Vemu HVDC Notes
Vemu HVDC Notes
(20A02604a )
LECTURE NOTES
Prepared by:
Mr. S. Venkat Rao, Assistant Professor
Department of Electrical and Electronics Engineering
● Various configurations of the above, Principle of operation, Characteristics of various FACTS devices
Course Outcomes (CO): After completion of the course, the student can able to
CO-1 Understand the necessity of HVDC systems as emerging transmission networks
CO-2: Understand the necessity of reactive power compensation devices
CO-3: Design equivalent circuits of various HVDC system configurations
CO-4: Design and analysis of various FACTS devices
Unit – I: INTRODUCTION
Electrical Transmission Networks, Conventional Control Mechanisms-Automatic Generation Control, Excitation Control,
Transformer Tap-Changer Control, Phase-Shifting Transformers; Advances in Power-Electronic Switching Devices, Principles and
Applications of Semiconductor Switches; Limitations of Conventional Transmission Systems, Emerging Transmission Networks,
HVDC and FACTS
Unit – II: HIGH VOLTAGE DC TRANSMISSION – I
Types of HVDC links - Monopolar, Homopolar, Bipolar and Back-to-Back, Advantages and disadvantages of HVDC
Transmission, Analysis of Greatz circuit, Analysis of bridge circuit without overlap, Analysis of bridge with overlap less than 600,
Rectifier and inverter characteristics, complete characteristics of rectifier and inverter, Equivalent circuit of HVDC Link.
Unit – III: HIGH VOLTAGE DC TRANSMISSION – II
Desired features and means of control, control of the direct current transmission link, Constant current control, Constant ignition
angle control, Constant extinction angle control, Converter firing-angle control-IPC and EPC, frequency control and Tap changer
control, Starting, Stopping and Reversal of power flow in HVDC links.
Unit – IV: FLEXIBLE AC TRANSMISSION SYSTEMS-I
Types of FACTS Controllers, brief description about various types of FACTS controllers, Operation of 6-pulse converter,
Transformer Connections for 12-pulse, 24-pulse and 48-pulse operation, principle of operation of various types of Controllable
shunt Var Generation, Principle of switching converter type shunt compensator, principles of operation of various types of
Controllable Series Var Generation, Principle of Switching Converter type series compensator
Unit – V: FLEXIBLE AC TRANSMISSION SYSTEMS-II
Unified Power Flow Controller (UPFC) – Principle of operation, Transmission Control Capabilities, Independent Real and Reactive
Power Flow Control; Interline Power Flow Controller (IPFC) – Principle of operation and Characteristics, UPFC and IPFC control
structures (only block diagram description), objectives and approaches of voltage and phase angle regulators
Textbooks:
1. Narain G. Hingorani and Laszlo Gyugyi, Understanding FACTS: Concepts and Technology of Flexible AC Transmission
Systems, IEEE Press, Wiley-Interscience, New Jersey, 2000.
2. E.W. Kimbark, Direct current transmission, Vol. I, Wiley Interscience, New York, 1971
Reference Books:
1. K R Padiyar, FACTS Controllers in Power Transmission and Distribution, New Age International Publishers, New Delhi, 2007.
2. AnriqueAcha, Claudio R. Fuerte-Esquivel, Hugo Ambriz-Pérez and César Angeles-Camacho, FACTS: Modelling and
Simulation in Power Networks, John Wiley & Sons, West Sussex, 2004.
1
distance is one at which the cost of the two systems is the same. It is understood from the below
figure that a DC line is economical for long distances which are greater than the break-even
distance.
Technical Performance:
Due to its fast controllability, a DC transmission has full control over transmitted power,
an ability to enhance transient and dynamic stability in associated AC networks and can limit
fault currents in the DC lines. Furthermore, DC transmission overcomes some of the following
problems associated with AC transmission.
Stability Limits:
The power transfer in an AC line is dependent on the angle difference between the
voltage phasors at the two line ends. For a given power transfer level, this angle increases with
distance. The maximum power transfer is limited by the considerations of steady state and
transient stability. The power carrying capability of an AC line is inversely proportional to
transmission distance whereas the power carrying ability of DC lines is unaffected by the
distance of transmission.
3
Voltage Control:
Voltage control in ac lines is complicated by line charging and voltage drops. The voltage
profile in an AC line is relatively flat only for a fixed level of power transfer corresponding to its
Surge Impedance Loading (SIL). The voltage profile varies with the line loading. For constant
voltage at the line ends, the midpoint voltage is reduced for line loadings higher than SIL and
increased for loadings less than SIL.
The maintenance of constant voltage at the two ends requires reactive power control as
the line loading is increased. The reactive power requirements increase with line length.
Although DC converter stations require reactive power related to the power transmitted, the DC
line itself does not require any reactive power. The steady-state charging currents in AC cables
pose serious problems and make the break-even distance for cable transmission around 50kms.
Line Compensation:
Line compensation is necessary for long distance AC transmission to overcome the
problems of line charging and stability limitations. The increase in power transfer and voltage
control is possible through the use of shunt inductors, series capacitors, Static Var Compensators
(SVCs) and, lately, the new generation Static Compensators (STATCOMs). In the case of DC
lines, such compensation is not needed.
Problems of AC Interconnection:
The interconnection of two power systems through ac ties requires the automatic
generation controllers of both systems to be coordinated using tie line power and frequency
signals. Even with coordinated control of interconnected systems, the operation of AC ties can be
problematic due to:
1. The presence of large power oscillations which can lead to frequent tripping,
2. Increase in fault level, and
3. Transmission of disturbances from one system to the other.
4
The fast controllability of power flow in DC lines eliminates all of the above
problems. Furthermore, the asynchronous interconnection of two power systems can only be
achieved with the use of DC links.
Ground Impedance:
In AC transmission, the existence of ground (zero sequence) current cannot be permitted
in steady-state due to the high magnitude of ground impedance which will not only affect
efficient power transfer, but also result in telephonic interference. The ground impedance is
negligible for DC currents and a DC link can operate using one conductor with ground return
(monopolar operation).
The ground return is objectionable only when buried metallic structures (such as pipes)
are present and are subject to corrosion with DC current flow. While operating in the monopolar
mode, the AC network feeding the DC converter station operates with balanced voltages and
currents. Hence, single pole operation of dc transmission systems is possible for extended period,
while in AC transmission, single phase operation (or any unbalanced operation) is not feasible
for more than a second.
Disadvantages of DC Transmission:
The scope of application of DC transmission is limited by
1. High cost of conversion equipment.
2. Inability to use transformers to alter voltage levels.
3. Generation of harmonics.
4. Requirement of reactive power and
5. Complexity of controls.
Over the years, there have been significant advances in DC technology, which have
tried to overcome the disadvantages listed above except for (2). These are
1. Increase in the ratings of a thyristor cell that makes up a valve.
2. Modular construction of thyristor valves.
3. Twelve-pulse (and higher) operation of converters.
4. Use of forced commutation.
5. Application of digital electronics and fiber optics in the control of converters.
Reliability:
5
exceeded. Examples of this type of application abound from the earlier Pacific Intertie to the
recent links in China and India.
The breakeven distance is being effectively decreased with the reduced costs of new
compact converter stations possible due to the recent advances in power electronics.
Stabilization of power flows in integrated power system:
In large interconnected systems, power flow in AC ties (particularly under disturbance
conditions) can be uncontrolled and lead to overloads and stability problems thus endangering
system security. Strategically placed DC lines can overcome this problem due to the fast
controllability of DC power and provide much needed damping and timely overload capability.
The planning of DC transmission in such applications requires detailed study to evaluate the
benefits. Example is the Chandrapur-Padghe link in India.
Presently the number of DC lines in a power grid is very small compared to the number
of AC lines. This indicates that DC transmission is justified only for specific applications.
Although advances in technology and introduction of Multi-Terminal DC (MTDC) systems are
expected to increase the scope of application of DC transmission, it is not anticipated that the AC
grid will be replaced by a DC power grid in the future. There are two major reasons for this:
First, the control and protection of MTDC systems is complex and the inability of voltage
transformation in dc networks imposes economic penalties.
Second, the advances in power electronics technology have resulted in the improvement
of the performance of AC transmissions using FACTS devices, for instance through introduction
of static VAR systems, static phase shifters, etc.
Types of Valves
Based on the controllability and configuration valves are classified into four types as
under.
7
A monopolar link as shown in the above figure has one conductor and uses either ground
and/or sea return. A metallic return can also be used where concerns for harmonic interference
and/or corrosion exist. In applications with DC cables (i.e., HVDC Light), a cable return is used.
Since the corona effects in a DC line are substantially less with negative polarity of the
conductor as compared to the positive polarity, a monopolar link is normally operated with
negative polarity.
Bipolar Link:
8
A bipolar link as shown in the above figure has two conductors, one positive and the
other negative. Each terminal has two sets of converters of equal rating, in series on the DC side.
The junction between the two sets of converters is grounded at one or both ends by the use of a
short electrode line. Since both poles operate with equal currents under normal operation, there is
zero ground current flowing under these conditions. Monopolar operation can also be used in the
first stages of the development of a bipolar link. Alternatively, under faulty converter conditions,
one DC line may be temporarily used as a metallic return with the use of suitable switching.
Homopolar Link:
In this type of link as shown in the above figure two conductors having the same polarity
(usually negative) can be operated with ground or metallic return.
Due to the undesirability of operating a DC link with ground return, bipolar links are
mostly used. A homopolar link has the advantage of reduced insulation costs, but the
disadvantages of earth return outweigh the advantages.
The major components of a HVDC transmission system are converter stations where
conversions from AC to DC (Rectifier station) and from DC to AC (Inverter station) are
performed. A point to point transmission requires two converter stations. The role of rectifier and
inverter stations can be reversed (resulting in power reversals) by suitable converter control.
A typical converter station with two 12 pulse converter units per pole is shown in figure
below. The block diagram of converter station is given above.
Converter Unit:
1
0
This usually consists of two three phase converter bridges connected in series to form a
12 pulse converter unit as shown in above figure. The total number of valves in such a unit is
twelve. The valves can be packaged as single valve, double valve or quadrivalve arrangements.
Each valve is used to switch in segment of an AC voltage waveform. The converter is fed by
converter transformers connected in star/star and star/delta arrangements.
The valves are cooled by air, oil, water of freon. Liquid cooling using deionized water is
more efficient and results in the reduction of station losses. The design of valves is based on the
modular concept where each module contains a limited number of series connected thyristor
levels.
Valve firing signals are generated in the converter control at ground potential and are
transmitted to each thyristor in the valve through a fiber optic light guide system.
The valves are protected using snubber circuits, protective firing and gapless surge
arrestors.
Converter Transformer:
The converter transformer has three different configurations-
(i) three phase, two winding,
(ii) single phase, three winding and
(iii)single phase, two winding
The valve side windings are connected in parallel with neutral grounded. The leakage
reactance of the transformer is chosen to limit the short circuit currents through any valves.
1
1
The converter transformers are designed to withstand DC voltage stresses and increased
eddy current losses due to harmonic currents. One problem that can arise is due to the DC
magnetization of the core due to unsymmetrical firing of valves.
Filters:
There are three types of filters used which are
1. AC Filters:
These are passive circuits used to provide how impedance, shunt paths for AC
harmonic currents. Both tuned and damped filter arrangements are used.
2. DC Filters:
These are similar to AC filters and are used for the filtering of DC harmonics.
3. High Frequency (RF/PLC) Filters:
These are connected between the converter transformer and the station AC bus to
suppress any high frequency currents. Sometimes such filters are provided on high-voltage DC
bus connected between the DC filter and DC line and also on the neutral side.
Reactive power source:
Converter stations require reactive power supply that is dependent on the active power
loading. But part of the reactive power requirement is provided by AC filters. In addition, shunt
capacitors, synchronous condensors and static VAR systems are used depending on the speed of
control desired.
Smoothing Reactor:
A sufficiently large series reactor is used on DC side to smooth DC current and also for
protection. The reactor is designed as a linear reactor and is connected on the line side, neutral
side or at intermediate location.
DC Switchgear:
It is modified AC equipment used to interrupt small DC currents. DC breakers or Metallic
Return Transfer Breakers (MRTB) are used, if required for interruption of rated load currents.
In addition to the DC switchgear, AC switchgear and associated equipment for protection
and measurement are also part of the converter station.
The trends which are being introduced are for the effective development to reduce the
cost of the converters and to improve the performance of the transmission system.
Power semiconductors and valves:
The IGBTs or GTOs employed required huge amount of current to turn it ON which was
a big problem. GTOs are available at 2500V and 2100A. As the disadvantage of GTOs is the
large gate current needed to turn them OFF, so MCT which can be switched OFF by a small
current is preferred as valves.
The power rating of thyristors is also increased by better cooling methods. Deionized
water cooling has now become a standard and results in reduced losses in cooling.
Converter Control:
The development of micro-computer based converter control equipment has made
possible to design systems with completely redundant converter control with automatic transfer
between systems in the case of a problem.
The micro-computer based control also has the flexibility to implement adaptive control
algorithms or even the use of expert systems for fault diagnosis and protection.
DC Breakers:
Parallel rather than series operation of converters is likely as it allows certain flexibility
in the planned growth of a system. The DC breaker ratings are not likely to exceed the full load
ratings as the control intervention is expected to limit the fault current.
Conversion of existing AC lines:
There are some operational problems due to electromagnetic induction from AC circuits
where an experimental project of converting a single circuit of a double circuit is under process.
Constant reactive current control or AC voltage control may overcome some of the
problems of weak AC systems.
The power modulation techniques used to improve dynamic stability of power systems
will have to be modified in the presence of weak AC systems.
from two different (three-phase) transformers with voltages differing in phase by 30o .
Pulse Number
The pulse number of a converter is defined as the number of pulsations (cycles of ripple)
of direct voltage per cycle of alternating voltage.
The conversion from AC to DC involves switching sequentially different sinusoidal
voltages onto the DC circuit.
14
A valve can be treated as a controllable switch which can be turned ON at any instant,
provided the voltage across it is positive.
The output voltage Vd of the converter consists of a DC component and a ripple whose
frequency is determined by the pulse number
A converter configuration can be defined by the basic commutation group and the
number of such groups connected in series and parallel.
If there are ‘q’ valves in a basic commutation group and r of those are connected in
parallel and s of them in series then,
p=qrs
Note:
1
5
A commutation group is defined as the group of valves in which only one (neglecting
overlap) conducts at a time.
Valve Rating:
The valve rating is specified in terms of Peak Inverse Voltage (PIV). The ratio of PIV to
average DC voltage is an index of valve utilization.
So, average maximum DC voltage across the converter is given by,
q
Vdo = s q E m cos td ( t)
2 q
q /q sq sq
=s Em (sin t) = E m sin sin = E m .2 sin
/q
2 2 q q 2 q
s
q
V = E sin q ----- (1)
do m
If ‘q’ is even, then maximum inverse voltage occurs when the valve with a phase
displacement of 180o is conducting and is given by,
PIV = 2Em
If ‘q’ is odd, then maximum inverse voltage occurs when the valve with a phase shift of
π±(π/q) is conducting and is given by,
PIV = 2Em cos(π/2q)
2
E m cos 2 .cos 2 .cos
For q odd, PIV = 2q = 2q = 2q
s
V
do q
Em sin q sq.sin q sq.2 cos 2q sin 2
q
sq.sin 2q
Transformer Rating:
The current rating of a valve is given by,
I
I d
v =---------------
r q (2)
tv
.
2
q.sin q
S
Transformer utilization factor tv is a function of q.
V I
do d
As AC supply is three phase so, commutation group of three valves can be easily
arranged. So, for q = 3,
S
tv =
V I
do d
(2 X 3) sin 3
S
tv =
VI
do d 6sin 60o
Stv
= 1.48
VI
do d
Transformer utilization can be improved if two valve groups can share single transformer
winding. In this case, the current rating of the winding can be increased by a factor of √2 while
decreasing the number of windings by a factor of 2.
18
3
= 2ELL [cos( + 60o cos( +120o )]
19
2
V h = V do h2 1[1 + (h2 +1) sin 2
]1/ 2
The waveforms of the direct voltage and calve voltage are shown for different values of
α.
20
AC Current Waveform:
It is assumed that direct current has no ripple (or harmonics). The AC currents flowing
through the valve (secondary) and primary windings of the converter transformer contain
harmonics.
The waveform of the current in a valve winding is shown. The rms value of the
fundamental component of current is given by
1 2 / 3d d
where as the rms value of the current is
2
I = 3 .I d
The harmonics contained in the current waveform are of the order given by
h = np 1
Where n is an integer, p is the pulse number. For a six pulse converter, the order of AC
harmonics is 5, 7, 11, 13 and higher order. These are filtered out by using tuned filters for each
one of the first four harmonics and a high pass filter for the remaining.
th I1
I
The rms value of h harmonic is given by h = h
Power Factor:
The AC power supplied to the converter is given by
The reactive power requirements are increased as α is increased from zero (or reduced
from 180o ).
di di
3
e e =L 1
b adt dtc
The LHS in the above equation is called the commutating emf whose value is given by
eb ea = 2ELL sin t
Which is the voltage across valve 3 just before it starts conducting.
22
Since, i1 = I d i3
We get,
di
2ELL sin t = 2Lc dt3
Solving the above equation, we get
i3 (t) = I s (cos cos t), t +
Where,
2E
LL
Is=
2 Lc
3
= V do cos 2 2E LL [cos cos( + )]
32
Since, ELL = Vdo , we get
V
Vd = 2 [cos + cos( + )]
do
2I s
do
Where,
3 3
Rc = Lc = Xc
Rc is called equivalent commutation resistance and the equivalent circuit for a bridge
converter is shown below.
23
Inverter Equations:
For an inverter, advance angle β is given by
β=π-α
and use opposite polarity for the DC voltage with voltage rise opposite to the direction of
current. Thus,
V
V = doi [cos + cos( + )]
di
2
V
= doi [cos( ) + cos( )] 2
V
V = doi
[cos + cos ]
di
2
Where, the extinction angle γ is defined as
γ = β-μ = π-α-μ
Similarly, it can be shown that
Vdi = Vdoi cos + Rci I d
I
I d = 2s [cos( 30o ) cos( + + 30o )]The
3
Vd = 2 V do[cos( 30o ) + cos( + + 30o )]
Finally
V
do 2I s
The voltage and current characteristics are linear with different slopes in these cases. For
d Vdo d
B) Inverter:
The inverter characteristics are similar to the rectifier characteristics. However, the
operation as an inverter requires a minimum commutation margin angle during which the voltage
across the valve is negative. Hence the operating region of an inverter is different from that for a
rectifier.
So, the margin angle (ξ) has different relationship to γ depending on the range of
operation which are
Mode 1
1(a) β < 60o for values of μ < (60o - ξo )
The characteristics are linear defined by
Vd| = cosγo – Id|
1(b) 60o < β < 90o for
μ = 60o – ξo = 60o – γo = constant
26
As long as the AC voltages at the converter bus remain sinusoidal (with effective
filtering), the operation of one bridge is unaffected by the operation of the other bridge connected
in series. The region of rectifier operation can be divided into five modes as Mode 1: 4 and 5
valve conduction
0 < μ < 30o
Mode 2: 5 and 6 valve conduction
30o < μ < 60o
Mode 3: 6 valve conduction
0 < α < 30o , μ = 60o
Mode 4: 6 and 7 valve conduction
60o < μ < 90o
27
Questions
1) What is the need for interconnection of systems? Explain the merits of connecting HVAC
systems by HVDC tie-lines?
2) (a) Discuss the different factors that favor HVDC transmission systems over EHVAC
transmission over long distances.
(b) What are the different HVDC links normally adopted?
3) (a) With the help of a neat schematic diagram of a typical HVDC converter station
explain the functions of various components available.
(b) What are the applications and merits of HVDC transmission system?
4) (a) Explain for what reasons as a system planner, you consider the applications of HVDC
in India?
28
Consider the steady state equivalent circuit of a two terminal DC link. This is based on
the assumption that all the series connected bridges in both poles of a converter station are
identical and have the same delay angles. Also the number of series connected bridges (nb ) in
both stations (rectifier and inverter) are the same.
where Evr and Evi are the line to line voltages in the valve side windings of the rectifier
and inverter transformer respectively. From the above figure these voltages can be obtained by
N Er N E
E = sr , E = si i --------------------
(3)
vr
N prTr vi
N piTi
where Er and Ei are the AC (line to line) voltages of the converter buses on the rectifier
and inverter side. Tr and Ti are the OFF-nominal tap ratios on the rectifier and inverter side.
Combining equations (1), (2) and (3),
Edr = (Ar Er /Tr) cosαr ----------(4)
Edi = (Ai Ei /Ti) cosγi-----------(5)
where Ar and Ai are constants.
The steady-state current Id in the DC link is obtained as
Id (Edr Edi )
=R
+ Rd Rci cr
Rcr + Rd Rci
The control variables in the above equation are Tr , Ti and αr , βi . However, for
maintaining safe commutation margin, it is convenient to consider γi as control variable instead
of βi .
As the denominator in the final equation is small, even small changes in the voltage
magnitude Er or Ei can result in large changes in the DC current, the control variables are held
constant. As the voltage changes can be sudden, it is obvious that manual control of converter
angles is not feasible. Hence, direct and fast control of current by varying α r or γr in response to a
feedback signal is essential.
While there is a need to maintain a minimum extinction angle of the inverter to avoid
commutation failure, it is economical to operate the inverter at Constant Extinction Angle (CEA)
which is slightly above the absolute minimum required for the commutation margin. This results
in reduced costs of the inverter stations, reduced converter losses and reactive power
consumption. However, the main drawback of CEA control is the negative resistance
characteristics of the converter which makes it difficult to operate stably when the AC system is
weak (low short-circuit ratios). Constant DC Voltage (CDCV) control or Constant AC Voltage
(CACV) control are the alternatives that could be used at the inverter.
31
Under normal conditions, the rectifier operates at Constant Current (CC) control and the
inverter at the CEA control.
The power reversal in the link can take place by the reversal of the DC voltage. This is
done by increasing the delay angle at the station initially operating as a rectifier, while reducing
the delay angle at the station initially operating as the inverter. Thus, it is necessary to provide
both CEA and CC controllers at both terminals.
The feedback control of power in a DC link is not desirable because
1) At low DC voltages, the current required is excessive to maintain the required level of
power. This can be counterproductive because of the excessive requirements of the
reactive power, which depresses voltage further.
2) The constant power characteristic contributes to negative damping and degrades dynamic
stability.
The characteristic AB has generally more negative slope than characteristic FE because
the slope of AB is due to the combined resistance of (Rd + Rcr ) while is the slope of FE is due to
Rci .
The above figure shows the control characteristics for negative current margin I m (or
where the current reference of station II is larger than that of station I). The operating point shifts
now to D which implies power reversal with station I (now acting as inverter) operating with
minimum CEA control while station II operating with CC control.
This shows the importance of maintaining the correct sign of the current margin to avoid
inadvertent power reversal. The maintenance of proper current margin requires adequate
telecommunication channel for rapid transmission of the current or power order.
persistent commutation failure because of the increase of the overlap angle. In such cases, it is
necessary to reduce the DC current in the link until the conditions that led to the reduced DC
voltage are relieved. Also the reduction of current relieves those valves in the inverter which are
overstressed due to continuous current flow in them.
If the low voltage is due to faults on the rectifier side AC system, the inverter has to
operate at very low power factor causing excessive consumption of reactive power which is also
undesirable. Thus, it becomes useful to modify the control characteristics to include voltage
dependent current limits. The figure above shown shows current error characteristics to stabilize
the mode when operating with DC current between I d1 and Id2 . The characteristic cc| and c|c||
show the limitation of current due to the reduction in voltage.
System Control Hierarchy
The control function required for the HVDC link is performed using the hierarchical
control structure.
3
4
The master controller for a bipole is located at one of the terminals and is provided with
the power order (Pref ) from the system controller (from energy control centre). It also has other
information such as AC voltage at the converter bus, DC voltage etc. The master controller
transmits the current order (Iref ) to the pole control units which in turn provide a firing angle
order to the individual valve groups (converters). The valve group or converter control also
oversees valve monitoring and firing logic through the optical interface. It also includes bypass
pair selection logic, commutation failure protection, tap changer control, converter start/stop
sequences, margin switching and valve protection circuits.
The pole control incorporated pole protection, DC line protection and optional converter
paralleling and deparalleling sequences. The master controller which oversees the complete
bipole includes the functions of frequency control, power modulation, AC voltage and reactive
power control and torsional frequency damping control.
The current or extinction angle controller generates a control signal V c which is related to
the firing angle required. The firing angle controller generates gate pulses in response to the
control signal Vc . The selector picks the smaller of the α determined by the current and CEA
controllers.
1. The firing instant for all the valves are determined at ground potential and the firing
signals sent to individual thyristors by light signals through fibre-optic cables. The
required gate power is made available at the potential of individual thyristor.
2. While a single pulse is adequate to turn-on a thyristor, the gate pulse generated must send
a pulse whenever required, if the particular valve is to be kept in a conducting
state. The two basic firing schemes are
1. Individual Phase Control (IPC)
2. Equidistant Pulse Control (EPC)
The delays are produced by independent delay circuits and controlled by a common
control voltage V derived from the current controllers.
The zero crossing of the sum of the two voltages initiates the firing pulse for the
particular valve is considered. The delay angle α is nominally proportional to the inverse cosine
of the control voltage. It also depends on the AC system voltage amplitude and shape.
The main advantage of this scheme is that the average DC voltage across the bridge
varies linearly with the control voltage Vc .
pulses are not equidistant in steady-state. This in turn leads to the generation of noncharacteristic
harmonics (harmonics of order h ≠ np ± 1) in the AC current which can amplify the harmonic
content of the AC voltage at the converter bus. The problem of harmonic instability can be
overcome by the following measures
1. Through the provision of synchronous condensers or additional filters for filtering out
noncharacteristic harmonics.
2. Use of filters in control circuit to filter out noncharacteristic harmonics in the
commutation voltages.
3. The use of firing angle control independent of the zero crossings of the AC voltages. This
is the most attractive solution and leads to the Equidistant Pulse Firing scheme.
The output pulses of the generator drive the ring counter and also reset the integrator. The
instant (tn ) of the firing pulse is determined by
t n
K1 (Vc +V1 )dt = V3
t n 1
t n
K1V1dt = V3 +Vc
t n 1
K1 V1 (tn – tn-1 ) = V3 + Vc
With Vc = 0, the interval between consecutive pulses, in steady-state, is exactly equal to
1/pfo .
where Vcn and Vc(n-1) are the control voltages at the instants tn and tn-1 respectively.
For proportional current control, the steady-state can be reached when the error of Vc is
constant.
The major advantages claimed for PPC over PFC are (i) easy inclusion of α limits by
limiting Vc as in IPC and (ii) linearization of control characteristic by including an inverse cosine
function block after the current controller. Limits can also be incorporated into PFC or pulse
period control system.
Drawbacks of EPC Scheme
EPC Scheme has replaced IPC Scheme in modern HVDC projects; it has certain
limitations which are
1. Under balanced voltage conditions, EPC results in less DC voltage compared to IPC.
Unbalance in the voltage results from single phase to ground fault in the AC system
4
0
which may persist for over 10 cycles due to stuck breakers. Under such conditions, it is
desirable to maximize DC power transfer in the link which calls for IPC.
2. EPC Scheme also results in higher negative damping contribution to torsional oscillations
when HVDC is the major transmission link from a thermal station.
The extinction angle controller can be of predictive type or feedback type with IPC
control. The predictive controller is considered to be less prone to commutation failure and was
used in early schemes. The feedback control with PFC type of Equidistant Pulse Control
overcomes the problems associated with IPC.
The extinction angle, as opposed to current, is a discrete variable and it was felt the
feedback control of gamma is slower than the predictive type. The firing pulse generation is
based on the following equation
tn
0= ecj d ( t) + 2 X c I d
+n 1
where ecj is the commutation voltage across valve j and t n is the instant of its
firing. In general, the prediction of firing angle is based on the equation
Βj = γref + µj
where µj is the overlap angle of valve j, which is to be predicted based on the current knowledge
of the commutation voltage and DC current.
Under large disturbances such as a sudden dip in the AC voltage, signals derived from the
derivative of voltage or DC current aid the advancing of delay angle for fast recovery from
commutation failures.
41
With the selection of bypass pair 1 and 4, the commutation from valve 2 to4 is there, but
the commutation from valve 3 to valve 5 is prevented. In the case of a predetermined choice of
the bypass path, the time lapse between the blocking command and the current transfer to bypass
path can vary from 600 and 1800 for a rectifier bridge. In the inverter, there is no time lag
involved in the activation of the bypass pair. The voltage waveforms for the rectifier and inverter
during de-energisation are shown below where the overlap is neglected.
42
The current from bypass pair is shunted to a mechanical switch S1 . With the aid of the
isolators S, the bridge can be isolated. The isolator pair S and switch S1 are interlocked such that
one or both are always closed.
The energisation of a blocked bridge is done in two stages. The current is first diverted
from S1 to the bypass pair. For this to happen S1 must generate the required arc voltage and to
minimize this voltage, the circuit inductance must be small. In case the bypass pair fails to take
over the current, S1 must close automatically if the current in that does not become zero after a
predetermined time interval. AC breakers with sufficient arc voltage, but with reduced breaking
capacity are used as switch S1 .
In the second stage of energisation, the current is diverted from the bypass pair. For the
rectifier, this can take place instantaneously neglecting overlap. The voltage waveforms for this
case are shown below.
Start-Up of DC Link:
There are two different start-up procedures depending upon whether the converter firing
controller provides a short gate pulse or long gate pulse. The long gate pulse lasts nearly 1200 ,
the average conduction period of a valve.
Start-up with long pulse firing:
1. Deblock inverter at about γ = 900
2. Deblock rectifier at α = 850 to establish low direct current
3. Ramp up voltage by inverter control and the current by rectifier control.
43
The voltage is raised before raising the current. This permits the insulation of the line to
be checked before raising the power. The ramping of power avoids stresses on the generator
shaft. The switching surges in the line are also reduced.
The required power ramping rate depends on the strength of the AC system. Weaker
systems require fast restoration of DC power for maintaining transient stability.
Power Control
The current order is obtained as the quantity derived from the power order by dividing it
by the direct voltage. The limits on the current order are modified by the voltage dependent
current order limiter (VDCOL). The objective of VDCOL is to prevent individual thyristors from
carrying full current for long periods during commutation failures.
By providing both converter stations with dividing circuits and transmitting the power
order from the leading station in which the power order is set to the trailing station, the fastest
response to the DC line voltage changes is obtained without undue communication requirement.
When the DC line resistance is large and varies considerably e.g., when
the overhead line is very long and exposed to large temperature variations, the DC line voltage
drop cannot be compensated individually in the two stations. This problem can be solved by
using a current order calculated in one substation only and transmitting its output to the other
substation.
Questions:
1) Write detailed notes on the following
(a) Preductive commutation margin control
(b) Equidistant firing control.
2) (a) Differentiate between the two start-up procedures based upon the pulse.
(b) Describe about starting and stopping of DC link.
3) (a) Explain with neat sketch, constant extinction angle control.
(b) What is meant by current margin between two stations in a HVDC link? Why is the
inverter station, operated as a constant voltage controller under normal conditions?
4) Enumerate the relative merits and demerits of constant current control and constant
voltage control of HVDC link.
5) (a) Explain the necessity of “VDCOL" control in a HVDC link with the help of VI
characteristics..
(b) Explain the procedure of Energization and Deenergization of a converter bridge.
6) (a) Draw the complete converter control characteristics and explain the principle of
power control in a DC link.
(b) Explain Inverse cosine control scheme for firing pulse generations.
7) (a) Explain pulse frequency control scheme for firing pulse generation and discuss its
drawbacks.
(b) Explain clearly the procedure for start up of a DC link.
8) Explain the individual characteristics of a Rectifier and an Inverter with sketches.
9) With block diagram, discuss the principle of operation of a basic power controller.
10) Write short notes on the following:
(a) Constant Alpha control (b) Inverse cosine control.
11) Explain the drawbacks in Individual phase control and equidistant pulse control schemes
used in HVDC projects.
4
5
The converter which forms the basic unit in HVDC transmission imposes changes of
impedances in the current.
Generation of Harmonics
The harmonics which are generated are of two types.
(i) Characteristic harmonics.
(ii) Non- characteristic harmonics.
Characteristic Harmonics
The characteristic harmonics are harmonics which are always present even under ideal
operation.
4
7
In the converter analysis, the DC current is assumed to be constant. But in AC current the
harmonics exist which are of the order of
h = np ± 1
and in DC current it is of the order of
h = np
where n is any integer and p is pulse number.
Neglecting overlap, primary currents of Y-Y and Y-∆ connection of the transformer are
considered taking the origin symmetrical where
i = Id for –π/3≤ ωt≤π/3
= 0 for π/3≤ωt≤2π/3 and for Y-Y connection
-π/3≤ωt≤-2π/3 converter
= - Id for –2π/3≤ ωt≤-π and transformer
2π/3≤ ωt≤π
Figure (a): Phase current on primary side of Y-Y connection converter transformer
Figure (b): Phase current on primary side of Y-∆ connection converter transformer
4
8
For convenience, the ordinate axis (corresponding to ωt = 0) is chosen such that the
waveform has even symmetry. So, generally, by fourier series
1
f (t) = a0 + an cos n t + bn sin n t
2 n=0 n=0
As positive and negative half cycle cancel each other, so a0 = 0 and as it is (waveform is)
even symmetry, so bn = 0 due to which f(t) becomes
PeriodOfConduction
2
where, an1 = f (t)dt
T 0
(Here as it is symmetry)
/3
4I /3 4I sin n t
a = d d
n1 cos n td ( t) =
0 n 0
4
I
an = n
d
sin n 3
1
Questions
1) Derive the relationship between pulse conversion and harmonics generated.
2) What are the various sources of harmonics generation in a HVDC line?
3) (a) Discuss the effect of pulse number and overlap angle on harmonics generated by
HVDC converters.
(b) Using fourier analysis show that the lowest order voltage harmonic
present in Graetz circuit output voltage is six.
4) Analyze the harmonics in the AC current during 6-pulse and 12-pulse operations using
fourier analysis. What orders of harmonics predominate in the current wave?
4
9
17) What are the filter configurations that are employed for HVDC converter
station? Give design aspect of one such filter.
18) Derive an equation for harmonic voltage and current for single tuned filter and discuss
the influence of network admittance on design aspects.
19) Explain in detail, the different configurations of static VAR system.
50
20) (a) Describe the method of compensation of reactive power in HVDC substation.
(b) Draw simple single line schematics for each.
21) What is a Static VAR system? How many types of SVS schemes are present and what
are they?
22) (a) Discuss about alternate converter control strategies for reactive power control.
(b) Discuss how shunt capacitors can be used to meet reactive power requirement of a converter.
23) (a) Why Reactive power control is required for HVDC stations? Discuss about
conventional control strategies for Reactive power control in HVDC link.
(b) Discuss how reactive power requirement is met using synchronous condensers.
25) Write a note on the following sources of reactive power
(a) Synchronous condensers
(b) Static VAR system
Design of AC Filters
1. Harmonic Distortion:
Harmonic Distortion is given by,
m
I Z
n n
n=2 100
D=
E1
where,
In – harmonic current injected
Zn – harmonic impedance of the system
E1 – fundamental component of line to neutral voltage
m – highest harmonic considered
Harmonic Distortion is also given by,
m 1/2
(I n Z n )2
DRSS = n=2 100
E
1
where,
Fn = 5 n f1 pn
Pn is the c message weighting used by Bell Telephone Systems (BTS) and Edison
Electric Institute (EEI) in USA. This weighting reflects the frequency dependent sensitivity of
the human ear and has a maximum value at the frequency of 1000Hz.
Types of AC Filters
The various types of filters that are used are
1. Single Tuned Filter
2. Double Tuned Filter
3. High Pass Filter
a) Second Order Filter
b) C Type Filter
Single Tuned Filter
Single Tuned Filters are designed to filter
out characteristic harmonics of single
frequency.
52
A converter system with 12 pulse converters has Double Tuned (or two Single Tuned)
Filter banks to filter out 11th and 13th harmonics and a High Pass Filter bank to filter the rest of
harmonics. Sometimes a third harmonic filter may be used to filter the non-characteristic
harmonics of the 3rd order particularly with weak AC systems where some voltage unbalance is
expected.
All filter branches appear capacitive at fundamental frequency and supply reactive power.
h h
r n n r n
Considering variations in the frequency (f), inductance (L) and capacitance (C),
54
1/ 2
f L C
=1+ 1+ 1+
fn L
n
C
n
= f+1 L+1
Cfn 2 Ln
2 Cn
where Ln and Cn are the nominal values of L and C such that hrωn=(LnCn)-
1/2
The variation in C can be due to
(i) error in the initial setting of C
(ii) the variation in C due to the temperature dependence of the dielectric constant.
L C
Z = R + jX n n
Fh 0
L C
n n
1
where X 0 = hr n Ln =
hr n Cn
The single tuned filters are designed to filter out characteristic harmonics of single
frequency. The harmonic current in the filter is given by
Z
I I h Sh
Fh =
Z
Sh + Z Fh
The optimum value of Q can be obtained from game-theoretic analysis. If one selects YFh
arbitrarily (the tip of YFh lying along the semicircle), the network can select YSh such that the
vector Yh is perpendicular to the vector YSh and ensure Yh is minimum. To maximize the
minimum magnitude of Yh , it is necessary to have YSh tangential to the circle. Thus, we select
YFh to maximize Yh when the network tries to minimize it.
h0 1 = 1/ LC , Z0 = L C , = R / Z0
The following values can be chosen
0.5 < σ < 2
h0 ≤ √2 hmin
where hmin is the smallest value of h to be handled by the filter. The choice of h0 given above
implies that the filter impedance at hmin has decreased approximately to the value of R.
The filter impedance is given by
Z [ + j(h / h).( 2 1 ( h / h)2 )]
Zf = 0 0
2
0
1 + ( h / h)
0
The filtering is improved if Qf is increased and higher value of h0 can be chosen. Hence,
it is advantageous in designing high pass filter to exclude six pulse operation.
Protection of Filters
The filter is exposed to overvoltage during switching in and the magnitude of this
overvoltage is a function of the short-circuit ratio (higher with low values of SCR) and the
saturation characteristics of the converter transformer.
During switching in, the filter current (at filter frequencies) can have magnitudes ranging
from 20 to 100 times the harmonic current in normal (steady-state) operation. The lower values
for tuned filters and higher values are applicable to high pass filters. These overcurrents are taken
into consideration in the mechanical design of reactor coils.
When filters are disconnected, their capacitors remain charged to the voltage at the
instant of switching. The residual direct voltages can also occur on bus bars. To avoid, the
capacitors may be discharged by short-circuiting devices or through converter transformers or by
voltage transformers loaded with resistors.
If the network frequency deviates from the nominal value, higher currents and losses will
result in AC filters. If they exceed the limits,
LECTURE NOTES
ON
FLEXIBLE AC TRANSMISSION
SYSTEMS
FACTS CONTROLLERS
INTRODUCTION
The electric power supply systems of whole world are interconnected, involving connections
inside the utilities, own territories with external to inter-utility, internationals to inter regional
and then international connections. This is done for economic reasons, to reduce the cost of
electricity and to improve reliability of power supply. We need the interconnections to pool
power plants and load centers in order to minimize the total power generation capacity and fuel
cost. Transmission lines interconnections enable to supply, electricity to the loads at minimized
cost with a required reliability. The FACTS Technology is adopted in the transmissions to
enhance grid reliability and to overcome the practical difficulties which occur in mechanical
The FACTS Technology has opened a new opportunity to the transmission planner for
controlling power and enhancing the useable capacity presently, also to upgrade the
transmission lines. The current through the line can be controlled at a reasonable cost which
enables a large potential of increasing the capacity of existing lines with large conductors and
by the use of FACTS controllers the power flow through the lines is maintained stable. The
FACTS controllers control the parameters governing the operation of transmission systems,
such as series impedance, shunt impedance, current, voltage, phase angle and damping of
In an A.C power flow, the electrical generation and load must be balanced all the times. Since
the electrical system is self-regulating, therefore, if one of the generators supplies less power
than the load, the voltage and frequency drop, thereby load goes on decreasing to equalize the
generated power by subtracting the transmission losses. How ever there is small margin of self
regulating. If voltage is dropped due to reactive power, the load will go up and frequency goes
on decreasing and the system will collapse ultimately. Also the system will collapse if there is
a large reactive power available in it. In case of high power generation the active power flows
POWER FLOW
Consider a simple case of power flow in parallel paths. Here power flows from surplus
generation area to the deficit generation area. Power flow is based on the inverse of line
impedance. It is likely that lower impedance line become overloaded and limits the loading on
both the paths, though the higher impedance area is not fully loaded. There would not be any
chance to upgrade the current capacity of the overloaded path, because it would further
decrease the impedance. The power flow with HVDC converters is controlled by high speed
HVDC converters. The parallel A.C. transmission maintains the stability of power flow. The
power flow control with FACTS controllers can be carried out by means of controlling
1400 MW
A
C
10
2000 MW
10 3000
600 5 1600 MW
MW MW load
1000 MW
(a)
-5 1750 MW
A
C
10
2000 MW
B 1000 MW
(b)
1750 MW
A
C
10
7
B 1000 MW
(c)
-4.24 1750 MW
A
C
10
2000MW
1250 MW
7
B 1000 MW
(d)
For understanding free flow of power, consider a simplified case in which two generators are
sending power to load center from different sites. The Mesh network has the lines AB, BC and
AC having continuous rating of 1000 MW, 1250 MW respectively. If one of the generators is
generating 2000 MW and the other 1000 MW, a total power of 3000 MW would be delivered
to the load center. In Fig 2.1 (a) the three impedances 10Ω, 5Ω and 10Ω, carry the powers 600
MW, 1600 MW and 1400 MW respectively. Such a situation would overload line BC and
therefore generation would have to be decreased at „B‟ and increased at „A‟ in order to meet
Fig 2.1 (b), it reduces the line impedance from 10Ω to 5Ω so that the power flow through the
lines AB, BC and AC are 250 MW, 1250 MW and 1750 MW respectively. It is clear that if the
series capacitor is adjusted the power flow level may be realized. The complication is if the
series capacitor is mechanically controlled it may lead to sub synchronous resonance. This
resonance occurs when one of the mechanical resonance frequencies of the shaft of a multiple-
turbine generator unit coincides with normal frequency by subtracting the electrical resonance
frequency of the capacitor with the inductive load impedance of the line. Then the shaft will be
damaged.
If the series capacitor is thyristor controlled, it can be varied whenever required. It can be
modulated to rapidly damped and sub synchronous conditions. Also can be modulated at
damped low frequency oscillations. The transmission system to go from one steady-state
condition to another without the risk of damaging the shaft, the system collapse. In other words
thyristor controlled series capacitor can enhance the stability of network similarly as in Fig
-
-
with the line AB, the series inductor which is controlled by thyristor could serve to adjust the
Another option of thyristor controlled method is, phase angle regulator could be installed
instead of series capacitor in the line as in Fig 2.1(d). The regulator is installed in line AC to
reduce the total phase angle difference along the line from 8.5 degree to 4.26 degrees. Thus the
combination of Mesh and thyristor control of the phase angle regulator may reduce the cost.
The same result could be achieved by injecting a variable voltage in one of the lines. Balancing
of power flow in the line is carried out by the use of FACTS controller in the line.
For the best use of the transmission and to improve the loading capability of the system one
Thermal Limitations
Dielectric Limitations
Limitations of Stability
Thermal Limitations
variable environment and the loading history. It needs to find out the nature of environment
and other loading parameters. For this, off-line computer programs are made use to calculate a
line loading capability based on available ambient environment and present loading history.
The over load line monitoring devices are also used to know the on line loading capability of
the line. The normal loading of the line is also decided on a loss evaluation basis which may
vary for many reasons. The increase of the rating of transmission line involves the
-
-
temperature, aging of transformer and present loading history of off-line and on-line
monitoring. The loading capability of transformer is also used to obtain real time loading
transmission line. From the above discussion it is necessary of upgrading line loading
capability which can be done by changing the conductor of higher current rating which
requires the structural upgrading. The loading capability of line is also achieved by converting
a single circuit to double circuit line. If the higher current capability is available then the
question arises, how to control this high current in the line, also, the acceptance of sudden
voltage drop with such high current etc. The FACTS technology helps in making an effective
Dielectric Limitations
From insulation point of view, many transmission lines are designed very conservatively. For a
normal voltage rating, it is rarely possible to increase normal operation by +10% voltages, e.g.
500 kV, - 550 kV or even higher. Care must be taken such that the dynamic and transient over
voltages are within the limit. Modern type of gapless arresters, or line insulators with internal
are used to increase the line and sub station voltage capability. The FACTS technology could
Limitations of Stability
There are a number of stability issues that limit the transmission capability. They are:
Transient Stability
Dynamic Stability
-
-
Steady-state Stability
Frequency Collapse
Voltage Collapse
Control of line impedance „X‟ with a Thyristor controlled series capacitor can provide a
When the angle is not large in some cases the control of „X‟ or the angle provides the
Control of angle with a phase angle regulator controls the driving voltage, which
provides the powerful means of controlling the current flow and hence active power
Injecting a voltage in series with the line, which is perpendicular to the current flow can
increase or decrease the magnitude of current flow. Since the current flow lags the
driving voltage by 90º, this means injection of reactive power in series compensation
can provide a powerful means of controlling the line current and hence the active power
Injecting voltage in series with line with any phase angle with respect to the driving
voltage can control the magnitude and the phase of the line current. This means that
injecting a voltage phasor with variable phase angle can provide a powerful means of
controlling the active and reactive power flow. This requires injection if both active and
-
-
When the angle is not-large, controlling the magnitude of one or the other line voltages
with a Thyristor-controlled voltage regularly can very cost-effective means for the
Combination of the line impedance with a series controller and voltage regulation with
shunt controller can also provide a cost effective means to control both the active and
Series controllers
Shunt controllers
Line
Line
-
-
Line
Line
Coordinated
Controller
DC Power Link
(e) (f) Unified Series
shunt controller
Fig 2.2 (a) shows the general symbol for FACTS controller; with a thyristor arrow inside a
box. Fig 2.2 (b) shows the series controller could be variable impedance, such as capacitor,
reactor etc. or it is a power electronics based variable source of main frequency sub-
synchronous frequency and harmonics frequencies or combination of all to serve the desired
need. The principle of series controller is to inject the voltage in series with the line. Even
variable impedance multiplied by the current flow through it, represents an injected series
voltage in the line. So long as the voltage is in phase quadrature with the line current, the series
controller supplies or consumes variable reactive power. If any other phase relation involves it
Fig 2.2 (c) shows the shunt controllers. As series controller, the shunt controller also has
variable impedance, variable source, or a combination of all. The principle of shunt controller
is to inject current into the system at the point of connection. Even variable shunt impedance
connected to the line voltage causes a variable current flow and hence represents injection of
current into the line. As long as the injected current is in phase quadrature with the line
voltage. The shunt controller supplies or consumes variable reactive power. If any other phase
-
-
Fig 2.2 (d) shows the combination of two separate series controllers, which are controlled in a
coordinated manner, in a multi line transmission system. Other wise it could be unified
controller. As shown in Fig 2.2 (d) the series controllers provide independent series reactive
compensation for each line and also transfer the real power among the lines via the unified
series-series controller, referred to as inter-line power flow controller, which makes it possible
to balance both the real and reactive power flow in the lines and thereby maximizing the
utilization of transmission system. Note that the term “unified” here means that the D.C
terminals of all controller converters are connected together for real power transfer.
Fig 2.2 (e & f) shows the combined series-shunt controllers. This could be a combination of
separate shunt and series controllers, which are controlled in coordinated manner in Fig 2.2 (e)
or a unified power flow controller with series and shunt elements in Fig 2.2 (f). The principle
of combined shunt and series controllers is, it injects current into the system with the shunt part
of the controller and voltage through series part. However, when the shunt and series
controllers are unified, there can be a real power exchange between the series and shunt
Control of power flow is in order, meet the utilities, own needs, ensure optimum power
Increase the loading capability of lines to their thermal capabilities, including short
term and seasonal, this can be done by overcoming other limitations and sharing of
-
-
Increase the system security through raising the transient stability limit, limiting short
circuit currents and over loads, managing cascading black-outs and damping electro-
Reduce the reactive power flow, thus allowing the lines to carry more active power.
UNIT - II
VOLTAGE SOURCE CONVERTERS
1
11 3 31 P&Q
Vd Vab
iab AC System
4
41 2 21
Fig 2.3 (a) shows a single phase bridge converter consisting of four valves i.e. valves (1-1') to
(4 -4'), a capacitor to provide stiff D.C. Voltage and two A.C. connection points „a‟ and „b‟.
The designated valve numbers represent their sequence of turn on and turn off operation. The
-
-
D.C. voltage is converted to A.C. voltage with the appropriate valve turn-off sequence, as
explained below. As in the first wave form 2.3 (b) when devices 1and 2 are turned on voltage
„Vab‟ becomes „+Vd‟ for one half cycle and when devices 3 and 4 turned off „Vab‟ becomes „-
Vb‟ for the other half cycle. Suppose the current flow in Fig 2.3 (c) is A.C. wave form which is
a sinusoidal wave form „Iab,‟ the angle „θ‟ leads with respect to the square-wave voltage wave
Vab AC Voltage
AC Voltage
Iab AC Current
-Vd
Id DC Current
Rectifier Inerter
Vas
Ias
(b)
1. From instant t1 to t2 when devices 1 and 2 are ON and 3 and 4 are OFF, „Vab‟ is +ve and Iab
is -ve. The current flows through device 1 into A.C. phase „a‟ and then out of A.C. phase „b‟
through device „2‟ with power flow from D.C. to A.C. (inverter action).
2. From instant t2 to t3 the current reverses i.e. becomes +ve and flows through diodes 1' and 2'
-
-
3. From instant t3 and t4 device 1 and 2 are OFF and 3 and 4 are ON, Vab becomes -ve and Iab
is still +ve the current flow through devices 3 and 4 with power flow from D.C. to A.C.
(inverter action).
4. From instant t4 and t5 devices 3 and 4 still ON and 1 and 2 OFF Vab is -ve current Iab
reverses and flows through diodes 3' and 4' with power flow from A.C. to D.C. (rectifier
operation).
Fig 2.3(d) shows D.C. current wave form and Fig 2.3(e) shows Voltage across valve (1-1') Fig
2.3(f) shows phasor of power flow from A.C. to D.C. with lagging power factor. Four
operating modes in one cycle of a single phase converter are shown in table
Table 2.1 Operational mode of Single Phase Full Wave Bridge Converter
Conducting
1 & 2 ON
1 & 2 ON
1 & 2 OFF
1 & 2 OFF
-
-
1 11 3 31 5 51
a
P Vd N
b
c
4 41 6 2 21
61
+Vd/2
1
Va Phase to DC mid point
4 4
-Vd/2
+Vd/2
Vb 3 3
6 6
-Vd/2
+Vd/2
5 5
Vc
2 2
-Vd/2
(b) (b)
-
-
1,3 4,6
1,6 1,6
Vab=Va-Vb
3,4 3,4 ph-to-ph voltage
2,6 3,5
3,2 3,2
Vbc=Vb-Vc
5,6 5,6 5,6
1,5 3,4
5,4 5,4
Vca=Vc-Va
1,2 1,2
(c) (c)
t1 t2 t3
11 4 11 4
ia 1
4 1 4 1
1 41 1
(d) (d)
+vd/6
Vn nature
voltage
-vd/6
(e) (e)
-vd/3
(f) (f)
V1 Valve
(g) voltage
-
-
11 4 1 41
DC Current from
1 4 1 4 ph-a
(h) (h)
31 61 31
DC Current from ph-b
3 6 3 6
(i) (i)
(j) (j)
(k) (k)
(l)
-
- FACTS Controllers 26
Fig 2.4 (a) shows a three phase wave converter with six valves, i.e. (1-1') to (6-6') they are
designated in the order. 1 to 6 represents the sequence of valve operation in time.It consists of
three legs, 120º apart. The three legs operate in a square wave mode; each valve alternately
closes for 180º as in the wave form of Fig 2.4 (b), Va, Vb and VC.
These three square-wave waveform are the voltages of A.C. buses a, b and c with respect to a
D.C. capacitor mid point „N‟ with peak voltages of +Vd/2 and -Vd/2. The three phase legs have
their timing 120º apart with respect to each other to a 6-phase converter operation phase leg (3-
6) switches 120º after phase leg (1-4) and phase leg (5-2) switches 120º after phase (3-6), thus
Fig 2.4 (c) shows the three phase-to-phase voltages Vab, Vbc and Vca, where VAB = Va-Vb, Vbc =
Vb-Vc and Vca = Vc-Va. These phase-to-phase voltages have 120º pulse width with peak
voltage magnitude of Vd. The periods of 60, º when the phase-to-phase voltages are zero,
represents the condition when two valves on the same order of the D.C. bus.
For example the waveform for Vab shows voltage Vd when device „1‟ connects A.C. bus „a‟ to
the D.C. + Vd/2, and device 6 connects A.C. bus „b‟ to the D.C. bus -Vd/2, giving a total voltage
Vab = Va-Vb = Vd. It is seen 120º later, when device „6‟ is turned OFF and device „3‟ is turned
ON both A.C. buses „a‟ and „b‟ become connected to the same D.C. bus +Vd/2, giving zero
voltage between buses „a‟ and „b‟. After another 60º later. When device 1 turns OFF and
device „4‟ connects bus „a‟ to -Vd/2, Vab becomes -Vd. Another 120º later, device „3‟ turns OFF
and device „6‟, connects bus „b‟ to -Vd/2, giving Vab = 0 the cycle is completed, after another
60º. device „4‟ turns OFF and device „1‟ turns ON, the other two voltages Vab and Vca have the
-
-
The turn ON and turn OFF of the devices establish the wave forms of the A.C. bus voltages in
relation to the D.C. voltage, the current flows itself, is the result of the interaction of the A.C.
voltage with the D.C. system. Each converter phase-leg can handle resultant current flow in
either direction. In fig 2.4 (d) A.C. current „Ia‟ in phase „a‟ with +ve current representing
current from A.C. to D.C. side for simplicity, the current is assumed to have fundamental
frequency only. From point t1 to t2. For example phase „a‟ current is -ve and has to flow
through either valve (1-1') or valve (4-4'). It is seen, when comparing the phase „a‟ voltage
with the form of the phase „a‟ current that when device 4 is ON and device „1‟ is OFF and the
current is -ve, the current would actually flow through diode 4'. But later say from point t 2, t3,
when device „1‟ is ON, the -Ve current flows through device „1‟, i.e., the current is transferred
from diode 4' to device „1‟ the current covering out of phase „b‟ flows through device „6‟ but
then part of this current returns back through diode 4' into the D.C. bus. The D.C. current
returns via device „5‟ into phase „e‟. At any time three valves are conducting in a three phase
converter system. In fact only the active power part of A.C. current and part of the harmonics
The harmonics content of the phase to phase voltage and phase to neutral voltage are 30º out of
phase. If this phase shift is corrected, then the phase to neutral voltage (Van) other then that of
the harmonics order 12n±1 would be in phase opposition to those of the phase to phase voltage
In Fig 2.5 (a) if the phase to phase voltages of a second converter were connected to a delta-
connected secondary of a second transformer, with √3 times the turns compared to the star
connected secondary, and the pulse train of one converter was shifted by 30º with respect to the
-
-
other “in order to bring „Vab‟ and „Van‟ to be in phase”, the combined out put voltage would
have a 12-phase wave form, with harmonics of the order of 12n±1, i.e. 11th , 13th , 23rd , 25th
…. And with amplitudes of 1/11th, 1/13th, 1/23rd 1/25th. respectively, compared to the
fundamental.
I N
Vd
300
3
(a)
Vd
Six pulse phase to
phase
2Vd/3
Vd3 3x6 pulse phase to
„N‟
12- pulse
(b)
-
-
Vd
(c)
Fig 2.5 (b): shows the two wave forms Van and Vab, adjusted for the transformer ratio and one
of them phase displaced by 30º. These two wave forms are then added to give the third wave
form, which is a 12-pulse wave form, closer to being a sine wave than each of the six-phase
wave form.
In the arrangement of Fig 2.5 (a), the two six-pulse converters, involving a total of six-phase
legs are connected in parallel on the same D.C. bus, and work together as a 12-pulse converter.
It is necessary to have two separate transformers, otherwise phase shift in the non 12-pulse
harmonics i.e. 5th, 7th, 17th, 19th …. In the secondaries it will result in a large circulating current
due to common core flux. To the non 12-pulse voltage harmonics, common core flux will
represent a near short circuit. Also for the same reason, the two primary side windings should
not be directly connected in parallel to the same three phase A.C. bus bars on the primary side.
Again this side becomes the non 12-pulse voltage harmonics i.e. 5th, 7th, 17th, 19th …. while
they cancel out looking into the A.C. system would be in phase for the closed loop. At the
-
-
same time harmonics will also flow in this loop, which is essentially the leakage inductance of
the transformers.
Where I1 is the nominal fundamental current, n is the relevant harmonic number, and XT is the
per unit transformer impedance of each transformer at the fundamental frequency. For
example, if XT is 0.15 per unit at fundamental frequency, then the circulating current for the
fifth harmonic will be 26.6%, seventh, 14.9%, eleventh, 5.5%, thirteenth, 3.9%, of the rated
fundamental current, and so on. Clearly this is not acceptable for practical voltage sourced
transformers in series and connect the combination to the A.C. bus as shown in Fig 2.5 (a),
with the arrangement shown in Fig 2.5 (a), the 5th, 7th, 17th, 19th…. harmonics voltages cancel
out, and the two fundamental voltages add up, as shown in Fig 2.5 (b), and the combined unit
Two 12-pulse converters phase shifted by 15º from each other can provide a 24-pulse
converter, with much lower harmonics on both A.C. and D.C. sides. It‟s A.C. out put voltage
would have 24n±1 order of harmonics i.e. 23rd, 25th, 47th, 49th …. , with magnitudes of 1/23rd,
1/25th, 1/47th, 1/49th …. respectively, of the fundamental A.C. voltage. The question now is,
how to arrange this phase shift. One approach is to provide 15º phase shift windings on the
two transformers of one of the two 12-pulse converters. Another approach is to provide phase
shift windings for (+7.5º) phase shift on the two transformers of one 12-pulse converter and (-
7.5º) on the two transformers of the other 12-pulse converter, as shown in Fig2.6 (a), the later
-
-
is preferred because it requires transformer of the same design and leakage inductances. It is
also necessary to shift the firing pulses of one 12-pulse converter by 15º with respect to the
other. All four six-pulse converters can be connected on the D.C. side in parallel, i.e. 12-pulse
legs in parallel. Alternately all four six-pulse converters can be connected in series for high
voltage or two pair of 12-pulse series converters may then be connected will have a separate
transformer, two with star connected secondaries, and the other two with delta-connected
secondaries.
AC System AC System
-12.50
-12.50
+12.50
+12.50
Primaries of all four transformers can be connected in series as shown in Fig 2.6 (b) in order to
avoid harmonic circulation current corresponding the 12-pulse order i.e. 11th, 13th, and 23rd,
24th. It may be worth while to consider two 12-pulse converters connected in parallel on the
A.C. system bus bars, with inter phase reactors as shown in Fig 2.6 (b) for a penalty of small
harmonic circulation inside the converter loop. While this may be manageable from the point
-
of view of converter rating. Care has to be taken in the design of converter controls,
particularly during light load when the harmonic currents could become the significant part of
the A.C. current flowing through the converter. As increase in the transformer impedance to
say 0.2 per unit may be appropriate when connecting two 12-pulse transformers to the A.C. bus
directly and less than that when connected through inter phase reactors. For high power
FACTS Controllers, from the point of view of the A.C. system, even a 24-pulse converter with
out A.C. filters could have voltage harmonics, which are higher then the acceptable level in
this case, a single high pass filter turned to the 23 rd - 25th harmonics located on the system side
The alternative of course, is go to 48-pulse operation with eight six pulse groups, with one set
of transformers of one 24-pulse converter phase shifted from the other by 7.5º, or one set
shifted (+7.5º) and the other by (-3.7º). Logically, all eight transformer primaries may be
connected in series, but because of the small phase shift (i.e. 7.5º) the primaries of the two 24-
pulse converters each with four primaries in series may be connected in parallel, if the
consequent circulating current is accepted. This should not be much of a problem, because the
higher the order of a harmonic, the lower would be the circulating current. For 0.1 per unit
transformer impedance and the 23rd harmonic, the circulating current can be further limited by
higher transformer inductance or by inter phase reactor at the point of parallel connection of
the two 24-pulse converters, with 48-pulse operation A.C. filters are not necessary.
The three level converters is one, which is used to vary the magnitude of A.C. out put voltage
-
-
+Vd/2
1
D1 11
1A 41 11A
ia
4A
41A
D4
4 41
-Vd/2
(a)
1,1A 1,1A
Va +vd/2
-vd/2 4,4A
1,1A 1,1A
Va
1A,4A
4,4A
3,3A
Vb
3,3A 3,5A
+vd
+vd/2
Va-Vb
-vd
(b)
-
-
One phase leg of a three level converter is shown in Fig 2.7 (a). The other two phase legs (not
shown) would be connected across the same D.C. bus bars and the clamping diodes connected
to the same mid point „N‟ of the D.C. capacitor. It is seen that each half of the phase leg is
splitted into two series connected valves i.e. 1-1' is Sp' into 1-1' and 1A-1'A. The mid point of
the splitted valve is connected by diodes D1 and D2 to the mid point „N‟ as shown on the phase
of it; this may seen like doubling the number of valves from two to four per phase leg, in
addition to providing two extra diode valves. However, doubling the number of valves with the
same voltage rating would double the D.C. voltage and hence the power capacity of the
converter. Thus only the addition of the diode clamping valves D1 and D4 per phase leg as in
Fig 2.7 (a) adds to the converter cost. If the converter is a high voltage converter with devices
in series, then the number of main devices would be about the same. A diode clamp at the mid
point may also help to ensure a more voltage sharing between the two valve halves.
Fig 2.7 (b) shows out put voltage corresponding to one three level phase leg. The first wave
form shows a full 180º square wave obtained by the closing of devices 1 and 1 A to give (+Vd/2)
for 180º and the closing of valves 4 and 4A for180º to give (-Vd/2) for 180º . Now consider
second voltage wave form in Fig 2.7 (b) in which upper device 1 is OFF and device 4 A is ON
an angle α earlier than they were due in the 180º square wave operation. This leaves only
device 1A and 4A ON, which in combination with diodes D1 and D2, clamp the phase voltage
Va to zero with respect to the D.C. mid point „N‟ regardless of which way the current is
flowing, this continues for a period 2α until device 1A is turned OFF and device 4 is turned ON
and the voltage jumps to (-Vd/2) with both the lower devices 4 and 4A turned ON and both the
upper devices 1 and 1A turned OFF and so ON. The angle α is variable and the output voltage
Va is made up of σ = 180º - 2αº square waves. This variable period σ per half cycle allows the
-
-
voltage Va to be independently variable with a fast response. It is seen that devices 1 A and 4A
are turned ON for 180º during each cycle devices 1 and 4 are turned ON for σ = 180º - 2αº
during each cycle, while diodes D1 and D4 conduct for 2αº = 180ºσ each cycle. The converter is
referred to as three level because the D.C. voltage has three levels i.e. (-Vd/2) 0 and (+Vd/2).
A current source converter is characterized by the fact that the D.C. current flow is always in
one direction and the power flow reverses with the reversal of D.C. voltage shows in Fig 2.8
(b). Where as the voltage source converter in which the D.C. voltage always has one polarity
and the power reversal of D.C. current is as shown in Fig 2.8 (a). In Fig2.8 (a) the converter
box for the voltage source converter is a symbolically shown with a turn OFF device with a
reverse diode. Where as the converter box in Fig 2.8 (b) for the current source converter is
shown without a specific type of device. This is because the voltage source converter requires
turn OFF devices with reverse diodes; where as the current source converter may be based on
diodes conventional thyristor or the turn OFF devices. Thus, there are three principal types of
current source converters as shown in Fig 2.8 (c), 2.8 (d), 2.8 (e).
Id
Vd Active power
DC power Reactive power
-
-
Id
Vd or
Active power
DC power or Reactive
or power
DC Current
DC Voltage
DC Power
DC Current
Active power Reactive power
DC Voltage
DC Power
Filter &
Capacitors
DC Current
Active Reactive
power power
DC Voltage
DC Power
Capacitor Filter
-
-
Fig 2.8 (c) represents the diode converter, which simply converts A.C. voltage to D.C. voltage
and utilizes A.C. system voltage for commutating of D.C. current from one valve to another.
Obviously the diode based line commutating converter just converts A.C. power to D.C. power
without any control and also in doing so consumes some reactive power on the A.C. side.
It is based on conventional thyristor with gate turn ON but without gate turn OFF capability as
in Fig 2.8 (d): utilizes A.C. system voltage for commutation of current from one valve to
another. This converter can convert and controls active power in either direction, but in doing
so consumes reactive power on the A.C. side. It can not supply reactive power to the A.C.
system.
It is based on turn OFF devices like (GTOs, MTOs, IGBTs, etc) in which commutation of
current from valve to valve takes place with the device turn OFF action and provision of A.C.
capacitors to facilitate transfer of current from valve to valve as in Fig 2.8 (e).Where as in a
voltage source converter the commutation of current is supported by a stiff D.C. bus with D.C.
capacitors provide a stiff A.C. bus for supplying the fact changing current pulses needed for
Current source converters in which direct current always has one polarity and the
power reversal takes place through reversal of D.C. voltage polarity. Where as voltage
source converters in which the D.C. voltage always has one polarity, and the power
-
-
Conventional Thyristor-based converters, being without turn OFF capability, can only
be current source converters. Where as turn OFF device based converters can be of
Diode based current source converters are the lowest cost converters, if control of
active power by the converter is not required. Where as the same type of voltage source
If the leading reactive power is not required, then a conventional Thyristor based
current source converter provides a low cost, converter with active power control. But
The current sourced converter does not have high short circuit current, where as the
For current source converters, the rate of rise of fault current during external or internal
faults is limited by the d.c reactor. For the voltage source converters the capacitor
discharge current would rise very rapidly and can damage the valves.
The six-pulse current source converter does not generate 3rd harmonic voltage, where as
The transformer primaries connected to current source converter of 12-pulse should not
be connected in series, where as the voltage source converter for the same purpose may
In a current stiff converter, the valves are not subject to high dv/dt, due to the presence
-
A.C capacitors required for the current stiff converters can be quite large and
expensive, where as voltage source converter used small size of capacitors which are
cheap.
Continuous losses in the d.c reactor of a current source converter are much higher than
the losses in the d.c capacitor, where as in voltage source converter they are
relaxable.[23]
UNIT-III
STATIC SHUNT COMPENSATORS
Objectives of shunt compensation –methods of controllable VAR generation-static VAR
compensators, SVC and STATCOM, comparison
****************
Shunt compensation is used to influence the natural characteristics of the transmission line to “ steady-state
transmittable power and to control voltage profile along the line” shunt connected fixed or mechanically switched reactors are
used to minimize line over-voltage under light load conditions. Shunt connected fixed or mechanically switched capacitors are
applied to maintain voltage levels under heavy load conditions.
Consider simple two-machine(two-bus)transmission model in which an ideal var compensator is shunt connected at the
midpoint of the transmission line
FIG:
NOTE:
i. The midpoint of the transmission line is the best location for compensator because the voltage sage along the
uncompensated transmission line is the longest at the midpoint
ii. The concept of transmission line segmentation can be expanded to use of multiple compensators, located at equal
segments of the transmission line as shown in fig.
A simple radial system with feeder line reactance X and load impedance Z is shown.
NOTE:
1. For a radial line , the end of the line, where the largest voltage variation is experienced, is the best location for the
compensator.
2. Reactive shunt compensation is often used too regulate voltage support for the load when capacity of sending –end
system becomes impaired.
The shunt compensation will be able to change the power flow in the system during and following disturbances. So as to increase the
transient stability limit. The potential effectiveness of shunt on transient stability improvement can be conveniently evaluated by
“EQUAL AREA CRITERION”.
Assume that both the uncompensated and compensated systems are subjected to the same fault for the same period of time. The
dynamic behavior of these systems is illustrated in the following figures.
Capacitors generate and inductors (reactors)absorb reactive power when connected to an ac power source. They have been used
with mechanical switches for controlled var generation and absorption. Continuously variable var generation or absorption for
Using appropriate switch control, the var output can be controlled continuously from maximum capacitive to maximum
inductive output at a given bus voltage.
More recently gate turn-off thyristors and other power semiconductors with internal turn off capacity have been use of ac
capacitors or reactors.
It is evident that the magnitude of current in the reactor can be varied continuously by the method of delay angle control from
maximum (α=0) to zero (α=90).
In practice, the maximum magnitude of the applied voltage and that of the corresponding current will be limited by the ratings of the
power components(reactor and thyristor valve)used. Thus, a practical TCR can be operated anywhere in a defined V-I area ,the
boundaries of which are determined by its maximum attainable admittance, voltage and current ratings are shown in fig.
Note: If Thyristor Controlled Reactor(TCR) switching is restricted to a fixed delay angle, usually α=0, then it becomes a thyristors –
switched reactor (TSR). The TSR provides a fixed inductive admittance. Thus, when connected to the a.c. system, the reactive current
TSRs can provide at α=0, the resultant steady-state current will be sinusoidal.
THYRISTOR SWITCHED CAPACITOR(TSC):
It consists of a capacitor, a bi-directional thyristors valve, and a relatively small surge current limiting reactor. This reactor is
needed primarily
To limit the surge current in the thyristors valve under abnormal operating conditions To avoid
Under steady state conditions, when the thyristor valve is closed and the TSC branch is connected to a sinusoidal a.c. voltage source,
The TSC branch can be disconnected (“switched out”) at any current zero by prior removal of the gate drive to the thyristor valve.
At the current zero crossing, the capacitor voltage is at its peak valve. The disconnected capacitor stays charged to this voltage, and
consequently the voltage across the non-conducting thyristors valve varied between zero and the peak-to-peak value of the
The static compensator term is used in a general sense to refer to an SVC as well as to a STATCOM.
The static compensators are used in a power system to increase the power transmission capacity with a given network, from the
generators to the loads. Since static compensators cannot generate or absorb real power, the power transmission of the system is
affected indirectly by voltage control. That is, the reactive output power ( capacitive or inductive) of compensator is varied to control
the voltage at given terminals of the transmission network so as to maintain the desired power flow under possible system
Static Var Compensator(SVC) and Static Synchronous Compensator(STATCOM) are var generators, whose output is varied so as
to maintain to control specific parameters of the electric power system.
The basic compensation needs fall into one of the following two main categories
Direct voltage support to maintain sufficient line voltage for facilitating increased power flow under heavy loads and for
preventing voltage instability.
Transient and dynamic stability improvements to improve the first swing stability margin and provide power oscillation
damping.
SVC:
SVCs are part of the Flexible AC transmission system device family, regulating voltage and stabilizing the system. Unlike a
synchronous condenser which is a rotating electrical machine, a "static" VAR compensator has no significant moving parts (other
than internal switchgear). Prior to the invention of the SVC, power factor compensation was the preserve of large rotating machines
such as synchronous condensers or switched capacitor banks.
Fig.shows Static Var Compensator(SVC).
An SVC comprises one or more banks of fixed or switched shunt capacitors or reactors, of which at least one bank is switched by
thyristors. Elements which may be used to make an SVC typically include:
Thyristor controlled reactor (TCR), where the reactor may be air- or iron-cored Thyristor
switched capacitor (TSC)
Harmonic filter(s)
Mechanically switched capacitors or reactors (switched by a circuit breaker)
The SVC is an automated impedance matching device, designed to bring the system closer to unity power factor. SVCs are used in
two main situations:
Connected to the power system, to regulate the transmission voltage ("Transmission SVC") Connected near
SVC will use thyristor controlled reactors to consume vars from the system, lowering the system voltage. Under inductive (lagging)
conditions, the capacitor banks are automatically switched in, thus providing a higher system voltage. By connecting the thyristor-
controlled reactor, which is continuously variable, along with a capacitor bank step, the net result is continuously-variable leading or
lagging power.
In industrial applications, SVCs are typically placed near high and rapidly varying loads, such as arc furnaces, where they can
STATCOM:
A static synchronous compensator (STATCOM), also known as a "static synchronous condenser" ("STATCON"), is a regulating device
used on alternating current electricity transmission networks. It is based on a power electronics voltage-source converter and can act
as either a source or sink of reactive AC power to an electricity network. If connected to a source of power it can also provide active
AC power. It is a member of the FACTS family of devices.
The STATCOM generates a 3-phase voltage source with controllable amplitude and phase angle behind reactance. When the a.c.
output voltage from the inverter is higher(lower) than the bus voltage, current flow is caused to lead(lag) and the difference in the
voltage amplitudes determines how much current flows. This allows the control of reactive power.
Fig. shows block diagram representation of STATCOM and V-I characteristics.
The STATCOM is implemented by a 6-pulse Voltage Source Inverter(VSI) comprising GTO thyristors fed from a d.c.storage
capacitor.The STATCOM is able to control its output current over the rated maximum capacitive or inductive range independently of
a.c. system voltage, in contrast to the SVC that varies with the ac system voltage. Thus STATCOM is more effective than the SVC in
providing voltage support and stability improvements. The STATCOM can continue to produce capacitive current independent of
voltage.The amount and duration of the overload capability is dependent upon the thermal capacity of the GTO.
Note : Multi-pulse circuit configurations are employed to reduce the harmonic generation and to produce practically
sinusoidal current.
Comparison between STATCOM and SVC:
INTRODUCTION
SERIES COMPENSATOR
(a) (b)
Figure 3.2 shows the simple system with the series compensated
line. Assumptions that are made here are as follows:
• The pre-fault and post-fault systems remain the same for the
series compensated system.
Figures 3.3 (a) and (b) show the equal area criterion for a simple
two machine system without and with series compensator for a three phase to
ground fault in the transmission line. From the figures, the dynamic
behaviour of these systems are discussed.
(a) (b)
CONVERTERS
Basic Concept
The conventional thyristor device has only the turn on control and
its turn off depends on the natural current zero. Devices such as the Gate
Turn Off Thyristor (GTO), Integrated Gate Bipolar Transistor (IGBT), MOS
Turn Off Thyristor (MTO) and Integrated Gate Commutated Thyristor
(IGCT) and similar devices have turn on and turn off capability. These
devices are more expensive and have higher losses than the thyristors without
turn off capability; however, turn off devices enable converter concepts that
can have significant overall system cost and performance advantages. These
advantages in principle result from the converter, which are self commutating
as against the line commutating converters. The line commutating converter
consumes reactive power and suffers from occasional commutation failures in
the inverter mode of operation. Hence, the converters applicable for FACTS
controllers are of self commutating type (Hingorani and Gyugyi, 2000).
There are two basic categories of self commutating converters:
UNIT-V
POWER FLOW CONTROLLERS
THE UNIFIED POWER FLOW CONTROLLER
The Unified Power Flow Controller (UPFC) concept was proposed by Gyugyi in 1991. The UPFC was devised
for the real-time control and dynamic compensation of ac transmission systems, providing multifunctional flexibility
required to solve many of the problems facing the power delivery industry. Within the framework of traditional power
transmission concepts, the UPFC is able to control, simultaneously or selectively, all the parameters affecting power flow
in the transmission line (i.e., voltage, impedance, and phase angle), and this unique capability is signified by the adjective
"unified"
in its name. Alternatively, it can independently control both the real and .reactive power flow in the line. The reader
should recall that, for all the Controllers discussed in the previous chapters, the control of real power is associated with
similar change in reactive power, i.e., increased real power flow also resulted in increased reactive line power.