Power System Stability
Power System Stability
Introduction
Transient stability limit is almost always lower than the steady state limit and
hence it is much important. Transient stability limit depends on the type of
disturbance, location and magnitude of disturbance.
Review of mechanics
1 2
K.E. = I Mega Joules (1)
2
1
K.E. = M Mega Joules (2)
2
The angular momentum M depends on the size of the machine as well as on its
type.
The Inertia constant H is defined as the Mega Joules of stored energy of the
machine at synchronous speed per MVA of the machine. When so defined, the
relation between the Angular Momentum M and the Inertia constant H can be
derived as follows.
Relationship between M and H
Stored energy in MJ
By definition H =
Machine' s rating in MVA
1 1
Further, K.E. = M MJ = M MJ = M x f MJ (4)
2 2
GH
M= MJ sec. / elec. rad. (5)
f
If the power is expressed in per unit, then G = 1.0 per unit and hence
H
M= (6)
f
While the angular momentum M depend on the size of the machine as well as on
its type, inertia constant H does not vary very much with the size of the machine,
The quantity H has a relatively narrow range of values for each class of machine.
Swing equation
The differential equation that relates the angular momentum M, the acceleration
power Pa and the rotor angle is known as SWING EQUATION. Solution of swing
equation will show how the rotor angle changes with respect to time following a
disturbance. The plot of Vs t is called the SWING CURVE. Once the swing curve
is known, the stability of the system can be assessed.
The flow of mechanical and electrical power in a generator and motor are shown
in Fig. 1.
Pe Pe
Te Ts
Generator Motor
Pm Pm
Ts Te
(a) Fig. 1 (b)
Consider the generator shown in Fig. 1(a). It receives mechanical power P m at the
shaft torque Ts -mover. It
delivers electrical power Pe to the power system network via. the bus bars. The
generator develops electromechanical torque Te in opposition to the shaft torque
Ts. At steady state, Ts = Te.
Assuming that the windage and the friction torque are negligible, in a generator,
Ta = Ts Te (7)
Pa = Ps Pe (8)
In case of motor
Ta = Te Ts (9)
Pa = Pe Ps (10)
d2
Thus M = Pa (12)
dt 2
Here = angular displacement (radians)
d
= angular velocity (rad. / sec.)
dt
d d2
= = = angular acceleration
dt dt 2
Now we can see how the angular displacement can be related to rotor angle .
x = vs t + d
where d is the displacement of the first object wrt the second as shown in Fig. 2.
x
vs Fig. 2
d
vs
Similarly in the case of angular movement, the angular displacement , at any
time t is given by
s t + (13)
d d
s + (14)
dt dt
d2 d2
2
= (15)
dt dt 2
d2
M 2
= Pa (16)
dt
d2 d
M 2
+D = Pa (17)
dt dt
Swing curve, which is the plot of torque angle vs time t, can be obtained by
solving the swing equation. Two typical swing curves are shown in Fig. 3.
d
0
. dt
0
0
t t
(a) (b)
Fig. 3
Swing curves are used to determine the stability of the system. If the rotor angle
reaches a maximum and then decreases, then it shows that the system has
transient stability. On the other hand if the rotor angle increases indefinitely,
then it shows that the system is unstable.
We are going to study the stability of (1) a generator connected to infinite bus
and (2) a synchronous motor drawing power from infinite bus.
jX I Thus E = E
V
I 1
Current I = [ E cos j E sin V ]
jX
E V
Electric output power Pe = Re [ V I ] = sin = Pmax
X
Consider a synchronous motor drawing power from infinite bus.
Xd XT
V jXI = E
V
E I V
-jXI
I
E
1
Thus E = E Current I = [ V ( E cos j E sin ) ]
jX
E V
Electric input power Pe = Re [ V I ] = sin = Pmax
X
Thus Swing equation for alternator is
d2
M = Pm Pmax
dt 2
Swing equation for motor is
d2
M = Pmax - Pm
dt 2
Notice that the swing equation is second order nonlinear differential equation
Equal area criterion
The accelerating power in swing equation will have sine term. Therefore the
swing equation is non-linear differential equation and obtaining its solution is not
simple. For two machine system and one machine connected to infinite bus bar,
it is possible to say whether a system has transient stability or not, without
solving the swing equation. Such criteria which decides the stability, makes use
of equal area in power angle diagram and hence it is known as EQUAL AREA
CRITERION. Thus the principle by which stability under transient conditions is
determined without solving the swing equation, but makes use of areas in power
angle diagram, is called the EQUAL AREA CRITERION.
From the Fig. 3, it is clear that if the rotor angle oscillates, then the system is
stable. For to oscillate, it should reach a maximum value and then should
d
decrease. At that point = 0. Because of damping inherently present in the
dt
system, subsequence oscillations will be smaller and smaller. Thus while
d
changes, if at one instant of time, = 0, then the stability is ensured.
dt
d
Let us find the condition for to become zero.
dt
The swing equation for the alternator connected to the infinite bus bars is
d2
M = Ps Pe (18)
dt 2
d
Multiplying both sides by , we get
dt
d2 d d 1 d d 2 d
M = (Ps Pe) i.e. M ( ) (Ps Pe) (19)
dt 2 dt dt 2 dt dt dt
Thus
d d 2 dt 2 (Ps Pe ) d d 2 2 (Ps Pe )
( ) ; i.e. ( ) On integration
dt dt d M d dt M
d
Before the disturbance occurs, 0 was the torque angle. At that time = 0. As
dt
d
soon as the disturbance occurs, is no longer zero and starts changing.
dt
Torque angle will cease to change and the machine will again be operating at
d
synchronous speed after a disturbance, when = 0 or when
dt
2 (Ps Pe )
d = 0 i.e.
0
M
(Ps Pe ) d = 0 (21)
0
If there exist a torque angle for which the above is satisfied, then the machine
will attain a new operating point and hence it has transient stability.
The machine will not remain at rest with respect to infinite bus at the first time
d
when = 0. But due to damping present in the system, during subsequent
dt
oscillation, maximum value of keeps on decreasing. Therefore, the fact that
has momentarily stopped changing may be taken to indicate stability.
Sudden load increase on Synchronous motor
- E jX V
+
E=V I ( jX )
I
E V
E Pe sin Pmax sin
X
I
P
Input power
Ps d b A2 e Changed output
A1
a Initial output
P0
0 s m
Fig. 4
P Input power
V
Ps d b A2 e Changed output
A1 E
Initial output I
P0 a
Fig. 4
0 s m
s 0.
Between a-b Output > Input; Rotating mass starts loosing energy resulting
d
Point b min s s
s
P Input power
V
Ps d b A2 e Changed output
A1 E
Initial output I
P0 a
0 s m
Between b-c Input > output; Rotating masses start gaining energy;
Point c Input s m
s m.
Point b max s s,
P
(Ps Pe ) d = 0 i.e. Pe d = Ps d Input power
0 0 0
From Fig. 4, Pe d 0 m
0
Ps d b A2 e Changed output
A1
m
and Ps d 0 m
a Initial output
0 P0
0 m 0 m 0 s m
Fig. 4
Subtracting 0 m from both sides of above equation, we get A2 = A1.
Thus for stability,
A2 = A1 (22)
Fig. 5 shows three different cases: The one shown in case a is STABLE. Case b
indicates CRITICALLY STABLE while case c falls under UNSTABLE.
P P P
A2
A2 Ps
Ps
A2 A1 A1
Ps
A1
P0 P0 P0
0 m 0 s m 0
s
Fig. 5
Note that the areas A1 and A2 are obtained by finding the difference
Solution
P
Referring to Fig. 6,
200
A2
for critical stability PS C D
A1 Electric Input
A2 = A1 power
50 B
200 0 = 50 i.e.
A E
50 -
0 = sin-1 0.25268 rad. 0 s S
200 Fig. 6
S = PS
Adding area ABCDEA to both A1 and A2 and equating the resulting areas
S
S 0 S 0 S 0 S i.e.
S S - S = 0.9682458
Consider the system shown in Fig. 7. The power angle diagrams corresponding
to stable and unstable conditions are shown in Fig. 8.
G Fig. 7
Electric Output
power (2 lines) A2
Electric Output
A2
power (1 line) PS A1
PS
A1
0 s m
Short circuit occurring in the system often causes loss of stability even though
the fault may be removed by isolating it from the rest of the system in a relatively
short time. A three phase fault at one end of a double circuit line is shown in Fig.
9(a) which can be reduced as shown in Fig. 9(b).
+ + +
+ Ei Eg Ei
- - -
Eg Ig
-
(a) (b)
Fig. 9
It is to be noted that all the current from the generator flows through the fault and
this current Ig lags the generator voltage by 900. Thus the real power output of the
generator is zero. Normally the input power to the generator remains unaltered.
ncrease indefinitely
because entire the input power will be used for acceleration. This may result in
unstable condition.
When the three phase fault occurring at one end of a double circuit line is
disconnected by opening the circuit breakers at both ends of the faulted line,
power is again transmitted. If the fault is cleared before the rotor angle reaches a
particular value, the system will remain stable; otherwise it will loose stability as
shown in Fig. 10.
Pre-fault output
power
Post-fault output
power
A2 A2 A2
PS Input power
A1 A1 A1
0 C m 0 CC m 0 C
During fault
output power
C< CC C> CC
Note that the areas A1 and A2 are obtained by finding difference between INPUT
and OUTPUT.
When a three phase fault occurs at some point on a double circuit line, other than
on the extreme ends, as shown in Fig. 11(a), there is some finite impedance
between the paralleling buses and the fault. Therefore, some power is transmitted
during the fault and it may be calculated after reducing the network to a delta
connected circuit between the internal voltage of the generator and the infinite
bus as shown in Fig. 11(b).
Xb
+ + +
Xa Xc
+ Em Eg Em
Eg - - -
-
(a) (b)
Fig. 11
Eg Em
Power transmitted during the fault = sin (23)
Xb
Stable, critically stable and unstable conditions of such systems are shown:
C < CC;
Post-fault output power
A2 = A1; A2
Input power
STABLE
A1
During-fault
output power
0 C m
Pre-fault output power
C = CC; A2
Input power
A2 = A1;
A1
CRITICALLY During-fault
STABLE output power
0 CC m
A2 < A1;
A2 Input power
UNSTABLE
A1
During-fault
output power
0 C
Example 2
In the power system shown in Fig. 12, three phase fault occurs at P and the faulty
line was opened a little later. Find the power output equations for the pre-fault,
during fault and post-fault conditions.
0.16 0.16
Xg = 0.28 0.24 0.16
G
P
Eg
'
1.25 p.u. x
V 1.0 p.u.
0.24
0.16 0.16
Values marked are p.u. reactances
Solution Fig. 12
Pre-fault condition
0.16
0.56 0.72
0.28 0.56 + + +
1.0 1.25 1.0
+
1.25 - - -
-
1.25 x 1.0
Power output Pe = sin 1.736 sin
0.72
During fault condition:
0.16 0.56
0.56
0.16 0.4
2.99
0.08 0.2 0.16
0.28
+ 1.25 1.0
+
1.25 0.057 1.0
- -
1.25 x 1.0
Power output Pe = sin 0.418 sin
2.99
Post-fault condition:
0.16
0.56
1.0
0.28 +
1.0 1.25 1.0
+
1.25 -
-
1.25 x 1.0
Power output Pe = sin 1.25 sin
1.0
Here
Pm1
Consider the power Pre-fault
angle diagrams output power
shown in Fig. 13
Pm3
Post-fault
A2 output power
Pm 1 = Ps PS
0 Input power
Pm2
Pm 3 sin = Ps A1
s
During-fault
output power
CC 0 s CC m - s
Area A2 = Area A1
PS ( m 0 ) Pm 3 cos m Pm 2 cos 0
cos CC
Pm 3 Pm 2
1
PS ( m 0 ) Pm3 cos m Pm2 cos 0
CC cos [ ] (26)
Pm3 Pm2
1 PS 1 PS
0 sin ( ) m sin ( ) (27)
Pm1 Pm 3
Example 3
In the power system described in the previous example, if the generator was
delivering 1.0 p.u. just before the fault occurs, calculate CC .
Solution
PS ( m 0 ) Pm 3 cos m Pm 2 cos 0
cos CC
Pm 3 Pm 2
In order to specify a circuit breaker of proper speed, the engineer must know the
CRITICAL CLEARING TIME, which is the time taken by the machine to swing from
its initial position to its critical clearing angle. If the Critical Clearing Angle (CCA)
is determined by the equal area criterion, then to determine corresponding
Critical Clearing Time (CCT), the swing curve for the sustained faulted condition
is required.
The step by step method of obtaining swing curve, using hand calculation is
necessarily simpler than some of the methods recommended for digital
computer. In the method suitable for hand calculation,the period of interest is
divided into several short intervals. The change in the angular position of the
rotor during a short interval of time is computed by making the following
assumptions.
1. The accelerating power Pa computed at the beginning of an interval is
constant from the middle of the proceeding interval to the middle of the
interval considered.
d
2. is constant throughout any interval at the value computed at the
dt
middle of the interval.
d
Above assumptions are made to approximate continuously varying P a and as
dt
stepped curve. Fig. 14 will help in visualizing the assumptions. The accelerating
power is computed for the points enclosed in circles, at the beginning of n-1, n
and n+1 th intervals. The step of Pa in the figure results from assumption 1.
d d
( = - s), the excess of angular velocity over the synchronous
dt dt
angular velocity is shown as a step curve that is constant throughout the interval,
at the value computed at the midpoint.
3 1
Between the ordinates n - and n -
2 2
caused by constant angular acceleration (caused by constant Pa).
Pa
Pa (n 2)
Pa (n 1)
Pa (n)
n-2 n-1 n t
n th interval
n - 1 th interval
(n 1/2)
(n 3/2)
n 3/2 n 1/2 t
n
n-1
Fig. 14 n-1
n-2
n-2 n-1 n t
The is
1 3
(n - )- (n - ) = Constant angular acceleration x time duration
2 2
Pa ( n 1) d2 1
= ( Because = Pa ) (28)
M dt 2 M
x time
duration. Thus
1
(n) (n - (29)
2
3
(n 1) (n - (30)
2
1 3 Pa ( n 1) 2
Therefore (n) - (n 1) (n - )- (n - =
2 2 M
Pa ( n 1) 2
Thus (n) (n 1) + (31)
M
Pa ( n 1) 2
(n) (n 1) + (31)
M
Equation (31) shows that the change in torque angle during a given interval is
equal to the change in torque angle during the proceeding interval plus the
( t)2
accelerating power at the beginning of the interval X .
M
Pa ( n 1) 2
where (n) (n 1) + (33)
M
The above two equations are known as Recursive equations using which
approximate swing curve can be obtained.
The process of computation is now repeated to obtain P a (n) (n+1) (n+1). The
solution in discrete form is thus carried out over the desired length of time
normally 0.05 sec. Greater accuracy of solution can be achieved by reducing the
time duration of interval.
Any switching event such as occurrence of a fault or clearing of the fault causes
discontinuity in the accelerating power P a. If such a discontinuity occurs at the
beginning of an interval then the average of the values of P a just before and just
after the discontinuity must be used.
Thus in computing the increment of angle occurring during the first interval after
a fault is applied at time t = 0, becomes
1 - + ( t) 2
1 = 0 + (Pa 0 + Pa 0 )
2 M
2
1 + ( t)
= Pa 0 (Because Pa 0- = 0)
2 M
If the discontinuity occurs at the middle of an interval, no special procedure is
needed. The correctness of this can be seen from Fig. 15.
n th interval n th interval
n - 1 th interval n - 1 th interval
Fig. 15
Example 4
fault occurs at the mid point of one of the transmission lines. Obtain the swing
curve over a period of 0.5 sec. if the fault is sustained.
0.2 p.u.
GH 1.0 x 2.52 4
Angular momentum M = 2.8 x 10 sec2 / elec. deg.
180 f 180 x 50
( t) 2 (0.05)2 x 10 4
Let us choose Then = 8.929
M 2.8
Recursive equations are
(n) (n 1) (n)
1.1 x 1.0
Pre fault: X = 0.45 p.u.; Pe = sin
0.45
During fault:
0.2
0.2
0.1 0.1
0.35 + 0.35 +
+ 1.0 + 0.1 0.1
1.1 -
- - -
1.25
Converting the star 0.35, 0.1 and 0.2 as delta
1.1 1.0
1.1 x 1.0
Pe = sin
1.25
Initial calculations:
( t) 2
1 = 0 + Pa average x = 0.288 x 8.929 = 2.570
M
= 24.210
0.50 159.65
Swing
shown in Fig. 16.
Fig. 16
Example 5
Solution
From the previous example: Ps = 0.9; Pm1 = 2.44 and Pm2 = 0.88
1.1 x 1.0
X = 0.55 p.u; Pe = sin 2.0 sin
0.55
PS ( m 0 ) Pm 3 cos m Pm 2 cos 0
cos CC
Pm 3 Pm 2
0 0 = 0.3778 rad.
CC = 118.630
Fig. 17
Let us first consider solution of first order differential equation. Later we shall
extend it for solving a set of first order DE. The swing equation is a second order
DE which can be written as two first order DE and solution can be obtained using
dx
f ( t, x ) (34)
dt
dx
x 1(0) = x 0 + |0
dt
(0)
Thus (t 1, x 1 ) is the first estimated point of (t 1, x 1). Second and the final
estimate of x 1 is calculated as
1 dx dx (0)
x1 = x0 + ( |0 + |1 ) (36)
2 dt dt
dx (0) dx
where |1 is the value of computed at (t 1, x 1(0)). Thus the next point
dt dt
tn=tn 1 (37)
dx
x n(0) = x n 1 + |n 1 (38)
dt
dx (0) dx
Compute |n which is computed at (t n, x n(0)). (39)
dt dt
1 dx dx (0)
Then xn = xn-1 + ( |n - 1 + |n (40)
2 dt dt
Same procedure can be extended to solve a set of two first order DE given by
dx dy
= f1 (t, x, y) and = f2 (t, x, y)
dt dt
tn=tn 1
dx
x n(0) = x n 1 + |n 1
dt
dy
y n(0) = y n 1 + |n 1
dt
dx (0) dx
Compute |n which is computed at (t n , x n(0), y n(0)) and
dt dt
dy (0) dy
|n which is computed at (t n , x n(0), y n(0))
dt dt
1 dx dx (0)
Then x n = x n - 1 + ( |n - 1 + |n
2 dt dt
1 dy dy (0)
yn = yn-1 + ( |n - 1 + |n
2 dt dt
We know that the swing equation is
d2
M = Pa
dt 2
H
M=
f
d2 f f f
2
= Pa ( Ps Pe ) = K ( Ps Pe ) where K =
dt H H H
d2
The second order DE 2
= K ( Ps Pe )
dt
d
s
dt
d
= K ( Ps Pe )
dt
d d
Note that generally of the form = f1
dt dt
d d
generally of the form = f2
dt dt
As soon as disturbance occurs, electric network changes and the expression for
electric power Pe
Pe shall be computed by the said expression.
The whole procedure can be carried out until t reaches the time upto which
transient stability analysis is required.
Example 6
An alternator rated for 100 MVA supplies 100 MW to an infinite bus through a line
of reactance 0.08 p.u. on 100 MVA base. The machine has a transient reactance of
0.2 p.u. and its inertia constant is 4.0 p.u. on 100 MVA base. Taking the infinite
bus voltage as reference, current supplied by the alternator is ( 1.0 j 0.6375 )
p.u.
Calculate the torque angle and speed of the alternator for a period of 0.14 sec.
when there is a three phase fault at the machine terminals and the fault is cleared
Solution
100 MVA
Ps = 100 MW
H=4 I 00
E = ( 1.0 + j0) + j 0.28 ( 1.0 j 0.6375) = 1.1785 + j 0.28 = 1.2113 13.36510 p.u.
0
= 0.2333 rad.
Shaft power Ps = 100 MW = 1.0 p.u. This remains same
d2 f 50
2
= ( Ps Pe ) = (1 Pe ) 39.2699 ( 1 - Pe )
dt H 4
d
314.1593 Initial point is:
dt
d
= 39.2699 ( 1 Pe )
dt
d
= 39.2699 ( 1 0 ) = 39.2699
dt
x 0.02 ) = 0.2333 rad.
d
= 314.9447 314.1593 = 0.7854
dt
d
= 39.2699 ( 1 0 ) = 39.2699; Thus
dt
1
( 0 + 0.7854 ) x 0.02 = 0.24115 rad.
2
1
( 39.2699 + 39.2699 ) x 0.02 = 314.9447 rad. / sec.
2
d d
314.1593 39.2699 (1 Pe )
dt dt
d
= 314.9447 314.1593 = 0.7854
dt
d
= 39.2699 ( 1 0 ) = 39.2699
dt
= 0.24115 + ( 0.7854 x 0.02 ) = 0.2569 rad.
= 314.9447 + ( 39.2699 x 0.02 ) = 315.7301 rad. / sec.
Second estimate: First estimated point is:
d
= 315.7301 314.1593 = 1.5708
dt
d
= 39.2699 ( 1 0 ) = 39.2699; Thus
dt
1
(0.04) = 0.24115 + ( 0.7854 + 1.5708 ) x 0.02 = 0.2647 rad.
2
1
(0.04) = 314.9447 + ( 39.2699 + 39.2699 ) x 0.02 = 315.7301 rad. / sec.
2
Calculations can be repeated until the fault is cleared i.e. t = 0.1. The results are
tabulated. Thus
Once the fault is cleared, reactance between internal voltage and the infinite bus
is 0.28 and thus generator out put is;
1.2113 x 1.0
Pe = sin 4.3261 sin
0.28
d
= 39.2699 ( 1 4.3261 sin 0.4297 rad. ) = - 31.5041
dt
d
= 39.2699 ( 1 4.3261 sin 0.50825 rad. ) = - 43.4047; Thus
dt
1
(0.12) = 0.4297 + ( 3.9276 + 3.2975 ) x 0.02 = 0.50195 rad.
2
1
(0.12) = 318.0869 + ( - 31.5041 - 43.4047 ) x 0.02 = 317.3378 rad. / sec.
2
Complete calculations are shown in the Table:
d d
314.1593; 39.2699 (1 Pe ); Pe = 0 for t < 0.1 and Pe = 4.3261 sin
dt dt
0.02 0.2412 314.9447 0.7854 39.2699 0.2569 315.7301 1.5708 39.2699 0.2647 315.7301
0.04 0.2647 315.7301 1.5708 39.2699 0.2961 316.5155 2.3562 39.2699 0.304 316.5155
0.06 0.304 316.5155 2.3562 39.2699 0.3511 317.3009 3.1416 39.2699 0.359 317.3009
0.08 0.359 317.3009 3.1416 39.2699 0.4218 318.0863 3.927 39.2699 0.4297 318.0869
-
0.10 0.4297 318.0869
+
0.10 0.4297 318.0869 3.9276 -31.504 0.5083 317.4568 3.2975 -43.405 0.502 317.3378
0.12 0.502 317.3378 3.1785 -42.468 0.5655 316.4884 2.3291 -51.761 0.557 316.3955
Fourth order Runge Kutta (RK) method is one of the most commonly used
methods of solving differential equation.
dx
f ( t, x )
dt
tm+1 = tm + h
1
xm+1 = xm + ( k1 + 2 k2 + 2 k3 + k4) where
6
h k
k 1 = f ( t m, x m ) h k2 = f ( t m + ,xm+ 1)h
2 2
h k
k3 = f ( t m + ,xm+ 2 )h k4 = f ( t m + h, x m + k3 )
2 2
Note that in this method, the function has to be evaluated four times in each step.
Same procedure can be extended to solve a set of first order DE such as
dx dy
f1 ( t , x , y ) and f2 ( t , x , y )
dt dt
1 1
xm+1 = xm + ( k1 + 2 k2 + 2 k3 + k4) ym+1 = ym + 1 2 3 4)
6 6
where
k1 = f1 ( t m, xm, ym 1 = f2 ( t m, x m, ym ) h
h k h k
k2 = f1 ( t m + , xm + 1 , ym + 1 2 = f2 ( t m + , xm + 1 , ym + 1 ) h
2 2 2 2 2 2
h k h k
k3 = f1 ( t m + , xm + 2 , ym + 2 3 = f2 ( t m + , xm + 2 , ym + 2 ) h
2 2 2 2 2 2
k4 = f1 ( t m + h, xm + k3, ym 3 4 = f2 ( t m + h, xm + k3, ym 3 )h
We know that the swing equation can be written as
d
s
dt
d f
= K ( Ps Pe ) where K =
dt H
th
The initial solution point is ( order RK method is used, k1,
1, k2 2, k3 3, k4 4 are computed and then the next solution point is obtained as
Consider the problem given in previous example and solve it using 4 th order RK
method.
Solution
d
314.1593 Initial point is:
dt
d
= 39.2699 ( 1 Pe )
dt
During the first switching interval t = 0+ to 0.1 sec. electric output power Pe = 0.
d d
314.1593 39.2699 (1 Pe ) Initial point is:
dt dt
1
[ 0 + 2 (0.007854) + 2 (0.007854) + 0.0157 ] = 0.24115 rad.
6
1
[ 0.7854 + 2 (0.7854) + 2 (0.7854) + 0.7854 ]
6
1 = 2 3 4 = 0.7854
d d
314.1593 39.2699 (1 Pe )
dt dt
Latest point is:
)
1
[ 0.01571 + 2 (0.02356) + 2 (0.02356) + 0.03142 ] = 0.2647 rad.
6
1
+ [ 0.03142 + 2 (0.03927) + 2 (0.03927) + 0.04712 ] = 0.304 rad.
6
1
[ 0.04712 + 2 (0.05498) + 2 (0.05498) + 0.06283 ] = 0.359 rad.
6
d d
314.1593 39.2699 (1 Pe )
dt dt
1
1) = 0.359 + [ 0.06283 + 2 (0.07069) + 2 (0.07069) + 0.07854 ] = 0.4297 rad.
6
At t = 0.1 sec., the fault is cleared. As seen in the previous example, for t 0.1
sec., electric power output of the alternator is given by Pe
d d
314.1593 39.2699 (1 Pe )
dt dt
1
+ [ 0.07854 + 2 (0.07224) + 2 (0.07104) + 0.06373 ] = 0.5012 rad.
6
1
+ [ - 0.63 - 2 (0.7504) - 2 (0.7406) - 0.8456 ]= 317.3434 rad. / sec.
6
d d
314.1593 39.2699 (1 Pe )
dt dt
)
Latest point is:
k1 = (317.3434 314.1593) x 0.02 = 0.06368
d. / sec.
Pe = 4.3261 sin (0.5012 rad.) = 2.0786
1
+ [ 0.06368 + 2 (0.05521) + 2 (0.05427) + 0.04511 ] = 0.5558 rad.
6
1
+ [- 0.8471- 2 (0.9411)- 2 (0.9287)- 1.0064 ]= 316.4112 rad. / sec.
6
Smaller value of H:
Pa ( n 1) 2
(n) (n 1) +
M
the angular swing of the machine in any interval is larger. This will result in
lesser CCT and hence instability may result.
Larger value of Xd :
Pre-fault output
power
Post-fault
output power
Input power
During-fault
output power
0 m m
0
Fig. 17
The net result is that increased value of constrains
a machine to swing though a smaller angle from its original position before it
reaches the critical clearing angle and the possibility of instability is more.
Thus any developments which lower the H constant and increase the
transient reactance of the machine cause the CCT to decrease and lessen
the possibility of maintaining the stability under transient conditions.