TECHNOR® Brochure EJB EN
TECHNOR® Brochure EJB EN
TECHNOR® Brochure EJB EN
SERIES
FLAMEPROOF ENCLOSURES
EJB.. SERIES
EJB.. Series are Ex d enclosures suitable for a wide range of applications such as control units, junction boxes, industrial
power distribution switch racks; receptacles; heat tracing and lighting panels.
EJB.. series can host electric and/or electronic equipment and / or terminals.
CERTIFICATION DATA
II 2(1) GD
Ex db [ia Ga] IIB T6 Gb or
Ex db ia/ib [ia Ga] IIB T6 Gb or
Ex db [ia Ga] IIB+H2 T6 Gb or
Ex db ia/ib [ia Ga] IIB+H2 T6 Gb and/or
Ex tb [ia Da] IIIC T85°C Db
II 2(2) GD
Ex db [ib] IIB T6 Gb or
Ex db ia/ib [ib] IIB T6 Gb or
Ex db [ib] IIB+H2 T6 Gb or
Ex db ia/ib [ib] IIB+H2 T6 Gb and/or
Ex tb [ib] IIIC T85°C Db
I M2 Ex db I Mb
I M2(M1) Ex db [ia Ma] I Mb
I M2(M2) Ex db [ib] I Mb
Maximum dissipated power is related to T4/
T150°C, see tables 5.1, 5.2, 5.3 on pages 11-12.
Certification 0080
ATEX - INERIS 00ATEX0021X
ATEX - INERIS 21ATEX9004U
IECEx - IECEx INE 10.0015X
IECEx - IECEx INE 21.0006U
RU C-IT.BH02.B.00588/20
KC - 1
6-KA4BO-0466X, 16-KA4BO-0467X,
16-KA4BO-0468X, 17-KA4BO-0296X,
18-KA4BO-0260X, 20-KA4BO-0598X, 22-KA4BO-0091X
PESO - P529307/1
technor.com 3
MECHANICAL FEATURES
Handle
Window
Stainless steel hinges
4 technor.com
DIMENSIONS - EJB.. IN COPPER-FREE ALUMINIUM
M20 - ½” 9/7 14/7 14/7 14/9 27/13 24/18 35/16 27/24 57/21 32/27 61/28 48/32 81/54 111/110
M25 - ¾” 9/5 7/3 7/3 7/4 14/7 14/10 29/13 24/18 46/18 21/27 40/18 27/18 54/36 71/70
M32 - 1” 4/3 6/3 6/3 6/4 12/5 12/9 18/8 12/10 29/10 14/12 32/16 23/16 35/24 43/43
M50 - 1 ½” 3/2 4/2 4/2 4/3 5/2 5/4 7/3 9/9 14/5 6/5 16/7 9/6 18/10 17/17
M63 - 2” 2/1 3/1 3/1 3/2 4/2 4/3 6/2 4/4 12/4 5/4 12/5 8/5 14/9 11/11
M75 - 2 ½” - - - - 3/1 3/2 4/2 3/3 5/2 4/3 6/3 6/4 6/4 7/7
M80 - 3” - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 6/6
M90 - 3 ½ - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 6/5
M100 – 4” - - - - 2/1 2/2 2/1 2/2 4/1 3/2 4/2 4/3 5/3 5/4
technor.com 5
DIMENSIONS - EJB.. IN AISI316L/GALVANIZED CARBON STEEL
Unlimited design possibilities: EJB dimensions can increase/decrease up to 15%* thanks to state-of-
the-art technologies and components in order to fully satisfy all specific customers’ requirements
6 technor.com
EJB.. SERIES – TERMINALS
Full customization based on users’ needs in terms of size and number of terminals or cables to be
installed inside the enclosure. All terminals can be equipped with accessories as per customers’
request. Our technical dept. will determine the most suitable size of the enclosure taking into account:
the required parameters as specified by the customer in the request stage and the limits allowed by
the certificate.
ELECTRICAL FEATURES
TERMINALS
Max. supply voltage 20 KVac or 20 KVdc
Busbars
EJB MODELS NOMINAL SECTION (MM2) NOMINAL CURRENT (A)
From EJB-2 to EJB-14 36 72
From EJB-2 to EJB-14 100 200
From EJB-2 to EJB-14 160 250
From EJB-4 to EJB-14 250 400
From EJB-6 to EJB-14 400 625
technor.com 7
EJB.. SERIES – TERMINALS
8 technor.com
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS
EJB.. Series can be used as control, monitoring and signaling units offering complete protection for
electrical equipment and control circuits located in hazardous areas and in particularly aggressive
environments.
Used to host electrical equipment, such as: switches, indicators, contactors, transformers, EJB..
enclosures can be equipped with lid-mounted control and signaling devices, such as pushbuttons
and indicator lights.
The number of components and installable equipment inside the enclosures and their disposition
vary according to your requirements: Technor Italsmea offers full customization providing extremely
complex solutions, yet meeting all the limits allowed by the certificate.
technor.com 9
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS
Wide range of lid-mounted Ex d operators* which allow the external control of components installed
inside the enclosure.
COMPONENTS SPECIFICATIONS:
IP rating IP66
RATINGS:
PUSH BUTTONS
Max. current 10 A
PILOT LAMPS
ROTARY SWITCH
Max. current 63 A
10 technor.com
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS
Temperature class and max. surface temperature of the control and monitoring units depend on
enclosure size, ambient temperature and power dissipation inside the enclosure.
The total dissipated power (W) of the installed apparatus cannot exceed the values stated in the tables
below.
Table 5.1 - Maximum dissipated power (W / VA) for EJB without windows and without or with IS apparatus
when IS apparatus is protected by thermal probes
TYPE OF T6/T85°C T5/T100°C T4/T135°C T3/T200°C
ENCLOSURE FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO
40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C
EJB-2 74 56 47 38 101 83 74 65 164 146 137 128 281 263 254 245
EJB-3 96 72 61 49 131 107 96 84 213 189 178 166 365 341 330 318
EJB-3A 102 77 65 52 140 115 102 90 227 202 190 177 390 365 352 340
EJB-4 114 86 72 58 156 128 114 100 253 225 211 197 434 406 392 378
EJB-5 138 110 82 64 193 156 138 119 322 285 267 248 561 524 506 487
EJB-6 173 139 104 81 243 197 173 150 405 359 336 312 706 660 637 614
EJB-8; 9 216 173 130 101 303 245 216 187 505 448 419 390 881 823 794 765
EJB-10; 11 254 203 152 118 355 287 254 220 592 525 491 457 1033 955 931 897
EJB-12 324 237 194 151 453 367 324 280 756 670 627 583 1319 1232 1189 1146
EJB-13 431 308 246 185 615 492 431 369 1046 923 861 800 1845 1722 1661 1599
EJB-13A; 13 XL 487 348 278 209 695 556 487 417 1181 1042 973 904 2085 1946 1876 1807
EJB-14 728 520 416 312 1039 832 728 624 1767 1559 1455 1351 3117 2909 2806 2702
T° Cable 80°C 90°C 120°C 175°C
Table 5.2 - Maximum dissipated power (W / VA) for EJB with windows, and without or with IS apparatus
when IS apparatus is protected by thermal probes.
TYPE OF T6/T85°C T5/T100°C T4/T135°C
ENCLOSURE FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO
40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C
EJB-2; 3; 3A 67 48 39 30 94 76 67 58 158 140 131 121
EJB-4; 5; 6 114 86 72 58 156 128 114 100 253 225 211 197
EJB-8; 9 144 108 88 72 195 144 119 100 315 234 211 197
EJB-10; 11 180 132 108 90 268 200 161 134 360 270 216 197
EJB-12 240 180 144 120 323 242 195 162 405 301 243 203
EJB-13 280 208 168 140 365 272 221 183 450 337 270 225
EJB-13A; 13 XL 320 240 192 160 408 306 246 204 477 355 288 239
T° Cable 80°C 90°C 120°C
technor.com 11
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS
Table 5.3 - Maximum dissipated power (W / VA) for EJB with or without windows with IS apparatus without
thermal probes protection.
TYPE OF T.AMB OF THE T6/T85°C FOR AMBIENT UP TO
ENCLOSURE INTRINSIC SAFETY
ELEMENT 40°C 50°C 55°C 60°C
12 technor.com
EJB.. SERIES – WITH WINDOWS
EJB.. Series may host electrical equipment which requires a direct reading from the outside. For
this reason, our enclosures can be equipped with a window suitable for the visualization of internal
apparatus such as: voltmeters, ammeters and/or other analogue measuring instruments.
Our windows may have multiple shape options and different sizes according to customers' requirements.
Our technical department will support you in choosing the suitable window to meet your specifications
within the technical limits allowed by the certificate.
COMPONENTS SPECIFICATIONS:
Window glass Toughened Calciosodium
T class T6 / T5 / T4
technor.com 13
ACCESSORIES UPON REQUEST
WALL MOUNTING
Available for all EJB versions
BRACKETS
DRAIN / BREATHER
ECR-1 Valve
VALVE
NEW
HELPING CLOSING
SYSTEM C/W Available for all EJB versions
SCREWS
14 technor.com
ACCESSORIES UPON REQUEST
WALL MOUNTING
Available for all EJB versions
BRACKETS
DRAIN / BREATHER
ECR-1 Valve
VALVE
NEW
HELPING CLOSING
SYSTEM C/W
Available for all EJB versions
SCREWS
technor.com 15
WORLD PRESENCE
NON CONTRACTUAL DOCUMENT AND PICTURES. All the indications appearing in this catalogue are indicative and could not constitute a commitment on our part. We reserve the right to alter specifications of our products without any prior notice in our efforts to continuously improve our products features.
MARECHAL
GMBH
MARECHAL
ELECTRIC
TECHNOR ITALSMEA
MELTRIC
MARECHAL ELECTRIC
CHINA
TECHNOR
MIDDLE EAST
MARECHAL ELECTRIC
ASIA
MARECHAL ELECTRIC
AFRICA
MARECHAL
AUSTRALIA
marechal.com technor.com