SCD6000 - IO Specification - PSS 31H-8K1
SCD6000 - IO Specification - PSS 31H-8K1
SCD6000 - IO Specification - PSS 31H-8K1
Process Automation
System
Product Specifications
PSS 31H-8K1
OVERVIEW
The Foxboro Evo™ Input/Output Modules are used 4 Channel Analog Output Module
with SCD5200/SC6000. They provide a means for Digital Output Module.
monitoring and control of Industrial plants. Field Interrogation Power Supply (FIPS) options for
digital inputs include nominal 24 V to 129 V,
INTRODUCTION selectable via jumper settings.
The Foxboro Evo™ Input/Output Modules provide A 1 kV isolation option is available for the analog
connection of wide range of field equipment and inputs on the Analog Digital Input (ADI) Module and
devices to the SCD5200/SCD6000 Station 20 Channel Analog Input Module.
Computing Devices for monitoring and control of
Latched and non-latched relay options are available
industrial plant.
on Digital Outputs.
The range of I/O modules comprises:
Key features of the range include:
Multi I/O Module
Opto-isolated digital inputs
Analog Digital Input (ADI) Module
Relay-isolated digital outputs
20 Channel Analog Input Module
High isolation optional on analog inputs
PSS 31H-8K1
Page 2
Analog outputs individually isolated The one I/O card file and five I/O card file options
High security “check-before-operate” control (Refer PSS 31H-8G1 SCD5200 Architecture
outputs Overview) aim to meet the needs of small I/O and
Sequence of Events resolution of 1 ms space limited applications.
High resolution analog inputs (12 bit plus sign) The Multi I/O Module provides the highest I/O density
and analog outputs (12 bit) of combined digital input, analog input, and digital
Digital inputs provide Status, Momentary Change output (24 DI, 6 AI, and 6 or 8 DO). The ADI Module
Detect, Accumulator, and Sequence of Events (32 DI and 4 AI) provides for high density input-only
Software configurable configurations.
• Digital outputs as individual variable pulse or Where greater flexibility of configuration, connection,
latched, trip/close or raise/lower pairs, and/or isolation is required, the Analog Input
multiple relay variable pulsed or latched Modules, Analog Output and Digital Output Modules
• Analog output range and offset, open loop may be combined with the high density Multi I/O and
detection ADI Module types.
High transient and surge immunity As the modular design of the SCD5200/SCD6000
EMC emission and immunity to CE standards for allows any mix of I/O modules, a wide range of
industrial equipment number and type of I/O connections may be
Analog current loop resistors integral to terminal economically accommodated.
boards The I/O module range is designed and tested for
Enclosed insulated terminal assemblies for safety application in the most demanding industrial
Removable terminal assemblies allow card environments. Compliance standards include
replacement without disconnecting field wiring European Community (CE) Electro-Magnetic
Run/fail status front panel indicator and database Compliance (EMC) immunity and emissions, transient
health point and surge immunity, isolation, and electrical safety.
High density for compact connection of large I/O CE Mark certification and CE compliant installation
count guidelines are available.
Range of I/O combinations provides connection
Software complements the I/O module hardware.
flexibility at minimum cost.
Momentary Change Detect, Sequence of Events,
Through flexible I/O configurations and options, the and Accumulator functionality is provided for digital
range of I/O Modules is matched to a wide range of inputs. Digital outputs are highly secure, incorporate
applications. “check before operate” execution, and may be
The combination of a ten I/O module capacity file, configured as variable pulse, latch, trip/close pairs, or
integrated local network capability, and high I/O multiple relay groups (set point).
density modules can accommodate large to very
large I/O counts while providing excellent value for
money.
PSS 31H-8K1
Page 3
FUNCTIONAL DESCRIPTION
NOTE
Analog/Digital Input Modules The Analog/Digital Input Module is available
The Analog/Digital Input Module provides flexible in two variants to support two different sizes
data collection and input monitoring facilities through of wires in terminal assembly. The size of the
32 individually configured digital inputs and four high- wire is based on insulation requirements,
resolution analog inputs. that is, thicker wires are required to support
The Analog/Digital Input Module has 1 kV isolation on higher insulation requirements.
the analog inputs. SY-0399160 accommodates wire sizes of
The module supports digital inputs over the nominal 0.5 sq.mm and SY-0399222 accommodates
ranges of 24 V to 48 V and 48 V to 129 V. A jumper wire sizes of 1sq.mm.
for each digital input can be individually set to select The thickest wire size supported for a fully
either of these ranges. The factory default setting is
populated IO count [45 wires] is 0.75 sq.mm
for 48 V to 129 V operation. for the SY-0399160 and 1.0 sq.mm for the
WARNING SY-039922. In all other respects, SY-
0399222 is identical to SY-0399160.
In this module, the jumpers J3 to J34 must
be removed when using digital input voltages Digital Inputs
in the range 60–129 V (dc) or 72–144 V RMS The digital input subsystem processes 32 contact
(ac). Failure to do so may result in permanent inputs. The module optically isolates, filters, and
damage to the module and possible electric protects against surge transients. It interfaces the
hazard. contact state to the on-board microprocessor.
Features Digital input circuits employ contact bounce
Key features of the ADI Modules include: elimination circuitry, which rejects noisy contact
transitions until the input signal has been stable for
Removable plug-connected terminal board
2 ms.
Plug in current loop resistors
Software configurable digital inputs The digital inputs are grouped into four groups of
Optical isolation on digital inputs eight, with a common terminal for each group. Each
Galvanic isolation on analog inputs group accepts common positive or common
Common voltage inputs (+VE or –VE) that are negative.
selectable in groups of eight digital inputs Digital inputs status is provided by scanning every
Digital input bounce elimination circuitry millisecond. Sequence of Events with one millisecond
Individually configurable chatter filters resolution time-tagging is available.
RUN/FAIL LED indicator.
In addition, each of the digital inputs supports
accumulator and Momentary Change Detection
functionality.
PSS 31H-8K1
Page 4
Features For the 10A relay modules, the relays are mounted
Key features of 10A Digital Output Modules include: on the logic board. The plug-in terminal assembly
carries screw terminals for loop termination of heavy
Eight independent single pole normally open
gauge wire.
digital outputs
Two power relays in series provide high current
Multi Input/Output Module
DC inductive load break capacity
Configurable output types (latch, variable pulse, The Multi I/O Module provides a cost effective
trip/close pairs, raise/lower pairs, and multiple solution for applications utilizing a combination of
relays setpoint) status inputs, analog inputs and control outputs.
High security control output logic with two pass The Multi I/O Module combines the technology of the
‘check before operate’ and one-of-N check on Analog Digital Input Module and the 12 Digital Output
paired outputs Module within one module:
Built-in hardware and software monitoring of 24 Digital Inputs
control operations 6 Analog Inputs
Removable plug-connected termination 8 mini pilot relay or 6 paired pilot relay outputs.
assembly
Variants of the Multi I/O Module are:
Control output duration is individually
configurable 129 V 8 Mini Pilot Relay
Screw terminals for loop connection of up to 16 48 V 8 Mini Pilot Relay
gauge cable. 24 V 8 Mini Pilot Relay
RUN/FAIL LED indicator 129 V 6 Paired Pilot Relay
Module operating condition available as database 48 V 6 Paired Pilot Relay
point. 24 V 6 Paired Pilot Relay.
Digital Inputs
• 6 analog inputs
• Plug-in current loop resistors
• 12 bits plus sign analog-to-digital converter
• ±2 V range
• Continuous automatic input
calibration/check
Control Outputs
M U LT I I / O M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S
M ULT I I / O M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S ( C O N T. )
M ULT I I / O M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S ( C O N T. )
PRODUCT SAFETY
This product complies with the U.S. Standard for Safety UL 61010-1 - Safety requirements for electrical
equipment for measurement, control, and laboratory use - PART 1: GENERAL REQUIREMENTS - Edition 2 -
Revision Date 2008/10/28 and CSA C22.2 NO. 61010-1 - Safety requirements for Electrical equipment for
measurement, control, and laboratory use.
PSS 31H-8K1
Page 12
2 0 C H A N N E L A N A L O G I N P U T M O D U L E ( I S O L AT E D ) F U N C T I O N A L S P E C I F I C AT I O N S
PRODUCT SAFETY
This product complies with the U.S. Standard for Safety UL 61010-1 - Safety requirements for electrical
equipment for measurement, control, and laboratory use - PART 1: GENERAL REQUIREMENTS - Edition 2 -
Revision Date 2008/10/28 and CSA C22.2 NO. 61010-1 - Safety requirements for Electrical equipment for
measurement, control, and laboratory use.
PSS 31H-8K1
Page 13
A NA L O G / D I GI TAL I N P U T M OD U L E F UN C T I O N AL S PE CI F I CAT I ON S
A N A L O G /D I G I TA L I N P U T M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S ( C O N T I N U E D )
PRODUCT SAFETY
This product complies with the U.S. Standard for Safety UL 61010-1 - Safety requirements for electrical
equipment for measurement, control, and laboratory use - PART 1: GENERAL REQUIREMENTS - Edition 2 -
Revision Date 2008/10/28 and CSA C22.2 NO. 61010-1 - Safety requirements for Electrical equipment for
measurement, control, and laboratory use.
PSS 31H-8K1
Page 15
1 2 C H A N N E L D I G I TAL O U T P U T M OD U L E S F U N C T I O N A L S P E C I F I C AT I O N S
8 C H A NN E L DI GI TAL O UT P U T M O D U L E S F U N CT I ON A L S PE CI F I CAT I O N S
4 C H A N N E L A N A L O G O U T PU T M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S
PRODUCT SAFETY
This product complies with the U.S. Standard for Safety UL 61010-1 - Safety requirements for electrical
equipment for measurement, control, and laboratory use - PART 1: GENERAL REQUIREMENTS - Edition 2 -
Revision Date 2008/10/28 and CSA C22.2 NO. 61010-1 - Safety requirements for Electrical equipment for
measurement, control, and laboratory use.
PSS 31H-8K1
Page 18
P H Y S I C A L S P E C I F I C AT I O N S
Input/Output Modules share the same physical and (Electrobus) via a DIN 41612 connector and are
environmental specifications. double Eurocard size (233.4 mm x 149 mm). DIN
Physical Size 41612 connectors are also fitted to the front edge of
the PCB to provide connection to the terminal board
Each plug-in module requires frame space of 35 mm.
assembly.
Modules are assemblies of one or more printed circuit
boards. These modules plug into a backplane
E N V I R O N M E N TA L S P E C I F I C AT I O N S
Operating Temperature
STANDARD
0°C to +60°C (32°F to 140°F)
Humidity
10 to 95% (non-condensing)
O R D E R I N G I N F O R M AT I O N