EJB.. Series are Ex d enclosures suitable for a wide range of applications such as control units, junction boxes, industrial
power distribution switch racks; receptacles; heat tracing and lighting panels.
EJB.. series can host electric and/or electronic equipment and / or terminals.

CERTIFICATION DATA

Classification Group II – Category 2GD

Group I – Category M2 (aluminum version excluded)

Application Zone Gas: 1, 2 Dust: 21, 22

Marking Full Conformity Certificate Component Certificate


II 2 GD II 2G Ex db IIB Gb or
Ex db IIB T(*) Gb or II 2G Ex db IIB+H2 Gb or
Ex db IIB+H2 T(*) Gb or I M2 Ex db I Mb and/or
Ex db ia/ib IIB T(*) Gb or II 2D Ex tb IIIC Db IP66
Ex db ia/ib IIB+H2 T(*) Gb and/or
Ex tb IIIC T(*) Db
*T6/T85°C, T5/T100°C,
T4/T135°C, T3/T200°C

II 2(1) GD
Ex db [ia Ga] IIB T6 Gb or
Ex db ia/ib [ia Ga] IIB T6 Gb or
Ex db [ia Ga] IIB+H2 T6 Gb or
Ex db ia/ib [ia Ga] IIB+H2 T6 Gb and/or
Ex tb [ia Da] IIIC T85°C Db

II 2(2) GD
Ex db [ib] IIB T6 Gb or
Ex db ia/ib [ib] IIB T6 Gb or
Ex db [ib] IIB+H2 T6 Gb or
Ex db ia/ib [ib] IIB+H2 T6 Gb and/or
Ex tb [ib] IIIC T85°C Db

I M2 Ex db I Mb
I M2(M1) Ex db [ia Ma] I Mb
I M2(M2) Ex db [ib] I Mb
Maximum dissipated power is related to T4/
T150°C, see tables 5.1, 5.2, 5.3 on pages 11-12.

Certification 0080
ATEX - INERIS 00ATEX0021X
ATEX - INERIS 21ATEX9004U
IECEx - IECEx INE 10.0015X
­IECEx - IECEx INE 21.0006U
RU C-IT.BH02.B.00588/20
KC - 1
 6-KA4BO-0466X, 16-KA4BO-0467X,
16-KA4BO-0468X, 17-KA4BO-0296X,
18-KA4BO-0260X, 20-KA4BO-0598X, 22-KA4BO-0091X
­PESO - P529307/1

Standards EN/IEC 60079-0; EN/IEC 60079-1; EN/IEC 60079-11; EN/IEC 60079-31

Ambient temperature Full Conformity Certificate Component Certificate


-60°C to +60°C (without window) -60°C to +200°C (without window)
-50°C to +60°C (with window and/or pilot light -50°C to +130°C (with window - EJB-2 to EJB-9)
PLD) -50°C to +128°C (with window - EJB-10 to EJB-14)

Degree of protection IP66

technor.com 3
MECHANICAL FEATURES

Body Copper-free aluminium or


AISI316L stainless steel or
Galvanized carbon steel

Hinges AISI316L Stainless steel

Handle Polyamide reinforced with glass fiber or Polypropylene

Hardware & Screws AISI316L stainless steel

Entries Metric pitch 1.5 and/or NPT according to ANSI/ASME B1.20.1

Mounting brackets Galvanized steel


Upon request: Stainless steel A4-80

Coating Polyurethane painting cycle RAL5014 (other colours available on request)

Certification label Acrylic laminate.


Upon request: AISI316L stainless steel

Thanks to its design, the handle ensures:


• Easy opening and closing of the enclosure;
• Greater safety of use for the operator;
• Corrosion resistance in saline environments;
• Pleasing aesthetics.

Handle

Stainless steel bolts Mounting brackets

Window
Stainless steel hinges

4 technor.com
DIMENSIONS - EJB.. IN COPPER-FREE ALUMINIUM

Table 1.1 - EJB.. Series enclosures c/w internal mounting plate


TYPE DIMENSIONS [MM] WEIGHT COVER MOUNTING
ENTRIES
A B C D E F G H I L M N ØP R [KG] PLATE(S)
EJB-2 298 238 163 230 168 116 135 205 140 250 280 9 M6 20 10.07 12 160 X 220
EJB-3 410 236 167 340 167 115 136 330 150 250 280 9 M8 20 13.40 18 155 X 330
EJB-3A 410 236 191 340 167 115 158 330 150 250 280 9 M8 20 13.50 9 155 X 330
EJB-4 415 300 165 335 220 116 132 300 190 300 320 9 M8 20 17.50 20 210 X 325
EJB-5 477 297 221 392 209 157 182 350 185 300 320 9 M8 20 20.50 22 200 X 385
EJB-6 478 404 226 387 310 160 186 355 280 390 420 9 M8 20 33.00 28 300 X 380
EJB-8 630 361 246 530 262 173,5 204 495 225 340 370 9 M8 20 36.05 36 250 X 520
EJB-9 532 465 252 426 363 177 204 410 340 440 470 12 M10 20 40.00 34 350 X 420
EJB-10 754 366 294 630 250 217 234 580 205 330 360 12 M10 20 48.50 34 240 X 620
EJB-11 592 501 257 483 394 174 204 445 360 480 510 12 M10 20 53.30 44 380 X 470
EJB-12 801 450 300 690 335 206,5 243 640 285 425 450 14 M12 20 73.00 54 325 X 625
EJB-13 830 604 298 723 500 160 236 630 405 580 620 14 M12 20 106.00 76 463 X 683
EJB-13A 830 604 404 723 500 265 322 630 405 580 620 14 M12 20 124.00 76 463 X 683
EJB-14 970 770 478 795 595 343 404 765 565 710 770 16 M14 25 245.00 0 795x595
745 545 378 439 745x545
EJB-14* 970 770 461 795 595 343 367 765 565 710 770 16 M14 25 310.00 57 795x595
745 545 378 402 745x545

*Copper-free aluminium enclosure with stainless steel/galvanized carbon steel cover

Table 1.2 - Maximum number of entries on sides A/B


TYPE EJB-2 EJB-3 EJB-3A EJB-4 EJB-5 EJB-6 EJB-8 EJB-9 EJB-10 EJB-11 EJB-12 EJB-13 EJB-13A EJB-14

M20 - ½” 9/7 14/7 14/7 14/9 27/13 24/18 35/16 27/24 57/21 32/27 61/28 48/32 81/54 111/110
M25 - ¾” 9/5 7/3 7/3 7/4 14/7 14/10 29/13 24/18 46/18 21/27 40/18 27/18 54/36 71/70
M32 - 1” 4/3 6/3 6/3 6/4 12/5 12/9 18/8 12/10 29/10 14/12 32/16 23/16 35/24 43/43
M50 - 1 ½” 3/2 4/2 4/2 4/3 5/2 5/4 7/3 9/9 14/5 6/5 16/7 9/6 18/10 17/17
M63 - 2” 2/1 3/1 3/1 3/2 4/2 4/3 6/2 4/4 12/4 5/4 12/5 8/5 14/9 11/11
M75 - 2 ½” - - - - 3/1 3/2 4/2 3/3 5/2 4/3 6/3 6/4 6/4 7/7
M80 - 3” - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 6/6
M90 - 3 ½ - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 6/5
M100 – 4” - - - - 2/1 2/2 2/1 2/2 4/1 3/2 4/2 4/3 5/3 5/4

technor.com 5
DIMENSIONS - EJB.. IN AISI316L/GALVANIZED CARBON STEEL

Unlimited design possibilities: EJB dimensions can increase/decrease up to 15%* thanks to state-of-
the-art technologies and components in order to fully satisfy all specific customers’ requirements

*provided that internal volume does not increase/decrease of more than 1%

Table 2.1 - EJB.. Series enclosures c/w internal mounting plate


TYPE DIMENSIONS [MM] WEIGHT COVER INT. MOUNTING
[KG] ENTRIES PLATE
A B C D E G H L M ØP R
EJB-2 296 234 158 230 168 132 205 250 280 10 20 35 12 160 X 220
EJB-3 408 235 161 340 167 130 330 250 280 10 20 45 18 155 X 330
EJB-4 414 298 160 336 220 126 300 305 340 12 20 55 20 210 X 325
EJB-5 472 289 210 392 209 176 350 295 330 12 20 70 22 200 X 385
EJB-6 489 414 224 399 324 190 355 410 450 14 25 93 28 300 X 380
EJB-8 617 348 237 531 162 198 495 360 400 14 25 114 36 250 X 520
EJB-9 516 453 237 426 363 198 400 460 500 14 25 118 34 350 X 420
EJB 10 726 344 267 630 248 228 580 340 380 14 25 125 40 560X178
EJB-11 585 496 236 483 394 215 445 490 530 14 25 139 44 380 X 470
EJB-12 809 459 299 705 355 256 640 440 480 16 30 181 54 325 X 675
EJB-13 825 602 269 723 500 226 667 605 650 18 30 235 76 463 X 683
EJB-13A 825 602 355 723 500 330 667 605 650 18 30 262 76 463 X 683
EJB-13 XL 940 650 404 840 550 356 775 650 690 18 30 300 80 793 x 509
EJB-14 970 770 436 850 650 378 790 760 800 20 30 530 57 795 X 595

Table 2.2 - Maximum number of entries on sides A/B


TYPE EJB-2 EJB-3 EJB- EJB-4 EJB-5 EJB-6 EJB-8 EJB-9 EJB- EJB- EJB- EJB- EJB- EJB- EJB-14
3A 10 11 12 13 13A 13XL
M20 - ½” 9/7 14/7 14/7 14/9 27/13 24/18 35/16 27/24 57/21 32/27 61/28 48/32 81/54 96/110 111/110
M25 - ¾” 9/5 7/3 7/3 7/4 14/7 14/10 29/13 24/18 46/18 21/27 40/18 27/18 54/36 62/70 71/70
M32 - 1” 4/3 6/3 6/3 6/4 12/5 12/9 18/8 12/10 29/10 14/12 32/16 23/16 35/24 39/43 43/43
M50 - 1 ½” 3/2 4/2 4/2 4/3 5/2 5/4 7/3 9/9 14/5 6/5 16/7 9/6 18/10 17/17 17/17
M63 - 2” 2/1 3/1 3/1 3/2 4/2 4/3 6/2 4/4 12/4 5/4 12/5 8/5 14/9 12/11 11/11
M75 - 2 ½” - - - - 3/1 3/2 4/2 3/3 5/2 4/3 6/3 6/4 6/4 7/7 7/7
M80 - 3” - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 6/6 6/6
M90 - 3 ½ - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 5/3 5/3 5/4 6/5
M100 - 4” - - - - 2/1 2/2 3/1 2/2 4/1 3/2 4/2 4/3 4/3 4/3 5/4

6 technor.com
EJB.. SERIES – TERMINALS

Full customization based on users’ needs in terms of size and number of terminals or cables to be
installed inside the enclosure. All terminals can be equipped with accessories as per customers’
request. Our technical dept. will determine the most suitable size of the enclosure taking into account:
the required parameters as specified by the customer in the request stage and the limits allowed by
the certificate.

ELECTRICAL FEATURES
TERMINALS
Max. supply voltage 20 KVac or 20 KVdc

Max. current 2.000 A

Rated frequency 0-1.000 Hz

Max. supply voltage for 500 V


«IS» element

Busbars
EJB MODELS NOMINAL SECTION (MM2) NOMINAL CURRENT (A)
From EJB-2 to EJB-14 36 72
From EJB-2 to EJB-14 100 200
From EJB-2 to EJB-14 160 250
From EJB-4 to EJB-14 250 400
From EJB-6 to EJB-14 400 625

technor.com 7
EJB.. SERIES – TERMINALS

Table 3.1 – Terminals rated current


TERMINALS – RATED CURRENT

Terminal cross- 2,5 4 6 10 16 35 50 70 95 120 185 240 300


sectional area (mm2)
Rated current (A) 24 32 41 57 76 125 150 192 239 269 353 415 520

Table 3.2 - Indicative maximum quantity of terminals


Max. number of terminals calculated according to following parameters:
• T. class = T3
• Ambient temp. = +40°C
TYPE EJB-2 EJB-3 EJB-4 EJB-5 EJB-6 EJB-8 EJB-9 EJB-10 EJB-11 EJB-12 EJB-13 EJB-14
EJB-13A
EJB-
SECTION 13XL
2,5 mmq 52 84 122 148 224 276 320 308 360 488 712 1026
4 mmq 48 69 102 122 188 195 220 259 300 357 600 856
6 mmq 36 54 78 69 138 150 168 168 232 273 425 594
10 mmq 21 32 40 57 87 102 123 122 148 186 276 406
16 mmq 17 26 32 45 72 80 84 95 114 130 228 325
35 mmq 9 18 24 23 36 45 50 56 69 82 140 196
50 mmq - 14 20 20 30 36 44 48 57 70 108 168
70 mmq - 7 15 18 28 33 38 33 44 60 88 140
95 mmq - - - 7 13 18 24 24 26 33 50 87
120 mmq - - - 7 13 16 15 24 26 33 50 87
185 mmq - - - - - - - - - 18 24 48
240 mmq - - - - - - - - - 16 24 48
300 mmq - - - - - - - - - 5 16 20

Max. number of terminals calculated according to following parameters:


• T. class = T6
• Ambient temp. = +60°C
TYPE EJB-2 EJB-3 EJB-4 EJB-5 EJB-6 EJB-8 EJB-9 EJB-10 EJB-11 EJB-12 EJB-13 EJB- EJB-14
13A
EJB-
SECTION 13XL
2,5 mmq 40 44 49 50 59 64 66 65 71 76 84 93 117
4 mmq) 34 37 42 42 50 55 57 56 61 66 73 81 103
6 mmq 32 35 40 39 47 51 53 52 57 62 68 75 95
10 mmq 25 27 31 31 37 41 42 42 46 50 56 61 79
16 mmq 18 20 23 23 28 32 33 33 36 40 45 50 64
35 mmq 9 11 13 14 17 19 20 21 22 25 29 32 43
50 mmq - 7 8 9 11 13 14 15 15 18 21 24 33
70 mmq - 11 13 14 16 19 19 20 21 24 27 30 40
95 mmq - - - 12 15 18 18 19 20 23 27 30 40
120 mmq - - - 8 10 11 11 12 13 15 17 19 25
185 mmq - - - - - - - - - 8 10 11 16
240 mmq - - - - - - - - - 7 8 9 13
300 mmq - - - - - - - - - 5 7 8 11

8 technor.com
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS

EJB.. Series can be used as control, monitoring and signaling units offering complete protection for
electrical equipment and control circuits located in hazardous areas and in particularly aggressive
environments.
Used to host electrical equipment, such as: switches, indicators, contactors, transformers, EJB..
enclosures can be equipped with lid-mounted control and signaling devices, such as pushbuttons
and indicator lights.
The number of components and installable equipment inside the enclosures and their disposition
vary according to your requirements: Technor Italsmea offers full customization providing extremely
complex solutions, yet meeting all the limits allowed by the certificate.

Table 4 – Example of equipment which can be installed:


COMPONENT TYPE

Instruments of measure of electric parameters Time relay


Electronic thermoregulation units Photocells
Radio communication and telephony units Capacitors
PLC and multiplexer Transformers
Devices for the control and the weight measure; pressure; damp; Anticondensate heatings
level; temperature and capacity
Automatic and/or earth leakage circuit breakers Circumferentor and recorders of physical data
Switches; on load switches; rotary switches Displays
Fuses / antitrouble filters Ignitors
Contactors; remote control switches General purpose drive and UPS
Relay Fans
Led lamps 3 W max. Cells and batteries
Electric and electronic of regulation and of starting devices Terminals
Intrinsically safe devices

technor.com 9
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS

Wide range of lid-mounted Ex d operators* which allow the external control of components installed
inside the enclosure.

COMPONENTS SPECIFICATIONS:
IP rating IP66

T. amb range -60°C to +60°


-50°C to +60°C for pilot light
PLD

Barrel thread Metric M12x1,75; M16x1,5;


M32x1,5

Option With AISI316L external


hexagonal ring
(Upon request)

RATINGS:
PUSH BUTTONS

Max. voltage 660 V

Max. current 10 A

PILOT LAMPS

Max. voltage 400V AC-DC

Max. power 3 W (LED lamp)

ROTARY SWITCH

Max. voltage 750 V

Max. current 63 A

*Visit our catalogue and find out more about Ex d components

10 technor.com
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS

Temperature class and max. surface temperature of the control and monitoring units depend on
enclosure size, ambient temperature and power dissipation inside the enclosure.
The total dissipated power (W) of the installed apparatus cannot exceed the values stated in the tables
below.

Table 5.1 - Maximum dissipated power (W / VA) for EJB without windows and without or with IS apparatus
when IS apparatus is protected by thermal probes
TYPE OF T6/T85°C T5/T100°C T4/T135°C T3/T200°C
ENCLOSURE FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO
40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C
EJB-2 74 56 47 38 101 83 74 65 164 146 137 128 281 263 254 245
EJB-3 96 72 61 49 131 107 96 84 213 189 178 166 365 341 330 318
EJB-3A 102 77 65 52 140 115 102 90 227 202 190 177 390 365 352 340
EJB-4 114 86 72 58 156 128 114 100 253 225 211 197 434 406 392 378
EJB-5 138 110 82 64 193 156 138 119 322 285 267 248 561 524 506 487
EJB-6 173 139 104 81 243 197 173 150 405 359 336 312 706 660 637 614
EJB-8; 9 216 173 130 101 303 245 216 187 505 448 419 390 881 823 794 765
EJB-10; 11 254 203 152 118 355 287 254 220 592 525 491 457 1033 955 931 897
EJB-12 324 237 194 151 453 367 324 280 756 670 627 583 1319 1232 1189 1146
EJB-13 431 308 246 185 615 492 431 369 1046 923 861 800 1845 1722 1661 1599
EJB-13A; 13 XL 487 348 278 209 695 556 487 417 1181 1042 973 904 2085 1946 1876 1807
EJB-14 728 520 416 312 1039 832 728 624 1767 1559 1455 1351 3117 2909 2806 2702
T° Cable 80°C 90°C 120°C 175°C

Table 5.2 - Maximum dissipated power (W / VA) for EJB with windows, and without or with IS apparatus
when IS apparatus is protected by thermal probes.
TYPE OF T6/T85°C T5/T100°C T4/T135°C
ENCLOSURE FOR AMBIENT UP TO FOR AMBIENT UP TO FOR AMBIENT UP TO
40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C 40°C 50°C 55°C 60°C
EJB-2; 3; 3A 67 48 39 30 94 76 67 58 158 140 131 121
EJB-4; 5; 6 114 86 72 58 156 128 114 100 253 225 211 197
EJB-8; 9 144 108 88 72 195 144 119 100 315 234 211 197
EJB-10; 11 180 132 108 90 268 200 161 134 360 270 216 197
EJB-12 240 180 144 120 323 242 195 162 405 301 243 203
EJB-13 280 208 168 140 365 272 221 183 450 337 270 225
EJB-13A; 13 XL 320 240 192 160 408 306 246 204 477 355 288 239
T° Cable 80°C 90°C 120°C

technor.com 11
EJB.. SERIES – CONTROL, MONITORING, SIGNALING UNITS
Table 5.3 - Maximum dissipated power (W / VA) for EJB with or without windows with IS apparatus without
thermal probes protection.
TYPE OF T.AMB OF THE T6/T85°C FOR AMBIENT UP TO
ENCLOSURE INTRINSIC SAFETY
ELEMENT 40°C 50°C 55°C 60°C

EJB-2 60°C 18 4 N/A N/A


70°C 32 18 11 4
80°C 46 32 25 18
85°C 53 39 32 25
EJB-3 60°C 27 13 7 N/A
70°C 40 27 20 13
80°C 53 40 33 27
85°C 60 47 40 33
EJB-3A 60°C 29 14 7 N/A
70°C 43 29 21 14
80°C 57 43 36 29
85°C 64 50 43 36
EJB-4 60°C 32 16 8 N/A
70°C 48 32 24 16
80°C 64 48 40 32
85°C 71 56 48 40
EJB-5 60°C 41 20 10 N/A
70°C 61 41 31 20
80°C 81 61 51 41
85°C 92 71 61 51
EJB-6 60°C 51 26 13 N/A
70°C 77 51 38 26
80°C 103 77 64 51
85°C 115 90 77 64
EJB-8; 9 60°C 64 32 16 N/A
70°C 96 64 48 32
80°C 128 96 80 64
85°C 144 112 96 80
EJB-10; 11 60°C 75 38 19 N/A
70°C 113 75 56 38
80°C 150 113 94 75
85°C 169 131 113 94
EJB-12 60°C 96 48 24 N/A
70°C 144 96 72 48
80°C 192 144 120 96
85°C 215 168 144 120
EJB-13 60°C 123 61 31 N/A
70°C 184 123 92 61
80°C 245 184 153 123
85°C 276 214 184 153
EJB-13A; 13 XL 60°C 138 69 35 N/A
70°C 208 138 104 69
80°C 277 208 173 138
85°C 312 242 208 173
EJB-14* 60°C 207 104 52 N/A
70°C 311 207 155 104
80°C 414 311 259 207
85°C 466 362 311 259
T° Cable 80°C

*Without window only

12 technor.com
EJB.. SERIES – WITH WINDOWS
EJB.. Series may host electrical equipment which requires a direct reading from the outside. For
this reason, our enclosures can be equipped with a window suitable for the visualization of internal
apparatus such as: voltmeters, ammeters and/or other analogue measuring instruments.
Our windows may have multiple shape options and different sizes according to customers' requirements.
Our technical department will support you in choosing the suitable window to meet your specifications
within the technical limits allowed by the certificate.
COMPONENTS SPECIFICATIONS:
Window glass Toughened Calciosodium

T class T6 / T5 / T4

Max. T amb +60°C


(according to the dissipated heat
temperature, refer to Table 5.2)

Min. T amb -50°C


When T. amb is lower than -20°C
and window size is equal to or
larger than 150 x 150 mm, internal
reinforcements need to be provided.

Table 6 – Window specifications


TYPE OF MAX. REMOVABLE AREA [CM²] MAX. WINDOW GLASS THICKNESS
ENCLOSURE DIMENSIONS [mm]
TAMB ≥ -20°C -50°C < TAMB < -20°C [mm]

EJB 2 170 170 170 x 100 12


170 170 170 x 100 15
EJB 3 220 170 270 x 100 12
270 270 270 x 100 15
EJB 4 220 170 270 x 100 12
270 270 270 x 100 15
EJB 5 220 170 270 x 100 12
355 270 270 x 100 15
410 319 290 x 110 19
EJB 6 234 (=7 x *) 189 (=6 x *) 70 x 45 12
235 190 290 x 110 15
410 319 290 x 110 19
EJB 8 312 (=9 x *) 252 (=8 x *) 70 x 45 12
235 190 290 x 110 15
410 319 290 x 110 19
EJB 9 350 (=11 x *) 283 (=9 x *) 70 x 45 12
235 190 290 x 110 15
410 319 290 x 100 19
EJB 10 126 (=4 x *) 126 (=4 x *) 70 x 45 15
225 225 300 x 75 19
EJB 11 126 (=4 x *) 126 (=4 x *) 70 x 45 15
225 225 300 x 75 19
EJB 12 315 (=10 x *) 315 (=10 x *) 70 x 45 15
225 225 300 x 75 19
EJB 13 & EJB 13A 504 (= 16 x *) 504 (= 16 x *) 70 x 45 15
450 450 300 x 150 19
EJB 14 504 (= 16 x *) 504 (= 16 x *) 70 x 45 15
450 450 300 x 150 19
*Max window dimension 70 x 45 mm

technor.com 13
ACCESSORIES UPON REQUEST

EJB.. SERIES IN COPPER-FREE ALUMINIUM

ILLUSTRATION DESCRIPTION FEATURES

WALL MOUNTING
Available for all EJB versions
BRACKETS

DRAIN / BREATHER
ECR-1 Valve
VALVE

EJB from 2 to 5: Length 56x38mm


AISI304 / AISI316L
STAINLESS STEEL EJB from 6 to 11: Length 60x45mm
HINGES
EJB from 12 to 14: Length 108x45mm

DOOR HANDLE C/W


EJB from 8 to 14
SCREWS

KNOB C/W SCREWS EJB up to 6

PL.. Series: Push buttons, mechanical


operators, signaling lamps
OPERATION HEADS
PSRC.. Series: Rotating switches

Standard shape: Rectangular


Standard dimensions (mm):
WINDOWS 70x45; 170x100; 270x100;
290x100; 300x75; 300x150
Customization is available upon request

NEW
HELPING CLOSING
SYSTEM C/W Available for all EJB versions
SCREWS

14 technor.com
ACCESSORIES UPON REQUEST

EJB.. SERIES IN GALVANIZED CARBON STEEL / AISI316L

ILLUSTRATION DESCRIPTION FEATURES

WALL MOUNTING
Available for all EJB versions
BRACKETS

DRAIN / BREATHER
ECR-1 Valve
VALVE

DOOR HANDLE C/W


EJB from 8 to 14
SCREWS

KNOB C/W SCREWS EJB up to 6

PL.. Series: Push buttons, mechanical


operators, signaling lamps
OPERATION HEADS

PSRC.. Series: Rotating switches

Standard shape: Rectangular

Standard dimensions (mm):


WINDOWS 70x45; 170x100; 270x100;
290x100; 300x75; 300x150

Customization is available upon request

NEW
HELPING CLOSING
SYSTEM C/W
Available for all EJB versions
SCREWS

technor.com 15
WORLD PRESENCE

NON CONTRACTUAL DOCUMENT AND PICTURES. All the indications appearing in this catalogue are indicative and could not constitute a commitment on our part. We reserve the right to alter specifications of our products without any prior notice in our efforts to continuously improve our products features.
MARECHAL
GMBH

MARECHAL
ELECTRIC

TECHNOR ITALSMEA

MELTRIC

MARECHAL ELECTRIC
CHINA
TECHNOR
MIDDLE EAST

MARECHAL ELECTRIC
ASIA

MARECHAL ELECTRIC
AFRICA

MARECHAL
AUSTRALIA

MARECHAL ELECTRIC S.A.S (Head Office)


5 avenue du chemin de Presles
94410 Saint-Maurice, FRANCE
Phone : +33 (0)1 45 11 60 00
e-mail: contact@marechal.com

GbBro16P_EJB series_2022-03 – A.0 – All rights reserved


Africa SADC area Australia Germany/Austria/Switzerland/ USA/Canada/Mexico
MARECHAL ELECTRIC AFRICA MARECHAL AUSTRALIA PTY LTD East Europe/Russia MELTRIC Corporation
(PTY) LTD. 20 A Technology Circuit MARECHAL GmbH 4765 W. Oakwood Park Drive
PO Box 13875 Witfield 1467 HALLAM VIC 3803 Im Lossenfeld 8 Franklin WI 53132, USA
Unit A1 Harvard Lane Australia D-77731 Willstätt-Sand Tel.: +1 414 433 2700
Aero Star Business Park Tel. : +61 (0)3 8786 2500 Germany e-mail: mail@meltric.com
Jet Park Road, Jet Park e-mail : sales@marechal.com.au Tel.: +49 (0)7852/91 96-0
South Africa e-mail: info.de@marechal.com
Tel.: +27 11 894 7226/7/8
e-mail: sales.za@marechal.com

Asia China Middle East


MARECHAL ELECTRIC Asia MARECHAL ELECTRIC (CHINA) TECHNOR Middle East DMCC TECHNOR ITALSMEA S.p.A.
Pte Ltd Co., Ltd Unit No.2101, Fortune Executive Via Italia 33,
9 Tagore Lane 11 North Xiangshui Road, Tower, Plot No T1 20060 Gessate (MILANO)
#01-05 9@Tagore West Dayawan District, Jumeirah Lakes Towers Italia
Singapore 787472 Huizhou.P.R.C P.O. Box 392054 Tel. : +39 02 95 00 151
Tel. : +65 6554 2722 Tel: +86 (0)752-5319536 Dubai, United Arab Emirates e-mail : sales@italsmea.com
e-mail: sales.asia@marechal.com e-mail: sales.cn@marechal.com Tel. : +971 4 362 1418
e-mail: sales.me@marechal.com

For any other country or area, please contact head office.

marechal.com technor.com

You might also like