Eaton SPD Series: Surge Protective Device For Integrated Units

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Instruction Manual IM01005019E - Rev.

6 Effective October 2018

Eaton SPD Series


Surge Protective Device
For Integrated Units
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

Table of Contents

1.0 Introduction ....................................................................................... 1


1.1 Manual Organization ...................................................................1
1.2 Product Overview ....................................................................... 1
1.3 Safety Precautions ...................................................................... 1
1.4 Catalog Numbering System ...................................................... 1
1.5 Equipment Testing ..................................................................... 2

2.0 Installation ........................................................................................ 2


2.1 Preparation for Installation ........................................................ 2
2.2 Installation Locations ................................................................. 2
2.2.1 Direct Bus Mount Applications ......................................... 2
2.2.2 Connected Through a Circuit Breaker Applications ....... 2
2.3 Installation Procedures .............................................................. 2
2.3.1 Direct Bus Mount Applications ......................................... 2
2.3.2 Connected Through a Circuit Breaker Applications ....... 5

3.0 Operating Features .......................................................................... 6


3.1 General ........................................................................................ 6
3.2 Displays and Indicators ............................................................. 6
3.2.1 Basic Feature Package ...................................................... 6
3.2.2 Standard Feature Package ................................................ 7
3.2.3 Standard With Surge Counter Feature Package ............. 7
3.2.4 SPD Display Rotation.......................................................... 8
3.3 Remote Display Panel (RDP) Option ........................................ 8

3.4 IEC Approved Models................................................................. 8

4.0 Troubleshooting ............................................................................... 8

5.0 Specifications .................................................................................... 10

6.0 Ordering Guidelines ......................................................................... 11

7.0 Warranty ............................................................................................ 12

Eaton is a registered trademark of Eaton Corporation or its subsidiaries and affiliates. National Electric Code and NEC are registered trade-
marks of the National Fire Protection Association. Power Chain Management is a registered trademark of Eaton Corporation, UL is a federally
registered trademark of Underwriters Laboratories, Inc. All other trademarks are property of their respective companies.

B Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

1.0 Introduction WARNING


1.1 Manual Organization ARC FLASH DURING INSTALLATION COULD CAUSE INJURY. USE
APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC
This Installation Manual describes the safe installation, testing FLASH PROTECTION.
and operation of the Eaton® SPD Series Surge Protective Device
(SPD).
This manual is organized into seven sections, as follows: 1.4 Catalog Numbering System
1.0 Introduction Each Eaton SPD Series unit has a name plate that identifies
2.0 Installation the parameters used for manufacture. These parameters are
3.0 Operating Features expressed in letters and numbers, to reflect the Series, kA
Rating, Voltage Code, Feature Package, and Application.
4.0 Troubleshooting
5.0 Specifications Table 1. Catalog Numbering System
6.0 Ordering Guidelines
7.0 Warranty SPD 250 480D 2 J
1.2 Product Overview
The Eaton SPD Series protects critical electrical and electronic
equipment from damage by power surges. This is done by Series Voltage Code Application
shunting high energy lightning surges (and other transient dis-
turbances) away from the equipment being protected. It does
this in nanoseconds by providing a low impedance surge path to
ground while supporting power frequency voltage. kA Rating Feature Package

The Eaton SPD Series is designed to mount on Panelboards,


Switchgear, Switchboards, Busway, and Motor Control Centers
(MCCs). It is available with surge current capacity ratings from For example, a 480 volt Delta (3-wire plus Ground) for use in
50 to 400kA. an MCC application requires an SPD model SPD 250480D2J,
where:
The Eaton SPD Series is available in three feature pack-
ages (Basic, Standard, and Standard with Surge Counter), as SPD = SPD model,
described in Section 3, "Operating Features." Each model is avail- 250 = the kA rating (50 – 400 kA),
able in Delta, Wye, and Split Phase wiring configurations.
480D = the voltage,
All Eaton SPD Series models have been tested and certified by
2 = the feature package (Basic, Standard, Standard With Surge
Underwriter’s Laboratory (UL®), to comply with UL Standard
Counter), and,
1449, 4th Edition.
J = the Application Suffix (such as Direct Bus Mounted in a pan-
Eaton’s One-Port low-voltage Surge Protective Device Wye
Models SPD120480Y2C, SPD160480Y2C, SPD200480Y2C elboard or Connected Through a Circuit Breaker).
and Delta Models SPD120480D2C, SPD160480D2C, These numbers appear as part of the product label attached to
SPD200480D2C meet the requirements of IEC 61643-11 / EN the front left side of the SPD. See Figure 1.
61643-11, Part 11: Test Class II, and are intended to be installed
in indoor applications with a degree of protection rated IP 00.

1.3 Safety Precautions


A licensed/qualified electrician must complete all instructions
in this manual in accordance with the National Electric Code
(NEC®), state, and local codes, or other applicable country
codes. All applicable local electrical codes supersede these
instructions.

WARNING
IMPROPER INSTALLATION COULD CAUSE DEATH, INJURY AND
EQUIPMENT DAMAGE. FOLLOW ALL WARNINGS AND CAUTIONS.
COMPLETELY READ AND UNDERSTAND THE INFORMATION IN THIS
INSTRUCTION MANUAL BEFORE ATTEMPTING TO INSTALL OR OPER-
ATE THIS EQUIPMENT.

IMPROPER WIRING COULD CAUSE DEATH, INJURY AND/OR EQUIP-


MENT DAMAGE. ONLY LICENSED/QUALIFIED ELECTRICIANS WHO ARE Figure 1. Product Label
TRAINED IN THE INSTALLATION AND SERVICE OF ELECTRICAL SER-
VICES ARE TO INSTALL AND SERVICE THIS EQUIPMENT.

HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE SPD DURING


NORMAL OPERATION. FOLLOW ALL SAFE WORK PRACTICES TO AVOID
ELECTRICAL SHOCK.

Eaton www.eaton.com 1
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

1.5 Equipment Testing NOTICE


A POOR GROUND, OR GROUNDING/BONDING VIOLATIONS, COULD
PREVENT THE SPD FROM PERFORMING AS SPECIFIED.
WARNING
DO NOT USE THE SPD TO CARRY OR PASS THROUGH GROUND TO
CONDUCTING DIELECTRIC, MEGGER, OR HI-POTENTIAL TESTING OTHER DEVICES OR LEADS. DAMAGE TO THE EQUIPMENT MAY
WITH THE SPD INSTALLED WILL CAUSE INTERNAL DAMAGE TO THE RESULT.
SPD. THE SPD WILL ALSO CAUSE THE TEST TO FAIL.
• Check the facility grounding system. All grounding, bonding,
Every Eaton SPD Series unit is tested at the factory for dielec- and earthing must meet the NEC and any other national, state
tric breakdown. No further SPD testing is required for installa- and local electrical codes.
tion.
If you desire to test distribution equipment by performing 2.2 Installation Locations
dielectric, megger, or hi-potential tests, any installed SPD must Eaton's SPD Series can be installed directly to the bus for
be disconnected from the power distribution system to prevent Panelboard applications.
damage to the unit.
The SPD can also be connected through a circuit breaker for
Follow this procedure to safely disconnect the SPD: installations in Panelboards, Switchboards, Switchgear, MCC’s
and Busway applications.
1. Remove bus connected SPDs completely from the instal- Follow these guidelines to determine the best location for
lation prior to performing any form of hi-potential testing. mounting this product.
2. Isolate SPDs connected via conductors as follows:
2.2.1 Direct Bus Mount Applications
a. 3-wire delta SPDs: Turn off the circuit breaker to • Install the SPD on the load side of the main breaker. Connect
isolate the SPD, if connected through a circuit the SPD directly to the bus located as close as possible to
breaker. the main breaker.
b. Wye connected SPDs: Turn off the circuit breaker and
2.2.2 Connected Through a Circuit Breaker Applications
remove the Neutral connection.
3. Remove MCC units with SPDs from the MCC structure.
• Install the SPD next to the first breaker after the incoming
main lugs or main breaker.
2.3 Installation Procedures
2.0 Installation
2.3.1 Direct Bus Mount Applications

WARNING 1. Verify that the SPD you are about to install is rated
INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRI- for the application voltage and system. See Table 5 in
CAL SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS Section 6, "Ordering Guidelines".
CONDITION, RESULTING IN INJURY OR EQUIPMENT DAMAGE. 2. Follow all national, state and local electrical codes when con-
necting the SPD.
2.1 Preparation for Installation 3. Before mounting the SPD, first determine the bus bar con-
figuration. If the panelboard uses an offset B-Phase bus bar
configuration, no action is required. If the panelboard uses a
CAUTION coplanar bus bar configuration, remove the bus bar
EATON SPD SERIES PRODUCTS MUST BE INSTALLED OR REPLACED extension bushing from the back of the SPD and discard.
BY A QUALIFIED ELECTRICIAN TO AVOID INJURY OR EQUIPMENT See Figure 2.
DAMAGE. 4. Mount the SPD to the support brackets (customer supplied)
using #10 fasteners and tighten to 4.1 Nm (36 in-lbs). See
Before installing an Eaton SPD Series unit, do the following: Figures 4 and 5 for mounting details.
5. Install the bus mount fasteners and tighten to 4.1 Nm (36
• Verify that the area is clear of any dirt, debris or clutter that in-lbs). See Figure 3.
may hamper the installation process.
• Verify that there is enough space in the cabinet or MCC to
install the SPD. See Section 2.3, "Installation Procedures" for
dimensions.
• Confirm that all tools and equipment needed for the installa-
tion are available.
• Confirm that the system voltage and wiring configuration is
the same as the SPD you are installing. Check the voltage
rating label on the front left side of the SPD. See Figure 1.

WARNING
TURN OFF THE POWER SUPPLY BEFORE WORKING IN ANY ELECTRI-
CAL CABINET OR ON ANY CIRCUIT BREAKER PANEL. FAILURE TO DO
SO COULD RESULT IN INJURY OR DEATH FROM ELECTRICAL SHOCK. Figure 2. Bus Bar Extension Bushing
2 Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

6. Select the correct wiring diagram for the SPD you are install-
ing. You must refer to this diagram while wiring the SPD.
See Figures 6, 7, 8, and 9, on page 4.

Figure 3. Bus Connection

3X Ø.221
BUS MTG
MOUNTING 8.80 [223.5]
4X MTG .19 [4.8] 4.40 [111.8]
BUS .34 [8.5] .04 [1.0] 2.015 [51.2] 2.015 [51.2]

.95 [24.0]

5.40 [137.0]
MTG 3.42 [86.9]
4.66 [118.4]
3.42 [86.9]

2.52 [64.0] .26 [6.7] 3.42 [86.9] 4X Ø.218 MOUNTING


3.45 [87.7] TERMINALS 8.74 [222.0]
4X #10-32 X .38 DP
9.50 [241.3] BRASS TERMINALS

Figure 4. Dimensions for 50-200kA Units

MOUNTING 8.80 [223.5]


4X MTG 2.52 [63.9] 3.42 [86.9]

3.42 [86.9]
MTG 3.42 [86.9]
5.40 [137.0]
4.66 [118.4]

1.71 [43.5]

4.85 [123.1] 4X Ø.218 MOUNTING


TERMINALS 8.74 [222.0]
5.78 [146.8] 9.50 [241.3] 4X #10-32 X .38 DP
BRASS TERMINALS

Figure 5. Dimensions for 250-400kA Units

Eaton www.eaton.com 3
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

Figure 6. Wiring - Single Phase Units (230 L) Figure 8. Wiring - 3-Phase Delta Units

Figure 7. Wiring - Split Phase Units Figure 9. Wiring - 3-Phase Wye Units

Figure 10. Wiring - High Leg Delta Units

NNote: Please consult the factory for 240 delta high leg (4W+G) applica-
tions with high leg on the 'C' Phase.

4 Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

7. Connect the System Ground wire (green) to the SPD’s


Surge Ground connection using a ring terminal suitable
for use with a #10 fastener and a #10-32 x 3/8" fastener
(customer supplied). Tighten the Surge Ground connection
to 4.1 Nm (36 in-lbs). If the system uses an isolated ground,
connect the isolated ground wire to Surge Ground. There
are two Surge Ground connection points provided on the
SPD. Connect only one of them. See Figure11.

Figure 13. Form C Connection


10. Install the dead-front panel to complete the installation.

2.3.2 Connected Through a Circuit Breaker Applications

1. Verify that the SPD you are about to install is rated for
the application voltage and system. See Table 5 in Section 6,
Figure 11. Ground Connection "Ordering Gidelines".
2. Follow all national, state and local electrical codes when
8. If equipped, connect the System Neutral wire (grey or connecting the SPD.
white) to the SPD. Connect the System Neutral wire to the 3. Mount the SPD to the support brackets (customer sup-
SPD’s Neutral connection using a ring terminal suitable for plied) using #10 x 2-3/4" fasteners and tighten to 4.1 Nm
use with a #10 fastener and a #10-32 x 3/8" fastener (cus- (36 in-lbs). For 50-200kA models, see Figure 4 for mount-
tomer supplied). Tighten the Neutral connection to 4.1 Nm ing dimensions. For 250-400kA models, see Figure 5 for
(36 in-lbs). There are two Neutral connection points provided mounting dimensions. Note: Mount the SPD as close as
on the SPD. Connect only one of them. See Figure 12. possible to the circuit breaker.
4. Determine the wire length required to connect to the
breaker and cut Phase wires to the appropriate length.
(To maximize SPD performance, wire length should be
as short as possible). Note: For wire lengths longer than
4", Phase wires should be twisted once for each 4" of
wire length to maximize SPD performance.
5. Connect Phase wire to circuit breaker. NEC requires that
conductors to a surge device be protected by an overcur-
rent protection device. The cables on the SPD are #10 AWG,
therefore would require a 30A 3-pole breaker. See Figure 14,
and the wiring diagrams shown in Figures 6, 7, 8 and 9.

Figure 12. Neutral Connection

9. The SPD (Standard and Standard with Surge Counter mod-


els) also has an available connection for remote monitoring
of the Form C relay contacts. See Figure13. This is a green
connector located on the side of the SPD. To make the con-
nection, remove the green connector and install the remote
monitor leads (connector supports 12-24AWG wire). Fasten
the remote monitoring wires to the N.O., N.C and COM
connection points per the label on the front of the SPD.
Contacts are rated: 150 Vac or 125 Vdc at 1A. Follow all
national, state and local electrical codes. With wiring com-
plete, plug the green connector into the SPD.
Figure 14. Phase Connections

Eaton www.eaton.com 5
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

6. Connect the System Ground wire (green) to the SPD’s 2. Connect the RDP cable to the SPD. Use tie wraps
Surge Ground connection using a ring terminal suitable (already on the SPD) to secure the cable to the
for use with a #10 fastener and #10-32 x 3/8" fastener SPD. See Figure 16. Cable can be routed as a right
(customer supplied). Tighten the Surge Ground connec- or left dress.
ion to 4.1 Nm (36 in-lbs). If the system uses an isolated
ground, connect the isolated ground wire to Surge
Ground. There are two Surge Ground connection points
provided on the SPD. Connect only one of them. See
Figure 11.
7. If equipped, connect the System Neutral wire (grey or
white) to the SPD. Connect the System Neutral wire to
the SPD’s Neutral connection using a ring terminal suit
able for use with a #10 fastener and a #10-32 x 3/8" fas-
tener (customer supplied). Tighten the Neutral connec-
tion to 4.1 Nm (36 in-lbs). There are two Neutral connection
points provided on the SPD. Connect only one of them.
See Figure 12.
Figure 16. RDP to SPD Connection
8. The SPD (Standard and Standard with Surge Counter
models) also has a connection available for remote
monitoring of the Form C relay contacts. See Figure 14. 3. Connect the RDP cable to the display. Use tie wraps
This is a green connector located on the side of the SPD. (already on the RDP) to secure the cable to the
To make the connection, remove the green connector RDP. See Figure 17.
and install the remote monitor leads (connector supports
12-24 AWG wire). Fasten the remote monitoring wires to
the N.O., N.C. and COM connection points per the label
on the front of the SPD. Contacts are rated: 150 Vac or
125 Vdc at 1A. Follow all national, state and local electrical
codes. With wiring complete, plug the green connector into
the SPD.
9. The final step of the SPD installation depends on the spe-
cific application. The various applications are listed below
by catalog suffix.
a. Suffix 'B': This is the Remote Display Panel (RDP)
option. The RDP option requires the addition of a fac-
tory supplied RDP cable. See Section 3.3, "Remote
Display Panel (RDP) Option" for Cable Catalog num-
bers.
1. Install the RDP using cutout and mounting dimen-
sions provided in Figure 15.

Figure 17. RDP Cable to Display Connection

b. Suffix 'C': This unit is intended for use in Panelboard,


Switchboard, and Busway applications.
1. Ensure that the dead-front or door has the appro-
priate cut-out to accommodate the SPD Display.
See Figure 4 or Figure 5.
2. Install dead-front or door and secure.
c. Suffix 'J': This unit is intended for MCC applications
that require a NEMA 12 enclosure rating.
1. Ensure that the MCC bucket door has the appro-
priate cut-out to accommodate the SPD Display.
See Figure 4 or Figure 5.
2. Place an appropriate NEMA 12 rated gasket around
the Display opening on the inside of the door.
3. Install the door and secure.

Figure 15. RDP Cutout and Mounting

6 Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

3.0 Operating Features 3.2.2 Standard Feature Package

3.1 General The Eaton SPD Series Standard Feature Package display is
shown in Figure 19.
The Eaton SPD Series comes in three feature packages: Basic,
Standard, and Standard with Surge Counter. The operating spe-
cifics of each feature package are described below.
The Eaton SPD Series requires no operator involvement, other
than to monitor the display panel to determine status of the
SPD.
After system power is applied, the SPD automatically begins
protecting downstream electrical equipment from voltage tran-
sients.
Some SPD units have a Form C relay contact that allows for the
remote indication of SPD status. Form C contact wires are con-
nected via a three terminal connector. See Figure 13.

3.2 Displays and Indicators


All Eaton SPD Series units (Basic, Standard, and Standard With Figure 19. Standard Feature Package Display
Surge Counter) use a display panel to indicate system status.
The display panel is slightly different for each feature package. The Standard Feature Package has the following features:
Each display has both green and red light emitting diodes • All features of the Basic Feature Package.
(LEDs) to indicate the status of the protection on each phase. • One Form C relay contact rated at 150Vac or 125Vdc @1A.
Green indicates the phase is fully protected. Red indicates a
loss of protection. Wye, Split Phase and High-Leg Delta units • Normal operating conditions. N.O. = OPEN. N.C =
have an additional set of green/red LEDs to indicate status of CLOSED.
Neutral/Ground protection. • Loss of protection on any phase or loss of power. N.O. =
When the LEDs turn red, an audible alarm will also sound on CLOSED. N.C. = OPEN.
units equipped with an audible alarm. • Audible alarm with Reset push button.
Specific operating conditions displayed for each Eaton SPD • EMI/RFI filtering.
Series Feature Package are described below.
3.2.1 Basic Feature Package 3.2.3 Standard With Surge Counter Feature Package
The Eaton SPD Basic Feature Package display is shown in The Eaton SPD Series Standard With Surge Counter Feature
Figure 18. Package display is shown in Figure 20.

Figure 18. Basic Feature Package Display


Figure 20. Standard With Surge Counter Feature Package
The Basic Feature Package has the following features: Display

The Standard With Surge Counter Feature Package has the fol-
• Green LEDs: Illumination indicates the phase is fully pro-
lowing features:
tected, and operating normally, with all protection active and
available. Green LEDs also indicate Neutral to Ground protec- • All features of the Standard Feature Package.
tion on units with a Neutral wire. Green LEDs do not indicate • LCD screen that displays surge count.
on/off status of power.
• Reset button to RESET the surge counter to zero.
• Red LEDs: Illumination indicates a loss of protection, and
that one or more protective devices are now inactive and
unavailable for that Phase. Red LEDs also indicate Neutral to
Ground protection on units with a Neutral wire. Red LEDs do
not indicate on/off status of power.

Eaton www.eaton.com 7
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

3.2.4 SPD Display Rotation 3.3 Remote Display Panel (RDP) Option
The SPD display can be rotated on the SPD enclosure, up to 360 The Eaton Series SPD displays may be monitored on a remote
degrees. This allows you to position the display for the best vis- display panel (RDP). This is indicated by the catalog style with a
ibility regardless of the position in which the SPD is installed. 'B' suffix (such as SPD250480D2B).
Rotations are at 90, 180, and 270 degrees. A separately purchased RDP cable is required to connect the
SPD unit to the display.
For a typical horizontal mounting see Figure 21. For a typical ver-
tical mounting see Figure 22. Table 2 lists these cables and their part numbers.
Reposition the SPD display as follows:
Table 2. RDP Cable Options
1. Remove power from the unit. Description Catalog No.
2. Remove and discard the perforated overlay material at the
4 ft. Cable for RDP SPDRDCAB04
two opposite corners of the display. 8 ft. Cable for RDP SPDRDCAB08
3. Remove the two phillips head screws that hold the display. 12 ft. Cable for RDP SPDRDCAB12
4. Rotate the display to the desired position. Be careful not to
overstress the display ribbon cable. 3.4 IEC Approved Models
5. Place the display back onto the SPD enclosure. Again, be Eaton’s One-Port low-voltage Surge Protective Device Wye
careful not to overstress or crimp the ribbon cable. Models SPD120480Y2C, SPD160480Y2C, SPD200480Y2C
and Delta Models SPD120480D2C, SPD160480D2C,
6. Replace the two phillips head screws. Tighten screws to SPD200480D2C meet the requirements of IEC 61643-11 / EN
1.35 Nm (12 in-lbs). 61643-11, Part 11: Test Class II, and are intended to be installed
7. Restore power to the unit. in indoor applications with a degree of protection rated IP 00.
The SPD Delta and Wye Models are intended for use with a 3
Phase TN-S System with PE and Neutral Distribution, 5 conduc-
tor with a minimum 10 AWG or 6 mm2. The Delta Models are
also intended for use with a 3 Phase TN-C System with PEN
Distribution, 4 conductor with a minimum 10 AWG or 6mm2.
Screws used for connection to ground shall be #10-32 x 3/8”
and shall not be zinc or aluminum. This product is not service-
able and contains no replaceable parts.
Additional product information and ratings for IEC Applications:
−− The SPD contains internal disconnects with a short circuit
current rating ISCCR of 200kA.
−− Residual Current IPE for this product is 5 mA.
Figure 21. Typical Horizontal Display Mounting −− Operating temperature is Normal -5°C to 40°C (23°F to
104°F.
−− Humidity range is 5% through 95% non-condensing.
−− The SPD may be mounted directly to earthed conductive
surface, installed as per this manual.
−− Temporary overvoltage rating UT = 402.6 V.
−− Withstand or safe failure mode, for tT = 120 minutes,
UT = 526 V.
−− Modes of protection as marked on a Wye SPD = L - L, L - N,
L - G(PE), N - G(PE).
−− Modes of protection as marked on a Delta SPD = L - L,
L - G(PE).

Figure 22. Typical Vertical Display Mounting

8 Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

4.0 Troubleshooting
Many SPD failures result from improper installation. Once the
SPD is installed properly, it is a highly reliable unit.
If the SPD does not function properly, first confirm that it is
installed properly. See Section 2, “Installation.”
If the SPD malfunctions after it has been operating routinely,
refer to Table 3. This Troubleshooting Chart identifies possible
causes and solutions to the malfunction. Further assistance
may be obtained by calling Eaton’s Applications Engineers, at
1-800-809-2772, option 4, sub-option 2, including being directed
to the warranty process if applicable.
Table 3. Troubleshooting Chart

Condition Probable Cause Solution

Green LEDs ON (1 per phase) and one Green LED ON for Normal operation N/A.
Neu/Gnd Protection
Audible Alarm OFF, Form C (N.C.) contact in the CLOSED Normal operation N/A.
state
Phase Green LED is OFF, same Phase Red LED is ON, Phase protection compromised or lost Replace SPD
Audible Alarm is ON
Extended Temporary Overvoltage (TOV) Check electrical system for TOV sources, correct,
replace SPD
Significant surge event
Replace SPD
Neu/Gnd Green LED is OFF, Neu/Gnd Red LED is ON, Neu/Gnd protection is compromised or lost Replace SPD
Audible Alarm is ON (for models with Neutral connections)
Significant surge event Replace SPD
All phase Green LEDs OFF, all phase RED LEDs ON, Audible All phase protection is compromised or lost Replace SPD
Alarm is ON
SPD rated voltage is less than system voltage Replace SPD with correct voltage model

Extended Temporary Overvoltage (TOV) Check electrical system for TOV sources, correct,
replace SPD
Significant surge event
Replace SPD

One of the display Red LEDs is ON. Audible Alarm is OFF Audible Alarm Silence button has been depressed and Normal operation
Alarm is silenced
If power is cycled and a fault condition still exists, the
Audible Alarm will reactivate
All Green and Red LEDs are OFF, LCD display (on Surge SPD is not connected to a power source Check system voltage at SPD connection
Counter models) is OFF
Check SPD connections

Eaton www.eaton.com 9
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

5.0 Specifications
Table 4. Specifications
Description Specification

Surge current capacity per phase 50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available

Nominal discharge current (In) 20kA

Short circuit current rating (SCCR) 200kA

SPD Type Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter feature packages = Type 2
Standard split phase voltages available 120/240
Single phase 230
Three phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600
Three phase delta system voltages 240, 480, 600
Three phase high leg delta system voltages 120/240
Input Power Frequency 50/60 Hz
Power consumption (Basic units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes 0.5W
400Y and 480Y and 480D voltage codes 1.1W
600Y and 600D voltage codes 1.3W
Power consumption (Standard and Standard with Surge Counter units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes 0.6W
400Y, 480Y, and 480D Basic voltage codes 1.7W
600Y and 600D voltage codes 2.1W
Protection modes Single split phase .....................L-N, L-G, N-G, L-L
Single phase .............................L-N, L-G, N-G
Three phase Wye...................... L-N, L-G, N-G, L-L
Three phase delta......................L-G, L-L
Three phase high leg delta........L-N, L-G, N-G, L-L
Maximum continuous operating voltage (MCOV)
208Y, 220Y, 240S, 240D, and 240H voltage codes 150 L-N,150 L-G, 150 N-G, 300 L-
230L, 400Y and 480Y voltage codes 320 L-N, 320 L-G, 320 N-G, 640 L-L L
600Y voltage code 420 L-N, 420 L-G, 420 N-G, 840 L-L
240 D voltage code 320 L-G, 320 L-L
480 D voltage code 640L- L-G, 640 L-L
600D voltage code 840 L-G, 840 L-L

Ports 1
Operating temperature -40 through 50° C (-40 through 122° F)
Operating humidity 5% through 95%, non-condensing
Operating altitude Up to 16,000 ft (5000 m)
Seismic withstand capability Meets or exceeds the requirements specified in the IBC® 2006, CBC 2007, and UBC® Zone 4
Weight 50-200kA - Approximately 1.6 kg (3.5 lbs) – 250 - 400kA - Approximately 3.2kg (7.0 lbs)
Form C relay contact ratings 150 Vac or 125 Vdc, 1A maximum
Form C relay contact loogic Power on, normal state - NO contact = OPEN, NC contact = CLOSED
Power off, fault state, - NO contact = CLOSED, NC contact = OPEN
EMI/RFI filtering attenuation (Standard and Standard With Surge Counter Up to 50 dB from 10 kHz to 100 MHz
Agency certifications and approvals UL1449 4th Edition recognized component for the US and Canada, UL1283 7th Edition (Type 2 SPDs only)
IEC 61643-11/EN 61643-11, Part 11: Test Class II. See Section 6.0 Ordering Guidelines for specific models.
Warranty 10 Years, 15 Years if you register on www.eaton.com/spd and click the warranty registration icon.
UL 96A Compliant Yes
NFPA 780 Compliant Yes
ROHS Compliant Yes
Wire Length and AWG Factory prewired with 18 inches of 10 AWG wire for Mounting Suffix B,C,J

10 Eaton www.eaton.com
Eaton SPD Series Instruction Manual IM01005019E - Rev.6
Surge Protective Device for Integrated Units Effective October 2018

6.0 Ordering Guidelines


Table 5. Eaton SPD Series

SPD 250 480D 2 J

SPD
kA Rating
Voltage Code
Options
50kA Per Phase Options
80kA Per Phase Integrated Units
100kA Per Phase 240S = 120/240 Split Phase
120kA Per Phase 208Y = 120/208 Wye (4W + G)
160kA Per Phase 220Y = 127/220 Wye (4W + G)
200kA Per Phase 400Y = 230/400 Wye (4W + G)
250kA Per Phase 480Y = 277/480 Wye (4W + G)
300kA Per Phase 600Y = 347/600 Wye (4W + G)
400kA Per Phase 240D = 240 Delta (3W + G)
480D = 480 Delta (3W + G)
600D = 600 Delta (3W + G)
240H = 240 Delta High Leg (4W + G) on 'B' Phase
230L = 230 Single Phase*
NOTE: Please consult the factory for 240 Delta HIgh
Leg (4W+G) applications with high leg on 'C' Phase

Feature Package Application Suffix


Options Options
1 = Basic. Integrated Units
Dual colored LED per Phase to indicate Protection status
Dual colored LED to indicate protection status of the N-G Mode on A = Panelboards, Direct Bus Mounted
units with a Neutral Wire B = Switchgear (Includes remote display panel & mounting hardware). Order cable
2 = Standard. separately
Dual colored LED Per Phase to indicate Protection Status C = Panelboards, Switchboards, Busway
Dual colored LED to indicate Protection Status of the N-G Mode on J = Motor Control Centers
units with a Neutral Wire
Audible alarm with Silence button NOTE: Units used in Panelboard applications are available in
Form 'C' Relay Contact. See Table 4 Specifications 50 – 200kA ratings only
EMI/RFI filtering Providing up to 50dB of Noise Attenuation from NOTE: Use the 'C' option for Panelboard Applications when
10KHz to 100Mhz unit is connected through a Circuit Breaker
3 = Standard With Surge Counter
Dual colored LED Per Phase to indicate Protection Status
Dual colored LED to indicate Protection Status of the N-G Mode on
units with a Neutral Wire
Audible alarm with Silence button
Form 'C' Relay Contact
EMI/RFI filtering Providing up to 50dB of Noise Attenuation from
10kHz to 100Mhz
Surge Counter with Reset Button

** Eaton’s Wye Catalog Numbers SPD120480Y2C, SPD160480Y2C, and SPD200480Y2C and Eaton’s Delta Catalog Numbers SPD120480D2C, SPD160480D2C, and SPD200480D2C
meet the requirements of IEC 61643-11/EN 61643-11, Part 11: Test Class II, and intended to be installed in indoor applications with a degree of protection rated IP 00.

Example: SPD 250480D2J = SPD Series, 250kA Per Phase, 480D Voltage, Standard Feature Package, Motor Control Center Application.

Eaton www.eaton.com 11
Instruction Manual IM01005019E - Rev. 6 Eaton SPD Series
Effective October 2018 Surge Protective Device for Integrated Units

7.0 Warranty Copyright © 2013 by Eaton, Moon Township, PA, USA. All rights
reserved. No part of this document may be reproduced in any way
Eaton warrants these products for a period of 10 years from the
without the express written approval of Eaton.
date of delivery to the purchaser , 15 years if you register on www.
eaton.com/spd and click the warranty registration icon to be free
Specifications contained herein are subject to change without
from defects in both workmanship and materials. Eaton assumes no
notice.
risk or liability for results of the use of the products purchased from
it, including but without limiting the generality of the foregoing: (1)
EATON - CONFIDENTIAL AND PROPRIETARY NOTICE TO
The use in combination with any electrical or electronic components,
PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL
circuits, systems, assemblies, or any other materials or substances;
INFORMATION IN THIS DOCUMENT, INCLUDING THE DRAWING
(2) Unsuitability of any product for use in any circuit or assembly.
AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL
Purchaser’s rights under the warranty shall consist solely of requir- AND IS THE EXCLUSIVE PROPERTY OF EATON, AND IS MERELY
ing Eaton to repair, or at Eaton's sole discretion, replace, free of ON LOAN AND SUBJECT TO RECALL BY EATON AT ANY TIME.
charge, F.O.B. factory, and defective items received at said factory BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT
within said term determined by Eaton to be defective. The giving of ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT
or failure to give any advice or recommendations by Eaton shall not BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF
constitute any warranty by or impose any liability upon Eaton. The EATON, AND THAT NO PORTION OF THIS DOCUMENT MAY BE
foregoing constitutes the sole and exclusive liability of Eaton AND COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR
IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED, WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING
IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY, CONTRACTUAL PROVISIONS, THIS NOTICE SHALL GOVERN THE
FITNESS FOR PURPOSE SOLD, DESCRIPTION, QUALITY, STATUS OF THIS DOCUMENT.
PRODUCTIVENESS OR ANY OTHER MATTER.
In no event shall Eaton be liable for special or consequential dam- DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
ages or for delay in performance of the warranty.
The information, recommendations, descriptions and safety nota-
tions in this document are based on Eaton's ("Eaton") experience
This warranty does not apply if the product has been misused, and judgment and may not cover all contingencies. If further infor-
abused, altered, tampered with, or used in applications other than mation is required, an Eaton sales office should be consulted. Sale
specified on the nameplate. At the end of the warranty period, of the product shown in this literature is subject to the terms and
Eaton shall be under no further warranty obligation expressed or conditions outlined in appropriate Eaton selling policies or other
implied. contractual agreement between Eaton and the purchaser. THERE
ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES,
The product covered by this warranty certificate can only be repaired EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF
or replaced by the factory. For help on troubleshooting the SPD, or FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY,
for warranty information, call 1-800-809-2772, Option 4, sub-option OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
2. Repair or replacement units will be returned collect. If Eaton CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT
finds the return to be a manufacturer’s defect, the product will be STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF
returned prepaid. THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY
ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in


contract, in tort (including negligence), strict liability or otherwise
for any special, indirect, incidental or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims
against the purchaser or user by its customers resulting from the
use of the information, recommendations and descriptions con-
tained herein.

Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland OH 44122
United States
1-800-809-2772, option 4, sub-option 2
Eaton.com

© 2018 Eaton Eaton is a registered trademark.


All Rights Reserved
Printed in USA All other trademarks are property of their
Publication No. IM01005019E TBG000335 respective owners.
October 2018