLER
The PIC Micro-controller is used ONLY for monitoring the disconnector position and CB status. There is no interaction between the PIC and CB operations (Close & Trip).
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE
DESCRIPTION CB in Open position CB in Closed position Selector Access Cover position State of Trip Circuit Supervision (TCS). Sets Remote TCS Alarm Contact if failed ON CB In Open Position
Yellow
CB In Open Position Disconnector Access Cover Closed Trip Circuit Unhealthy Check: - Control & Actuator Fuse - Actuator Wiring - Trip Control Circuit Wiring - Battery Condition Circuit Breaker Unhealthy Check: a) If Fail To Close:- Permanent Trip Signal Present - Actuator Fuse - Access Cover Open - Battery Condition - Close control circuit wiring - Module Powered - Access Cover is Closed - NO close inhibit b) If Fail To Trip:- Disconnector in Earth - Trip Circuit Healthy - Control & Actuator Fuse Aux Wiring Unhealthy Check: - If Remote Alarm Board is showing disconnector in more than one Position - Disconnector Microswitch inputs to module
Yellow
Monitors CB operation Alarms if fails to trip or Closed after receiving a valid control signal. Sets Remote General Alarm Contact if failed
Yellow
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE
Details for the Remote Trip / Close Unit can be found in Section 3.4.7 of the Eclipse Operation & Maintenance Manual No. 55/4154
6 6.1
All modules will withstand the maximum voltage in the operating range continuously. All modules will Trip down to 70% of rated voltage and Close down to 85%. Rating(VDC) 110/125 Operating range (VDC) 70-150 Part Number DV19450
6.2
BURDEN
Absolute Maximum Burden Rating(VDC) 110/125 Max. Module Voltage (VDC) 150 Supply Burden (mA) 70mA Watts (W) 10.5
6.3
CONTACT RATING
Alarm & Disconnector Position Indication relays Resistive Load (Cos _ =1) 3A at 220Vac 3A at 24VDC 3A 250Vac, 125VDC 3A 660VA 72W 1mA, 1VDC Inductive Load (Cos _ =0.4) 0.8A at 220Vac 1.5A at 24VDC
Rated Load Rated carry current Max. Switching voltage Max. Switching current Max. Switching capacity Min. permissible Load
16VA 36W
6.4
TYPE TESTING
The module was tested in accordance to Draft specification IEC publication 694 (17A/485/FDIS) and the Electrical Association Protection Approval Panel EATS 48-5 (Environmental test requirements for protection relay panel & systems). Where tests are not specifically addressed by standards called up by 694 or EATS 485, then generic standards for industrial electrical apparatus apply. The Eclipse Control Module is in compliance to the following: Cold Dry Heat Damp Heat Steady State Damp Heat Steady Cyclic Vibrations Endurance Shock Surge Fast Burst ESD Radiated Immunity Radiated Immunity Phones Radiated Emissions IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-3 IEC 60068-2-30 BS EN 60068-2-6 BS EN 60068-2-6 IEC 255-5 EN 61000-4-4 EN 61000-4-2 EN 61000-4-3 ENV 50204 EN 55011
6
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE Conducted Emissions Power Frequency Magnetic Field Immunity Pulse Magnetic Field Immunity Damped Oscillatory Magnetic Field Immunity Damped Oscillatory Generic Emissions Generic Immunity EN 55011 EN 61000-4-8 EN 61000-4-9 EN 61000-4-10 EN 61000-4-12 EN 50081-2 EN 50082-2
TERMINAL FUNCTIONS
The tables below explain the function of each terminal on the Eclipse Control Module.
7.1.1 Key +VDC -VDC Battery positive (i.e. 110VDC) Battery negative (i.e. 0v)
Disconnector Microswitch Inputs Pin Number J1-1 J1-2 J1-3 Function +VDC O/P Supply for microswitches (Usually NOT wired) Service Position Microswitch Input: Pin High (+VDC) when Isolator In Service, Low (VDC) when in other Position Service Position Microswitch Input (Bus-Section Coupler): Pin High (+VDC) when Isolator In Service, Low (-VDC) when in other Position: NOTE: Only wired when module fitted to a Bus-Section Panel Trip Circuit Supply Pin (See Note 1) Earth Position Microswitch Input: Pin High (+VDC) when Isolator NOT In Earth, Low (Resistor Volt drop) when in Earth Function External Wire Link to J1-5 and Coupler Earth Microswitch (Shorting Link if Switch NOT fitted) Earth Position Microswitch Input (Bus-Section Coupler): Pin High (Same potential as J1-6) when Isolator NOT In Earth, Low (Resistor Volt drop) when in Earth: NOTE: Shorting Link wired to J1-6 when module fitted to a Bus-section Panel External Wire Link to J1-7 and Circuit Breaker Position Microswitch Circuit Breaker Position Microswitch Input: Pin High (Same potential as J1-8) when CB CLOSED, Low (Resistor Volt drop) when CB OPEN Isolated Position Microswitch Input: Pin High (+VDC) when Isolator In Isolated, Low (VDC) when in other Position Isolated Position Microswitch Input (Bus-Section Coupler): Pin High (+VDC) when Isolator In Isolated, Low (-VDC) when in other Position: NOTE: Only wired when module fitted to a Bus-Section Panel Isolator Access Cover Microswitch Input: Pin High (+VDC) when cover CLOSED, Low (-VDC) when OPEN
J1-4 J1-5
J1-12
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE 7.1.2 Supply & Control Inputs Pin Number J2-1 J2-2 J2-3 J2-4 J2-5 J2-6 J2-7 Function Module Supply Input (+VDC) Module Supply Input (-VDC) Earth External Wire Link to J1-9 and Trip Control Trip Control Input: Pin High (Same potential as J1-8) when Trip requested, Low (Resistor Volt drop) when Trip not requested External Wire Link to J2-5 (See Note 2) Close Control Input: Pin High (+VDC) when Close requested, Low when Close not requested
7.1.3 Disconnector & Alarm Outputs Pin Number J3-1 J3-2 J3-3 J3-4 J3-5 J3-6 J3-7 Function Open Collector Transistor O/P pulls Pin Low (-VDC) when Isolator in Service Position Open Collector Transistor O/P pulls Pin Low (-VDC) when Isolator in Isolated Position Open Collector Transistor O/P pulls Pin Low (-VDC) when Isolator in Earth Position Open Collector Transistor O/P pulls Pin Low (-VDC) when Trip Circuit Supervision Fail NO CONNECTION Open Collector Transistor O/P pulls Pin Low (-VDC) when CB Unhealthy, Aux Wiring Fail (General Alarm) Open Collector Transistor O/P pulls Pin (Bus-Section Coupler) Low (-VDC) when coupler Isolator in Service Position: NOTE: Only wired when module fitted to a Bus-Section Panel Open Collector Transistor O/P pulls Pin (Bus-Section Coupler) Low (-VDC) when coupler Isolator in Isolated Position: NOTE: Only wired when module fitted to a Bus- Section Panel Open Collector Transistor O/P pulls Pin (Bus-Section Coupler) Low (-VDC) when coupler Isolator in Earth Position: NOTE: Only wired when module fitted to a Bus-Section Panel
J3-8
J3-9
7.1.4 Actuator Inputs Pin Number J4-1 J4-2 J4-3 J4-4 J4-5 Function Trip Actuator Supply Input (+VDC) Close Actuator Supply From J6-4 Actuator Input 1A: Pin voltage potential will be a resistor voltage drop below the Actuator Supply Pin J4-1 (See Note 3) Actuator Input 2A: Pin voltage potential will be two resistor voltage drops below the Actuator Supply Pin J4-1 (See Note 3) Actuator Supply Input (-VDC)
7.1.5 Local/Remote Switch & Secondary Close Inhibit Contact Inputs Pin Number J5-1 J5-2 J5-3 J5-4 Function +VDC Supply to Local/Remote Switch Contact Contact Closed when Local/Remote Switch Selected to Remote +VDC Supply to Close Inhibit Contact Contact Closed to Inhibit Close
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE 7.1.6 Close Supply Input/Output Pin Number J6-1 J6-2 J6-3 J6-4 J6-5 Function Close Actuator Supply Input (+VDC) Close External Capacitor +ve Input Close External Capacitor ve Input Close Actuator Supply output to J4-2 Close Actuator Supply Input (-VDC)
NOTES: 1. The Trip Control Circuit connections are from J1-4 to J1-9 and J2-4 to J2-6. Optocoupler devices are connected in parallel with each microswitch and across the Trip Input with resistors in series with each diode of the optocoupler device to monitor the Trip Control Circuit. This requires the external wiring to form a continual loop with a continuous current being passed through the circuit for the optocoupler to monitor. This means that if a microswitch is open then the voltage measured on that pin is going to be the supply to that microswitch minus the voltage drop across the resistor as noted by (Resistor Volt drop) in the description. 2. ONLY VOLT FREE CONTACTS are to be fitted in parallel with J2-4 and J2-5 to J2-6. If a +VDC supply is connected to J2-5 or J2-6 then the module will attempt a trip even if the CB is already Open and if the Isolator is in the Earth Position. 3. The Actuator Circuit is monitored in a similar way to the trip control circuit with an optocoupler connected across the Trip Contactor contacts. See note 1 for description of operation and reason for volt drop measured at Pins J4-2 & J4-3.
7.2 7.3
7.3.1 Module has NO indication. Check:Control Fuse 315mA Fuse Battery Supply is above: 55VDC for 110/125VDC DV19450 Circuit Breaker will not Close
Close Actuator Fuse Disconnector Access Cover is CLOSED There is no Close Inhibit ie J5-3 & J5-4 are open circuit Module has power. Leds ON NO Permanent Trip Signal Trip Circuit is Healthy Battery Condition Close Circuit Wiring
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
ECLIPSE RANGE 7.3.3 Circuit Breaker will not Trip. Check:Trip Actuator Fuse Control Fuse Disconnector NOT in Earth (Including Bus-Section Coupler if fitted) Trip Circuit Healthy Battery Condition
7.3.4 Trip Circuit Healthy (TCS) LED Flashing Check:Trip Actuator Fuse Control Fuse Battery Condition. Open circuit voltage must be above: 70VDC for 110/125VDC DV19450 Check terminal voltages as shown in sections 9 - 11
TCS Healthy LED resets when Trip Circuit becomes healthy. 7.3.5 Circuit Breaker Healthy LED Flashing Check:Parts 2 & 3 above.
CB Healthy LED resets when a subsequent operation of the CB is within the pre-set timings. 7.3.6 Aux. Wiring Healthy LED Flashing Check:ONLY one disconnector input is selected i.e. Service micro-switch CLOSED OR Isolator micro-switch CLOSED OR Earth micro-switch OPEN. Check Bus-Coupler if fitted.
Aux. Wiring Healthy LED resets when a valid subsequent of the disconnector is performed. NOTE: If any of the above faults persist, please contact Customer Service Department
7.4
If the TCS Healthy LED continues to flash after checking the above, the next step is to ascertain the module is receiving the correct inputs. This is achieved by measuring voltages in the two trip circuits to ensure that there are no breaks in the wiring. To aid this the circuits shown on pages 15-23 show the voltages that would be expected on each terminal of the trip circuit with all contacts OPEN. This means that the CB must be OPEN, the disconnector in the Earth position (Bus-Coupler if applicable) and NO trip signal present. The voltages shown assume the open circuit supply to be either: 110VDC 120VDC 130VDC Shown in RED text Shown in BLUE text Shown in MAGENTA text
For Feeder/Incomer Panels use pages 15 & 17, 18 & 20 or 21 & 23 to check. For Bus-section Panels use pages 16 & 17, 19 & 20 or 22 & 23 to check. All voltages shown are ideal therefore values shown are +/-10%.
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08 10
ECLIPSE RANGE
8 8.1
J1-4
Earth Microswitch CB
J1-5
Opto-Coupler Diode
18K
18K
J1-8
CB Position Micro-switch
J1-9 37VDC 41VDC 44VDC J2-4
18K
Trip Contact
J2-5
200R
200R
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
11
ECLIPSE RANGE
8.2
18K
J1-4
Earth Microswitch CB
J1-5
Opto-Coupler Diode
J1-6
Earth Microswitch Coupler Eclipse Control Module - PSU & I/O Board
200R
J1-7
J1-8
CB Position Micro-switch
J1-9 28VDC 31VDC 33VDC J2-4
18K
Trip Contact
J2-5 0.79VDC 0.87VDC 0.94VDC
200R
J2-6
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
12
J4-1
22K 4K7
ECLIPSE RANGE
78.50VDC
83.50VDC J4-3
Opto-Coupler Diode
88.50VDC
Actuator Coil
J4-4
22K 4K7
78.49VDC
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
83.49VDC
88.49VDC
J4-5
13
10
+VDC
+VDC +12V
J1-1
+VE
J2-1
+5V +5V
J2-2
Service Position
J1-2
Trip +VDC
J1-4
Service
-VE
ECLIPSE RANGE
PIC
Earth General Alarm O/P TCS General Alarm
Earth Position
Isolated
J1-5
Access Cover
J1-8
CB Aux.Switch
J5-2
J1-9
Lanyard Inhibit
Local LD1 LD2 LD3 LD4 LD5 LD6 Trip Circuit Supervision (TCS) Healthy LED J6-2 GND Close Inhibit +12V K3 +VDC RLY6 R16 Aux. Wiring Healthy LED D6 CB Healthy LED Access Cover Open LED CB Open LED CB Closed LED
Input Monitoring C
J5-3
J2-4
Trip
J2-5
J6-1
Close +VE
J6-4
R5
R6
J2-6
RLY1
+
External Capacitor Cext1 J6-3 RLY6
U5
Operations Counter
J2-7
Close Antipump
GND GND TCS_Status RLY3 GND R14
R15
J4-1 J4-2
Close
Trip +VE
J1-12
Isolator Position
J1-11
J4-4
J4-5
Actuator
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
J4-3
-VE
14
ECLIPSE RANGE
11
GENERAL ASSEMBLY
12
CONTACT DETAILS
To order additional accessories or additional copies of this manual, or for any other enquiries, please contact your sales representative or our Customer Service Department: Hawker Siddeley Switchgear Ltd Newport Road Blackwood Gwent NP12 2XH United Kingdom Telephone: +44 (0) 0800 42426666 +44 (0) 1495 223001 Fax: +44 (0) 1495 225674 e-mail: [email protected] Website: www.hss-ltd.com Hawker Siddeley Switchgear Ltd Technology Centre 2 Broadfield Distribution Centre, Heywood, Greater Manchester OL10 2TU Telephone: +44 (0) 0800 42426666 +44 (0) 1706 674000 Fax: +44 (0) 1706 674001
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
15
ECLIPSE RANGE OPERATION AND MAINTENANCE MANUAL MANUAL NO. 55/4201 Issue 2/08
16
Hawker Siddeley Switchgear Ltd Newport Road, Blackwood, South Wales, NP12 2XH UK Tel: +44 (0) 1495 223001 Fax: +44 (0) 1495 225674 [email protected] Hawker Siddeley Switchgear Pty Australia PO Box 36, Kallangur, QLD 4503, Australia Tel: +61 (0) 7 3888 2333 Fax: +61 (0) 7 3888 3241 [email protected] Hawker Siddeley Switchgear South America Carrera 21 No 86A-31 of 101, Bogota, Colombia Tel: +57 (0) 1 256 4617 Fax: +57 (0) 1 655 8915 [email protected] Hawker Siddeley Switchgear Ltd Technology Centre 2 Broadfield Distribution Centre, Heywood, Greater Manchester, OL10 2TU UK Tel: +44 (0) 1706 674000 Fax: +44 (0) 1706 674001 [email protected] Whipp & Bourne Inc. 2500 Almeda Avenue, Suite 115, Norfolk, USA VA 23513 Tel: +1 (0) 757 858 8972 Fax: +1 (0) 757 858 8987 [email protected]