ABB Circuit Breaker Selectivity
ABB Circuit Breaker Selectivity
ABB Circuit Breaker Selectivity
May 2007
Selectivity techniques
Time-current selectivity ........................................... 7 ACB-ACB Selectivity
Current selectivity .................................................... 8 Time selectivity ...................................................... 28
Time selectivity ........................................................ 9 Zone selectivity between Emax............................. 29
Energy selectivity................................................... 10 Directional time selectivity ..................................... 32
Zone selectivity ..................................................... 11 Directional zone selectivity .................................... 34
Appendix A:
How to obtain selectivity with MV/LV selectivity ................................................... 40
1
Technical Application Papers
Example
The following two circuit-breakers are considered:
On the supply side T4N250 PR221 In250 (Icu=36kA)
On the load side S294 C 100 (Icu=15kA)
T4N 250 PR221DS-LS/I
From the “Coordination Tables” publication it can be seen that there
is total selectivity (T) between the two circuit-breakers.
This means that there is selectivity up to 15kA, i.e. the
lower of the two Icu values.
S 294 C 100
Obviously, the maximum possible short-circuit current at the point
of installation of the S294 C 100 circuit-breaker will be less than
or equal to 15kA.
Tmax T4 - S290 @ 400/415 V
Now the following two circuit-breakers are considered:
On the supply side T4N250 PR221 In160 (Icu=36kA) Supply T4
On the load side S294 C 100 (Icu=15kA) side
Version N,S H,L,V
Release TM, M EL
From the “Coordination Tables” publication it can be seen that the
selectivity value is Is=12kA between the two circuit-breakers. Iu [A] 250 320 250 320
This means that, if the maximum prospective short-circuit current Load-side Charact. Icu [kA] In [A] 160 200 250 320 160 250 320
80 5 11 T T T T T
on the load-side of the S294 C 100 circuit-breaker is less than 12kA, C-K
100 5* 8 T T 12 T T
there will be total selectivity, whereas if the short-circuit current has
S290 C 15 125 8* 12 T T T
a higher value, there will be partial selectivity, i.e. only for the faults
80 5 11 T T T T T
with a current below 12kA, whereas for faults between 12 and 15 kA D
100 8 T T 12 T T
non-tripping of the supply-side circuit-breaker is not guaranteed.
* Value valid with magnetic only circuit-breaker on the suppy side
Main definitions
Overload zone – Short-circuit zone By “short-circuit zone” one means the ranges of current
values, and therefore the relative part of the trip curves
A theoretical outline of selectivity
For the purposes of the selectivity analysis made in this of the circuit-breaker, which are 8-10 times higher than
publication, the concepts of “overload zone” and “short- the rated current of the circuit-breaker.
circuit zone” are introduced.
This is the zone in which the magnetic protection for
By “overload zone” one means the ranges of current thermomagnetic releases or protections S, D and I for
values, and therefore the relative part of the circuit- electronic releases are normally called on to intervene.
breaker trip curves coming between the rated current of
the circuit-breaker itself and 8-10 times this value. These current values usually correspond to a fault on the
supply circuit. This event is most unlikely than a simple
This is the zone in which the thermal protection for overload.
thermomagnetic releases and protection L for electronic
releases are normally called on to intervene.
103s 103s
102s 102s
10s 10s
1s 1s
10-1s 10-1s
10-2s 10-2s
tA
A
tB
IA=IB
B
IA=IB
tA
tB
A
IA=IB+Iloads
B
IB IA
A tA
IA=(IB+Iloads)/n tB
Where: I I
A B
IB is the overcurrent which passes through circuit-breaker B
IA is the overcurrent which passes through circuit-breaker A
Iloads is the sum of the currents which, during normal operation, is consumed by the loads (excluding B) supplied by the supply-side
circuit-breaker A. This sum can, if necessary, be corrected with suitable contemporaneity and use factors
n is the number of circuit-breakers placed in parallel on the power supply side.
* These formulas do not take into account the different phase displacement of the currents or any asymmetry of the circuit; the first two formulas are
however conservative and the third one is acceptable when the two supply circuits are equal.
Selectivity techniques
This section describes the different selectivity techniques and their area of application.
A theoretical outline of selectivity
In the overload zone with the protections in play, time-current type selectivity is usually realised.
In the short-circuit zone with the protections in play, various selectivity techniques can be used. In particular, the
following will be illustrated in the paragraphs below:
current selectivity
time selectivity
energy selectivity
zone selectivity.
After an initial theoretical description of the different selectivity techniques, the selectivity technique which can be
used appropriately for the different types of circuit-breakers will then be analysed.
Operatively speaking
With regard to the tolerances, ABB SACE makes the trip curves of their releases available in the technical catalogues and in the DOCWin
software. In particular, in the curve module of the DOCWin software, the curves of both the electronic and thermomagnetic releases include
the tolerances. A release trip is therefore shown by two curves, one which indicates the highest trip times (top curve), and the other which
indicates the most rapid trip times (bottom curve).
For a correct analysis of selectivity, the worst conditions must be considered, i.e.:
- the supply-side circuit-breaker trips according to its own bottom curve
- the load-side circuit-breaker trips according to its own top curve
With regard to the real currents circulating in the circuit-breakers:
- if the two circuit-breakers are passed through by the same current, it is sufficient for there to be no overlapping between the curve of
the supply-side circuit-breaker and the curve of the load-side circuit-breaker;
- if the two circuit-breakers are passed through by different currents, it is necessary to select a series of significant points on the time
current curves and check that the trip times of the supply-side protection are always higher than the corresponding times of the load
side protection.
In particular, in the case of circuit-breakers equipped with electronic releases, since the trend of the curves is at I2t=const, to carry out
the check correctly, it is sufficient to examine two current values:
1.05 x I11 of the supply-side circuit-breaker (value below which the supply-side protection never intervenes)
1.20XI3 (or I2)2 of the load-side circuit-breaker (value above which the load-side protection certainly trips with the protections against
short-circuit)
Time-current Selectivity
1.05 x I1 of the supply-side circuit-breaker
Assuming IA =1.05xI1, with reference to what has been said about A
103s
the real currents which circulate in the circuit-breakers, the IB current
is obtained on the load side.
The trip times of the two devices are obtained from the time-current 102s
curves.
B
10s
1s
A
10-1s
B
10s
If the following is true for both the points considered:
tA>tB 1s
then selectivity in the overload zone is guaranteed.
0.1s
In the figure at the side an absorption of current from other loads has been
assumed 0.1kA 1kA 10kA 100kA
1 1.05 is the value for minimum definite non-intervention dictated by the Standard (IEC60947-2). For some types of circuit-breakers this value could vary
(see the technical catalogue for further information).
2 1.2 is the value for maximum definite intervention for protection against short-circuit dictated by the Standard (IEC60947-2). For some types of circuit-
breakers this value could be lower (see the technical catalogue for further information).
Selectivity techniques
Current selectivity cables). The time-current trip curves of the devices are
normally used for this study.
A theoretical outline of selectivity
This type of selectivity is based on the observation that It is intrinsically fast (instantaneous), easy to realise and
the closer the fault point is to the power supply of the economical.
installation, the higher the short-circuit current is. It is
therefore possible to discriminate the zone the fault However:
occurred in by setting the instantaneous protections to – the ultimate selectivity current is usually low and
different current values. therefore selectivity is often only partial;
– the setting level of the protections against overcur-
Total selectivity can normally be achieved in specific rents rises rapidly;
cases only where the fault current is not high and where – redundancy of the protections, which guarantees
there is a component with high impedance interposed elimination of the fault (rapidly) in the case of one
between the two protections (transformer, very long of them not operating, is not possible.
cable or a cable with reduced cross-section, etc.) and
therefore a great difference between the short-circuit It is a type of selectivity which can also be made between
current values. circuit-breakers of the same size and without protection
against delayed short-circuit (S).
This type of coordination is therefore used above all in the
distribution terminal (low rated current and short-circuit
current values, and high impedance of the connection
Operatively speaking
– The protection against short-circuit of supply-side circuit-breaker A will be set to a value which means
it does not trip for faults which occur on the load side of protection B. (In the example in the figure I3minA
3kA A
> 1kA)
– The protection of load-side circuit-breaker B will be set so as not to trip for faults which occur on its Cable
load side. (In the example in the figure I3MaxB < 1kA)
Obviously the setting of the protections must take into account the real currents circulating in the circuit- 1kA
breakers. B
Current Selectivity
The ultimate selectivity value which can be obtained is equal to
the instantaneous trip threshold of the supply-side protection less
103s any tolerance.
Is
A Is = I3minA
102s
10s
1s
B Note
This selectivity limit, linked to the magnetic threshold of the supply-side circuit-
10-1s
breaker, is exceeded in all cases where energy type selectivity is realised.
If the settings indicated for energy selectivity are respected for the com-
10-2s binations of circuit-breakers with an energy selectivity value given in the
coordination tables published by ABB, the selectivity limit to be taken into
consideration is the one given in the tables and not the one which can be
0.1kA 1kA 10kA obtained using the formula given above.
Operatively speaking
The protections against short-circuit of the two circuit-breakers will be set:
- with the I2 trip thresholds against delayed short-circuit adjusted so as not to create trip overlapping, A
taking into consideration the tolerances and the real currents circulating in the circuit-breakers.
- with t2 trip times adjusted so that the load-side circuit-breaker B extinguishes the fault whereas the
supply-side circuit-breaker A, still in the timing phase, manages to “see” the extinction of the current
and therefore remains closed. B
Time Selectivity
The ultimate selectivity limit which is obtained is equal:
– to the instantaneous trip threshold of the supply-side protection, 104s
if this function is enabled, less any tolerance:
A Is
Is = I3minA 103s
– to the value of Icw for supply-side air circuit-breakers when the
instantaneous protection function is set to OFF. 102s
B
10s
Note
These selectivity limits are exceeded in all the cases where energy type 1s
selectivity is realised.
If the settings indicated for energy selectivity are respected for the com- 10-1s
binations of circuit-breakers with an energy selectivity value given in the
coordination tables published by ABB, the selectivity limit to be taken into
consideration is the one given in the tables and not the one which can be 10-2s
obtained from the considerations made in this paragraph. 0.1kA 1kA 10kA 100kA
Selectivity techniques
Energy selectivity current trip curves of the circuit-breakers, obtained with
symmetrical sinusoidal types of wave forms, for the
A theoretical outline of selectivity
Operatively speaking
The protections against short-circuit of the two circuit-breakers must respect the conditions given below.
- Supply-side release of thermomagnetic type
the magnetic trip thresholds must be such so as not to create trip overlapping, taking into consideration the tolerances A
and the real currents circulating in the circuit-breakers;
the magnetic threshold of the supply-side circuit-breaker must be equal to or higher than10xIn or set to the maximum
value when it is adjustable.
- Supply-side release of electronic type
B
any protections against delayed short-circuit S must be adjusted following the same indications as time selectivity;
the instantaneous protection function I of the supply-side circuit-breakers must be set to off
I3=OFF
The Is ultimate selectivity limit obtained is the one given in the tables which ABB SACE makes available to the customer.
A
Supply T5
side Energy Selectivity
Version
N,S,H,L,W
Release TM LL 103s
In [A] 400 630 400 630
Load side In [A] A Is
63 25 25 25 25 25 25 25 102s
80 25 25 25 25 25 25 25
100 25 25 25 25 25 25 25 B
N 125 20 20 20 20 20 20 20 10s
160 20 20 20 20 20
B 200 20 20 20 20
1s
250 20 20 20 20
T3 TM 160
63 25 25 25 25 25 25 25
80 25 25 25 25 25 25 25 10-1s
100 25 25 25 25 25 25 25
S 125 20 20 20 20 20 20 20
160 20 20 20 20 20 10-2s
200 20 20 20 20
250 20 20 20
0.1kA 1kA 10kA
Operatively speaking
This is a type of selectivity which can be realised:
- between Emax air circuit-breakers equipped with PR122 and PR123 releases.
The ultimate selectivity limit which can be obtained is equal to the Icw Is = Icw
- between Tmax T4L,T5L and T6L moulded-case circuit-breakers equipped with PR223 EF releases.
The ultimate selectivity limit which can be obtained is 100kA Is = 100kA
Then, by means of the additional IM210 module, it is possible to make a chain of zone selectivity between Tmax and Emax. It is also
possible to realise a selectivity chain including ABB MV protections.
A A
B B
MCCB
Moulded-Case Circuit-Breakers
These are the Tmax series of circuit-breakers.
They can be equipped with thermomagnetic or electronic
releases.
The most advanced electronic release of the Tmax series
is the PR223EF which allows zone selectivity to be reali-
sed between moulded-case circuit-breakers.
ACB
Air Circuit-Breakers
These are the Emax series of circuit-breakers.
They can be equipped with electronic releases.
The most advanced electronic releases of the Emax
series are the PR122/P, which allows zone selectivity to
be realised, and the PR123/P which, apart from zone
selectivity, also allows directional zone selectivity to be
realised.
Supply-side S290D-S800D / Load-side S200 Energy selectivity between S290 D100 and S200L C25
Between the S800 curve D or S290 curve D circuit-breakers on the
supply side and the circuit-breakers of the S200 series on the load
side, ABB SACE provides selectivity tables which give the values 103s
of energy selectivity. Is
In particular, for the values of the tables to be considered valid, the 102s
following prescriptions are valid: A
B
- in the overload zone, the load-side circuit-breaker must trip 10s
more rapidly than the supply-side circuit-breaker, taking into
consideration the tolerances and the real currents circulating in 1s
the circuit-breakers.
10-1s
- in the short-circuit zone, the lower magnetic trip threshold
of the supply-side circuit-breaker and the upper magnetic trip
10-2s
threshold of the load-side circuit-breaker must be such so as
not to create trip overlapping, taking into consideration the real
currents circulating in the circuit-breakers.
0.1kA 0.1kA 1kA 10kA
A
Supply
side S290 S800N-S
A Characteristic D D
Icu [kA] 15 36-50
Load side In [A] 80 100 32 40 50 63
6-8 T T 0.6 0.8 1.1 1.4
10 5 T 0.6 0.8 1.1 1.4
13 4.5 T 0.6 0.8 1.1 1.4
B
S200L C 5 16 4.5 T 0.6 0.8 1.1 1.4
B 20 3.5 5 0.8 1.1 1.3
25 3.5 5 0.8 1.1 1.3
The Is ultimate selectivity limit which is obtained is the one given in 32 4.5 0.9 1.1
the tables which ABB SACE makes available to the customer 40 1.1
MCCB-MCB Selectivity
The case where selectivity is looked for between a moul- In this case, thanks to the different size of the two
ded-case circuit-breaker on the supply side and a modu- circuit-breakers, it is always possible to obtain energy
How to obtain selectivity with ABB circuit-breakers
The Is ultimate selectivity limit which is obtained is the one given in the “Coordination Tables” publication
A
Supply side T2
Version N,S,H,L
Release TM,M EL
Iu [A] 160
Load side Charact. Icu [kA] In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 10 25 63 100 160
≤2 T T T T T T T T T T T T T T T T T
C 3 15 15 15 15 15 15 15 15 15 17 T T T T T T T
4 15 15 15 15 15 15 15 15 15 17 T T T T T T T
6 5.5* 5.5 5.5 5.5 5.5 5.5 5.5 10.5 15 17 T T T T T T
8 5.5 5.5 5.5 5.5 5.5 10.5 15 17 T T T T T T
25
10 3* 3 3 3 4.5 7.5 8.5 17 T T T T T T
13 3* 3 3 4.5 7.5 7.5 12 20 T T T T T
S200P 16 3* 3 4.5 5 7.5 12 20 T T T T
B-C 20 3* 3 5 6 10 15 T T T T
25 3* 5 6 10 15 T T T T
32 3* 6 7.5 12 T T T T
40 5.5* 7.5 12 T T T
B 15
50 3* 5* 7.5 10.5 10.5 10.5
63 5* 10.5 10.5
Short-circuit zone
Supply-side circuit-breaker of thermomagnetic type
The magnetic trip threshold must be:
- higher than or equal to 10xIn when the magnetic threshold is Selectivity between T5N400 PR221In320 and S284 D63
fixed (TMD)
104s
- set to the maximum value when the magnetic threshold is
adjustable (TMA)
103s
- such so as not to create trip overlapping with the load-side Is
circuit-breaker, taking into consideration the tolerances and
the real currents circulating in the circuit-breakers. 102s
A
10s
Supply-side circuit-breaker of electronic type
The instantaneous protection function I must be set to OFF B
I3=OFF 1s
The Is ultimate selectivity limit is the lesser between the breaking capacity of the supply-side circuit-breaker and the breaking capacity
of the load-side circuit-breaker.
With reference to the example given in the figure above
S284D63 Icu = 15kA
T5N400 Icu = 36kA
there is therefore Is = 15kA
MCCB-MCCB Selectivity
The case where selectivity is looked for between two an energy selectivity value and the supply-side circuit-
moulded-case circuit-breakers is now analysed. In this breaker is equipped with an electronic release
How to obtain selectivity with ABB circuit-breakers
Current selectivity
Looking for current selectivity between moulded-case circuit-breakers may be necessary when there are circuit-breakers of the same
size which do not have energy selectivity values in the tables.
In any case, only low selectivity values in the order of a maximum of 10 times the In rated current of the release on the supply side can
be obtained.
To obtain the current type of selectivity, the following prescriptions must be respected:
In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into consideration
the tolerances and the effective currents circulating in the circuit-breakers.
In the short-circuit zone given that the following are: Current selectivity between T4N250 TMA250 and T4N250 TMA80
I3minA the lower magnetic threshold of the supply-side circuit-breaker A
104s
I3MaxB the upper magnetic threshold of the load-side circuit-breaker B
IkB the maximum prospective short-circuit current on the load side of B
103s Is
A
If the following relationships are true: 102s
I3minA > IkB
I3MaxB < IkB 10s
A
one can speak of total selectivity. B
To obtain the time type of selectivity, the following prescriptions must be respected: B
In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side cir-
cuit-breaker, taking into consideration the tolerances and the real currents circulating in the circuit-
breakers.
This relationship must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more frequent
case - use of the available settings through dip-switches - the values given in the following tables must be complied with:
t2 times set
MCCB on the supply side t2A=250 t2A=250 t2A =500
MCCB on the load side t2B=50 t2B=100 t2B =250
Note
The indications about the adjustments of the releases are valid in general and useful for a rapid choice of setting guaranteing selectivity. For specific
combinations of circuit-breakers and for specific installation conditions, ABB SACE may provide indications which do not respect the rules given in
this document, but however able to ensure selectivity.
The ultimate selectivity limit is equal to the istantaneus trip threshold I3 of the upstream circuit-breaker minus the tollerance
Is = I3minA
MCCB-MCCB Selectivity
Energy selectivity
How to obtain selectivity with ABB circuit-breakers
ABB SACE makes selectivity tables available to the customer which provide the energy selectivity values
at 415V between the possible combinations of moulded-case circuit-breakers.
Since the moulded-case circuit-breakers can be equipped with thermomagnetic and electronic releases A
which are both adjustable, it is necessary for the user to carry out some checks in order to obtain selec-
tivity up to the short-circuit current value given in the tables.
In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-
breaker, taking into consideration the tolerances and the real currents circulating in the circuit-breakers.
In the short-circuit zone B
This relationships must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more fre-
quent case - use of the available settings through dip-switches - the values given in the following tables must be complied with:
t2 times set
MCCB on the supply side t2A=250 t2A=250 t2A =500
MCCB on the load side t2B=50 t2B=100 t2B =250
Note: The indications about the adjustments of the releases are valid in general and useful for a rapid choice of setting guaranteing selectivity. For
specific combinations of circuit-breakers and for specific installation conditions, ABB SACE may provide indications which do not respect the rules
given in this document, but however able to ensure sectivity.
The Is ultimate selectivity limit obtained is the one given in the MCCB - Tmax T5 @ 400/415 V
“Coordination Tables” publication.
Supply side T6 T7
Versions N,S,H,L S,H,L,V(1)
Release TM, M EL EL
Iu [A] 630 800 630 800 1000 800 1000 1250 1600
Load side In [A] 630 800 630 800 1000 800(2) 1000(2) 1250 1600
400 320 30 30 30 30 30 T T T T
N, TM 400 30 30 30 T T T T
S, 630 500 30 30 T T T T
T5 H, 320 30 30 30 30 30 T T T T
Available only with Iu ≤ 1250 A L, EL 400
(1)
(2)
Value valid only for PR232/P, 400 30 30 30 30 30 T T T T
V
PR331/P and PR332/P trip units 630 630 30 T T T T
Interlock configuration
Each release is characterised by:
- an input destined for connection with the release on the supply
side “Uplink”
- an output destined for connection with the release on the load
side “Downlink”
Uplink: PP/MP
Each of the two can be configured in two ways: PP (point-point)
or MP (multi-point) according to the installation condition the PR223EF
releases are in.
Downlink: PP/MP
The main configurations are given below:
MP MP MP MP MP MP
PR223EF PP
PR223EF PR223EF PR223EF PR223EF PR223EF PR223EF
MCCB-MCCB Selectivity
The main parameters, characteristic of the release, are:
How to obtain selectivity with ABB circuit-breakers
Trip delayed Enabling this parameter introduces a trip delay in the case when, on the load side of a release, smaller sized
Tmax or modular circuit-breakers are installed. The aim of this parameter is to obtain selectivity with the
other devices on the load side not equipped with PR223EF.
This parameter is only enabled in the circuit-breakers which have the device outside the zone selectivity
chain on the load side.
EF enable/disable Enabling/disabling protection EF.
If protection EF is enabled:
the presence of Vaux leads to automatic exclusion of function I and enabling of protection EF,
the lack of Vaux leads to exclusion of protection EF and to the return of function I (if enabled).
100 kA Ultimate selectivity limit which can be obtained with the PR223EF suitably cabled and supplied with power.
16 Maximum number of releases which can be connected to the BUS of a level.
1200 meters Maximum overall length of the connection cable. Cabling the different releases is carried out as in the classic
“Bus topology” (see figure).
PR223EF
Down
Cable RS485
= max 1200 m
Short-circuit 102s
- No trip overlapping of the I2 current thresholds of function S,
taking into consideration the tolerances and the real currents 10s
circulating in the circuit-breakers.
1s
- Trip time t2
Adjusted so as to realise time selectivity with any load-side
circuit-breaker placed outside the zone selectivity chain. 10-1s
Between the circuit-breakers equipped with PR223EF and inter-
locked with each other, if A is the supply-side circuit-breaker and 10-2s
B the load-side circuit-breaker, the following must be valid:
t2A ≥ t2B.
When possible, it is advisable to look for time type selectivity as 0.1kA 1kA 10kA
well between the interlocked circuit-breakers so as to guarantee
partial selectivity in case the auxiliary power supply is lost.
A
PR223EF
- Trip delayed
By enabling this parameter on the releases which have a circuit-
breaker directly on the load side not equipped with PR223EF, B
selectivity is obtained with the Tmax of a smaller size or the PR223EF
MCBs placed on the load side. Trip delayed ON
C
PR221DS
MCCB-MCCB Selectivity
Example of application
In the following example a comparison between an installation where selectivity is implemented with traditional techniques and the same
How to obtain selectivity with ABB circuit-breakers
QF1
E3H800 PR122/P-LSI In800
WC1
6x(1x400)+2x(1x240)+1G400
Ib = 740 A
Iz = 1050 A
L = 17m
PVC
QF1 Switchboard A
E3S/ S1000
IkA=74 kA
QF2 QF3
T6L630 PR222DS-LSI In630 T4L250 PR222DS-LSI In250
WC2 WC3
6x(1x300)+2x(1x150)+1G300 3x(1x150)+1x(1x95)+1G95
Ib = 540 A Ib = 200 A
Iz = 682 A Iz = 275 A
L = 25 m L = 10m
PVC PVC
L1
QS2
Switchboard B L In = 200 A
T6D630
IkA=54.5 kA
L2 L3 L4
L In = 200 A L In = 170 A L In = 170 A
The choice of the protection devices shall be carried out above all making reference to the rated currents of the loads and to the short-
circuit current of the busbars. Besides, this choice is influenced by the search for selectivity realized through traditional techniques, whose
values can be found in the “Coordination Tables” publication.
The short-circuit current at the busbars of switchboard B (IkB=54.5kA) influences the choice of the protection devices and imposes the
use T4H 250 circuit-breakers on the outgoing feeders.
In order to guarantee selectivity, the circuit-breaker (QF2) on the supply side of switchboard B and installed in switchboard A must be
T6L 630 type.
The busbar of switchboard A is characterized by a short-circuit current value IkA=74kA: this affects deeply the choice of the upstream
protection device which, independent of the rated current, shall be an Emax circuit-breaker and precisely an Emax E3H, therefore able
to guarantee selectivity towards the apparatus on the load side.
Each switchboard has got as main device a switch-disconnector, which shall be protected against short-circuit and overload by the
circuit-breaker on the supply side. Generally speaking, in order to guarantee protection, it is necessary to use a switch-disconnector in
the version derived from the circuit-breaker on the supply side.
Therefore it is evident that the selectivity requirements condition deeply the choice of the protection devices and direct it towards diffe-
rentiated sizes according to the location of the circuit-breakers in the installation.
QF1
T6L800 PR223EF In800
WC1
6x(1x400)+2x(1x240)+1G400
Ib = 740 A
Iz = 1050 A
L = 17m
PVC
QF1 Switchboard A
T6D800
IkA=74 kA
QF2 QF3
T5L630 PR223EF In630 T4L250 PR223EF In250
WC2 WC3
6x(1x300)+2x(1x150)+1G300 3x(1x150)+1x(1x95)+1G95
Ib = 540 A Ib = 200 A
Iz = 682 A Iz = 275 A
L = 25 m L = 10m
PVC PVC
L1
QS2
Switchboard B L In = 200 A
T5D630
IkA=54.5 kA
L2 L3 L4
L In = 200 A L In = 170 A L In = 170 A
Since the rated current and the short-circuit values of the network under consideration remain unchanged, the use of the new protection
release PR223EF allows selectivity to be obtained without increasing the size of the apparatus to be used.
In particular, a T5L630 equipped with PR223EF can be used as circuit-breaker on the supply side of switchboard B (QF2). As a conse-
quence, the switch-disconnector on the incoming feeder of switchboard B can be reduced in size.
The most evident reduction in size which can be obtained regards the main device of the installation: thanks to the use of PR223EF
release, a moulded-case circuit-breaker can be chosen instead of an air circuit-breaker. In this specific case, a T6L800 circuit-breaker
with a downstream switch-disconnector of the same size can be used.
MCCB-MCCB Selectivity
The following table summarizes the advantages deriving from the use of the new electronic release.
In details, it has been possible:
How to obtain selectivity with ABB circuit-breakers
• to replace a large-sized moulded-case circuit-breaker with a smaller one – T5L 630 PR223EF instead of T6L630 PR221-LS;
• to replace a large-sized air circuit-breaker with a much smaller moulded-case one – T6L 800 PR223EF instead of E3H800 PR122/P-
LSIG;
• to replace a large-sized switch-disconnector with a smaller-sized one – T5D 630 instead of T6D630;
• to replace an air switch-disconnector with a switch-disconnector derived from a much smaller-sized moulded-case circuit-breaker
– T6D 800 instead of E3S/MS1000.
Besides a remarkable reduction in the applicable sizes, with the consequent advantages from a dimensional and economical point of
view, the installation equipped with PR223EF releases is subject to more limited electrodynamical and thermal stresses than those of the
traditional solution. Hereunder the let-through energy and peak curves relevant to the considered circuit-breakers are shown.
E3H 800
103 MA2s
E3H 800
102 MA2s
102 kA
T6L 800
T6H 630
T6L 800
T6H 630
10 MA2s T5L 630
T5L 630
1 MA2s 10 kA
10 kA 102 kA 103 kA 10 kA 102 kA 103 kA
Irms [kA] Irms [kA]
From the curves above, it should be noticed that at a short-circuit current value corresponding to 55kA, the specific let-through energy
allowed by T6H630 is equal to 13 MA2s, whereas that of T5L630 is 3.5 MA2s. Also the peak values decrease drastically from 54kA of T6H
to about 35kA of T5L630.
Similarly, at 74kA short-circuit current, the specific let-through energy and the peak current limited by T6L800 circuit-breaker reduce very
much the thermal and dynamical stresses if compared with E3H circuit-breaker.
In particular, in this case, it is possible to use the current limiting capacities of the moulded-case circuit-breaker to optimize the dimen-
sioning of the busbar system of switchboard A. In fact, with an air circuit-breaker on the supply side, it is necessary to adopt a busbar
system dimensioned for a rated short-time withstand current (Icw) equal to 75kA and consequently with a current carrying capacity much
more higher than the total current required by the installation. On the contrary, by using a T6L800 circuit-breaker on the supply side of
the switchboard, it is possible to adopt a busbar system with Icw equal to 35kA, which results more consistent from a dimensional point
of view with 800A current, which is the current carrying capacity required to this busbar system.
In details, the following values correspond to 35kA rated short-time withstand current of the busbar system:
- peak current Ip = (35x2.1) = 73.5kA, which results to be higher than the peak of 66kA allowed by T6L800 circuit-breaker at 75kA short-
circuit current;
- let-through energy I2t = 352 x 1 =1225 MA2s, which results to be higher than the let-through energy equal to 20MA2s of T6L800 circuit-
breaker with a short-circuit value corresponding to 75kA.
Traditional solution
In this case, ABB SACE makes a table available in which the selectivity values between air circuit-breakers on the supply side and moul-
ded-case circuit-breakers on the load side are given.
The need to set the releases appropriately to obtain the selectivity value given in the table is obvious.
The following must be true:
In the overload zone, the load-side circuit-breaker must trip more rapidly than the supply-side circuit-breaker, taking into consideration
the tolerances and the real currents circulating in the circuit-breakers.
In the short-circuit zone Emax-MCCB selectivity
- instantaneous protection function I must be set to OFF 104s
I3=OFF
103s
- the I2A trip threshold of the supply-side circuit-breaker must
be adjusted so as not to create trip overlapping with the trip B A
threshold of the protection against short-circuit (I3 or I2) of 102s
the load-side circuit-breaker, taking into consideration the
tolerances and the effective currents circulating in the circuit-
10s
breakers
when the I2A threshold of the supply-side circuit-breaker is only higher than the I2B threshold of the load-side circuit-breaker, by
using curves with the same characteristics, the following is valid:
t2A - tolerance ≥ t2B + tolerance + 50ms
This relationship must be respected when, through the dialogue or the PR010T unit, electronic settings are used. In the more frequent
case - use of the available settings through dip-switches - the values given in the following tables must be complied with:
t2 times set
ACB on the supply side t2A=200 t2A=200 t2A =400 t2A =700
MCCB on the load side t2B=50 t2B=100 t2B =250 t2A =500
Note
The indications about the adjustments of the releases are valid in general and useful for a rapid choice of settings guaranteeing selectivity. For speci-
fic combinations of circuit-breakers and for specific installation conditions, ABB SACE may provide indications which do not respect the rules given
in this document, but however able to ensure selectivity.
The Is ultimate selectivity limit obtained is the one given in the “Coordination Tables” publication.
ACB-MCCB Selectivity
Zone selectivity between Emax and Tmax
How to obtain selectivity with ABB circuit-breakers
By means of the IM210 interlocking module, it is possible to extend zone selectivity from the PR223EF releases to the PR122/P or PR123/P
release on the supply side.
In practice, the device makes interfacing between the IL protocol of PR223EF and ZS zone selectivity of the PR122/P and PR123/P
devices possible.
Furthermore, by making this selectivity chain between Emax and Tmax, the limit selectivity value shall be the lesser value between:
- the short-time withstand current of the supply-side circuit-breaker (Icw of the Emax)
- the breaking capacity of the circuit-breaker on the load side (Icu of the Tmax in version L → 100kA)
- the Emax release receives a “lock” signal: if its I2 threshold has been exceeded, it trips within the t2 time set on the release;
- the Emax release does not receive a “lock” signal: if its I2 threshold has been exceeded, it trips within a “selectivity time” time
set on the release.
A
PR122P
This being stated, to obtain total selectivity, both in the case of over-
load and short-circuit, making the selections and settings described
below is recommended, where:
IM210
A is the Emax with PR122/P on the supply side of the PR223EF B C
PR223EF PR221DS
B is the Tmax with PR223EF
C is a device outside the zone selectivity chain
Short-circuit 10s
- No trip overlapping of the I2 current thresholds of function S, t2A
taking into consideration the tolerances and the real currents
1s
circulating in the circuit-breakers.
10-1s
- Trip times t2A and “selectivity time” of the Emax on the supply
side adjusted in the following way: 10-2s
selectivity time adjusted so as to realise time-current se-
lectivity with the C device on the load side
0.1kA 1kA 10kA
placed outside the zone selectivity chain
selectivity time
t2A (time of function S) adjusted so as to guarantee no
tripping of circuit-breaker A which recei-
ves the lock signal, i.e. according to the
relationship:
t2A > t2B+70ms*
ACB-ACB Selectivity
The case where selectivity is looked for between two air circuit-breakers is now analysed. In this case various
methods can be used to obtain selectivity between the circuit-breakers:
How to obtain selectivity with ABB circuit-breakers
Time selectivity
To obtain the maximum level of selectivity compatible with the chosen strategy, both in the case of overload and short-circuit, the following
selections and the following settings between the various circuit-breakers are recommended:
104s
Overload
- Check that there is no trip overlapping of protection functions L 103s
(against overload), taking into consideration the tolerances and
the real currents circulating in the circuit-breakers. 102s
10s
Short-circuit
- The instantaneous protection function I of the supply-side circuit-
breaker must be set to OFF 1s
I3A=OFF
10-1s
- the I2A trip threshold of the supply-side circuit-breaker must be
adjusted so as not to create trip overlapping with the trip threshold 10-2s
of the protection against short-circuit (I3 or I2) of the load-side
circuit-breaker, taking into consideration the tolerances and the
real currents circulating in the circuit-breakers 0.1kA 1kA 10kA 100kA
Minimum difference between the t2 times of two Emax circuit-breakers equipped with PR121, PR122, and PR123
t=const t2A > t2B + 100ms* *70ms if in aux supply or in self-supply under steady conditions
I2t=const t2A > t2B + 100ms t2A < 400ms
I2t=const t2A > t2B + 200ms t2A ≥ 400ms
Note
The indications about the adjustments of the releases are valid in general and useful for a rapid choice of settings guaranteeing selectivity. For specific
combinations of circuit-breakers and for specific installation conditions, ABB SACE may provide indications which do not respect the rules given in this
document, but however able to ensure selectivity.
A A
B B
As can be seen, if the settings indicated below have been respected, in the case of a short-circuit no circuit-breaker trips in the t2 time,
but all of them trip within the selectivity time set.
A t2A t2A
selectivity
timeA
PR122/P PR122/P PR122/P
B t2B
selectivity
timeB
does not
trip
PR122/P PR122/P PR122/P
PR122/P PR122/P PR122/P
C selectivity
timeC
does not
trip
does not
trip
PR122/P PR122/P
PR122/P
Fault current
Connection with lock signal
Connection without lock signal
ACB-ACB Selectivity
Indications about the settings
To obtain total selectivity, both in the case of overload, short-circuit and earth fault, using the “zone selectivity” function, making the
How to obtain selectivity with ABB circuit-breakers
following selections and the following settings between the various circuit-breakers is recommended:
Short-circuit
- No trip overlapping of the I2 current thresholds of function S, 10s
taking into consideration the tolerances and the real currents t2A
circulating in the circuit-breakers.
1s
*Δt minumum between the trip times of two CBs in series, with auxiliary
power supply, and with constant time curves, to guarantee no trip of the
CB on the supply side. B
The maximum number of circuit-breakers which can be connected to the outputs (Z out) of a release is 20.
The lock signal of the release is a +24V signal.
ZSA MODULE
In the case where several load-side circuit-breakers have to lock several supply-side circuit-breakers, but in a different way, it is necessary
to use the ZSA module supplied by ABB.
With reference to the figures at the side, let us suppose, for exam-
ple, that:
C must lock A and B
D must only lock B.
With the cabling made as in the figure at the side, it would not be A B
possible to obtain the desired solution.
In fact, the lock signal coming from D would also be transmitted to
A by means of the electrical continuity which is created between
the different B-C and C-A interlocking connections.
C D
A B
ZSA
C D
ACB-ACB Selectivity
Directional time selectivity
How to obtain selectivity with ABB circuit-breakers
By means of the directional protection D present on the Emax circuit-breakers equipped with PR123 releases, it is possible to realise
time selectivity of directional type.
This type of selectivity has all the advantages and limits of time selectivity realised by means of function S, but is also able to trip within
different times according to the direction of the fault.
Using this type of selectivity is particularly recommended in all those cases where there is more than one power supply source.
In fact, in the case of a fault near a source, service continuity of the remaining power supply can be guaranteed by means of
directional protection.
Directional protection
Directional protection is based on the possibility of correlating the circuit-breaker behaviour with the direction of the fault current which
passes through it in relation to the reference direction which can be set on the release.
According to the direction of the current, it is possible to set two different trip times on the PR123 release:
a time (t7Fw) in a direction concordant (Fw) with the reference direction set;
a time (t7Bw) in a direction discordant (Bw) with the reference direction set.
These times are enabled when the only current threshold (I7) set on the PR123 release is exceeded.
If the fault current is discordant (Bw) with the reference direction set, the protection will trip once the I7 threshold in the t7Bw time set is
reached (unless functions S and I are not set to intervene before D).
If the fault current is concordant (Fw) with reference direction set, the protection will trip once the I7 threshold in the t7Fw time set is
reached (unless functions S and I are not set to intervene before D).
Furthermore, if function I is enabled and the short-circuit current exceeds the I3 value set, the circuit-breaker will open instantaneously
regardless of the direction of the current.
The default reference direction is from the top of the circuit-breaker (zone where the release is) to the bottom (top to bottom).
The figure at the side shows the actual configuration which two G1 G2
circuit-breakers have in an installation.
The default reference direction set on the circuit-breaker is indicated
by the red arrow. Release Release
Reference
If the circuit-breaker power supply direction is from top to bottom Direction
direction
Reference
set by direction
(power supply from G2), the reference direction remains the ABB ABB inverted set by
through
default one. software
ABB
If the circuit-breaker power supply direction is from bottom to
top (power supply from G1), by working on its software, the new
PR123 electronic release allows the default setting to be reversed
(bottom to top).
Working in this way, all the values measured with the PR123 release G1
Contribution to the
G2
short-circuit by each
will be assessed as they actually flow in the installation. Further- generator: 10 kA
more, on the single-line diagram which represents the installation, A QF1
with PR123
B QF2
with PR123
the reference direction to carry out a selectivity study and consider Reference Reference
the Bw or Fw trip directions correctly always remains from top to direction direction
bottom.
To realise directional time selectivity, it is necessary to assume the significant fault points and, having assessed the short-circuit currents
in play, establish which circuit-breakers will have to trip.
To be sure that everything functions as foreseen in the case of a fault, i.e. the circuit-breakers always trip with directional protection, the
following settings and selections are recommended:
- Select the circuit-breakers with a short-time withstand current value higher than the maximum prospective short-circuit current
which can occur at the point where they are installed:
Icw ≥ Ik MAX
- Set the trip thresholds of directional protections D to a lower value than the minimum prospective short-circuit current which can
occur at the point where that release is installed:
I7 < Ik min
- Set the trip thresholds of protections S and I in such a way so as not to create trip overlapping with function D.
Also remember that, in the case of constant time curves, to guarantee tripping of an air circuit-breaker equipped with PR121/P, PR122/P
or PR123/P and no trip of another air circuit-breaker equipped with these releases, a difference between the trip times set must be kept,
equal to:
Δt = 100ms (which can be reduced to 70ms if there is an auxiliary power supply or if it is considered that the fault occurs when the
releases under self-supply are in a steady condition).
ACB-ACB Selectivity
This function allows selectivity to be obtained even in mesh networks and ring networks.
In particular, in the presence of a bus tie, thanks to directional zone selectivity it is possible to keep a half-busbar supplied with voltage
even in the case of a fault on the other half-busbar.
For it to be possible to apply zone selectivity to function D (directional zone selectivity), a series of conditions must exist:
- zone selectivity S and G must be disabled [OFF]
- there is a 24Vdc auxiliary power supply source
- the Emax circuit-breakers are equipped with the PR123 releases.
Each release has 4 ports available:
- two inputs (one in a concordant and one in a discordant direction), through which the release receives the lock signal coming from
other
releases
- two outputs (one in a concordant and one in a discordant direction), through which the release sends the lock signal to other relea-
ses.
By using directional zone selectivity, it is possible to obtain selectivity even in meshed networks up to an ultimate selectivity limit equal
to the Icw of the circuit-breakers furthest on the supply side (if the I3=OFF).
In the same way as for directional protection, to be sure that everything functions as foreseen in the case of a fault, i.e. the circuit-breakers
always trip with directional protection, the following settings and selections are recommended:
- Select the circuit-breakers with a short-time withstand current value higher than the maximum prospective short-circuit current
which can occur at the point where they are installed:
Icw ≥ IkMAX
- Set the trip thresholds of directional protections D to a lower value than the minimum prospective short-circuit current which can
occur at the point where that release is installed:
I7 < Ikmin
- Set the trip thresholds of the protections S and I in such a way so as not to create trip overlapping with the function D.
By means of these settings, it is certain that, for any foreseeable fault in the installation, the circuit-breakers will trip according to the
settings of function D.
IN QF1+ IN QF2+ IN
Fw Bw PR123 Fw Bw PR123 Fw Bw
OUT OUT OUT
Fw Bw Fw Bw Fw Bw
-B1 -B2
L M
Reference direction
With reference to the installation indicated in the figure, once the maximum and minimum short-circuit currents in the different points of
the installation are known, it is necessary to:
- hypothesise the various significant fault points;
- for the first fault: establish which circuit-breakers must isolate the fault;
establish which circuit-breakers must be locked and by what;
draw the appropriate cabling;
- repeat the operation for the subsequent faults in order to determine all the necessary cabling.
Finally, it is necessary to check that the cabling carried out does not create any conflicts.
Application example
Note
The QF4 circuit-breaker could be provided with PR122/P release since, with a passive load, the short-circuit current may have a single direction and conse-
quently directional protection results to be unnecessary.
The use of PR122/P release, with zone selectivity implemented on protection S, guarantees an input and an output, which allow to realise selectivity in the
case of a fault on the load side of QF4.
ACB-ACB Selectivity
Fault in B1:
Only the QF1 and QF3 circuit-breakers must interrupt the fault: in particular the QF3 circuit-breaker is passed through by a current coming
How to obtain selectivity with ABB circuit-breakers
from busbar B2 (therefore in a direction concordant with the one set); the OUT Fw bus sends a lock signal to the IN Fw bus of the QF2
circuit-breaker (passed through by a current coming from transformer TM2 and therefore in a direction concordant with the one set), and
to the IN Bw bus of the QF5 circuit-breaker (passed through by a current coming from the motor and therefore in a direction discordant
with the one set).
L M
Fault in B2:
The QF2 and QF3 and QF5 circuit-breakers must interrupt the fault: in particular the QF3 circuit-breaker is passed through by a current
coming from busbar B1 (therefore in a direction discordant with the one set); the OUT Bw bus sends a lock signal to the IN Fw bus of the
QF1 circuit-breaker (passed through by a current coming from transformer TM1 and therefore in a direction concordant with the one set).
Direction (OUT-IN) Arrow
Fw Fw
Fw Bw
Bw Fw -TM1 -TM2
Bw Bw
Reference direction
IN QF1+ IN QF2+ IN
Fw Bw PR123 Fw Bw PR123 Fw Bw
OUT OUT OUT
Fw Bw Fw Bw Fw Bw
-B1 -B2
L M
OUT
Cabling QF1 QF2 QF3 QF4 QF5
FW BW FW BW FW BW FW BW FW BW
FW
QF1
BW
FW
QF2
BW
FW
IN QF3
BW
FW
QF4
BW
FW
QF5
BW
L M
Fault on the load side of QF5:
In this case only the QF5 circuit-breaker must interrupt the fault. The QF5 circuit-breaker is passed through by a current coming from the
busbars B1 and B2, in a concordant direction in relation to the direction set, therefore the OUT Fw bus of QF5 locks both the IN Fw bus
of QF2 (passed through by a current coming from TM2 and therefore in a direction concordant to the one set) and the IN Bw bus of QF3
(passed through by a current coming from TM1 and therefore in a direction discordant with the one set). These cabling operations must
be carried out. In the same way as before, the QF3 circuit-breaker locks QF1 with the cabling already present.
Direction (OUT-IN) Arrow
Fw Fw
Fw Bw
Bw Fw -TM1 -TM2
Bw Bw
Reference direction
IN QF1+ IN QF2+ IN
Fw Bw PR123 Fw Bw PR123 Fw Bw
OUT OUT OUT
Fw Bw Fw Bw Fw Bw
-B1 -B2
L M
OUT
Cabling QF1 QF2 QF3 QF4 QF5
FW BW FW BW FW BW FW BW FW BW
FW
QF1
BW
FW
QF2
BW
FW
IN QF3
BW
FW
QF4
BW
FW
QF5
BW
ACB-ACB Selectivity
Fault on the supply side of QF1:
Only the QF1 circuit-breaker must interrupt the fault. The QF1 circuit-breaker is passed through by a current coming from busbar B1
How to obtain selectivity with ABB circuit-breakers
(therefore in a direction discordant with the one set); the OUT Bw bus sends a lock signal to the IN Fw bus of the QF3 circuit-breaker
(passed through by a current coming from transformer TM2 and therefore in a direction concordant with the one set). This cabling must
be carried out.The QF3 circuit-breaker will then lock the circuit-breakers which insist on busbar B2 by means of the cabling operations
already carried out.
Direction (OUT-IN) Arrow
Fw Fw
Fw Bw
Bw Fw -TM1 -TM2
Bw Bw
Reference direction
IN QF1+ IN QF2+ IN
Fw Bw PR123 Fw Bw PR123 Fw Bw
OUT OUT OUT
Fw Bw Fw Bw Fw Bw
-B1 -B2
L M
L M
OUT
Cabling QF1 QF2 QF3 QF4 QF5
FW BW FW BW FW BW FW BW FW BW
FW
QF1
BW
FW
QF2
BW
IN FW
QF3
BW
FW
QF4
BW
FW
QF5
BW
Apart from realising directional zone selectivity with the settings indicated, selectivity between the QF4 and QF5 circuit-breakers towards
the supply-side circuit-breakers and between QF1 and QF2 can also be achieved, in the case of loss of the auxiliary power supply.
The maximum length of the cabling between two units for zone selectivity is 300 metres. This limit can be increased using special mecha-
nisms.
The maximum number of circuit-breakers which can be connected to the outputs (Z out) of a release is 20.
The lock signal of the release is a +24V signal.
In the case of directional zone selectivity, the use of the ZSA module described on page 31 is recommended.
Appendix A
MV/LV Selectivity 1. transformer:
• connection curve (inrush);
Appendix A
Example
The selectivity study for the network represented in the figure is to be carried out:
Data:
• Distributor utility: U Vref = 15000 V
- rated voltage Un = 15 kV
- three-phase short-circuit current Ik3 = 12.5 kA
- single-phase earth fault current Ik1E = 50 A QF1
- overcurrent protection 51:
• first threshold: I> ≤ 250 A, t ≤ 0.5 s
• second threshold: I>> ≤ 900 A, t ≤ 0.12 s
• 15/0.4 kV Transformer: Vn1 = 15000 V
- rated power Sn = 1600 kVA Vn2 = 400V
Sn = 1600 kVA
- short-circuit voltage uk = 8 % Vk = 8%
- rated primary current It1 = 61.6 A
- rated secondary current It2 = 2309.4 A
- inrush current Ii1 = 9⋅It1 = 554.4 A
- inrush time constant tthe = 0.4 s QF2
E3H 2500 PR121/P-LSI In2500
I -t
= it . e t i
Appendix A
103s
102s
10s
Thermal
withstand
1s
Inrush
10-1s
10-2s
Ik LV busbars
Now the data regarding the limits set by the distributor utility are Time-Current Curve
put in: 104s
103s
102s
10s
1s
Distributor utility limits
10-1s
10-2s
Apart from protecting the transformer, the curve of the main low Time-Current Curve
voltage circuit-breaker must also guarantee selectivity with the 104s
low voltage circuit-breakers. The curves of the low voltage circuit-
breakers can therefore be traced so as to define a minimum limit 103s
for the curve of the main circuit-breaker:
102s
QF3
10s
1s
QF4
10-1s
10-2s
To ensure selectivity between QF3 and QF4, function L and S of T4 must be set as follows:
QF3 T4H 320 PR222DS/P-LSI R320
L: Setting: 0.9x320 = 288 A Curve: 3s
S: t=const Setting: 5.8x320 = 1856 A Curve: 0.1s
I: OFF
At this point it is possible to trace the trip curves of the main QF2 LV circuit-breaker bearing in mind the following:
Appendix A
(1) less restrictive settings can be used when the overloading capacity of the machine is known.
Now the settings for the medium voltage release are defined, taking into account the following:
Appendix B
than the maximum trip time of the circuit-breaker on
the load side:
With its many functions and types, the residual current Tminsupply>Ttotload
circuit-breaker can be defined as follows:
a device sensitive to the earth currents, able to open
an electric circuit within a certain time when the earth For residual current circuit-breakers conforming to the
current exceeds the preset value. It is used to protect IEC60947-2 Standard (CEI EN 60947-2), the prescriptions
people and things against: direct contacts (a device with regarding the trip curves for residual current without
high sensitivity, it is an additional protection) - indirect delay or for the delayed type are given in Annex B of
contacts or loss of insulation. the Standard.
The professional rule for the electrical installation always The differentiation of the trip time can be made more
imposes, except for special plants, the presence of an easily by using delayed type residual current (Δt = time
earthing system, both in civil and industrial buildings. limit of no trip in ms or if Δt=60ms) with definite time
Furthermore, the IEC 60364 Standard makes the use of or with inverse time, where tripping can be delayed ac-
a residual current circuit-breaker compulsory in many cording to a selectable time.
cases for protection of people, giving prescriptions
referring to the trip time and currents in relation to the These pieces of apparatus are generally installed on the
installation voltage, to the distribution system present, supply side of other general type residual current devices
and to the places of installation. and it is advisable to have a relationship of 3 between
the trip thresholds.
Good protection of the installation should provide:
- a main residual current type of circuit-breaker so as Function G
to have protection against faults which could occur Protection against earth faults can be realised, using
between the main circuit-breaker and the distribu- function G present on the electronic releases installed on
tion; board the moulded-case or air circuit-breakers.
- protection of each individual shunt with a residual The trip characteristics can be adjusted for the current
current device. (from 0.2 to 1 x In) and for the time, with an inverse or de-
finite time trend, depending on the different versions.
In this way, there is the need to study selections of the Realising protection against indirect contacts with this
devices carefully to guarantee selectivity, and prevent type of function requires a careful analysis of the distribu-
an earth fault in any point of the distribution circuit from tion system and of the value of the earth fault current.
putting the whole installation out of service.
For Emax circuit-breakers it is possible to realise zone
In general, two residual current devices are selective selectivity for function “G” according to the same philo-
for each current value if their trip zones do not overlap. sophy described for function “S”.
This condition is obtained by respecting the following This makes it possible to reduce the trip times between
points: two residual current protections in series, increasing the
safety margin for any fault on the load side of the supply-
- The residual current trip threshold of the device on side circuit-breaker, since its trip time is not as high as it
the supply side must be higher than or at maximum should have been to obtain selectivity towards the load
equal to double the residual current trip threshold of side with the classic method for time selectivity.
the device on the load side:
IΔnSupply side≥2xIΔnLoad side.
This relationship is necessary for taking into account
the concept of rated no trip residual current, which
is the maximum current value for which the residual
current circuit-breaker definitely does not trip.
The Standards indicate a current value of IΔn/2 and
within this value the device does not have definite
behaviour, i.e. it may trip just as it may not trip.
Example
Appendix B
RCQ
Adjustable trip thresholds IΔn [A] 0.03 – 0.05 – 0.1 – 0.3 – 0.5 – 1 – 3 – 5 – 10 - 30
Trip times [s] instantaneous - 0.1 – 0.2 – 0.3 – 0.5 - 0.7 - 1 – 2 – 3 - 5
Time-Current Curve
102s
RCD 1 RCD 2 RCD 3
10s
RCD3 Delayed type ∆t=Is [300mA]
1s
10-1s
RCD2 Delayed type 300ms [100mA]
10-2s
Appendix C
The selectivity study for the installation shown in the figure supplied
by a transformer with a 400V secondary winding is to be carried
out:
QF1
E1B 1250 PR121/P-LSI In1250
Ik = 20kA
QF2
T4N 320
PR222DS/P-LSI
In320
Ik = 10.5kA
QF3
T2N 160
TMD In160
Ik = 1.2kA
In the study below, it is assumed that the circuit-breakers are passed through by the same fault current (the real currents passing through
the circuit-breakers are ignored) and it is assumed that the circuit-breakers selected are able to protect the cables, the switch-discon-
nectors and whatever else.
Time-Current Curve
First of all, the curves of the QF4 circuit-breaker are traced: 104s
103s
102s
10s
1s
10-1s
10-2s
S 200L C 16 1.2 kA
0.1 kA 1 kA 10 kA
Noting that the maximum short-circuit current at the point where QF4 is installed is 1.2 kA, to obtain total selectivity it is sufficient for the
magnetic threshold of the QF3 supply-side circuit-breaker to be higher than this value, taking into account the tolerances:
Appendix C
Time-Current Curve
104s
103s
T2N 160
S200L C16
102s
10s
1s In any case, a total energy selectivity value, i.e. equal to the breaking
capacity of S200L (6 kA) is found in the coordination tables. The
settings of QF2 will be:
10-1s
S200L C16
102s
10s The settings of QF2, in accordance with what has been said in the
previous chapters, will be:
1s QF2, T4N 320 PR222DS/P-LSI In320
L: Settings: 0.9 Curve: 12s
10-1s S: t=const Settings: 8.8 Curve: 0.1s
I: OFF
10-2s
In this way, in accordance with the coordination tables, the selecti-
vity value will be 25 kA which, in this specific case, means total.
0.1 kA 1 kA 10 kA
Time-Current Curve
104s
T2N 160
103s E1 B1250
S200L C16
102s
T4N320
10s The settings of QF1, in accordance with what has been said in the
previous chapters, will be:
1s QF1, E1B 1250 PR121/P-LSI In1250
L: Settings: 0.47 Curve: 48s
10-1s S: t=const Settings: 3.5 Curve: 0.2s
I: OFF
10-2s
With these settings, total selectivity, i.e. up to the breaking capacity
of T4N equal to 36 kA, is obtained from the coordination tables.
0.1 kA 1 kA 10 kA
Appendix C
just seen above will be considered, assuming that there are two other 100 A loads:
QF1
E1B 1250 PR121/P-LSI In1250
Ik = 20kA
The most critical condition is analysed, taking into consideration the trip times with the lowest tolerance for the supply-side circuit-breaker
and the highest tolerance for the load side one: an overload of 416 A is presumed in QF2. The current which passes through QF1 will
be 616 A:
Time-Current Curve
104s
T4N 320
103s
372 s E1B 1250
102s 315 s
10s
1s
10-1s
Under these conditions, the QF1 E1B 1250 supply-side circuit-
breaker trips in a time of 315 s whereas the QF2 T4N 320 load-side
10-2s one trips in a slightly longer time of 372 s. For this current value,
416 A 616 A selectivity in the overload zone is not guaranteed.
0.1 kA 1 kA 10 kA
Of course the supply-side circuit-breaker does not trip under 416 A, whereas for sufficiently higher values than 416 A (e.g. 700 A) the
supply-side circuit-breaker trip time is greater than that of the load side one, since the sum of the currents of the other loads ‘weighs’
less on the total current which passes through them.
Finally, assessment of the currents which effectively pass through the circuit-breakers could make selectivity critical for certain overload
current values and in these cases the solution may be to use a higher function L curve.
Appendix D
Further considerations about the real circuit-breakers on the load side (supply-side circuit-
currents which circulate in the circuit- breaker passed through by a current higher than that
Appendix D
10s
1s
10-1s
L -Ls
0.1 kA 1 kA 10 kA
Appendix D
This installation is certainly the one met with most commonly in practice.
Having more than one circuit-breaker on the load side, there will be different current values between the supply-side circuit-breaker and
the load-side circuit-breaker towards which selectivity is looked for.
Therefore the trip time of the load-side circuit-breaker due to an overcurrent must be compared with the trip time of the supply-side
circuit-breaker in correspondence with the sum of all the currents which pass through it.
Example
In the installation in the figure, under normal conditions the supply-side circuit-breaker is passed through by a current of 360A whereas
any outgoing feeder is passed through by 90 A.
Possible settings of the circuit-breaker based on the currents which pass through the circuit-breakers are:
CB A: I1 = 0.92 x 400 = 368A (t1=3s)
CB B: I1 = 0.90 x 100 = 90A
The curves of the circuit-breakers with the settings indicated above are shown in the figure. From an initial analysis, time-current selectivity
would appear to be ensured between the two circuit-breakers.
T4S400 PR221 400 - T2S160 TMD
Vref = 400 104s
U LLLN/TN-S
103s
A
T5S 400 PR221DS-LSI R400 102s
Ib = 360.0 A
V = 400 V
I”k LLL = 50 kA
10s
B1 B2 B3 B3
T2S 160 T2S 160 T2S 160 T2S 160
1s
TMD100-1000 TMD100-1000 TMD100-1000 TMD100-1000
10-1s
Ib = 90.0 A Ib = 90.0 A Ib = 90.0 A Ib = 90.0 A
Iz = 134.0 A Iz = 134.0 A Iz = 134.0 A Iz = 134.0 A
10-2s
Let us now suppose that there are overload conditions with load 103s
L1 which absorbs a current of 200A.
Circuit-breaker B1 will therefore be passed through by 200A, 102s
whereas circuit-breaker A will be passed through by 470A (200+
90+ 90+90). 10s
With the settings hypothesised above, there are the conditions
shown in the figure, where both the circuit-breakers trip in a time 1s
of about 50s.
Therefore, with the settings hypothesised, in the case of overload 10-1s
there will not be selectivity between the pair of circuit-breakers
considered. 10-2s
0.1 kA 1 kA 10 kA
By modifying the settings of the supply-side circuit-breaker, for T4S400 PR221 400 - T2S160 TMD
104s
example by raising the trip time of protection L against overload:
CB A: I1 = 0.92 x 400 = 368A (t1=12s)
103s
Selectivity can be obtained in the overload zone since:
load-side circuit-breaker B trips in about 50s 102s
supply-side circuit-breaker A trips in about 200s.
10s
1s
In most cases, even not carrying out this analysis, the size and
distribution of the overload between the circuit-breakers allows a 10-1s
difference in the trip times able to realise time-current selectivity.
10-2s
0.1 kA 1 kA 10 kA
To carry out a simplified analysis, it must be assumed that the circuit is perfectly symmetrical and therefore that the total current recalled
by the loads is divided into equal parts in the three supply-side circuit-breakers.
Example
Under normal conditions, in the installation in the figure, the supply-side circuit-breakers are passed through by a current of 1000A,
whereas the two outgoing feeders are passed through by 1000A and the other by 2000 A.
In the analysis given here, selectivity between a supply-side circuit-breaker A and the largest outgoing feeder B1 is verified.
Possible settings of the circuit-breakers based on the currents which pass through the apparatus are:
CB A: I1 = 0.925 x 1250 = 1156A (t1=12s)
I2 = 8 x 1250 = 10000A (t2=0.4s)
I3=OFF
CB B1: I1 = 0.80 x 2500 = 2000A (t1=3s)
I2 = 3 x 2500 = 7500A (t1=0.2s)
I3=OFF
U Vref = 20000 V
E1B 1250 PR121/P - E3N 2500 PR121/P
104s
TM1 TM2 TM3
Vn2 = 400 V Vn2 = 400 V Vn2 = 400 V
Sn = 800 kVA Sn = 800 kVA Sn = 800 kVA 103s B1
A
CB A CB A CB A 102s
E1B 1250 E1B 1250 E1B 1250
PR121/P-LSI PR121/P-LSI PR121/P-LSI
In1250 In1250 In1250 10s
Ik = 55 kA
CB B1 CB B2
E3N 2500 T7H 1250 1s
PR121/P-LSI PR232/P-LSI
In2500 In1250
10-1s
L1 L1
Sn = 1385.64 kVA Sn = 692.82 kVA 10-2s
L Cosphi = 0.90 L Cosphi = 0.90
In = 2000 A In = 1000 A 0.1 kA 1 kA 10 kA 100 kA
The curves of the two circuit-breakers being examined with the settings indicated above are shown in the figure.
At first glance there would not seem to be time-current selectivity between the two pieces of apparatus.
Since these are circuit-breakers equipped with electronic releases, the trip times of the two devices at the significant currents are verified.
E1B 1250 PR121/P - E3N 2500 PR121/P E1B 1250 PR121/P - E3N 2500 PR121/P
104s 104s
103s 103s
102s 102s
10s 10s
1s 1s
10-1s 10-1s
10-2s 10-2s
0.1 kA 1 kA 10 kA 100 kA 0.1 kA 1 kA 10 kA 100 kA
Appendix D
Selection of the Icw must also take into account the real currents circulating in the circuit-breaker.
The A circuit-breakers are passed through by a maximum of:
36kA due to a fault between the circuit-breaker and the transformer
18kA due to a fault on the busbar.
For possible selectivity towards other load-side apparatus, circuit-breaker B1 must have:
Icw > 55kA.
Glossary
Is ultimate selectivity limit
Glossary
L.V. Breakers
Via Baioni, 35
24123 Bergamo - Italy
Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com